APPROVED RESUB1 FIR2022-0076+Drawings+8.30.2022_8.00.18_AM+3079706TYPE 1 - Kitchen Hood 8'6" Hood Length 7 TOTAL FLOWS 17 NOZZLES Kidde WHDR 260 Tank System (8 Flow Max Capacity) NOTIFICATION DEVICE Approved with addition of signage "If activated call 911" (Fire Marshal to choose location.) Approved by Fire 09/09/2022 AFM /C]=Gtte er Kidde t WHDR O PULL STATION 1-j (10-20ft from hood) [located in /�� KiddeWHDR pathofegress] v ` Fire System 260 Tank (7 flows) CLASS GAS VALVE 6 Ltr K Class Extinguisher [located within 30' of all cooking appliances] I 60`) ADP F— 13"W x 13"L-1 ADP ADP •0I ADP NADP Salamander -36"W ' Griddle Range (48"W x 24"D) (24"W x 24"D) RESUB Aug 30 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT GENERAL NOTES: INITIALS REVISION DATE DRAWN By: Holly Gualco HG Issued For Construction 08/05/22 A L E X A N D E R G O W , 1/ RED TWIG CAFE 1. 3/8" pipe used in all distribution piping. HG REV A - Addition of Notification Device 08/29/22 FIRE EQUIPMENT CO. CHECKED BY: Chris Bingham 2. Fire Suppression System to be tied into PLOT DATE: 08/29/22 117 5TH AVE S building fire alarm (if applicable). 1436 NW 53RD STREET 3.8 MAX Flow points per 260 style cylinder. S E AT T L E, WA 9 8 1 0 7 w EDMONDS, WA 98020 4. Upon activation of fire suppression system, F" I all gas or electrical power supply under the P H: ( 2 0 6) 6 3 2- 2 8 10 ' SHEETTITLE: Fire Suppression System Schematic SCALE: N.T.S. hood WIII SIIUt down. F X : (2 O 6) 6 3 3 - 0 4 3 4 G��W SHEET NUMBER: MM Y