APPROVED PLN BLD2022-0475+Site_Plan+4.14.2022_1.42.24_PM+2803126COMMON SPACE VENTILATION SCHEDULE
04/05/22
2018IMC
2018IMC
2018IMC
2018IMC
ADJUSTED
SPACE FLOOR
AREA
PEOPLE
OCC.
VENTILATION
VENTILATION
SERVED BY
AREA SERVED
AREA
OUTDOOR
DENSITY
OUTDOOR
REQUIRED
RATE
(SF)
AIR RATE
AIR RATE
#/1000SF
(CFM)
(CFM)
(CFM/SF)
(CFM/PERS)
ERV-101
COMMUNITY ROOM
963
0.06
30
5
202.2
205
ERV-102
OFFICE
157
0.06
5
5
13.3
15
SPIRAL MOUNT REGISTER SCHEDULE LAST UPDATED: 03/30/22
UNIT
TAG
BASIS OF
DESIGN
DUCT
IN DIA
MAX
CFM
CORE
SIZE
FACE
SIZE
THROW
15 0/100/50
NC
MOUNTING
MATERIAL
REMARKS
SM1
SHOEMAKER RS34
MIN 8
150
12 X 4
14 X 6
9/10/15
` 23
DUCT
STEEL
1 2 3 4 5
SM2
SHOEMAKER RS34
MIN 10
225
12 X 6
14 X 8
12/13/18
20
DUCT
STEEL
1 2 3 4 5
SM3
SHOEMAKER RS34
MIN 10
350
16 X 6
18 X 8
15/17/23
26
DUCT
STEEL
1 2 3 4 5
SM4
SHOEMAKER RS34
MIN 12
450
1 16 X 8
18 X 10
17/19/26
25
DUCT
I STEEL
1 1 2 3 4 5
SM5
SHOEMAKER RS34
MIN 12
525
1 18 X 8
20 X 10
17/20/27
25
DUCT
I STEEL
1 1 2 3 4 5
GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC...) WITH APPROVED SUBMITTALS
PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION &INSTALL PER MANUFACTURERS REQUIREMENTS
REMARKS:
1 PROVIDE WITH OPPOSED BLADE DAMPER (RS34-0)
2 REFER TO DRAWINGS FOR DUCT SIZE DIAMETER TO BE ATTACHED TO (MUST EXCEED CORE HEIGHT BY 4" MINIMUM)
3 STANDARD GALVANIZED FINISH, CUSTOM COLORS ONLY IF SPECIFIED BY ARCHITECT
4 REGISTER SHALL BE SIZED FOR CORE SIZE AND SPIRAL DUCT DIAMETER
5 THROW BASED ON 100 FPM TERMINAL VELOCITY
TRANSFER / RETURN / EXHAUST AIR GRILLES
LAST UPDATED: 3/30/2022
UNIT
TAG
BASIS OF
DESIGN
MAX
CFM
NECK SIZE
IN DIA
MOUNTING
FACE
SIZE
MATERIAL
REMARKS
G1
SHOEMAKER 905 -0
150
-- --
GWB
8 x 8
STEEL
3, 6, 9, 10
G2
SHOEMAKER 905 -0
250
-- --
GWB
10 x 10
STEEL
3 6 9 10
G3
SHOEMAKER 905 -0
375
-- --
GWB
12 x 12
STEEL
3, 6, 9, 10
G4
SHOEMAKER 905 -0
525
-- --
GWB
14 x 14
STEEL
3 6 9 10
G5
SHOEMAKER 905 -0
600
-- --
GWB
16 x 16
STEEL
3, 6, 9, 10
G6
SHOEMAKER 905 -0
900
-- --
GWB
18 x 18
STEEL
3 6 9 10
G7
SHOEMAKER 905 -0
1,200
-- --
GWB
24 x 24
STEEL
3, 6, 9, 10
G8
SHOEMAKER 905 -0
2,400
-- --
GWB
24 x 48
STEEL
3 6 9 10
G9
SHOEMAKER 905 -0
150
8
GWB
8 x 8
STEEL
1, 3, 6, 7/8, 9, 10
G10
SHOEMAKER 905 -0
250
10
GWB
10 x 10
STEEL
1 3 6 7/8 9 10
G11
SHOEMAKER 905 -0
375
12
GWB
12 x 12
STEEL
1 3 6 7/8 9 10
G12
SHOEMAKER 905 -0
525
14
GWB
14 x 14
STEEL
1 3 6 7/8 9 10
G13
SHOEMAKER 905 -0
600
14
GWB
16 x 16
STEEL
1 3 6 7/8 9 10
G14
SHOEMAKER 905 -0
900
16
GWB
18 x 18
STEEL
1 3 6 7/8 9 10
G15
SHOEMAKER 905 -O
1 1 200
1 16
GWB
24 x 24
STEEL
1 3 6 7/8 9 10
G16
SHOEMAKER 905 -O
1 2 400
1 20
GWB
24 x 48
STEEL
1 3 6 7/8 9 10
GENERAL: ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC...) WITH APPROVED SUBMITTALS
PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION &INSTALL PER MANUFACTURERS REQUIREMENTS
REMARKS:
1 RUNOUT SAME AS DWG NECK SIZE U.N.O. ON DWG
2 CORE ONLY - LAY -IN
3 SURFACE MOUNT FRAME
4 CHANNEL FRAME - LAY -IN
5 T-BAR LAY -IN
6 PROVIDE OPPOSED BLADE DAMPER (OBD)
7 PROVIDE DUCTBOARD PLENUM
8 PROVIDE SHEETMETAL PLENUM
9 STANDARD SOFT WHITE
10 PROVIDE ALUMINUM GRILLES IN SHOWERS/HUMID AREAS
11 ALL NON-FERROUS MATERIALS IN MRI ROOMS
12 WHERE VOLUME DAMPERS ARE NOT ACCESSIBLE, PROVIDE HAND HOLE ACCESS
SPLIT SYSTEM INDOOR FAN COIL UNIT SCHEDULE LAST UPDATED: 03/30/22
UNIT
TAG
LOCATION
SERVES
BASIS OF
DESIGN
ASSOCIATED
CONDENSER
SUPPLY
CFM
OSA
CFM
ESP
IN WG
MAX REFR
LINE FT
HEATER
WATTS
ELECTRICAL
SOUND
dBA
WEIGHT
LBS
REMARKS
MCA
V/PH
IDU-101
WALL
COMMUNITY
DAIKIN FTXS18
HP-101
360/385/484/583
N/A
N/A
98.4'
N/A
1.0
208-230/1
33-36-41-46
31
1 - 12
IDU-102
WALL
OFFICE
DAIKIN FTXS09
HP-102
145/194/279/381
N/A
N/A
65.6'
N/A
1.0
208-230/1
1 22-25-33-41
20
1 1 - 12
GENERAL ALL TRADES TO CONFIRM EOUIPMENT
REOUIREMENTS (ELECTRICAL. WEIGHT. SIZE. FTC --- ) WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION: FIELD COORDINATE FINAL LOCATION
& INSTALL PER
MANUFACTURERS REQUIREMENTS
1 ELECTRICAL CONTRACTOR TO PROVIDE SCCR PROTECTION FOR EQUIPMENT AS REQUIRED BY NATIONAL ELECTRICAL CODE.
MANUFACTURER TO PROVIDE SCCR LISTING (5 KAIC MINIMUM) INSIDE CONTROL PANEL AS REQUIRED BY NATIONAL ELECTRICAL CODE.
2 SINGLE CONDENSING UNIT FOR EACH INDOOR FAN COIL UNIT. PROVIDE WITH WALL -MOUNTED WIRELESS PROGRAMMABLE T'STAT, REFER TO MFG'S REQUIREMENTS FOR REFRIGERANT PIPE SIZES
3 INDOOR UNIT POWERED FROM OUTDOOR UNIT BY ELECTRICAL CONTRACTOR
4 REFRIGERANT: R-410A. PROVIDE ADDITIONAL CHARGING OF LINES AS REQUIRED FOR LONG LINE LENGTH APPLICATIONS
5 PROVIDE WALL MOUNTED FCU CONDENSATE DRAIN PUMP (I.E. GOBI 230-XL - 2.5 GPH @ 10 FT LIFT & < 100 FT HORIZ, 115V/1PH @ 32W, 5 LBS). TERMINATE DRAIN LINE IN HUB DRAIN BY NEAREST SINK
TAILPIECE OR INDIRECT AT NEAREST FLOOR DRAIN
6 PROVIDE PLENUM RATED OVERFLOW SHUT-OFF DEVICE CONFORMING TO UL-508 (I.E. RECTORSEAL SS2AP) IN LIEU OF SECONDARY DRAIN PAN
7 OUTSIDE AIR INDICATES MINIMUM CFM PER ASHRAE. TAB WORK MUST MEET OR EXCEED INDICATED QUANTITY.
8 ECONOMIZER EXEMPT PER 2018 WSEC C403.5 EXCEPTION 1 (INSTALLED IN CONJUNCTION W/ DOAS COMPLYING W/ C403.3.5)
9 HEAT PUMPS SHALL UTILIZE COMPRESSION HEATING AS FIRST STAGE OF HEAT AND AUXILIARY ELECTRIC HEAT SHALL NOT OPERATE ABOVE 40°F.
10 PROVIDE FILTERS AT RETURN AIR OPENINGS OF NEW AND/OR EXISTING UNITS, UPSTREAM OF ANY HEAT EXCHANGER OR COILS PER IMC 605
11 PROVIDE WITH AIREX PROSYSTEM KIT E-FLEX GUARD OR APPROVED EQUAL WHEN EXPOSED TO WEATHER IN COLOR TO MATCH SURROUNDING AREAS (BLACK OR WHITE) COLOR FROM EXTERIOR
PENETRATION TO CONDENSING UNIT CONNECTION IN COMPLIANCE WITH WSEC C403.2.9.1
12 HEATING & COOLING FANS/PUMPS SHALL SHUT OFF WHEN THERE IS NO CALL FOR HEATING AND COOLING IN THE ZONE PER WSEC 2018 C403.3.5.2, EXCEPT IF HEATING/COOLING FANS <0.12W/CFM
SPLIT SYSTEM OUTDOOR HEAT PUMP UNIT SCHEDULE LAST UPDATED: 03/30/22
UNIT
TAG
LOCATION
AREA
SERVED
BASIS
OF DESIGN
ASSOCIATED
FAN COIL
COOLING CAPACITY BTUH
HEATING CAPACITY
ELECTRICAL
SOUND
dBA
WEIGHT
LBS
REMARKS
TOTAL
SENS
SEER/EER
BTUH
HSPF/COP
MCA
V/PH
HP-101
EXTERIOR
COMMUNITY
DAIKIN RXS18
IDU-101
18,000
14,790
20.3 / -
21,600
11.0 / -
13.8
208-230/1
49
104
1-6
HP-102
EXTERIOR
OFFICE
DAIKIN RXS09
IDU-102
9,000
8,100
24.5 / -
12,000
12.5 / -
8.0
208-230/1
48
75
1-6
GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC...) WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION & INSTALL PER
MANUFACTURERS REQUIREMENTS
1 ELECTRICAL CONTRACTOR TO PROVIDE SCCR PROTECTION DIRECTION FOR EQUIPMENT AS REQUIRED BY LATEST APPROVED VERISON OF THE NATIONAL ELECTRICAL CODE, PRIOR TO ORDER.
MANUFACTURER TO PROVIDE SCCR LISTING (5 KAIC MINIMUM OR PER ELECTRICAL CONTRACTOR CALCULATION) INSIDE CONTROL PANEL AS REQUIRED BY NATIONAL ELECTRICAL CODE.
2 SPLIT SYSTEM UNITS REQUIRE DISCONNECT AT THE CONDENSING UNIT BY ELECTRICAL CONTRACTOR
3 INVERTER DRIVEN COMPRESSOR, TEST CONDITIONS BASED ON AHRI 210/240
4 SINGLE CONDENSING UNIT FOR EACH INDOOR FAN COIL UNIT. REFER TO MFG'S REQUIREMENTS FOR REFRIGERANT PIPE SIZES FOR EACH UNIT CONNECTION, WIND BAFFLE, LOW AMBIENT
OR HEAD PRESSURE CONTROL SUITABLE FOR LOW AMBIENT COOLING - ADDITIONALLY, CONFIRM CONTROL WIRE GAUGE (14 OR 16 AWG) WITH SUBMITTALS PRIOR TO INSTALLATION TO INDOOR UNIT
5 REFRIGERANT: R-410A. PROVIDE ADDITIONAL CHARGING OF LINES AS REQUIRED FOR LONG LINE LENGTH APPLICATIONS
6 ECONOMIZER EXEMPT PER 2018 WSEC C403.5 EXCEPTION 1 (INSTALLED IN CONJUNCTION W/ DOAS COMPLYING W/ C403.3.5)
ENERGY RECOVERY VENTILATOR SCHEDULE LAST UPDATED: 03/30/22t
UNIT
TAG
LOCATION
AREA
SERVED
BASIS OF DESIGN
TIME
OF
YEAR
OUTSIDE AIR
EXHAUST AIR
FAN INFO
AHRI
%
EFFECT
WGT
LBS
REMARKS
CFM
EAT°F
LATOF
CFM
EATOF
LATOF
SUPPLY FAN
EXHAUST FAN
DB
WB
DB
WB
DB
WB
DB
WB
V/PH
BHP
HP
ESP
W/CFM
CTRLV/PH
HP
ESP
CTRL
ERV-101
CEILING
COMMUNITY
ROOM
LOSSNAY LGH-
F300
SUM
205
86
67
79
65
205
75
63
81
65
230/1
0.3
0.50
0.06
1.09
ECM
230/1
0.50
0.06
ECM
70%
75
1-8
WIN
205
24
19
57
43
205
70
53
38
29
70%
STACK
-
-
-
-
-
-
-
-
-
-
-
ERV-102
CEILING
OFFICE
CFM ECO-FLO-
15
86
67
79
65
15
75
63
81
65
12011
-
0.01
N/A
0.10
ECM
120/1
0.01
N/A
ECM
70%
20
1 - 3, 5 - 6
WIN
15
24
19
57
43
15
70
53
38
29
70%
STACK
-
I -
-
I -
-
I -
-
-
-
-
-
GENERAL: ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC...) WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION &
INSTALL PER MANUFACTURERS REQUIREMENTS
REMARKS:
1 ELECTRICAL CONTRACTOR TO PROVIDE SCCR PROTECTION DIRECTION FOR EQUIPMENT AS REQUIRED BY LATEST APPROVED VERISON OF THE NATIONAL ELECTRICAL CODE, PRIOR TO ORDER.
MANUFACTURER TO PROVIDE SCCR LISTING (5 KAIC MINIMUM OR PER ELECTRICAL CONTRACTOR CALCULATION) INSIDE CONTROL PANEL AS REQUIRED BY NATIONAL ELECTRICAL CODE.
2 UL/ETL LISTED UNIT. SUPPLY AND EXHAUST FAN MOTORS TO BE CAPABLE OF ADJUSTABLE SPEEDS; PROVIDE EC TYPE MOTOR IF >:1/12 HP TO <1HP AND AVAILABLE AS FACTORY OPTION
3 PROVIDE WITH EC MOTORS (70% EFFICIENT MINIMUM) AT SUPPLY AND EXHAUST FANS TO ACCOMMODATE FILTER LOADING
4 MANUFACTURER TO PROVIDE 2" FILTER RACK WHERE AVAILABLE AS ACCESSORY FOR MERV-8 FILTERS FOR OUTSIDE AIRFLOW SYSTEM AND MERV-8 FILTERS FOR EXHAUST AIRFLOW SYSTEM.
5 UNIT TO OPERATE CONTINUOUSLY DURING OCCUPIED HOURS, DECOUPLED FROM CENTRAL SYSTEM PER C403.6.2
6 MINIMUM UNIT EFFICIENCY TO MEET THE ENERGY CODE TABLE C403.5.1
7 INSULATE OSA INTAKE AND EXHAUST DUCTWORK FROM EXTERIOR UP TO THE ERV UNIT, AND SUPPLY DUCTWORK IF LEAVING TEMPERATURE IS <55°F
8 PROVIDE SEISMIC BRACING PER ACSE 7, UNLESS: UNIT <20 LBS OR IS RIGID MOUNTED INLINE WITH DUCT (NO FLEX) AND <75 LBS OR <400 LBS WITH FLEX CONN'S & Ip=1.0 & 4' MAX MOUNT HEIGHT AFF
1SF LOUVER ASSUMING
50% MIN FREE AREA
1SF LOUVER ASSUMING
50% MIN FREE AREA
F
80W(R-7) OSA
r 1
I I
I I
I I
I _I
80
G10-205
100
ERV-101
COMMUNITY ROOM
/ 4 'COND DN TO
NEAREST INDIRECT DRAIN 1
IDU-101 REFRIGERANT PIPING,
SEE MANUFACTURER'S
SUBMITTAL FOR SIZING d
PROVIDE WATERPROOF J HP-101
SEAL AT EXTERIOR
PIPING PENETRATIONS
SM1-105
(TYP 2)
o C ° M
L� A
z PARTIAL 1 ST FLOOR PLAN - HVAC
SCALE: 1 /4" = 1'-0"
ti
a
O 0 ti
� � A
z SITE MAP
SCALE: NONE
ti
APPROVED BY PLANNING
iz f SCALE: 4
Apr 27 2022
1' 3' 5'
2' 4'
10'
15'
a"COND DN TO
NEAREST INDIRECT DRAIN
25'
PROVIDE WATERPROOF
SEAL AT EXTERIOR
PIPING PENETRATIONS
/ � IDU-102
/ REFRIGERANT PIPING,
SEE MANUFACTURER'S
SUBMITTAL FOR SIZING
nrrinr
Hermanson
Building Today, Defining Tomorrow
ERV-102 Hermanson Company LLP
1221 2nd Avenue North
Kent, Washington 98032
Tel: (206) 575-9700
Fax: (206) 575-9800
www.hermanson.com
Contractor Reg #: HERMACLO05BJ
H ERV-102
Zone CG Corner Flag
Setbacks: Required Actual
Front
Sides
Rear
Other
Height
WA OF WORT(
o� C a�
z KEY PLAN
SCALE: NONE
ti
a
FOR CITY USE:
RECEIVED
BLD2022-0475 Apr 14 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
SPLIT SYSTEM
& INSULATION
BALLINGER COURT SENIOR APARTMENTS
22707 76TH AVE. WEST
EDMONDS, WA 98026
ISSUE FOR PERMIT
Revisions
04/06/22 WSS ISSUE FOR PERMIT
No. Date By Description
Design Team
Design WSS
Drawn FVP
Checked DTN
Pre —Construction Number 14-22-21472
Construction Number
Issue Date 04/06/22
PARTIAL 1ST FLOOR
PLAN & SCHEDULE
- HVAC
M2001