RESUB 1 - FIR2021-0116+Fire_Alarm_Battery_Calculations+12.8.2021_3.46.25_PM+2561332FIR2021-0116
Honeywell
®SILENT'
GHT
IntelliKnight 6700 Battery Calcuiaiion
Secondary Power Source Requirements
Device ••
Standby Current (amps) Secondary Alarm Current (amps)
Qty Current Draw TotalTotal
1. Control Panel
6700 Control Panel 1 x 1 0.165000 1=1 0.165000 1 1 jxj 0.310000 1=1 0.310000
2. Addressable SLC Devices
SK-PHOTO (-T)
x
0.000300
=
x 0.000300
=
SK-PHOTO-W (-T)
6
x
0.000200
=
0.001200
6
x 0.000450
=
0.002700
SK-HEAT(-HT) (-ROR)
x
0.000300
=
x 0.000300
=
SK-HEAT-W(HT) (ROR)
x
0.000200
=
x 0.000450
=
SK-BEAM
x
0.002000
=
x 0.002000
=
SK-BEAM-T
x
0.002000
=
x 0.002000
=
SK-DUCT
x
0.000300
=
x 0.000300
=
SK-ACCLIMATE
x
0.000300
=
x 0.000300
=
SK-CONTROL
x
0.000375
=
x 0.000375
=
SK-MONITOR
x
0.000375
=
x 0.000375
=
SK-MINIMON
5
x
0.000375
=
0.001875
5
x 0.000375
=
0.001875
SK-PULL-SA
x
0.000375
=
x 0.000375
=
SK-PULL-DA
x
0.000375
=
x 0.000375
=
SK-MONITOR-2
x
0.000750
=
x 0.000750
=
SK-MON-10
x
0.003500
=
x 0.003500
=
SK-RELAY-6
x
0.001450
=
x 0.001450
=
SK-CONTROL-6
x
0.002250
=
x 0.002250
=
SK-RELAY
3
x
0.000255
=
0.000765
3
x 0.000255
=
0.000765
SK-RELAYMON-2
x
0.001300
=
x 0.024000
=
SK-ZONE
x
0.000270
=
x 0.000270
=
SK-ZONE-6
x
0.002000
=
x 0.002000
=
SK-FIRE-CO
x
1 0.000300
=
x 0.007200
=
3. SLC Accessory Bases
4. SLC Isolator Devices
5. Auxiliary Power Draw - SLC Devices
6. Accessory Modules
5860 1 1 jxj 0.020000 1=1 0.020000 1 1 1 x 1 0.025000 1=1 0.025000
7. Miscellaneous Devices
8. Notification Appliance Circuits
NAC 1
0.000000
=
0.237000
=
0.237000
NAC 2
0.000000
=
0.079000
=
0.079000
Total Standby Load
0.188840
Total Alarm Load
0.656340
RESUB
Dec 09 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
Page 1 12/8/2021
Honeywell
SILENT
KNIGHT
IntelliKnight 6700 Battery Calculation
Note 1: You are fully responsible for verifying these calculations.
Note 2: Use the dro downs in the yellow cells to enter values.
Calculation in Total Sheet
StandbyRequired
24 Hours
Standby Load Current
0.18884 Amps
x 24 =
4.532 AH
5 Minutes
Alarm Load Current Amps
0.65634 Amps
x 0.084 1 =
0.055 AH
Total Current Load
4.587 AH
Multiply by the Derating Factor 1.2 1 =
x 1.20
Total Ampere Hours Required
5.50 AH
Recommended Batteries: I BAT-1270 - 7AH Batteries
Battery Check
The batteries can be charged by the 6700 Charger.
The batteries can be housed in the 6700 Cabinet.
Circuit#1 current is within the limitations of the circuit.
Circuit#2 current is within the limitations of the circuit.
6700 Control Panel:
The output current is within the panel's limitations.
RESUB
Dec 09 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
Page 2 12/8/2021
Honeywell
SILENT'IntelliKnight 6700 Circuit Detail
NAC 1
Non-AlarmDevice Qty . . .
P2RK
3
x
0.000000
=
0.000000
3
x 0.079000
=
0.237000
x
0.000000
=
x 0.040000
=
x
0.000000
=
x 0.000000
=
x
0.000000
=
x 0.000000
=
x
0.000000
=
x 0.000000
=
x
1 0.000000
=1
X1 0.000000
=
x
0.000000
=
x 0.000000
=
x
0.000000
=
x 0.000000
=
x
0.000000
=
x 0.000000
=
x
0.000000
=
x 0.000000
=
Total
Standby Load
0.000000
Total Alarm Load
0.237000
NAC 2
Device e Qty Alarm Draw Total
P2RK
1
x
0.000000
=
0.000000
1
x 0.079000
=
0.079000
x
0.000000
=
x 0.000000
=
x
0.000000
=
x 0.000000
=
x
0.000000
=
x 0.000000
=
x
0.000000
=
x 0.000000
=
x
1 0.000000
=1
X1 0.000000
=
x
0.000000
=
x 0.000000
=
x
0.000000
=
x 0.000000
=
x
0.000000
=
x 0.000000
=
x
0.000000
=
x 0.000000
=
Total
Standby Load
0.000000
Total Alarm Load
0.079000
RESUB
Dec 09 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
Page 3 12/8/2021
Honeywell RESU B
SILENT'®r Intellil(night 6700 EOL Voltage Drop Dec 09 2021
CITY OF EDMONDS
BEYEEEIPMENT SERVICES
Starting Voltagel 20.4 Volts
Minimum Voltage @ EOL 16 Volts
Voltaoe DrOD Warnina % 10.00%
uurrent
I
Hcivai
rercem
Draw
Wire Type
Resistance
Length I
Resistance
Voltage @ EOL
Drop
Feet
Circuit Name
Amps
AWG
Ohms/1000 ft.
(One way)
Ohms
Volts
Percent
NAC 1
0.237
#14 Solid
3.07
140
0.86
20.20
1.00%
NAC 2
0.079
#12 Solid
1.93
55 1
0.21
20.38
0.08%
Resistance Table
Wire Type
Resitance
AWG
Ohms/1000 ft.
#10 Solid
1.21
#10 Stranded
1.24
#12 Solid
1.93
#12 Stranded
1.98
#14 Solid
3.07
#14 Stranded
3.14
#16 Solid
4.89
#16 Stranded
4.99
#18 Solid
7.77
#18 Stranded
7.95
Note: All Resistance values are taken from Table 8
Conductor Properties of the NFPA 70 National Electrical
Code. All values are for Direct Current Resistance at 75°C
(167°F).