ENG CORRECTION NOTICE 1.12.2023CITY OF EDMONDS of ED4o CORRECTION NOTICE 1P ENGINEERING DIVISION (425) 771-0220 City Website: www.edmondswa.gov �Sr. 1 gqo BLD2021-13 84/ DATE: January 12, 2023 PERMIT NUMBER: ENG2022-0208 OWNER: Port of Edmonds SITE CONTACT: Mike Linn ADDRESS: 471 Admiral Way TYPE OF INSPECTION: ROW — Storm Main ❑ WORK DESCRIBED BELOW HAS BEEN INSPECTED AND APPROVED ❑ APPROVED PLANS AND PERMIT JOB CARD MUST BE AVAILABLE TO INSPECTOR ON SITE ® CORRECTIONS LISTED BELOW MUST BE MADE BEFORE WORK CAN BE APPROVED AND/OR THE NEXT PHASE OF WORK IS STARTED. ® RECALL FOR INSPECTION ❑ REINSPECTION FEE MUST BE PAID PRIOR TO NEXT INSPECTION REQUEST. ❑ STOP WORK UNTIL AUTHORIZED TO CONTINUE BY CITY INSPECTOR Upon inspection, it was determined that the proposed storm main crossing Admiral Way is in conflict with the City water main as currently constructed. Submit a revision to the plans addressing the following comments: 1. The entire on -site system will need to be shallower to make grade in the right-of-way. 2. The storm main will need to be shown going over the water main. 3. Provide grades and invert elevations for all down- and upstream structures. 4. Pothole for all utilities and provide grades and invert elevations. If the connection to the storm system needs to be revised to tie into the catch basin (CB 7-194) instead of the manhole (MH 7-915), revise the plans accordingly. Backfill and pave the trench across Admiral Way in the meantime. Steel plates will not be approved. THE ACTIONS OR CORRECTIONSINDICATED ABOVE ARE REQUIRED TO BE CORRECTED. FOR INSPECTION SCHEDULE THROUGH mybuildingpermit.com Inspector: _ Natalie Griggs Date: January 12, 2023