Air Balance ReportRecord Date: F:,roject Number: 2/22/2023 22•505 Air Balance Report. Project Name: Edmonds Yacht Club —�—_-- Unit ICI: RTU-6 Location: Roof_ --- Unit Type: Package_ Unit Design Airflow letting: 1626 _ Ac;lual Airflow (CFM): 1670 Inlet S.P.: N/A Max Rated CFM: 1,62f> 71 Min Rated CFM: Outlet Test Report 430 SUS/ '153rd St Burien, WA 98166 206-762-1960 Address: 326 Admiral Way City/State: Edmonds, WA !,8020 --�! Mfd & Model: York, Z.J048N06P2AAA1 ;Serial No.: --- Inlet Size: N/AJ Fan Speedl--_=1 C:oeff. = 'A Igo. Size Design C:F Initial Test 1 Test 2 Nest 3 Te-st 4 Test 5 Test 6 T'est 7 Test 8 Final % of design 1 •...2 _ 6' 100 . 9`} 107 107 _ _ 10" 225 _ 177 198 --_—_ -- ,._ _---_ 219 -_97�- . 3 101, 225 257 206 N 230 1_02 - 4 81, 200 215 _ _ _ 219 _ I 10 ,- 5 200 _ 165 152 200 100 6 ..•.7 _8" 8" 225 268 - --_ � _ 229 .• � 102 ... -^8" _ 225 2_99- -- -- .� _. 233 ..� 104 8 _ _• 8" 225. 96 296T 233 ..._--1 q4 -- -- - — - ----- 10 Totals 1625 1 *771 152 404 0 0 0 0 0 0 1670 10.3% Comments: Unit air flow is 103"K. of design CFM. Technician: Trent Scacco Date:-/22/20.23 1 Record Date: 2/22/2023 _ [project Number: _—_�-22-505 Air Balance Report Project Name: Edmonds Yacht Club Unit ID: EF-1 _ Location: Break Room Unit Type: Exhaust I=an Design Airflow Setting: 350 Ac:lual Airflow (CFM): Inlet S.P.: N!A .__J Max Rated CFM: 356 Min Rated CFIVI:,_— Ou1aet Test Report 430 SW 153rd St Burien, WA 98166 206-762-1960 Address: 326 Admiral W iy _ -- f.;Ity/SI:ate: Edmonds, WA! 8020 Mfg & Model: FG 6M EC Serial No.: 1007066630--___---- Inlet. Size:C:_-1 FanSpeedli_CM �_-1 C,oeIf. EEA Su I /fir ...- -- -•-- --_ — — _.._—_ IVo. Size Design l FD Initial Test 1 7est 2 `test 3 T"tist 4 Test 5 Test 6 Te,st T Test 8 Final % of design '--- .._ 1 ----8'� 350 234.... _ — ...-- ---• — 234 67— 2 3- _ — ---- --- 4 —_ - --- _ - — 5---- 6 10 12 _ Totals 350 234- 0 0 0 U 0E 0- 0 234 — 67% Comments: Exhaust is only a 6" exhaust. The ecru motor is turned to high. We are unable to achieve desired CFM with this far Unit air flow is 670/4,—of design I:FM. Ted-mician: "Front Scacco Date:I 2/22/2023 i Record Date: F'roject Number: 2/22/2023 22-505 Air Balance Report rb30 SW 'i53rd St Burien, WA 98166 206-762-1960 Project Name: Edmonds Yacht Club Address: 326 Admiral Way Unit ID: RTU-1 --- _--�_— City/Steil:(-:: Edmonds, WA!)8020 Location: Roof -- ---- Mfg & Model: York, ZJ036N04P2AAA1 Unit Type: Package: unit_ __-- :aerial No.: —_— Design Airflows Setting: 1200 Actual Airflow (CFM): 1239• Inlet S.P.: N/A Inlet Size: N/A Fan Speed Max Rated CFIV1: 1,2R. Coeff.EN'A Min Rated CFIb1: ,- Outlet Test Report (:',up TIVo. I Fur ••- Size Design C'.-FIV Initial Test 1 Test 2 -Test 3 Test 4 Test 5 Tes*i 6 Test 7 t Tes8 Fi nal %of design •- 1 �--200 8.1 -- 224_• _-- _ -- - 219 110 - 2 — 8" 200 --_ 202 _ -- - +- •• -- 202 ••.__ _ 101 - ... 3 _-81, -_. 200 _ 194 - - - 197 -.. 4 811 200 .— — _.... _- ..,-- ---• 220 ...— _99_ 110 -- • . 5 _-..£t" _1.20.._ 200 197 -- .. --- 198 - 99 --- 6 rtl 8" 200 16EI- 16 _— 203 _- - _ ....- --- 203 --- 102 7 -- - -- - - - - 8 10---.- 11 Totals 1200 12U3 203 0 0 0 0 0 0-� 0 1239 103% Comments: Unit air flow is 10311X- of design C:FM. Technician: Trent Scacco Date: I 2/22/2023� u Record Date: _ 2/22/2023 _ I''roject Number: _22-505 _ Air Balance Report Project Name: Edmonds Yacht Club IJ nit ID: RTU-4 Location: 12oof-- Unit Type: Packagt:: Unit-- -_ _—_-- Design AirflowSetting: 1200 Ad.ual Airflow (CFM): 1213 - Inlet S.P.:[- N/A..-1 Max Rated CFIVI: 1 1,20'' Min Rated CFM: .-] Oulaet Test Report 430 SW 153rd St Burien, WA 98166 206-762-1960 Address: 326 Admiral Way_ C lty/State: Edmonds, WA !8020 Mf(:1.I & MUCIC'.I: York, Z.J036NO 1P2AAA1 ,-ierial No.: _ _ _ Inlet Size: N/El Fan Speed 1. Coeff. NIA -140. Size De -sign Uff Initia 1 Test 2 Wrest 3 Test 4 Test 5 Test 6 Test I Test 8 Final . design _- 1 _ 10" 300 277 _Test 295 N_ '. •- � —_ 295 _ 9_8 _- 2 6" _ 100 97_._ 107 -- -•- ...- - — _ 107 107 _ —'110 3 --�81, _ 200 214 220 220 �—'I ..4 _ f}" 200 192.- 204 -- ..- - 204 G2 .---N98 "_. 5 8" 200 175 _ 195 —__ 195 6 8" _ 100 200- _ 100 r — 100 100 10------- - - - ---- 11 _..---- _ —_ -- --- - __ — -- - __jtotals 1200 1250 1213 0 0 0—To 0 0 0 1213 1f:i1% — Comments: Unit air flow is 101IX. of design (-,.FM. Technician: Trent Scacco Date: C 2/22/2023 1 Record Date: 2/22/2023 Project Number: 22-•505 ---___ ---- Air Balaince Report.. Project Name: Edmonds Yacht Club Unit ID: RTU-2 ..--•--- ...--___ Location.' Roof Unit Type: Package Unit Design'Airflow Setting: 800 At:.f.ual Airfloina (CFM): 861 -- Inlet S.P.: N/A _1 Max Rated CFM: 800 Min Rated CFM: Outlet Test Report 4 30 SW 153rd St BUrien, WA 98166 206-762-1960 Address: 326 Admiral Way_ City/State: Edmonds, WA !)8020 Mfg & Model: York, D2NZ0N N05606 `.aerial No.: Inlet. Size: r NiE1_I Fan Speed.— __1 Coeff. N/A No. .•- __—Size � Design CFIGFIV Initial 'Test 1 Test 2 Wrest 3 Test 4 Test 5 Test 6 Test 7 Test 8 Final % of design 1 81^ 200 188 -- -- �'— — 208 104 •,- 2 M8" 200 220~ —_ .— •.•— -- _ 219 ---- 110 3 81, 200 243 220 _ - — 215 108 .-. 4 —� 8" _ 200 221� --- — .� ...— __.._ 219 ---110 — 5 6 — -- --- -- — - -- 7 8- 9 10 - J- _ Totals 80G 872 E 0 0 M U. I 0 U OYE E61— IC)8�% Comments: Unit air flow is__ 108n/0 _of design C.FIVI. Technician: Trent Scacco Date: 1 .Record [Date: F ,roject Number: 2/22/2023 .. 22-505 -•------- Air 13alance Report Project Name: Edmonds Yacht Club Unit ID: _ RTU-3 Location: —�_--- Roof Roof Unit Type: - - --__- -- Ij Ckage.Unit�-- Design Airflow Settingf 870 Actual Airflow (CFM): L 886 Inlet S.P.: N/A_7 Max Rated CRVI: 870 _ Min Rated CFIVI: .. Outlet Test Report 4 30 SW 153rd St Burien, WA 98166 206-762-1960 Address. 326 Admiral Way C ity/St@te: Edmonds, WA !.8020 Mfg & MoClel: York, D2NZ02,11405606 erial No.: Inlet Size: N//1] Fan Speech. Coeff. F—WA I IJo. Size Design FFIV Initial Test 1 Test 2 Test 3 T,=st 4 Test 5 Te;it 6 T'eestt 1 Test T Final %of cIe_sign 1 _- £S" 150 174 154 - 154 •._-- '103 -- 2 _ ---8" 150 130- 149 Y_-- ...- -� 149 � 99 -- .- 3 -- £1" _ 150 152 -_ 154 --_ - • -- -M- 154 'I 03 _ ... 4 _ �-8" _ 150 154 156 - -�-_- --- _- — 156 •.---_ — 104. 5 8" 150.--_ 147 152 --- _-- - 152 101 —_ 6 6" 120 121 _ 121 - -- 121 101 8 ---.w ----- 10 ---- - - - - - _--Ibtals 870 878 886 0 " -0 - 0 0 0 0 0 886 I G2% Comments: Unit air flow is 102`ii__of design C;FIVI. Technician: Trent Sc:acco Date: 1--:2,122,12023 0