Loading...
APPROVED FIR2022-0123+Fire_Alarm_Battery_Calculations+11.10.2022_10.36.25_PM+3215272ZEVENBERGEN CAPITAL INVESTMENT III EDMOND I S YACHT CLUB FIRE ALARM TENANT IMPROVEMENT SHEET # SHEET TITLE FA-01 SYSTEM INFORMATION FA-02 TYPICAL WIRING, MOUNTING DIAGRAMS & CALCULATIONS FA-03 FIRE ALARM TENANT IMPROVEMENT FLOOR 2 LAYOUT SHEET INDEX ADDITION OF 1 NEW REMOTE BOOSTER POWER SUPPLY, 15 NEW CEILING MOUNT HORN/STROBES AND 4 NEW CEILING MOUNT STROBES DUE TO THIS TENANT IMPROVEMENT ON FLOOR 2 SCOPE OF WORK W RE SCHEDUEE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE S STROBE CIRCUIT TWO #14 FPLP CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1 /2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1 /4" .60 SQUARE INCH 1-1 /2" .82 SQUARE INCH 2" 1.34 SQUARE INCH DMONDS, WASHINGTON GENERAL NOTES: 1. ALL WALL —MOUNTED AUDIBLE & VISUAL SIGNALING APPLIANCES SHALL HAVE THEIR HEIGHTS ABOVE THE FINISHED FLOOR AT 80" TO BOTTOM. NFPA 72, 2013 EDITION, ALLOWS 80"-96" FOR VISUAL DEVICES (CH. 4-4.4) AND REQUIRES A MINIMUM OF 90" TO TOP FOR AUDIBLE DEVICES OR 6" FROM CEILING, WHICHEVER IS LOWER (CH. 4-3.5). FOR SLEEPING AREAS GREATER THAN 16' (LINEAR) VISIBLE NOTIFICATION SHALL BE WITHIN 16' OF PILLOW AND GREATER THAN OR EQUAL TO 24" FROM CEILING TO TOP OF LENS FOR 110cd (CH. 4-4.4.3.2) 2. ALL EQUIPMENT SHALL BE U.L. LISTED. 3. ELECTRICAL CONTRACTOR SHALL FURNISH ACCESS PANELS TO AREAS THAT REQUIRE SERVICING, TROUBLE SHOOTING, ETC. 4. DO NOT DEVIATE FROM CONDUIT RUNS AS SHOWN ON FLOOR PLANS WITHOUT PRIOR APPROVAL FROM SYSTEM SUPPLIER (GUARDIAN SECURITY SYSTEMS, INC., TEL (206)622-6545). FACTORS SUCH AS EXCESSIVE VOLTAGE DROP, ADDITIONAL PARTS, ENGINEERING, ETC., THAT ARE A RESULT OF CONDUIT RUN DEVIATIONS SHALL BE THE SOLE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. 5. DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIR —FLOW, NOR CLOSER THAN 3 FEET (900mm) FROM AN AIR SUPPLY DIFFUSER. 6. ALL 120VAC POWER REQUIREMENTS FOR THE FIRE ALARM SYSTEM SHALL BE FURNISHED BY THE ELECTRICAL CONTRACTOR AND SHALL MEET ALL REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION. 7. ALL FIRE ALARM DEVICE BACKBOXES, FIRE ALARM TERMINAL CABINETS, GUTTERS, JUNCTION BOXES, AND ASSOCIATED CONDUITS SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. REFER TO FIRE ALARM SYMBOL LIST AND/OR MOUNTING DETAILS FOR ADDITIONAL INFORMATION. SYSTEM SUPPLIER PROVIDED BACKBOXES SHALL BE INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. 8. SMOKE DETECTOR TESTING SHALL BE ACCOMPLISHED WITH APPROVED SMOKE. 9. ALL WIRING, INITIATING DEVICES AND ANNUNCIATOR PANEL SHALL BE SUPERVISED TO THE PRINCIPAL POINT OF ANNUNCIATION. THE FIRE ALARM CONTROL PANEL TO SUPERVISE THE ANNUNCIATOR PANEL, ALL INITIATING AND INDICATING DEVICE CIRCUITS. 10. ALL WIRING SHALL BE CUT FOR IN AND OUT. WIRING SHALL NOT BE LOOPED THROUGH DEVICES. ALL SPLICED WIRE POSSESING SHIELDS SHALL HAVE SHIELDS SPLICED AND TAPED TO PREVENT GROUND FAULTS. 11. THE ALARM SYSTEM SHALL HAVE AN AUDIBILITY OF NOT LESS THAN 15dB ABOVE AMBIENT NOISE LEVELS. TESTING SHALL BE ACCOMPLISHED WITH A dB METER. 12. ALL DEVICES IN THE ALARM SYSTEM SHALL BE COMPATIBLE AND INSTALLED PER MANUFACTURER'S SPECIFICATIONS. 13. FIRE ALARM SYSTEM INSTALLATION COMPANY SHALL BE UL LISTED (UUJS). 14. INSTALLATION SHALL BE IN STRICT COMPLIANCE WITH NFPA, LOCAL AND STATE, NEC AND CONTRACT DRAWINGS 15. ALL CONDUIT SIZING AND ROUTING BY ELECTRICAL CONTRACTOR PER NEC AND AHJ 16. THE FACP SHALL NOT BE ENERGIZED WITHOUT THE PRESENCE OF G.S.S. TECHNICIANS 17. A SET OF INSTALLATION AS —BUILT DRAWINGS SHOWING ACTUAL CONDUIT AND CONDUCTOR ROUTES SHALL BE KEPT BY PROJECT FOREMAN FOR USE BY G.S.S. FIELD TECHNICIANS 18. A SET OF AS BUILT DRAWINGS TO BE TURNED INTO GSSINC WITH APPROPRIATE COLOR CODED MARKUP DRAWINGS (SEE SYMBOL LEGEND FOR COLOR CODING). Approved DFM cabs-u.rt South County Fire Date: 12/06/2022 12-06-2022 PLAN REVIEW NOTES: APPROVED DFM BURT STEVE SENDLAKOWSKI NICET LEVEL III CERT. #115442 EXP. 01/01/2024 QUANTITY SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT E FACP FIRE ALARM CONTROL PANEL 5808 SILENT KNIGHT — 66" A.F.F. E (EXISTING) TO TOP SMOKE DETECTOR — SILENT KNIGHT CEILING E O O E (EXISTING) 1 NAC REMOTE BOOSTER PS-8—LP WHEELOCK — 66" A.F.F. POWER SUPPLY TO TOP FIRE ALARM HSWC WHEELOCK 4S DEEP BOX CEILING 15 o HORN STROBE 4( FIRE ALARM STWC WHEELOCK 4S DEEP BOX CEILING STROBE ILL END —OF —LINE LOCA IONSY RESISTOR IN FIELD BATTERY 2 12V 18AH SLA-1075 INTERSTATE BATTERY FACP I NAC E SYMBOLS LEGEND WORK AREA �4�# a SITE PLAN_ N SCALE: NTS S S S S S S S S S S 0 0 0 0 0 0 0 0 0 EOL S2 S2-1 S2-2 S2-3 S2-4 S2-5 S2-6 S2-7 S2-8 S2-9 S2-10 15Cd 15Cd 15Cd 15Cd 15Cd 15Cd 15Cd 3OCd 3OCd 15Cd EOL S1 S1-1 S1-2 S1-3 S1-4 S1-5 S1-6 S1-7 S1-8 S1-9 15Cd 15Cd 3OCd 15Cd 3OCd 3OCd 75Cd 75Cd 3OCd IaIZftiy�X0 81I PW z 0 Lu w CO Q w w � o �000\ o� z N o � � Z o N L4 x 3: Q yw Z~ a L ) � L,7 � 0 N L:> N a Q � N � w m w J U Lu z 0 CL U C0 w 0 0 z_ 3 a 0 CL 0 W w Q0) o N N � �aaaaa m J U F0— U Q z� Oz LLI 7�; N LLIIr LU > Op ..0 O N p � �JCC) F ILL d� z� �Q W 0 z >>� Q J 0 LL W Ir � -z0 z cr oo J (w Q Q N w `o ELE QLL U LU z W I— 1= r/ m RES B v, WNov 14 2CI22 CITY OF EDM DS w DEVELOPMENTS VICES W DEPARTME w ■ (SCALE -NOT TO SCALE DRAWN BY: C. ENGSTFELD DESIGNED BY: T. QUAALE DATE: 1 1 /09/22 BACKROUND PLAN PROVIDED BY: JOB NUMBER: 67943-1 WIRE DESIGNATION GENERAL NOTES RISER DETAIL Proprietary & Confidential, Copyright 2013 Guardian Security Systems, Inc. All Rights Reserved SHEET FA-01 TRIGGER FROM EXISTING FACP FIRE ALARM BOOSTER POWER SUPPLY BATTERY CALCULATION Project: ZEVENBERGEN CAPITAL INVESTMENT, EDMONDS YACKT CLUE Panel: PS-8-LP BOOSTER POWER SUPPLY Date: November 9, 2022 Module/Device Qty Standby Total Standby Alarm Total Alarm (mA) (mA) (mA) (mA) Power Module 1 15 15 01 140 140 1 0 A TOTAL FIRE ALARM POWER SUPPLY 15 140 B Auxiliary Device Current 0 0 C Notification Appliance Load (Max. Total / mA) 0 1664 Total(A)= 15 Total(B)= 1804 CALCULATION D Total current ratings of all devices in system (line A + line B + line C) 15 1804 E Total current ratings converted to amperes (line D x .001) 0.015 1.804 F Number of standby hours (24 or 60 per NFPA 72, Chapter 1, 1-5.2.5). 24 G Multiply lines E and F Total Standby AH 0.36 H Alarm sounding period in hours (15 mins= 0.25 hours) 0.25 Multiply lines E and H Total Alarm AH 0.451 J Add lines G and I Total Standby and Alarm AH 0.811 K Multiply line J by 1.2 (20% extra insurance to meet desired performance) 0.9732 12-V DC BATTERYSIZE RECOMMENDED (AMPERE -HOUR) 7 Fqo 0� CI CAUTION: LO] Imo' I Imo' I �pryNS CAUTION: D 01 CAUTION HOT SURFACES Fo PROIECININ ® Tb T12 ° ACAIH�SjT FIRpE�HAZARO� ❑ ❑ TPE � RATNG � �, DA 2WV ❑� FI +� RBD 0C RZI AC LOSS TROUBLE G CAUTION: CONTRUM PR —IN AGAINST FIIRREE HAZARD AC PONEN = 0 - 015 REPLTYPE RATHGAN E RO `� U7= R BATIFRY T31 O P84B55 WEELOCX -0 1 a IL mN v g NILI SNL„� �_ N1d IN /'°❑ N1G11N / NR s'l Ntl1lom pus m�/ ttvaB �® Pmn.0 BPS ( PS-8-LP ) 6 Yf1fVT ±❑ NIXP/YP ® 1 N1giY.i M4 ❑ � NF +AUX - +NACI- +NAC2- +NAGS- +NAG + N - IY OUT OUT CUT OUT OUT ARM +RET I- TROUBUE +CCI + IX2 - +RE12 - [G]+sAls - + u - + 9U COM NC NO BETn � ED R PS-8-LP POWER SUPPLY WIRING DETAIL SPARE SPARE NAC CIRCUIT S2 NAC CIRCUIT S1 Notification Appliance Circuit Detail PROJECT: ZEVENSBERGEN CAPITAL INVESTMENT, EDMONDS YACHT CLUB TI Panel: PS-8-LP POWER SUPPLY Wire Resistance 3.07 Date: November 9, 2022 CURRENT TOTAL= 1664.00 2 HSWC @75Cd 1 82 164 HSWC @30Cd 102 2 HSWC @75Cd 145 290 HSWC @110Cd 197 3 STCW @75Cd 57 171 #225#22.851 STCW @30Cd 85 DEVICES 9 TOTAL mA= 829 14 829 Tota I W i re Resista nce ( R) (W L * 2) * (Rlft) 1.38 Total Device Load, Amps (I) (Total Cct Load) 0.83 Voltage Drop ( E) (E= I * R) 1.15 i111111k 22.85 7 HSWC @15Cd 82 574 2 HSWC @30Cd 102 2 iHSWC @75Cd 145 0 HSWC @110Cd 197 1 STCW @ 15Cd 57 57 - STCW @30Cd 85 DEVICES 10 TOTAL mA= 835 14 175 23.10 835 Tota I W i re Resista nce ( R) (W L * 2) * (Rlft) 1.07 Total Device Load, Amps (I) (Total Cct Load) 0.84 Voltage Drop ( E) (E= I * R) 0.90 EOL Voltage 24 - E) 23.10 CALCULATIONS CEILIN TI LE HORN STROBE/STROBE MOUNTING DETAIL (DROP CEILING TO PS-8-LP POWER SUPPLY S HORN STROBE HARD LID - CEILING STROBE 4S BOX CEILING STROBE HORN STROBE/STROBE MOUNTING DETAIL (HARD LID HORN STROBE TYPICAL NAC CIRCUIT WIRING DETAIL HORN STROBE EOL STEVE SENDLAKOWSKI NICET LEVEL I i CERT. #115442 EXP. 01 %i3i%2b Y4 cn z 0 w w C0 Q W J W � Ili O 0\ ao 0\ 00 Z N O `0 ~ � \C) Z O N x 3: Q yw a cn LC) LD \? Q N L:> N a C) c� N � � J m � w J U w z 0 CL U C0 W Ln 0 z_ a o' 0 CL 0 W Q0) o N N \ � CD ❑❑❑❑❑ m Cn J z U 0 U U U) J z U 0 z 06 �w 0 w N LU > Ir O(p J C6 0 Q W w 1-->>� 0 z w w<z JQ z z 222 00 J � �w QQ� O LLI Q IY LL 0 U z z �w �V w J in RESIL B U WCITY Nov 14 2 22 OF EDM DEVELOPMENT S IDS � VICES w DEPARTME A 1 SCALE: NOT TO SCALE)l DRAWN BY: C. ENGSTFELD DESIGNED BY: T. QUAALE DATE: 1 1 /09/22 BACKROUND PLAN PROVIDED BY: JOB NUMBER: 67943-1 TYPICAL WIRING AND MOUNTING DETAILS Proprietary & Confidential, Copvright 2013 Guardian Security Systems, Inc. All Riqhts Reserved SHEET FA-02 NOT IN CONTRACT I / I I I I I ' � I I I I NOT IN CONTRACT 1 I ' I / I I I I I r—� r-------------J I I S2-2 S I I 15Cd I I o — — — — I I I I ' I S ' I S2-10 S ' I � EOL 15Cd S2 I S2- 1 0 S2-9 0 15C< 1 I 30Cd L - - - - S2-7 15Cd I I L--------\ I � I ` I I 1 I 1 I 1 I 1 I 1 I 1 I 1 I J 7NOT IN CONTRACT FLOOR 2 FIRE ALARM TENANT IMPROVEMENT LAYOUT SCALE: 3/16" = 1'0" STEVE SENDLAKOWSKI NICET LEVEL Ii CERT. #115442 EXP. 0`1%i3i%2b Y4 V) z 0 �n LLJ w CO Q LLJ J LLJ � r0 o ON ON 00 z o \-0 ~ � \0 o LUx Q yw J Z~ w QC Ln - LO � � oLO N LJJ N Q � o (n N r1r) � J W m w J U W z 0 U LLJ V) 0 Z Q Cr 0 CL 0 LLJ 0 CV CV 0 0aaaaa m � c� O H U � N U) cr o O z� O Oz J LLI LL wLU N M > .. O O c\1 J LU 00 G a LU LU > zap Z vi O U z Qo z0 Er L U oC z moo — a LLJ J a� z � LLJ EL-Ir z a LU U z � w m RESL B a WNov 14 2 22 w CITY OF EDMC DEVELOPMENTS IDS VICES IM LUDEPARTME w ■ LL SCALE: 3/ 1 6" = 1 ' 0" DRAWN BY: C. ENGSTFELD DESIGNED BY: T. QUAALE DATE: 1 1 /09/22 BACKROUND PLAN PROVIDED BY: JOB NUMBER: 67943-1 Proprietary & Confidential, Copyriqht 2013 Guardian Security Systems, Inc. All Riqhts Reserved SHEET FA-03