APPROVED FIR2022-0123+Fire_Alarm_Battery_Calculations+11.10.2022_10.36.25_PM+3215272ZEVENBERGEN CAPITAL INVESTMENT
III EDMOND I S YACHT CLUB
FIRE ALARM TENANT IMPROVEMENT
SHEET # SHEET TITLE
FA-01 SYSTEM INFORMATION
FA-02 TYPICAL WIRING, MOUNTING DIAGRAMS & CALCULATIONS
FA-03 FIRE ALARM TENANT IMPROVEMENT FLOOR 2 LAYOUT
SHEET INDEX
ADDITION OF 1 NEW REMOTE BOOSTER POWER SUPPLY, 15 NEW CEILING
MOUNT HORN/STROBES AND 4 NEW CEILING MOUNT STROBES DUE TO THIS
TENANT IMPROVEMENT ON FLOOR 2
SCOPE OF WORK
W RE SCHEDUEE AND CONDUIT FILL CHART
WIRE DESIGNATION
SYMBOL DESCRIPTION
NUMBER OF CONDUCTORS SIZE
TYPE
COLOR CODE
S STROBE CIRCUIT
TWO #14
FPLP
CONDUIT FILL CHART
NO. OF CONDUCTORS
VOLTS WIRE SIZE TYPE DIMENSIONS
AREA
TWO
600V #12 AWG THHN/THWN .244
O.D.
.0467
TWO
600V #14 AWG THHN/THWN TWISTED .210
O.D.
.0346
TWO CONDUCTOR
300V #18 AWG FPL TW CABLE .156
O.D.
.0191
CONDUIT FILL
CALCULATE THE
TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT
FROM
THE TABLE
ABOVE. CHOOSE
THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL
DIMENSION
FROM
THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE
WIRE.
CONDUIT SIZE MAXIMUM FILL
1 /2" .12 SQUARE INCH
3/4" .21 SQUARE INCH
1" .34 SQUARE INCH
1-1 /4" .60 SQUARE INCH
1-1 /2" .82 SQUARE INCH
2" 1.34 SQUARE INCH
DMONDS, WASHINGTON
GENERAL NOTES:
1. ALL WALL —MOUNTED AUDIBLE & VISUAL SIGNALING APPLIANCES SHALL HAVE
THEIR HEIGHTS ABOVE THE FINISHED FLOOR AT 80" TO BOTTOM. NFPA 72,
2013 EDITION, ALLOWS 80"-96" FOR VISUAL DEVICES (CH. 4-4.4) AND
REQUIRES A MINIMUM OF 90" TO TOP FOR AUDIBLE DEVICES
OR 6" FROM CEILING, WHICHEVER IS LOWER (CH. 4-3.5).
FOR SLEEPING AREAS GREATER THAN 16' (LINEAR) VISIBLE NOTIFICATION SHALL BE
WITHIN 16' OF PILLOW AND GREATER THAN OR EQUAL TO 24" FROM CEILING
TO TOP OF LENS FOR 110cd (CH. 4-4.4.3.2)
2. ALL EQUIPMENT SHALL BE U.L. LISTED.
3. ELECTRICAL CONTRACTOR SHALL FURNISH ACCESS PANELS TO AREAS THAT
REQUIRE SERVICING, TROUBLE SHOOTING, ETC.
4. DO NOT DEVIATE FROM CONDUIT RUNS AS SHOWN ON FLOOR PLANS WITHOUT
PRIOR APPROVAL FROM SYSTEM SUPPLIER (GUARDIAN SECURITY SYSTEMS, INC., TEL
(206)622-6545). FACTORS SUCH AS EXCESSIVE VOLTAGE DROP, ADDITIONAL
PARTS, ENGINEERING, ETC., THAT ARE A RESULT OF CONDUIT RUN DEVIATIONS
SHALL BE THE SOLE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
5. DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIR —FLOW, NOR CLOSER THAN
3 FEET (900mm) FROM AN AIR SUPPLY DIFFUSER.
6. ALL 120VAC POWER REQUIREMENTS FOR THE FIRE ALARM SYSTEM SHALL BE
FURNISHED BY THE ELECTRICAL CONTRACTOR AND SHALL MEET ALL REQUIREMENTS
OF THE AUTHORITIES HAVING JURISDICTION.
7. ALL FIRE ALARM DEVICE BACKBOXES, FIRE ALARM TERMINAL CABINETS,
GUTTERS, JUNCTION BOXES, AND ASSOCIATED CONDUITS SHALL BE FURNISHED
AND INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. REFER
TO FIRE ALARM SYMBOL LIST AND/OR MOUNTING DETAILS FOR ADDITIONAL
INFORMATION. SYSTEM SUPPLIER PROVIDED BACKBOXES SHALL BE INSTALLED
BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED.
8. SMOKE DETECTOR TESTING SHALL BE ACCOMPLISHED WITH APPROVED SMOKE.
9. ALL WIRING, INITIATING DEVICES AND ANNUNCIATOR PANEL SHALL BE
SUPERVISED TO THE PRINCIPAL POINT OF ANNUNCIATION. THE FIRE ALARM
CONTROL PANEL TO SUPERVISE THE ANNUNCIATOR PANEL, ALL INITIATING
AND INDICATING DEVICE CIRCUITS.
10. ALL WIRING SHALL BE CUT FOR IN AND OUT. WIRING SHALL NOT BE
LOOPED THROUGH DEVICES. ALL SPLICED WIRE POSSESING SHIELDS SHALL HAVE
SHIELDS SPLICED AND TAPED TO PREVENT GROUND FAULTS.
11. THE ALARM SYSTEM SHALL HAVE AN AUDIBILITY OF NOT LESS THAN 15dB ABOVE
AMBIENT NOISE LEVELS. TESTING SHALL BE ACCOMPLISHED WITH A dB METER.
12. ALL DEVICES IN THE ALARM SYSTEM SHALL BE COMPATIBLE AND INSTALLED
PER MANUFACTURER'S SPECIFICATIONS.
13. FIRE ALARM SYSTEM INSTALLATION COMPANY SHALL BE UL LISTED (UUJS).
14. INSTALLATION SHALL BE IN STRICT COMPLIANCE WITH NFPA, LOCAL AND STATE,
NEC AND CONTRACT DRAWINGS
15. ALL CONDUIT SIZING AND ROUTING BY ELECTRICAL CONTRACTOR PER NEC AND AHJ
16. THE FACP SHALL NOT BE ENERGIZED WITHOUT THE PRESENCE OF G.S.S. TECHNICIANS
17. A SET OF INSTALLATION AS —BUILT DRAWINGS SHOWING ACTUAL CONDUIT AND
CONDUCTOR ROUTES SHALL BE KEPT BY PROJECT FOREMAN FOR USE BY G.S.S.
FIELD TECHNICIANS
18. A SET OF AS BUILT DRAWINGS TO BE TURNED INTO GSSINC WITH APPROPRIATE
COLOR CODED MARKUP DRAWINGS (SEE SYMBOL LEGEND FOR COLOR CODING).
Approved
DFM cabs-u.rt
South County Fire
Date: 12/06/2022
12-06-2022
PLAN REVIEW
NOTES: APPROVED
DFM BURT
STEVE SENDLAKOWSKI
NICET LEVEL III
CERT. #115442 EXP. 01/01/2024
QUANTITY
SYMBOL
DESCRIPTION
MODEL
MANUFACTURER BACKBOX
MOUNTING HEIGHT
E
FACP
FIRE ALARM
CONTROL PANEL
5808
SILENT KNIGHT —
66" A.F.F.
E
(EXISTING)
TO TOP
SMOKE DETECTOR
—
SILENT KNIGHT
CEILING
E
O
O E
(EXISTING)
1
NAC
REMOTE BOOSTER
PS-8—LP
WHEELOCK —
66" A.F.F.
POWER SUPPLY
TO TOP
FIRE ALARM
HSWC
WHEELOCK 4S DEEP BOX
CEILING
15
o
HORN STROBE
4(
FIRE ALARM
STWC
WHEELOCK 4S DEEP BOX
CEILING
STROBE
ILL
END —OF —LINE
LOCA IONSY
RESISTOR
IN FIELD
BATTERY
2
12V 18AH
SLA-1075
INTERSTATE BATTERY
FACP I NAC
E
SYMBOLS LEGEND
WORK AREA
�4�#
a
SITE PLAN_ N
SCALE: NTS
S
S
S
S
S
S
S
S
S S
0
0
0
0
0
0
0
0
0 EOL S2
S2-1
S2-2
S2-3
S2-4
S2-5
S2-6
S2-7
S2-8
S2-9 S2-10
15Cd
15Cd
15Cd
15Cd
15Cd
15Cd
15Cd
3OCd
3OCd 15Cd
EOL S1
S1-1
S1-2
S1-3
S1-4
S1-5
S1-6
S1-7
S1-8
S1-9
15Cd
15Cd
3OCd
15Cd
3OCd
3OCd
75Cd
75Cd
3OCd
IaIZftiy�X0 81I PW
z
0
Lu
w
CO
Q
w
w
�
o
�000\
o�
z
N
o
�
�
Z
o
N
L4
x
3:
Q
yw
Z~
a
L )
�
L,7
�
0
N
L:>
N
a
Q
�
N
�
w
m
w
J
U
Lu
z
0
CL
U
C0
w
0
0
z_
3
a
0
CL
0
W
w
Q0)
o
N
N
�
�aaaaa
m
J
U
F0—
U
Q
z�
Oz
LLI
7�; N
LLIIr
LU > Op
..0 O
N
p
� �JCC)
F ILL d�
z�
�Q
W 0
z >>�
Q
J
0 LL
W Ir
� -z0
z cr oo
J (w Q Q N
w `o
ELE
QLL
U LU
z
W I—
1= r/
m RES B v,
WNov 14 2CI22
CITY OF EDM DS w
DEVELOPMENTS VICES
W DEPARTME
w ■
(SCALE -NOT TO SCALE
DRAWN BY:
C. ENGSTFELD
DESIGNED BY:
T. QUAALE
DATE: 1 1 /09/22
BACKROUND PLAN PROVIDED BY:
JOB NUMBER: 67943-1
WIRE DESIGNATION
GENERAL NOTES
RISER DETAIL
Proprietary & Confidential, Copyright 2013
Guardian Security Systems, Inc. All Rights Reserved
SHEET
FA-01
TRIGGER FROM
EXISTING FACP
FIRE ALARM BOOSTER POWER SUPPLY BATTERY CALCULATION
Project: ZEVENBERGEN CAPITAL INVESTMENT, EDMONDS YACKT CLUE
Panel: PS-8-LP BOOSTER POWER SUPPLY
Date: November 9, 2022
Module/Device Qty Standby Total Standby Alarm Total Alarm
(mA) (mA) (mA) (mA)
Power Module
1
15
15
01
140
140
1 0
A TOTAL FIRE ALARM POWER SUPPLY 15 140
B Auxiliary Device Current 0 0
C Notification Appliance Load (Max. Total / mA) 0 1664
Total(A)= 15 Total(B)= 1804
CALCULATION
D
Total current ratings of all devices in system (line A + line B + line C)
15
1804
E
Total current ratings converted to amperes (line D x .001)
0.015
1.804
F
Number of standby hours (24 or 60 per NFPA 72, Chapter 1, 1-5.2.5).
24
G
Multiply lines E and F Total Standby AH
0.36
H
Alarm sounding period in hours (15 mins= 0.25 hours)
0.25
Multiply lines E and H Total Alarm AH
0.451
J
Add lines G and I Total Standby and Alarm AH
0.811
K
Multiply line J by 1.2 (20% extra insurance to meet desired performance)
0.9732
12-V DC BATTERYSIZE RECOMMENDED (AMPERE -HOUR) 7
Fqo 0�
CI CAUTION: LO]
Imo' I Imo' I
�pryNS
CAUTION: D 01 CAUTION HOT SURFACES
Fo PROIECININ ® Tb
T12 ° ACAIH�SjT FIRpE�HAZARO� ❑ ❑
TPE � RATNG �
�, DA 2WV
❑� FI +�
RBD 0C
RZI
AC LOSS TROUBLE
G CAUTION:
CONTRUM PR —IN
AGAINST FIIRREE HAZARD
AC PONEN = 0 - 015 REPLTYPE RATHGAN
E
RO `�
U7= R BATIFRY
T31 O P84B55 WEELOCX -0 1 a IL
mN v g
NILI SNL„� �_
N1d IN /'°❑
N1G11N / NR
s'l Ntl1lom
pus m�/ ttvaB �®
Pmn.0 BPS ( PS-8-LP ) 6 Yf1fVT ±❑
NIXP/YP ® 1
N1giY.i M4
❑
� NF
+AUX - +NACI- +NAC2- +NAGS- +NAG
+ N - IY OUT OUT CUT OUT OUT
ARM
+RET I- TROUBUE
+CCI + IX2 - +RE12 - [G]+sAls - + u - + 9U COM NC NO
BETn � ED R
PS-8-LP POWER SUPPLY
WIRING DETAIL
SPARE
SPARE
NAC CIRCUIT S2
NAC CIRCUIT S1
Notification Appliance Circuit Detail
PROJECT: ZEVENSBERGEN CAPITAL INVESTMENT, EDMONDS YACHT CLUB TI
Panel: PS-8-LP POWER SUPPLY Wire Resistance 3.07
Date: November 9, 2022 CURRENT TOTAL= 1664.00
2
HSWC @75Cd 1
82
164
HSWC @30Cd
102
2
HSWC @75Cd
145
290
HSWC @110Cd
197
3
STCW @75Cd
57
171
#225#22.851
STCW @30Cd
85
DEVICES
9 TOTAL mA=
829 14 829
Tota I W i re Resista nce ( R)
(W L * 2) * (Rlft) 1.38
Total Device Load, Amps (I)
(Total Cct Load) 0.83
Voltage Drop ( E)
(E= I * R) 1.15
i111111k
22.85
7 HSWC @15Cd
82
574
2 HSWC @30Cd
102
2
iHSWC @75Cd
145
0
HSWC @110Cd
197
1 STCW @ 15Cd
57
57
- STCW @30Cd
85
DEVICES 10 TOTAL mA=
835 14 175 23.10
835
Tota I W i re Resista nce ( R)
(W L * 2) * (Rlft)
1.07
Total Device Load, Amps (I)
(Total Cct Load)
0.84
Voltage Drop ( E)
(E= I * R)
0.90
EOL Voltage
24 - E)
23.10
CALCULATIONS
CEILIN
TI LE
HORN STROBE/STROBE
MOUNTING DETAIL (DROP CEILING
TO PS-8-LP
POWER SUPPLY
S
HORN
STROBE
HARD LID -
CEILING
STROBE
4S BOX
CEILING
STROBE
HORN STROBE/STROBE
MOUNTING DETAIL (HARD LID
HORN
STROBE
TYPICAL NAC CIRCUIT WIRING DETAIL
HORN
STROBE
EOL
STEVE SENDLAKOWSKI
NICET LEVEL I i
CERT. #115442 EXP. 01 %i3i%2b Y4
cn
z
0
w
w
C0
Q
W
J
W
�
Ili
O
0\
ao
0\
00
Z
N
O
`0
~
�
\C)
Z
O
N
x
3:
Q
yw
a
cn
LC)
LD
\?
Q
N
L:>
N
a
C)
c�
N
�
�
J
m
�
w
J
U
w
z
0
CL
U
C0
W
Ln
0
z_
a
o'
0
CL
0
W
Q0)
o
N
N
\
�
CD
❑❑❑❑❑
m
Cn
J
z
U
0
U
U
U)
J
z
U
0
z
06
�w
0
w
N
LU
>
Ir
O(p
J
C6
0
Q
W
w
1-->>�
0
z
w
w<z
JQ
z
z
222
00
J
�
�w
QQ�
O
LLI
Q
IY
LL
0
U
z
z
�w
�V
w
J
in
RESIL
B U
WCITY
Nov 14 2
22
OF EDM
DEVELOPMENT S
IDS
�
VICES
w
DEPARTME
A 1
SCALE: NOT TO SCALE)l
DRAWN BY:
C. ENGSTFELD
DESIGNED BY:
T. QUAALE
DATE: 1 1 /09/22
BACKROUND PLAN PROVIDED BY:
JOB NUMBER: 67943-1
TYPICAL WIRING AND MOUNTING DETAILS
Proprietary & Confidential, Copvright 2013
Guardian Security Systems, Inc. All Riqhts Reserved
SHEET
FA-02
NOT IN CONTRACT
I / I
I I
I I
' � I
I I
I NOT IN CONTRACT 1
I '
I / I
I I
I I
r—� r-------------J
I I S2-2 S
I I 15Cd
I I o
— — — — I
I
I I
' I S
' I S2-10 S
'
I � EOL 15Cd
S2
I S2-
1 0 S2-9 0 15C<
1 I 30Cd
L - - - -
S2-7
15Cd
I
I
L--------\
I �
I `
I
I 1
I 1
I 1
I 1
I 1
I 1
I 1
I J
7NOT IN CONTRACT
FLOOR 2 FIRE ALARM TENANT IMPROVEMENT LAYOUT
SCALE: 3/16" = 1'0"
STEVE SENDLAKOWSKI
NICET LEVEL Ii
CERT. #115442 EXP. 0`1%i3i%2b Y4
V)
z
0
�n
LLJ
w
CO
Q
LLJ
J
LLJ
�
r0
o
ON
ON
00
z
o
\-0
~
�
\0
o
LUx
Q
yw
J
Z~
w
QC
Ln
-
LO
� �
oLO
N
LJJ
N
Q
�
o
(n
N
r1r)
�
J
W
m
w
J
U
W
z
0
U
LLJ
V)
0
Z
Q
Cr
0
CL
0
LLJ
0
CV
CV
0
0aaaaa
m
�
c�
O
H
U
�
N
U)
cr
o
O
z�
O
Oz
J
LLI
LL
wLU
N
M
>
.. O
O c\1
J
LU
00
G
a
LU
LU
>
zap
Z
vi
O
U
z
Qo
z0
Er
L U
oC
z
moo
—
a LLJ
J
a�
z
�
LLJ
EL-Ir
z
a
LU
U
z
�
w
m
RESL
B a
WNov
14 2
22 w
CITY OF EDMC
DEVELOPMENTS
IDS
VICES IM
LUDEPARTME
w ■
LL
SCALE: 3/ 1 6" = 1 ' 0"
DRAWN BY:
C. ENGSTFELD
DESIGNED BY:
T. QUAALE
DATE: 1 1 /09/22
BACKROUND PLAN PROVIDED BY:
JOB NUMBER: 67943-1
Proprietary & Confidential, Copyriqht 2013
Guardian Security Systems, Inc. All Riqhts Reserved
SHEET
FA-03