APPROVED ENG Power Service and Street Light Deferred Submittal PLN2021-0037 Letter of Transmittal December 2, 2022 RAM Job No: 20-024 To: City of Edmonds Public Works Department Engineering Division 121 5th Avenue N. Edmonds, WA 98020 From: Rob Long, PE RAM Engineering 19109 36th Ave W, Suite 100 Lynnwood WA 98036 Subject: Brackett’s Reserve, PLN2021-0037 - Power and Street Light Deferred Submittal Per the City of Edmonds construction plan approval, the applicant shall provide a deferred submittal for the power service and street light locations. Attached is the Snohomish County PUD power service plan that includes the power service layout for the plat and the proposed new street light location (between lots 3 and 4). For reference, attached to this memo is the email correspondence between the applicant, City of Edmonds and PUD discussing the new street light location. The below sketch shows the proposed street light location. Attachments: 1. PUD Power Service Plan (2 pages) 2. Street Light Location email correspondence (8 pages) N NORTH A-55347 & A-55348 112336 & 112337 SCW 4/15/22 GAS IN PLAT CUSTOMER CONSTRUCTED & ENERGIZED DATE: 15-Apr-22 10:01TAGS VAULT: CABLE: VICINITY MAP UGND 14516-1 FEES REQ'D E# DATE APPROVED PHASECIRCUIT NO SUBSTATION PRIMARY RECEIPT# WORK IN RIGHT OF WAY UGND NO ORDER APPROVED JPN# SCALE COMMERCIAL RESIDENTIAL RESIDENTIAL COMMERCIAL BASIC FEE $=$@FT BASIC FEE LEU# LEO# $@ =$ VAULT PERMIT # ONE CALL DATE LOCATION MAP PAGE PRE-CONSTR REQUIREMENTS (DATE GRANTED) TREE TRIM TREE TRIM $ $ PRIMARY OVERHEAD RT PUD LOCATOR BACKHOE POLE STENCILING FROM TO TAKE OFF POLE FOREIGN CONTACTS EASEMENTS REQUIRED NOT REQUIRED PERMITS CITY COUNTY STATE YES NO MISCELLANEOUS FEES TOTAL DUE DATE PAID $ $ $ $ $ $ $@ $ SECONDARY UNDERGROUND $@ $ PRIMARY UNDERGROUND DATE WORK COMPLETED FOREMAN REASON FOR WORK POLE NO LOCATION DATE AREA ENGINEER DRAFTER ROAD CROSSINGS ONLY DATEAPPVNO.DESCRIPTION DATEAPPV DESCRIPTION DATEAPPVNO.DESCRIPTION REVISIONS AS-BUILT ENGINEER PHONE CUSTOMER CONTACT ¼S PUBLIC UTILITY DISTRICT NO 1 SNOHOMISH COUNTY PROVIDE 1Ì PRIMARY UNDERGROUND DISTRIBUTION SYSTEM FOR PRINTED NOTED /'= /'= PHONE SECONDARY REQUEST NO. GIS GIS QC AS-BUILT JOINT USE DATE & INSPECTOR STREET LIGHTING YES NO CELLULAR DATE OPERATION M&R M&R GIS Ph 9125 240TH ST SW, EDMONDS 98026 LYNNWOOD PLI 15330 SW 31 27 4 THE PLAT OF BRACKETS RESERVE (11 LOTS) 3/3/22 S ELWIN EJS 100084031 0060 14516-1 RICHMOND PARK 12-5217 1 PACIFIC RIDGE DRH LLC JOHN MIRANTE (206) 619-4009 JOINT TRENCH W/PSE 474,H3 JOINT TRENCH ZIPLY & CATV JOINT BORE ZIPLY & CATV FILE: W:\UG\14500\14516-1.dgnWOODWAYPARKDOGWOOD 226THST SW EDMONDS WAY 100thAVW244TH ST SWLNRD3RDAV S220TH ST SW KING COUNTYPUGET SOUNDWOODWAY EDMONDS HWY 9995TH PL W2 10 8 7 1 3 4 5 6 9 11 998 999 CABLE VAULTS TRANSFORMERS ASSY#12U610 MAKE SER UTC A-55347 ALL FOOTAGES APPROXIMATE BY CUSTOMER 7200-240/120V BY CUSTOMER 75 KVA S D W U LAYOUT LEGEND: OVHD SCHEMATIC LEGEND: J J P S P ADDITIONAL UGND TAPPED AT T/O POLE FAULT INDICATOR FEED THRU BUSHING ON TRANSFORMER EXISTING OVERHEAD PRIMARY UNDERGROUND CABLE FUSE 200 AMP J-BOX 1 Ì TRANSFORMER SL UNDERGROUND LOCATOR MARKER STREET LIGHT FIRE HYDRANT WATER MAIN/METER STORM DRAIN/CATCH BASIN SANITARY SEWER/MANHOLE FUTURE DUCT EXISTING DUCT EXISTING UNDERGROUND CABLE RIGHT-OF-WAY LINE PROPERTY LINE POLE AND OVERHEAD LINE SERVICE CONDUIT STREET LIGHT CABLE 1/0 SECONDARY UNDERGROUND CABLE 4/0 SECONDARY UNDERGROUND CABLE #350 SECONDARY UNDERGROUND CABLE PRIMARY UNDERGROUND CABLE STREET LIGHT PEDESTAL LARGE SECONDARY PEDESTAL SMALL SECONDARY PEDESTAL SUBMERSIBLE SWITCH CABINET PAD MOUNTED SWITCH CABINET PULLING VAULT SECONDARY VAULT SUBMERSIBLE J-BOX ABOVE GROUND J-BOX SUBMERSIBLE TRANSFORMER PAD MOUNTED TRANSFORMER 240TH ST SW & UTILITY ESMT 15' INGRESS/EGRESS & UTILITY ESMT 15' INGRESS/EGRESS 15-228576 PLI 15330 P P P P P109'A-55348 A-55347 1" = 50' LAYOUT ASSY#12U612 MAKE SER UTC A-55348 25 KVA MAKE PO REEL 164'OF (1) FROM POLE TO A-55347 1/0 AL 15KV CNCTRC NEUT JCKTD PRI IN 2" PVC FT MARK TO 410'OF 350 KCMIL AL TPX SEC IN 3" PVC MAKE PO REEL 132'OF (1) FROM A-55347 TO A-55348 1/0 AL 15KV CNCTRC NEUT JCKTD PRI IN 2" PVC FT MARK TO DUCT A 50'3"OF (1) PVC XINGS BY CUSTOMER XINGS TO BE INSPECTED BY PUD LINE PERSONNEL A-55347 & A-55348 BY CUSTOMER A 3 VAULT LIST VAULT SHEET A-55347 & A-55348 1 SECONDARY PEDESTALS 4 SEC PEDS/INSTALL PER DIST ASSY# 1U801 BY CUSTOMER 2 SEC PEDS/INSTALL PER DIST ASSY# 1U802 FEED THRU PEDS ON LOT LINE 7/8 & 9/10 POLE RISER BY CUSTOMER AT POLE PLI 15330 RISER PER DIST ASSY# 12U111 INSTALL UGND TERMINAL POLE GENERAL NOTES, DETAILS & NTS SCHEMATIC DESIGN LOAD CRITERIA 4000' SQ FT PARTIAL ELECTRIC 175A MOTOR LOAD LOT#CONDUCTORLENGTH(ft) 11 10 9 8 7 6 5 4 3 2 1 SVC-4/0 AL TPX SVC-4/0 AL TPX SVC-4/0 AL TPX SVC-4/0 AL TPX SVC-4/0 AL TPX SVC-4/0 AL TPX SVC-4/0 AL TPX SVC-4/0 AL TPX SVC-4/0 AL TPX SVC-4/0 AL TPX SVC-4/0 AL TPX 53 62 60 59 63 61 60 56 51 61 61 REFER TO SHEET 2 ROAD SECTIONS: WORK SITE P 2 A 1 A102'(425) 783-4356 STEPHANIE ELWIN (425) 737-3987 VAULT W/A 22" x 24" ACCESS HOLE 43" x 38" x 36" FIBERGLASS OPEN BOTTOM STREET LIGHTS 1 INSTALL PER DIST ASSY# 1L902 ALL ST LT CA TO BE IN 2" PVC ST LTS/SOURCE VOLTAGE 120V BY CUSTOMER 15'#8OF AL DX ST LT IN 2" PVC OVHD OVHD 10028 UGND AMPS FU 4015 PLI 15330 1 2 240TH ST SW A-55347 75- A-55348 25- AMPS FU 40 112336 112337 0 14516-2 ROAD SECTIONS DETAILS & GENERAL NOTES, RESERVE BRACKETS 100084031 0060 NTS EJS EJS S ELWIN SCW 3/3/22 PUBLIC UTILITY DISTRICT NO 1 SNOHOMISH COUNTY DATE APVD ENGR CHKR DFTR SCALE REV DESCRIPTIONNoDATEBYAPVDCHKRDRAWING REVISIONSENGRDATE: 15-Apr-22 10:01DESCRIPTIONNoDATEBYCHKRENGRAPVDORDER OPERATION FILE: W:\UG\14500\14516-2.dgnGENERAL NOTES: ALL AND MAINTAIN ALL ALL ALL INTEGRITY OF A CONDUCTOR OR CONDUIT. ROCK OR OTHER SHARP OBJECTS, WHICH COULD DAMAGE THE SIZE THUMBNAIL. BACKFILL SHALL NOT CONTAIN CRUSHED NATURALLY OCCURRING OBJECT LARGER THAN AN AVERAGE NATURAL EARTH SOIL CONTAINING NO ROCKS OR OTHER SELECT BACKFILL IS DEFINED BY THE DISTRICT AS SELECTED SHALL BE REQUIRED IF SELECT BACKFILL IS UNAVAILABLE. AND COMMUNICATION CONDUITS TO PREVENT CRUSHING. SAND 6"-8" OF SELECT BACKFILL SHALL BE PLACED ABOVE POWER INSPECTOR BEFORE THE PLAT WILL BE ENERGIZED. CUSTOMER MUST RETURN AS-BUILT PRINTS TO THE PUD'S LINE FINAL VISUAL INSPECTION. REQUIRE ALL VAULTS AND PEDESTALS TO BE OPENED FOR A PLAT IS ENERGIZED. THIS MAY, AT THE ENGINEER'S DISCRETION, PROJECT LEADER/ENGINEER AND THE DEVELOPER BEFORE THE WALK THROUGH INSPECTION OF THE PLAT WITH THE INSPECTOR, THE CUSTOMER SHALL BE RESPONSIBLE FOR COORDINATING A AND STANDARDS. DE-ENERGIZED EQUIPMENT USING APPROVED PUD MATERIALS THE CUSTOMER SHALL BE RESPONSIBLE FOR CONNECTING INSPECTED BY PUD LINE INSPECTORS. WHILE UNDER CONSTRUCTION, PUD FACILITIES SHALL BE REVIEW ANY CHANGES PRIOR TO CONSTRUCTION. PUD ENGINEER AND INSPECTOR SHALL BE NOTIFIED OF AND DRAINS, ETC.) LOCATED ON OR NEAR PROPERTY CORNERS. THE CHANGE DUE TO UNDERGROUND OBSTACLES (WATER, SEWER, CONSTRUCTION OF PUD FACILITIES IN THE EASEMENT AREA MAY STEEL ELBOWS. ALL CONDUITS USED FOR PRIMARY CONDUCTORS WILL REQUIRE ALL UNDERGROUND CABLE SHALL BE INSTALLED IN CONDUIT. THE CUSTOMER'S EXPENSE. REQUIRE THE CUSTOMER TO CORRECT THE ERROR AT STAKED FACILITIES MAY, AT THE DISTRICT'S DISCRETION, FACILITIES PER THE DRAWING. ANY VARIANCE TO THE THE CUSTOMER SHALL STAKE AND INSTALL ELECTRICAL TRENCH WIDTH SHALL BE AS INDICATED. MEETING. AMONG ALL CONCERNED PARTIES AT THE PRECONSTRUCTION PRIOR TO BACK FILLING, UNLESS OTHERWISE AGREED UPON TO GIVE JOINT TRENCH UTILITIES TWO WORKING DAYS NOTICE THEIR FACILITIES INSTALLED. THE CUSTOMER IS RESPONSIBLE SLOUGHING, WATER PUMPING, ETC.) UNTIL UTILITIES HAVE THE INTEGRITY OF THE TRENCH (SHORING, IT SHALL BE THE CUSTOMER'S RESPONSIBILITY TO PROVIDE INSTALLING FACILITIES IN THE CUSTOMER PROVIDED TRENCH. ARE TO BE UTILIZED FOR JOINT TRENCH UTILITIES AND HEALTH ACT, CHAPTER 49.17 RCW. THE SAFETY SYSTEMS REQUIREMENTS OF THE WASHINGTON INDUSTRIAL SAFETY FOR SUCH TRENCHING AND EXCAVATION THAT MEET THE CUSTOMER SHALL PROVIDE ADEQUATE SAFETY SYSTEMS TRENCHING, WHERE THE DEPTH WILL EXCEED 4',THAT THE AGREES THAT IN ANY WORK OR OPERATION INVOLVING FOR TRENCHING AND VAULT EXCAVATIONS, THE CUSTOMER ISSUING OF THE NOTICE TO PROCEED. TELEPHONE, CATV AND PUD ONE WEEK PRIOR TO THE PRECONSTRUCTION MEETING WITH DEVELOPER, GAS, CUSTOMER SHALL BE RESPONSIBLE FOR HOLDING A FOUR DAYS PRIOR TO CONSTRUCTION. MATERIALS ON SITE AND READY FOR INSPECTION CUSTOMER SHALL HAVE ALL CONSTRUCTION-RELATED FEES AND PERMITS AS REQUIRED BY LAW. EQUIPMENT, MANPOWER, PAPERWORK, ADMINISTRATION THE CUSTOMER SHALL PROVIDE ALL NECESSARY TIME, 15. 14. 13. 12. 11. 10. 9. 8. 7. 6. 5. 4. 3. 2. 1.ABOVE PEDESTAL18" MAXIMUM12" MINIMUMPEDESTAL SECONDARY SMALL/LARGE TRIPLEX CABLES SECONDARY TERMINALS SET SCREW 4-POS/5-POS PEDESTAL OF CORNERS OF TO FEED IN/OUT 3" PVC DUCT NTS TYPICAL PEDESTAL DETAIL TRANSFORMER/PEDESTAL PVC BELL END FROM FLEXIBLE PVC W/SCH 40 3" CORRUGATED 20'20' 12'12' R/W Ò R/W EASEMENT 10' EASEMENT 10' 1'1' NTS TYPICAL ROAD SECTION TRENCH PEDESTAL SECONDARY VAULT TRANSFORMER/ 3'-6" ROAD A 5'5' PED SEC 5'-3" 30' 12' R/W Ò EASEMENT 10' 6" NTS TYPICAL ROAD SECTION 240TH ST SW 5' TRENCH 3'-6"47" *SECONDARY DEPTHPRIMARY DEPTHTELE TV NOTE: 12" MIN TYPICAL JOINT ROAD CROSSINGS NTS SEPARATION 2" MIN 24" MINIMUM FROM FINAL GRADE36" MIN-42" MAX FROM FINAL GRADEEND OF CONDUI TEXTEND TRENCH 3' PASTFINAL GRADE FINAL GRADE AND THEN BACKFI LLAT ENDS. CONDUITS SHALL BE EVEN DUCT TAPE SHALL NOT BE USED. W/DISTRICT APPROVED PLUGS, SEAL ENDS OF CONDUIT PRIMARY POWER SECONDARY POWER 12" MINIMUM GAS SEPARATION. CONDUITS. MIN 2" SEPARATION BETWEEN PLUGS. WITH DISTRICT APPROVED ALL CONDUITS TO BE SEALED IN XINGS VARIES NUMBER OF CONDUITS 4. 3. 2. 1. WIDTH VARIES/30" MINIMUM MAX TRENCH DEPTH* FINAL GRADE CONDUIT OVER MARKER. PLACE 5' LONG PIECE OF OF POWER CONDUITS. MARKERS PLACED AT ENDS NOTES. SEE GENL BACKFILL. SELECT PROJECT ENGINEER. IN WRITING BY THE DISTRICT'S UNLESS OTHERWISE APPROVED12" MINIMUM OF SANDABOVE GAS CONDUITS, TYPSAND GAS 3" MINIMUM OF SIDE OF CONDUIT SAND ON EACH6" MINIMUM OF SANDBELOW GAS CONDUITSPOSITION. NEEDED TO RETAIN TRENCH EVERY 10' OR SHADED AS POWER AND GAS TO STAKE47" *WIDTH VARIES 36" MINIMUM 24" MINIMUMSECONDARY DEPTH36" MINIMUMPRIMARY DEPTH2"VARIES TELE TV GAS SECONDARY PRIMARY SECONDARY 12" MINSTREET SIDETYPICAL JOINT TRENCH DETAIL NTS SINGLE PHASEBELOW GAS CONDUITS3" MINIMUM OF NOTE:ABOVE GAS CONDUITS, TYP36" MINIMUM DEPTH6" MINIMUM OF SAND1. 2. 3. MAX TRENCH DEPTH* PROJECT ENGINEER. IN WRITING BY THE DISTRICT'S UNLESS OTHERWISE APPROVED SAND SIDE OF CONDUIT SAND ON EACH RETAIN TRENCH POSITION. EVERY 10' AS NEEDED TO POWER AND GAS TO STAKE LIGHT STREET NOTES. SEE GENL BACKFILL. SELECT FINAL GRADE CONDUIT. ALL CONDUCTORS IN IN TRENCH VARIES. NUMBER OF CONDUITS POWER SEPARATION. 12" MINIMUM GAS TO 12" MINIMUM OF SANDVAULT TRANSFORMER/ PEDESTAL 10' EASEMENT8'10' EASEMENTPEDESTAL R/W R/WÓ Ó PC PC NTSA-12345PEDTRENCH Ò 3'-6"TRENCH Ò 3'-6"WITH FACILITIES ON PROPERTY LINE TYPICAL STAKING LAYOUT MARKINGS STAKE TYPICAL STREET SIDE STREET SIDE 10' EASEMENT4'8'R/W Ó PC VAULT PRIMARY GAS TELEPHONE PUD PED SECPED CATV PED TELE 4' NTS 10' EASEMENTR/W Ó PED SEC PED CATV PED TELE 1' STUBOUTS VAULT AND EXCAVATE FOR 2' 3' TRENCH, TYP ACROSS JOINT ON GAS STUB PVC CONDUIT TYP GAS STUB, 1' PC TRENCH, TYP ACROSS JOINT ON GAS STUB PVC CONDUIT GAS TELEPHONE PUD CATV GAS STUB, TYP CATV LAYOUT WITH FACILITIES ON PROPERTY LINE TYPICAL JOINT TRENCH VAULT/PED STREET SIDE STREET SIDE Ò TRENCH3'-6"Ò 3'-6"TRENCH 3' 2' STUBS, TYP. ABOVE GAS CONDUITS AND AND 12" MINIMUM OF SAND 6" MINIMUM OF SAND BELOW STUBS, TYP. ABOVE GAS CONDUITS AND AND 12" MINIMUM OF SAND 6" MINIMUM OF SAND BELOW