Loading...
RESUB 1 - FIR2021-0116+Fire_Alarm_Battery_Calculations+12.8.2021_3.46.25_PM+2561332FIR2021-0116 Honeywell ®SILENT' GHT IntelliKnight 6700 Battery Calcuiaiion Secondary Power Source Requirements Device •• Standby Current (amps) Secondary Alarm Current (amps) Qty Current Draw TotalTotal 1. Control Panel 6700 Control Panel 1 x 1 0.165000 1=1 0.165000 1 1 jxj 0.310000 1=1 0.310000 2. Addressable SLC Devices SK-PHOTO (-T) x 0.000300 = x 0.000300 = SK-PHOTO-W (-T) 6 x 0.000200 = 0.001200 6 x 0.000450 = 0.002700 SK-HEAT(-HT) (-ROR) x 0.000300 = x 0.000300 = SK-HEAT-W(HT) (ROR) x 0.000200 = x 0.000450 = SK-BEAM x 0.002000 = x 0.002000 = SK-BEAM-T x 0.002000 = x 0.002000 = SK-DUCT x 0.000300 = x 0.000300 = SK-ACCLIMATE x 0.000300 = x 0.000300 = SK-CONTROL x 0.000375 = x 0.000375 = SK-MONITOR x 0.000375 = x 0.000375 = SK-MINIMON 5 x 0.000375 = 0.001875 5 x 0.000375 = 0.001875 SK-PULL-SA x 0.000375 = x 0.000375 = SK-PULL-DA x 0.000375 = x 0.000375 = SK-MONITOR-2 x 0.000750 = x 0.000750 = SK-MON-10 x 0.003500 = x 0.003500 = SK-RELAY-6 x 0.001450 = x 0.001450 = SK-CONTROL-6 x 0.002250 = x 0.002250 = SK-RELAY 3 x 0.000255 = 0.000765 3 x 0.000255 = 0.000765 SK-RELAYMON-2 x 0.001300 = x 0.024000 = SK-ZONE x 0.000270 = x 0.000270 = SK-ZONE-6 x 0.002000 = x 0.002000 = SK-FIRE-CO x 1 0.000300 = x 0.007200 = 3. SLC Accessory Bases 4. SLC Isolator Devices 5. Auxiliary Power Draw - SLC Devices 6. Accessory Modules 5860 1 1 jxj 0.020000 1=1 0.020000 1 1 1 x 1 0.025000 1=1 0.025000 7. Miscellaneous Devices 8. Notification Appliance Circuits NAC 1 0.000000 = 0.237000 = 0.237000 NAC 2 0.000000 = 0.079000 = 0.079000 Total Standby Load 0.188840 Total Alarm Load 0.656340 RESUB Dec 09 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Page 1 12/8/2021 Honeywell SILENT KNIGHT IntelliKnight 6700 Battery Calculation Note 1: You are fully responsible for verifying these calculations. Note 2: Use the dro downs in the yellow cells to enter values. Calculation in Total Sheet StandbyRequired 24 Hours Standby Load Current 0.18884 Amps x 24 = 4.532 AH 5 Minutes Alarm Load Current Amps 0.65634 Amps x 0.084 1 = 0.055 AH Total Current Load 4.587 AH Multiply by the Derating Factor 1.2 1 = x 1.20 Total Ampere Hours Required 5.50 AH Recommended Batteries: I BAT-1270 - 7AH Batteries Battery Check The batteries can be charged by the 6700 Charger. The batteries can be housed in the 6700 Cabinet. Circuit#1 current is within the limitations of the circuit. Circuit#2 current is within the limitations of the circuit. 6700 Control Panel: The output current is within the panel's limitations. RESUB Dec 09 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Page 2 12/8/2021 Honeywell SILENT'IntelliKnight 6700 Circuit Detail NAC 1 Non-AlarmDevice Qty . . . P2RK 3 x 0.000000 = 0.000000 3 x 0.079000 = 0.237000 x 0.000000 = x 0.040000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 1 0.000000 =1 X1 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 0.237000 NAC 2 Device e Qty Alarm Draw Total P2RK 1 x 0.000000 = 0.000000 1 x 0.079000 = 0.079000 x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 1 0.000000 =1 X1 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = Total Standby Load 0.000000 Total Alarm Load 0.079000 RESUB Dec 09 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Page 3 12/8/2021 Honeywell RESU B SILENT'®r Intellil(night 6700 EOL Voltage Drop Dec 09 2021 CITY OF EDMONDS BEYEEEIPMENT SERVICES Starting Voltagel 20.4 Volts Minimum Voltage @ EOL 16 Volts Voltaoe DrOD Warnina % 10.00% uurrent I Hcivai rercem Draw Wire Type Resistance Length I Resistance Voltage @ EOL Drop Feet Circuit Name Amps AWG Ohms/1000 ft. (One way) Ohms Volts Percent NAC 1 0.237 #14 Solid 3.07 140 0.86 20.20 1.00% NAC 2 0.079 #12 Solid 1.93 55 1 0.21 20.38 0.08% Resistance Table Wire Type Resitance AWG Ohms/1000 ft. #10 Solid 1.21 #10 Stranded 1.24 #12 Solid 1.93 #12 Stranded 1.98 #14 Solid 3.07 #14 Stranded 3.14 #16 Solid 4.89 #16 Stranded 4.99 #18 Solid 7.77 #18 Stranded 7.95 Note: All Resistance values are taken from Table 8 Conductor Properties of the NFPA 70 National Electrical Code. All values are for Direct Current Resistance at 75°C (167°F). Page 4 12/8/2021