Loading...
FIR2022-0002+SEISMIC_BRACING+1.6.2022_12.13.45_PM+2607060FIR2022-0002 TOLBraceTM Seismic Bracing Calculations Contractor: Fire Systems West Project Address: EDMONDS WWTF II Address: 206 Frontage Rd. N, Suite C 1 Pacific, WA 98047 200 2ND AVE. S Patnrenrrg8r3sinesslNorfdwrde E C E I V E D Phone: 253-833-1248 Jan 11 2022 EDMONDS, WA Licence: FIRESWI1401131 CITY OF EDMONDS DEVELOPMENT SERVICES Job # 2-11-11859 DEPARTMENT Calculations based on 2013 NFPA Pamphlet #13 Brace Information TOLCOTM Brace Components Maximum Brace Length TO" (2.134 m) TOLCOTIM Component Listed Load Adjusted Load Diameter of Brace 1 Fig. 1001 Clamp 2015 Ibs (914 kg) 1425 Ibs (646 kg) Fig.980 Universal Swivel 2015 Ibs (914 kg) 1425 Ibs (646 kg) Type of Brace Sch.40 See Fastener Information Angle of Brace 45' Min. *Calculation Based on CONCENTRIC Loading *Please Note: These calculations are for TOLCOTM components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42" (11 mm) Seismic Brace Assembly Detail L/R Value 200 Max Horizontal Load 1310 Ibs (594 kg) TOLCO FIG. 980 UNIVERSAL SWAY BRACE ATTACHMENT Fastener Information O STEEL PIPE Orientation to Connecting Surface NFPAType B Fastener .f Type POWERS POWER -STUD +SD2 i Diameter 1/2in. 1 ' Length 3 1/4in. TOLCO FIG. 1001 FAST CLAMP Maximum Load 412 Ibs (187 kg) Brace Identification on Plans 31N. LATERAL CONC. NO LINES Prying Factor 1.156 Brace Type Lateral [X] Longitudinal [ ] 4-Way [ ] Sprinkler System Load Calculation (Fpw = CpWp) C = 0.601 Diameter Type Length Total Length Weight Per Unit Length Total Weight 3" (80 mm) I Sch. 10 140 ft (12.2 m) I40 ft (12.2 m) 17.94 Ib/ft (11.82 kg/m) 1318 Ibs (144 kg) Subtotal Weight 318 Ibs (144 kg) Wp (incl. 15%) 366 Ibs (166 kg) Main Size Type/Sch. Spacing (ft) 3" Sch. 10 40 Total (Fpw) Maximum Fpw per 9.3.5.5.2 (if applicable) 220 Ibs (100 kg) 454 lb (205 kg) {TOLBraceTM Version 81 Use of TOLBraceTM is subject to terms and conditions per the end user license agreement TOLBraceT"" Seismic Calculations EDMONDS WWTF II 200 2ND AVE. S Brace Identification Brace Type (Per NFPA#13) Braced Pipe (ft) Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # 2-11-11859 FAT*N PommW Sus aw ft fdvAW 31N. LATERAL CONC. NO LINES NFPA Type B 3" Sch.10 Steel Pipe 40' 0" (12.19 m) Lateral 1" Sch.40 7' 0" (2.13 m) 200 45' POWERS POWER -STUD +SD2 1/2in. x 3 1/4in. (3,000 PSI Normal Weigh 3 1/4in. Summary of Pipe within Zone of Influence 3" Sch.10 Steel Pipe (76.2 mm) 40 ft (12.2 m) G-Factor Used 0.601 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 220 Ibs (100 kg) Material Capacity 1310 Ibs (594 kg) Fastener Capacity 412 Ibs (187 kg) Fig. 1001 Clamp 1425 Ibs (646 kg) Fig.980 Universal Swivel 1425 Ibs (646 kg) Structural Member CONCRETE BEAM Calculations prepared by KEVIN RIDER * The description of the Structural Member is for informational purposes only. TOLBrace"" software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBrace'"' 8 Visit us at www.tolco.com POWERS POWER-STUD+SD2 WEDGE ANCHORS IN 3,000 PSI NORMAL WEIGHT CONCRETE a 4 a • • � • Y d + a. H TOLCO SM SERIES ATTACHMENT. POWERS POWER -STUPID •SD2 CARBON STEEL WEDGE ANCHOR. NFPA BRACE ORIENTATIONS A, B, AND C SHOWN ABOVE (MINUS ANGLES), OTHER ORIENTATIONS SIMILAR Fig- 980/ Fig. 910 ANCHOR DIA NOMINAL EMBED. DEPTH "E" MIN. EFFECTIVE EMBED. DEPTH "D" DESIGN EDGE DISTANCE "H" MIN. BASE MATERIAL THICKNESS ALLOWABLE STRENGTH DESIGN (ASD) MAX- ALLOWABLE HORIZONTAL LOAD (LBS.) NFPA BRACE ORIENTATION I PRYING FACTOR A B C D E F G H 1 3.275 1.156 1.739 1.461 1.850 2.894 3,478 Z.459 2.D08 3/8" 2 3/6" 2" 4" 4" 93 198 151 136 145 109 75 106 131 1/2" 3 3/4" 3 1/4" 6" S 3/4" 19S 412 315 294 302 226 157 222 273 5/8" 3 7/8" 3 1/4" 6" 5 3/4" 221 464 356 320 341 257 178 250 308 3/4" 4 1/2" 3 3/4" 1 8" 7" 281 1 620 1 467 434 446 319 233 329 405 VALUES CALCULATED IN ACCORDANCE WITH ACI 318-11 AND INCLUDE OVER STRENGTH FACTOR Q - 26 Fig. 9D9 ANCHOR DIA NOMINAL EMBED. DEPTH "E" MIN. EFFECTIVE EMBED. DEPTH "D" DESIGN EDGE DISTANCE "H' MIN. BASE MATERIAL THICKNESS ALLOWABLE STRENGTH DESIGN (ASD) MAX. ALLOWABLE HORIZONTAL LOAD (LBS.) NFPA BRACE ORIENTATION I PRYING FACTOR A B C D E F G H 2.626 1.DO2 1.230 1.513 1A87 2.226 2.460 1.740 1.4ZD 3/8" 1 2 3/8" 2" 4" 4" 111 215 190 134 168 141 95 133 165 1/2" 3 3/4" 1 3 1/4" 6" 5 3/4" 232 448 397 279 351 294 198 278 343 5/8" 3 7/8" 3 1/4" 6" S 3/4" 263 SOS 447 314 396 334 223 314 387 3/4" 4 1/2" 3 3/4" 8" 7" 340 678 1 595 425 523 415 1 297 418 51 VALUES CALCULATED IN ACCORDANCE WITH AC1318-11 AND INCLUDE OVER STRENGTH FACTOR 0.26 NOTES: I j ALLOWABLE LOADS ARE FOR ANCHORS INSTALLED IN STONE AGGREGATE CONCRETE HAVING A MIN. COMPRESSIVE STRENTH OF 3,000 PSI AT THE TIME OF INSTALLATION AND DETERMINED PER ICC ESR-2502 FOR ANCHORS IN CRACKED CONCRETE. ALLOWABLE LOADS HAVE BEEN CALCULATED IN ACCORDANCE WITH ACI31,341, APPENDIX D 24 PER ICC-ESR, PERIODIC SPECIAL INSPECTIONS ARE REQUIRED IN ACCORDANCE WITH SECTION 1706.1.1 AND TABLE 1705.3 OF THE 2015 AND 2012 IBC; ❑R SECTION 1704.16 AND TABLE 1704A OF THE 2009 IBC, AS APPLICABLE. THE SPECIAL INSPECTOR MUST MAKE PERIODIC INSPECTIONS DURING THE ANCHOR I NSTAL LATION TO VERIFY ANCHOR TYPE, ANCHOR 01MENSIONS CONCRETE TYPE, CONCRETE COMPRESSIVE STRENGTH, HOLE DIMENSIONS, HOLE CLEANING PROCEDURE, ANCHOR SPACING, EDGE DISTANCES, CONCRETE MEMBERTHICKNESS, ANCHOR EMBEDMENT, TIGHTENING TORQUE AN ADHERENCE TO THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. CONSULT LOCAL CODES FOR ANY ADDITIONAL SPECIAL INSPECTION REQUIREMENTS. 3,1 FOLLOW ALL WEDGE ANCHOR INSTALLATION REQUIREMENTS PER IC ESR,25D2 4.1 WHEN INSTA ILL ING ANCHORS IN REINFORCED CONCRETE, AVOID DAMAGING REINF0RCI NG STEEL 5.I WHEN INSTALLING ANCHORS IN PRESTRESSED CONCRETE. LOCATE PRESTR ES 8I NG STEEL AND AVOID DAMAGING PRESTRESSING STEEL. 6.I STRUCTURAL ENGINEER OF RECORD SHALL VERIFY ADEC UACY OF THE STRUCTURE FOR THE TABULATED ALLOWABLE LOADS. 7.I TO LC 900 SERIES ATTAC NM E NT DIAMETER SHALL BE EQUAL TO THE ANCHOR DIAMETER 8.I 1F SUBSTRATE CONDITIONS DIFFER FROM WHAT IS LISTED IN THE ABOVE TA BLES, CONTACT EATON B-LI NE AT TOLCO SUPPO RT@EATO N. COM DETAIL PER NFPA 13, 2016 FIGURE A . .5.1 .1(a - c) iY:PlcriErC NJC11�R -2[r 2 2M SF¢JY+N UImti1+5K:N S5AML: FOR 7{:1CORG9!D� TOLCO FIG- 990 TOLC-O FIG. 009 I - a�;, + IR P- i n.ss Farton ppr N FPA 13, 21316 Se rf on !13.4.12 r,hr.n i nstal!pd in mr r. •w.tp s ah ceus Fig. FMO/1M] A 9 C d is F G F I Pr R,. P, Pr ?r Pr Pr P. P. 3.275 1.156 1.73E 1.4C1 1.K-0 j 2-8-94 1.478 2.459 2.00E Fi0. S, i9 A 6 C d E F G 1- I P. P, P P, Pr Pr P, P. F. 2,6215 1.002 1.230 1.513 1.437 2.226 2.460 1.740 1.420 PingFactn•s per NFPA 1.4,20165pct'.nnq..1.5.12 when i L,," IM'n onnrroc. mP..talr.acks tvitr.1"rante,nttsat Fig. 4d4d f91!] A 9 C d E I F G 1 I Pr Pr P- Pr P. P, Pr P. #. 3.275 1.156 1.73E Fig. 909 A 9 C d f F G I P, F P. P, F. P. P. P. P. 2.626 1.002 1.230 P--jngFuclo-sDu-VFflA13,201rxS-cliu:r9.35.12!-jhc-rn-LallccintuncrcLurnclu dUtts!!,'Lh1.125"cu7leruMd Fig. �W!910 A B C d E F G L- I Fr Pr. P. Pr Pr Pr Pr P: P- 3,275 1.156 1.738 - fig- W9 1 B C d E F G L- I Pr Pr Pr P. P. P. P. P. P. 2.52fi 1.003 1.230 - 'Wh� -i irlt5al led i n a �o-.cm.tP meta dec a {TV,)p. Vi 41 /� " x .i'1: d:mprrsipr, W wore r.' hF depe. %ent upon Me. contact area. For S Q2 a-.chors 1*.P max oftspt is 1" s o 'S' wou d he 1.25'. Frir $a'ic-It am Wow. -Knor:kr• 11 # anr.nnrs. the max nffsr.t is 1.125" so W tjnu d of 1.12.;"- TOLBraceTM Seismic Bracing Calculations Contractor: Fire Systems West Project Address: EDMONDS WWTF II Address: 206 Frontage Rd. N, Suite C 1 Pacific, WA 98047 ,i 200 2ND AVE. S pomwng8�esinessl4brumde Phone: 253-833-1248 EDMONDS, WA Licence: FIRESWI1401131 Job # 2-11-11859 Calculations based on 2013 NFPA Pamphlet #13 Brace Information TOLCOTM Brace Components Maximum Brace Length TO" (2.134 m) TOLCOTM Component Listed Load Adjusted Load Diameter of Brace 1 Fig. 1001 Clamp 2015 Ibs (914 kg) 1425 Ibs (646 kg) Fig.980 Universal Swivel 2015 Ibs (914 kg) 1425 Ibs (646 kg) Type of Brace Sch.40 See Fastener Information Angle of Brace 45' Min. *Calculation Based on CONCENTRIC Loading *Please Note: These calculations are for TOLCOTM components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42" (11 mm) Seismic Brace Assembly Detail L/R Value 200 Max Horizontal Load 1310 Ibs (594 kg) TOLCO FIG. 980 UNIVERSAL SWAY BRACE ATTACHMENT Fastener Information O STEEL PIPE Orientation to Connecting Surface NFPAType B Fastener .f Type POWERS POWER -STUD +SD2 i Diameter 1/2in. 1 ' Length 3 1/4in. TOLCO FIG. 1001 FAST CLAMP Maximum Load 412 Ibs (187 kg) Brace Identification on Plans 31N. LATERAL CONC. Prying Factor 1.156 Brace Type Lateral [X] Longitudinal [ ] 4-Way [ ] Sprinkler System Load Calculation (Fpw = CpWp) C = 0.601 Diameter Type Length Total Length Weight Per Unit Length Total Weight 3" (80 mm) Sch. 10 20 ft (6.1 m) 20 ft (6.1 m) 7.94 Ib/ft (11.82 kg/m) 159 Ibs (72 kg) 1.5" (40 mm) Sch. 40 77 ft (23.5 m) 77 ft (23.5 m) 3.61 lb/ft (5.37 kg/m) 278 Ibs (126 kg) 1.25" (32 mm) Sch. 40 18 ft (5.5 m) 18 ft (5.5 m) 2.93 lb/ft (4.36 kg/m) 53 Ibs (24 kg) 1" (25 mm) Sch. 40 46 ft (14 m) 46 ft (14 m) 2.05 Ib/ft (3.05 kg/m) 94 Ibs (43 kg) Subtotal Weight 584 Ibs (265 kg) Wp (incl. 15%) 672 Ibs (305 kg) Main Size 3" Type/Sch. Sch. 10 Spacing (ft) 20 Total (Fpw) Maximum Fpw per 9.3.5.5.2 (if applicable) 404 Ibs (183 kg) 966 lb (438 kg) {TOLBraceTM Version 81 Use of TOLBraceTM is subject to terms and conditions per the end user license agreement TOLBraceT"" Seismic Calculations EDMONDS WWTF II 200 2ND AVE. S Brace Identification Brace Type (Per NFPA#13) Braced Pipe (ft) Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # 2-11-11859 FAT*N PommW Sus aw ft fdvAW 31N. LATERAL CONC. NFPA Type B 3" Sch.10 Steel Pipe 20' 0" (6.1 m) Lateral 1" Sch.40 7' 0" (2.13 m) 200 45' POWERS POWER -STUD +SD2 1/2in. x 3 1/4in. (3,000 PSI Normal Weigh 3 1/4in. Summary of Pipe within Zone of Influence 3" Sch.10 Steel Pipe (76.2 mm) 20 ft (6.1 m) 1.5" Sch.40 Steel Pipe (38.1 mm) 77 ft (23.5 m) 1.25" Sch.40 Steel Pipe (31.75 mm) 18 ft (5.5 m) 1" Sch.40 Steel Pipe (25.4 mm) 46 ft (14 m) G-Factor Used 0.601 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 404 Ibs (183 kg) Material Capacity 1310 Ibs (594 kg) Fastener Capacity 412 Ibs (187 kg) Fig. 1001 Clamp 1425 Ibs (646 kg) Fig.980 Universal Swivel 1425 Ibs (646 kg) Structural Member CONCRETE BEAM Calculations prepared by KEVIN RIDER * The description of the Structural Member is for informational purposes only. TOLBrace"" software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBrace'"' 8 Visit us at www.tolco.com POWERS POWER-STUD+SD2 WEDGE ANCHORS IN 3,000 PSI NORMAL WEIGHT CONCRETE a 4 a • • � • Y d + a. H TOLCO SM SERIES ATTACHMENT. POWERS POWER -STUPID •SD2 CARBON STEEL WEDGE ANCHOR. NFPA BRACE ORIENTATIONS A, B, AND C SHOWN ABOVE (MINUS ANGLES), OTHER ORIENTATIONS SIMILAR Fig- 980/ Fig. 910 ANCHOR DIA NOMINAL EMBED. DEPTH "E" MIN. EFFECTIVE EMBED. DEPTH "D" DESIGN EDGE DISTANCE "H" MIN. BASE MATERIAL THICKNESS ALLOWABLE STRENGTH DESIGN (ASD) MAX- ALLOWABLE HORIZONTAL LOAD (LBS.) NFPA BRACE ORIENTATION I PRYING FACTOR A B C D E F G H 1 3.275 1.156 1.739 1.461 1.850 2.894 3,478 Z.459 2.D08 3/8" 2 3/6" 2" 4" 4" 93 198 151 136 145 109 75 106 131 1/2" 3 3/4" 3 1/4" 6" S 3/4" 19S 412 315 294 302 226 157 222 273 5/8" 3 7/8" 3 1/4" 6" 5 3/4" 221 464 356 320 341 257 178 250 308 3/4" 4 1/2" 3 3/4" 1 8" 7" 281 1 620 1 467 434 446 319 233 329 405 VALUES CALCULATED IN ACCORDANCE WITH ACI 318-11 AND INCLUDE OVER STRENGTH FACTOR Q - 26 Fig. 9D9 ANCHOR DIA NOMINAL EMBED. DEPTH "E" MIN. EFFECTIVE EMBED. DEPTH "D" DESIGN EDGE DISTANCE "H' MIN. BASE MATERIAL THICKNESS ALLOWABLE STRENGTH DESIGN (ASD) MAX. ALLOWABLE HORIZONTAL LOAD (LBS.) NFPA BRACE ORIENTATION I PRYING FACTOR A B C D E F G H 2.626 1.DO2 1.230 1.513 1A87 2.226 2.460 1.740 1.4ZD 3/8" 1 2 3/8" 2" 4" 4" 111 215 190 134 168 141 95 133 165 1/2" 3 3/4" 1 3 1/4" 6" 5 3/4" 232 448 397 279 351 294 198 278 343 5/8" 3 7/8" 3 1/4" 6" S 3/4" 263 SOS 447 314 396 334 223 314 387 3/4" 4 1/2" 3 3/4" 8" 7" 340 678 1 595 425 523 415 1 297 418 51 VALUES CALCULATED IN ACCORDANCE WITH AC1318-11 AND INCLUDE OVER STRENGTH FACTOR 0.26 NOTES: I j ALLOWABLE LOADS ARE FOR ANCHORS INSTALLED IN STONE AGGREGATE CONCRETE HAVING A MIN. COMPRESSIVE STRENTH OF 3,000 PSI AT THE TIME OF INSTALLATION AND DETERMINED PER ICC ESR-2502 FOR ANCHORS IN CRACKED CONCRETE. ALLOWABLE LOADS HAVE BEEN CALCULATED IN ACCORDANCE WITH ACI31,341, APPENDIX D 24 PER ICC-ESR, PERIODIC SPECIAL INSPECTIONS ARE REQUIRED IN ACCORDANCE WITH SECTION 1706.1.1 AND TABLE 1705.3 OF THE 2015 AND 2012 IBC; ❑R SECTION 1704.16 AND TABLE 1704A OF THE 2009 IBC, AS APPLICABLE. THE SPECIAL INSPECTOR MUST MAKE PERIODIC INSPECTIONS DURING THE ANCHOR I NSTAL LATION TO VERIFY ANCHOR TYPE, ANCHOR 01MENSIONS CONCRETE TYPE, CONCRETE COMPRESSIVE STRENGTH, HOLE DIMENSIONS, HOLE CLEANING PROCEDURE, ANCHOR SPACING, EDGE DISTANCES, CONCRETE MEMBERTHICKNESS, ANCHOR EMBEDMENT, TIGHTENING TORQUE AN ADHERENCE TO THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. CONSULT LOCAL CODES FOR ANY ADDITIONAL SPECIAL INSPECTION REQUIREMENTS. 3,1 FOLLOW ALL WEDGE ANCHOR INSTALLATION REQUIREMENTS PER IC ESR,25D2 4.1 WHEN INSTA ILL ING ANCHORS IN REINFORCED CONCRETE, AVOID DAMAGING REINF0RCI NG STEEL 5.I WHEN INSTALLING ANCHORS IN PRESTRESSED CONCRETE. LOCATE PRESTR ES 8I NG STEEL AND AVOID DAMAGING PRESTRESSING STEEL. 6.I STRUCTURAL ENGINEER OF RECORD SHALL VERIFY ADEC UACY OF THE STRUCTURE FOR THE TABULATED ALLOWABLE LOADS. 7.I TO LC 900 SERIES ATTAC NM E NT DIAMETER SHALL BE EQUAL TO THE ANCHOR DIAMETER 8.I 1F SUBSTRATE CONDITIONS DIFFER FROM WHAT IS LISTED IN THE ABOVE TA BLES, CONTACT EATON B-LI NE AT TOLCO SUPPO RT@EATO N. COM DETAIL PER NFPA 13, 2016 FIGURE A . .5.1 .1(a - c) iY:PlcriErC NJC11�R -2[r 2 2M SF¢JY+N UImti1+5K:N S5AML: FOR 7{:1CORG9!D� TOLCO FIG- 990 TOLC-O FIG. 009 I - a�;, + IR P- i n.ss Farton ppr N FPA 13, 21316 Se rf on !13.4.12 r,hr.n i nstal!pd in mr r. •w.tp s ah ceus Fig. FMO/1M] A 9 C d is F G F I Pr R,. P, Pr ?r Pr Pr P. P. 3.275 1.156 1.73E 1.4C1 1.K-0 j 2-8-94 1.478 2.459 2.00E Fi0. S, i9 A 6 C d E F G 1- I P. P, P P, Pr Pr P, P. F. 2,6215 1.002 1.230 1.513 1.437 2.226 2.460 1.740 1.420 PingFactn•s per NFPA 1.4,20165pct'.nnq..1.5.12 when i L,," IM'n onnrroc. mP..talr.acks tvitr.1"rante,nttsat Fig. 4d4d f91!] A 9 C d E I F G 1 I Pr Pr P- Pr P. P, Pr P. #. 3.275 1.156 1.73E Fig. 909 A 9 C d f F G I P, F P. P, F. P. P. P. P. 2.626 1.002 1.230 P--jngFuclo-sDu-VFflA13,201rxS-cliu:r9.35.12!-jhc-rn-LallccintuncrcLurnclu dUtts!!,'Lh1.125"cu7leruMd Fig. �W!910 A B C d E F G L- I Fr Pr. P. Pr Pr Pr Pr P: P- 3,275 1.156 1.738 - fig- W9 1 B C d E F G L- I Pr Pr Pr P. P. P. P. P. P. 2.52fi 1.003 1.230 - 'Wh� -i irlt5al led i n a �o-.cm.tP meta dec a {TV,)p. Vi 41 /� " x .i'1: d:mprrsipr, W wore r.' hF depe. %ent upon Me. contact area. For S Q2 a-.chors 1*.P max oftspt is 1" s o 'S' wou d he 1.25'. Frir $a'ic-It am Wow. -Knor:kr• 11 # anr.nnrs. the max nffsr.t is 1.125" so W tjnu d of 1.12.;"- TOLBraceTM Seismic Bracing Calculations Contractor: Fire Systems West Project Address: EDMONDS WWTF II Address: 206 Frontage Rd. N, Suite C 1 Pacific, WA 98047 ,i 200 2ND AVE. S pomwng8�esinessl4brumde Phone: 253-833-1248 EDMONDS, WA Licence: FIRESWI1401131 Job # 2-11-11859 Calculations based on 2013 NFPA Pamphlet #13 Brace Information TOLCOTM Brace Components Maximum Brace Length TO" (2.134 m) TOLCOTM Component Listed Load Adjusted Load Diameter of Brace 1 Fig. 1001 Clamp 2015 Ibs (914 kg) 1425 Ibs (646 kg) Fig.980 Universal Swivel 2015 Ibs (914 kg) 1425 Ibs (646 kg) Type of Brace Sch.40 See Fastener Information Angle of Brace 45' Min. *Calculation Based on CONCENTRIC Loading *Please Note: These calculations are for TOLCOTM components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42" (11 mm) Seismic Brace Assembly Detail L/R Value 200 Max Horizontal Load 1310 Ibs (594 kg) TOLCO FIG. 980 UNIVERSAL SWAY BRACE ATTACHMENT Fastener Information O STEEL PIPE Orientation to Connecting Surface NFPAType B Fastener .f Type Bolt i, Diameter 1/2n. (12 mm) i Length N/A TOLCO FIG. FAST CLAMP Maximum Load 2050 Ibs (930 kg) Brace Identification on Plans 31N. LATERAL STEEL Prying Factor N/A Brace Type Lateral [X] Longitudinal [ ] 4-Way [ ] Sprinkler System Load Calculation (Fpw = CpWp) C = 0.601 Diameter Type Length Total Length Weight Per Unit Length Total Weight 3" (80 mm) Sch. 10 30 ft (9.1 m) 30 ft (9.1 m) 7.94 Ib/ft (11.82 kg/m) 238 Ibs (108 kg) 1.5" (40 mm) Sch. 40 40 ft (12.2 m) 40 ft (12.2 m) 3.61 lb/ft (5.37 kg/m) 144 Ibs (65 kg) 1.25" (32 mm) Sch. 40 10 ft (3 m) 10 ft (3 m) 2.93 lb/ft (4.36 kg/m) 29 Ibs (13 kg) 1" (25 mm) Sch. 40 18 ft (5.5 m) 18 ft (5.5 m) 2.05 Ib/ft (3.05 kg/m) 37 Ibs (17 kg) Subtotal Weight 448 Ibs (203 kg) Wp (incl. 15%) 515 Ibs (234 kg) Main Size 3" Type/Sch. Sch. 10 Spacing (ft) 30 Total (Fpw) Maximum Fpw per 9.3.5.5.2 (if applicable) 310 Ibs (140 kg) 633 lb (287 kg) {TOLBraceTM Version 81 Use of TOLBraceTM is subject to terms and conditions per the end user license agreement TOLBraceT"" Seismic Calculations EDMONDS WWTF II 200 2ND AVE. S Job # 2-11-11859 FAT*N PommW Sus aw ft fdvAW Brace Identification Brace Type (Per NFPA#13) Braced Pipe (ft) Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener 31N. LATERAL STEEL NFPA Type B 3" Sch.10 Steel Pipe 30' 0" (9.14 m) Lateral 1" Sch.40 7' 0" (2.13 m) 200 45' 1/2 (12mm) Bolt N/A Summary of Pipe within Zone of Influence 3" Sch.10 Steel Pipe (76.2 mm) 30 ft (9.1 m) 1.5" Sch.40 Steel Pipe (38.1 mm) 40 ft (12.2 m) 1.25" Sch.40 Steel Pipe (31.75 mm) 10 ft (3 m) 1" Sch.40 Steel Pipe (25.4 mm) 18 ft (5.5 m) G-Factor Used 0.601 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 310 Ibs (141 kg) Material Capacity 1310 Ibs (594 kg) Fastener Capacity 2050 Ibs (930 kg) Fig. 1001 Clamp 1425 Ibs (646 kg) Fig.980 Universal Swivel 1425 Ibs (646 kg) Structural Member STEEL BEAM Calculations prepared by KEVIN RIDER * The description of the Structural Member is for informational purposes only. TOLBrace"" software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBrace- 8 Visit us at www.tolco.com TOLBraceTM Seismic Bracing Calculations Contractor: Fire Systems West Project Address: EDMONDS WWTF II Address: 206 Frontage Rd. N, Suite C iTeN Pacific, WA 98047 m 200 2ND AVE. S PawenogRURs IessWorwimde Phone: 253-833-1248 EDMONDS, WA Licence: FIRESWI1401131 Job # 2-11-11859 Calculations based on 2013 NFPA Pamphlet #13 Brace Information TOLCOTM Brace Components Maximum Brace Length TO" (2.134 m) TOLCOTM Component Listed Load Adjusted Load Diameter of Brace 1 Fig. 41-A Clamp 1000 Ibs (454 kg) 707 Ibs (321 kg) Fig.980 Universal Swivel 2015 Ibs (914 kg) 1425 Ibs (646 kg) Type of Brace Sch.40 See Fastener Information Angle of Brace 45' Min. *Calculation Based on CONCENTRIC Loading *Please Note: These calculations are for TOLCOTIM components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42" (11 mm) Seismic Brace Assembly Detail L/R Value 200 Max Horizontal Load 1310 Ibs (594 kg) B LINE T-ROW BR F1aINENT - - BRACE PIPE Y uHE I roLca .0 Fastener Information Orientation to Connecting Surface NFFAType B Fastener "IW4HE""OSWAT BRACE ATTACHMENT Type Bolt Diameter 1/2n. (12 mm) I Length N/A wo ----- — ---�- Maximum Load 2050 Ibs (930 kg) Fn A A "A I ,. "..", Brace Identification on Plans 31N. LONG. STEEL Prying Factor N/A Brace Type Lateral [ ] Longitudinal [X] 4-Way [ ] Sprinkler System Load Calculation (Fpw = CpWp) C = 0.601 Diameter Type Length Total Length Weight Per Unit Length Total Weight 3" (80 mm) Sch. 10 80 ft (24.4 m) 80 ft (24.4 m) 7.94 Ib/ft (11.82 kg/m) 635 Ibs (288 kg) Subtotal Weight 635 Ibs (288 kg) Wp (incl. 15%) 730 Ibs (331 kg) Main Size Type/Sch. Spacing (ft) 3" Sch. 10 80 Total (Fpw) Maximum Fpw per 9.3.5.5.2 (if applicable) 439 Ibs (199 kg) N/A {TOLBraceTIM Version 81 Use of TOLBraceTM is subject to terms and conditions per the end user license agreement TOLBraceT"" Seismic Calculations EDMONDS WWTF II 200 2ND AVE. S Brace Identification Brace Type (Per NFPA#13) Braced Pipe (ft) Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # 2-11-11859 31N. LONG. STEEL NFPA Type B 3" Sch.10 Steel Pipe 80' 0" (24.38 m) Longitudinal 1" Sch.40 7' 0" (2.13 m) 200 45' 1/2 (12mm) Bolt N/A Summary of Pipe within Zone of Influence 3" Sch.10 Steel Pipe (76.2 mm) 80 TEE m) G-Factor Used 0.601 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 439 Ibs (199 kg) Material Capacity 1310 Ibs (594 kg) Fastener Capacity 2050 Ibs (930 kg) Fig. 4LA Clamp 707 Ibs (321 kg) Fig.980 Universal Swivel 1425 Ibs (646 kg) Structural Member STEEL BEAM Calculations prepared by KEVIN RIDER * The description of the Structural Member is for informational purposes only. TOLBrace"" software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBrace- 8 Visit us at www.tolco.com FAT*N PommW Sus aw ft fdvAW TOLBraceTM Seismic Bracing Calculations Contractor: Fire Systems West Project Address: EDMONDS WWTF II Address: 206 Frontage Rd. N, Suite C iTeN Pacific, WA 98047 m 200 2ND AVE. S PawenogRURs IessWorwimde Phone: 253-833-1248 EDMONDS, WA Licence: FIRESWI1401131 Job # 2-11-11859 Calculations based on 2013 NFPA Pamphlet #13 Brace Information TOLCOTM Brace Components Maximum Brace Length TO" (2.134 m) TOLCOTM Component Listed Load Adjusted Load Diameter of Brace 1 Fig. 4LA Clamp 1000 Ibs (454 kg) 707 Ibs (321 kg) Fig.980 Universal Swivel 2015 Ibs (914 kg) 1425 Ibs (646 kg) Type of Brace Sch.40 See Fastener Information Angle of Brace 45' Min. *Calculation Based on CONCENTRIC Loading *Please Note: These calculations are for TOLCOTIM components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42" (11 mm) Seismic Brace Assembly Detail L/R Value 200 Max Horizontal Load 1310 Ibs (594 kg) B LINE T—ROW BR F1aINENT - - BRACE PIPE Y uHE I roLca .0 Fastener Information Orientation to Connecting Surface NFPAType B Fastener "IW4HE""OSWAT BRACE ATTACHMENT Type POWERS POWER -STUD +SD2 Diameter 1/2in. I Length 3 1/4in. to Maximum Load 449 Ibs (204 kg) Fn A A "A I ,. "..", Brace Identification on Plans 31N. LONG. CONC. Prying Factor 1.156 Brace Type Lateral [ ] Longitudinal [X] 4-Way [ ] Sprinkler System Load Calculation (Fpw = CpWp) C = 0.601 Diameter Type Length Total Length Weight Per Unit Length Total Weight 3" (80 mm) Sch. 10 80 ft (24.4 m) 80 ft (24.4 m) 7.94 Ib/ft (11.82 kg/m) 635 Ibs (288 kg) Subtotal Weight 635 Ibs (288 kg) Wp (incl. 15%) 730 Ibs (331 kg) Main Size Type/Sch. Spacing (ft) 3" Sch. 10 80 Total (Fpw) Maximum Fpw per 9.3.5.5.2 (if applicable) 439 Ibs (199 kg) N/A {TOLBraceTIM Version 81 Use of TOLBraceTM is subject to terms and conditions per the end user license agreement TOLBraceT"" Seismic Calculations EDMONDS WWTF II 200 2ND AVE. S Brace Identification Brace Type (Per NFPA#13) Braced Pipe (ft) Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # 2-11-11859 FAT*N PommW Sus aw ft fdvAW 31N. LONG. CONC. NFPA Type B 3" Sch.10 Steel Pipe 80' 0" (24.38 m) Longitudinal 1" Sch.40 7' 0" (2.13 m) 200 45' POWERS POWER -STUD +SD2 1/2in. x 3 1/4in. (4,000 PSI Normal Weigh 3 1/4in. Summary of Pipe within Zone of Influence 3" Sch.10 Steel Pipe (76.2 mm) 80 TEE m) G-Factor Used 0.601 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 439 Ibs (199 kg) Material Capacity 1310 Ibs (594 kg) Fastener Capacity 449 Ibs (204 kg) Fig. 4LA Clamp 707 Ibs (321 kg) Fig.980 Universal Swivel 1425 Ibs (646 kg) Structural Member CONCRETE BEAM Calculations prepared by KEVIN RIDER * The description of the Structural Member is for informational purposes only. TOLBrace"" software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBrace'"' 8 Visit us at www.tolco.com POWERS POWER-STUD+SD2 WEDGE ANCHORS IN 4,000 PSI NORMAL WEIGHT CONCRETE a 4 a • • � • Y d + a. H TOLCO SM SERIES ATTACHMENT. POWERS POWER -STUPID •SD2 CARBON STEEL WEDGE ANCHOR. NFPA BRACE ORIENTATIONS A, B, AND C SHOWN ABOVE (MINUS ANGLES), OTHER ORIENTATIONS SIMILAR Fig- 980/ Fig. 910 ANCHOR DIA NOMINAL EMBED. DEPTH "E" MIN. EFFECTIVE EMBED. DEPTH "D" DESIGN EDGE DISTANCE "H" MIN. BASE MATERIAL THICKNESS ALLOWABLE STRENGTH DESIGN (ASD) MAX- ALLOWABLE HORIZONTAL LOAD (LBS.) NFPA BRACE ORIENTATION I PRYING FACTOR A B C D E F G H 1 3.275 1.156 1.739 1.461 1.850 2.894 3,478 Z.459 2.D08 3/8" 2 3/6" 2" 4" 4" 102 215 165 148 158 119 82 116 143 1/2" 3 3/4" 3 1/4" 6" S 3/4" 219 449 348 306 334 261 174 24S 301 5/8" 3 7/8" 3 1/4" 6" 5 3/4" 255 536 411 369 394 297 205 289 356 3/4" 4 1/2" 3 3/4" 1 8" 7" 319 1 679 1 518 470 496 368 259 364 449 VALUES CALCULATED IN ACCORDANCE WITH ACI 318-11 AND INCLUDE OVER STRENGTH FACTOR Q - 26 Fig. 9D9 ANCHOR DIA NOMINAL EMBED. DEPTH "E" MIN. EFFECTIVE EMBED. DEPTH "D" DESIGN EDGE DISTANCE "H' MIN. BASE MATERIAL THICKNESS ALLOWABLE STRENGTH DESIGN (ASD) MAX. ALLOWABLE HORIZONTAL LOAD (LBS.) NFPA BRACE ORIENTATION I PRYING FACTOR A B C D E F G H 1 2.626 1.DO2 1.230 1.513 1A87 2.226 2.460 1.740 1.4ZD 3/8" 1 2 3/8" 2" 4" 4" 122 233 207 145 183 155 103 145 179 1/2" 3 3/4'.1 3 1/4" 6" 5 3/4" 259 486 433 301 385 332 216 304 375 5/8" 1 3 7/8" 3 1/4" 6" S 3/4" 304 583 516 363 457 386 258 362 447 3/4" 1 4 1/2" 3 3/4" 8" 7" 381 1 739 1 653 461 577 479 1 326 459 566 VALUES CALCULATED IN ACCORDANCE WITH ACI318-11 AND INCLUDE OVER STRENGTH FACTOR 0.26 NOTES: I j ALLOWABLE LOADS ARE FOR ANCHORS INSTALLED IN STONE AGGREGATE CONCRETE HAVING A MIN. COMPRESSIVE STRENTH OF 4,000 PSI AT THE TIME OF INSTALLATION AND DETERMINED PER ICC ESR-2502 FOR ANCHORS IN CRACKED CONCRETE. ALLOWABLE LOADS HAVE BEEN CALCULATED IN ACCORDANCE WITH ACI31841, APPENDIX D 24 PER ICC-ESR, PERIODIC SPECIAL INSPECTIONS ARE REQUIRED IN ACCORDANCE WITH SECTION 1706.1.1 AND TABLE 1705.3 OF THE 2015 AND 2012 IBC; ❑R SECTION 1704.16 AND TABLE 1704A OF THE 2009 IBC, AS APPLICABLE. THE SPECIAL INSPECTOR MUST MAKE PERIODIC INSPECTIONS DURING THE ANCHOR I NSTAL LATION TO VERIFY ANCHOR TYPE, ANCHOR 01MENSIONS CONCRETE TYPE, CONCRETE COMPRESSIVE STRENGTH, HOLE DIMENSIONS, HOLE CLEANING PROCEDURE, ANCHOR SPACING, EDGE DISTANCES, CONCRETE MEMBERTHICKNESS, ANCHOR EMBEDMENT, TIGHTENING TORQUE AN ADHERENCE TO THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. CONSULT LOCAL CODES FOR ANY ADDITIONAL SPECIAL INSPECTION REQUIREMENTS. 3,1 FOLLOW ALL WEDGE ANCHOR INSTALLATION REQUIREMENTS PER IC ESR,25D2 4.1 WHEN INSTA ILL ING ANCHORS IN REINFORCED CONCRETE, AVOID DAMAGING REINF0RCI NG STEEL 5.I WHEN INSTALLING ANCHORS IN PRESTRESSED CONCRETE. LOCATE PRESTR ES 8I NG STEEL AND AVOID DAMAGING PRESTRESSING STEEL. 6.I STRUCTURAL ENGINEER OF RECORD SHALL VERIFY ADEC UACY OF THE STRUCTURE FOR THE TABULATED ALLOWABLE LOADS. 7.I TO LC 900 SERIES ATTAC NM E NT DIAMETER SHALL BE EQUAL TO THE ANCHOR DIAMETER 8.I 1F SUBSTRATE CONDITIONS DIFFER FROM WHAT IS LISTED IN THE ABOVE TA BLES, CONTACT EATON B-LI NE AT TOLCO SUPPO RT@EATO N. COM DETAIL PER NFPA 13, 2016 FIGURE A . .5.1 .1(a - c) iY:PlcriErC NJC11�R -2[r 2 2M SF¢JY+N UImti1+5K:N S5AML: FOR 7{:1CORG9!D� TOLCO FIG- 990 TOLC-O FIG. 009 I - a�;, + IR P- i n.ss Farton ppr N FPA 13, 21316 Se rf on !13.4.12 r,hr.n i nstal!pd in mr r. •w.tp s ah ceus Fig. FMO/1M] A 9 C d is F G F I Pr R,. P, Pr ?r Pr Pr P. P. 3.275 1.156 1.73E 1.4C1 1.K-0 j 2-8-94 1.478 2.459 2.00E Fi0. S, i9 A 6 C d E F G 1- I P. P, P P, Pr Pr P, P. F. 2,6215 1.002 1.230 1.513 1.437 2.226 2.460 1.740 1.420 PingFactn•s per NFPA 1.4,20165pct'.nnq..1.5.12 when i L,," IM'n onnrroc. mP..talr.acks tvitr.1"rante,nttsat Fig. 4d4d f91!] A 9 C d E I F G 1 I Pr Pr P- Pr P. P, Pr P. #. 3.275 1.156 1.73E Fig. 909 A 9 C d f F G I P, F P. P, F. P. P. P. P. 2.626 1.002 1.230 P--jngFuclo-sDu-VFflA13,201rxS-cliu:r9.35.12!-jhc-rn-LallccintuncrcLurnclu dUtts!!,'Lh1.125"cu7leruMd Fig. �W!910 A B C d E F G L- I Fr Pr. P. Pr Pr Pr Pr P: P- 3,275 1.156 1.738 - fig- W9 1 B C d E F G L- I Pr Pr Pr P. P. P. P. P. P. 2.52fi 1.003 1.230 - 'Wh� -i irlt5al led i n a �o-.cm.tP meta dec a {TV,)p. Vi 41 /� " x .i'1: d:mprrsipr, W wore r.' hF depe. %ent upon Me. contact area. For S Q2 a-.chors 1*.P max oftspt is 1" s o 'S' wou d he 1.25'. Frir $a'ic-It am Wow. -Knor:kr• 11 # anr.nnrs. the max nffsr.t is 1.125" so W tjnu d of 1.12.;"-