APPROVED BLD-BLD2022-0099+Architectural_Plan+1.26.2022_11.36.43_AM+2642750GENERAL STRTUCURAL NOTES: THE FOLLOWING NOTES APPLY EXCEPT WHERE SHOWN OTHERWISE: CODE INTERNATIONAL CON5ITDRUC IONOMDANUALE IRC(WFFCM)(2018) § Uniform Plumbing Code UPC (2018) ; .............................................� 5TRUCTURALLOAD5 ATTIC LIVE LOADS: TYPICAL UNINHABITABLE ATTIC WITHOUT STORAGE LIVE LOAD = I OP5F ROOF SNOW LOAD5: ROOF SNOW LOAD, Pf = 25P5F (MIN) ANCHORAGE TO HARDENED CONCRETE WHERE DRILL -IN ANCHORS ARE SPECIFIED, U5E "51MP50N TITEN-HD" SCREW ANCHORS. WHERE EPDXY ANCHORS ARE SPECIFIED, USE "51MP50N AT-XP ADHESIVE". USE A5TM A3G THREADED ROD OR #4 REBAR, UNLE55 OTHERWISE NOTED. hOLE5 MUST BE CLEANED OF DUST AND DEBRIS AND BE FREE OF STANDING WATER WHEN EPDXY 15 INSTALLED. SPECIAL INSPECTION OF EPDXY ANCHORS 15 REQUIRED. DO NOT CUT ANY REINFORCING 13AR5 TO INSTALL ANCHORS. DEFECTIVE HOLES SHALL BE FILLED 50LID WITH EPDXY. FOR ANY SUBSTITUTIONS TO THE ABOVE, THE CONTRACTOR SHALL SUBMIT TO THE STRUCTURAL ENGINEER MANUFACTURER'S LITERATURE DESCRIBING THE ANCHORS AND L15TING ICC APPROVED ALLOWABLE SHEAR AND TEN51ON VALUES. PLYWOOD/ 055 PLYWOOD/055 ROOF, FLOOR AND WALL 5HEATHING TO BE APA RATED C-D EXP05URE I PER APA "PLYWOOD DE51GN SPECIFICATION" (Y5 10), UNLE55 NOTED OTHERWISE. MAXIMUM NAIL 5PACING SHALL BE A5 FOLLOWS: G"oc AT ALL SUPPORTED PANEL EDGES, AND 1 2"oc AT INTERMEDIATE SUPPORTS. NAIL5 511ALL BE A5 FOLLOWS: 8D COMMON FOR 1/2" ROOF 5HEATHING, 8D COMMON FOR 1/2" WALL 5HEATHING. STAGGER END LAP5 AT ROOF 511EATHING. ALL PANEL EDGE5 TO BE BLOCKED AT 5HEAR WALLS. SUPPORT 5HALL BE SUPPLIED TO ALL PLYWOOD EDGES WITH PLYCLIP5, BLOCKING, TONGUE AND GROOVE PLYWOOD JOINTS OR OTHER APPROVED METHODS PER APA RECOMMENDATION. TIMBER STRUCTURAL TIMBER AND LUMBER TO BE STRESS GRADE HEM -FIR OR DOUGLA5 FIR A5 FOLLOWS: STRUCTURAL GLUED -LAMINATED LUMBER SHALL BE FABRICATED TO THE REQUIREMENTS OF PRODUCT STANDARD P5 5G. LUMBER SHALL BE V15UALLY GRADED WESTERN SPECIES, COMBINATION 24F-V4 FOR 51MPLE BEAMS, 24F-V8 FOR CANTILEVER BEAMS, COMBINATION 2 FOR COLUMNS, AND COMBINATION 5 FOR TRUSS MEMBERS PER 2018 ND5 SUPPLEMENT, TABLE 3.1 (BEAMS) AND 3.2 (COLUMNS). LAMINATED MEMBERS TO BE AITC CERTIFIED. USE WATERPROOF GLUE. PRESERVATIVE TREATMENT ALL LUMBER, TIMBER, PLYWOOD, GLUE -LAMINATED AND OTHER COMPOSITE LUMBER THAT 15 IN CONTACT WITH CONCRETE OR MASONRY OR EXP05ED TO WEATHER SHALL BE PRESERVATIVE TREATED IN ACCORDANCE WITH CURRENT AMERICAN WOOD -PRESERVERS' ASSOCIATION (AWPA) PRESERVATIVE (P) STANDARDS. THE5E MEMBERS 5HALL BE TREATED WITH AN APPROVED PRESERVATIVE IN ACCORDANCE WITH CURRENT AWPA COMMODITY (C) STANDARDS AND THE AWPA U5E CATEGORY SYSTEM (UC5). WHEREVER POSSIBLE, PRECUT ALL MATERIAL BEFORE TREATMENT. HANDLE TREATED LUMBER IN ACCORDANCE WITH AWPA M4 STANDARDS. FIELD CUTS, HOLES (SUCH A5 ANCHOR BOLT HOLES IN TREATED SILL PLATES) AND PENETRATION DAMAGE SHALL BE TREATED IN ACCORDANCE WITH THE CURRENT AWPA M4 STANDARDS. THE M05T COMMONLY AVAILABLE PRESERVATIVE MEETING THE REQUIREMENTS OF STANDARD M4 15 A COPPER NAPHTHENATE SOLUTION CONTAINING AT LEAST 2% COPPER. CERTAIN DAP, WM BARR, CUPRINOL, BEHR, GREEN'S, JA5CO, HENRY AND FIELDS PRESERVATIVE PRODUCTS CONTAIN TH15 METAL CONTENT. ALL FASTENERS AND CONNECTORS IN CONTACT WITH PRESERVATIVE TREATED WOOD SHALL BE HOT -DIPPED GALVANIZED OR TYPE 5TAINLE55 STEEL. 5EE THE "WOOD CONNECTORS" SECTION. SCOPE OF STRUCTURAL ENGINEERING SERVICES THE STRUCTURAL ENGINEER HAS PERFORMED THE STRUCTURAL DE51GN AND PREPARED THE STRUCTURAL WORKING DRAWINGS FOR TH15 PROJECT. THE CONSTRUCTION MUST BE PERFORMED IN STRICT ACCORDANCE WITH THE STRUCTURAL DRAWINGS. ANY DEVIATION FROM THE DRAWINGS MUST BE APPROVED IN WRITING BY THE STRUCTURAL ENGINEER. ERRORS AND/OR OMISSIONS FOUND ON THE 5TRUCTURAL DRAWING5 MUST BE BROUGHT TO THE STRUCTURAL ENGINEER'S ATTENTION IMMEDIATELY. OMISSIONS FROM THE DRAWINGS OR SPECIFICATIONS OR THE INADVERTENT M15LA13ELING OF DETAILS OF WORK WHICH ARE MANIFESTLY NECE55ARY TO CARRY OUT THE INTENT OF THE DRAWINGS AND SPECIFICATIONS, OR WHICH ARE CUSTOMARILY PERFORMED, SHALL NOT RELIEVE THE CONTRACTOR FROM PERFORMING SUCH OMITTED OR INADVERTENT M15LA13ELED DETAILS OF THE WORK BUT THEY SHALL BE PERFORMED A5 IF FULLY AND CORRECTLY 5ET FORTH AND DESCRIBED IN THE DRAWINGS AND SPECIFICATIONS. USE SPECIES GRADE Fb THE STRUCTURAL ENGINEER 15 RESPONSIBLE FOR THE DE51GN OF THE PRIMARY STRUCTURAL SYSTEM. HEADERS (SEE PLAN) (SEE PLAN) --- RESPONSIBILITY FOR ANY SECONDARY STRUCTURAL AND NON-STRUCTURAL SYSTEMS NOT SHOWN ON THE STRUCTURAL PLANS RESTS WITH 50MEONE EXTERIOR * BEARING WALL STUDS HEM -FIR NO. 2 750 P51 OTHER THAN THE STRUCTURAL ENGINEER. THE STRUCTURE SHOWN ON THE5E DRAWING5 15 5TRUCTURALLY 50UND ONLY IN ITS COMPLETED FORM. 5HEAR WALL 5TUD5, PLATES, AND BLOCKING HEM -FIR NO. 2 750 P51 THE CONTRACTOR 5HALL PROVIDE ALL NECE55ARY BRACING TO STABILIZE THE BUILDING DURING CONSTRUCTION. THE STRUCTURAL ENGINEER 15 NOT ROOF JOISTS, FLOOR JOISTS HEM -FIR NO. 2 750 P51 RESPONSIBLE FOR, AND WILL NOT HAVE CONTROL OF, CONSTRUCTION MEAN5, METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES, OR FOR INTERIOR STUDS AT NON -BEARING WALLS HEM -FIR STANDARD 550 PSI SAFETY PRECAUTIONS AND PROGRAM5 IN CONNECTION WITH THE CONSTRUCTION WORK, NOR WILL HE BE RESPONSIBLE FOR THE CONTRACTOR'S ALL OTHER LUMBER HEM -FIR STANDARD/BETTER --- FAILURE TO CARRY OUT THE CONSTRUCTION WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. WOOD AND WOOD BASED MATERIALS U5ED IN CONTACT WITH SOIL, CONCRETE OR MASONRY, INSTALLED WITHIN I " OF CONCRETE OR MASONRY, OR EXP05ED TO MOISTURE EITHER INTERIOR OR EXTERIOR, SHALL BE TREATED WITH AN APPROVED PRESERVATIVE. 50LID BLOCKING OF NOT LE55 THAN 2" NOMINAL THICKNE55 SHALL BE PROVIDED AT ENDS AND AT ALL SUPPORTS OF JOISTS AND RAFTERS. BETWEEN SUPPORTS PROVIDE BLOCKING OR BRIDGING AT 8' - 0" OC ALL SILL PLATES AT SHEAR WALLS TO BE 2x_ PRESERVATIVE TREATED DOUGLA5-FIR #2, U.N.O. ON THE PLAN5. SILL PLATES 5HALL HAVE A M015TURE CONTENT OF NOT GREATER THAN 1 9% BEFORE BEING COVERED WITH INSULATION, INTERIOR WALL FINISH, FLOOR COVERING OR OTHER MATERIAL. WOOD CONNECTORS ALL WOOD -TO -WOOD NAILING 5HALL BE PER IBC TABLE 2304.9. 1. IF PLANS AND DETAILS SPECIFY 8D, I OD OR I GD NAILS, THEY SHALL HAVE THE FOLLOWING PROPERTIES: 8D = 0. 13 1 " DIA x 2-1/2" 1 OD = 0. 1 48" DIA x 3" 1 GD = 0. 1 G2" DIA x 3-1/2" ALL SUBSTITUTIONS SHALL HAVE THE WRITTEN APPROVAL OF THE ENGINEER OF RECORD PRIOR TO USE. LIGHT GAUGE METAL FRAMING CONNECTORS AND THEIR REQUIRED FASTENERS 511ALL BE "STRONG -TIE" BY 51MP50N COMPANY, OR APPROVED EQUAL. ALL FASTENERS AND CONNECTORS IN CONTACT WITH PRESERVATIVE TREATED WOOD SHALL BE HOT -DIPPED GALVANIZED STEEL WITH A G 185 SPECIFICATION OR TYPE 304 * 3 I G STAINLESS 5TEEL. TYPE 304 AND 3 1 G 5TAINLE55 STEEL SHOULD BE USED FOR ALL CONNECTORS AND FASTENERS IN CONTACT WITH AZCA TREATED WOOD AND 50ME VARIATIONS OF ACID TREATED WOODS. HOT -DIPPED GALVANIZED STEEL SHOULD NEVER COME IN CONTACT WITH 5TAINLE55 STEEL. GENERAL INSPECTIONS - WOOD FRAMING CONSTRUCTION ELEMENT: FRAMING PERIOD: BUILDING INSPECTOR SHALL INSPECT PER IBC I 10 AND LOCAL AHJ REQUIREMENTS. ELEMENT: 13OLT5 IN CONCRETE, INCLUDING EMBEDDED BOLTS, AND EXPAN51ON AND EPDXY TYPE ANCHORS. PERIOD: BUILDING INSPECTOR 5HALL INSPECT PER IBC I 10 AND LOCAL AHJ REQUIREMENTS. : INTERCONNECTED SMOKE ALARMS AND CO DETECTORS ARE A REQUIREMENT OF THIS : : PERMIT IN ACCORDANCE WITH R314.2.2 ------------------------------------------------------------ .•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-......•....., !SEPARATE PLUMBING PERMIT REQUIRED FOR THIS PROJECT. .........................................................: S H EAR WALL SCHEDULE (ALL FASTENER SPACING ARE FOR USE WITH DOUGLA5 FIR MATERIAL) STUD AND BLKG TOP PLATE TOP PLATE APA RATED NAIL 51ZE AND BOTTOM PLATE LABEL 51ZE AT ATTACHMENT TO ATTACHMENT TO 51LL PLATE ATTACHMENT SHEATHING SPACING AT EDGES ATTACHMENT ADJOINING EDGES ROOF ABOVE FLOOR ABOVE 51LL PLATE ANCHOR BOLT NAILING TO TO CONCRETE 51ZE AT WOOD BELOW (9) FOUNDATION (1) (2) (3) (4) (5) (6) (7) (7) (8) (10) "RBC" CLIP 1TP4" CLIP 5/8 0 AB A 7/ 1 G" ONE 51DE 8d AT 4" oc 2x I Gd AT 1 2" oc 2x @8"oc @ 12"oc AT 42" oc NAIL SPEC: 8d = 0. 13 1 "0 1 Od = 0. 148"0 1 Gd = =0. I G2"O SHEAR WALL INSTALLATION NOTES: 1 .INSTALL WALL SHEATHING PANELS EITHER HORIZONTALLY OR VERTICALLY 2.5HEAR WALLS WITH WINDOW OPENINGS INCLUDED IN THEIR LENGTH ARE DE51GNED A5 "PERFORATED WALLS." PROVIDE SHEAR WALL SHEATHING AND NAILING FOR ENTIRE LENGTH * HEIGHT OF WALLS A5 INDICATED ON THE PLANS. SEE PLANS FOR HOLDOWN REQUIREMENTS 3.5HEATHING EDGE NAILING 15 REQUIRED AT ALL HOLDOWN POSTS. EDGE NAILING MAY AL50 BE REQUIRED TO EACH STUD USED IN BUILT-UP HOLDOWN5 POSTS. REFER TO HOLDOWN MANUFACTURER'S INSTALLATION DETAILS FOR ADDITIONAL INFORMATION 4. BLOCKING 15 REQUIRED AT ALL PANEL EDGES. 5.INTERMEDIATE FRAMING TO BE WITH 2x MINIMUM MEMBERS. FIELD NAILING 1 2"oc G. 3x MEMBERS CAN BE SUBSTITUTED BY (2)2x NAILED w/ I Od STAGGERED NAILS @G"oc. EDGE D15TANCE - I ", END D15TANCE - 2 1 /2" 7. BA5ED ON 0. 13 1 "0 x 1 1 /2" LONG NAILS USED TO ATTACH SHEAR CLIPS DIRECTLY TO FRAMING. USE 0. 13 1 "0 x 2 1/2" NAILS WHERE INSTALLED OVER SHEATHING 8.5HEAR CLIPS: 51MP50N "RBC" OR "LTP4" OR APPROVED EQUIVALENT 9. WHERE PLATE ATTACHMENT SPECIFIES (2) ROWS OF NAILS, PROVIDE DOUBLE JOIST, RIM OR EQUAL BELOW WALL I O.ANCHOR BOLTS SHALL BE PROVIDED WITH STEEL PLATE WASHERS 1/4" x 3" x 3". EMBED ANCHOR BOLTS 7" MINIMUM INTO THE CONCRETE 1 1. FOR ATTACHING TO EX15TING CONCRETE USE 5/8" DIAMETER BY G" LONG 51MP50N "TITEN-HD" SCREW ANCHORS 12. PRESSURE TREATED MATERIAL CAN CAUSE EXCE551VE CORROSION IN THE FASTENERS. PROVIDE HOT -DIPPED GALVANIZED (ELECTRO-PLATING 15 NOT ACCEPTABLE) NAILS AND CONNECTOR PLATES (FRAMING ANGLES, ETC) FOR ALL CONNECTORS IN CONTACT WITH PRESSURE TREATED FRAMING MEMBERS 13. WHEN PANELS ARE APPLIED ON BOTH FACES OF A SHEAR WALL, NAIL SPACING 15 LE55 THAN G"OC, PANEL JOINTS TO BE OFFSET TO FALL ON DIFFERENT STUDS. PANEL JOINTS CAN FALL ON ONE STUD IF 3x or (2)2x STUD 15 PROVIDED. 1 4. (SPECIAL INSPECTION MAY BE REQUIRED) OBTAIN ELECTRICAL PERMIT FROM STATE LABOR & INDUSTRIES ALL WORK SUBJECT TO FIELD INSPECTION FOR CODE COMPLIANCE APPROVED PLANS MUST BE ON JOB SITE CITY OF EDMONDS BUILDING DIVISION APPROVED PLAN City Of Edmonds Building Department Work REMODEL Address 1131 EMERALD HILLS DR Owner ANDREWS Approved Date 02/25/2022 Q Building Official QiA/it 46100i416( Permit Number BLD2022-0099 RECEIVED Jan 27 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ESG DESIGN z O_ ~ w tu F v � 2:Q w w a Q m Q ; to LU E o z 1 1 /2413022 J LLJ O z J W LU ? p W o o QQ0 �Q0 w � Q � LLI LU O LU p Z —LLI <M LU � U .m v8 H JNm m � A 0 1L� p a W JLuo u, z yW y U O En a �i 1-10--1 N Z —1 A W \D co DATE: 1 / 1 9/2022 SHEET 51ZE: 18" x 24" DRAWING: D1 G— 1 1 /2" V 2G— I " V 13' — I " a N N N p IE u) cf) 5'-9 1/2" AS-BU I LT FL 11411 _ 1 1_011 r--4x4 MAIN FLOOR DECK POSTS 22' — 0" 2' — 8" 00, 10, 6'— 10" I'-3" 5'-8" 7-9" 2'-8" 31— 10" 00, 00 4E co 2'-3" 4'-4" 2'-4" I'-5" 4'-0" 13'-8" 2'-5" 100 5'— 10" 00,4'-0" 00,2'-5" 4'-8" oe oe 5E ■ IG'-4" 5' — 10" 6E 24'-5" 1 T—G 1/2" 1 12'-4" 1 G'-2" 1 12'-5" OOK PLAN - BASEMENT (NO GHANOE5 PROP05ED) LOWER LEVEL WINDOW SCHEDULE Mark Width Height Header Height Area I 51- 10" 21- 10" G'-8" 175F 2 E 3' - 1011 4' - 0" G' - G" 15 5F 3E 31- 10" 4'-0" G' -G" 1551F 4E G'- 10" 4'-0" G' -G" 275F 5 E 5' - 10" 3' - 0" G' - G" 18 5F GE 51- 10" 3'-0" G' -G" 185E Total WIndOW5: G N N N N N O N 1 10 5F LOWER LEVEL DOOR SCHEDULE Mark Width Height Area I 5'-8" G'-8" 385F 2E 2'-8" G'-8" 185F 3E 2'-G" G'-8" 175F 4E 2'-0" G'-8" 135F 5E 2'-G" G'-8" 1751' GE 2'-0" G'-8" 135E 7E 3' - 1011 G' - 8" 2G 51F 8E 2'-8" G'-8" 1851' 9E 2'-G" G'-8" 175F IOE 2'-G" G'-8" 175E 1 IE 31- 10" G'-8" 2G51F 12E 2'-G" G'-8" 175E Total Doors: 12 234 5F 9'-3" 5' — 1011 IF LOOK PLAN LEGEND: EXISTING WALL (LINE OF STUD) Ox WINDOW TAG, (REFER TO WINDOW SCHEDULE) DOOR TAG, (REFER TO DOOR SCHEDULE) ESG DESIGN z O w j F m � w o LU J HN H W o � Q N � Q N ill m o Z tECEIVE Jan 27 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT z � Q � W W � Q m m � Q W m U r� �Nm v� cz — ��O A O W Q a W n z Lu Z U Q N m�� � O ONE Z J�C3 q W 17�U) U) DATE: 1 / 1 9/2022 SHEET SIZE: 18" x 24" DRAWING: D 2 =1 I'- I'l0"1'-2" IS'-0" 1'-2"10'I'_ 7 24' - 2" AS-BU I LT FLOOK PLAN - MAIN LEVEL 1411 _ I 1_011 Ln N c� N U LE ier height Area 5'-0" 55F 5'-0" 55F 7'-4" 185E 0'-8" 225E 1' - 10" 39 5F 1' - 10" 39 5F 1'- 10" 285E 0'-8" 135E 1' - 10" 23 5F 55F 55F 235E 7'-0" 55F 1'- 10" 285E 259 5F 29E 5' - 10" G' - 8" 39 SF Total Doors: 16 545 5F FLOOR PLAN LEGEND: EXISTING WALL (LINE OF STUD) (SEE 104' FOR REMODEL) Ox WINDOW TAG, (REFER TO WINDOW SCHEDULE) 0 DOOR TAG, (REFER TO DOOR SCHEDULE) ESG DESIGN z O w Lu F ~ J V m � Q WLu J HN H W o � Q N � Q N Lu m o Z ,ECEIVEI Jan 27 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT W m U v JNm v� A o W A n pi Il u"'i o LU U Q c0 z Z ��� O ONM Z J o A W OWN u) DATE: 111912022 SHEET SIZE: 18" x 24" DRAWING: D3 REMODEL FLOOD PLAN LEGEND: EXISTING WALL TO REMAIN (LINE OF STUDS) EXISTING WALL TO BE REMOVED (LINE OF STUDS) NEW WALL (LINE OF STUDS) O WINDOW TAG, (REFER TO WINDOW SCHEDULE) 0 DOOR TAG, (REFER TO DOOR SCHEDULE) Q EXHAUST FAN, SEE PLAN FOR SIZE REMODEL ENERGY CODE 5PEGIFIGATION5: INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENTa CLIMATE ZONE 5 AND MARINE 4 Fenestration U-Factorb 0.30 Skylightb U-Factor 0.50 Ceiling R-Valuee 49 Wood Frame Wallg,h R-Value 21 int r•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-• INTERCONNECTED SMOKE ALARMS AND CO ' DETECTORS ARE A REQUIREMENT OF THIS PERMIT IN ACCORDANCE WITH R314.2.2 ' .-.-.-.-.-.-.-.-.-.-.-.-.-.-.-.-.-.-.-.-.-.-.-.-.-.-.-.-.-. GLA55 GUARDRAILS (E) OPEN MAIN FLOOR DECK 13' - 10" DN 5'-7" 51- 10" 2'-5" 3'-2" 13 `3 DISHWASHERS SHALL HAVE AN APPROVED AIR GAP' FITTING ON THE DISCHARGE SIDE OF THE DISH WASHING MACHINE. REFERENCE UPC 807.3 ......................................................................- (E) STAIRS (E) WINDOW TO BE REMOVED 21'-2" 3' - 10" / . 4' - 4" n (E) DOOR "23E" TO BE 5hIFTED LEFT 8'-0" 1'-5" 51- 10" II N Ln } I u Q � 4' - 2" ,/ DINING ROOM illi z `r' w iv (RECONFIGURED) — J u — —=1 — w ALL INTERIOR WALL5 ARE KITCHEN NON -LOAD BEARING L (RECONFIGURED) REF. II II II II 1G'-8" (N) WINDOW, MATCH "I3E" 51ZE oz) 8'-0" I'- 10" 0 G-0" PANTRY (NEW) 6, - Oil (h 29 oO BEDROOM (EXISTING) REMODEL PARTIAL FLOOK PLAN -MAIN LEVEL 1 /411 _ 1 1_011 5E15MIG RETROFIT EXTERIOR WALL (5EE 5TRU( TURAL SHEET 05) ESG DESIGN z O_ ~ w Lu F F v 1 Y_ Q to w � a � J H cv LU m A ; Lu Eno z RECEIVE Jan 27 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Q J Lu C) O LLJ J W W > p W o 0 A o W � ks) Q tS> LLI Lu O p Lu Z Lu <� W M U Lu Lu �Nm A O lY p Lu P., LuJ o v, W U O z Z En a ON< Z J�a A W %D �2� DATE: 1 / 1 9/2022 SHEET 51ZE: 18" x 24" DRAWING: D4 FLAMING NOTES: 5' - 7" 00,5' - 10" 1. SEE GENERAL NOTES D I FOR FLOOR AND WALLS 511EATING AND NAILING. 2. TYPICAL INTERIOR AND EXTERIOR WALL HEADER TO BE MINIMUM (2)2x8 UNO. 3. WINDOW AND DOOR HEADERS SHALL BE INSULATED WITH A MINIMUM OF R- 10 INSULATION. 4. ALL WOOD POSTS CALLED OUT ON PLANS SHALL CARRY DOWN TO FOUNDATION, UNLESS CARRIED BY BEAM. 5. ALL BEAM -POST CONNECTIONS TO HAVE METAL BRACKET TIES. G. PROVIDE SOLID J015T BLOCKING BELOW ALL CROSS WALLS. 7. SHEAR WALLS, WHERE INDICATED ON PLAN, SHALL BE FRAMED PER SHEAR WALL 5110EDULE D 1. (E) HDR 8. CONTRACTOR TO COORDINATE SHEAR WALL ANCHOR BOLT AND HOLDOWN REQUIREMENTS WITH -IF SHEAR WALL LAYOUT. PROVIDE (N) (2)2x4 hF#2 POSTS AT EACH (N) HEADER END FLAMING PLAN LEGEND: I I (N) 2x4 * 2xG HF#2 BOARDS BTWN (E) TOP AND BOTTOM CHORDS OF SIDE TRUSSES w w/ "LU524(2G)" HANGERS AT EACH BOARD END, Q TOTAL OF (2) BOARDS /A\ SHEAR WALL TAG, (REFER TO SHEAR WALL SCHEDULE) CUT PORTION OF (E) TRU55 TOP AND HD I HOLD-DOWN TAG, (REFER TO HOLD-DOWN SCHEDULE) BOTTOM CHORDS AT (N) SKYLIGHT, "LU524(2G)" PROVIDE (N) HANGERS EXISTING WALL TO BE UPGRADED OR VERIFIED (E) TRU55 CHORDS TO (N) 5EAM5 END OR CHANGE OF --- DIRECTION OF WALL MAX (2)2x_ 5TUD5 MIN PANEL -EDGE NAIL PLWD SHEATHING TO EACH STUD (STAGGER) "5D5" 1 /4 x 2-1/2" WOOD SCREWS VERIFY (E) OR PROVIDE (N) BRACKETS PER SW SCHEDULE (E) FOUNDATION WALL TO REMAIN (N) ANCHOR PER PLAN AND a, HOLD-DOWN SCHEDULE I I I I I (N) HOLD-DOWN BRACKET, SEE PLAN FOR SIZE AND LOCATIONS (E) WALL 5TUD5 TO REMAIN, VERIFY (E) OR PROVIDE NEW EXTERIOR SHEATHING PER 5W SCHEDULE (E) BOTTOM PLATE TO REMAIN PROVIDE NEW NAILING PER SW SCHEDULE (E) RIM JOIST TO REMAIN (E) SILL PLATE TO REMAIN, VERIFY (E) OR PROVIDE NEW TITEN-HD ANCHORS PER SW SCHEDULE RETROFIT HOLD-DOWN DETAIL 3/411 _ 1 1_011 (E) @24"oc ROOF TRUSSES SPAN DIRECTION VERIFY (E) OR PROVIDE (N) EXTERIOR SHEATHING PER SW SCHEDULE, PROVIDE (N) HOLD-DOWNS PER HD SCHEDULE 1'-5 8'-0" 11'-5 51- 10" 4'-4" (N) 3-1/2" x 7-1/2"I 24F-V4 GLULAM HDR (N) 4x8 HF#2 HDR _ �( I 3 _I (2)2x PROVIDE (N) 4 HF#2 D7 P05T5 AT EACH (N) HEADER END (N) 3.5' x 5' II TRACE POSTS DOWN TO (E) FOUNDATION SKYLIGHT � (E) 3.5' x 5' II MATCH (E) II I SKYLIGHT "SKYLIGHT SIZE,, I� 4'-2" II (N) (2)2x4 t- (2)2xG HF#2 BEAMS BTWN (E) TOP AND BOTTOM CHORDS OF SIDE TRUSSES I, w/ "LU524-2(2G-2)" HANGERS AT EACH BEAM END TOTAL OF (2) BEAMS II I (E) ROOF TRUSSES II I' II TO REMAIN II iI II II II II REMODEL PARTIAL ROOF FRAMING PLAN / MAIN FLOOR SHEARWALL UPGRADE PLAN 1 /411 _ 1 1-011 TYP OF2 ANCHORED BRACKET ATTACHMENT TO FOUNDATION HOLD-DOWN SCHEDULE MINIMUM END ATTACHMENT TO "5ET" EPDXY ADHE51VE O "TITEN-HD" BOLT O P05T 51ZE END STUDS EMBEDMENT DEPTH EMBEDMENT DEPTH TAG MODEL OI MIDWALL CORNER ENDWALL MIDWALL CORNER ENDWALL HD I 11HDU4" (2)2x— (14) 1 /4"x2-1 /2" 5D5 5/8"0 x 5/8"0 x 5/8110 x 1011 1211 1211 7" EMBED. 1 O" EMBED. 1 O" EMBED. 1. MINIMUM SIZE OF POST AT THE END OF SHEARWALL, UNLESS NOTED OTHERWISE ON FRAMING PLANS. 2. EPDXY GROUTED RETROFIT ANCHORS SHALL BE INSTALLED PER THE FOLLOWING SPECIFICATIONS: 2. 1 .51MP50N "RFB" 5/5"0 ALL -THREAD ROD OR SIMILAR (A3G STEEL) TO BE USED WITH 51MP50N "SET" EPDXY ADHESIVE. 2.2.CONTRACTOR TO INSTALL 51MP50N "SET" EPDXY ADHESIVE PER MANUFACTURER'S SPECIFICATIONS CONTAINED IN REPORT E5R- 1772. 2.3.EPDXY HOLD-DOWN INSTALLATION REQUIRES A MINIMUM 8" THICK STEM WALL (CONTACT ENGINEER IF G" STEM WALL 15 PRESENT). 3. FOR ALL RETROFIT ANCHORS, MINIMUM 51DE EDGE DISTANCE = 1 -3/4", MIMIMUM CORNER OR END WALL DISTANCE = 4- 1 /4". 4. REFER TO PROJECT STRUCTURAL NOTES AND BUILDING INSPECTOR INSTRUCTIONS FOR POST -INSTALLED ANCHOR INSPECTION REQUIREMENTS. 5. ALL FASTENERS SPECS ARE FOR USE w/ HEM FIR LUMBER. G. ALL BRACKETS TO BE "51MP5ON STRONG -TIE" OR APPROVED EQUAL. REFER TO MFR'5 INSTALLATION INSTRUCTIONS. RECEIVED Jan 27 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ESG DESIGN z O_ W w C4 � v � Q w w J to m Q ; to E o z J W Lu _ p W o o QC'4 �Q0 W � k Q w W 0 Q W Cl Z LU < m W Lq U H �Nm In A oLuQ a W J�o v, z yWy L U O a Z A W kD�2� DATE: 1 / 1 9/2022 SHEET 51ZE: 18" x 24" DRAWING: D5 ESG DESIGN 14 0 13E � 12 —III III III III III III III III III III III III III III III III III III III III III III III III III III IIII III— 71 iEd lEd MEM EMH IEMI 1EI-11 EIM IEMI IEMI ETH EMH lEd -Mll I z EXISTING REAR ELEVATION � Q 3/1 61I — I f-OII W W (N) SKYLIGHT (N) HEADER � LU W >' PER FRAMING PLAN A (E) DOOR "23E" O [a o (N) WINDOW, MATCH " 13E" 51ZE TO BE SHIFTED LEFT q -- � Q w zn VERIFY (E) OR PROVIDE A 23 O II I� 3 13 O 12E �o (N) EXTERIOR 5HEATHING �1��1 O W w O PER 5W SCHEDULE, Q PROVIDE (N) HOLD-DOWNS I m PER HD SCHEDULE I D5 6E 5E �E 4E y � W ms � m �Nm v� cz — o A — REMODEL REAR ELEVATION a W U Q N Q 3 1 6" = 1'—O" z z m / o oLU N� Z ��C3 A W ��N DATE: 111912022 SHEET SIZE: 18" x 24" DRAWING: D6 z O w � W ~ J V m � � w W o � J � (V H W o � Q N � Q N W m o Z r.> Lo N N O STUDS (USE 3x STUD AT PANEL EDGES WHERE REQD IN SHEARWALL SCHED) DOUBLE 2X PLATE PORTION OF (E) TRUSS TO REMAI (N)2xG BOARD AT TOP CHORD AND (N)2x4 BOARD AT BOTTOM CHORD ROOF TRUSSES TO REMAIN 5IMP50N "LU52G(24)" HANGERS (N) BOARDS TO (E) TRUSS CHORDS) 5IMP50N "LU52G(24)" HANGERS (E) TRUSS CHORDS TO (N) BOARDS II CUT PORTION OF (E) TRUSS TOP AND BOTTOM CHORDS AT (N) SKYLIGHT LOCATION (N) 3.5' x 5' SKYLIGHT, (MATCH (E) SKYLIGHT SIZE) BLKG REQD AT ALL PANEL EDGES (USE (N) (2)2xG BEAM AT TOP CHORD 3x WHERE REQD AND (N) (2)2x4 BEAM AT BOTTOM CHORD PLWD 5HTG W/ FACE IN SHEARWALL SCHED (N) "LU52G-2(24-2)" HANGERS GRAIN PERPENDICULAR OR PARALLEL TO STUDS EDGE NAILING PER SHEARWALL SCHED. NAIL PANEL FIELD AT 1 2" oc BOT PL (USE 3x WHERE REQD IN SHEARWALL SCHED) SHEARWALL f=RAM I NG DETAIL 2 3/411 _ I I_o11 (E) TOP P (N)(4) (N) ( I CRIPPLE STUDS AT 1 2" oc (N)2xG CROSS -BOARD SUPPORTING SHORT TRUSS PORTION w/ "LU52G" HANGERS TO SIDE TRUSSES (E) ROOFNG AND SHEATHING TO REMAIN PORTION OF (E) TRUSS TO REMAIN (E) BLOCKING TO REMAI (E) FASCIA TO REMAIN SKYLIGHTS SHALL BE INSTALLED, S REQUIRED BY IRC R308.6 AND I THE WA STATE ENERGY CODE PORTION OF (E) TRUSS TO REMAIN "�-51MP501\1 "LU52G(24)" HANGERS (E) TRUSS CHORDS TO (N) BEAMS 5 D7 TEMPORARY SHORING OF THE ROOF STRUCTURE WILL BE NECESSARY PRIOR TO CUT THE PORTION OF EXISTING ROOF TRUSS AND INSTALLING NEW BEAMS AND HANGERS. ALL SHORING WORK AND INSTALLATION SHALL BE PER THE CONTRACTOR (N) SKYLIGHT FRAMING DETAIL (N) HEADER PER PLAN (E) EXTERIOR MAIN FLOOR WALL TO REMAIN ----I u (N) HEADER POST PER PLAN (N)SIMPSON "LU524" HANGER (E) TRUSS CHORD TO (N) CROSS -BOARD (N)2x4 CROSS -BOARD SUPPORTING SHORT TRUSS PORTION w/ "LU524" HANGERS TO SIDE TRUSSES NEW DROPPED HEADER F17) RAMING DETAIL 4 3/411 _ 11_011 3/411 _ 11_011 (N) (2)2xG CROSS -BEAM BTWN (E) TRUSSES TOP CHORDS (N) 3.5' x 5' SKYLIGHT MATCH (E) SKYLIGHT SIZE F -------------- ------------------- (N) YtKIM[ILK 1/2" GWt5 CUT PORTION OF (E) TRUSS TOP AND BOTTOM CHORDS AT (N) SKYLIGHT LOCATIONS (N) (2)2x4 CROSS -BEAM BTWN (E) TRUSSES BOTTOM CHORDS 5IMP50N "LU524" HANGER (E) TRUSS CHORD TO (N) BEAM c5�(N) SKYLIGHT FRAMING 3/411 _ 11_011 5IMP50N "LU52G" HANGER (E) TRUSS CHORD TO (N) BEAM PORTION OF (E) MID TRUSS TO REMAIN PROVIDE (N) VERTICAL WEB w/ METAL CONNECTOR PLATES TO (E) TRUSS CHORDS ) R-21 BATT INSULATION (N) SKYLIGHT PERIMETER FRAMING PER CONTRACTOR (E) ATTIC INSULATION TO REMAIN 5/5" GWB TO REMAIN SIDE VIEW DETAIL RECEIVED Jan 27 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ESG DESIGN z O_ ~ w tu F v en X Q w w � a � Q LU ~Q r m Q ; to Ell o z v w > Q o 0 Q o J � W � wwo W o ca Z w < m W m U JNm j E Z A lSi O 1L� Q P., W Lu J o U O m LU z Z m a ON< Z J�a A W %D �2� DATE: 1 / 1 9/2022 SHEET 51ZE: 18" x 24" DRAWING: D 7 GENERAL NOTES Nothing in this permit approval process shall be interpreted as allowing or permitting the maintenance of any currently existing illegal, nonconforming, or unpermitted building, structure, or site condition which is outside the scope of the permit application, regardless of whether such building, structure, or condition is shown on the site plan or drawing. Such building, structure, or condition may be the subject of a separate enforcement action. Sound/noise originating from temporary construction sites as a result of construction activity are exempt from the noise limits only during the hours of 7:OOam to 6:OOpm on weekdays and 10:00am and 6:OOpm on Saturdays, excluding Sundays and Federal Holidays. At all other times the noise originating from construction sites/activities must comply with the noise limits, unless a variance has been granted. ECC Chapter 5.30 All changes in plans and field modifications shall be approved by the local jurisdiction. The design professional shall prepare drawings as required for approval. IBC 107.4 Temporary address shall be clearly visible from street during all phases of construction. Failure to properly post house/building numbers may result in no inspection by the City Inspector. Curb signage is not acceptable. Address numbers (4" min. lit. & 1/2" min. stroke width) shall be posted to be plainly visible from the street or road fronting the property. IRC R319 LIFE SAFETY NOTES Smoke alarms shall be installed in each sleeping room, outside of each separate sleeping area in the immediate vicinity of the bedrooms, and on each level (including basements and habitable attics) in new construction and in existing dwellings when alterations, repairs or additions requiring a permit occur. A heat detector or heat alarm shall be provided in new attached garages. Smoke alarms shall be hard -wired with battery backup, and when more than one smoke alarm is required within an individual dwelling unit, they shall be interconnected. Discuss exceptions to the power source requirements with the Building Inspector. IRC R314 IBC 907.2.11.2 R314.2.1 Carbon monoxide alarms shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms and on each level in new construction and in existing dwellings when alterations, repairs or additions requiring a permit occur, or when one or more sleeping rooms are added or created. IRC R315 Handrails and guards must be capable of resisting a concentrated load of 200 pounds per square foot applied in any direction at any point along the top. Guard in -fill components must be capable of resisting 50 pounds per square foot. IRC Table R301.5 IBC TABLE 1607.1 IBC 1607.8 s shall be continuous through stair flights of tour or more risers, without interruption by newel posts (unless at a turn) or other obstructions, and return to a wall, newel post, or safety terminal. The grip -size shall be Type I or II or of equivalent graspablity. IRC 311.7.8 IBC 1011.11 LIFE SAFETY NOTES (continued) Provide one operable escape window in the basement, habitable attic and in each sleeping room meeting all of the following quirements: *An operable area of not less than 5.7 sq. ft. (5 sq. ft. for grade floor opening) •A minimum clear opening height of 24 inches •A minimum clear opening width of 20 inches *Not more than 44 inches between the finished floor and the bottom of the clear opening. Escape windows located under decks or porches must have a path 36 inches in height to a yard or court. R310 IBC 1029 The greatest riser height within any flight of stairs or the greatest tread depth within any flight of stairs shall not exceed the smallest by more than 3/8 inch. IRC R311.7.5.1 IRC R311.7.5.2 FOOTINGS/FOUNDATIONS Footing drains are required around concrete/masonry foundations that retain earth and enclose habitable or usable spaces located below grade, or for crawl spaces when a minimum 6 inch slope within the first 10 feet of the foundation wall is not achieved. A separate footing drain inspection by COE Engineering department is required. IRC R401.3 IRC R405.1 Slab -on -grade floors shall be a minimum 3.5-inch thick concrete over a 6 mil vapor barrier and 4-inch base of sand/gravel/etc. There shall be a thermal -break for slabs inside a foundation wall, and if the slab is less than 24" below the exterior grade, 24" wide R-10 perimeter insulation must be provided. Slabs used as part of a hydronic heating system shall have R-10 insulation provided throughout the entire slab area. IRC R506 WSEC R402.2.9 WSEC Table R402.1.1 Vertical rebar must be hooked and tied in place at time of footing inspection. Maintain minimum 3" clearance to earth, 1-1/2" to form -work for reinforcement. R403.1.3 R404.1.2.3.7.4 Anchor bolts shall be at least 1/2 -inch in diameter and extend 7 inches into concrete. There shall be a minimum of two bolts per plate, with one bolt within 12 inches but not closer than seven bolt diameters from the end of the plate. The bolt spacing shall not exceed 6 feet o.c. and shall have a nut and 3"x3"x0.229" washers unless engineered. IRC R403.1.6 FRAMING NOTES Hardware and fasteners in contact with preservative -treated wood shall be of hot -dipped zinc galvanized steel, stainless steel, silicon bronze or copper. IRC R317.3.1 IBC 2304.10.5.1 Joists less than 18" and beams less than 12" to grade and all wood exposed to weather shall be preservative -treated or naturally resistant to decay. IRC R317 IBC 2304.12.1.1 Joists shall have not less than 1.5 inches bearing on wood or metal and 3 inches on concrete. Joists shall be prevented from rotating at the ends and at intermediate support by approved hangers, 2 inch nominal blocking, or attachment to a rim board. IRC 502.6 IRC 502.7 IBC 2308.4.2.2 IBC 2308.4.2.3 FRAMING NOTES (continued) Foundation cripple walls shall be framed of studs not less in size than the studs above. Walls over 4 feet in height shall be framed of studs having the size required for an additional story. Cripple walls studs less than 14 inches in height shall be sheathed on at least one side with a wood structural panel that is fastened to both the top and bottom plates in accordance with Table R602.3 (1), or cripple walls shall be constructed of solid blocking. Cripple walls shall be supported on continuous foundations. IRC R602.9 IBC 2308.5.6 Prior to the framing inspection, the building must be dried in with a minimum of roofing, windows, and siding paper installed. Truss layouts showing girder truss/hip-master locations are not permitted to change and must be followed correctly. If the truss manufacturer requests to change, in part or in whole, the layout shown, they must contact the architect/designer to ensure that the structural design of the building is maintained. If the layout shown is changed, in part or in whole, the Building Division requires new engineering calculations and must approve the changes prior to the installation of the roof sheathing. Exterior and bearing wall studs may be notched <25% and bored <40% of the stud width. Non -bearing wall studs may be notched <40% and bored <60% of the stud width. Any bore located <5/8" from the stud face is considered a notch. Rafters and joists may be notched in the outer thirds of the span with a maximum notch depth 1 /6th and a notch width 1 /3rd the depth of the member. Rafters and joists may be bored up to 1/3rd the depth of the member no closer than 2" to each edge or to another bore. Top plates notched or bored >50% of the width must have a 16ga. strap, 6 inches past and fastened with 8-1 Od nails at each side of the opening. IRC R502.8 IRC R602.6 IBC 2308.4.2.4 Attic access openings are required for buildings with combustible ceiling or roof construction over an area >30 sq. ft. and with a 30" vertical space between ceiling and roof framing members. The rough -framed opening shall be 22"00" and located in a hallway or other readily accessible location. The access cover shall be weather-stripped and insulated to a level equal to the surrounding surfaces. IRC R807.1 WSEC 402.2.4 ,ttic ventilation openings shall not be less than 1/150 of the area f the space ventilated. It may be reduced to 1/300 if at least 50 ercent and not more than 80 percent of the required openings are t least 3 feet above the eave vents with the balance provided by ie eave vents. The net free cross -ventilation area may also be educed to 1/300 when a Class I or II vapor barrier is installed on e warm -in -winter side of the ceiling. IRC R806.2 IBC 1202.2 IBC 1202.4 ADDITIONAL REQUIREMENTS A survey may be required prior to the foundation wall inspection is the Building Inspector is unable to verify setbacks. Lot line stakes should be in place at the time of the foundation inspection and established property pins should be made visible. MECHANICAL NOTES A 307700" level working space shall be provided in front of the control side to service appliances. In attics and underfloor areas, a passageway a minimum of 30 inches high and 20 inches wide traveling not more than 20 feet from the access shall be provided. A 24 inch wide solid pathway shall be provided in attics. A switch -controlled luminaire is required at the passageway opening and a receptacle outlet at or near the appliance. A means of electrical disconnect is required within sight of the appliance or the breaker is to be capable of being locked in the open position. IRC M1305 IMC 306 NEC 422.31(B) Provide the combustion air required for the proper operation of the appliance(s). The minimum required volume per the standard method is 50 cubic feet per 1000 BTU/hr. Where exhaust fans, clothes dryers, and kitchen ventilation systems interfere with the operation of appliances, makeup air shall be provided. Fuel -fired appliances shall not be located in sleeping rooms, bathrooms, toilet rooms, or storage closets unless specific installation requirements are met. IRC R1503.6 G2407.4 G2407.5.1 IFGC 303.3 304.4 304.5 An exhaust hood/system of >400cfm installed or required by the range or cooktop manufacturer must be provided with makeup air equal to the exhaust air rate. IRC M1503.6 IMC 505.4 Provide required makeup air in the laundry room. Louvered doors or openings/grilles into other spaces may be used to meet the requirements. Other limitations may arise if a gas dryer is installed. IMC 504.6 G2407.4 G2407.9.1 IFGC 304.9.1 Dryer ducts shall terminate outside of the building, 3 ft. from any openings into the building. The termination shall have a back draft damper and no screen. The dryer duct shall be a minimum 28 ga. thick, a minimum 4 inches in diameter, have a smooth interior finish, have sections joined with the insert end in the direction of airflow, be supported at 12 ft. intervals, and secured in place protected by nail plates that extend 2" above/below bottom/top plates. The joints shall be sealed with UL181A listed mastic or tape. Dryer duct maximum lengths is 35 ft. with deductions for fittings (or sized/length per manufacturer). If concealed, the equivalent length of the duct shall be permanently labeled or tagged within 6 ft. of the dryer connection. IRC M1502 M1601.4.1 G2439 IMC 504 IFGC 614 Hydronic heating system piping shall be tested at 100 psi water pressure or 1 1/2 times the operating pressure, whichever is greater, for a minimum of 15 minutes. Piping embedded in concrete shall be pressure tested prior to the placing of concrete and be maintained at operating pressure during concrete placement. The test must be observed by the Building Inspector prior to concrete placement. Note: a means of providing outdoor air per IRC R303.49 M505 IRC Chapter 21 and IMC 403.2 is required. IMC 1208 - 1209 Refrigerant circuit access ports located outdoors shall be fitted with locking -type tamper- resistant caps. or shall be otherwise secured to prevent unauthorized access. IRC M1411.8 IMC 1101.10 PLUMBING NOTES ixtures installed on a floor level that is lower than the next upstream manhole cover of the public or private sewer shall be protected from backflow of sewage by installing an approved type of backwater valve. Fixtures on floor levels above such elevation shall not discharge through the backwater valve. UPC 710.1 Vent all plumbing fixtures through the roof per UPC 906.0 or with a loop vent per UPC 909.0. Air admittance valves are not permitted unless first approved by the Building Inspector on a case case basis. Water heaters installed in attics, attic -ceiling assemblies, floor -ceiling assemblies or a floor/sub-floor assembly, where damage may occur from a leak, shall be installed in a watertight pan made of corrosion -resistant materials. The pan shall not be less than 1 1/2" in depth and have a minimum 3/4" drain and the drain shall terminate in a visible location. The drain cannot empty into the crawlspace beneath a building. Discharge from a relief valve into a water heater pan shall be prohibited. UPC 507.4 UPC 507.5 UPC 608.5(7) Access will be required for the whirlpool/jetted tub pump and the tempering valve for all tubs. The tempering valve may also be installed at the water heater. UPC 409.6 Showers shall be a minimum of 900 square inches and be capable of encompassing a 30 inch circle. The shower receptor shall have a finished dam, curb, or threshold between 2" and 9" above the top of the drain. The floor of the shower shall slope a minimum of 1/4" and a maximum of 1/2". Lining materials for built-up showers and shower seats shall be sloped, extend upward 3" above the horizontal surface, and over the top of the dam or threshold. Shower receptors shall be tested by filling with water to the top of the rough threshold while plugged at the drain. Protect the weep holes in the sub -drain clamping ring from clogging. UPC 408.5 - 408.7 Main building shut-off required on water supply line. UPC 606.2 Pressure reduction valve on main water supply line required by City code. Vent hot water tank relief valve directly into the drainage system OR outside. UPC 608.5 (3) Hot water tank must be seismically anchored or strapped at points within the upper one-third and lower one-third of its vertical dimensions. At the lower point, a minimum distance of 4" must be maintained above the controls with the strapping. C 507.2 All pressure absorbing devices (e.g. air chambers, mechanical devices, hammer arrestors) shall be accessible or installed per manufacturer. UPC 609.10 Minimum 1" air -gap required at dishwasher. UPC 414.3 Hose bibs (exterior faucets) are required to have a permanently affixed anti -siphon device installed. UPC 603.5.7 Soaker and jetted tubs shall be installed and supported per the manufacturer's installation specifications. UPC 409.6 FIRE -RATED CONSTRUCTION Dwelling/garage separation shall be maintained by installing 1/2" gypsum wallboard on the garage side from the foundation to the underside of the roof sheathing. Ceiling of garages with habitable space above shall have 5/8-inch Type X gypsum wallboard attached with 1-7/8 inch 6d coated nails or equivalent drywall screws and the structural elements supporting the ceiling protected with 1/2 gypsum wallboard. Enclosed accessible space under stairs shall have walls, under -stair surface and any soffits protected on the enclosed side with 1/2" gypsum wallboard. Water resistant gypsum shall not be used as a the backing board where there will be direct exposure to water, or in areas subject to continuous high humidity (showers, etc.). IRC R302.6 IRC R702.3.7 Fireblocking shall be provided to cut off all concealed draft openings (both vertical and horizontal) and to form an effective fire barrier between stories, and between a top story and the roof space. Fireblocking shall be provided in wood -frame construction in the following locations: 1) In concealed spaces of stud walls and partitions, including furred spaces and parallel rows of studs or staggered studs as follows: 1.1 Vertically at the ceiling and floor levels. 1.2 Horizontally at intervals not exceeding 10 feet. 2) At all interconnections between concealed vertical and horizontal spaces such as occur at soffits, drop ceilings and cove ceilings. 3) In concealed spaces between stair stringers at top and bottom of the run. 4) At openings around vent, pipes, and ducts at ceiling and floor level, with an approved material to resist the free passage of flame and products of combustion. For additional requirements see IRC 302.11 Draftstops shall be installed in combustible construction where there is usable space both above and below the concealed space of a floor/ceiling assembly, so that the area of the concealed space does not exceed 1000 sq. ft. and shall divide the space into approximately equal areas. Where the assembly is enclosed by a floor membrane above and a ceiling membrane below, draftstopping shall be provided in floor/ceiling assemblies under the following circumstances: 1.Ceiling is suspended under the floor framing. 2.Floor framing is constructed of truss -type open -web or perforated members. Draftstopping materials shall not be less than 1/2 inch gypsum board, 3/8 inch wood structural panels or other approved materials adequately supported and installed parallel to the floor framing members IRC R302.12 ADDITIONAL REQUIREMENTS Height verification shall be done by the applicant's agent/contractor and observed by the Building Inspector on site. The agent/contractor shall set up the equipment (transit/builders level), establish the datum point, and the point of average grade. These items must be consistent with the approved plans. If the proposed height of a building (as shown on the plans) is within 12 inches of the maximum height permitted for the zone, an elevation survey is required. An elevation survey consists of three components to be conducted by a licensed surveyor. 1) Prior to construction, the surveyor shall establish average grade as specified in ECDC 21.40.030, and shall establish a reference datum point that will be undisturbed and can be freely accessed. 2) The surveyor shall locate the elevation of the first floor prior to the City under -floor inspection. 3) A final letter of height confirmation shall be provided upon completion of the structure.