BLD2023-0202_Site_Plan_2.16.2023_10.17.02_AM_3373115GENERAL NOTES 1. INSTALLATION OF SOLAR PHOTOVOLTAIC SYSTEM SHALL BE IN ACCORDANCE WITH NEC ARTICLE 690, AND ALL OTHER APPLICABLE NEC CODES WHERE NOTED OR EXISTING 2. PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110 3. ALL WIRES, INCLUDING THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE IN ACCORDANCE WITH NEC ARTICLE 250 4. THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE; THIS SYSTEM IS UTILITY INTERACTIVE PER UL 1741 AND DOES NOT INCLUDE STORAGE BATTERIES OR OTHER ALTERNATIVE STORAGE SOURCES 5. ALL DC WIRES SHALL BE SIZED ACCORDING TO [NEC 690.81 6. DC CONDUCTORS SHALL BE WITHIN PROTECTED RACEWAYS IN ACCORDANCE WITH [NEC 690.311 7. ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL JURISDICTIONAL BUILDING CODE MAP VIEW: PHOTOVOLTAIC (PV) SYSTEM SPECIFICATIONS EQUIPMENT: AC System Size: 7.48 kW AC / 7.48 kVA DC SYSTEM SIZE: 10.35 kW DC (23) CANADIAN SOLAR CSW3-450MS (450W) PV (23) ENPHASE IQ8M-72-2-US (240V) Inverters RACKING: NANOMOUNT - 48" O.C. APPLICABLE GOVERNING CODES 2020 NEC 2018 IRC 2018 IMC 2018 IFGC • w 0 s G� H ' P � 20111163 �� TBRQO �`rrONAL 8NG` Signed 2/03/2023 SITE SPECIFICATIONS OCCUPANCY: R-3 ZONING: RESIDENTIAL Revolution Energy Systems Inc. 9981 West 190th St Unit K Mokena IL 60448 T: 708-995-1643 SITE INFORMATION NATHAN MOSS 19220 76TH AVE W SEATTLE, WA 98133 AC System Size: 7.48 kW AC / 7.48 kVA DC System Size: 10.35 kW DC Lat, 47.82465 Long,-122.33644 (23) CANADIAN SOLAR CSW3-450MS (450W) PV Modules (23) ENPHASE IQ8M-72-2-US (240V) Inverter(s) 6111911.1139I► 1697N19111►1CAleis] SHEET INDEX: PV01 COVER PAGE PV02 SITE PLAN PV03 ROOF ATTACHMENTS PV04 MOUNTING DETAIL PV05 LINE DIAGRAM PV06 ELECTRICAL CALCS PV07 LABELS PV08 PLACARD PV09 SITE PHOTOS DRAWN BY: ALINSUG W. DATE: 2/3/2023 COVER PAGE - PV01 �CD J 12' a UTILITY METER MAIN SERVICE rwSP PANEL CLOSE UP OF HOUSE PL—113'-10" PL—114'-1" ARRAY DETAILS: MOUNTING PLANE: AZIMUTH: TILT: MP1 1800 180 MP2 1800 180 M P3 2700 180 MP4 1800 180 M P5 90° 180 EQUIPMENT LEGEND: Ac VISIBLE, LOCKABLE, LABELED INv INVERTER SUB PANEL MSD MAIN SERVICE SS SMART SWITCH PV MODULES 5uB AC DISCONNECT DISCONNECT (IQ System Controller) u METEPv (For utillt0CKET —y PV meter) AUTOMATIC lclCOMBINER BOX �c LOAD CENTER GATT BATTERY(IES) JB JUNCTION BOX ATS TRANSFER SWITCH M P4 MP1 VISIBLE, LOCKABLE, FIRE ACCESS LABELED AC DISCONNECT PATHWAY (3' TYP) LOCATED WITHIN 10' PROPERTY LINE OF UTILITY METER ■l■■ ,#'�� Revolution Energy Systems Inc. 9981 West 190th St Unit K Mokena IL 60448 T: 708-995-1643 SITE INFORMATION NATHAN MOSS 19220 76TH AVE W SEATTLE, WA 98133 AC System Size: 7.48 kW AC / 7.48 kVA DC System Size: 10.35 kW DC Lat, 47.82465 Long,-122.33644 (23) CANADIAN SOLAR CSW3-450MS (450W) PV Modules (23) ENPHASE IQ8M-72-2-US (240V) Inverter(s) SNOHOMISH COUNTY PUD I • W GOB s H ' 20111163 O ICI TF, ?�`V �s�70 N A 1. @NG` DRAWN BY: ALINSUG W. DATE: 2/3/2023 SITE PLAN - PV02 F T TYP HOUSE ELEVATION 52'-7" T TYP EQUIPMENT INFORMATION: ROOF INFORMATION PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA: RAIL MANUFACTURER: SUNMODO ROOF TYPE: COMP SHINGLE PV MODULE COUNT: 23 RAIL PART NUMBER: SMR ROOF FRAMING: MANUFACTURED TRUSS ARRAY AREA: MODULE COUNT * 23.63 ft2 = 543.49 ATTACHMENTS NANOMOUNT RAFTER/TOP CHORD SIZE: 2" X 4" ROOF AREA: 2355.0077 ft2 ATTACHMENT CITY: 108 RAFTER/TOP CHORD SPACING: 24" PERCENT OF ROOF COVERED: 23% SPLICE CITY: 2 ATTACHMENT SPACING: 48" ARRAY WEIGHT: MODULE COUNT * 54.9 Ibs = 1262.70 Ibs MIDCLAMP CITY: 18 POINT LOAD: ARRAY LBS/ATTACHMENTS = 11.69 ENDCLAMP CITY: 56 DISTRIBUTED LOAD: (Ibs/ft2) (ARRAY) WEIGHT/AREA = 2.3 Ibs/ft2 Revolution Energy Systems Inc. 9981 West 190th St Unit K Mokena IL 60448 T: 708-995-1643 SITE INFORMATION NATHAN MOSS 19220 76TH AVE W SEATTLE, WA 98133 AC System Size: 7.48 kW AC / 7.48 kVA DC System Size: 10.35 kW DC Lat, 47.82465 Long,-122.33644 (23) CANADIAN SOLAR CSW3-450MS (450W) PV Modules (23) ENPHASE IQ8M-72-2-US (240V) Inverter(s) a01roP■[N1► IG97[K9111►1CIA 5 'S, E • W GOB s 0 h • 1 �� 20111163 C O sslONAL LNG` Signed 2/03/2023 DRAWN BY: ALINSUG W. DATE: 2/3/2023 ROOF ATTACHMENTS - PV03 SHARED RAIL END CLAMP PV MODULE RAIL 1 END CLAMP DETAILS Material. Aluminum Finish: Black Powder Coating 9KLU KA1L bUIVUINU ) CLAMP �� MID CLAMP DETAILS PV MODULE RAIL M" 48" MAX SPAN FRONT VIEW 6" MAX RAIL NANO MOUNT 2'-8" MIN - 3'-10" MAX 10" MIN - 7 1'-4" MAX / PV MODULE RAIL k? (E) RAFTER/TOP CHORDS 10" MIN - 1'-4" MAX ffV9iff9* 5 L A R Revolution Energy Systems Inc. 9981 West 190th St Unit K Mokena IL 60448 T: 708-995-1643 SITE INFORMATION NATHAN MOSS 19220 76TH AVE W SEATTLE, WA 98133 AC System Size: 7.48 kW AC / 7.48 kVA DC System Size: 10.35 kW DC Lat, 47.82465 Long,-122.33644 (23) CANADIAN SOLAR CSW3-450MS (450W) PV Modules CANADIAN SOLAR CSW3-450MS 450 Specs POWER MAX (PMAX): 450W OPEN CIRCUIT VOLTAGE (VOC): 49.1V MAX POWER -POINT CURRENT (IMP): 10.96A MAX POWER -POINT VOLTAGE (VMP): 41.1V SHORT CIRCUIT CURRENT (ISC): 11.6A SERIES FUSE RATING: 20A ENPHASE: IQ8M-72-2-US (240V) Specs MAX INPUT VOLTAGE: 480 V MAX INPUT CURRENT: 20 A NOMINAL DC INPUT VOLTAGE: 400 V MAXIMUM OUTPUT POWER: 325 W NOM. OUTPUT VOLTAGE: 240 V MAX OUTPUT CURRENT: 1.35 A 1-Phase, 60 HZ, UL 1741 Listed Equipment Schedule TYPE: CITY: DESCRIPTION: RATING: MODULES: (23) CANADIAN SOLAR CSW3-45OMS 450 450 W INVERTERS: (23) ENPHASE IQ8M-72-2-US (240V) 325 W AC DISCONNECTS: (1) PV AC Disconnect, 240V, 2-Pole With 40A Fuses 60 A COMBINER BOX: (1) ENPHASE COMBINER 4 125 A STRING (1): 20.OA 690.12 FZAPID SHUTDOWN COMPLIANT 8 MODULES = I = I - "I J-BOX STRING (2): 20.OA 1 2 8 MODULES I - = = J-BOX I STRING (3): 20.OA 1 2 I I 7 MODULES = I = I = I I L — — — — — — — — — -L — — 1 — — — — — — — — — — t — — — — J-BOX (N)240V/125A PV ENPHASE PV LOAD CENTER, AC COMBINER WITH INTEGRATED MONITORING, NEMA 311 RATED ENVOY -IQ MONITOR 2P-10A 2P-20A Conduit & Conductor Schedule TAG CITY WIRE GAUGE DESCRIPTION CONDUIT SIZE (2) 12 AWG (90°C) Q-CABLE, COPPER (L1, L2) 1 (1) 12AWG (90°C) THWN-2COPPER -(GROUND) N/A - FREE AIR 2 (2) 30 AWG (90°C) THHN/THWN-2, COPPER - (Ll, L2) 3/4" PVC (1) 10AWG (90-C) THWN-2COPPER -(GROUND) 3 (6) 10 AWG (90°C) THHN/THWN-2, COPPER - (L1, L2) 3/4" PVC (1) 10AWG (90-C) THWN-2COPPER -(GROUND) (3) 8 AWG (90°C) THHN/THWN-2, COPPER - (L1, L2, NEUTRAL) 3/4" PVC 4 (1) 8AWG (90°C) THWN-2COPPER -(GROUND) (3) 6 AWG (75-C) THHN/THWN-2, COPPER - (L1, L2, NEUTRAL) 3/4" PVC 5 (1) 6AWG (75°C) THWN-2COPPER -(GROUND) PV AC DISCONNECT 60A VISIBLE, LOCKABLE, LABELED, OPEN 240V, 2-POLE WITH 40A FUSES 2P-20A - - - - - - - - - - - - I 2P-20A I —� " 4 1-BOX__N— �OLrvO� — — CONNECTION AS A LINE/SUPPLY LINE SIDE TAP SIDE CONNECTION - NEC USING INSULATION 705.12(A) PEIRCING 705.12(A) 120/240 VAC (E) 200A MAIN SERVICE PANEL TO UTILITY GRID (E) 200A-2 (E) LOADS (E) LOADS I N I I I L LTL (E) UTILITY METER (E) GROUNDING ELECTRODE ffV9iff9* 5 L A R Revolution Energy Systems Inc. 9981 West 190th St Unit K Mokena IL 60448 T: 708-995-1643 SITE INFORMATION NATHAN MOSS 19220 76TH AVE W SEATTLE, WA 98133 AC System Size: 7.48 kW AC / 7.48 kVA DC System Size: 10.35 kW DC Lat, 47.82465 Long,-122.33644 (23) CANADIAN SOLAR CSW3-4501VIS (45OW) PV Modules (23) ENPHASE IQ8M-72-2-US (240V) Inverter(s) 6101If] :[•ILTA 1617NTi11J►1CAlei Q VISIBLE, LOCKABLE, DRAWN BY: ALINSUG W. LABELED AC DISCONNECT DATE: LOCATED WITHIN 10' 2/3/2023 OF UTILITY METER LINE DIAGRAM - PV05 STRING CALCULATIONS ENPHASE : IQ8M-72-2-US (240V) STRING #1 STRING #2 STRING #3 MAX AC CURRENT 13.54A 13.54A 11.85A MICRO INVERTER(S) IN SERIES: 8 8 7 NOMINAL VOLTAGE / RANGE 211V - 264V 211V - 264V 211V - 264V MAX AC OUTPUT POWER: 260OW 260OW 2275W ARRAY DC POWER: 10350W TOTAL MAX AC CURRENT: 31.15A NUMBER OF CURRENT CARRYING CONDUCTORS PERCENT OF VALUES 4-6 .80 7-9 .70 10-20 .50 SYSTEM OCPD CALCULATIONS INVERTER MODEL(S): EN PHASE IQ8M-72-2-US (240V) # OF INVERTER(S): 23 MAX OUTPUT CURRENT: 1.35A (# OF INVERTERS) X (MAX OUTPUT CURRENT) X 125% <= OCPD RATING (23 X 1.35A X 1.25) = 38.93A <= 40A, OK PV LOAD CALCULATIONS: SUPPLY SIDE TIE-IN FEEDER WIRE RATING: 200A ALLOWABLE SOLAR CALCULATION (FEEDER RATING - 1.25) 160.000OA (FEEDER WIRES ALLOWABLE SOLAR) 160.000OA (AVAILABLE FOR PV) Conduit & Conductor Schedule TAG CITY WIRE GAUGE DESCRIPTION CONDUIT SIZE CONDUCTOR RATING CONDUCTOR TEMP. RATE AMBIENTTEMP TEMP. DERATE # OF CONDUCTORS DERATE CONDUCTOR RATING W/DERATES CONDUIT FILL 1 (2) 12 AWG Q-CABLE , COPPER (L1, L2) N/A - FREE AIR 30A 900C 260C 1.0 N/A - FREE AIR 30A N/A - FREE AIR (1) 12 AWG THWN-2 COPPER- (GROUND) 2 (2) 10 AWG THHN/THWN-2, COPPER - (L1, L2) 3/4" PVC 40A 90°C 26°C 1.0 1.0 40A 12.03% (1) 10 AWG THWN-2 COPPER - (GROUND) 3 (6) 10 AWG THHN/THWN-2, COPPER - (L1, L2) 3/4" PVC 40A 90°C 26°C 1.0 0.8 32A 28.07% (1) 10 AWG THWN-2 COPPER - (GROUND) 4 (3) 8 AWG THHN/THWN-2, COPPER - (L1, L2, NEUTRAL) 3/4" PVC 55A 90°C 26°C 1.0 1.0 55A 28.07% (1) 8 AWG THWN-2 COPPER - (GROUND) 5 (3) 6 AWG THHN/THWN-2, COPPER - (L1, L2, NEUTRAL) 3/4" PVC 65A 75°C 26°C 1.0 1.0 65A 38.37% (1) 6 AWG THWN-2 COPPER - (GROUND) GROUNDING & GENERAL NOTES: 1. PV INVERTER IS UNGROUNDED, TRANSFORMER -LESS TYPE. 2. DC GEC AND AC EGC TO BE SPLICED TO EXISTING ELECTRODE 3. ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT IS FOUND TO BE INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINAL INSPECTION. 4. JUNCTION BOX QUANTITIES, AND PLACEMENT SUBJECT TO CHANGE IN THE FIELD - JUNCTION BOXES DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRE TYPE TRANSITIONS. 5. AC DISCONNECT NOTED IN EQUIPMENT SCHEDULE OPTIONAL IF OTHER AC DISCONNECTING MEANS IS LOCATED WITHIN 10' OF SERVICE DISCONNECT. INTERCONNECTION NOTES: 1. INTERCONNECTION SIZING, LIMITATIONS AND COMPLIANCE DETERMINED IN ACCORDANCE WITH [NEC 705.121, AND [NEC 690.64]. 2. GROUND FAULT PROTECTION IN ACCORDANCE WITH [NEC 215.9], [NEC 230.95] AND [NEC 690.5] 3. ALL EQUIPMENT TO BE RATED FOR BACKFEEDING. 4. PV BREAKER TO BE POSITIONED AT THE OPPOSITE END OF THE BUSBAR RELATIVE TO THE MAIN BREAKER. DISCONNECT NOTES 1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING LIVE ARE CONNECTED TO THE TERMINALS MARKED "LINE SIDE" (TYPICALLY THE UPPER TERMINALS) 2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE -BREAK SWITCH S L A R Revolution Energy Systems Inc. 9981 West 190th St Unit K Mokena IL 60448 T: 708-995-1643 SITE INFORMATION NATHAN MOSS 19220 76TH AVE W SEATTLE, WA 98133 AC System Size: 7.48 kW AC / 7.48 kVA DC System Size: 10.35 kW DC Lat, 47.82465 Long,-122.33644 (23) CANADIAN SOLAR CSW3-45OMS (450W) PV Modules (23) ENPHASE IQ8M-72-2-US (240V) Inverter(s) SNOHOMISH COUNTY PUD DRAWN BY: ALINSUG W. DATE: 2/3/2023 ELECTRICAL CALCS - PV06