FIR2022-0002+Fire_Sprinkler_Plan+1.6.2022_12.13.39_PM+2607058RETAINER STRAP .
STEEL I
STRUCTURE
NUT
BEAM CLAMP
A.T.R. SIZE
PER N.F. P.A.
16) RING HANGER
HANGER ❑
TOP BEAM CLAMP
(Fig. 4LA) Pipe Clamp for
Sway Bracing
�/<'/2 x 7 Machine (Hex)
Boft
(('Fig. 980) Universal
Swivel Sway Brace
Attachment
1 Pipe, Schedule 40
3 INCH LONGITUDINAL STEEL
e d a
° 4 a
a �
HILTI HDI-P TZ
CONCRETE INSERT
ALL THREAD ROD
RING HANGER---_
UL I FM APPROVED FOR 4" PIPE
HANGER C05
CONCRETE INSERT
'/ x 7 Machine (Hex)
Bolt
(Fig. 1001) Sway Brace
Clamp
/ (Fig. 980) Universal
Swivel Sway Brace
Attachment
1 Pipe, Schedule 40
3 INCH LATERAL STEEL
'/2 x 3% Kwik Bolt TZ
(Fig. 1001) Sway Brace
Clamp
/ (Fig. 980) Universal
Swivel Sway Brace
Attachment
1 Pipe, Schedule 40
3 INCH LATERAL CONCRETE
(Fig. 4LA) Pipe Clamp for
Sway Bracing
22 x 3% Kwik Bolt TZ
1. 980) Universal
vel Sway Brace
ichment
hedule W
3 INCH LONGITUDINAL CONCRETE
DEWATERING FLOOR FIRE SPRINKLER PLAN
N sCuE.,a .1a
HANGERLEGEND
zr
TO EX. SYSTEM I �'I
N El Capitan a -
Edmonds Landing a a.
> Assisted Living Ta
H Ratelco Properties U S
Corporation
,,;I w Dayton st Dayton st ® Dayton S! Edmonds Short Safes y
Da tan Ss
Farmers
Compass Course: w - 4
a
a
3 Art Works Edmands4 0
4 d
Austin Harp Arts r
tieu:cal innrumen� m
eD 2170 2nd Ave S,
N Edmonds, WA 98020
Edmonds Wastewater
m Treatment
3
Q
a
� a
or
Riser Material
Number
Quantity
Size
Description
Manufacturer
1
1
3
G-G Butterfly Valve w/ Tamper
Tyco
2
1
4
G-G Double Check Detector Assembly
Deringer
3
1
3 x 2
VSR Waterf low Switch
Potter Electric
4
1
2
T-T Test and Drain Valve
AGF
5
1 1
1/4
Pressure Gauge
Generic
RISER I50 VIEW
SCALE: NTS
RISER SECTION VIEW
o rsuLE: 1/2
N
-4 FF
i TS•
II
EX G" FP
MAIN
1_' 1
SUPPLY
Hydraulic Information
DCCUPANCY CLASSIFICATION
Ordinary Group I
)ENSITY (gpm/ft2)
0.15 for 1500ft2 (Actual 1610ft2)
rOTAL HOSE STREAMS
250.00
rOTAL HEADS FLOWING
16
(-FACTOR
5.6
rOTAL WATER REQUIRED
675.09
rOTAL PRESSURE REQUIRED
105.865
BASE of RISER (gpm)
675.09
BASE of RISER (psi)
105.865
;AFETY MARGIN (psi)
+19.964 (15.9%)
Edmonds Park
VICINITY MAP
N SCALE: NONE
71z�� SHOP FLOOR FIRE SPRINKLER PLAN
C1.
W Walnul Sl
D.
4
SCOPE OF WORK
FSW WILL ADD NEW SPRINKLERS TO PROTECT THE NEW
GASIFICATION ROOM, SOLIDS HANDLING ROOM, AND ID FAN
ROOM.
EXCLUSIONS
1, OFF HOURS AND TAXES.
2. RELOCATION OF EXISTING PIPING.
3. GWB CUTAND PATCH.
4. PRINTING OF ANY KIND.
5. WIRING OF ANY KIND.
6. REPLACE, REPAIR, OR MODIFICATION OF CEILING TILES.
7. ABATEMENT OF ANY KIND.
S. STRUCTURAL VERIFICATION IF REQUIRED.
DESIGN CRITERIA
1. NFPA 13 2013 ED.
2. CITY OF EDMONIDS.
3. ORDINARY HAZARD G-1 0.15/1500 S.F.
WATERFLOW AVAILABILITY
STATIC:127.61 PSI
RESIDUAL:102.81 PSI
FLOW: 2803 GPM
ELEVATION: SITE
LOCATION: SITE
DATE:10.27-2021
INFORMATION PROVIDED BY: CITY OF EDMONDS PUBLIC WORKS
FIRE PR IC UIMNM EMS
Craig A. Miller
9719-0108-C Level
Fire Systems West, Inc.
FIRESWI1401137
Expires
1 Z/31/31
Signature
Approved by Fire
01/25/2022 AFM /'<_/F�tte er
1.Replace FDC connection with locking Storz fitting
2.Monitored fire alarm is required
3.Separate permit for fire alarm
4.Fire alarm initiated by sprinkler flow and tamper
switch
55ire alarm notification only (with exception of above
#2)
6.New calculations to be posted in riser room
7.Subject to field inspection
2'-7�/2
FIR2022-0002
RECEIVED
Jan 11 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
3
PER PLAN
EX. MAIN �
10'41/2
CO r
11' -1'/2 L 1 1'-10%
RISER DETAIL PLAN VIEW
Jam\ ]SCALE: 1/2" = 1'-0"
SPRINKLER
HEADS
REVISIONS
GENERAL NOTES
DESIGN CRITERIAAND NOTES
CONTRACT NAME:
EDMONDS WWTF 11
200 2N❑ AVE. S
EDMONDS, WA 98020
SYM
TYPE
MFG
MODEL
ORIFICE
THREAD
TEMP
FINISH
CANOPY
QTY
MK
DATE
BY
DESCRIPTION
1. ALL MATERIAL AND EQUIPMENTTO BE NEW AND UNDERWRITERS APPROVED.
2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & DIMENSIONS SHOWN
THUSLY (1'-6') WHICH ARE END TO END.
3.EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA#13.
4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA#13.
5.PIPING SHALL BE IN ACCORDANCE WITH NFPA#13.
6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE
WITH NFPA#13.
7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM
FREEZING IN AREAS PROTECTED BY WET PIPE SPRINKLER SYSTEM.
8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORTTHE SPRINKLER PIPING IS
THE RESPONSIBILITY OF THE OWNER OR HIS STRUCTURAL REPRESENTATIVE.
1. ALL BRANCH LINE PIPING TO BE THREADED SCH 40 JOINED WI CAST IRON FITTINGS (UNO),
2, ALL NEW HANGERS TO BE PER HANGER DETAILS) (UNO),
3.ALL NEW HEADS AT ACOUSTICAL CEILING TO BE ON FLEX DROP FITTINGS.
4. ALL NEW CONNECTIONS TO EXISTING PIPE TO BE MADE WITH MECHAN ICAL TEE (UNO).
QR 1 UPRIGHT
TYCO
TY313
5.6K
112"
1550
BRZ
NONE
26
QR 1 DRY HSW
TYCO
TY3355
5.6K
1"
155'
BRZ
NONE
2
R / UPRIGHT/ SPRIC
TYCO
TY313
5.61K
1/2"
1550
BRZ
NONE
3
OR 1 PENDENT
TYCO
TY323
S.fiK
112"
155°
BRZ
NONE
22
CONTRACT WITH:
GENERAL MECHANICAL, INC.
2316 SOUTH STATE STREET
TACOMA, VITA 98405
CONTACT. NATE CRUISE
Phone: 253-606-5983 Fax:
❑
APPROVALS REQUIRED:
DISTRIBUTION:
AHJ
AHJ
3
OWNER /ARCHITECT
OWNER /ARCHITECT
1
TOTAL
53
FIRE SYSTEMS WEST
1
2
FIRE SPRINKLER PLAN
4 , dire Systems West
206 Frontage Road North, Suite C
Pacific, WA. 98047
(253) 833-1248 Fax: (253) 735-0113
WACL# FIRESWI 140B1
D.C. FAB BY: Q.C. IN57ALL BY:
DESIGNER DATE JOB NUMBER SHEET
KEVIN RIDER 11/01/21 2-11-11859 1 OF 1