APPROVED BLD BLD2022-1450+Plumbing_Plan+10.21.2022_9.24.14_AM+3177850ABBREVIATIONS PLUMBING SYMBOL LEGEND PLUMBING LINETYPE LEGEND EQUIPMENT TAGS
AC AIR CONDITION (-ING, -ED) INV INVERT - - - - - - - - - - - - - - - - - - - - - - - - - - - - - DOMESTIC COLD WATER ACCU AIR COOLED CONDENSING UNIT GWH GAS WATER HEATER
AFF ABOVE FINISHED FLOOR KW KILOWATT ----------------------------- DOMESTIC COLD WATER (BELOW FLOOR/GRADE) AHU AIR HANDLING UNIT HU HUMIDIFIER
AMP AMPERE (AMP, AMPS) LAT LEAVING AIR TEMPERATURE ® FLOOR DRAIN X ANCHOR a REDUCER DOMESTIC COLD WATER (EXISTING) AHUP AIR HANDLING UNIT PUMP HUH HORIZONTAL UNIT HEATER
AP ACCESS PANEL LBS POUNDS - DOMESTIC HOT WATER BP BOOSTER PUMP HWP HEATING WATER PUMP
-------------------------------- - CDWP CONDENSER WATER PUMP IH INTAKE HOOD
BTU BRITISH THERMAL UNIT LWB LEAVING WET BULB FLOOR SINK DOMESTIC HOT WATER (EXISTING) CEF CEILING EXHAUST FAN MAU MAKE-UP AIR UNIT
CBV CIRCUIT BALANCING VALVE LWT LEAVING WATER TEMPERATURE lid PIPE FLANGE 0- FLOW ARROW
CFH CUBIC FEET PER HOUR MA MIXED AIR W/HALF GRATE G GAS CHWP CHILLED WATER PUMP PCWP PRIMARY CHILLED WATER PUMP
CFM CUBIC FEET PER MINUTE MAX MAXIMUM ------------------ G------------------ GAS (ON ROOF) CP CIRCULATING PUMP PHWP PRIMARY HEATING WATER PUMP
CHW CIRCULATING HOT WATER MBH THOUSAND BTU'S/HR FLOOR SINK PIPE GUIDE STEAM TRAP F&T G GAS (EXISTING) CPR CONDENSATE PUMP AND RECEIVER PRV POWER ROOF VENTILATOR
CHWR CHILLED WATER RETURN MIN MINIMUM ® W/FULL GRATE ( ) ) CRP CONDENSATE RETURN PUMP REF RELIEF EXHAUST FAN
CHWR CHILLED WATER SUPPLY MISC MISCELLANEOUS G GAS (EXISTING ON ROOF) CUH CABINET UNIT HEATER RF RETURN FAN
NOT APPLICABLE SANITARY SEWER (ABOVE FLOOR/GRADE) DHC DUCT HEATING COIL RH RELIEF HOOD
CLG CEILING NA MI
�] BALL VALVE Q AIR CHAMBER , r THERMOSTAT WELL SANITARY SEWER (BELOW FLOOR/GRADE) ECH ELECTRIC CABINET HEATER RTU ROOFTOP UNIT
CO CLEANOUT NC NOISE CRITERIA EF EXHAUST FAN SCWP SECONDARY CHILLED WATER PUMP
CR CONDENSATE RETURN NIC NOT IN CONTRACT SANITARY SEWER (EXISTING) EHC ELECTRIC HEATING COIL SEP SEWAGE EJECTOR PUMP
CW COLD WATER NTS NOT TO SCALE WATER HAMMER -------------------------------------- VENT ES ELECTRONIC SENSOR SHWP SECONDARY HEATING WATER PUMP
DB DECIBEL OA OUTSIDE AIR X GATE VALVE * ARRESTER o EXPANSION JOINT -------------------------------------- VENT (UNDERFLOOR/GRADE) EUH ELECTRIC UNIT HEATER SP SUMP PUMP
DEMO DEMOLITION OBD OPPOSED BLADE DAMPER VENT (EXISTING) EWC ELECTRIC WATER COOLER TF TRANSFER FAN
DIA DIAMETER ORD OVERFLOW ROOF DRAIN _ EWH ELECTRIC WATER HEATER USF UTILITY SET FAN
DIFF DIFFUSER PH PHASE (ELECTRICAL) CHECK VALVE FLEXIBLE CONNECTOR
WALL HYDRANT/ FCU FAN COIL UNIT VAV VARIABLE AIR VOLUME BOX
1�I �
DWG DRAWING PVC POLYVINYL CHLORIDE HOSE BIBB FPB FAN POWERED VARIABLE AIR VOLUME BOX VUH VERTICAL UNIT HEATER
DX DIRECT EXPANSION RA RETURN AIR MISC. SYMBOL LEGEND WS WATER SOFTENER
EAT ENTERING AIR TEMPERATURE RD ROOF DRAIN
ELEC ELECTRICAL REC RECESSED jai DRAIN VALVE EXPANSION TANK T TEST PLUG
REL RELIEF 0 SPRINKLER HEAD (SEMI -RECESSED)
ELEV ELEVATION ® EQUIPMENT TAG � CONNECTION TO EXISTING
RH RELATIVE HUMIDITY
EMS ENERGY MANAGEMENT SYSTEM RM ROOM �Q� STEAM TRAP
ESP EXTERNAL STATIC PRESSURE RPM REVOLUTIONS PER MINUTE 2-WAY VALVE 0 WATER METER (THERMOSTATIC) O SPRINKLER HEAD (UPRIGHT)
EWB ENTERING WET BULB EWT ENTERING WATER TEMPERATURE SA SUPPLY AIR A REVISION TRIANGLE < KEY NOTE
O SPRINKLER HEAD FULLY RECESSED
SAN SANITARY s ( )
EXH EXHAUST SD SMOKE DAMPER � SOLENOID VALVE a FLOW METER 4 VACUUM RELIEF VALVE
EXIST EXISTING
F COMBINATION
SHEET INDEX SF SQUARE FEET
FSD COMBIN FIRE/SMOKE DAMPER SP STATIC PRESSURE M 4 ALL WORK SUBJECT
FCO FLOOR CLEANOUT SPEC SPECIFICATION � MOTORIZED VALVE � THERMOMETER AQUASTAT
FD FIRE DAMPER ST STORM
FD FLOOR DRAIN STD STANDARD EMERGENCY GAS PO.0 MECHANICAL TITLE SHEET AND SPECIFICATIONS
FDC FIRE DEPARTMENT CONNECTION TD TEMPERATURE DIFFERENCE PRESSURE GAGE PRESSURE REGULATOR TO FIELD
FIFE FINISHED FLOOR ELEVATION TSP TOTAL STATIC PRESSURE SHUT-OFF VALVE P1.0 PLUMBING PLAN
FLR FLOOR TYP TYPICAL
FPM FEET PER MINUTE V VOLTS THERMOSTATIC/PRESSURE
FT FOOT OR FEET VFD VARIABLE FREQUENCY DRIVE BALANCE MIXING VALVE STRAINER PIPE DOWN
GA GAGE OR GAUGE VSD VARIABLE SPEED DRIVE INSPECTION FOR
GAL GALLONS VOL VOLUME
GC GENERAL CONTRACTOR VTR VENT THROUGH ROOF FI
TP TRAP PRIMING VALVE PUMP o PIPE UP
GPH GALLONS PER HOUR W WATTS CODE CO M P LIAN C E
HP HORSEPOWER W/ WITH
HT HEIGHT W/0 WITHOUT 2�_ PRESSURE RELIEF VALVE P# PLUMBING FIXTURE TAG TEE DOWN
HVAC HEATING, VENTILATING, AIR CONDITIONING WC WATER CLOSET
HW HOT WATER WCO WALL CLEANOUT
HZ HERTZ WT WEIGHT
ID INSIDE DIAMETER 11 BUTTERFLY VALVE F# FLOOR RECEPTOR TAG III UNION
X GLOBE VALVE Fs FLOW SWITCH rl PIPE CAP
b CIRCUIT BALANCING 3-WAY VALVE S PIPE BREAK
VALVE
0 PLUG VALVE >qM BACKFLOW PREVENTER APPROVED
M E C H A N I C A L S P E C I F I C A T 1 0 N S
15000 GENERAL PROVISIONS
0.01 DEFINITIONS: THE TERMS LISTED BELOW ARE DEFINED AS FOLLOWS WHEN USED IN DIVISION 15
WORK AND ONLY DIVISION 15 WORK.
A. WORK: LABOR AND MATERIALS OF THE CONTRACTOR AND/OR SUBCONTRACTOR.
B. FURNISH: OBTAIN, COORDINATE, SUBMIT THE NECESSARY DRAWINGS, DELIVER TO THE
JOBSITE IN NEW CONDITION AND GUARANTEE.
C. INSTALL: RECEIVE AT THE JOB -SITE, UNLOAD, STORE, SET IN PLACE, CONNECT, PLACE IN
OPERATION AND GUARANTEE.
D. PROVIDE: FURNISH AND INSTALL.
E. CONNECT: BRING SERVICE TO THE EQUIPMENT AND MAKE FINAL ATTACHMENTS INCLUDING
NECESSARY PIPE FITTINGS, DUCTWORK, TRANSITIONS, ETC.
F. CONCEALED: HIDDEN FROM SIGHT IN CHASES, FURRED SPACES, SHAFTS, ABOVE CEILING,
EMBEDDED IN CONSTRUCTION, IN CRAWL SPACES OR BURIED.
G. EXPOSED: NOT INSTALLED UNDERGROUND OR CONCEALED AS DEFINED ABOVE.
H. REMOVE: REMOVE ALL EQUIPMENT AND MATERIALS NOT BEING RE -USED. DISPOSE OF
OFF -SITE IN A LEGAL AND ENVIRONMENTALLY CONCIOUS MANNER.
0.02 PERFORMANCE: MECHANICAL CONTRACTOR SHALL PERFORM ALL WORK SPECIFIED, INDICATED
AND REQUIRED UNLESS OTHERWISE NOTED, INCLUDING FINAL CONNECTIONS, IN A WORKMANLIKE
MANNER USING WORKERS SKILLED AND EXPERIENCED IN THE TRADE.
0.03 SITE EXAMINATION: EXAMINE SITE BEFORE BIDDING. CLAIM NO EXTRAS RESULTING FROM LACK
OF KNOWLEDGE OF SITE CONDITIONS. IF SITE CONDITIONS REQUIRE MODIFICATION OF THE
SYSTEMS INDICATED IN THESE DOCUMENTS, SO ADVISE ENGINEER, AND IF ACCEPTED BY
ENGINEER, INCLUDE COST OF SUCH MODIFICATIONS IN BID.
0.04 JOBSITE CONDITIONS: ACCEPT SOLE AND COMPLETE RESPONSIBILITY FOR CONDITIONS OF THE
JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING PERFORMANCE OF THE
WORK.
0.05 FULL FUNCTION: PROVIDE ALL MINOR ITEMS NECESSARY FOR A COMPLETE AND FULLY
FUNCTIONAL INSTALLATION.
0.06 ADMINISTRATION: PROVIDE EVIDENCE OF LICENSING, BONDING, AND INSURANCE, AND PERFORM
OTHER ADMINISTRATIVE FUNCTIONS, AS REQUIRED.
0.07 PERMITS: PROCURE AND PAY FOR ALL REQUIRED PERMITS AND SERVICE CHARGES.
0.08 UTILITY SERVICES: ARRANGE FOR ALL REQUIRED UTILITY SERVICES AND PAY ALL UTILITY
SERVICE FEES.
0.09 COORDINATION: CONFORM TO GENERAL CONSTRUCTION CONTRACT DOCUMENTS EXCEPT AS
MODIFIED HEREIN. REFER ALSO TO STRUCTURAL AND ELECTRICAL CONTRACT DOCUMENTS.
COORDINATE ALL WORK WITH OTHER TRADES.
0.10 CUTTING AND PATCHING: CUT AND PATCH AS REQUIRED. CUT OR WELD STRUCTURAL
MEMBERS ONLY WITH APPROVAL OF STRUCTURAL ENGINEER. PATCHING SUBJECT TO APPROVAL
BY ARCHITECT.
0.11 EXISTING FLOORS: TRENCH OR CORE BORE EXISTING FLOORS PER LANDLORD REQUIREMENTS.
0.12 ROOF PENETRATIONS: ALL ROOFING WORK SHALL BE PERFORMED BY LANDLORD -APPROVED
ROOFING CONTRACTOR AT THIS CONTRACTOR'S COST. COORDINATE WITH LANDLORD.
0.13 EQUIPMENT SUBSTITUTIONS: REIMBURSE ELECTRICAL CONTRACTOR, AT NO CHARGE TO TENANT,
FOR HIS COSTS INCURRED DUE TO SUBSTITUTION OF MECHANICAL EQUIPMENT HAVING
ELECTRICAL REQUIREMENTS DIFFERING FROM THOSE INDICATED.
0.14 ADJUSTMENTS: MAKE MINOR ADJUSTMENTS TO WORK WHERE REQUESTED BY TENANT, WHEN
SUCH ADJUSTMENTS ARE NECESSARY TO PROPER OPERATION AND WITHIN THE INTENT OF THE
CONTRACT.
0.15 REFERENCE STANDARDS: COMPLY WITH APPLICABLE STANDARDS OF NFPA, ANSI, UL, ASHRAE,
AND SMACNA, EXCEPT AS SUPERSEDED BY LOCAL AUTHORITY. CONFORM WITH CONTRACT
DOCUMENTS WHERE THEY EXCEED CODE MINIMUM REQUIREMENTS.
0.16 LOCAL REQUIREMENTS: COMPLY WITH THE REQUIREMENTS OF APPLICABLE CODES, LANDLORD,
SERVING UTILITIES, AND THE LOCAL AUTHORITY HAVING JURISDICTION. SECURE APPROVAL OF
INSTALLATION BY LANDLORD, LOCAL AUTHORITY, AND OTHERS AS REQUIRED.
0.17 MATERIALS AND EQUIPMENT: PROVIDE NEW, UL LISTED, COMMERCIAL GRADE MATERIALS,
DEVICES, EQUIPMENT, AND FIXTURES, SUITABLE FOR ENVIRONMENT. REUSE EXISTING ONLY WHEN
COMPLIANT WITH THE CONTRACT DOCUMENTS, IN GOOD CONDITION, AND APPROVED BY THE
ENGINEER.
0.18 SHOP DRAWINGS: BEFORE ORDERING EQUIPMENT AND MATERIALS, SUBMIT NOT LESS THAN FIVE
CERTIFIED COPIES OF ALL SHOP AND EQUIPMENT DRAWINGS FOR ENGINEER'S REVIEW, WHO WILL
RETAIN TWO COPIES. ONLY FURNISH SYSTEMS AND EQUIPMENT IN COMPLIANCE WITH ACCEPTED
SHOP DRAWINGS.
0.19 INSTALLATION: INSTALL ALL MATERIALS, EQUIPMENT AND SYSTEMS IN FULL ACCORD WITH
MANUFACTURER'S INSTRUCTIONS.
0.20 LAYOUT: INSTALL ALL PIPING AND DUCTWORK TO PRESENT A NEAT AND ORDERLY
APPEARANCE. RUN ALL LINES PARALLEL WITH BUILDING CONSTRUCTION. MAINTAIN HEADROOM
AND EQUIPMENT CLEARANCE, AND GRADIENT WHERE REQUIRED. ALLOW FOR EXPANSION AND
CONTRACTION.
0.21 ACCESS DOORS: PROVIDE ACCESS DOORS OR PANELS FOR ALL VALVES, CLEANOUTS,
DAMPERS, CONTROLS, DEVICES, AND OTHER ITEMS REQUIRING INSPECTION OR MAINTENANCE.
ACCESS PANELS SERVING HVAC COMPONENTS SHALL BE 12-INCHES BY 12-INCHES MINIMUM OR
LARGER TO PROVIDE SUFFICIENT WORKING CLEARANCE FOR COMPONENT BEING ACCESSED.
0.22 COMMISSIONING: THOROUGHLY TEST AND DEMONSTRATE PROPER OPERATION OF ALL SYSTEMS
AND EQUIPMENT FURNISHED OR INSTALLED UNDER THIS CONTRACT.
0.23 RECORD DRAWINGS: PREPARE AND SUBMIT TO GENERAL CONTRACTOR RECORD DRAWINGS
SHOWING ALL SIGNIFICANT DEVIATIONS FROM CONSTRUCTION DOCUMENTS. INCLUDE
MANUFACTURER AND MODEL NUMBERS FOR ALL EQUIPMENT INSTALLED.
0.24 0 & M MANUALS: AN OPERATION AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE
BUILDING OWNER OR OPERATOR. THE MANUAL SHALL INCLUDE BASIC DATA RELATING TO THE
OPERATION AND MAINTENANCE OF HVAC SYSTEMS AND EQUIPMENT. REQUIRED ROUTINE
MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED. WHERE APPLICABLE, HVAC CONTROLS
INFORMATION SUCH AS DIAGRAMS, SCHEMATICS, CONTROL SEQUENCE DESCRIPTIONS, AND
MAINTENANCE AND CALIBRATION INFORMATION SHALL BE INCLUDED.
0.25 WARRANTY: UNCONDITIONALLY WARRANT ALL WORK TO BE FREE OF DEFECTS IN MATERIALS
AND WORKMANSHIP FOR ONE YEAR FROM DATE OF FINAL ACCEPTANCE, EXCEPT WARRANT AIR
CONDITIONING COMPRESSORS FOR FIVE YEARS AND GAS -FIRED HEAT EXCHANGERS FOR 10
YEARS. DURING WARRANTY PERIOD, REPAIR OR REPLACE DEFECTIVE MATERIALS, EQUIPMENT OR
WORKMANSHIP WITHOUT COST TO TENANT.
0.26 EQUIPMENT IDENTIFICATION: IDENTIFY ALL APPLICABLE ROOFTOP EQUIPMENT WITH TENANT'S
NAME, SPACE NUMBER AND UNIT NUMBER, USING 2" HIGH PAINTED CHARACTERS OR STAMPED
METAL TAG. LABEL INDOOR EQUIPMENT WITH UNIT NUMBER IN LIKE MANNER.
0.27 DRAWINGS ARE DIAGRAMMATIC: VERIFY ALL DIMENSIONS AND LENGTHS, AND ADJUST
EQUIPMENT, PIPE AND DUCT LOCATIONS TO AVOID CONFLICTS WITH OTHER CONSTRUCTION AND
TRADES.
0.28 DOCUMENT PRIORITY: DRAWING INDICATIONS AND NOTATIONS SUPERSEDE THESE
SPECIFICATIONS.
0.29 RATINGS: REFER TO DRAWINGS AND SCHEDULES FOR ADDITIONAL RATINGS AND REQUIREMENTS.
0.30 PROJECT REQUIREMENTS: REFER TO DRAWINGS FOR PARTICULAR PROJECT REQUIREMENTS, AS
NOT ALL ITEMS INCLUDED IN THESE SPECIFICATIONS MAY BE REQUIRED FOR THIS PROJECT.
0.31 DOCUMENT ERRORS: NOTIFY THE ENGINEER OF ANY ERRORS, DISCREPANCIES OR OMISSIONS
BEFORE CONSTRUCTION OR FABRICATION OF AFFECTED WORK, OR, FAILING SUCH NOTICE, BE
RESPONSIBLE FOR CORRECTING SAME WITHOUT COST TO TENANT, ARCHITECT OR ENGINEER.
15100 BASIC MATERIALS AND METHODS
1.10 PIPE HANGERS AND SUPPORTS: PROPERLY SUPPORT ALL PIPING FROM JOISTS (TOP CHORD)
OR OTHER STRUCTURAL MEMBERS. FOR PIPES UP TO 4" O.D., USE GRINNELL FIG. 260 CLEVIS
HANGERS WITH 3/8" ROD, OR FIG. 195 BRACKETS.
1.20 INSULATION SHIELDS: PROVIDE 18 GAUGE X 12" LONG GALVANIZED INSULATION SHIELDS AT
SUPPORT POINTS FOR INSULATED PIPES.
1.30 PIPE SUPPORT SPACING: SUPPORT PIPE NOT LESS THAN 6 FT. ON CENTER FOR COPPER PIPE
UP TO 2" O.D., OR NOT LESS THAN 10 FT. ON CENTER FOR STEEL PIPE UP TO 4" O.D.
1.40 COPPER CONTACT: PROVIDE COPPER PLATED HANGERS AND SUPPORTS WHERE IN CONTACT
WITH COPPER PIPE.
1.50 PIPE SLEEVES: SLEEVE ALL HORIZONTAL PIPING WHICH PENETRATES WALLS WITH STANDARD
WEIGHT STEEL PIPE OF 1" GREATER DIAMETER THAN PIPE OR INSULATION O.D. CUT SLEEVE
FLUSH WITH WALL. FINISH BOTH SIDES.
1.60 SEALANT: SEAL PIPE SLEEVES WITH ROPE AND EXPANDO NON -SHRINK SEALANT. FIRE/SMOKE
SEAL PENETRATIONS OF RATED CONSTRUCTION TO MAINTAIN RATING.
1.70 WALL PLATES: FIT UNCOVERED PIPE PASSING THROUGH WALLS WITH WALL PLATES, CRANE NO.
10 OR EQUAL.
15200 THERMAL AND ACOUSTIC INSULATION
2.10 VIBRATION ISOLATION: PROVIDE EFFECTIVE VIBRATION ISOLATION DEVICES, AND FLEXIBLE
CONNECTIONS, FOR ALL MOVING MACHINERY. PROVIDE DEVICES IN ACCORDANCE WITH THE
RECOMMENDATIONS IN THE ASHRAE HANDBOOK, HVAC APPLICATIONS (LATEST EDITION), CHAPTER
"SOUND AND VIBRATION CONTROL".
2.20 NOISE TRANSMISSION: INSTALL PIPING AND DUCTWORK FREE FROM CONTACT WITH STRUCTURE
OR EQUIPMENT TO PREVENT NOISE TRANSMISSION.
2.30 INSULATION REQUIREMENTS: INSULATE SYSTEMS AS SPECIFIED ONLY AFTER THEY HAVE BEEN
TESTED AND INSPECTED. CLEAN ALL SURFACES THOROUGHLY OF MOISTURE, FOREIGN MATERIAL,
GREASE, AND RUST. INSTALL INSULATION CONTINUOUS THROUGH WALL AND FLOOR
PENETRATIONS.
2.31 EXISTING SYSTEMS BEING RE -USED: INSULATE EXISTING PIPE AND DUCT SYSTEMS BEING
RE -USED SAME AS SPECIFIED FOR NEW SYSTEMS. REPAIR/REPLACE EXISTING INSULATION TO
LIKE -NEW CONDITION AS REQUIRED.
2.32 INSULATION HAZARDS: USE ONLY INSULATION, JACKETS, ADHESIVES, SEALERS, AND COATINGS
WITH FIRE HAZARD RATING NOT TO EXCEED 25/50/50 FLAME SPREAD, FUEL CONTRIBUTED, AND
SMOKE DEVELOPED, IN ACCORDANCE WITH UL 723 AND ASTM E84.
2.33 INSULATED PLUMBING SYSTEMS: INSULATE HOT AND COLD WATER PIPING WITH 1" THICK
CLOSED CELL, SELF SEALING FLEXIBLE TUBING, ARMAFLEX 2000 OR EQUAL.
15400 PLUMBING
4.10 DRAIN, WASTE AND VENT PIPING:
A. BELOW GRADE:
1. PVC PIPE ASTM D2665, WITH PVC FITTINGS AND ASTM D2855 SOLVENT WELD JOINTS
WITH ASTM D2564 SOLVENT CEMENT.
2. NO -HUB CAST IRON SANITARY SYSTEM PER CISPI 301-69T.
3. SERVICE WEIGHT CAST IRON HUB AND SPIGOT WITH NEOPRENE GASKET, PER CISPI
HSN-68T.
B. ABOVE GRADE:
1. NO -HUB CAST IRON SANITARY SYSTEM PER CISPI 301-69T.
2. GALVANIZED PIPE WITH CAST IRON DRAINAGE FITTINGS.
3. INDIRECT DRAINS: COPPER TUBE, ASTM B306, DWV, WITH COPPER FITTINGS AND
SOLDERED JOINTS.
4.20 DOMESTIC (POTABLE) WATER SUPPLY PIPING:
A. BELOW GRADE: TYPE K SOFT TEMPER COPPER TUBE, WITH NO JOINTS.
B. ABOVE GRADE: TYPE L HARD TEMPER COPPER TUBE PER ASTM B88, WITH WROUGHT
COPPER FITTINGS PER USASI B16.18 AND .18A.
C. JOINTS: USE ONLY 95/5 LEAD-FREE SOLDER IN POTABLE WATER PIPING. PROVIDE
DIELECTRIC UNIONS AT EVERY JUNCTION OF TWO DISSIMILAR METAL PIPE MATERIALS.
4.40 VALVES: FURNISH AND INSTALL VALVES WHERE INDICATED ON PLAN AND AS NECESSARY FOR
PROPER SYSTEM OPERATION AND COMPONENT ISOLATION. PROVIDE VALVES RATED FOR 125
PSIG OR GREATER WORKING PRESSURE IN WATER PIPING.
A. CHECK VALVE UP TO 3": CRANE NO. 37, OR EQUAL
B. GLOBE VALVE UP TO 3": CRANE NO. 1, 17TF, OR EQUAL
C. GATE VALVE UP TO 3": CRANE NO. 428, 1334, OR EQUAL
D. BALL VALVE UP TO 3": APOLLO SERIES 70-100, 70-200, OR EQUAL
E. SHOCKSTOP: WADE W-5 (HOT), WADE W-10 (COLD), OR EQUAL
F. BACKFLOW PREVENTER: WATTS NO. 913D, OR EQUAL
G. VACUUM RELIEF VALVE: WATTS NO. N36 - 3/4", OR EQUAL
H. PRESSURE REDUCING VALVE: WATTS NO. U5 SERIES, OR EQUAL
I. TRAP SEAL PRIMER: JOSAM NO. 88250
4.50 PLUMBING FIXTURES AND EQUIPMENT: FURNISH AND INSTALL PLUMBING FIXTURES AND
EQUIPMENT AS SCHEDULED ON DRAWINGS, OR APPROVED EQUAL.
4.60 INSTALLATION:
A. INSTALL AND SECURE FIXTURES IN PLACE WITH WALL CARRIERS AND BOLTS. PROVIDE
BRACKETS, BRACES AND REINFORCING ANGLES AS REQUIRED IN ALL PARTITIONS NOT
SUFFICIENT IN THEMSELVES TO SUPPORT PLUMBING FIXTURES OR OTHER WALL -HUNG
EQUIPMENT.
B. INSTALL EACH FIXTURE WITH CHROME PLATED, 17 GAUGE TUBING TRAP WITH CLEANOUT,
EASILY REMOVABLE FOR SERVICING AND CLEANING.
C. INSTALL COMPONENTS LEVEL, PLUMB AND SECURE.
D. SEAL FIXTURES TO WALL AND FLOOR SURFACES WITH SEALANT, COLOR TO MATCH FIXTURE.
E. ROUTE PIPING IN ORDERLY MANNER. INSTALL PIPING TO CONSERVE BUILDING SPACE AND
NOT INTERFERE WITH USE OF SPACE. GROUP PIPING AT COMMON ELEVATION WHENEVER
PRACTICAL. INSTALL PIPING TO ALLOW FOR EXPANSION AND CONTRACTION WITHOUT
STRESSING PIPE, JOINTS OR CONNECTED FIXTURES/EQUIPMENT. PROVIDE CLEARANCE FOR
INSTALLATION OF INSULATION AND ACCESS TO VALVES AND FITTINGS. PROVIDE ACCESS
WHERE VALVES AND FITTINGS ARE NOT EXPOSED. SLOPE PIPING AND ARRANGE TO DRAIN
AT LOW POINTS.
F. INSTALL NON -CONDUCTING DIELECTRIC CONNECTIONS WHENEVER JOINING DISSIMILAR METALS.
G. PROVIDE SHUT-OFF VALVES AT ALL SUPPLY CONNECTIONS TO FIXTURES AND EQUIPMENT.
H. INSULATE SUPPLY AND WASTE PIPES OF ALL HANDICAP FIXTURES.
I. EXPOSED WATER PIPING SHALL BE CHROME -PLATED BRASS.
4.95 CLEANING AND TESTING: CLEAN, DISINFECT, AND TEST ALL PLUMBING AND PIPING SYSTEMS.
5.65 MISCELLANEOUS DRAIN LINES, RECEIVING COOLING COIL CONDENSATE, DRIP FOR HUMIDIFIERS,
ETC.: TYPE "DWV" COPPER, WITH WROUGHT COPPER FITTINGS AND SOLDERED JOINTS.
GLANS MUST BE
ON JOB SITE
City Of Edmonds
Building Department
Work PLUMBING FOR TI
Address 23632 HIGHWAY 99 SUITE A
Owner nFINITY
Approved Date 11 /08/2022
Building Official Eric, Ga4*_r
Permit Number
BLD2022-14 ❑ 0
RECEIVED
Oct 21 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
HALLBERG
ENGINEERING
Mechanical/Electrical Consulting Engineers
1750 Commerce Court
White Bear Lake, MN 55110
(651) 748-1100 - Fax (651) 748-9370
0.
W
z
N�
L.L
0-
0
LU
0
z
m
N
0
W
z
rja,24�%
0/20221
w
U
aaN
wC)
00
Y��
Q
Qrn�
Q��
0�=z
ONO
�
M
CO
Q
N
W
Preliminary Issue: 10/20/2022
Bid Issue:
10/20/2022
Landlord Issue:
10/20/2022
Permit Issue:
10/20/2022
Construction Issue:
-
MECHANICAL
FITLE SHEET AND
SPECIFICATIONS
Comm. Number R22-4301.020
Date 10/20/2022
Drawn By LAK
Checked By TMS
P0.0
WASTE AND VENT PLAN
1 /4" = 1'-0"
DOMESTIC WATER PLAN
1 /4" = 1'-0"
GENERAL NOTES
WASTE AND VENT RISER
N.T.S.
A. SUBCONTRACTOR TO VERIFY POINT OF CONNECTION AND SCOPE
KEYNOTES O
O
3/4"
1 /2"
2"
0
DOMESTIC WATER RISER
N.T.S.
1. EXTEND AND CONNECT NEW 2" SANITARY SEWER TO EXISTING 2"
(MIN) SANITARY SEWER PIPING. FIELD VERIFY EXACT LOCATION,
SIZE, FLOW DIRECTION, AND INVERT ELEVATION OF CONNECTION
POINT PRIOR TO ROUGH —IN OF NEW SANITARY SEWER. PROVIDE
FCO AT POINT OF CONNECTION TO EXISTING.
2. CONNECT NEW 3/4" CW PIPING TO EXISTING 3/4" (MIN) CW PIPING.
FIELD VERIFY EXACT LOCATION OF CW PIPING PRIOR TO ROUGH —IN.
PROVIDE SHUTOFF VALVE AT POINT OF CONNECTION TO EXISTING.
OF WORK TO INSTALL ALL PLUMBING PIPING & EQUIPMENT TO 3. CONNECT NEW 1-1/2" VENT PIPING ABOVE FLOOD PLAIN OF
SPACE PRIOR TO BID. IF INCONSISTENCIES OCCUR BETWEEN PLUMBING FIXTURES TO EXISTING 2" (MIN) VENT. FIELD VERIFY
PLANS AND LANDLORD CRITERIA, OWNER'S CONSTRUCTION EXACT LOCATION AND SIZE OF VENT STUB PRIOR TO ROUGH —IN OF
MANAGER SHALL BE NOTIFIED PRIOR TO BID SUBMITTAL. NEW VENT SYSTEM.
B. IN THE EVENT THAT THE GENERAL CONTRACTOR MUST 4. REPLACE EXISTING WATER CLOSET IN SAME LOCATION. CONNECT
PENETRATE THE ROOF, THE OWNER — APPROVED ROOFER NEW WATER CLOSET TO EXISTING PLUMBING IN WALL. MODIFY
SHALL BE USED. EXISTING PLUMBING IN WALL AS REQUIRED FOR NEW CONNECTION.
PLUMBING FIXTURE SCHEDULE P#
FIXTURE
NO.
FIXTURE TYPE
MANUFACTURER
TYPE & MODEL
N0.
TRIM/FAUCET
NO.
SUPPORT
PIPE SIZES
REMARKS
TRAP
WASTE
VENT
CW
HW
P1
WATER CLOSET
AMERICAN STANDARD
CADET WHITE
3305.000
CHICAGO FAUCET
1016
FLOOR
MOUNT
__
4
2
1/2"
1.6 GPF, ELONGATED, SIPHON ACTION JETTED BOWL, ADA COMPLIANT
16-1 2" RIM HEIGHT. PROVIDE WHITE SEAT —CHURCH MODEL 295C.
P2
LAVATORY
AMERICAN STANDARD
LUCERNE (WHITE)
0355.012
CHICAGO FAUCET
894-317
WALL
HUNG
1-1 /2"
1-1 /2"
1-1 /2"
1 /2"
1 /2"
PROVIDE INSULATED CAST BRASS P—TRAP, HANDICAP INSULATION KIT, (2)
CHICAGO FAUCET 1016 ANGLE VALVES, WALL CARRIER, 0.5 GPM FLOW LIMIT,
ASSE 1070 APPROVED POINT OF USE THERMOSTATIC MIXING VALVES.
INSTANTANEOUS WATER
HEATER
SCHEDULE pp_
UNIT
N0.
MANUFACTURER
I
MODEL
KW
OUTPUT
(GPM)
TEMP.
RISE °F
VOLTAGE
REMARKS
IWH-1
CHRONOMITE LABS, INC.
SR-20L
4.16
.5
57
208/1/60
NONE
RECEIVED
Oct 21 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
HALLBERG
ENGINEERING
Mechanical/Electrical Consulting Engineers
1750 Commerce Court
White Bear Lake, MN 55110
(651) 748-1100 • Fax (651) 748-9370
Ire I"%71
j c Nt
0/2022
w
U
W a Q N
0
00
< Qrn�
0 LU
�=Z
Z O04O
M
CD
coQ N 0W
N
0
O
a-0
Q
U
N
W
O
Z
Preliminary Issue: 10/20/2022
Bid Issue:
10/20/2022
Landlord Issue:
10/20/2022
Permit Issue:
10/20/2022
Construction Issue:
-
PLUMBING PLAN
Comm. Number R22-4301.020
Date 10/20/2022
Drawn By LAK
Checked By TMS
P1.0