HEAT PUMP OUTDOOR UNITS L ENVNI 7x RES/DENT/AL PROD UC T SPEC/FICA TONS EL16XP1 ELITE° Series R-410A - 60 Hz Bulletin No. 210880 January 2023 Supersedes September 2022 00 ELITE @ SERIES LENNOX QUANTUM" COIL SEER up to 17.00 HSPF up to 9.80 1.5 to 5 Tons Cooling Capacity - 18,000 to 58,500 Btuh Heating Capacity - 16,900 to 56,000 Btuh MODEL NUMBER IDENTIFICATION Product Tier------� Revision Number EL = Elite`p Series ' -- Ratings Revision Letter - Voltage Refrigerant Type ----- 230 = 208/23OV-1 ph-60Hz X = R-410A ----- Nominal Cooling Capacity 018 = 1.5 tons Unit Type -----� 024=2tons P = Heat Pump Outdoor Unit 030 = 2.5 tons 036 = 3 tons Cooling Stages ---- 042=3.5tons 1 = Single Stage Compressor 048 = 4 tons 060 = 5 tons FEATURE HIGHLIGHTS 00 CONTENTS 1. Outdoor Coil Fan 2. Quantum'" Coil 3. High Pressure Switch 4. Expansion Valve - Outdoor Unit 5. Four -Way Reversing Valve 6. High -Capacity Liquid Line Drier 7. Scroll Compressor 8. Compressor Sound Dampening System 9. Defrost Control 10. Heavy Gauge Steel Cabinet 11. SmartHingeT" Louvered Coil Protection 12. Refrigerant Line Connections Approvals And Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Controls...........................................................8 Dimensions........................................................11 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Features...........................................................3 Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Installation Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Model Number Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Optional Accessories - Order Separately . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 SoundData........................................................10 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 TXV Substitution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 TXVUsage.........................................................12 EL16XP1 - 1.5 to 5 Ton Heat Pump / Page 2 APPROVALS AND WARRANTY APPROVALS • AHRI Certified to AHRI Standard 210/240 • For AHRI Certified system match -ups and expanded ratings, visit www.LennoxPros.com • ENERGY STAR° certified • Sound rated to AHRI Standard 270-2008 test conditions • Tested in the Lennox Research Laboratory environmental test room • Rated According to U.S. Department of Energy (DOE) test procedures • Units and components UL, NEC, and CEC bonded for grounding to meet safety standards for servicing • ETL certified (U.S. and Canada) • ISO 9001 Registered Manufacturing Quality System WARRANTY • Compressor: • Limited ten years in residential installations • Limited five years in non-residential installations • All other covered components: • Limited five years in residential installations • Limited one year in non-residential installations NOTE - Refer to Lennox° Basic Limited Warrenty at www.Lennox.com for additional details. FEATURES APPLICATIONS • 1.5 through 5 tons • Sound levels as low as 71 dBA • Single phase power supply • Vertical air discharge • Applicable to indoor air handlers or gas furnaces with indoor add -on coils • Shipped completely factory assembled, piped and wired • Factory test operated NOTE - When heat pumps are used with gas furnaces, a dual -fuel compatible thermostat or a zone control system with dual -fuel capabilities must be used (order separately) NOTE - Installer must set outdoor unit, connect refrigerant lines and make electrical connections to complete job REFRIGERATION SYSTEM R-410A Refrigerant • Non -chlorine, ozone friendly • Unit is factory pre -charged NOTE - Total system refrigerant charge is dependant on outdoor unit size, indoor unit size and refrigerant line length. NOTE - Refer to the unit -mounted charging sticker to determine correct amount of charge required. OOutdoor Coil Fan • Direct drive fan • EL16XP1-036-042-048-060 models have a variable - speed outdoor fan motor for quiet operation • Vertical air discharge • Ball bearings • Inherently protected • Totally enclosed fan motor • Fan guard constructed of corrosion -resistant PVC (polyvinyl chloride) coated steel © QuantumT" Coil • Lennox designed and fabricated coil • Enhanced aluminum alloy tube/enhanced fin coil • Ripple -edged aluminum fins • Aluminum tube construction • Lanced fins for maximum fin surface exposure • Fin collars grip tubing for maximum contact area • Flared shoulder tubing connections • Factory tested under high pressure • Entire coil is accessible for cleaning EL16XP1 - 1.5 to 5 Ton Heat Pump / Page 3 FEATURES REFRIGERATION SYSTEM (continued) © High Pressure Switch • Protects the system from high pressure conditions that can be a result of fan failure or a blocked/dirty coil • Automatic reset Low Pressure Switch • Shuts off unit if suction pressure falls below setting • Provides loss of charge and freeze-up protection • Automatic reset OExpansion Valve - Outdoor Unit • Designed and sized for heat pump systems • Sensing bulb senses evaporator suction temperature during heating cycle © Four -Way Reversing Valve • Rapid changeover of refrigerant flow direction from cooling to heating and vice versa • Operates on pressure differential between outdoor unit and indoor unit of the system • Factory installed 0 High -Capacity Liquid Line Drier • Factory installed in the liquid line • Drier traps moisture or dirt • 100% molecular -sieve, bead type, bi-flow drier Optional Accessories Check/Expansion Valve Kits • Field installed on certain indoor units • SeeTXV Usage table • Chatleff style fitting Loss of Charge Kit • Helps protect the compressor from damage due low refrigerant charge conditions • SPST, normally -closed switch, automatic reset switch Freezestat • Installs on or near the vapor line of the indoor coil or on the suction line • Senses suction line temperature • Cycles compressor off when suction line temperature falls below it's setpoint • Opens at 29°F and closes at 58°F • Installs on or near the discharge line of the evaporator or on the suction line Refrigerant Line Kits • Refrigerant lines are shipped refrigeration clean • Lines are cleaned, dried, pressurized and sealed at factory • Suction line fully insulated • Lines are stubbed at both ends EL16XP1 - 1.5 to 5 Ton Heat Pump / Page 4 FEATURES COMPRESSOR © Scroll Compressor • High efficiency with uniform suction flow • Constant discharge flow, high volumetric efficiency and quiet operation • Low gas pulses during compression reduces operational sound levels • Compressor motor is internally protected from excessive current and temperature • Muffler in discharge line reduces operating sound levels Compressor is installed in the unit on resilient rubber mounts for vibration free operation Scroll Compressor Operation • Two involute spiral scrolls matched together generate a series of crescent -shaped gas pockets between them • During compression, one scroll remains stationary while the other scroll orbits around it • Gas is drawn into the outer pocket, the pocket is sealed as the scroll rotates • As the spiral movement continues, gas pockets are pushed to the center of the scrolls. Volume between the pockets is simultaneously reduced • When the pocket reaches the center, gas is now at high pressure and is forced out of a port located in the center of the fixed scrolls • During compression, several pockets are compressed simultaneously resulting in a smooth continuous compression cycle • Continuous flank contact, maintained by centrifugal force, minimizes gas leakage and maximizes efficiency • Compressor is tolerant to the effects of slugging and contaminants. If this occurs, scrolls separate, allowing liquid or contaminants to be worked toward the center and discharged CONTROLS ODefrost Control • Control furnished as standard • Gives a demand defrost cycle whenever system heating performance falls below optimum levels. The sensing element on coil determines when defrost cycle is required and when to terminate cycle • Anti -short cycle (5 minutes) incorporated into the board • Diagnostic LEDs furnished as an aid in troubleshooting • Conveniently located in control box Optional Accessories Compressor Low Ambient Cut -Off • Non-adjustable switch (low ambient cut-out) prevents compressor operation when outdoor temperature is below 35°F Compressor Hard Start Kit • Single-phase units are equipped with a PSC compressor motor • This type of motor normally does not need a potential relay and start capacitor • In conditions such as low voltage, kit may be required to increase the compressor starting torque Indoor Blower Off Delay Relay • Delays the indoor blower -off time during the cooling cycle. See AHRI System Matches for usage Low Ambient Kit • Heat pump in the cooling mode will operate satisfactorily down to 45°F outdoor air temperature without any additional controls • Allows unit to operate properly down to 30°F in the cooling mode NOTE - Crankcase heater (optional for-018-024-030 models) and Freezestat should be installed on compressors equipped with a low ambient kit. NOTE - A compressor lock -out thermostat should be added to terminate compressor operation below recommended operation conditions. Compressor Crankcase Heater Monitor Kit - Service Light (Factory Installed on-036-042-048-060) • Ambient compensating thermistor • Protects against refrigerant migration that can occur • Service light thermostat during low ambient operation • For thermostats requiring indicator light inputs Compressor Sound Dampening System • Polyethylene compressor cover • 2-inch thick batt of fiberglass insulation • Hook and loop fastening tape on all open edges Optional Accessories Compressor Crankcase Heater (Optional for-018-024-030 models) • Protects against refrigerant migration that can occur during low ambient operation EL16XP1 - 1.5 to 5 Ton Heat Pump / Page 5 FEATURES CONTROLS (continued) Optional Accessories (continued) E30 Smart Wi-Fi Thermostat • Wi-Fi enabled, electronic 7-day, universal, multi -stage, programmable, touchscreen thermostat • 3 Heat/2 Cool • Auto -changeover • Controls dehumidification during cooling mode and humidification during heating mode • Offers enhanced capabilities including humidification / dehumidification / dewpoint measurement and control, Humiditrol° control, and equipment maintenance reminders • Easy to read 7 in. color touchscreen (measured diagonally) • LCD display with backlight shows the current and set temperature, time, inside relative humidity, system status (operating mode and schedules) and outside temperature (optional outdoor sensor required) • Smooth Setback Recovery starts system early to achieve setpoint at start of program period • Compressor short -cycle protection (5 minutes) • Up to four separate schedules are available plus Schedule IQTM • One -Touch Away Mode - A quick and easy way to set the cooling and heating setpoints while away • Smart AwayTM - Uses geo-fencing technology to determine when the homeowner is within a predetermined distance from the home to operate the system when leaving, away and arriving • Wi-Fi remote monitoring and adjustment through a home wireless network for desktop PCs, laptops and apps for smartphones or tablets • Smart home automation compatible with Apple HomeKitTM, Amazon Alexa°, Google Assistant and IFTTT • Service Dashboard features online real-time monitoring of installed Lennox° thermostats • High Definition Color Display with Subbase, Smart Hub Controller, wallplate (for retrofit installations) furnished for easy installation • See the Lennox° E30 Smart Wi-Fi Thermostat Product Specifications bulletin for more information Remote Outdoor Temperature Sensor • Used with the Lennox° E30 Smart Thermostat • When installed outdoors, sensor allows thermostat to display outdoor temperature • Sensor is auto -detected when connected to thermostat NOTE - Sensor is required for high and low balance points option. NOTE - Sensor is required for Enhanced Dehumidification Accessory (EDA). Thermostat • Thermostat is not furnished with unit • See Lennox Price Book for selection Mild Weather Kit • Heat pump units operate satisfactorily in the heating mode at outdoor air temperatures up to 75°F • Allows heating operation above 75°F Outdoor Thermostat Kit • Outdoor thermostat locks out some of the electric heating elements on indoor units where two -stage control is applicable • Outdoor thermostat maintains the heating load on the low power input as long as possible before allowing the full power load to come on the line • Thermostat kit and Mounting Box must be ordered separately EL16XP1 - 1.5 to 5 Ton Heat Pump / Page 6 FEATURES 4) CABINET • Heavy -gauge steel construction • Pre -painted cabinet finish • Control box is conveniently located with all controls factory wired • Corner patch plate allows compressor access • Drainage holes are provided in base section for moisture removal • Drainage holes are provided in base section • High density polyethylene unit support feet raise the unit off of the mounting surface PermaGuardTM Unit Base • Durable zinc -coated base section resists rust and corrosion GoSmartHingeT' Louvered Coil Protection • Steel louvered panels provides complete coil protection • Panels are hinged to allow easy cleaning and servicing of coils. Panels may be completely removed • Interlocking tabs and slots assure tight fit on cabinet Refrigerant Line Connections, Electrical Inlets and Service Valves ®• Sweat connection vapor and liquid lines • Vapor valve can be fully shut off, while liquid valve may be front seated to manage refrigerant charge while servicing system • Refrigerant line connections and field wiring inlets are located in one central area of the cabinet • See dimension drawing Optional Accessories Snow Guard • For use in locations where the possibility of heavy snow or freezing rain accumulation may occur • Heavy gauge powder coated steel guard • Deflects snow and ice away from the outdoor fan NOTE - Snow Guards for 018-024-030 models are only available in Canada. EL16XP1 - 1.5 to 5 Ton Heat Pump / Page 7 SPECIFICATIONS General Model No. Data Nominal Tonnage EL16XP1-018 EL16XP1-024 EL16XP1-030 EL16XP1-036 1.5 2 2.5 3 Sound Rating Number (dBA) 71 72 72 72 Connections Liquid line OD - in. (sweat) Suction line OD - in. 3/8 3/8 3/8 3/8 3/4 3/4 3/4 7/8 Refrigerant 2 R-410A charge furnished 6 lbs. 6 oz. 6 lbs. 11 oz. 7 lbs. 10 oz. 8 lbs. 7 oz. Outdoor Net face area - sq. ft. Outer coil Coil Inner coil Tube diameter - in. No. of rows Fins per inch 24.5 18.7 18.7 22.2 - - - 18.0 18.0 21.5 5/16 5/16 5/16 5/16 1 2 2 2 22 22 22 22 Outdoor Diameter - in. Fan No. of blades Motor hp Cfm Rpm Watts 22 22 22 26 3 3 3 3 1/6 1/6 1/6 1/3 2670 2575 2575 3700 867 866 866 820 160 163 163 200 Shipping Data - lbs. 1 pkg. 213 211 211 214 ELECTRICAL DATA Line voltage data - 60 Hz 208/23OV-1 ph 208/23OV-1 ph 208/23OV-1 ph 208/23OV-1 ph 3 Maximum overcurrent protection (MOCP) amps 20 20 25 35 ° Minimum circuit ampacity (MCA) 12.2 13.6 16.4 20.9 Compressor Rated load amps Locked rotor amps Power factor 9 10.1 12.3 14.7 48 52 63 75 0.98 0.98 0.96 0.99 Outdoor Fan Motor Full load amps Locked rotor amps 1.0 1.0 1.0 2.6 1.9 1.9 1.9 --- CONTROLS E30 Smart Wi-Fi Thermostat 20A65 Remote Outdoor Temperature Sensor X2658 OPTIONAL ACCESSORIES - ORDER SEPARATELY Compressor Crankcase Heater 93M04 Factory Compressor Hard Start Kit LG 88M91 Compressor Low Ambient Cut -Off 45F08 Freezestat 3/8 in. tubing 93G35 5/8 in. tubing 50A93 Indoor Blower Off Delay Relay 58M81 Loss of Charge Switch Kit 84M23 6 Low Ambient Kit 54M89 Mild Weather Kit 111397 Monitor Kit - Service Light 76F53 Outdoor Thermostat Kit Thermostat 1 OZ23 Mounting Box 31461 Refrigerant 3/8 x 3/4 x 3/8 - 20 ft. 89J56 Line Sets 3/8 x 3/4 x 3/8 - 30 ft. 89J57 (Liq. x Suc. OD x 3/8 x 3/4 x 3/8 - 40 ft. 89J58 Insulation Thickness 3/8 x 3/4 x 3/8 - 50 ft. 89J59 - Length) 3/8 x 7/8 x 3/8 - 30 ft. 89J60 3/8 x 7/8 x 3/8 - 40 ft. 89J61 3/8 x 7/8 x 3/8 - 50 ft. 89,162 6 Snow Guard 35-1/2 x 31 in. (Canada Only) X8780 NOTE -Extremes of operating range are plus 10% and minus 5% of line voltage. Sound Rating Number rated in accordance with test conditions included in AHRI Standard 270. 2 Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the Installation Instructions for information about line set length and additional refrigerant charge required. HACR type breaker or fuse. Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. e Crankcase Heater and Freezestat are recommended with Low Ambient Kit. s Add 11-1/2 inches (292 mm) to unit height. EL16XP1 - 1.5 to 5 Ton Heat Pump / Page 8 SPECIFICATIONS General Model No. Data Nominal Tonnage EL16XP1-042 EL16XP1-048 EL16XP1-060 3.5 4 5 Sound Rating Number (dBA) 73 73 73 Connections Liquid line OD - in. (sweat) Suction line OD - in. 3/8 3/8 3/8 7/8 7/8 1-1/8 Refrigerant 2 R-410A charge furnished 10 lbs. 12 oz. 10 lbs. 7 oz. 10 lbs. 4 oz. Outdoor Net face area - sq. ft. Outer coil Coil Inner coil Tube diameter - in. No. of rows Fins per inch 29.1 29.1 29.1 28.2 28.2 28.2 5/16 5/16 5/16 2 2 2 22 22 22 Outdoor Diameter - in. Fan No. of blades Motor hp Cfm Rpm Watts 26 26 26 3 3 4 1/3 1/3 1/3 4150 4150 4250 820 820 820 216 216 245 Shipping Data - lbs. 1 pkg. 294 294 300 ELECTRICAL DATA Line voltage data - 60Hz 208/23OV--1 ph 208/23OV--1 ph 208/23OV--1 ph 3 Maximum overcurrent protection (MOCP) amps 40 40 50 Minimum circuit ampacity (MCA) 25 25.8 30.4 Compressor Rated load amps Locked rotor amps Power factor 15.9 18.5 22.2 112.3 124 127.9 0.99 0.99 0.99 Outdoor Fan Motor Full load amps 2.6 2.6 2.6 CONTROLS E30 Smart Wi-Fi Thermostat 20A65 Remote Outdoor Temperature Sensor X2658 1 OPTIONAL ACCESSORIES - ORDER SEPARATELY Compressor Hard Start Kit Compressor Low Ambient Cut -Off Copeland LG 1OJ42 88M91 45F08 Freezestat 3/8 in. tubing 5/8 in. tubing 93G35 50A93 Indoor Blower Off Delay Relay 58M81 Loss of Charge Switch Kit 84M23 5 Low Ambient Kit 541VI89 Mild Weather Kit 111397 Monitor Kit - Service Light 76F53 Outdoor Thermostat Kit Thermostat Mounting Box 1 OZ23 31461 Refrigerant Line Sets (Liq. x Suc. OD x Insulation Thickness - Length) 3/8 x 7/8 x 3/8 - 30 ft. 3/8 x 7/8 x 3/8 - 40 ft. 3/8 x 7/8 x 3/8 - 50 ft. 3/8 x 1-1/8 x 3/8 - 30 ft. 3/8 x 1-1/8 x 3/8 - 50 ft. 89,160 89,161 89J62 X0570 731391 s Snow Guard 39-1/2 x 35-5/8 in. Y1033 NOTE -Extremes of operating range are plus 10°% and minus 5% of line voltage. Sound Rating Number rated in accordance with test conditions included in AHRI Standard 270. Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the Installation Instructions for information about line set length and additional refrigerant charge required. s HACR type breaker or fuse. ° Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. s Crankcase Heater and Freezestat are recommended with Low Ambient Kit. 6Add 11-1/2 inches (292 mm) to unit height. EU 6XP1 - 1.5 to 5 Ton Heat Pump / Page 9 SOUND DATA ' Unit Model Octave Band Sound Power Levels dBA, re 10-12 Watts Center Frequency - HZ 1 Sound Rating Number (dBA) 2 Estimated Sound Pressure Level at Distance From Unit (dBA at distance in ft.) 125 250 500 1000 2000 4000 8000 3 5 10 15 50 018 56.5 62 65.5 66.5 62.5 59.5 52 71 64 59 53 50 39 024 54.5 62 67.5 67.5 63 58 50.5 72 65 60 54 51 40 030 54.5 62 67.5 67.5 63 58 50.5 72 65 60 54 51 40 036 56 61 66.5 65.0 62 57 49 72 65 60 54 51 40 042 57 62.5 68.5 67.5 65 59 50.5 73 66 61 55 52 41 048 57 62.5 68.5 67.5 65 59 50.5 73 66 61 55 52 41 060 54.5 60.5 66.5 68 65 61 56 73 66 61 55 52 41 NOTE - the octave sound power data does not include tonal correction. Tested according to AHRI Standard 270-2008 test conditions. z Estimated sound pressure level at distance based on AHRI Standard 275-2010 method for equipment located on the ground, roof, or on side of building wall with no adjacent reflective surface within 9.8 feet. Sound pressure levels will increase based on changes to assumptions. For other applications, refer to AHRI Standard 275. FIELD WIRING rDISC � � � SWITCH SWITCH I (By Others) I _ — — J r-----, OPTIONAL B O A -Two Wire Power (see Electrical Data) I ELHEATIC ----I DISCONNECT I B - Two or Three Wire Power (size to heater capacity) r I I --� SWITCH i—(— Others) C - Twelve Wire Low Voltage 18 ga. minimum OUTDOOR ITHERMOSTATI Fourteen Wire Low Voltage with Optional Outdoor �— — — — —� LENNOX INDOOR UNIT rI THERMOSTAT Thermostat (Optional)—� D - Eight Wire Low Voltage 18 ga. minimum LENNOX Y _ Ten Wire Low Voltage with Optional Outdoor Thermostat OUTDOOR UNIT O NOTE - Field Wiring Not Furnished All wiring must conform to NEC or CEC and local electrical codes. INSTALLATION CLEARANCES NOTES: Service clearance of 30 in. (762 mm) must be maintained on one of the sides adjacent to the control box. Clearance to one of the other three sides must be 36 in. (914 mm) Clearance to one of the remaining two sides may be 12 in. (305 mm) and the final side may be 6 in. (152 mm). A clearance of 24 in. (610 mm) must be maintained between two units. 48 in. (1219 mm) clearance required on top of unit. See NOTES -r Control See NOTES Box EL16XP1 - 1.5 to 5 Ton Heat Pump / Page 10 DIMENSIONS r TOP VIEW C (Depth) DISCHARGE AIRt� SIDE VIEW UNIT � SUPPORT FEET \ / VAPOR LINE CONNECTION LIQUID LINE CONNECTION LIQUID LINE CONNECTION ELECTRICAL INLETS VAPOR LINE jCONNECTION 4-3/4 4-1/4 (108) (121) • 0 13-7/8 0 0 0 20-5/8 (352) (524) 1 .� on 7-3/4 (197) (1/2 114) 3-1/4 27-1/8 3-5/8 (83) (689) (92) EL16XP1-018 TO -030 BASE SECTION (Medium Base) A 1 (25) END VIEW UNIT SUPPORT FEET t ov 16-7/8 26-7/8 (429) 0 0 0 (683) 8-3/4 (222) 3-3/4 (95) 3-1/8 30-3/4 (781) 4-5/8 (79) (117) EL16XP1-036 TO -060 BASE SECTION (Large Base) Model No. A in. mm B in. mm C in. mm EL16XP1-018 45 1143 30-1/2 775 35 889 EL16XP1-024 35 889 30-1/2 775 35 889 EL16XP1-030 35 889 30-1/2 775 35 889 EL16XP1-036 35 889 35-1/2 902 39-1/2 1003 EL16XP1-042 45 1143 35-1/2 902 39-1/2 1003 EL16XP1-048 45 1143 35-1/2 902 39-1/2 1003 EL16XP1-060 45 1143 35-1/2 902 39-1/2 1003 EL16XP1 - 1.5 to 5 Ton Heat Pump / Page 11 TXV USAGE TXV SUBSTITUTION Use this table for C35, CH23 and CR33 Field Installed TXV Match -Ups Model No. Order No. EL16XP1-018 12J18 EL16XP1-024 12J18 EL16XP1-030 12J18 EL16XP1-036 12J19 EL16XP1-042 I12J20 EL16XP1-048 I12J20 EL16XP1-060 I12J20 CX35 and CHX35 coils and all Lennox air handlers are shipped with a factory installed TXV. C35 coils - Replace the factory installed RFC orifice with the expansion valve listed. CH23 and CR33 - Use the expansion valve listed. MOST POPULAR MATCHES Outdoor Unit Indoor Unit Model No. Model No EL16XP1-018 CBA27UHE-018 EL16XP1-024 CBA27UHE-024 EL16XP1-030 CBA27UHE-030 EL16XP1-036 CBA27UHE-036 EL16XP1-042 CBA27UHE-048 EL16XP1-048 CBA27UHE-048 EL16XP1-060 CBA27UHE-060 AHRI STANDARD 210/240 Cooling or heating capacities are net values, including the effects of blower motor heat, and do not include supplementary heat. Power input is the total power input to the compressor(s) and fan(s), plus any controls and other items required as part of the system for normal operation. Units which do not have an indoor air -circulating blower furnished as part of the model, i.e., split system with indoor coil only, is established by subtracting from the total cooling capacity 1250 Btu/h per 1,000 cfm, and by adding the same amount to the heating capacity. Total power input for both heating and cooling is increased by 365 W per 1,000 cfm of indoor air circulated. A general guide for replacing the factory installed TXV if the indoor unit (coil/air handler) is larger or smaller than the outdoor unit. Outdoor Unit Indoor Unit TXV Furnished TXV Replacement Size Tons Size Tons 018 1.5 30/36 2.5/3 12J19 12J18 018 1.5 36 3 12J19 12J18 018 1.5 42 3.5 12J20 12J18 018 1.5 48 4 12J20 12J18 018 1.5 49 4 12J20 12J18 018 1.5 50/60 4/5 12J20 12J18 018 1.5 51 /61 4/5 12J20 12J18 018 1.5 60 5 12J20 12J18 024 2 42 3.5 12J20 12J18 024 2 48 4 12J20 12J18 024 2 49 4 12J20 12J18 024 2 50/60 5 12J20 12J18 024 2 51/61 5 12J20 12J18 024 2 60 5 12J20 12J18 030 2.5 42 3.5 12J20 12J18 030 2.5 43 3.5 12J20 12J18 030 2.5 48 4 12J20 12J18 030 2.5 49 4 12J20 12J18 036 3 24 2 12J18 12J19 036 3 30 2.5 12J18 12J19 042 3.5 24 2 12J18 12J20 042 3.5 30 2.5 12J18 12J20 042 3.5 30/36 3 12J19 12J20 042 3.5 36 3 12J19 12J20 048 4 30/36 2.5/3 12J19 12J20 048 4 36 3 12J19 12J20 TXV Ranges: 12J18 - 1.5 to 2.5 ton systems - Use on 2.5 ton (030) and lower systems. 12J19 - 3 ton systems - Use down to 2 ton (024) systems. 12J20 - 3.5 to 5 ton systems - Use down to 3 ton (036) systems. EL16XP1 - 1.5 to 5 Ton Heat Pump / Page 12 REVISIONS Sections Optional Accessories LE--7 NNOX Description of Change Updated Line Sets available. 0 AA ©*HXU MEMBER COMPANY O(TSTF-0 CUC ntertek Visit us at www.Lennox.com For the latest technical information, www.LennoxPros.com Contact us at 1-800-9-LENNOX NOTE - Due to Lennox' ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency. ©2023 Lennox Industries, Inc.