BLD2023-0035_Manufacturer_Specifications_and_Installation_Instructions_1.10.2023_8.44.00_AM_3306065Carrier 25VNA824AO03 2-Ton HP Unit @ 68 dBa. @ 15' = 47.0 dBa (+/- 2 Testing, 45.0 dBa Maximum per code) >>Does Not Include Additional Reduction from Heat Pump Riser Pad with Vibration Isolators ARI STANDARD 275-97 4.2 Procedure for Estimating Sound Pressure Levels - Single Unit Installation. The basic procedure for estimating A -Weighted sound pressure levels at a given point of evaluation consists of combining the sum of the application and evaluation factors with the Sound Rating Level for the equipment: 15 f t Sound Rating Level from ARI 270 68.0 + Equipment Location Factor — Barrier Shielding Factor None Installed — Sound Path Factor Not used for property lines 21.0 — Distance Factor Estimated A -Weighted Sound 47.0 Pressure Level I dB* +/- 2 dBa Tolerance Allowed for Testing Code Target is 45 Dba Max for HP >>Does Not Include Additional Reduction from Heat Pump Riser Pad with Vibration Isolators 4.1.2 Barrier Shielding Factor. This factor accounts for the sound reduction benefit of any solid structure that obstructs the line of sight (or sound) from the equipment location to the point of evaluation. Such a barrier may be the corner of a building, the edge of a roof, or a heavy wall of masonry, etc., built for the specific purpose of shielding noise from a unit to an area of concern. See Item 2, Table 1, for sketches and the normal barrier factors. p �athof ound Path Factor. This factor adjusts for the soun heunit to the point of evaluation, which may be to the ou only, to a room through open windows, to a room throug windows, or through a wall. See Item 3, Table 1. 4.1.4 Distance Factor. The direct distance, D, from the equipment location to the point of evaluation is a very significant application factor in determining the estimated A -Weighted sound pressure levels resulting from the operation of outdoor equipment in any installation. The distance factor is obtained from Table 2. Table 2. Distance Factor Factor Value ft. [m] (dB) 4 1.2 9.5 5 1.5 11.5 6 1.8 13.0 7 2.1 14.5 8 2.4 15.5 9 2.7 16.5 10 3.0 17.5 15 4.6 21.0 20 6.1 23.5 25 7.6 25.5 30 9.1 27.0 40 12.2 29.5 50 15.2 31.0 60 18.3 33.0 70 21.3 34.5 80 24.4 35.5 90 27.4 36.5 100 30.5 37.5 125 38.1 39.5 150 45.7 41.0 175 53.3 42.5 200 61.0 43.5 400 122.0 49.5 5 8 inch Heat Pump Pad Product Heat Pump Pad Purpose The DiversiTech Heat Pump Pad provides an effective base for heat pump equipment installed in snowy climates.Rather than a combination of a typical 2 inch (or 3 inch) equipment pad and 6 inch heat pump risers, the Heat Pump Pad provides a full 8 inch of elevation in a simple square footprint. The star pattern of the integral risers allows for installation of equipment with different size footprints up to 36 inch X 36 inch. Features . Include 8 anti -vibration pads uniquely designed to fit into the guide slots on the top of the risers. • The base is sloped outward to allow for easy drainage of condensate or defrost cycle condensate when the outdoor coil is operating in heat pump mode. • Nestable for efficient shipping, transportation, and warehousing. • Environmentally friendly General • Injection molded • Made from recycled polypropylene material Specifications . Drillable • UV Resistant • Load Capacity: HP3232-8: 307 Ibs HP3636-8: 389 Ibs General Characteristics Stock Number Dimensions Number per Pallet Weight HP3636-8 36 in x 36 in x 8 in 16 18 Ibs DIVERNTERk' 1 Ars lyl i I �r r Vibration Isolators Reduce Sound Transfer 8" Tall Legs Allow Sound Pressure to Travel Downward Towards Ground Reducing Radial Pressure Levels DOC 141725 www.diversitech.com 1.800.995.2222 Product Data pu.INFINIT'Y' lsys The Infmity® 18VS heat pump offers high -efficiency variable speed performance in a remarkably small cabinet and provides up to 11 HSPF heating efficiency and up to 19 SEER cooling efficiency. The variable speed inverter capacity control delivers up to 5 stages of operation for exceptional load matching, dehumidification and zoning performance. This product has been designed and manufactured to provide flexible system matching and work with a wide variety of indoor units and controls. NOTE: Ratings contained in this document are subject to change at any time. Always refer to the AHRI directory (www.ahridirectory.org) for the most up-to-date ratings information. INDUSTRY LEADING FEATURES / BENEFITS Energy Efficiency • Up to 19 SEER /13.0 EER / 11 HSPF • Microtube Technology - refrigeration system Sound • Sound level as low as 55 dBA (Silencer System II"") in low speed operation • Soft start and smooth ramp to operating speeds Comfort • Variable speed compressor operates at 5 stages with capacity range from as wide as 25-100% • Air cooled Inverter variable speed drive System requires Infmity® Touch Control for 5-stage operation (Requires version 11 or newer software on sizes 24 - 60 and version 12 or newer software on size 13.) Ratings provided with 2-stage thermostats and suitable non -communicating indoor products for 2-stage operation Reliability • Purono refrigerant - environmentally sound, won't deplete the ozone layer and low lifetime service cost • Front -seating service valves • Inverter control drives compressor and fan motor • No control module attached to fan motor • Pressure equalizer valve for easy compressor starting • High pressure switch • Suction pressure transducer • Electronic expansion valve (EXV) for heating, TXV for cooling • Compressor discharge temperature sensor • Suction temperature sensor • Filter drier (field installed) • Internal crankcase heater standard Flexibility and installation: • 2 control wires to outdoor unit in complete Infmity® system and Touch Control • Energy Tracking capability with the hifmity® Touch Control (Energy Tracking has the ability to monitor and estimate the energy consumption of your Infmity® system.) • Smaller and lighter than 2-stage units • Minimum and Maximum adjustments with Infmity® Touch Control • Hybrid Heat® dual fuel capable • Compatible with non -communicating thermostats Durability WeatherArmor Ultra- protection package: • Solid, Durable sheet metal construction • Steel louver coil guard • Baked -on, complete outer coverage, powder paint Applications • Line sets up to 100 ft (30.5 m) equivalent length • No long -line accessories required MODEL NUMBER NOMENCLATURE 1 2 3 4 5 6 7 8 9 10 11 12 13 N N A A A/N N N N A/N A/N A/N N N 2 5 V N A 8 3 6 A 0 0 3 0 Product Product Major Cooling Minor Series Family Tier Series SEER Capacity Variations Open Open Voltage Series N= 1,000 Btuh A = Standard O=Nat O=Nat 25 = HP V = VS HP Infinity Series A = Puron 8 = 18 SEER (nominal) B = Design Variation Defined Defined 3=208/230-1 0, 1, 2ikunffl CERTIFIED ... l Use of AHRI fled C �� US TJ__1ZT� Com rt TM Mark indicates a l� J 1Li�(LGII 1. XE�f %YV 8ra1EY � . manufacturer's • participation in the IFA LISTED Qualifying Models Only program For verification ISO 9001 of certification for individual oM1 sAi GI,A=d products, go to www.ahridirectory.org. STANDARD FEATURES FEATURES Unit Size 25VNA8 13 24B 25 36 37 48 60 Puron® Refrigerant X X X X X X X Variable Speed Rotary Compressor X X X X X X X Air —Cooled Integrated Inverter Drive X X X X X X X Louvered Coil Guard X X X X X X X Field Installed Filter Drier X X X X X X X Front Seating Service Valves X X X X X X X Internal Pressure and Temperature Protection X X X X X X X Suction Pressure Transducer X X X X X X X High Pressure Switch X X X X X X X Internal Crankcase Heater X X X X X X X Utility Interface Connections X X X X X X X Enhanced Diagnostics with Infinity® Touch Control (Version 11 or newer software on sizes 24 - 60 and version 12 or newer software on size 13.) X X X X X X X Energy Tracking Capability with Infinity® Touch Control (requires software version 11 or later) X X X X X X X Deluxe Sound Blanket X X X X X X X Outdoor Air Temperature Sensor X X X X X X X X = Standard 2 REFRIGERANT PIPING LENGTH LIMITATIONS Maximum Line Lengths: The maximum allowable total equivalent length for heat pumps can vary depending on the vertical separation. See the tables below for allowable lengths depending on whether the outdoor unit is on the same level, above or below the outdoor unit. Maximum Line Lengths for Heat Pump Applications MAXIMUM ACTUAL LENGTH MAXIMUM EQUIVALENT LENGTHt MAXIMUM VERTICAL SEPARA- ft (m) ft (m) TION ft (m) Units on equal level 100 (30.5) 100 (30.5) N/A Outdoor unit ABOVE indoor unit 100 (30.5) 100 (30.5) 100 (30.5) Outdoor unit BELOW indoor unit See Table 'Maximum Total Equivalent Length: Outdoor Unit BELOW Indoor Unit' t Total equivalent length accounts for losses due to elbows or fitting. Seethe Long Line Guideline for details. Maximum Total Equivalent Lengtht - Outdoor Unit BELOW Indoor Unit Liquid Line Diameter HP with Puron® Refrigerant - Maximum Total Equivalent Lengtht Vertical Separation ft (m) Outdoor unit BELOW indoor unit; Size w/ TXV 0-20 (0-6.1) 21-30 (6.4-9.1) 31-40 (9.4-12.2) 41-50 (12.5-15.2) 51-60 (15.5-18.3) 61-70 (18.6-21.3) 71-80 (21.6-24.4) 1-Ton 3/8 100* 100* 100* 100* 100* 100* 100* 2-Ton 3/8 100* 100* 100* 100* 100* 100* 100* 3-Ton 3/8 100* 100* 100* 100* 100* 100* 100* 4-Ton 3/8 100* 100* 100* 100* 100 100 -- 5-Ton 3/8 100* 100* 100* 100* 100 100 -- * Maximum actual length not to exceed 100 ft (30.5 m) t Total equivalent length accounts for losses due to elbows or fitting. -- = outside acceptable range LONG LINE APPLICATIONS Unit is approved for up to 100 ft (30.5 m) equivalent length and vertical separations shown above with no additional accessories. Longer line set applications are not permitted. COOLING CAPACITY LOSS TABLE Nominal Size (Btuh) Line OD (in.) 25VNA8 Cooling Capacity Loss (%) Total Equivalent Line Length (ft) 25 50 75 80 100 5/8 0.5 1.2 1.8 1.9 2.4 13 314 CIA 0.6 0.7 0.8 5/8 0.5 1.2 1.8 1.9 2.4 24B 3/4 0.1 0.4 0.6 0.7 0.8 1.8 1.9 2.4 25 3/4 0.1 0.4 0.6 0.7 0.8 7/8 0.0 0.1 0.3 0.3 0.4 5/8 1.1 2.4 3.7 4.0 5.0 36 3/4 0.3 0.8 1.3 1.4 1.8 7/8 0.0 0.3 0.5 0.6 0.8 3/4 0.7 1.6 2.4 2.6 3.2 37 48 7/8 0.3 0.7 1.1 1.2 1.6 1 1/8 0.0 0.1 0.2 0.3 0.4 3/4 1.0 2.3 3.5 3.8 4.8 60 7/8 0.4 1.0 1.7 1.8 2.3 1 1/8 0.0 0.1 0.3 0.4 0.5 Rating Line Size in BOLD 3 EQUIPMENT SIZING GUIDELINES If primary load is cooling, size the same as any other air conditioning system. If primary load is heating, use the chart below for maximum size for heating. MAXIMUM RECOMMENDED EQUIPMENT SIZE - HEATING COOLING LOAD (tons) MAXIMUM RECOMMENDED EQUIPMENT SIZE FOR HEATING* 1 24 1.5 24 2 36 2.5 36 3 48 3.5 60 4 60 5 60 * Make sure duct work is capable of delivering required airflow. Make sure combination rating exists for desired indoor and outdoor combination. MIN/MAX AIRFLOW TABLES The indoor airflow delivered by this system varies significantly based on outdoor temperature, indoor unit combination, and system demand. The airflows on these tables are for duct design considerations. Duct systems capable of these ranges will ensure the system will deliver full capacity at all outdoor temperatures. Minimum and maximum compressor stage can be adjusted from these numbers in the InfmityO Control Heat Pump Setup screen. Cooling — Comfort Mode Minimum Cooling (Dehum or Zoning) Size Max Stage 5 Airflow Max Stage 1 Airflow 1—Ton 420 300 300 2—Ton 739 300 300 3—Ton 990 300 300 4—Ton 1389 542 457 5—Ton 1600 700 600 Cooling — Efficiency Mode Size Max Stage 5 Airflow Max Stage 1 Airflow 1—Ton 420 300 2—Ton 825 585 3—Ton 1050 600 4—Ton 1400 875 5—Ton 1800 975 Heating — Comfort Mode Size Max Stage 5 Airflow Max Stage 1 Airflow 1—Ton 409 300 2—Ton 819 300 3—Ton 1014 300 4—Ton 1550 429 5—Ton 1600 500 Heating — Efficiency Mode Size Max Stage 5 Airflow Max Stage 1 Airflow 1—Ton 600 300 2—Ton 825 585 3—Ton 1200 700 4—Ton 1600 1000 5—Ton 1600 900 Cooling Max Mode Size Max Stage 5 Airflow Max Stage 1 Airflow 1—Ton (550 cfm/ delivered ton) 780 434 2—Ton (24) 850 585 2—Ton (25) (550 cfm/ delivered ton)* 1350 510 3—Ton 1200 600 4—Ton 1600 875 4—Ton —49 1450 875 5—Ton 2000 975 Heating Max Mode Size Max Stage 5 Airflow Max Stage 1 Airflow 1—Ton (550 cfm/ delivered ton) 600 300 2—Ton (24) 850 585 2—Ton (25) (550 cfm/ delivered ton)* 850 585 3—Ton 1200 700 4—Ton 1600 1000 5—Ton 2000 900 * Serial number beginning with 0115E and newer LEGEND:: Max Capacity Airflow — Stage 5 airflow varies depending on conditions. This is the highest airflow the system will attempt to deliver in this particular mode. Ductwork for non —zoned systems should be sized for this airflow to ensure the system can deliver full capacity when needed. Improper duct design may result in excessive airflow noise and/or cutback occurrences at max airflow conditions. Highest Min. Capacity Airflow — Stage 1 airflow also varies depending on conditions. In zoned systems, each zone must be capable of delivering this airflow for the system to deliver full capacity into the zone. Otherwise, airflow may be diverted to other zones or cutback may occur. Min Cooling (Dehum or Zoning) — Lowest airflow the system will deliver. May operate down to this airflow in dehumidification mode or in zoning applications where ductwork restrictions have caused the blower to cut —back. PHYSICAL DATA C UNIT SIZE SERIES 13-30 2413-30 25-31 36-31 37-30 48-30 60-30 Compressor Type Variable Speed Rotary REFRIGERANT Puron® (R-410A) Control TXV (Puron® Hard Shutoff) Charge lb (kg) 5.00 (2.27) 5.40 (2.45) 6.38 (2.89) 6.38 (2.89) 7.5 (3.40) 8.30 (3.76) 8.60 (3.90) Outdoor Htg Exp. Device EXV COND FAN Forward Swept Propeller Type, Direct Drive Air Discharge Vertical Air Qty (CFM) 1600 2080 2500 2500 3800 4500 4500 Motor HP 1/5 1/5 1/3 1/3 1/3 1/3 1/3 Motor RPM 650 825 1050 1050 750 850 900 COND COIL Face Area (Sq ft) 11.12 11.12 13.90 13.90 21.50 21.50 23.65 Fins per In. 20 20 20 20 20 20 20 Rows 1 1 1 1 1 1 1 Circuits 5 5 6 6 8 8 8 VALVE CONNECT. (In. ID) Vapor 5/8 5/8 3/4 3/4 7/8 7/8 7/8 Liquid 3/8 REFRIGERANT TUBES (In. OD) Rated Vapor* 3/4 3/4 7/8 7/8 1-1/8 1-1/8 1-1/8 Max Liquid Line 3/8 * Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset. Note: See unit Installation Instruction for proper installation. ELECTRICAL DATA UNIT SIZE- VOLTAGE, SERIES V/PH OPER VOLTS* COMPR FAN MCA MAX FUSE ** or CKTBRKAMPS MAX MIN LRA RLA FLA 2413-30 N/A 10.32 0.58 13.5 20 208-230-1 253 197 36-31 N/A 18.30 1.20 24.4 40 37-30 N/A 19.60 1.20 26.0 40 48-30 N/A 23.90 1.20 31.4 50 60-30 N/A 31.30 1.40 40.8 60 * Permissible limits of the voltage range at which the unit will operate satisfactorily ** Time -Delay fuse. FLA - Full Load Amps LRA - Locked Rotor Amps MCA - Minimum Circuit Amps RLA - Rated Load Amps NOTE: Control circuit is 24-V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection. Complies with 2010 requirements of ASHRAE Standards 90.1 CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE) UNIT SIZE -VOLTAGE, SERIES If a Touch Control is installed, subcooling recommendation displayed in Charging Mode must be followed. If not, subcooling chart shown on the charging label must be followed 13-30 24-30 25-31 36-31 37-30 48-30 60-30 SOUND POWER LEVEL (dBA) Unit Size- ' Min Speed Max Speed Max Speed Voltage, Series Spectrum Cooling Cooling Heating (without tone adjustment) 013-30 Freq (Hz) 1500 RPM 4700 RPM 5400 RPM 125 63.0 67.5 73.5 250 57.0 66.5 66.5 500 51.5 61.5 66.0 02413-30 1000 47.5 58.0 59.0 2000 41.5 54.5 56.5 4000 38.0 57.5 59.5 8000 45.5 53.5 55.0 Sound Rating (dBA) 55 67 68 125 59.5 70.0 68.5 250 56.0 67.5 67.0 500 54.0 67.5 65.0 025-31 1000 50.0 63.5 62.0 2000 41.5 59.0 59.0 4000 35.0 58.0 63.0 8000 48.0 51.5 55.0 Sound Rating (dBA) 55 69 71 Freq (Hz) 1200 RPM 4800 RPM 5400 RPM 125 59.5 70.0 69.0 250 56.0 68.0 70.0 500 54.0 66.0 66.0 036-31 1000 50.0 64.0 64.0 2000 41.5 61.5 60.5 4000 35.0 62.0 61.0 8000 48.0 55.5 56.0 Sound Rating (dBA) 55 72 71 Freq (Hz) 1200 RPM 3000 RPM 4800 RPM 125 64.0 74.0 75.5 250 61.0 68.0 70.5 500 57.5 66.5 68.0 037-30 1000 53.5 61.5 63.5 2000 49.0 59.5 61.0 4000 42.0 57.5 63.5 8000 44.0 51.0 55.5 Sound Rating (dBA) 60 69 72 Freq (Hz) 1500 RPM 4320 RPM 5400 RPM 125 67.0 73.5 69.0 250 63.0 71.5 68.5 500 57.0 69.5 66.5 048-30 1000 54.5 64.5 64.0 2000 51.0 62.5 61.5 4000 54.0 62.5 64.5 8000 47.5 54.5 60.0 Sound Rating (dBA) 64 72 73 Freq (Hz) 1200 RPM 4140 RPM 5400 RPM 125 61.5 71.5 70.5 250 59.5 73.0 71.5 500 54.5 70.0 68.0 060-30 1000 50.5 65.0 62.5 2000 44.0 62.0 60.0 4000 41.5 60.5 62.0 8000 49.0 58.0 61.5 Sound Rating (dBA) 57 72 71 NOTE: Tested in compliance with AHRI 270-1995 but not listed with AHRI RPM -CAPACITY -SOUND (dBA)* STAGE # I COMP RPM CAPACITY% SOUND (dBA) COOLING 1 1500 58% 59 2 1867 725 60 3 2100 810 61 4 2350 90% 62 5 2600 100% 63 HEATING 1 1500 38% 55 2 2300 59% 60 3 2450 63o 64 4 2600 67% 65 COOLING 1 1500 35% 55 2 2566 56% 60 3 3150 69% 65 4 3950 87% 66 5 4700 100% 67 HEATING 1500 29% 55 2 2800 53% 59 3 3150 59% 62 4 4700 88% 65 5 5400 100% 68 COOLING 1 1200 3800 55 2 1900 58% 60 3 2400 73% 62 4 2600 79% 66 5 3300 100% 69 HEATING 1 1200 25% 55 2 2400 50% 60 3 3300 69% 62 4 4200 88% 68 5 4800 100% 71 COOLING 1 1200 255 55 2 2400 50% 61 3 3300 69% 65 4 4200 88% 69 5 4800 100% 72 HEATING 1 1200 22% 55 2 2600 485 60 3 3400 63% 63 4 4800 89% 69 5 5400 100% 71 COOLING 1 1200 25o 60 2 1800 60% 61 3 2200 73% 67 4 2600 87% 67 5 3000 100% 69 HEATING 1 1200 25% 60 2 2400 50% 67 3 2700 565 68 4 3000 63% 69 5 4800 100% 72 *Estimated sound for stages 2, 3, and 4 *For 2—stage operation: Cooling Low = Stage 2, Heating low = Stage 3; both cooling and heating High = Stage 5 RPM -CAPACITY -SOUND (dBA)* continued STAGE # COMP RPM CAPACITY % SOUND (dBA) COOLING 1 1500 35* 64 2 2460 57% 67 3 2800 65% 68 4 3650 84% 70 5 4320 100% 72 HEATING 1 1500 28% 64 2 2800 52% 67 3 3300 61 % 68 4 4320 80% 71 5 5400 100% .r 73 COOLING 1 1200 32% 57 2 2180 55% 61 3 2850 70% 65 4 3700 90% 68 5 4140 100% 72 HEATING 1 1200 25% 57 2 2600 50% 51 3 3200 615 65 4 4140 88% 69 5 5400 100% 71 *Estimated sound for stages 2, 3, and 4 *For 2—stage operation: Cooling Low = Stage 2, Heating low = Stage 3; both cooling and heating High = Stage 5 CONTROLS SYSTXCCITN01* Infinity® Touch Control (non—Wi—Fi) (software version 11 or newer on unit sizes 24 — 60; version 12 or newer on size 13) SYSTXCCITC01* Infinity® Touch Control (Wi—Fi) — 12orne e13) SYSTXCCITW01 * Infinity® Touch Control with Wi—Fi & Wireless Access Point SYSTXCCSMS01 Infinity® Smart Sensor (Optional wall control used to monitor temperature and/or fan control in an individual zone.) SYSTXCCNIM01 Infinity® Network Interface Module (Connects Heat Recovery and Energy Recovery Ventilators on non —zoning applications.) SYSTXCCSMS01 Infinity® Smart Sensor * Requires version 11 software or newer on sizes 24 — 60 and version 12 software or newer on size 13. THERMOSTATS PART NUMBER PROGRAM GAS ELECTRIC HEAT PUMP HYBRID HEAT HEAT COOL TP—PRH01—A 7—Day V V 3 2 TP—PHP01 7—Day N 3 2 TP—NRH01—A NP V V V 3 2 TP—NHP01 NP V V 3 2 ACCESSORIES Accessory Number Description 13 24B 25 36 37 48 60 HK70EZ015 MODEL PLUG FOR FV4(A,B), FK, 40FK N/A X HK70EZ016 MODEL PLUG FOR FV4(A,B), FK, 40FK X HK70EZ017 MODEL PLUG FOR FV4(A,B), FK, 40FK X N/A HK70EZ018 MODEL PLUG FOR FV4(A,B), FK, 40FK X HK70EZ019 MODEL PLUG FOR FV4(A,B), FK, 40FK X KHASS0606MPK SNOW STAND KIT X KSASF0201AAA SUPPORT FEET KIT X X X X X X X KSATX0201PUR TXV KIT X X X KSATX0301PUR TXV KIT X X KSATX0401PUR TXV KIT X KSATX0501PUR TXV KIT X KSBTX0201PUR TXV KIT X KSBTX0301PUR TXV KIT X X KSBTX0401PUR TXV KIT X LMlOKKO03 VAPOR LINE MUFFLER X X X X X X X x = Accessory Accessory Description and Usage Model Plug - FV4(A,B), FK, 40FK Replaces production model plug in outdoor unit and adjusts compressor speed in heating mode to match indoor airflow. Usage Guideline: Required when using heat pump in replacement applications with FV4(A,B), FK4, 40FK fan coil indoor unit. Support Feet Raises unit above base pad. 2 and 3 ton kit contains 5 feet for stable installation with small base. 4 and 5 ton kit contains 4 feet. Usage Guideline: Recommended in cold climates where snow can accumulate around unit. Allows improved base pan drainage. Recommended for rooftop applications. Thermostatic Expansion Valve (TXV) A modulating flow -control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator. Usage Guideline: Required if indoor unit does not already contain Puron refrigerant TXV Vapor Line Muffler An external muffler installed in the vapor line to minimize vibration transmitted through refrigerant lines Usage Guideline: Recommended if vapor line is not installed per recommendations in the installation instructions and vibration may be transmitted into the structure. DIMENSIONS SHIPPING A B C D E F G H I U K OPERATING SHIPPING LENG(Sq WIDTH SHIPPING UWT SERIES cHMACTERISTICs WEIGHT WEIGHT HEIGHT INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM Lbs K9s Lbs K9s INCH MM INCH MM 4 7/16 113.0 18 1/16 459.0 713116 197.9 1 1/8 28.2 313/16 97.4 11 1/4 285.8 11 1/4 285.8 14 1/2 63.0 162 73.5 25 1/4 641.5 36 9116 929.5 25VN4624B0030050 0 Y N N N 23 1/8 587.3 32 1/8 815.E 3/4 19.1 4 7/i6 113.0 16 1/16 459.0 713/16 197.9 1 1/8 28.2 313/16 97.4 11 1/4 285.8 11 1/4 285.8 14 1/2 63.0 162 73.5 25 1/4 841.5 36 9/i6 929.5 4 7/16 113.0 18 1/16 459.0 713116 197.9 1 1/8 28.2 313/16 97.4 10 3(4 273.1 10 314 273.1 18 1/4 74.4 190 86.2 25 114 641.5 43 318 1102.2 25VNA836AO031050 1 Y N N N 23 587.3 15/16 988.4 3/4 19.1 4 7/16 113.0 18 1/16 459.0 7 lam 197.9 1 1/8 28.2 313/16 97.4 10 3/4 273.1 10 3/4 273.1 18 1/4 g463.6 L21 74.4 190 86.2 25 1/4 641.5 43 3/8 1102.2 25VNA837AO030050 0 Y N N N 31 3/1 792.5 39 3/8 1000.5 7/8 22.2 6 9/1 166.1 2411/16 626.3 9 1/8 231.3 1 1/8 282 313/16 974 14 1/2 3683 14 5/8 371.5 18 3/4 98.9 257 1166 33 5116 8466 45 1/4 11491 25VNA848AO030050 0 Y N N N 31 3/16 39 3/8 1000.5 7/8 22.2 6 9/16 166.1 2411/16 626.3 9 1/8 231.3 1 1/8 28.2 313/16 97.4 14 1/2 368.3 14 ISM 371.5 18 3/4 98.9 257 116.6 33 5/16 846.6 45 1/4 1149.1 25VNA86OA0030050 0 Y N N N 31 3/16 �49N 4213/16 1086.9 7/8 22.2 11 6 9/16 166.1 -11116 626.3 1 9 1/8 1 231.3 11 1 US 11 28.2 31-16 97.4 16 1/2 1 419.1 1 15 1 381.0 20 508.0 245 111.1 286 129.7 33 5/16 846.6 48 1/4 12-S W � /N. NOTES: \ 1. CENTER OF GRAVITY A sc AIR DISCHARGE = / p) All It AIR F DISCHARGE � C z3 Q I � CIE10 POWER SUPPL9 C014M. (n W B 22.2) BOLE WIT N 411t 14 AIR IN JOT118 1 11a'l�ta.61 AmOCAOUIam O FIELD CONTROL SVPPLT CONY m I87181(022 2) $So[ tp' E uOUlojil�CAnSi K J 3 r�• s Ir - I le'al 188.I H p 0CVAPO1l LiKE CONK Y :- I 111i,i t,17 112 G 1 X ''' 112.i) 3/8'(09.5) TIEDOWN KNOCKOUTS (2) PLACES 1 ISrt6' iP IN t71.01 UNIT SIZE MINIMUM GROUND MOUNTING MINIMUM ROOF -TOP MOUNTING PAD APPLICATION DIMENSIONS PAD APPLICATION DIMENSIONS 13, 24, 25, 36 23 118 587.3 17 7/8 454.6 25 3/4 654.0 20 7/16 518.5 37,48,60 31 3/16 792.5 22 15/16 583.2 NOTE: ALL DIMENSIONS IN INCH (MM) U.S. ECCN: Not Subject to Regulation (N.S.R.) 35 889.0 26 3/4 679.7 SD5235-4 REV, G CLEARANCES Wall 6" (152.4 mm) 24" (609.6) Service 12" (304.8) 24" (609.6) Service 24" (609.6) Clearances (various examples) 12" (304.8) 24" (609.6) Note: Numbers in () = mm Wall 24" (609.6) Service Wall 24" Service 12" V (304.8) 152. 12" (304.8) 24" (609.6) 24" (609.6) Service IMPORTANT: When installing multiple units in an alcove, roof well, or partially enclosed area, ensure there is adequate ventilation to prevent re -circulation of discharge air. A07833 VA m PAO C TESTED AHRI COMBINATION RATINGS* NOTE: Ratings contained in this document are subject to change at any time. For AHRI ratings certificates, please refer to the AHRI directory www.ahridirectory.org Additional ratings and system combinations can be accessed via the Carrier database at: www.MyCarrierRatings.com Outdoor Model Indoor Model Furnace Model Cooling Heating Cooling 9 SEER EER ID CFM High Temp Low Temp HSPF Capacity 47°F (8°C) COP Capacity 17°F (-8°C) COP 25VNA824B*030* FE4ANF002L+UI 24,000 17.5 11.0 825 9.5 24,400 3.62 15,600 2.58 25VNA836A*031* FE4AN(B,F)005L+UI 34,200 17.5 10.0 1,050 10.0 34,200 3.56 23,000 2.58 25VNA837A*030* FE4ANB006L+UI 33,600 19.0 13.0 1,050 10.0 40,000 3.50 30,400 2.66 25VNA848A*030* FE4AN(B,F)005L+UI 46,000 18.0 11.0 1,400 11.0 50,500 3.44 35,200 2.66 25VNA860A*030* FE4ANB006L+UI 57,000 1 17.0 1 10.0 1,600 9.0 60,000 3.10 44,500 2.48 * Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on: Cooling Standard: 80°F (27°C) db 67°F (19°C) wb indoor entering air temperature and 95°F (35°C) db air entering outdoor unit. High —Temp Heating Standard: 70°F (21 °C) db indoor entering air temperature and 47°F (8°C) db 43° F (6°C) wb air entering outdoor unit. Low —Temp Heating Standard: 70°F (21 °C) db indoor entering air temperature and 17°F (-8°C) db 15° F (-9°C) wb air entering outdoor unit. COP — Coefficient of Performance EER — Energy Efficiency Ratio HSPF— Heating Seasonal Performance Factor SEER — Seasonal Energy Efficiency Ratio w UI— User Interface NOTE: Ratings contained in this document are subject to change at any time. DETAILED COOLING CAPACITIES# - EFFICIENCY MODE CONTINUED 25VNA824B / FE4ANF002L Efficiency Mode EVAp Condenser Entering Air Temperature ° F (° C) EDB AIR 115 (46.1) 105 (40.5) 95 (35) 85 (29.4) 75 (23.9) 65 (18.3) °F('C) EWB ID Capacity MBtuhjtj�L.;IFM DSys.ID Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total SCFM KW SCFM . KW 5 SCFM . KW SCFM Sys. KW SCFM Sys°F(°C) KW Ttl S Total Sens# Total Sens# STAGE Total Sens# Total Sens# Total Sens# 72 (22.2) 23.99 9.99 3.08 25.38 10.48 2.68 26.51 10.88 2.31 27.76 11.32 1.97 28.92 11.74 1.65 30.00 12.14 1.37 67 (19.4) 21.78 14.06 3.03 23.03 14.51 2.64 24.07 14.89 2.29 25.19 15.30 1.95 26.23 15.68 1.65 27.21 16.06 1.38 75 (23.9) 825 825 825 825 825 825 63 (17.2) 20.14 17.25 2.99 21.29 17.68 2.61 22.25 18.03 2.26 23.28 18.42 1.94 24.25 18.78 1.65 25.14 19.13 1.38 57 (13.9) 19.20 19.20 2.96 20.07 20.07 2.59 20.78 20.78 2.25 21.53 21.53 1.93 22.23 22.23 1.65 22.88 22.88 1.39 72 (22.2) 23.92 14.05 3.08 25.31 14.51 2.68 26.44 14.88 2.31 27.69 15.29 1.97 28.85 15.69 1.65 29.93 16.06 1.36 67 (19.4) 21.71 18.07 3.03 22.96 18.50 2.64 24.00 18.85 2.29 25.12 19.23 1.95 26.16 19.59 1.65 27.14 19.94 1.38 80 (26.7) 825 825 825 825 825 825 63 (17.2) 20.49 20.49 3.00 21.42 21.42 2.62 22.32 21.83 2.27 23.31 22.27 1.94 24.26 22.63 1.65 25.15 22.94 1.38 (1 7 3. 20.46 20.46 3.00 21.38 21.38 2.62 22.11 22.11 STAGE 2.26 3 22.90 22.90 1.94 23.62 23.62 1.65 24.28 24.28 1.39 72 (22.2) 14.71 6.31 1.53 16.06 6.81 1.40 17.24 7.25 1.24 18.61 7.76 1.10 20.01 8.28 0.95 21.40 8.82 0.80 67 (194) 13.26 9.12 1.52 14.47 9.68 1.40 15.56 10.19 1.25 16.82 10.77 1.11 18.08 11.35 0.97 19.33 11.95 0.83 75 (23.9) 650 650 650 650 650 650 63 (17.2) 12.21 11.32 1.52 13.33 11.93 1.40 14.34 12.51 1.25 15.50 13.13 1.12 16.65 13.77 0.98 17.80 14.40 0.85 57 (13.9) 11.92 11.92 1.51 12.87 12.87 1.40 13.73 13.73 1.25 14.68 14.68 1.12 15.62 15.62 0.99 16.56 16.56 0.87 72 (22.2) 14.65 9.16 1.53 16.00 9.72 1.40 17.18 10.22 1.24 18.55 10.80 1.10 19.95 11.38 0.95 21.35 11.99 0.79 67 (19.4) 13.23 11.93 1.52 14.43 12.55 1.40 15.52 13.13 1.25 16.77 13.77 1.11 18.02 14.42 0.97 19.28 15.07 0.83 80 (26.7) 650 650 650 650 650 650 63 (17.2) 12.80 12.80 1.52 13.80 13.80 1.40 14.71 14.71 1.25 15.72 15.72 1.11 16.74 16.71 0.98 17.88 17.42 0.85 3. (1 7 12.78 12.78 1.52 13.78 13.78 1.40 14.68 14.68 STAGE 1.25 1 15.69 15.69 1.12 16.69 16.69 0.98 17.68 17.68 0.85 72 (22.2) 10.98 4.91 1.02 12.29 5.41 1.00 7.32 3.62 0.42 8.41 4.06 0.40 9.55 4.54 0.36 10.67 5.00 0.30 67 (194) 9.86 7.42 1.02 11.05 8.01 1.00 6.54 5.94 0.43 7.50 6.56 0.42 8.51 7.19 0.38 9.56 7.86 0.33 75 (23.9) 650 650 585 585 585 585 63 (17.2) 9.15 9.15 1.02 10.29 9.90 1.00 6.40 6.40 0.43 7.27 7.27 0.42 8.18 8.18 0.39 9.11 9.11 0.35 57 (13.9) 9.13 9.13 1.02 10.15 10.15 1.00 6.40 6.40 0.43 7.27 7.27 0.42 8.17 8.17 0.39 9.10 9.10 0.35 72 (22.2) 10.93 7.45 1.02 12.27 8.08 1.00 7.28 5.99 0.42 8.36 6.61 0.40 9.50 7.26 0.36 10.68 7.95 0.30 67 (19.4) 9.88 9.86 1.02 11.12 10.63 1.00 6.97 6.97 0.43 7.91 7.91 0.41 8.89 8.89 0.37 9.91 9.91 0.32 80 (26.7) 650 650 585 585 585 585 63 (17.2) 9.86 9.86 1.02 10.95 10.95 1.00 6.96 6.96 0.43 7.90 7.90 0.41 8.88 8.88 0.37 9.90 9.90 0.32 (1 7 3. 9.85 9.85 1.02 10.94 10.94 1.00 6.95 6.95 0.43 7.89 7.89 0.41 8.87 8.87 0.37 9.88 9.88 0.32 Operation in this area is restricted to maintain reliable system operation and customer comfort. The system will default to the next available stage Stage 1 - Compressor speed limited to stage two at 105 and 115 outdoor. See additional notes on page 27 HEAT PUMP HEATING PERFORMANCE - EFFICIENCY MODE CONTINUED INDOOR AIR 25VNA824B / FE4ANF002L Heating Efficiency Mode Outdoor Coil Entering Air Temperature ° F (° C) 7 (-13.9) 17 (-8.3) 27 (-2.8) EDB F (' C) ID SCFM Capacity MBtuh Total Sys. KWt ID SCFM Capacity MBtuh Total Sys. KWt Total Integ# ID SCFM Capacity MBtuh Total Sys. KWt Total Integ# Total Integ# 65 (18.3) 450 12.00 11.03 1.37 825 STAGE 5 15.76 14.37 1.69 825 18.37 16.31 1.74 70 (21.1) 11.90 10.93 1.45 15.60 14.22 1.77 18.18 16.15 1.83 75 (23.3) 11.70 1.50 15.44 14.07 1.86 STAGE 17.99 15.98 1.92 65 (18.3) 300 8.37 7.69 0.89 500 3 10.11 9.21 0.88 650 11.81 10.49 0.90 70 (21.1) 8.22 7.56 0.94 9.93 9.05 0.93 11.61 10.31 0.96 75 (23.3) 8.07 7.42 0.98 9.75 8.89 0.99 11.41 10.13 1.01 65 (18.3) 300 8.37 7.69 0.89 500 STAGE 1 10.10 9.21 0.88 650 10.55 9.37 0.81 70 (21.1) 8.22 7.56 0.94j 9.93 9.05 0.93 7 10.36 9.20 0.84 75 (23.3) 8.07 7.42 0.98 9.75 8.89 0.99 10.17 9.03 0.89 INDOOR AIR 25VNA824B / FE4ANF002L Heating Efficiency Mode Outdoor Coil Entering Air Temperature ° F (° C) 37(2.8) 47(8.3) 57 (13.9) EDB ,F (, C) ID SCFM Capacity MBtuh Total Integ# Total Sys. KWt ID SCFM Capacity MBtuh Total Sys. KWt ID SCFM Capacity MBtuh Total Sys. KWt Total Integ# Total Integ# 65 (18.3) 825 21.73 19.77 1.82 21.46 19.52 1.92 825 21.18 19.27 2.02 STAGE 5 24.94 24.94 1.89 650 16.7 16.71 1.01 70 (21.1) 24.60 24.60 1.99 16.37 16.37 1.08 75 (23.3) 24.26 24.26 2.10 16.03 16.03 1.16 65 (18.3) 650 13.45 12.24 77 0.95 13.21 12.02 1.01 650 12.98 11.81 1.07 STAGE 3 15.09 15.09 7777 0.99 650 16.71 16.71 1.01 70 (21.1) 14.83 14.83 1.06 16.38 16.38 1.09 75 (23.3) 14.56 14.56 1.13 16.07 16.07 1.16 65 (18.3) 650 11.91 10.84 0.81 11.62 10.58 0.87 585 11.38 10.35 0.93 STAGE 1 7.42 7.42 -77777 0.37 585 7.98 7.98 0.37 70 (21.1) 7.20 7.20 0.42 7.74 7.74 0.42 75 (23.3) 6.99 6.99 0.46 7.52 7.52 0.47 Operation in this area is restricted to maintain reliable system operation and customer comfort. The system will default to the next available stage Stage 5 - Compressor speed limited to stage four at 7 and stage three at 57 outdoor; Stage t - Compressor speed limited to stage three at 7 and 17 and to stage two at 27 and 37 outdoor. See additional notes on page 41 GUIDE SPECIFICATIONS GENERAL AIR-COOLED, SPLIT -SYSTEM HEAT PUMP 25VNA8 System Description Outdoor -mounted, air-cooled, split -system heat pump unit suitable for ground or rooftop installation. Unit consists of a hermetic compressor, an air-cooled coil, forward -swept blade propeller -type condenser fan, and a control box. Unit will discharge supply air upward as shown on contract drawings. Unit will be used in a refrigeration circuit to match up to a packaged fan coil or coil unit. Quality Assurance Unit will be rated in accordance with the latest edition of AHRI Standard 240. Unit will be certified for capacity and efficiency, and listed in the latest AHRI directory. Unit construction will comply with latest edition of ASHRAE and with NEC. Unit will be constructed in accordance with UL standards and will carry the UL label of approval. Unit will have C-UL approval. Unit cabinet will be capable of withstanding Federal Test Method Standard No. 141 (Method 6061) 500-hr salt spray test. Air-cooled condenser coils are pressure tested and the outdoor units are leak tested. Unit constructed in IS09001 approved facility. Delivery, Storage, and Handling Unit will be shipped as single package only and is stored and handled per unit manufacturer's recommendations. Warranty (for inclusion by specifying engineer) U.S. and Canada only. PRODUCTS Equipment Factory -assembled, single -piece, air-cooled heat pump unit. Contained within the unit enclosure is all factory wiring, piping, controls, compressor, refrigerant charge Purono (R-410A) refrigerant, and special features required prior to field start-up. Unit Cabinet Unit cabinet will be constructed of galvanized steel, bonderized, and coated with a powder coat paint. Fans Condenser fan will be direct -drive propeller type, forward swept blade, discharging air upward. Condenser fan motors will be totally enclosed, 1-phase type with class B insulation and permanently lubricated. Shafts will be corrosion resistant. Fan blades will be statically and dynamically balanced. Condenser fan openings will be equipped with coated steel wire safety guards. Compressor Compressor will be hermetically sealed. Compressor will be mounted on rubber vibration isolators. Compressor will be covered with a sound absorbing blanket. Condenser Coil Condenser coil will be air cooled. Coil will be constructed of aluminum fins mechanically bonded to copper tubes which are then cleaned, dehydrated, and sealed. Refrigeration Components Refrigeration circuit components will include liquid -line front -seating shutoff valve with sweat connections, vapor -line front -seating shutoff valve with sweat connections, system charge of Purono (R-410A) refrigerant, POE compressor oil, accumulator, charge compensator, electronic expansion valve, and reversing valve. Unit will be equipped with high-pressure switch, suction pressure transducer, and filter drier for Puron® refrigerant. Operating Characteristics The capacity of the unit will meet or exceed Btuh at a suction temperature of °F (°C). The power consumption at full load will not exceed kW. Combination of the unit and the evaporator or fan coil unit will have a total net cooling capacity of Btuh or greater at conditions of CFM entering air temperature at the evaporator at °F (°C) wet bulb and °F (°C) dry bulb, and air entering the unit at °F ff). The system will have a SEER of Btuh/watt or greater at DOE conditions. Electrical Requirements Nominal unit electrical characteristics will be v, single phase, 60 hz. The unit will be capable of satisfactory operation within voltage limits of v to V. Unit electrical power will be single point connection. Control circuit will be 24v. Compliant with EEC 61000-4-5 Transient Surge Requirement. Special Features Refer to section of this literature identifying accessories and descriptions for specific features and available enhancements. Infinity control with appropriate software version is required for full featured operation. M SYSTEM DESIGN SUMMARY 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. we. 2. This product is not qualified for low ambient cooling operation. Minimum cooling outdoor operating temperatures: - Communicating systems: 40°F (4.44°C) - Non -communicating systems: 55°F (12.8°C) 3. The maximum outdoor operating ambient in cooling mode is 115 °F (46.11 °C). 4. Minimum outdoor operating air temperature for heating mode is 10°F (-12.2°C). 5. Maximum outdoor operating air temperature for heating mode is 66°F (18.9°C). 6. For reliable operation, unit should be level in all horizontal planes. 7. This unit is qualified for up to 100 ft (30.5 m) equivalent length of line set without additional accessories. 8. If any refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36 in. (914.4 mm) may be buried without further consideration. Do not bury refrigerant lines longer than 36 in. (914.4 mm). 9. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided. 10. Do not apply capillary tube indoor coils to these units. 11. Puron refrigerant TXV required on indoor coil. 43 r Product Data PREMIUM ENVIRONMENTALLY RESPONSIBLE FAN COIL The latest in technology makes the FE4A and FESA fan coil models the most advanced air handlers available. With attention to quiet, efficient, and comfortable operation, Carrier has developed a new benchmark for homeowner comfort and ease of installation. The FE4A and FESA utilize the Infinity° Control as a required accessory to enable state of the art smart —diagnostics capability. This enables faster troubleshooting, providing ease of service and repair. The FE4A and FESA also provide a 4—wire hook up with matching outdoor unit and the Infinity° Control. This makes installation simpler and a lot quicker than with conventional fan coils. The FE4A and FESA have advanced technology that allows the fan coil to self —configure with a matching outdoor unit and the Infinity's Control, cutting down on installation time. The FE4A and FESA feature Purono refrigerant, the chlorine —free alternate that is the future for the residential heating and cooling industry. The FE4A and FESA using Puron® refrigerant maximize performance for environmentally responsible systems. In addition to environmental safety, these systems are 30 to 40% more efficient than standard heating and cooling systems, thereby combining excellence in efficiency and environmental sustainability. The FE4A and FESA provide these benefits due to Carrier's command of Electronically Commutating Motor (ECM) technology. These motors are extremely efficient at all speeds, and enable the FE4A and FESA to operate at the correct speed to deliver airflow precisely, ensuring proper performance across a wide range of duct static pressures. This adaptive efficiency also makes installation quality easier to achieve for today's demanding homeowner. Carrier's command of ECM technology may be most evident in the comfort advantages that an ECM can deliver. For true comfort, the homeowner can achieve command of both temperature and humidity in cooling and heating modes. Another feature which sets the FE4A and FESA apart is the factory —installed TXV, which enhances efficiency and provides compressor —protecting operation at all recommended conditions. Grooved tubing, louvered aluminum fins, and the large face areas of the FE4A and FESA refrigerant coils also provide superior efficiency, for high SEER and HSPF performance. Carrier leads the way in condensate control, a hallmark of these multipoise fan coils. All of these featured components are protected within a rugged, pre —painted metal cabinet lined with super —thick, high —density insulation. For neat, high quality installations, the unit exterior features sweat refrigerant connections for simple leak free performance, and multiple electrical entry for both high and low voltage service. Assembled at the factory compliant with low leak requirements of less than 2% cabinet leakage rate at 0.5 inches W.C. and 1.4% cabinet leakage rate at 0.5 inches W.C. when tested in accordance with ASHRAE 193 standard. FEATURES Smart Diagnostics • Self configuring (ease of installation) • Easier troubleshooting, providing faster service and repair • Energy Tracking capability with the Infinity° Series Wall Control. (Energy Tracking has the ability to monitor and estimate the energy consumption of your Infinity° system.) Environmentally Responsible Refrigerant Technology • Puron® refrigerant the chlorine —free, non —ozone depleting refrigerant • Thermostatic Expansion Valve (TXV) designed to maximize performance with Puron® refrigerant Energy Efficient Operation • Electronically Commutated Motor (ECM) operates efficiently at all speeds • Maximizes efficiency of heating and cooling systems • Ultra —low power consumption during fan only operation Comfort Control • Warm, comfortable heating air temperatures • Unmatched humidity control Airflow and Sound Technology • Logarithmic spiral blower housings for high blower efficiency and quiet operation • Diffuser air discharge section for high airflow efficiency and quiet, smooth operation • High duct static capability • Design meets stringent regulations for cabinet air leakage of less than 2% when tested at 0.5 inches W.C., and cabinet air leakage less than 1.4% at 0.5 inches W.C. when tested in accordance with ASHRAE 193 standard. Condensate Control and Disposal Technology • Minimal standing water — less microbial growth for improved IAQ and reduced condensate line clogging and related condensate leakage • Condensate fittings relocated away from turbulent airflow patterns at the blower entrance for improved condensate control performance • Overflow feature for slope coil units allows condensate to exit the unit without damage to product under clogged primary and secondary line conditions • Tested for condensate disposal at conditions much more severe than those required by ARI • Primary and secondary drain connections to comply with HUD • All pans constructed of an injection molded glass —filled polycarbonate engineered resin material, with brass drain connections • High density, super thick cabinetry insulation with vapor barrier • Pre —painted galvanized sheet metal cabinet Heat Transfer Technology • Grooved tubing • Lanced sine wave aluminum fins • Discreet refined counterflow refrigerant circuitry • Bi—flow hard —shutoff TXV metering device Quality Assisting, Ease of Installation and Service Features • Easy 4 wire hook up: convenient and reduces installation time. • FE4A unit is multipoise • FE5A unit is upflow/downflow only (single drain pan). • Provision made for suspending from roof or ceiling joints • Modular cabinet on sizes 003 through 006 • Sweat connections for leak free service • Multiple electrical entry for application flexibility (high and low voltage) • Low voltage terminal strip, to safely hold connections within the cabinet • Cabinet construction features innovations designed to prevent cabinet sweating Controls and Electrical Features • Easy plug connection provided for quick installation of accessory heater packages • 40VA 208/230v transformer • Replaceable 3—amp blade —type auto fuse protects against transformer secondary short Filter Features • Factory supplied filter • Cleanable polyester filter media • Filter "springs" out for easy access — no tools required • Newly improved filter rack area — filter door insulation added for an improved air seal MODEL NUMBER NOMENCLATURE 1 2 3 4 5 6 7 8 9 10 11 12 F E 4 A N B 0 0 2 0 0 0 Product F = Fan Coil Type E = Infinity®, VS, Puron® Refrigerant Position 4 = Multi —poise 5 = Upflow / Downflow Series A Electrical N = 208/230v, 1 ph-60 Hz ArmorTech Coil Type T00 = Tin—plated 000 = Copper L00 = Aluminum Capacity 002 = 18-36,000 003 = 24-42,000 004 = 24-42,000 005 = 30-48,000 006 = 36-60,000 Cabinet / Insulation B = Modular F = Single piece Useofthe AHRICertifietl TM TM Mark indicates a manu participation in the U program For verification C& of certification for Individual 11,j products, go to vn—hridir-tory-g. ISO 9001 GMI-SAI Global 3 Am ON VILW NOTE: I. SERIES DESIGNATION IS THE I4TH POSITION OF UNIT PRODUCT NUMBER DISCONNECT OA C IACUIT BAEANEA LOCATION UNIT CONNECTION SIZES LOWE A, CONTROL, d EL EC iA IC HEATER SUCTION: 002 d 003 - 3//" I. D. SWEAT ACCESS PANEL ppN . 00R - 7/8" I. D. SWEAT LIQUID: 3/8' I.D. SWEAT CONDENSATE: 3/4" FPT OANEL IL ACCESS P 2 5/8' d II/I6' ING IOUID LINE CONN ECiION LIQUID LINE ,4A 3/I6' CONNECTION UCTION LINE CONNECTION10 T/I6- SUCTION LINE 10 3/4" CONNECTION 9 I/2'. 6 O I 1 2 I/8" NOTE: ALLOW 21" FROM FRONT FOR SEA, ICE 2 1/16. 10 3/16' 7/8' 1. � 3/4' OUT LET AIA '—ALTERNATE T/8",I 3/32',2'DIA. N.O.'S NOTE: MODULAR FOR HIGH VOLTAGE UNITS WLL HAVE POWER WIRING OPPOSITE SIDE A TWO - PIECE CABINET — OPTIONAL FIELD CONVEA TIED RIGHT SIDE RETURN OPENING ISLOPE COIL UNITS ONLY) � I I/2" Ax H FOR MODULAR UNITS 8" FILTER ACCESS OPENING 1• OPENING D PANEL SLOPE COIL DETAILS CONNECTION LOCATIONS SNOWN FOR OR BONS ACCESS PANEL CONFI6 FOR SLOPE COILS DOWNFLOW OR HOR11. AIGHi APPLICATIONS 11/4" 1913/I6" RIGHT SIDE VIEW L 21n° SHOWN WITH LOCATIONS INLET AIA FRONT VIEW 'A' COIL DETAILS CONNECTION FOR UPFLOW ORNOAI,. APPLICATIONS T APPLICATIONS LEFT APPLICATIONS AND "A" COILS DOWNFLOW APPLICATIONS INLET AIR DIMENSIONS A B C D E H* UNIT SIZE in MIT in mm in mm in. MUM in mm in mm FE4A 002 42-11/16 1084 17-5/8 448 15-3/4 400 15-5/8 397 10-3/4 273 FE4A 003* 53-7/16 1357 21-1/8 537 19-1/4 489 19-1/8 486 19-3/16 487 28-5/16 719 FE4A 005 53-7/16 1357 21-1/8 537 19-1/4 489 19-1/8 486 19-1/2 495 FE4A 005* 53-7/16 1357 21-1/8 537 19-1/4 489 19-1/8 486 19-1/2 495 28-5/16 719 FE4A 006* 59-3/16 1503 24-11/16 627 22-3/4 578 22-11/16 576 25-1/4 641 34-1/16 865 FE5A 004* 59-3/16 1503 24-11/16 627 22-3/4 578 22-11/16 576 25-1/4 641 34-1/16 865 * Modular Cabinet NOTES: I. CONDENSATE PAN DRAIN CAPS NOT SHOWN FOR CLARITY. SLOPE COI 6" TYP. AIRFLOW (2 PLACES)• AIRFLOW 2 3116" iYP. f I 12 PLACESIx L1' TYR. PRIMARY DAAI 12 PL ACES(• 3/4" SECONDARY DRAIN F G PRIMARY DAAI I I/d" SECONDARY DRAIN 13/I6' TYP.+ 5/I6' TIP SECONDARY DRAIN ® PA I MARY DRAIN ` © ® 1 TYP6.I 1 1/2" /d' � I' iYP. T Id/PLLACESI� TYP.x 5/8" 2 9/16" 12 PLACES Ix 7l8 2 T/8• 2 3TY P! 3 I/4" ITYP6•� P.' HORIZ. LEFT a PLace51' UPFLOW DOWNFLOW (AS SHIPPED) (AS SHIPPED) (FIELD CONVERTED) /I6" TYP. • HORIZONTAL MOUNT LOCATIONS - DIMPLES PROVIDED IN TOP PANEL, (d PLACES) AND DACN OF CABINET IN CABINET RDWAR E. HOLES FPROIELD IDED AIRFLOW AIRFLOW 2 3PLAC TYP . 136' DI A. HORIZONTAL HANGING HARDWARE TO BE FIELD SUPPLIED. } 12 PLACES), I+ --I" TYP © 12 PLACES) © Q 15/8" ® I/2" TYP.+ Tl8" F P.+ HORIZ. RIGHT (FIELD CONVERTED) SECONDARY DRAIN F d 3/d' O 0 G I PANAAY DR AI 3 I/16" O SECONDARY DRAIN AIMAAY DRAIN PRIMARY DRAIN 13/1S16 I ' SECONDARY DRAIN iYPx r r TYP . SECONDARY DRAIN 1 O O 0 PRIMARY DRAIN O r ®• O O O O 3' I'D © 12 IL YAM). I+ ® © L IT1i I/2- T /2 I/2' S/16" 3 1/I6" T/I6" TYP, �-F �118 3/I6" TYP+ 5 7/e' 2 II/16' _{ yllll TYP+ d 3l d" fd PLAC ES I• TYP.+ i/g13/16' 2 3/I6' 113116 rrPx TTra•' (2 PLACES)- DOWNFLOW TYP. HORIZ. RIGHT TVPe• HORIZ. LEFT UPFLOW (FIELD CONVERTED) (FIELD CONVERTED) (AS SHIPPED) (AS SHIPPED) A DIMENSIONS F G COIL CONFIGURATION SHIPPING WEIGHT UNIT SIZE in mm in mm Slone FE4A 002 18-9/16 472 18-1/4 464 — Yes 135 / 61 �tas�oeS I U/ I U e"* -- ..- _9g eeTe� FE4A 003* 26-15/16 684 27-1/2 699 Yes — 150 / 68 FE4A 005 27-1/4 692 26-15/16 684 — Yes 172 / 78 FE4A 005* 27-1/4 692 26-15/16 684 — Yes 172 / 78 FE4A 006* 32-15/16 837 32-5/8 829 — Yes 207 / 94 FE5A 004* 32-15/16 837 32-5/8 829 — Yes 200 / 91 * Modular Cabinet PHYSICAL DATA NOMINAL DIMENSIONS ORDERING NO. FIELD -INSTALLED HEAT COOLING CA - (kW) PACITY (BTUH) Height Width Depth FE4ANF002000 18,000 42-11/16-in10 17-5/8-in 448 22-1/16-in FE4ANF002T00 5, 8, 9, 10, 15, 20 to 84 mm mm 560 mm FE4ANF002L00 36,000 FE4ANF003000 24,000 53-7/16-in 21-1/8-in537 22-1/16-in FE4AN(B,F)003T00 5, 8, 9, 10, 15, 18, 20 to 1357 mm mm 560 mm FE4AN (B, F)003L00 42,000 FE4ANF005000 30,000 53-7/16-in 21-1/8-in537 22-1/16-in FE4AN(B,F)005T00 5, 8, 9, 10, 15, 18, 20, 24, 30 to 1357 mm mm 560 mm FE4AN (B, F)005L00 48,000 FE4ANB006000 36,000 59-3/16-in 24-11/16-in 22-1/16-in FE4ANB006T00 8, 9, 10, 15, 18, 20, 24, 30 to 1503 mm 627 mm 560 mm FE4ANB006L00 60,000 FE5ANB004T00 24,000 59-3/16-in 24-11/16-in 22-1/16-in FE5ANB004L00 5, 8, 9, 10, 15, 18, 20 to 1503 mm 627 mm 560 mm 42,000 COIL Refrigerant Metering Device TXV Size 2 Ton Configuration A Rows-Fins/In. Face Area (Sq Ft) 3.46 MATCHES OUTDOOR UNIT SIZES Nominal Cooling Tons 1.5, 2, 2.5, 3 FAN Air Discharge CFM/Ton (Nominal Clg/Htg) Motor HP (ECM) 1/2 Filter 16-3/8-in 21-1/2-in (546 mm) x (417 mm) CABINET CONFIGURATION OPTIONS 1-piece SPECIFICATIONS PuronSO Refrigerant (R-410A) TXV 3 Ton 4 Ton 5 Ton Slope A A 3/14.5 3.46 5.93 7.42 SHIPPING WEIGHT lb / kg 135 lb 61 kg 150 lb 68 kg 172 lb 78 kg 207 lb 94 kg 200 lb 91 kg 3 Ton A 7.42 2,2.5,3,3.5 2.5,3,3.5,4 3,3.5,4,5 2,2.5,3,3.5 Upflow, Downflow, Horizontal Upflow, Downflow 350+ 1/2 1/2 3/4 3/4 19-7/8-in 19-7/8-in 23-5/16-in 23-5/16-in (505 mm) (505 mm) (592 mm) (592 mm) 1-piece / Modular 1-piece / Modular Modular Modular 6 PERFORMANCE DATA AIRFLOW DELIVERY — COOLING, HEATING, ELECTRIC HEATING MODES The FE4 and FE5A fan coils will provide airflow at a rate that is documentation for the User Interface for more information on how requested by the Integrated System User Interface during air the User Interface controls the fan coil. Safe operation of electric conditioning or heat pump heating (without electric heat) modes. heaters requires airflow delivery at or above the minimum CFM for The nominal airflow for both heating and cooling modes is 350 electric heater application listed in the chart below. The fan coil cfm/ton nominal size of the outdoor unit installed. The airflow will adjust its airflow delivery to maintain safe airflow as operating actually requested by the User Interface is modified by its internal mode and staging conditions require. algorithms for zoning, comfort or efficiency concerns. Refer to the FE4A/FE5A FAN COIL AIRFLOW DELIVERY CHART (CFM) — ELECTRIC HEATING MODELS ELECTRIC HEATER kW RANGE MODEL FE4A OUTDOOR UNIT CAPACITY BTUH 5 9 10 15 20 24 30 EMERGENCY 625 625 675 775 950 18,000 625 625 675 002 24,000 650 725 775 900 30,000 800 875 875 925 1125 36,000 975 975 975 1025 1125 EMERGENCY 675 700 775 850 1050 24,000 675 875 875 1100 1150 003 30,000 800 875 875 1100 1150 36,000 975 975 1025 1150 1250 42,000 1125 1125 1125 1150 1350 EMERGENCY 675 700 775 850 1050 1400 1425 30,000 800 875 875 1100 1150 005 36,000 975 975 1025 1150 1250 42,000 1125 1125 1125 1150 1250 48,000 1305 1305 1305 1305 1350 1500 1600 EMERGENCY 1050 1050 1050 1050 1125 1750 1750 36,000 1050 1050 1100 1350 1350 006 42,000 1125 1125 1150 1350 1350 48,000 1300 1300 1300 1350 1500 1750 1750 60,000 1625 1625 1625 1625 1750 1750 1750 ELECTRIC HEATER kW RANGE MODEL FE5A OUTDOOR UNIT CAPACITY BTUH 5 9 10 15 20 24 30 EMERGENCY 675 775 775 900 1125 24,000 975 975 975 004 30,000 1050 1050 1100 1125 36,000 1050 1050 1100 1350 1350 42,000 1125 1125 1150 1350 1350 Note 1: Emergency — Air conditioner with electric heater application, or emergency heat. Note 2: These airflows are minimum airflows as UL listed. Note 3: Dashed entry indicates that the heater/fan coil/outdoor unit combination is not approved. Do not apply. 7 CFM - Cubic Ft per Minute EWB - Entering Wet Bulb (°F / °C) SHC - Gross Sensible Capacity 1000 Btuh BF - Bypass Factor NOTES: 1. Contact manufacturer for cooling capacities at conditions other than shown in table. 2. Formulas: Leaving db = entering db -sensible heat cap. 1.09 x CFM Leaving wb = wb corresponding to enthalpy of air leav- ing coil (hiwb) hlwb = hewb -total capacity_(Btuh) 4.5 x CFM where hewb = enthalpy of air entering coil. Direct inter- polation is permissible. Do not extrapolate. 3. SHC is based on 80°F db temperature of air entering coil. Below 80°F db, subtract (Correction Factor x CFM) from SHC. Above 80°F db, add (Correction Factor x CFM) to SHC. 4. Bypass Factor = 0 indicates no psychometric solution. Use bypass factor of next lower EWB for approximation. ESTIMATED SOUND POWER LEVEL (dBA) LWB - Leaving Wet Bulb (°F / °C) TC - Gross Cooling Capacity 1000 Btuh MBH - 1000 Btuh SHC CORRECTION FACTOR ENTERING AIR DRY-BULB TEMPERATURE (°F) BYPASS 79 78 77 76 75 Under 75 FACTOR 81 82 83 84 85 Over 85 Correction Factor 0.10 1.96 2.94 3.92 4.91 .098 Use formula 0.20 0.87 1.74 2.62 3.49 4.36 shown 0.30 0.76 1.53 2.29 3.05 3.82 below Interpolation is permissible. Correction Factor = 1.09 x (1 - BF) x (db - 80) MODEL CONDITIONS OCTAVE BAND CENTER FREQUENCY SIZE CFM ESP 63 125 250 500 1000 2000 4000 400 0.25 61.0 57.0 55.0 50.0 48.0 46.0 42.0 600 0.25 62.7 58.7 56.7 51.7 49.7 47.7 43.7 800 0.25 64.0 60.0 58.0 53.0 51.0 49.0 45.0 FE4ANF002 1000 0.25 65.0 61.0 57.0 56.0 52.0 50.0 46.0 1200 0.25 65.8 61.8 57.8 56.8 52.8 50.8 46.8 1400 0.25 66.4 62.4 58.4 57.4 53.4 51.4 47.4 400 0.25 61.0 57.0 55.0 50.0 48.0 46.0 42.0 600 0.25 62.7 58.7 56.7 51.7 49.7 47.7 43.7 800 0.25 64.0 60.0 58.0 53.0 51.0 49.0 45.0 FE4ANF003 1000 0.25 65.0 61.0 59.0 54.0 52.0 50.0 46.0 1200 0.25 65.8 61.8 59.8 54.8 52.8 50.8 46.8 1400 0.25 66.4 62.4 58.4 57.4 53.4 51.4 47.4 1600 0.25 67.0 63.0 59.0 58.0 54.0 52.0 48.0 600 0.25 62.7 58.7 56.7 51.7 49.7 47.7 43.7 800 0.25 64.0 60.0 58.0 53.0 51.0 49.0 45.0 1000 0.25 65.0 61.0 59.0 54.0 52.0 50.0 46.0 FE5AN6004 1200 0.25 65.8 61.8 59.8 54.8 52.8 50.8 46.8 1400 0.25 66.4 62.4 60.4 55.4 53.4 51.4 47.4 1600 0.25 67.0 63.0 61.0 56.0 54.0 52.0 48.0 400 0.25 61.0 57.0 55.0 50.0 48.0 46.0 42.0 600 0.25 62.7 58.7 56.7 51.7 49.7 47.7 43.7 800 0.25 64.0 60.0 58.0 53.0 51.0 49.0 45.0 FE4ANF005 1000 0.25 65.0 61.0 59.0 54.0 52.0 50.0 46.0 1200 0.25 65.8 61.8 59.8 54.8 52.8 50.8 46.8 1400 0.25 66.4 62.4 58.4 57.4 53.4 51.4 47.4 1600 0.25 67.0 63.0 59.0 58.0 54.0 52.0 48.0 600 0.25 62.7 58.7 56.7 51.7 49.7 47.7 43.7 800 0.25 64.0 60.0 58.0 53.0 51.0 49.0 45.0 1000 0.25 65.0 61.0 59.0 54.0 52.0 50.0 46.0 1200 0.25 65.8 61.8 59.8 54.8 52.8 50.8 46.8 FE4ANB006 1400 0.25 66.4 62.4 60.4 55.4 53.4 51.4 47.4 1600 0.25 67.0 63.0 61.0 56.0 54.0 52.0 48.0 1800 0.25 67.5 63.5 59.5 58.5 54.5 52.5 48.5 2000 0.25 68.0 64.0 60.0 59.0 55.0 53.0 49.0 2150 0.25 68.3 64.3 60.3 59.3 55.3 53.3 49.3 *Est. sound power levels have been derived using the method described in the 1987 ASHRAE HVAC Systems & Applications Handbook, chapter 52, p. 52.7. AIRFLOW PERFORMANCE CORRECTION FACTORS STATIC PRESSURE CORRECTION (in wc) HEATER KW ELEMENTS Sizes 002-005 Size 006 0 0 +.02 +.03 5 1 +.01 +.02 8,10 2 0 0 9,15 3 -.02 -.03 20 4 -.04 -.06 18, 24, 30 6 -.06 -.10 The FE4A airflow performance table was developed using fan coils with 10kW electric heaters (2 elements) in the units. For fan coils with heaters made up of a differ- ent number of elements, the external available static at a given CFM from the table may be corrected by adding or subtracting pressure. Use table for this correction. 10 FACTORY -INSTALLED FILTER STATIC PRESSURE DROP (in wc) MODEL CFM FE4A 400 600 800 1000 1200 1400 1600 1800 2000 002 0.020 0.044 0.048 0.072 0.100 003 - 0.020 0.035 0.051 0.070 0.092 - - - 005 - - 0.035 0.051 0.070 0.092 0.120 - - 006 0.038 0.053 0.070 0.086 0.105 0.133 MODEL CFM FE5A 400 600 800 1000 1200 1400 1600 1800 2000 004 - 0.015 0.026 0.038 0.053 0.070 - - - AIR DELIVERY PERFORMANCE CORRECTION COMPONENT PRESSURE DROP (in wc) AT INDICATED AIRFLOW (DRY TO WET COIL) MODEL CFM FE4A 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 002 0.012 0.016 0.022 0.028 0.034 0.040 0.049 003 - 0.026 0.034 0.042 0.052 0.063 0.075 0.083 0.091 0.098 0.110 005 - 0.006 0.008 0.010 0.012 0.015 0.017 0.020 0.023 0.027 0.030 CFM 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 006 0.013 0.016 0.018 0.020 0.023 0.027 0.030 0.034 0.039 0.044 0.048 MODEL CFM FE5A 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 004 0.004 0.005 0.007 0.009 0.011 0.013 0.016 0.018 0.020 0.023 - NOTE: Subtract the above pressure drop corrections from unit airflow data when that component or condition is used. The remaining external static pressure will be available for the duct system. UNITS WITHOUT ELECTRIC HEAT BRANCH CIRCUIT UNIT SIZE VOLTS -PHASE FLA MIN CKT AMPS Min Wire Size Awg* Fuse/Ckt Bkr Amps 002 208/230-1 4.3 5.4 14 15 003 208/230-1 4.3 5.4 14 15 005 208/230-1 4.3 5.4 14 15 004,006 208/230-1 6.8 8.5 14 15 * Use copper wire only to connect unit. If other than uncoated (non -plated) 75°C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used consult applicable tables of the National Electric Code (ANSI/NFPA 70). NOTE: If branch circuit wire length exceeds 100 ft / 30.5 m, consult NEC 210-19a to determine maximum wire length. Use 2 % voltage drop. FLA - Full Load Amps ACCESSORY ELECTRIC HEATERS HEATER kW VOLTS/ STAGES (kW INTERNAL FAN COIL HEATING CAP. INTELLIGENT PART NO. @° PHASE OPERATING) CIRCUIT SIZE USED @ 230Vt HEAT CAPABLE 240V PROTECTION WITH (kW OPERATING) KFCEHO501 N05 5 230/1 5 None All 15,700 - KFCEH0901 N10 10 230/1 10 None All 31,400 - KFCEH3001F15 15 230/1 5,15 Fuses** All 47,100 5, 10, 15 KFCEH3201 F20 20 230/1 5,20 Fuses** All 62,800 5, 10, 15, 20 KFCEH2901 N09 9 230/1 * 3,9 None All 28,300 3, 6, 9 KFCEH1601315 15 230/3 5,15 None All 47,100 - KFCEH3401 F24 24 230/3t 8, 16, 24 Fuses 005,006 78,500 8, 16, 24 KFCEH3501 F30 30 230/3t 10, 20, 30 Fuses 005,006 94,200 10, 20, 30 KFCEH2401C05 5 230/1 5 Ckt Bkr All 15,700 - KFCEH2601 C10 10 230/1 10 Ckt Bkr All 31,400 - KFCEH3101C15 15 230/1 5,15 Ckt Bkr All 47,100 5, 10, 15 KFCEH3301C20 20 230/1 5,20 Ckt Bkr All 62,800 5, 10, 15, 20 * Field convertible to 3 phase. t These heaters field convertible to single phase. ** Single point wiring kit required for these heaters in Canada. # Blower motor heat not included. ELECTRIC HEATER INTERNAL PROTECTION HEATER kW PHASE FUSES QTY / SIZE CKT BKR QTY / SIZE* 5 1 - 1/60 8 1 - 1/60 9 1/3 - - 10 1 - 1/60 15 1 2/30, 2/60 2/60 15 3 - - 18 3 - - 20 1 4/60 2/60 24 3/1 6/60 - 30 3/1 6/60 - * All circuit breakers are 2 pole. It ACCESSORY ELECTRIC HEATER ELECTRICAL DATA BRANCH CIRCUIT P H INTERNAL HEATER AMPS 208/230V Min Ampacity Min Wire Size (AWG) Min Gnd Wire Size Max Fuse/CM Bkr Amps Max Wire Length HEATER kW A CIRCUIT 208/230V** 208/230Vtt 208/230V 208/230V 208/230V (11)# PART NO. S PROTEC- E TION Single Dual Circuit Single Dual Circuit Single Dual Circuit Single Dual Circuit Single Dual Circuit Single Dual Circuit 24W 208V circuit L1,L2 L3,L4 Cireult L1,L2 L3,L4 circuit L1,L2 L3,L4 Circuit L1,L2 L3,L4 Circuit L1,L2 L3,L4 Circuit L1,L2 L3,L4 KFCEH0501 N05 5 3.8 1 None 18.1/20.0 — — 31.2/33.5 — — 8/8 — — 10/10 — — 35/35 — — 85/88 — — KFCEH2401C05 5 3.8 1 Ckt Bkr 18.1/20.0 — — 31.2/33.5 — — 8/8 — — 10/10 — — 35/35 — — 85/88 — — KFCEH0801N08 8 6.0 1 None 28.9/32.0 — — 44.7/48.5 — — 8/8 — — 10/10 — — 45/50 — — 59/60 — — KFCEH2501C08 8 6.0 1 Ckt Bkr 28.9/32.0 — — 44.7/48.5 — — 818 — — 10/10 — — 45/50 — — 59/60 — — KFCEH2901NOV 9 6.8 1 None 32.8/36.0 — — 49.5/53.5 — — 816 — — 10/10 — — 50/60 — — 54/87 — — KFCEH2901N09*# 9 6.8 3 None 18.8/20.8 — — 32.0/34.5 — — 818 — — 10/10 — — 35/35 — — 83/85 — — KFCEH0901 N10 10 7.5 1 Nona 36.2/40.0 53.8/58.5 6/6 10/10 60/60 78/80 KFCEH2601C70 10 7.5 1 C. Bkr W.2/40.0 — — 53.8/58.5 — — 616 — — 10/10 — — 60/60 — — 78/80 — — KFCEH3101C15* 15 11.3 1 Ckt Bkr — 36.2/40.0 18.1/20.0 — 53.8/58.5 22.7/25.0 — 6/6 10/10 — 10/10 10/10 — 60/60 25/25 — 78/80 75/76 KFCEH1601315 15 11.3 3 None 31.3/34.6 — — 47.7/51.8 — — 8/6 — — 10/10 — — 50/60 — — 56/90 — — KFCEH2O01318 18 13.5 3 None 37.6/41.5 — — 55.5/60.4 — — 6/6 — — 10/8 — — 60/70 — — 76/77 — — KFCEH3201F20*1 20 15.0 1 Fuse 72.3/79.9 36.2/40.0 36.2/40.0 98.9/108.4 53.8/58.5 45.3/50.0 3/2 6/6 8/8 8/6 10/10 10/10 100/110 60/60 50/50 85/109 78/80 59/59 KFCEH3301C20* 20 15.0 1 Ckt Bkr — 36.2/40.0 36.2/40.0 — 53.8/58.5 45.3/50.0 — 6/6 8/8 — 10/10 10/10 — 60/60 50/50 — 78/80 59/59 24 18.0 3 Fuse 50.1/55.4 — — 71.2/77.8 — — 4/4 — — 8/8 — — 80/80 — — 94/95 — — KFCEH3401F24*t 24 18.0 1 FUss 86.7/95.5 — — 116.9/127.9 — — 1/1 — — 6/6 — — 125/150 — — 115/116 — — 30 22.5 3 Fuse 62.6/69.2 — — 86.8/95.0 — — 3/3 — — 8/8 — — 90/100 — — 97/98 — — KFCEH3501F30*t 30 22.5 1 Fuse 109.0/120.0 — — 144.6/156.5 — — 0/00 — — 6/6 — — 150/175 — — 117/150 — — FIELD MULTIPOINT WIRING OF 24-AND 30-kW SINGLE PHASE N P kW H HEATER AMPS MIN AY MIN WIRE SIZE (AWG) MAX FUSE/CKT BKR AMPS MAX WIRE LENGTH HEATER PART A 208/230V 208/230V230V**** 208/230Vtt MIN GND WIRE SIZE 208/230V 208/230V (FT)## NO. S 208/230V 240V 208V E L1,L2 L3,1_4 L5,L6 L1,L2 L3,1_4 L5,L6 L1,L2 L3,1_4 L5,L6 L1,L2 L3,1_4 L5,L6 L1,L2 L3,1_4 L5,L6 KFCEH340l F24*t 24 18.0 1 28.9/32.0 28.9/32.0 28.9/32.0 44.7/48.5 36.2/40.0 36.2/40.0 8/8 8/8 8/8 10/10 45/50 40/40 40/40 59/60 73/73 73/73 KFCEH3501 F30*t 30 22.5 1 36.2/40.0 36.2/40.0 36.2/40.0 53.8/58.5 45.3/50.0 45.3/50.0 6/6 8/8 8/8 10/10 60/60 50/50 50/50 78/80 59/59 59/59 * Heaters are Intelligent Heat capable when used with the FE fan coil and Comfort Zone II- or Infinity Control-. t Field convertible to 1 phase, single or multiple supply circuit. $ Field convertible to 3 phase. ** Includes blower motor amps of largest fan coil used with heater. tt Copper wire must be used. If other than uncoated (non —plated), 75°C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the National Electric Code (ANSI/NFPA 70). $$ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%. NOTES: 1. Single circuit application of F15 and F20 heaters requires single —point wiring kit accessory. ACCESSORIES REQUIRED ACCESSORY ITEM ACCESSORY PART KinA FAN COIL SIZE USED WITH Infinity@ Touch Control with Integrated Wi—Fi SYSTXCCITC01 All 1 Infinity@ Touch Control Wi—Fi SYSTXCCITW01 All with bundled router or Infinity@ Touch Control SYSTXCCITN01 All ADDITIONAL ACCESSORIES ITEM ACCESNOORY PART FAN COIL SIZE USED WITH 2. Infinity@ Series 4 Zone Board SYSTXCC4ZC01 All 3. Infinity@ Series Smart Sensor SYSTXCCSMS01—A All 4. Infinity@ Remote Room Sensor SYSTXCCRRS01 All 5. Infinity@ Series Network Interface Module SYSTXCCNIM01 All 6. Disconnect Kit KFADK0201 DSC Cooling controls and heaters 3— through 10—kW KFACB0201 CFB 002 7. Downflow Base Kit KFACB0301 CFB 003,005 KFACB0401 CFB 004,006 8. Downflow Conversion Kit KFADCO201 SLIP 003 KFADC0401ACL 002, 004, 005, 006 9. Single —Point Wiring Kit KFASP0101 SPK Only with 15— and 20—kW Fused Heaters KFAFK0212MED 002 10. Filter Kit (12 Pack) KFAFK0312LRG 003,005 KFAFK0412XXL 004,006 FNCCABCCO017 002 11. Filter Media Cabinet FNCCABCCO021 003,005 FNCCABCCO024 004,006 FILCCFNCO017 002 12. Media Filter Cartridges FILCCFNCO021 003,005 FILCCFNCO024 004,006 GAPABXCC1620 002 13. Infinity@ Series Air Purifier GAPABXCC2020 003,005 GAPABXCC2024 004,006 14. PVC Condensate Trap Kit (50 pack) KFAET0150ETK All 15. Air Cleaner 240—volt Conversion Kit KEAVCO201240 All 16. Downflow/Horizontal Conversion Gasket Kit KFAHDO101SLP All 17. Horizontal Water Management Kit (25 pack) KFAHCO125AAA All KFAFR0101 FRM NA 18. Standard Filter Rack Kit KFAFR0201 FRM 002 KFAFR0301 FRM 003,005 KFAFR0401 FRM 004,006 19. Hydronic Relay Interface Kit KFAIF0101 HWC All 20. Door Gasket Kit ** 344994-751 All * Factory authorized and listed, field installed. ** This kit is for replacement of factory installed gaskets if they are damaged or removed from the fan coil. 13 A170203 Product Data E7 A180218C NOTE: Infmityo System Control compatible with Infmityo rated indoor equipment only. US Patents: Carrier® U.S. Pat No. 7,243,004, Carrier® U.S. Pat No. 7,775,452, pointSET- U.S. Pat No. 7,415,102 INFINITY(SYSTEM _ WORKS WITH Cor amazon alexa INFINITY® SYSTEM CONTROL Carrier specializes in creating a customized home comfort system tailored to your needs with our broad selection of residential heating and cooling products. The Infmityo System Control is the ultimate control center for all of your system components. When you add an Infinity° System Control to a compatible variable speed furnace, fan coil, Infmityo System split or package unit, or small packaged product, you will enjoy longer heating and cooling cycles at lower fan speeds for a more consistent temperature throughout your home. By adding a variable speed, multi -stage, or 2-stage outdoor unit, you will enjoy extra benefits which include better humidity and temperature control as well as a more energy efficient comfort system. When paired with Infinityo Zoning controls, the Infmityo System Control allows you to create up to 8 zones of customized comfort. The Infmityo Zoning system does not require a bypass damper, leaving air temperature (LAT) sensor, or field -installed power transformer. Always install the latest version of software to enable all features of the system. Over -the -Air software updates for Wi-Fi models connected to the Infmity server are automatically downloaded. Software updates via MicroSD are available on HVACpartners, or at www.MylnfmityTouch.com. Wi-RO is a registered trademark of Wi-Fi Alliance Corporation. Amazon Alexa is a trademark of Amazon. Inc. or its affiliates. INDUSTRY LEADING FEATURES/BENEFITS Carrier's revolutionary Infmityo System Control is the smart control of the future. Its unique system self -configuration and diagnostics capabilities make installation and service fast and accurate, helping to avoid costly call-backs. The Infinity° System Control features a high resolution display, making it easier to read. Intuitive prompts let you program everything from humidity levels to fan speeds, giving you the ultimate control over your home comfort. Other features include: 4-wire installation from each major component in the system 2-wire connection to hifimtyo System two or more stage outdoor equipment (including geothermal split units) Infmityo Zoning System compatibility Occupancy sensing to provide comfort when spaces are occupied and energy savings when they're not Intuitive on screen prompts for ease of installation and service Ideal Humidity System' settings are the default; no longer requiring increased system setup — Complete integration of the temperature, humidity and ventilation in every season — For Zoned Systems, auto mode selection to satisfy simultaneous heating and cooling demands in different zones via more aggressive Auto Changeover algorithm --installer must enable — 7-day programmability with Lifestyle Comfort Profiles and Touch-N-Go@ features; complies with California Title 24 programmability requirements — Easy timed -override schedule — Simplified vacation schedules — Day -at -a -glance programming for simplified ease of use — Programmable fan by period — TrueSense- Dirty Filter Detection — Indoor Air Quality pop up service reminders — General maintenance reminder messaging — Wi-Fi@ remote access capability — Upload photo, dealer info, and software updates locally via MicroSD card. Software updates available automatically when connected to the Infinity web server — Compatible with home automation through the SYSTXCCRCTOI or SYSTXCCRWFOI system access modules, or via the C& Home Automation app or Amazon '' Alexa '" interface. — Compatible with Infinity@ System geothermal products (GC and GZ models). Energy Tracking feature for geothermal systems is available with Entering Water Temperature sensor installed in heat pump. MODEL NUMBER NOMENCLATURE 1 2 3 4 5 S Y S T X Product Type InfinityO System Brand / Product CC = Carrier XX or NN = No Brand 6 7 8 9 10 11 C C I T C 0 12 13 14 1 -- B Version B Packaged Quantity 01 Model Type ITC — Black InfinityO System Control with Wi—Fi WIC— White InfinityO System Control with Wi—Fi ICF — Black InfinityO System Control with Wi—Fi (with French Literature) WIF— White InfinityO System Control with Wi—Fi (with French Literature) INFINITY Sl( 'STE)M INFINITY® SYSTEM CONTROL_ =„v,tEvap- (� V COr Com nHedt.0�N IW�Tg reenspeed INTELLIGENCE (141-mm) Fig. 1 - Unit Dimensions -in nm) 1.1-in (2.7-mm) A170101 2 PRODUCT DATA INFORMATION Compatible Communicating Products Compatible with most Infmity° System indoor and outdoor equipment built since 2004; see equipment specifications for details. Home Automation System Interface A cloud -to -cloud Open API (Application Program Interface) is available for the ITC and ITW model Infinity Touch and Infinity System Controls. See the Infmity Systems Open API Getting Started Guide available on www.HVACpartners.com or contact InfmityOpenAPI@carrier.utc.com for more information. The Infmity° System control may also connect to a variety of Home Automation systems using SAM modules. Note that not all Home Automation systems may be compatible. Reference the latest version of the Application Specification titled "SAM Remote Access Application Specification," available on HVACpartners.com to learn more about the latest Home Automation interfaces to the Infmity° systems. Work with the home automation supplier to see if the systems are compatible. If not, you may provide the "Infinity System Open API Getting Started Guide" or the "SAM Remote Access Application Specification" to the home automation supplier to develop an interface with the Infmity° System. Always be sure to obtain the latest version of the application specification from HVACpartners, as we continually update and add home automation interfaces. NOTE: The ability to remotely access and adjust the settings of the Infmity° System Control with the MyInfmity web and mobile applications is dependent on the compatibility of the user's computer, home network and/or mobile device, the Infinity@ System Control, and/or the MyInfinity web server or other system interfaces with, and the availability of, the user's internet service provider or mobile device carrier service. Carrier Corporation makes no representations or warranties, express or implied, including, to the extent permitted by applicable law, any implied warranty of merchantability or fitness for a particular purpose or use, about the compatibility of the user's computer, home network, and/or mobile device, with the Infmity@ System Control, and/or the MyInfmity web server or other system interfaces, with, and the availability of, the user's internet service provider or mobile device carrier service, or that the ability to remotely access and adjust the settings of the Infinity@ System Control will not be negatively affected by the network -related modifications, upgrades, or similar activity of the user's internet service provider or mobile device carrier service. Physical Characteristics Dimensions: See drawing Appearance: Black glass front, silver plastic body Electrical Characteristics/Communication Input Volts/Amps 24VAC Each device in the Infmity° System has a four -pin connector labeled ABCD. It is recommended that the following color code be used when wiring each device: A Green = Data A+ B Yellow = Data B- C White = 24VAC (Com) D Red = 24VAC (Hot) Always verify that the IDU and ODU are well-grounded, and that there are less than 10 volts AC/DC as measured between the cabinets of the IDU and ODU, while the equipment is operating at full capacity. If there is a larger voltage difference between the cabinets of the IDU and ODU, recheck the equipment grounding. Environmental Requirements: Operating Temperature/Relative Humidity: User interface and all sensors: 32°F to 104°F / 0°C to 40°C, 95% RH non -condensing Feature Specifications: Temperature set point range: 50°F to 90°F / 10.0°C to 32.0°C Separate heat and cool setpoints Programming days: 7 day Programming periods: Up to 5 periods per day Advanced Smart Setback (with programming) Touch-N-Goo feature Occupancy Sensing Non -Programmable (installer selectable) Auto Changeover* (may be disabled) Simultaneous Heat Cool Demand Algorithm for zoned systems Programmable fan (installer selectable) Humidity Sensor Offsets Auto Changeover Timer (installer adjustable) Smart Recovery (in heating and cooling) Hold function Copy functions: copy day of week; copy zones Permanent memory Humidity display and control Temperature sensor offsets (indoor and outdoor) TrueSense- Dirty Filter Detection with compatible indoor equipment * See Installation Instructions for details on Auto Changeover and Simultaneous Heat/Cool Demand Algorithm operation. Wiring Requirements: Power supply: 24VAC, 40 VA (minimum), 60 Hz, via indoor equipment ABCD Connector. Zoning systems with a large number of dampers, especially multiple dampers per zone, may require a separate, dedicated, field -installed 24VAC power supply. The SAM module requires an independent, isolated, field -supplied 24VAC power supply. Wiring material: Standard thermostat wire 18 to 22 gauge. Use 18 AWG wiring for wire lengths over 25 feet. Shielded, twisted pair cable for to ABCD communication bus is optional, and may be helpful in electrically noisy environments, or for zoning systems with Smart Sensors. NIM Requirements: IDU NON —COMMUNICATING ODU NIM REQUIRED? Furnace 1—stage A/C No Furnace 2—stage A/C Yes Furnace 1—stage HP Yes Furnace 2—stage HP Yes Fan Coil 1—stage A/C No Fan Coil 2—stage A/C Yes Fan Coil 1—stage HP No Fan Coil 2—stage HP Yes