Fire Comments- to be sent at issuanceSOUTH COUNTY FIRE
12425 Meridian Ave S., Everett WA 98208
tel (425) 551-1200 • fax (425) 551-1249
www.southsnofire.org
City of Edmonds
Department of Fire Prevention
Fire Comments:
DATE: 4/28/2021
PERMIT #: BLD2021-0427
PERMIT DESCRIPTION: Tenant Improvement and Change of use
JOB NAME/ADDRESS: Wonton Noodle but
22921 Highway 99
22931
CONTACTS:
FIRE PLAN REVIEW NOTES:
The proposed project is approved by Fire, with the following conditions:
1. As stated in the Edmonds Municipal Code 19.25.035, For the purpose of 19.25.035 spaces
separated by fire walls, fire barriers, fire partitions and fire resistance rated horizontal
assemblies noted in the IBC Chapter 7 shall not be considered separate buildings.
2. As stated in the Edmonds Municipal Code 19.25.035 C. Fire Alarms and Detection Systems. In
addition to the requirements of Section 907.2, an approved, monitored automatic fire alarm
system shall be installed and maintained throughout all buildings, structures, floors, and suites
described in this section. If conflicts exist between the IFC and this section, this section shall
prevail. Fire alarm systems shall be installed per NFPA 72 and SCF's fire alarm standard.
Partial area fire alarm systems are prohibited except where approved by the fire code official.
When required by the International Existing Building Code (IEBC) for existing buildings and
structures undergoing additions, alterations, repairs or changes of occupancy. The
classification of work level shall be determined by the building and fire code official.
3. This building by the above municipal code could be required to install a fire sprinkler system.
In existing buildings that are altered or have a change of use, but do not otherwise require that
a fire sprinkler be installed, a fire alarm for the entire building will be required. All class 1
hoods and gas shutoffs will be interconnected with the fire alarm system. Future
improvements or occupancy changes could require the space or entire building to be retro
fitted with a fire sprinkler system.
4. Occupant load to be determined by building.
5. Addressing 10 - 12 inch numbering on contrasting background. Suite identification 6 inch numbers
above door in a contrasting color.
6. 6. Knox box key entry to common areas and access to fire alarm panel
AFM Karl Fitterer CFI
Assistant Fire Marshal
12425 Meridian Ave. S, Everett WA 98208
0: 425-771-0213 VM: 425-551-1980
KFitterer@southsnofire.org I www.southsnofire.org