APPROVED PLN BLD2022-0475+Site_Plan+4.14.2022_1.42.24_PM+2803126COMMON SPACE VENTILATION SCHEDULE 04/05/22 2018IMC 2018IMC 2018IMC 2018IMC ADJUSTED SPACE FLOOR AREA PEOPLE OCC. VENTILATION VENTILATION SERVED BY AREA SERVED AREA OUTDOOR DENSITY OUTDOOR REQUIRED RATE (SF) AIR RATE AIR RATE #/1000SF (CFM) (CFM) (CFM/SF) (CFM/PERS) ERV-101 COMMUNITY ROOM 963 0.06 30 5 202.2 205 ERV-102 OFFICE 157 0.06 5 5 13.3 15 SPIRAL MOUNT REGISTER SCHEDULE LAST UPDATED: 03/30/22 UNIT TAG BASIS OF DESIGN DUCT IN DIA MAX CFM CORE SIZE FACE SIZE THROW 15 0/100/50 NC MOUNTING MATERIAL REMARKS SM1 SHOEMAKER RS34 MIN 8 150 12 X 4 14 X 6 9/10/15 ` 23 DUCT STEEL 1 2 3 4 5 SM2 SHOEMAKER RS34 MIN 10 225 12 X 6 14 X 8 12/13/18 20 DUCT STEEL 1 2 3 4 5 SM3 SHOEMAKER RS34 MIN 10 350 16 X 6 18 X 8 15/17/23 26 DUCT STEEL 1 2 3 4 5 SM4 SHOEMAKER RS34 MIN 12 450 1 16 X 8 18 X 10 17/19/26 25 DUCT I STEEL 1 1 2 3 4 5 SM5 SHOEMAKER RS34 MIN 12 525 1 18 X 8 20 X 10 17/20/27 25 DUCT I STEEL 1 1 2 3 4 5 GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC...) WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION &INSTALL PER MANUFACTURERS REQUIREMENTS REMARKS: 1 PROVIDE WITH OPPOSED BLADE DAMPER (RS34-0) 2 REFER TO DRAWINGS FOR DUCT SIZE DIAMETER TO BE ATTACHED TO (MUST EXCEED CORE HEIGHT BY 4" MINIMUM) 3 STANDARD GALVANIZED FINISH, CUSTOM COLORS ONLY IF SPECIFIED BY ARCHITECT 4 REGISTER SHALL BE SIZED FOR CORE SIZE AND SPIRAL DUCT DIAMETER 5 THROW BASED ON 100 FPM TERMINAL VELOCITY TRANSFER / RETURN / EXHAUST AIR GRILLES LAST UPDATED: 3/30/2022 UNIT TAG BASIS OF DESIGN MAX CFM NECK SIZE IN DIA MOUNTING FACE SIZE MATERIAL REMARKS G1 SHOEMAKER 905 -0 150 -- -- GWB 8 x 8 STEEL 3, 6, 9, 10 G2 SHOEMAKER 905 -0 250 -- -- GWB 10 x 10 STEEL 3 6 9 10 G3 SHOEMAKER 905 -0 375 -- -- GWB 12 x 12 STEEL 3, 6, 9, 10 G4 SHOEMAKER 905 -0 525 -- -- GWB 14 x 14 STEEL 3 6 9 10 G5 SHOEMAKER 905 -0 600 -- -- GWB 16 x 16 STEEL 3, 6, 9, 10 G6 SHOEMAKER 905 -0 900 -- -- GWB 18 x 18 STEEL 3 6 9 10 G7 SHOEMAKER 905 -0 1,200 -- -- GWB 24 x 24 STEEL 3, 6, 9, 10 G8 SHOEMAKER 905 -0 2,400 -- -- GWB 24 x 48 STEEL 3 6 9 10 G9 SHOEMAKER 905 -0 150 8 GWB 8 x 8 STEEL 1, 3, 6, 7/8, 9, 10 G10 SHOEMAKER 905 -0 250 10 GWB 10 x 10 STEEL 1 3 6 7/8 9 10 G11 SHOEMAKER 905 -0 375 12 GWB 12 x 12 STEEL 1 3 6 7/8 9 10 G12 SHOEMAKER 905 -0 525 14 GWB 14 x 14 STEEL 1 3 6 7/8 9 10 G13 SHOEMAKER 905 -0 600 14 GWB 16 x 16 STEEL 1 3 6 7/8 9 10 G14 SHOEMAKER 905 -0 900 16 GWB 18 x 18 STEEL 1 3 6 7/8 9 10 G15 SHOEMAKER 905 -O 1 1 200 1 16 GWB 24 x 24 STEEL 1 3 6 7/8 9 10 G16 SHOEMAKER 905 -O 1 2 400 1 20 GWB 24 x 48 STEEL 1 3 6 7/8 9 10 GENERAL: ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC...) WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION &INSTALL PER MANUFACTURERS REQUIREMENTS REMARKS: 1 RUNOUT SAME AS DWG NECK SIZE U.N.O. ON DWG 2 CORE ONLY - LAY -IN 3 SURFACE MOUNT FRAME 4 CHANNEL FRAME - LAY -IN 5 T-BAR LAY -IN 6 PROVIDE OPPOSED BLADE DAMPER (OBD) 7 PROVIDE DUCTBOARD PLENUM 8 PROVIDE SHEETMETAL PLENUM 9 STANDARD SOFT WHITE 10 PROVIDE ALUMINUM GRILLES IN SHOWERS/HUMID AREAS 11 ALL NON-FERROUS MATERIALS IN MRI ROOMS 12 WHERE VOLUME DAMPERS ARE NOT ACCESSIBLE, PROVIDE HAND HOLE ACCESS SPLIT SYSTEM INDOOR FAN COIL UNIT SCHEDULE LAST UPDATED: 03/30/22 UNIT TAG LOCATION SERVES BASIS OF DESIGN ASSOCIATED CONDENSER SUPPLY CFM OSA CFM ESP IN WG MAX REFR LINE FT HEATER WATTS ELECTRICAL SOUND dBA WEIGHT LBS REMARKS MCA V/PH IDU-101 WALL COMMUNITY DAIKIN FTXS18 HP-101 360/385/484/583 N/A N/A 98.4' N/A 1.0 208-230/1 33-36-41-46 31 1 - 12 IDU-102 WALL OFFICE DAIKIN FTXS09 HP-102 145/194/279/381 N/A N/A 65.6' N/A 1.0 208-230/1 1 22-25-33-41 20 1 1 - 12 GENERAL ALL TRADES TO CONFIRM EOUIPMENT REOUIREMENTS (ELECTRICAL. WEIGHT. SIZE. FTC --- ) WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION: FIELD COORDINATE FINAL LOCATION & INSTALL PER MANUFACTURERS REQUIREMENTS 1 ELECTRICAL CONTRACTOR TO PROVIDE SCCR PROTECTION FOR EQUIPMENT AS REQUIRED BY NATIONAL ELECTRICAL CODE. MANUFACTURER TO PROVIDE SCCR LISTING (5 KAIC MINIMUM) INSIDE CONTROL PANEL AS REQUIRED BY NATIONAL ELECTRICAL CODE. 2 SINGLE CONDENSING UNIT FOR EACH INDOOR FAN COIL UNIT. PROVIDE WITH WALL -MOUNTED WIRELESS PROGRAMMABLE T'STAT, REFER TO MFG'S REQUIREMENTS FOR REFRIGERANT PIPE SIZES 3 INDOOR UNIT POWERED FROM OUTDOOR UNIT BY ELECTRICAL CONTRACTOR 4 REFRIGERANT: R-410A. PROVIDE ADDITIONAL CHARGING OF LINES AS REQUIRED FOR LONG LINE LENGTH APPLICATIONS 5 PROVIDE WALL MOUNTED FCU CONDENSATE DRAIN PUMP (I.E. GOBI 230-XL - 2.5 GPH @ 10 FT LIFT & < 100 FT HORIZ, 115V/1PH @ 32W, 5 LBS). TERMINATE DRAIN LINE IN HUB DRAIN BY NEAREST SINK TAILPIECE OR INDIRECT AT NEAREST FLOOR DRAIN 6 PROVIDE PLENUM RATED OVERFLOW SHUT-OFF DEVICE CONFORMING TO UL-508 (I.E. RECTORSEAL SS2AP) IN LIEU OF SECONDARY DRAIN PAN 7 OUTSIDE AIR INDICATES MINIMUM CFM PER ASHRAE. TAB WORK MUST MEET OR EXCEED INDICATED QUANTITY. 8 ECONOMIZER EXEMPT PER 2018 WSEC C403.5 EXCEPTION 1 (INSTALLED IN CONJUNCTION W/ DOAS COMPLYING W/ C403.3.5) 9 HEAT PUMPS SHALL UTILIZE COMPRESSION HEATING AS FIRST STAGE OF HEAT AND AUXILIARY ELECTRIC HEAT SHALL NOT OPERATE ABOVE 40°F. 10 PROVIDE FILTERS AT RETURN AIR OPENINGS OF NEW AND/OR EXISTING UNITS, UPSTREAM OF ANY HEAT EXCHANGER OR COILS PER IMC 605 11 PROVIDE WITH AIREX PROSYSTEM KIT E-FLEX GUARD OR APPROVED EQUAL WHEN EXPOSED TO WEATHER IN COLOR TO MATCH SURROUNDING AREAS (BLACK OR WHITE) COLOR FROM EXTERIOR PENETRATION TO CONDENSING UNIT CONNECTION IN COMPLIANCE WITH WSEC C403.2.9.1 12 HEATING & COOLING FANS/PUMPS SHALL SHUT OFF WHEN THERE IS NO CALL FOR HEATING AND COOLING IN THE ZONE PER WSEC 2018 C403.3.5.2, EXCEPT IF HEATING/COOLING FANS <0.12W/CFM SPLIT SYSTEM OUTDOOR HEAT PUMP UNIT SCHEDULE LAST UPDATED: 03/30/22 UNIT TAG LOCATION AREA SERVED BASIS OF DESIGN ASSOCIATED FAN COIL COOLING CAPACITY BTUH HEATING CAPACITY ELECTRICAL SOUND dBA WEIGHT LBS REMARKS TOTAL SENS SEER/EER BTUH HSPF/COP MCA V/PH HP-101 EXTERIOR COMMUNITY DAIKIN RXS18 IDU-101 18,000 14,790 20.3 / - 21,600 11.0 / - 13.8 208-230/1 49 104 1-6 HP-102 EXTERIOR OFFICE DAIKIN RXS09 IDU-102 9,000 8,100 24.5 / - 12,000 12.5 / - 8.0 208-230/1 48 75 1-6 GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC...) WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION & INSTALL PER MANUFACTURERS REQUIREMENTS 1 ELECTRICAL CONTRACTOR TO PROVIDE SCCR PROTECTION DIRECTION FOR EQUIPMENT AS REQUIRED BY LATEST APPROVED VERISON OF THE NATIONAL ELECTRICAL CODE, PRIOR TO ORDER. MANUFACTURER TO PROVIDE SCCR LISTING (5 KAIC MINIMUM OR PER ELECTRICAL CONTRACTOR CALCULATION) INSIDE CONTROL PANEL AS REQUIRED BY NATIONAL ELECTRICAL CODE. 2 SPLIT SYSTEM UNITS REQUIRE DISCONNECT AT THE CONDENSING UNIT BY ELECTRICAL CONTRACTOR 3 INVERTER DRIVEN COMPRESSOR, TEST CONDITIONS BASED ON AHRI 210/240 4 SINGLE CONDENSING UNIT FOR EACH INDOOR FAN COIL UNIT. REFER TO MFG'S REQUIREMENTS FOR REFRIGERANT PIPE SIZES FOR EACH UNIT CONNECTION, WIND BAFFLE, LOW AMBIENT OR HEAD PRESSURE CONTROL SUITABLE FOR LOW AMBIENT COOLING - ADDITIONALLY, CONFIRM CONTROL WIRE GAUGE (14 OR 16 AWG) WITH SUBMITTALS PRIOR TO INSTALLATION TO INDOOR UNIT 5 REFRIGERANT: R-410A. PROVIDE ADDITIONAL CHARGING OF LINES AS REQUIRED FOR LONG LINE LENGTH APPLICATIONS 6 ECONOMIZER EXEMPT PER 2018 WSEC C403.5 EXCEPTION 1 (INSTALLED IN CONJUNCTION W/ DOAS COMPLYING W/ C403.3.5) ENERGY RECOVERY VENTILATOR SCHEDULE LAST UPDATED: 03/30/22t UNIT TAG LOCATION AREA SERVED BASIS OF DESIGN TIME OF YEAR OUTSIDE AIR EXHAUST AIR FAN INFO AHRI % EFFECT WGT LBS REMARKS CFM EAT°F LATOF CFM EATOF LATOF SUPPLY FAN EXHAUST FAN DB WB DB WB DB WB DB WB V/PH BHP HP ESP W/CFM CTRLV/PH HP ESP CTRL ERV-101 CEILING COMMUNITY ROOM LOSSNAY LGH- F300 SUM 205 86 67 79 65 205 75 63 81 65 230/1 0.3 0.50 0.06 1.09 ECM 230/1 0.50 0.06 ECM 70% 75 1-8 WIN 205 24 19 57 43 205 70 53 38 29 70% STACK - - - - - - - - - - - ERV-102 CEILING OFFICE CFM ECO-FLO- 15 86 67 79 65 15 75 63 81 65 12011 - 0.01 N/A 0.10 ECM 120/1 0.01 N/A ECM 70% 20 1 - 3, 5 - 6 WIN 15 24 19 57 43 15 70 53 38 29 70% STACK - I - - I - - I - - - - - - GENERAL: ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC...) WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION & INSTALL PER MANUFACTURERS REQUIREMENTS REMARKS: 1 ELECTRICAL CONTRACTOR TO PROVIDE SCCR PROTECTION DIRECTION FOR EQUIPMENT AS REQUIRED BY LATEST APPROVED VERISON OF THE NATIONAL ELECTRICAL CODE, PRIOR TO ORDER. MANUFACTURER TO PROVIDE SCCR LISTING (5 KAIC MINIMUM OR PER ELECTRICAL CONTRACTOR CALCULATION) INSIDE CONTROL PANEL AS REQUIRED BY NATIONAL ELECTRICAL CODE. 2 UL/ETL LISTED UNIT. SUPPLY AND EXHAUST FAN MOTORS TO BE CAPABLE OF ADJUSTABLE SPEEDS; PROVIDE EC TYPE MOTOR IF >:1/12 HP TO <1HP AND AVAILABLE AS FACTORY OPTION 3 PROVIDE WITH EC MOTORS (70% EFFICIENT MINIMUM) AT SUPPLY AND EXHAUST FANS TO ACCOMMODATE FILTER LOADING 4 MANUFACTURER TO PROVIDE 2" FILTER RACK WHERE AVAILABLE AS ACCESSORY FOR MERV-8 FILTERS FOR OUTSIDE AIRFLOW SYSTEM AND MERV-8 FILTERS FOR EXHAUST AIRFLOW SYSTEM. 5 UNIT TO OPERATE CONTINUOUSLY DURING OCCUPIED HOURS, DECOUPLED FROM CENTRAL SYSTEM PER C403.6.2 6 MINIMUM UNIT EFFICIENCY TO MEET THE ENERGY CODE TABLE C403.5.1 7 INSULATE OSA INTAKE AND EXHAUST DUCTWORK FROM EXTERIOR UP TO THE ERV UNIT, AND SUPPLY DUCTWORK IF LEAVING TEMPERATURE IS <55°F 8 PROVIDE SEISMIC BRACING PER ACSE 7, UNLESS: UNIT <20 LBS OR IS RIGID MOUNTED INLINE WITH DUCT (NO FLEX) AND <75 LBS OR <400 LBS WITH FLEX CONN'S & Ip=1.0 & 4' MAX MOUNT HEIGHT AFF 1SF LOUVER ASSUMING 50% MIN FREE AREA 1SF LOUVER ASSUMING 50% MIN FREE AREA F 80W(R-7) OSA r 1 I I I I I I I _I 80 G10-205 100 ERV-101 COMMUNITY ROOM / 4 'COND DN TO NEAREST INDIRECT DRAIN 1 IDU-101 REFRIGERANT PIPING, SEE MANUFACTURER'S SUBMITTAL FOR SIZING d PROVIDE WATERPROOF J HP-101 SEAL AT EXTERIOR PIPING PENETRATIONS SM1-105 (TYP 2) o C ° M L� A z PARTIAL 1 ST FLOOR PLAN - HVAC SCALE: 1 /4" = 1'-0" ti a O 0 ti � � A z SITE MAP SCALE: NONE ti APPROVED BY PLANNING iz f SCALE: 4 Apr 27 2022 1' 3' 5' 2' 4' 10' 15' a"COND DN TO NEAREST INDIRECT DRAIN 25' PROVIDE WATERPROOF SEAL AT EXTERIOR PIPING PENETRATIONS / � IDU-102 / REFRIGERANT PIPING, SEE MANUFACTURER'S SUBMITTAL FOR SIZING nrrinr Hermanson Building Today, Defining Tomorrow ERV-102 Hermanson Company LLP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ H ERV-102 Zone CG Corner Flag Setbacks: Required Actual Front Sides Rear Other Height WA OF WORT( o� C a� z KEY PLAN SCALE: NONE ti a FOR CITY USE: RECEIVED BLD2022-0475 Apr 14 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SPLIT SYSTEM & INSULATION BALLINGER COURT SENIOR APARTMENTS 22707 76TH AVE. WEST EDMONDS, WA 98026 ISSUE FOR PERMIT Revisions 04/06/22 WSS ISSUE FOR PERMIT No. Date By Description Design Team Design WSS Drawn FVP Checked DTN Pre —Construction Number 14-22-21472 Construction Number Issue Date 04/06/22 PARTIAL 1ST FLOOR PLAN & SCHEDULE - HVAC M2001