Loading...
BLD2022-1727_Manufacturer_Specifications_and_Installation_Instructions_12.19.2022_2.55.23_PM_3276719Installation Instructions Fig. 1 —Size 36K 1.,1 ,� W Fig. 2 —Sizes 48K and 58K NOTE: Read the entire instruction manual before starting the installation. NOTE: Images are for illustration purposes only. Actual models may differ slightly. TABLE OF CONTENTS SAFETY CONSIDERATIONS........................................................2 PARTSLIST....................................................................................3 SYSTEM REQUIREMENTS...........................................................4 WIRING...........................................................................................4 DIMENSIONS..................................................................................5 CLEARANCES................................................................................7 INSTALLATION TIPS....................................................................8 ELECTRICAL DATA......................................................................10 CONNECTION DIAGRAMS..........................................................10 SYSTEM VACUUM AND CHARGE.............................................10 START-UP.......................................................................................11 OUTDOOR UNIT DIAGNOSTIC GUIDES...................................12 Specifications subject to change without notice. SAFETY CONSIDERATIONS Installing, starting up, and servicing air- conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.). Only trained, qualified installers and service mechanics should install, start- up, and service this equipment. Untrained personnel can perform basic maintenance functions such as coil cleaning. All other operations should be performed by trained service personnel only. When working on the equipment, observe the precautions in the literature and on tags, stickers, and labels attached to the equipment. Follow all safety codes.Wear safety glasses and work gloves. Keep a quenching cloth and a fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the safety- alert symbol A . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety- alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label. HAZARD Failure to follow this warning could result in death, serious personal injury, and/or property damage. Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion. EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. (152 mm) vertical rise to the valve connections on the outdoor units. If more than the recommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start-up. Specifications subject to change without notice. 38MBR-03SI PARTS LIST Table 1 —Parts List PART NO. PART NAME QTY. 1 Outdoor unit 1 - Literature package including installation instructions and warranty 1 - Grommet to secure the outdoor unit (helps with vibration prevention during unit operation) 4 - Drain Joint 1 - Drain Hose 1 Fig. 3 —Parts List NOTE: - If the outdoor unit is higher than the indoor unit, prevent rain from flowing into the indoor unit along the connection pipe by making a downward arc in the connection pipe before it enters the wall to the indoor unit. This ensures that rain drips from the connection pipe before it enters the wall. - Piping and the interconnecting wiring are field supplied. - The illustration above is only a sketch. Different models may be slightly different. The following units are covered in these installation instructions. Table 2 — Unit Sizes SYSTEM TONS KBTUH VOLTAGE - PHASE OUTDOOR MODEL 3 36,000 208/230 - 1 38MBRQ36A- - 3 4 48,000 208/230 - 1 38MBRQ48A- - 3 5 58,000 208/230 - 1 38MBRQ58A- - 3 38MBR-03SI Specifications subject to change without notice. SYSTEM REQUIREMENTS Allow sufficient space for airflow and service of the unit. See Fig. 6 for the required minimum distances between the unit, walls or ceilings. Piping IMPORTANT: Both refrigerant lines must be insulated separately. Table 3 contains piping information for the product covered within this document. Table 3 — Piping and Refrigerant Information SYSTEM SIZE Min. Piping Length 36K 48K 58K ft(m) 10(3) 10(3) 10(3) Standard Piping Length ft(m) 25(7.5) 25(7.5) 25(7.5) Max. outdoor - indoor height difference (OU higher than IU) ft(m) 98(30) 98(30) 98(30) Max. outdoor - indoor height difference (IU higher than OU) ft(m) 98(30) 98(30) 98(30) PIPING Max. Piping length with no additional refrigerant charge ft(m) 26(8) 26(8) 26(8) Max. Piping Length ft(m) 213(65) 213(65) 213(65) Additional refrigerant charge (between Standard - Max piping length) Oz/ ft(g/m) 0.32 (30) 0.32(30) 0.32(30) Gas Pipe (size - connection type) in(mm) 5/8(16) 5/8(16) 3/4(19) Liquid Pipe (size- connection type) in(mm) 3/8(9.52) 3/8(9.52) 3/8(9.52) REFRIGERANT Refrigerant Type - - R410A R410A R410A Charge Amount Lbs(kg) 6.72(3.05) 9.26(4.2) 10.19(4.62) All outdoor units have an electronic expansion valve to manage the refrigerant flow of the fan coil connected. WIRING All wires must be sized per NEC (National Electrical Code) or CEC (Canadian Electrical Code) and local codes. Use Electrical Data table MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively. SIZES 36 - 58 RECOMMENDED CONNECTION METHOD FOR POWER AND COMMUNICATION WIRING Power and Communication Wiring: The main power is supplied to the outdoor unit. The field supplied power wiring from the outdoor unit to the indoor unit consists of three (3) wires and provides the power for the indoor unit. Two wires are high voltage AC power and one is a ground wire. To minimize voltage drop, the factory recommended wire size is 14/2 stranded with a ground. Communication Wiring: A separate shielded stranded copper conductor only, with a 600 volt rating and double insulated copper wire, must be used as the communication wire from the outdoor unit to the indoor unit. Please use a separate shielded 16GA stranded control wire. EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Wires should be sized based on NEC and local codes. EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Be sure to comply with local codes while running wire from the indoor unit to the outdoor unit. Every wire must be connected firmly. Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Ensure all wiring is tightly connected. No wire should touch the refrigerant tubing, compressor or any moving parts. Disconnecting means must be provided and shall be located within sight and readily accessible from the air conditioner. Connecting cable with conduit shall be routed through the hole in the conduit panel. 4 Specifications subject to change without notice. 38MBR-03SI DIMENSIONS Size 36K Ln N Fig. 4 —Size 36K Table 4 — Dimensions 36K UNIT SIZE WIDTH IN (MM) DEPTH IN (MM) HEIGHT IN (MM) L1 IN (MM) L2 IN (MM) WEIGHT LB (KG) 36K 37.24 (946) 16.14 (410) 31.89 (810) 26.50 (673) 15.87 (403) 136.47 (61.9) 38MBR-03SI Specifications subject to change without nofice. Sizes 48K and 58K 52AS In (t3}imN i i I 1 i , 1 I I I I I 17.6t1n -----i.46mRa ---. DETAIL 8 kiln (67M* 0 37.22 In ((lllu.!,�1u111(,,, r.�;vi�>�,n„1„um111111'I \ r illU!!f{ii(u(w!!�.�f���� nmtn11111V11111ti� I,ii1111114tntu,�, ��,�p„ 'nlu011�j!!!!lI!l LI 2196In I (634 awn) _.. 40.571n -- (1030mm) - u 15901n (404 mm) i I I OCTAL A Am In — I'611s1'1 I --� leis plsrN Pon% ` 0"00 Fig. 5 —Sizes 48K and 58K Table 5 — Dimensions 48K and 58K UNIT SIZE WIDTH IN (MM) DEPTH IN (MM) HEIGHT IN (MM) L1 IN (MM) L2 IN (MM) OPERATING WEIGHT LB (KG) 48K 37.22 (945) 15.58 (396) 52.48 (1333) 24.96 (634) 15.90 (404) 217.4 (98.6) 58K 37.22 (945) 15.58 (396) 52.48 (1333) 24.96 (634) 15.90 (404) 217.4 (98.6) 6 Specifications subject to change without notice. 38MBR-03SI CLEARANCES H Air -inlet Fig. 6 — Outdoor Unit Clearances Table 6 — Outdoor Unit Clearance Dimensions UNIT MINIMUM VALUE IN. (MM) A 24 (610) B 24 (610) C 24 (610) D 4 (101) E 4 (101) 931n (25cm) or more for properairflow 24in (61cm) or more is 98in (25cm)' or more for proper airflow 24in (61cm) or more is recommended for service 0 more 69in(160cm) 24in(60cm) or more 0na or more multiple parallel unit arrangement 24in (61cm) or more on a single parallel unit arrangement Fig. 7 —Clearances for multiple units I (48cm) or more on a multiple parallel unit arrangement 4in (10cm) or more on a single parallel unit arrangement 38MBR-03SI Specifications subject to change without notice. INSTALLATION TIPS Ideal installation locations include: Outdoor Unit • A location which is convenient to installation and not exposed to strong winds. • A location which can bear the weight of the outdoor unit and where the outdoor unit can be mounted in a level position. • A location which provides appropriate clearances (see Fig. 6). • Do not install the indoor or outdoor units in a location with special environmental conditions. For those applications, contact your Ductless representative. OUTDOOR UNIT INSTALLATION 1. Use a rigid base to support the unit in a level position. 2. Locate the outdoor unit and connect piping and wiring. EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. In regions with snowfall and cold temperatures, avoid installing the outdoor unit in areas where it can be covered by snow. If the outdoor unit is installed in areas where heavy snow is expected, a field supplied ice or snow stand and/or field supplied -installed wind baffle should be installed to protect the unit from snow accumulation and/or blocked air intake. Blocking the air intake may result in reduced airflow, significantly reduced performance and damage to the equipment. Strong wind 0 0 X Fig. 8 -High Wind Installation MAKE REFRIGERANT PIPING CONNECTIONS (OUTDOOR UNIT) IMPORTANT: Use refrigeration grade tubing ONLY. No other type of tubing may be used. Use of other types of tubing will void the manufacturer's warranty. Do not open the service valves or remove the protective caps from the tubing ends until all connections are made. Bend the tubing with bending tools to avoid kinks and flat spots. Keep the tubing free of dirt, sand, moisture, and other contaminants to avoid damaging the refrigerant system. Avoid sags in the suction line to prevent the formation of oil traps. Insulate each tube with a minimum 3/8-in. (10 mm) wall thermal pipe insulation. Inserting the tubing into the insulation before making the connections will save time and improve installation quality. 1. Remove the service valve cover, if provided with the unit. 2. Cott the pipe, with a pipe cutter, at 90 degrees (see Fig. 9). 3. Remove the service connection, if provided with the unit. 4. Remove all the burrs from the cut cross section of the pipe avoiding any burrs inside the tubes. 5. Remove the flare nuts attached to the indoor and outdoor units. 6. Install the correct size flare nut onto the tubing and make a flare connection. Refer to Table 7 for the flare nut spaces. Table 7 - Flare Nut Spacing OUTER DIAM. (MM) A (MM) MAX. MIN. 01/4"(6.35) 0.05 (1.3) 0.03 (0.7) 03/8"(9.52) 0.06 (1.6) 0.04 (1.0) 01/2"(12.7) 0.07 (1.8) 0.04 (1.0) 05/8"(15.88) 0.09 (2.2) 0.08 (2.0) HZBar. ndle a Bar Yoke Cone Copper pipe Clamp handle Red arrow mark Fig. 10 -Flare Nut Spacing 7. Apply a small amount of refrigerant oil to the flare connection on the tubing. 8. Align the center of the pipes and/or service valve. Indoor unit tubing " Flare nut Piping Fig. 11 -Align Pipe Center 9. Connect both the liquid and gas piping to the indoor unit. 10. Tighten the flare nut using a torque wrench as specified in Table 8. 11. Complete the installation. Table 8 - Tightening Torque PIPE DIAMETER INCH (MM) TIGHTENING TORQUE FT -LB N-M 01/4" (6.35) 10 to 13 13.6 to 17.6 03/8" (9.52) 24 to 31 32.5 to 42.0 01/2" (12.7) 37 to 46 50.1 to 62.3 05/8" (15.88) 50 to 60 67.7 to 81.3 Flare nut I Coppertube Fig. 12 -Tighten the Flare Nut q� 90° / X X oblique Roughness X Burr EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Excessive torque can break the flare nut depending on installation Fig. 9 -Cut the pipe conditions. Specifications subject to change without notice. 38MBR-03SI Install All Power and Interconnecting Wiring to Outdoor Units 1. Mount the outdoor power disconnect. 2. Run the power wiring from the main box to disconnect per NEC and local codes. 3. Remove the field wiring cover from the unit by loosening the screws. 4. Remove the caps on the conduit panel. 5. Connect the conduit to conduit panel (see Fig.13). 6. Properly connect both the power supply and control lines to the terminal block per the connection diagram for the appropriate unit capacity and voltage. 7. Ground the unit in accordance with NEC and local electrical codes. 8. Use the lock nuts to secure the conduit. 9. Reinstall the field wiring cover. EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Be sure to comply with local codes while running wire from indoor unit to outdoor unit. Every wire must be connected firmly. Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, ensure all wiring is tightly connected. No wire should be allowed to touch the refrigerant tubing, compressor or any moving parts. Disconnecting means must be provided and shall be located within sight and readily accessible from the air conditioner. Connecting cable with the conduit shall be routed through hole in the conduit panel. Outdoor unit Terminal B Ore r�s n ) 'gym Conduit Fig. 13 —Field Wiring panel Drain Connections Install drains must meet local sanitation codes. Install the outdoor unit drain joint Fit the seal into the drain joint, then insert the drain joint into the base pan hole of the outdoor unit. Rotate 90' to securely assemble them. Connect the drain joint with an extension drain hose to avoid condensate from draining off the outdoor unit during the heating mode. —/Seal Seal Base pan Drain joint Fig. 14 —Drain Joint NOTE: Images are for illustration purposes only. EQUIPMENT DAMAGE HAZARD In cold climates, ensure the drain hose is as vertical as possible to ensure swift water drainage. If water drains too slowly, it can freeze in the hose and flood the unit. NOTE: Basepan built-in with multiple holes for proper draining during defrost. For applications where it is required to seal these holes, and re -direct the condensate drain, rubber plugs are available through RCD. Table 9 — Base Pan Base Rubber Plugs OUTDOOR UNIT MODEL NUMBER PER UNIT BASE PAN BASE RUBBER PLUGS RCD PART NUMBER QUANTITY 38MBRQ36A- - 3 12600801AO0117 5 38MBRQ48A- - 3 12600801AO0118 5 38MBRQ58A- - 3 12600801AO0118 5 38MBR-03SI Specifications subject to change without notice. 9 ELECTRICAL DATA OUTDOOF POWER SUPPLY COMPRESSOR OUTDOOR FAN MOTOR Table 10 — Electrical Data UNIT SIZE 36K 48K 58K 208/230 - 1 - 60 208/230 - 1 - 60 208/230 - 1 - 60 Max — Min" Oper. Voltage 253 - 187 253 - 187 253 - 187 MCA 30 35 35 MOCP 50 50 50 Volts- PH- Hz 208/230 - 1 - 60 208/230 - 1 - 60 208/230 - 1 - 60 RLA 8.85 11.86 11.86 FLA 1.21 1.17 1.17 Rated HP 0.16 0.14 0.14 Output 120 85 85 `Permissible limits of the voltage range at which the unit will operate satisfactorily. LEGEND FLA - Full Load Amps MCA- Minimum Circuit Amps MOCP - Maximum Over -Current Protection RLA - Rated Load Amps CONNECTION DIAGRAMS CONNECTING CABLE OUTDOOR TO INDOOR nauro�'sd0w�. Indoor Unite Nonpolar R 85 Power Su Iy communication Nonpolar R 485 Ta �40o Outdoor Unit communication POW Power Supply 208-230.1.60 1 Low volts a Low voltage I 208.230-1-60 Fig. 15 —Connection Diagrams NOTES: 1. Do not use the thermostat wire for any connection between indoor and outdoor units. 2. All connections between indoor and outdoor units must be as shown. The connections are sensitive to polarity and will result in a fault code. SYSTEM VACUUM AND CHARGE 7. The factory charge contained in the outdoor unit is good for up to 25 ft. (8 m) of line length. For refrigerant lines longer than 25 ft. (8 m), add refrigerant, up to the allowable length, as specified in the System Requirements section. 8. Disconnect the charge hose from the charge connection of the low side service valve. 9. Fully open service valves B and A. UNIT DAMAGE HAZARD 10. Securely tighten the service valve caps. Failure to follow this caution may result in equipment damage or improper operation. Outdoor Unit Refrigerant Indoor Unit Never use the system compressor as a vacuum pump. ig i e Refrigerant tubes and the indoor coil should be evacuated using the recommended 500 microns deep vacuum method. The alternate triple Service Valve evacuation method may be used if the procedure outlined below is Fig. 16 —Service Valve followed. NOTE: Always break a vacuum with dry nitrogen. Using Vacuum Pump 500 microns Y Y Low side valve O High side valve 1. Completely tighten flare nuts A, B, C, D, connect the manifold Charge hose gage charge hose to a charge port of the low side service valve (see Charge hose Fig. 16). ,Vacuum pump 2. Connect the charge hose to vacuum pump. 3. Fully open the low side of manifold gage (see Fig. 17). Low side valve 4. Start the vacuum pump. 5. Evacuate using either the deep vacuum or triple evacuation method. Fig. 17 — Manifold 6. After evacuation is complete, fully close the low side of manifold gage and stop the vacuum pump operation. 10 Specifications subject to change without notice. 38MBR-03SI Deep Vacuum Method Final Tubing Check The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the best way to assure a system is free of air and moisture (see Fig. 18). 3500 LEAK IN cn SYSTEM p 3000 L) 2500 2000 1500 VACUUM TIGHT TOO WET SYSTEM 0 1 2 3 4 5 6 7 MINUTES Fig. 18 — Deep Vacuum Graph Triple Evacuation Method The triple evacuation method should only be used when the vacuum pump is only capable of pumping down to 28 in. of mercury vacuum and the system does not contain any liquid water. Refer to Fig. 19 and proceed as follows: 1. Pump the system down to 28 in. of mercury and allow the pump to continue operating for an additional 15 minutes. 2. Close the service valves and shut off the vacuum pump. 3. Connect a nitrogen cylinder and regulator to the system and open until the system pressure is 2 psig. 4. Close the service valve and allow the system to stand for 1 hr. During this time, dry nitrogen can diffuse throughout the system absorbing moisture. 5. Repeat this procedure as indicated in Fig. 19. The system will then be free of any contaminants and water vapor. EVACUATE BREAK VACUUM WITH DRY NITROGEN WAIT EVACUATE BREAK VACUUM WITH DRY NITROGEN WAIT EVACUATE CHECK FOR TIGHT, DRY SYSTEM (IF IT HOLDS DEEP VACUUM) RELEASE CHARGE INTO SYSTE Fig. 19 — Triple Evacuation Method IMPORTANT: Check to be certain factory tubing on both the indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to the feeder tubes, making sure wire ties on feeder tubes are secure and tight. START-UP Test Operation Perform a test operation after completing a gas leak and electrical safety check. See the indoor unit installation instructions and owner's manual for additional start up information. System Checks 1. Conceal the tubing where possible. 2. Make sure that the drain tube slopes downward along its entire length. 3. Ensure all tubing and connections are properly insulated. 4. Fasten the tubes to the outside wall, when possible. 5. Seal the hole through which the cables and tubing pass. Outdoor Unit Are there unusual noises or vibrations during operation? Explain the Following Items to the Customer (with the aid of the Owner's Manual): 1. Explain care and maintenance. 2. Present the installation instructions to the customer. 38MBR-03SI Specifications subject to change without notice. l l OUTDOOR UNIT DIAGNOSTIC GUIDES For ease of service, the systems are equipped with a diagnostic code display LEDs on both the indoor and outdoor units. The outdoor diagnostic is displayed on the outdoor unit microprocessor board. There may be a few error codes displayed in the indoor unit that might relate to the outdoor unit's problems. If possible, always check the diag- nostic codes displayed on the indoor unit first. The diagnostic codes displayed on the outdoor units are listed on Table 11. Table 11 — Unit Diagnostic Guides DISPLAY LED STATUS E1 Communication malfunction between indoor and outdoor units. FO Protection of over - current F1 Open circuit or short circuit of outdoor ambient temperature sensor T4 F2 Open circuit or short circuit of condenser coil temperature sensor T3 F3 Open circuit or short circuit of Compressor discharge temperature sensorT5 F4 Outdoor unit EEPROM error F5 Outdoor fan speed has been out of control PO IPM malfunction P 1 Over voltage or over low voltage protection P2 High temperature protection of compressor top P3 Outdoor low temperature protection P4 Inverter compressor drive error P7 Outdoor IGBT temperature sensor error JO High temperature protection of indoor coil in heating 11 Outdoor temperature protection of outdoor coil in cooling J2 Discharge temperature protection J 3 Protection of active PFC module J4 Communication error between control board and IPM board 15 High - pressure switch protection J6 Low- pressure switch protection 18 AC voltage protection For additional diagnostic information, refer to the service manual. Copyright 2018 CAC/BDP • 3300 Riverwood Parkway Atlanta GA, 30339 Edition Date: 09/18 catalog No. 38MBR-03SI Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Replaces: 38MBR-02SI