Loading...
APPROVED BLD2022-0982+Pad & Pier Details+7.22.2022_5.32.22_PM+3007699STRUCTURAL NOTES: 1. DESIGN INFORMATION & LOADING: 1.1. BUILDING CODE IBC, 2018 EDITION, OSSC-2019 1.2. ROOF LIVE LOAD 30 PSF (SNOW), Is=1.0, Cf=1.15 1.3. FLOOR LIVE LOAD 50 PSF OR 2,000# CONC. (OFFICE) 1.4. WIND CRITERION 120 MPH, EXP C, Kzt=1.0 1.5. SEISMIC CRITERION SDS=1.200, le=1.0, SITE CLASS D, CATEGORY D 1.6. ASSUMED SOIL BEARING 1,500 PSF 1.7. WALL PLATE HEIGHT 9'-0" 1.8. ROOF SLOPE 2:12 OR FLATTER 2. CONCRETE: 2.1. DESIGN COMP.STRENGTH 2,500 PSI 2.2. REINF. YIELD 60 KSI 3. MASONRY: 3.1. 8x16x8 UNITS ASTM C-90, GRADE N 3.2. SET UNITS W/CORES VERTICAL & NO MORE THAN 3 HIGH, PER PLAN, WITHOUT SOLID GROUTING CORES. SOLID GROUTED CORES OVER OVER 5 HIGH REQUIRES SPECIFIC ENGINEERING. 4. WOOD: 4.1. ALL WOOD TO BE HEM -FIR STUD GRADE OR BETTER. 4.2. WOOD FRAMING AND SHEATHING WITHIN 6-INCHES OF GRADE TO BE PRETREATED FOR EXPOSURE TO MEET IBC 2015 2303.01.9. 4.3. CONNECTORS IN TREATED MATERIALS SHALL BE HOT -DIPPED GALVANIZED OR STAINLESS STEEL PER IBC 2015, 2304.10.5. 4.4. SET MODULAR BUILDING SUCH THATTHE FLOOR JOISTS ARE A MINIMUM OF 18-INCHES ABOVE FINISHED SUBGRADE BELOW BUILDING. 5. SPECIALTY ITEMS: ("MINUTE MAN PRODUCTS, Inc." (800) 438-7277 www.minutemanproducts.com, OR EQUIVALENT.) 5.1. METAL PIERS TO BE CAPABLE OF SUPPORTING 6,000# 5.2. HOLD-DOWNS SET IN SOIL AND LOOSE GRAVEL SHALL BE SOIL ANCHOR AUGAR-TYPE SET VERTICAL W/STABILIZER PLATE OR HEAD; OR DRIVEN ANCHOR W/ STABILIZER PLATE OR HEAD, W/ A MIN. DESIGN WORKING LOAD OF 3,150# AND AN ULTIMATE LOAD OF 4,725#. NUMBER OF ANCHORS AS INDICATED ON TABLE A. CORNER TIE -DOWNS TO BE WITHIN 3'-0" OF THE BUILDING CORNER. TIE -DOWNS OTHER THAN AT THE CORNERS SHALL BE SPACED EQUALLY. EACH INDIVIDUAL EQUALLY SPACED TIE -DOWN SHALL BE WITHIN 4'-0" OF THE EQUAL SPACING. 5.3. TIE -DOWNS TO STABLE CONCRETE SHALL BE EITHER A MMA-I8-THDLS FOR PRE -POURED CONCRETE OR A MMA-42-210-PDH POUR INTO THE CONCRETE. NUMBER OF ANCHORS PER 5.4. TIE -DOWNS SET IN AN ASPHALT ROADWAY OR PARKING AREA SHALL BE "ROCK -TYPE" ANCHORS 5.5. INSTALL GROUND PORTION OF THE ANCHOR PRIOR TO SETTING THE BUILDING. CONNECT ANCHOR TIES TO BUILDING ONLY AFTER BUILDING IS FULLY BLOCKED AND LEVELED. 5.6. INSTALL ALL SPECIALTY ITEMS PER THE MANUFACTURER'S RECOMMENDATIONS. SEE INSTALLATION INSTRUCTION MANUAL. 4. VENTING: 4.1. PROVIDE UNDER FLOOR VENTILATION PER IBC CODE AND LOCAL REQUIREMENTS AT 1 NET SF OF VENTILATION PER 150 SF OF FLOOR AREA. 4.2. IF A SUITABLE VAPOR RETARDER IS INSTALLED THE RATIO MAY BE INCREASED TO Y15oo, IF ACCEPTABLE TO THE LOCAL BUILDING OFFICIAL. 6. ACCESS: 6.1. PROVIDE ACCESS TO THE UNDER FLOOR AREA PER THE CODE. 6.2. PROVIDE 12" MIN. CLEARANCE FROM SOIL TO UNDERSIDE OF ALL BUILDING SUPPORT MEMBERS. 7. SITE CONDITIONS: 7.1. FOUNDATION SUBGRADE TO BE UNDISTURBED NATIVE SOILS OR STRUCTURAL FILL, COMPACTED TO 95% OF THE STANDARD PROCTOR DENSITY PER ASTM D-698. 7.2. SLOPE FINISHED GRADE AWAY FROM THE BUILDING FOUNDATION AT A MIN. GRADE OF 5% FOR THE FIRST 10-FEET AND 2% THEREAFTER TO A SUITABLE DISCHARGE. ,�Typ) LENGTH OF UNIT mn M 00 IILjII 11-11 PADS & PIERS, NO. REQUIRED PER TABLE A — SEE DETAIL Al & A2/D1 SPACED EQUALLY ANCHOR HOLD—DOWNS, SEE DETAIL B1 & B2/D1, SPACED EQUALLY BETWEEN CORNERS 1 12' WIDE MODULAR FOUNDATION PLAN SCALE: 1 /8" = 1'-0" TABLE A MODULE RAIL PIER/PAD SPACING INSTALL PIER/PADS UNDER CHASSIS, SPACED EQUALLY BETWEEN CORNER PIERS INSTALL HOLD-DOWNS, SPACED EQUALLY BETWEEN CORNER HOLD-DOWNS LENGTH OF UNIT # PADS & PIERS # HOLD-DOWN ANCHORS EACH SUPPORT RAIL EA.SIDE EA.END 32'-0" 8 3 2 40'-0" 10 4 2 42'-0" 10 4 2 44'-0" 11 4 2 48'-0" 11 4 2 56'-0" 13 5 3 60'-0" 14 5 3 RECEIVED Aug 01 2022 CITY OF EDMONDS DEVELOPMENT SERVICES BLD2022-0982 DEPARTMENT The following documentation shall be available on site for the building inspector: ❑3COE APPROVED ARCHITECTURAL PLAN SET ■ R COE APPROVED STRUCTURAL PLAN SET ❑ COE REVIEWED CALCULATION PACKET = [:]ENERGY CREDIT WORKSHEET ■ SITE PLAN ❑ CIVIL PLAN = ❑ N N ■ o El N ■ � y z ■ CITY OF EDMONDS BUILDING DEPARTMENT 2021 , y Q Yj m F- 0 0 U) O 0 0cn APPROVED BY CITY OF U J EDMONDS BUILDING o DIVISION Aug 23 2022 w m w F o Ln U Ln F z �, l7 (D o co F Z 83 SS N w p T� S z m =" 1NE Q a LU w G � 3 � G 11 RENEWS I RENEWS: DECEMBER 31, 202311 RENEWS 9 27 2023 "DIAL STRAP OR kBLE WITH TURN -BUCKLE ) APPROVED ANCHOR )DULE SUPPORT BEAM Ix4"x6" SHIMS AP WITH NO MORE THAN ?) 2"X8"X16" PT PLATES R (1)-4"X8"X16" CMU 8"x8"x16" CMU (1)-4"X16"X16" CONC. OR 16"x16" ABS OR 2x12 - 24" LONG PT. WOOD A CMU PIER N.T.S. METAL STRAP PER SOIL ANCHOR MANUFACTURER WITH TURN BUCKLE TO APPROVED ANCHOR MODULE SUPPORT BEAM PREFABRICATED METAL PIER 16%16" MIN. FTC. PAD, CONC, ABS, OR 2x12 - 24" LONG PT. WOOD v A2 PAD & PIER N.T.S. IDULE SUPPORT BEAM STRAP W/GATOR CLAMP OR EQUIVALENT ANCHORAGE 1:i�ly:[Ila9�:a�r:1►t'��N�IZ.y SOIL ANCHOR-ENDWALL N.T.S. Ib[1D1111q Id@12" O.C. (TYP. 2 LINES) x6 CEDAR TRIM OR METAL T DRIP 10 @ 2'-0" O.C., TOE -NAILED T&B ;KIRTING MATERIAL 2x4 P.T. PLATE %"05" REBAR ANCHOR @ 48"O.C. MAX. DRIVEN 12" INTO THE GROUND C 1 SKIRTING DETAIL-NONBEARING NTS. MODULE SUPPORT BEAM GALV. STEEL STRAP PER ANCHOR MANUFACTURER ANCHOR PER PLAN & NOTES B 2 SOIL ANCHOR-SIDEWALL N. T. S. RECEIVED Aug 01 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT r7NNECTTOP PLATE MODULE W/ 16d 12" O.C.. MIL WATER -PROOF EET 0/ 2x4 TRT,WD, 4MING W/1/2" CDX T. SHEETING & GALV. NNECTORS. FLASH 'ER EXPOSED SHEET x15" REBAR @ 32" SECURING 2x4 4TE TO SOIL C 2 SKIRTING DETAIL -STRUCTURAL PITSET 11 RENEWS 9 30 2022 RENEWS: DECEMBER 31, 2023 FF�RENEWS 9 27 2023 zN N o N y c z :30 (� ` 0 0 < V) p 0 g � U O o �0 o N� ~ N w ao w U N z�� (n ::) 0 ',E9 (D oWm m \ Ua3 Q H a LU z � 3 G