APPROVED RESUB1 FIR2022-0076+Drawings+8.30.2022_8.00.18_AM+3079706TYPE 1 - Kitchen Hood
8'6" Hood Length
7 TOTAL FLOWS 17 NOZZLES
Kidde WHDR 260 Tank System
(8 Flow Max Capacity)
NOTIFICATION
DEVICE
Approved with addition
of signage "If activated
call 911" (Fire Marshal
to choose location.)
Approved by Fire
09/09/2022 AFM /C]=Gtte er
Kidde t
WHDR
O
PULL
STATION 1-j
(10-20ft
from hood)
[located in /�� KiddeWHDR
pathofegress] v ` Fire System
260 Tank
(7 flows)
CLASS
GAS VALVE
6 Ltr K Class
Extinguisher
[located within 30'
of all cooking appliances]
I
60`)
ADP
F— 13"W x 13"L-1
ADP ADP
•0I
ADP NADP Salamander -36"W '
Griddle Range
(48"W x 24"D) (24"W x 24"D)
RESUB
Aug 30 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
GENERAL NOTES: INITIALS REVISION DATE
DRAWN By: Holly Gualco HG Issued For Construction 08/05/22 A L E X A N D E R G O W , 1/
RED TWIG CAFE 1. 3/8" pipe used in all distribution piping. HG REV A - Addition of Notification Device 08/29/22 FIRE EQUIPMENT CO.
CHECKED BY: Chris Bingham 2. Fire Suppression System to be tied into
PLOT DATE: 08/29/22 117 5TH AVE S building fire alarm (if applicable). 1436 NW 53RD STREET
3.8 MAX Flow points per 260 style cylinder. S E AT T L E, WA 9 8 1 0 7
w EDMONDS, WA 98020 4. Upon activation of fire suppression system,
F" I all gas or electrical power supply under the P H: ( 2 0 6) 6 3 2- 2 8 10 '
SHEETTITLE: Fire Suppression System Schematic SCALE: N.T.S. hood WIII SIIUt down. F X : (2 O 6) 6 3 3 - 0 4 3 4 G��W
SHEET NUMBER: MM Y