Loading...
APPROVED REVISION 1-Structural_Calculations+6.8.2022■ A GENERAL STRUCTURAL NOTES (THE FOLLOWING APPLY UNLESS SHOWN OTHERWISE ON THE PLANS) CRITERIA 1. ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE DRAWINGS, SPECIFICATIONS, THE INTERNATIONAL BUILDING CODE (2018 EDITION), & EDMONDS BUILDING CODE MODIFICATIONS TO THE INTERNATIONAL BUILDING CODE. 2. DESIGN LOADING CRITERIA: FLOOR LIVE LOAD (RESIDENTIAL). . . . . . . . . . .40 PSF DECK LIVE LOAD (RESIDENTIAL) . . . . . . . . . . .60 PSF ROOF SNOW LOAD (Pf) . . . . . . . . . . . . . . . . 25 PSF WIND: BASIC WIND SPEED (3-SECOND GUST) . . . . . . . .110 MPH WIND IMPORTANCE FACTOR (Iw). . . . . . . . . . . . .1.0 WIND EXPOSURE . . . . . . . . . . . . . . . . . . . . B TOPOGRAPHICAL FACTOR (Kzt). . . . . . . . . . . . .1.00 EARTHQUAKE: LAT. / LONG . . . . . . . . . . . . . . 47.813 /-122.370 SEISMIC IMPORTANCE FACTOR (Ie) . . . . . . . . . . .1.0 SEISMIC USE GROUP. . . . . . . . . . . . . I MAPPED SPECTRAL RESPONSE (Ss/Si) . . . . . . 1.287g/0. 45g SPECTRAL RESPONSE COEF. (SDS/SD 1) . . . . . . 0.89g/0.45g SEISMIC FORCE RESISTING SYSTEM:. . .PLYWOOD SHEAR WALLS DESIGN BASE SHEAR. . . . . . . . . . . . . . . 9.62k SEISMIC RESPONSE COEFICIENT (Cs) . . . . . . . . .0.158 SEISMIC DESIGN CATEGORY . . . . . . . . . . . . . . . D RESPONSE MODIFICATION FACTOR (R). . . . . . . . . . 6.5 ANALYSIS PROCEDURE . . . . . . EQUIVALENT LATERAL FORCE REFERENCE: USGS NATIONAL SEISMIC HAZARD MAPPING PROJECT, 2015 DATA 3. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ARCHITECTURAL DRAWINGS FOR BIDDING AND CONSTRUCTION. CONTRACTOR SHALL VERIFY DIMENSIONS AND CONDITIONS FOR COMPATIBILITY AND SHALL NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO CONSTRUCTION. 4. CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS, MEMBER SIZES, AND CON- DITIONS PRIOR TO COMMENCING ANY WORK. ALL DIMENSIONS OF EXISTING CON- STRUCTION SHOWN ON THE DRAWINGS ARE INTENDED AS GUIDELINES ONLY AND MUST VERIFIED. CONTRACTOR SHALL DETERMINE THE LOCATION OF ALL ADJACENT UNDERGROUND UTILITIES PRIOR TO COMMENCING EXCAVATION. THE CONTRACTOR SHALL BRING ALL CONFLICTS AND DISCREPANICES TO THE ATTENTION OF THE ARCHITECT AND STRUCTURAL ENGINEER. 6. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING FOR THE STRUCTURE AND STRUCTURAL COMPONENTS UNTIL ALL FINAL CONNECTIONS HAVE BEEN COMPLETED IN ACCORDANCE WITH THE PLANS. 7. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SAFETY PRECAUTIONS AND THE METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES REQUIRED TO PERFORM THE WORK. THE STRUCTURAL ENGINEER HAS NO OVERALL SUPERVISORY AUTHORITY OR ACTUAL AND/OR DIRECT RESPONSIBILITY FOR THE SPECIFIC WORKING CONDITIONS AT THE SITE AND/OR FOR ANY HAZARDS RESULTING FROM THE ACTIONS OF ANY TRADE CON- TRACTOR. THE STRUCTURAL ENGINEER HAS NO DUTY TO INSPECT, SUPERVISE, NOTE, CORRECT, OR REPORT ANY HEALTH OR SAFETY DEFICIENCIES OF THE OWNER, CON - CONTRACTORS, OR OTHER ENTITIES OR PERSONS AT THE PROJECT SITE. GEOTECHNICAL 8. FOUNDATION NOTES: SUBGRADE PREPARATION INCLUDING DRAINAGE, EXCAVATION, COMPACTION, AND FILLING REQUIREMENTS, SHALL CONFORM STRICTLY WITH REC- OMMENDATIONS GIVEN IN THE SOILS REPORT OR AS DIRECTED BY THE SOILS ENGI- NEER. FOOTINGS SHALL BEAR ON SOLID UNDISTURBED EARTH (CONTROLLED, COM- PACTED STRUCTURAL FILL OR BOTH) AT LEAST 18" BELOW LOWEST ADJACENT FIN- ISHED GRADE. FOOTING DEPTHS/ELEVATIONS SHOWN ON PLANS (OR IN DETAILS) ARE MINIMUM AND FOR GUIDANCE ONLY; THE ACTUAL ELEVATIONS OF FOOTINGS MUST BE ESTABLISHED BY THE CONTRACTOR IN THE FIELD WORKING WITH THE TESTING LAB AND SOILS ENGINEER. BACKFILL BEHIND ALL RETAINING WALLS WITH FREE DRAINING GRANULAR FILL AND PROVIDE FOR SUBSURFACE DRAINAGE AS NOTED IN THE SOILS REPORT. ALLOWABLE SOIL PRESSURE. . . . . . . . . 2000 PSF LATERAL EARTH PRESSURE . . . . . . . . . 45 PCF SOILS REPORT REFERENCE:COBALT GEOSCIENCES, LLC PARCEL NO. 00434208501600 CONCRETE 9. CONCRETE SHALL BE MIXED, PROPORTIONED, CONVEYED AND PLACED IN ACCORD- ANCE WITH IBC SECTION 1905 AND ACI 301. CONCRETE SHALL ATTAIN A 28-DAY STRENGTH OF F'C = 2,500 PSI AND MIX SHALL CONTAIN NOT LESS THAN 5-1/2 SACKS OF CEMENT PER CUBIC YARD AND SHALL BE PROPORTIONED TO PRODUCE A SLUMP OF 5" OR LESS. THE MINIMUM AMOUNTS OF CEMENT AND MAXIMUM AMOUNTS OF WATER MAY BE CHANGED IF A CONCRETE PERFORMANCE MIX IS SUBMITTED TO THE STRUCTURAL ENGINEER AND THE EDMONDS DEPARTMENT OF PLANNING AND DEVELOPMENT FOR APPROVAL TWO WEEKS PRIOR TO PLACING ANY CONCRETE. THE CONCRETE PERFORMANCE MIX SHALL INCLUDE THE AMOUNTS OF CEMENT, FINE AND COARSE AGGREGATE, WATER AND ADMIXTURES AS WELL AS THE WATER CEMENT RATIO, SLUMP, CONCRETE YIELD AND SUBSTANTIATING STRENGTH DATA IN ACCORDANCE WITH IBC 1905.3. THE USE OF A PERFORMANCE MIX REQUIRES BATCH PLANT INSPECTION, THE COST OF WHICH SHALL BE PAID BY THE GENERAL CONTRACTOR. REVIEW OF MIX SUBMITTALS BY THE ENGINEER OF RECORD INDICATES ONLY THAT INFORMATION PRESENTED CONFORMS GENERALLY WITH CONTRACT DOCUMENTS. CONTRACTOR OR SUPPLIER MAINTAINS FULL RESPONSIBILITY FOR SPECIFIED PERFORMANCE. ALL CONCRETE WITH SURFACES EXPOSED TO STANDING WATER SHALL BE AIR - ENTRAINED WITH AN AIR -ENTRAINING AGENT CONFORMING TO ASTM C260, C494, AND C618. TOTAL AIR CONTENT SHALL BE IN ACCORDANCE WITH TABLE 1904.2.1 OF THE INTERNATIONAL BUILDING CODE. 10. REINFORCING STEEL SHALL CONFORM TO ASTM A615 (INCLUDING SUPPLEMENT S1), GRADE 60, FY = 60,000 PSI. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185. 11. REINFORCING STEEL SHALL BE DETAILED (INCLUDING HOOKS AND BENDS) IN ACCORD- ANCE WITH ACI 318-02. LAP ALL CONTINUOUS REINFORCEMENT 40 BAR DIAMETERS OR 2'-0" MINIMUM. PROVIDE CORNER BARS AT ALL WALL AND FOOTING INTER- SECTIONS. LAP CORNER BARS 40 BAR DIAMETERS OR 2'-0" MINIMUM. LAP ADJACENT MATS OF WELDED WIRE FABRIC A MINIMUM OF 8" AT SIDES AND ENDS. 12. CONCRETE PROTECTION (COVER) FOR REINFORCING STEEL SHALL BE AS FOLLOWS: A. FOOTINGS AND OTHER UNFORMED SURFACES, EARTH FACE . . .3" B. ALL OTHER SURFACES . . . . . . . . . . . . . . . . 1 1/2" 13. NON -SHRINK GROUT SHALL BE FURNISHED BY AN APPROVED MANUFACTURER AND SHALL BE MIXED AND PLACED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S PUBLISHED RECOMMENDATIONS. GROUT STRENGTH SHALL BE AT LEAST EQUAL TO THE MATERIAL ON WHICH IT IS PLACED (3000 PSI MINIMUM). ANCHORAGE 14. EXPANSION BOLTS INTO CONCRETE AND GROUTED MASONRY UNITS SHALL BE "STRONG -BOLT" ANCHORS AS MANUFACTURED BY THE SIMPSON COMPANY AND INSTALLED IN STRICT ACCORDANCE WITH ICC ESR 1771, INCLUDING MINIMUM EMBEDMENT REQUIREMENTS. 15. EPDXY -GROUTED ITEMS SPECIFIED ON THE DRAWINGS SHALL BE GROUTED WITH "SET-XP" HIGH STRENGTH EPDXY AS MANUFACTURED BY THE SIMPSON COMPANY AND INSTALLED IN STRICT ACCORDANCE WITH ICC ESR 2508. 16. TITEN HD ANCHORS SPECIFIED ON THE DRAWINGS SHALL CONSIST OF "TITEN HD" HEAVY DUTY SCREW ANCHORS AS MANUFACTURED BY THE SIMPSON COMPANY AND INSTALLED IN STRICT ACCORDANCE WITH ICC ESR 2713. WOOD 17. FRAMING LUMBER SHALL BE KILN DRIED OR MC-15, AND GRADED AND MARKED IN CON- FORMANCE WITH WCLIB STANDARD GRADING RULES FOR WEST COAST LUMBER NO. 17, LATEST EDITION. FURNISH TO THE FOLLOWING MINIMUM STANDARDS: JOISTS: (2X MEMBERS) HEM -FIR NO. 2 MINIMUM BASE VALUE, FB = 850 PSI (3X & 4X MEMBERS) DOUGLAS FIR NO. 1 MINIMUM BASE VALUE, FB = 1000 PSI STRUCTURAL LIGHT FRAMING: DOUGLAS FIR NO. 2 (INCL. 3X AND 4X POSTS) MINIMUM BASE VALUE, FB = 900 PSI BEAMS AND STRINGERS: DOUGLAS FIR NO. 1 (INCL. 6X AND LARGER) MINIMUM BASE VALUE, FB = 1350 PSI POSTS AND TIMBERS: DOUGLAS FIR NO. 1 (6X6 AND LARGER ) MINIMUM BASE VALUE, FC = 1000 PSI STUDS, PLATES & MISC. FRAMING: DOUGLAS FIR OR HEM -FIR STANDARD GRADE 2X6 STUDS AND PLATES: HEM -FIR NO.3/ STUD GRADE 2X AND 3X T & G DECKING HEM -FIR COMMERICAL DEX, MINIMUM BASE VALUE, FB = 1350 PSI 18. GLUED LAMINATED MEMBERS SHALL BE FABRICATED IN CONFORMANCE WITH ASTM AND AITC STANDARDS. EACH MEMBER SHALL BEAR AN AITC IDENTIFICATION MARK AND SHALL BE ACCOMPANIED BY AN AITC CERTIFICATE OF CONFORMANCE. ALL SIMPLE SPAN BEAMS SHALL BE DOUGLAS FIR COMBINATION 24F-V4, FB = 2,400 PSI, FV = 165 PSI. ALL CANTILEVERED BEAMS SHALL BE DOUGLAS FIR COMBINATION 24F-V8, FB = 2400 PSI, FV = 165 PSI. CAMBER ALL SIMPLE SPAN GLULAM BEAMS TO 2,000' RADIUS, UNLESS SHOWN OTHERWISE ON THE PLANS. ALL COLUMNS SHALL BE DOUGLAS FIR COMBINATION NO. 5, FC = 2400 PSI, E = 2.0 X 10E6 PSI. 19. ENGINEERED LUMBER MEMBERS SHALL BE MANUFACTURED UNDER A PROCESS BY THE NATIONAL RESEARCH BOARD. EACH PIECE SHALL BEAR A STAMP OR STAMPS NOTING THE NAME AND PLANT NUMBER OF THE MANUFACTURER, THE GRADE, THE NATIONAL RESEARCH BOARD NUMBER, AND THE QUALITY CONTROL AGENCY. ALL LUMBER SHALL BE MANUFACTURED IN ACCORDANCE WITH THE APPROPRIATE ICC REPORT AND GLUED WITH A WATERPROOF ADHESIVE MEETING THE REQUIREMENTS OF ASTM D2559 WITH ALL GRAIN PARALLEL WITH THE LENGTH OF THE MEMBER. PSL FB = 2900 PSI E = 2000 KSI FV = 290 PSI ESR-1387 LSL FB = 2250 PSI E = 1500 KSI FV = 285 PSI ESR-1387 LVL FB = 2600 PSI E = 1800 KSI FV = 285 PSI ESR-1387 DESIGN SHOWN ON PLANS IS BASED ON LUMBER MANUFACTURED BY THE WEYERHAUSER CORPORATION. ALTERNATE MANUFACTURERS MAY BE USED SUBJECT TO REVIEW AND APPROVAL BY THE ARCHITECT AND STRUCTURAL ENGINEER. ALTERNATE JOIST HANGERS AND OTHER HARDWARE MAY BE SUBSTITUTED FOR ITEMS SHOWN PROVIDED THEY HAVE ICC APPROVAL FOR EQUAL OR GREATER LOAD CAPACITIES. ALL JOIST HANGERS AND OTHER HARDWARE SHALL BE COMPATIBLE IN SIZE WITH MEMBERS PROVIDED. ALL PROPOSED HOLE SIZES AND LOCATIONS SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER FOR APPROVAL TWO WORKING DAYS PRIOR TO DRILLING HOLES. 20. PREFABRICATED PLYWOOD WEB JOIST DESIGN SHOWN ON PLANS IS BASED ON JOISTS MANUFACTURED BY THE WEYERHAUSER CORPORATION AND SHALL BE FURNISHED AND INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S PUBLISHED SPECIFICATIONS. ALL NECESSARY BRIDGING, BLOCKING, BLOCKING PANELS, STIFFENERS, ETC., SHALL BE DETAILED AND FURNISHED BY THE MANUFACTURER. SUBMIT SHOP DRAWINGS TO THE ARCHITECT AND STRUCTURAL ENGINEER FOR REVIEW PRIOR TO FABRICATION. ALTERNATE PLYWOOD WEB JOIST MANUFACTURERS MAY BE USED SUBJECT TO REVIEW AND APPROVAL BY THE ARCHITECT AND STRUCTURAL ENGINEER. ALTERNATE JOIST HANGERS AND OTHER HARDWARE MAY BE SUBSTITUTED FOR ITEMS SHOWN PROVIDED THEY HAVE ICC APPROVAL FOR EQUAL OR GREATER LOAD CAPACITIES. ALL JOIST HANGERS AND OTHER HARDWARE SHALL BE COMPATIBLE IN SIZE WITH PLYWOOD WEB JOIST PROVIDED. ALL HOLES SHALL CONFORM TO THE MANUFACTURERS SPECIFICATIONS. IF THREE OR FEWER HOLES ARE PROPOSED FOR A SINGLE JOIST, HOLES SHALL CONFORM TO THE WEYERHAUSER ILEVEL TJI ALLOWABLE HOLE CHART. IF MORE THEN THREE HOLES ARE PROPOSED FOR ONE SINGLE JOIST, ALL HOLE SIZES AND LOCATIONS SHALL BE SUB- MITTED TO THE STRUCTURAL ENGINEER FOR APPROVAL TWO WORKING DAYS PRIOR TO DRILLING HOLES. 21. PLYWOOD SHEATHING SHALL BE GRADE C-D, EXTERIOR GLUE OR STRUCTURAL II, EXTERIOR GLUE IN CONFORMANCE WITH APA STANDARDS. ORIENTED STRAND BOARD OF EQUIVALENT THICKNESS, EXPOSURE RATING AND SPAN RATING MAY BE USED IN LIEU OF PLYWOOD. A. ROOF SHEATHING SHALL BE 1/2" (NOM.) WITH SPAN RATING 24/0. B. FLOOR SHEATHING SHALL BE 3/4" (NOM.) WITH SPAN RATING 40/20. C. WALL SHEATHING SHALL BE 1/2" (NOM.) WITH SPAN RATING 24/0. REFER TO WOOD FRAMING NOTES BELOW FOR TYPICAL NAILING. 22. ALL WOOD IN DIRECT CONTACT WITH CONCRETE OR MASONRY SHALL BE PRESSURE - TREATED WITH AN APPROVED PRESERVATIVE OR (2) LAYERS OF ASPHALT IMPREGNATED BUILDING PAPER SHALL BE PROVIDED BETWEEN UNTREATED WOOD AND CONCRETE OR MASONRY. ALL WOOD EXPOSED TO WEATHER WITHOUT THE ADEQUATE PROTECTION OF A ROOF OR EAVE SHALL BE AN APPROVED WOOD OF NATURAL RESISTANCE TO DECAY OR PRESSURE TREATED. SUCH MEMBERS INCLUDE HORIZONTAL MEMBERS SUCH AS GIRDERS, JOISTS, AND DECKING; OR VERTICAL MEMBERS SUCH AS POSTS, POLES, AND COLUMNS. 23. TIMBER CONNECTORS CALLED OUT BY LETTERS AND NUMBERS SHALL BE "STRONG -TIE" BY SIMPSON COMPANY, AS SPECIFIED IN THEIR MOST RECENT CATALOG. EQUIVALENT DEVICES BY OTHER MANUFACTURERS MAY BE SUBSTITUTED, PROVIDED THEY HAVE ICC APPROVAL FOR EQUAL OR GREATER LOAD CAPACITIES. PROVIDE NUMBER AND SIZE OF FASTENERS AS SPECIFIED BY MANUFACTURER. CONNECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. WHERE CONNECTOR STRAPS CONNECT TWO MEMBERS, PLACE ONE-HALF OF THE NAILS OR BOLTS IN EACH MEMBER. ALL BOLTS IN WOOD MEMBERS SHALL CONFORM TO ASTM A307. PROVIDE WASHERS UNDER THE HEADS AND NUTS OF ALL BOLTS AND LAG SCREWS BEARING ON WOOD. UN- LESS NOTED OTHERWISE, ALL NAILS SHALL BE COMMON. ALL SHIMS SHALL BE SEA- SONED AND DRIED AND THE SAME GRADE (MINIMUM) AS MEMBERS CONNECTED. HANGERS IN DIRECT CONTACT WITH PRESERVATIVE -TREATED WOOD SHALL BE EITHER STAINLESS STEEL (SST300), POST HOT -DIPPED GALVANIZED(HDG) OR GALVANIZED WITH A MINI- MUM OF 1.850Z ZINC PER SQUARE INCH (ZMAX). UNLESS NOTED OTHERWISE, ALL LUMBER JOISTS SHALL BE CONNECTED TO FLUSH BEAMS WITH "LUS" SERIES JOIST HANGERS, AND ALL TJI JOISTS SHALL BE CONNECTED TO FLUSH BEAMS WITH "ITT" OR "IUT" SERIES JOIST HANGERS. 24. NAILS - NAIL SIZES SPECIFIED ON DRAWINGS ARE BASED ON THE FOLLOWING SPECIFICATIONS: SIZE LENGTH DIAMETER 6D 2" 0. 113" 8D 2-1/2" 0. 131" 10D 3" 0. 148" 12D 3-1/4" 0. 148" 16D 3-1/2" 0. 162" IF CONTRACTOR PROPOSES THE USE OF ALTERNATE NAILS, THEY SHALL SUBMIT NAIL SPECIFICATIONS TO THE STRUCTURAL ENGINEER (PRIOR TO CONSTRUCTION) FOR REVIEW AND APPROVAL. NAILS SHALL BE DRIVEN FLUSH TO FACE OF SHEATHING WITH NO COUNTERSINKING PERMITTED. 25. WOOD FRAMING NOTES --THE FOLLOWING APPLY UNLESS OTHERWISE SHOWN: A. ALL WOOD FRAMING DETAILS NOT SHOWN OTHERWISE SHALL BE CONSTRUCTED TO THE MINIMUM STANDARDS OF THE INTERNATIONAL BUILDING CODE. MINIMUM NAILING, UNLESS OTHERWISE NOTED, SHALL CONFORM TO TABLE 2304.9.1 OF THE INTERNATIONAL BUILDING CODE. UNLESS NOTED OTHERWISE, ALL NAILS SHALL BE COMMON. COORDINATE THE SIZE AND LOCATION OF ALL OPENINGS WITH MECHANICAL AND ARCHITECTURAL DRAWINGS. PROVIDE WASHERS UNDER THE HEADS AND NUTS OF ALL BOLTS AND LAG SCREWS BEARING ON WOOD. B. WALL FRAMING: ALL STUD WALLS SHOWN AND NOT OTHERWISE NOTED SHALL BE 2X4 STUDS @ 16" 0. C. AT I NTER I OR WALLS AND 2X6 @ 16" 0. C. AT EXTER I OR WALLS. TWO STUDS MINIMUM SHALL BE PROVIDED AT THE END OF ALL WALLS AND AT EACH SIDE OF ALL OPENINGS. TWO 2X8 HEADERS SHALL BE PROVIDED OVER ALL OPENINGS NOT OTHERWISE NOTED. SOLID BLOCKING FOR WOOD COL- UMNS SHALL BE PROVIDED THROUGH FLOORS TO SUPPORTS BELOW. WALLS SHALL HAVE A SINGLE BOTTOM PLATE AND A DOUBLE TOP PLATE. END NAIL TOP PLATE TO EACH STUD WITH TWO 16D NAILS, AND TOENAIL OR END NAIL EACH STUD TO BOTTOM PLATE WITH TWO 16D NAILS. FACE NAIL DOUBLE TOP PLATE WITH 16D AT 12" O.C. AND LAP MINIMUM 4'-0" AT JOINTS AND PROVIDE SIX 16D NAILS AT 4" O.C. EACH SIDE OF JOINT. ALL STUD WALLS SHALL HAVE THEIR LOWER WOOD PLATES ATTACHED TO WOOD FRAMING BELOW WITH 16D NAILS AT 12" O.C. STAGGERED OR BOLTED TO CONCRETE WITH 5/8" DIAMETER ANCHOR BOLTS (WITH 7" MINIMUM EMBEDMENT) @ 4' -0" 0. C. UNLESS INDICATED OTHERWISE. INDIVI- DUAL MEMBERS OF BUILT-UP POSTS SHALL BE NAILED TO EACH OTHER WITH 16D @ 12" O.C. STAGGERED. REFER TO THE PLANS AND SHEAR WALL SCHEDULE FOR REQUIRED SHEATHING AND NAILING. WHEN NOT OTHERWISE NOTED, PROVIDE GYPSUM WALLBOARD ON INTERIOR SURFACES NAILED TO ALL STUDS, TOP AND BOTTOM PLATES AND BLOCKING WITH NAILS AT 7" O.C. USE 5D COOLER NAILS FOR 1/2" GWB AND 6D COOLER NAILS FOR 5/8" GWB. WHEN NOT OTHERWISE NOTED, PROVIDE 1/2" (NOM.) APA RATED SHEATHING ( SPAN RATING 24/0) ON EXTERIOR SURFACES NAILED AT ALL PANEL EDGES (BLOCK UNSUPPORTED EDGES), TOP AND BOTTOM PLATES WITH 8D @ 6" O.C. AND TO ALL INTERMEDIATE STUDS AND BLOCKING WITH 8D @ 12" O.C. ALLOW 1/8" SPACING AT ALL PANEL EDGES AND ENDS. C. FLOOR AND ROOF FRAMING: PROVIDE DOUBLE JOISTS AROUND ALL OPENINGS IN FLOORS OR ROOFS UNLESS OTHERWISE NOTED. PROVIDE SOLID BLOCKING AT ALL BEARING POINTS. TOENAIL JOISTS TO SUPPORTS WITH TWO 16D NAILS. ATTACH TIMBER JOISTS TO FLUSH HEADERS OR BEAMS WITH METAL JOIST HANGERS IN ACCORDANCE WITH TIMBER CONNECTOR NOTE. NAIL ALL MULTI -JOIST BEAMS TO- GETHER WITH 16D @ 12" O.C. STAGGERED. UNLESS OTHERWISE NOTED ON THE PLANS, ROOF AND FLOOR SHEATHING SHALL BE LAID UP WITH STRENGTH AXIS PERPENDICULAR TO SUPPORTS AND NAILED WITH 8D NAILS @ 6" O.C. TO FRAMED PANEL EDGES AND OVER STUD WALLS AS SHOWN ON PLANS AND @ 12" O.C. TO INTERMEDIATE SUPPORTS. PROVIDE APPROVED PLYWOOD EDGE CLIPS CENTERED BETWEEN JOISTS/TRUSSES AT UNBLOCKED ROOF SHEATHING EDGES. ALL FLOOR SHEATHING EDGES SHALL HAVE APPROVED TONGUE -AND -GROOVE JOINTS OR SHALL BE SUPPORTED WITH SOLID BLOCKING. ALLOW 1/8" SPACING AT ALL PANEL EDGES AND ENDS OF ALL ROOF AND FLOOR SHEATHING. TOENAIL BLOCKING TO SUPPORTS WITH 16D @ 12" O.C. UNLESS OTHERWISE NOTED. AT BLOCKED FLOOR AND ROOF DIAPHRAGMS PROVIDE FLAT 2X BLOCKING AT ALL UNFRAMED PLYWOOD PANEL EDGES AND NAIL WITH EDGE NAILING SPECIFIED. BLD2021-1590 Harriott Valentine Engineers Inc. 1932 First Avenue, Suite 720 Seattle, Washington 98101-2447 tel 206 624 4760 fax 206 447 6971 www.harriottvalentine.com REVISED PLAN APPROVED CITY OF EDMONDS BUILDING DIVISION E r i & Jun 27 2022 APPROVED DATE �**�' 4127122 Project Contact Jim Harriott tel 206 778 2990 jharriott@harriottvalentine.com Project Architect Maggie Hanna - WAKEdesign, LLC 1752 NW Market St, #203 Seattle, WA 98107 Project Dunn Residence 315 8th Ave N Edmonds, WA 98020 Issue Date Issue Description 11/10/2021 Permit 02/11/2022 Corrections 02/28/2022 Coordination 01 4/27/2022 Construction Set Z Building Department Approval REVISION Jun 08 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Drawing Title GENERAL STRUCTURAL NOTES Drawing Number S1.0 w 0 Z w 0 U) w z z 0 ■ A 10" 0 PLINTH, REINF. W/ (4) #4 VERT. (3) #4 EACH WAY BOTTOM 5/8 0 x 8" TITEN HD TO EX. CONC. STEMWALL (3) #4 EACH WAY BOTTOM NEW FOOTING BELOW EX. STEMWALL l a 2'-0" SQUARE COLUMN PER PLAN (PRESSURE -TREATED) ABA SERIES POST BASE 3/4" = 1'-0" COLUMN PER PLAN (PRESSURE -TREATED) ABA SERIES POST BASE EXISTING SLAB REPAIR SLAB PER 4/S2.0 EX. STEMWALL PER PLAN 1/2" EPDXY GROUT FOR FULL BEARING 3/4" = 1'-0" IN 3 4" THICK SLAB REINF. W/ W2.9xW2.9 6x6 W.W.M. CTR'D. TYPICAL _—X x x x X x— 6 MIL VAPOR BARRIER o�000 °moo°°oa000°o�'� (OMIT AT EXTERIOR SLABS) SLAB 80°00�� 0°080°00°�° 0°08° ° 4" FREE -DRAINING GRANULAR FILL CONTROL -X x X� rx X X- og°o o JOINT 800� �2nd POUR 1st POUR CON STR. -x x x x x x- a JOINT 8`0°00�� 0°080°oo°R°� 0°08 CONTROL JOINT FORMER "ZIP STRIP" 11/2" DEEP (JOINT MAY BE SAW -CUT AT CONTRACTOR'S OPTION) CUT ALT. WIRES AT JOINT PLASTIC JOINT KEY "MEADOW BURKE" STOP REINF. 1" CLEAR OF JOINT EACH SIDE SLAB -ON -GRADE (NOT INSULATED) 3/4" = 1'-0" FOUNDATION PLAN scale: 1/4° = V-0° FOUNDATION PLAN NOTES WHERE NEW CONCRETE WALLS OR FOOTING ABUT EX. CONCRETE, PROVIDE DOWELS #4 x 2'-0" TO MATCH HORIZ. REINFORCING, EMBED 5" IN EPDXY GROUT. 2. SEE 10/S4.0 FOR TYPICAL HOLDOWN REQUIREMENTS AT CONCRETE WALLS AND FOOTINGS. 3. SLAB -ON -GRADE SHALL BE PLACED AND CURED FOR A MINIMUM OF SEVEN DAYS BEFORE RETAINING WALLS ARE BACKFILLED. SEE RETAINING WALL DETAILS FOR SPECIFIC CONFIGURATION. LEGEND SECTION DETAIL PRESSURE -TREATED ALL -THREAD HOLDOWN AT END OF SHEARWALL ABOVE STRAP HOLDOWN AT END OF SHEARWALL ABOVE WALL OR COLUMN ABOVE EXISTING STUD WALL NEW STUD WALL EXISTING MASONRY WALL EXISTING CONCRETE WALL NEW CONCRETE WALL BLD2021-1590 Harriott Valentine Engineers Inc. 1932 First Avenue, Suite 720 Seattle, Washington 98101-2447 tel 206 624 4760 fax 206 447 6971 www.harriottvalentine.com REVISED PLAN APPROVED CITY OF EDMONDS BUILDING DIVISION E r i & Jun 27 2022 APPROVED DATE Orwwwgw F 4127122 Project Contact Jim Harriott tel 206 778 2990 jhardoft@hardoftvalentine.com Project Architect Maggie Hanna — WAKEdesign, LLC 1752 NW Market St, #203 Seattle, WA 98107 Project Dunn Residence 315 8th Ave N Edmonds, WA 98020 Issue Date 11/10/2021 Issue Description Permit 02/11/2022 02/28/2022 Corrections Coordination 4/27/2022 Construction Set 0 Building Department Approval REVISION Jun 08 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Drawing Title FOUNDATION PLAN Drawing Number SIO LL I U z LLI 0 07 LL I z z 0 44 (P.T.) STANCHIONS SEE ARCH'L. FOR LAYOUT SEE ARCH'L. FOR INFILL, TOP AND BOTTOM RAILS UNLESS NOTED OTHERWISE, PROVIDE THE FOLLOWING AT A MINIMUM: 26 RAIL CAP, AND 2x4 TOP AND BOTTOM RAILS, WITH A MAXIMUM SPAN OF 6'-0"oc, ATTACH EACH WITH (2) NO. 8 WOOD SCREWS EACH END (MIN.) 2x2 PICKETS @ 4"oc, ATTACH EACH WITH (1) NO. 8 WOOD SCREW TOP AND BOTTOM NOTE: REFER TO 5/S3.1 FOR FLOOR FRAMING R E SI GAT LEDGER CONTINUOUS FLASHING WITH DRIP EDGE (COORD. WITH ARCHITECTURAL) DECK JOISTS PER PLAN WITH HANGERS PER PLAN (3) 10d BOX EACH SIDE OF BLOCKING L N _ N HD2A TOP AND BOTTOM EACH WITH 5/8" 0 THRU— BOLT TO STANCHIONS AND (2) 5/8"0 DIAMETER THRU— BOLTS TO BLOCKING (5) 16d BLOCK ONE BAY FULL DEPTH WITH (2) 2x (AT JOISTS PARALLEL CONDITION, SHOWN) OR PROVIDE 2x BACKER 16" LONG (AT JOISTS PERPENDICULAR CONDITION, SIMILAR) 1-1/2" = 1'-0" 2 SHEARWALL PER PLAN (2) ROWS 1/2" 0 THRU— BOLTS @ 8"oc (EACH ROW) JOISTS PER PLAN SHEARWALL PER PLAN 1-1/2)) = 1'-0" 3 PANEL EDGE NAILING PLAN (8d @ Coc U.N.O.) TAPERED JOISTS / (SLOPE PER ARCH'L.� � EX. JOISTS PER PLAN BEAM PER PLAN BLOCK ONE BAY EACH SIDE FULL —DEPTH @ 48"oc — FIT TIGHT 3/4" = 1'-0" 4 ■ A Harriott Valentine Engineers Inc. 1932 First Avenue, Suite 720 Seattle, Washington 98101-2447 tel 206 624 4760 fax 206 447 6971 www.harriottvalentine.com REVISED PLAN APPROVED CITY OF EDMONDS BUILDING DIVISION E r i & Jun 27 2022 APPROVED DATE Orwwwgw — 4127122 Project Contact Jim Harriott tel 206 778 2990 jhardoft@hardoftvalentine.com Project Architect Maggie Hanna — WAKEdesign, LLC 1752 NW Market St, #203 Seattle, WA 98107 Project Dunn Residence 315 8th Ave N Edmonds, WA 98020 Issue Date 11/10/2021 Issue Description Permit 02/11/2022 02/28/2022 Corrections Coordination 4/27/2022 Construction Set 0 Building Department Approval REVISION Jun 08 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Drawing Title MAIN FLOOR FRAMING PLAN U z w 0 ' V O Drawing Number S11 z z 0 HV Harriott Valentine Engineers Inc. 8d @ 6"oc RAFTERS PER PLAN 4x10 PER PLAN 2 PANEL EDGE NAILING PER PLAN (8d @ Coc U.N.O.) 8d @ Coc TO BLOCKING EX. OUTRIGGERS 1932 First Avenue, Suite 720 Seattle, Washington 98101-2447 tel 206 624 4760 fax 206 447 6971 www.harriottvalentine.com BLOCK FULL —DEPTH (VENT PER ARCH'L.) REVISED PLAN APPRO BLOCK FULL —DEPTH CITY OF EDMONDS BUILDING DIVI 4x10 PER (VENT PER ARCH'L.) — TAPERED SLEEPERS (SLOPE PER ARCH'L.) (3) 16d Erg PLAN FURR AS REQUIRED TO MATCH EXISTING CEILING AT BLOCK EX. RAFTERS BUILDING OFFICIAL Jun 27 2022 RAFTERS PER PLAN HEIGHT — OR RIP 2x12 EX. RAFTER PER PLAN PER PLAN APPROVED DATE P. TO OVERALL DEPTH BLOCK FULL —DEPTH BLOCK ONE RAFTER HANGER LUS210 2 A35 @ 24"oc @ 24"oc — NAIL WITH (3) 12d EACH — A35 PER SW SCHEDULE BAY @ 48"oc SIDE EACH BLOCK SHEARWALL PER PLAN A35 PER SW SCHEDULE H2.5A AT EACH RAFTER H2.5A EACH JOIST WIND BEAM PER PLAN SHEARWALL PER PLAN SHEARWALL PER PLAN 3/4" = 1'-0" 1 3/4" = 1'-0" 2 3/4" = 1'-0" 3/4" = 1'-0" 4 GE NAILING PER @ Coc U.N.O.) LL—DEPTH PANEL EDGE NAILING PLAN (8d @ Coc U.N.O.) TAPERED SLEEPERS (SLOPE PER ARCH'L.) PANEL EDGE NAILING PLAN (8d @ Coc U.N.O.) PANEL EDGE NAILING PLAN (8d @ Coc U.N.O.) ARCH'L.) LBK TAPERED SLEEPERS BEAM PER PLAN TAPERED SLEEPERS BEAM PER PLAN BLOCK FULL —DEPTH @ MIDSPAN OF OVERHANG SLEEPERS R ARCH'L.) (SLOPE PER ARCH'L.) EX. JOISTS PER PLAN (BEAR 13/4" MIN.) (3) 1Od BOX EACH SIDE OF BLOCKING EX. JOISTS PER PLAN (SLOPE PER ARCH'L.) EX. JOISTS PER PLANWA (BEAR 13/4" MIN.) g ° O .t 2u4� RAFTERS PER PLAN �o 4127122 A35 PER SW SCHEDULE BEAM PER PLAN --___ - Project Contact H2.5A EACH JOIST HANGERS PER PLAN BLOCK ONE BAY EACH SIDE FULL —DEPTH @ 48"oc — FIT TIGHT HANGERS PER PLAN Jim Harriott tel 206 778 2990 jharriott@harriottvalentine.com Project Architect SHEARWALL PER PLAN Maggie Hanna — WAKEdesign, LLC 1752 NW Market St, #203 Seattle, WA 98107 (WHERE OCCURS) Project 3/4" = 1'-0" 5 3/4" = 1'-0" 6 3/4" = 1'-0" 7 3/4" = 1'-0" 8 Dunn Residence 315 8th Ave N Edmonds, WA 98020 2 2 Issue Date Issue Description 11/10/2021 Permit 02/11/2022 Corrections EXISTING 2x4 @ 24"oc PANEL EDGE NAILING 8d @ Coc RAFTERS PER PLAN (NEW) PANEL EDGE NAILING 8d @ Coc 02/28/2022 Coordination 2 4/27/2022 Construction Set 22 RAFTERS PER PLAN RAFTERS PER PLAN (EXISTING) (EXISTING) Building Department Approval EXISTING 2x8 @ 16"oc FURR AS REQUIRED TO MATCH EXISTING CEILING 2 CDETA:ILDE:LETED 2 DETAIL DELETED REVISION Jun 08 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT HEIGHT — OR RIP 2x12 GLULAM BEAM PER PLAN TO OVERALL DEPTH GLULAM BEAM PER PLAN Drawing Title STRUCTURAL DETAILS BLD2021-1590 Drawing Number » > » 3/4 = 1 —0 9 ,> > » 3/4 = 1 —0 10 >, , �, 3/4 = 1 —0 11 7 /A" 1'_n" ./ , _ 1 12 S3.0 ED ;ION Lu U z LL I 0 U) LL I IY z z 0 HV Harriott Valentine Engineers Inc. 1932 First Avenue, Suite 720 Seattle, Washington 98101-2447 tel 206 624 4760 fax 206 447 6971 www. harriottvalenti ne. com A35 @ 48"oc 26 P.T. PLATE WITH REVISED PLAN APPRONJ 5/8" 0 X 8" TITEN HD CITY OF EDMONDS BUILDING DIVI BOLTS @ 48"oc (3) 10d BOX EACH Erg 2 2 2 SIDE OF BLOCKING DETAIL DELETED =DETAILETED DETAIL DELETED BUILDING OFFICIAL Jun 27 2022 PT RIMBOARD--------- APPROVED DATE (U.N.O. ON PLAN) ° BLOCK ONE BAY FULL — DEPTH @ 48"oc WITH PT RIMBOARD — j FIT TIGHT TO JOISTS EX. CONC. WALL 10d BOX TOENAIL EACH SIDE OF RIM TO PLATE a 3/4" = 1'-0" 1 3/4" = 1'-0" 2 3/4" = 1'-0" 3 ° a 3/4" = 1'-0" 4 PLATE NAILING PER SHEARWALL SCHEDULE SHEARWALL PER PLAN EX. FLOOR SHEATHING TRIM TONGUES AND/OR PANEL EDGE NAILING GROOVES AT EDGE OF PER PLAN FROM NEW SHEATHING SHEATING TO FLAT 26 BLOCKING WAA 10d BOX FACENAIL {~ �i `� � ' AT TOP AND BOTTOM OF JOIST NEW FLOOR SHEATHING 2 DETAIL DELETED =DELETED `� '�{�;J � ::, EX. JOISTS PER PLAN (BEAR 13/4" MIN.) 29049 o EX. 2x RIM (U.N.O. ON ON PLAN) — FLAT 26 BLOCKING @ 4127122 EACH JOIST BAY Project Contact Jim Harriott A35 PER SW SCHEDULE tel 206 778 2990 j harriott@harriottvalenti ne.com SHEARWALL PER PLAN A35 PER SW SCHEDULE Project Architect Maggie Hanna — WAKEdesign, LLC 1752 NW Market St, #203 Seattle, WA 98107 Project 3/4" = 1'-0" 3/4" = 1'-0" 3/4" = 1'-0" c� 8 Dunn Residence 315 8th Ave N Edmonds, WA 98020 Issue Date Issue Description 11/10/2021 Permit 02/11/2022 Corrections 02/28/2022 Coordination 0 4/27/2022 Construction Set Building Department Approval 2 REVISION DETAIL DELETED Jun 08 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Drawing Title STRUCTURAL DETAILS BLD2021-1590 Drawing Number 9 10 11 12 S3.1 3/4 = 1 —0 3/4 = 1 —0 3/4 = 1 —0 "/ I _ 1 ED ;ION Lu 0 Z LLI 0 U) LLI z z D 0 ■A z DETAIL DELETED 3/4" = 1'-0" STRAP SCHEDULE (NOT ALL USED) MARK END LENGTH NAILS NAIL SPACING CS20 9" (16) 8d x 21/2" 21/16'$ MSTCM40 111/4" (14) 1Old x 31/4 N/A 1. 10d AND 12d DIAMETER = 0.148"; 8d DIAMETER = 0.131". 2. USE HALF OF THE REQUIRED NAILS IN EACH MEMBER BEING CONNECTED (i.e. IN EACH END LENGTH). HOLDOWN SCHEDULE (NOT ALL USED ON PLANS) MARK FASTENERS TO STUDS' ANCHOR DIA.2 EMBEDMENT LENGTH SSTB' EPDXY' 8" CAST —IN' 11 HDU2 (6) 1/4n0 x 21/2" SCREWS 5/8" SSTB16 1. 10d AND 12d DIAMETER = 0.148"; 16d DIAMETER = 0.162". SCREWS SHALL BE SIMPSON "SDS" TYPE SCREWS, INSTALL PER SIMPSON RECOMMENDATIONS. 2. PROVIDE A36 OR A307 ALL —THREAD AT EPDXY AND CAST —IN ANCHORS. 3. PROVIDE SIMPSON "SET—XP" EPDXY PER GENERAL STRUCTURAL NOTES. SPECIAL INSPECTION IS REQUIRED. 4. AT CAST —IN ANCHORS PROVIDE HEAVY HEX NUT AT BOTTOM OF ALL —THREAD. HOOKED J—BOLT MAY BE USED FOR LTT HOLDOWNS. 5. AT 3x SILL PLATES, PROVIDE LONGER SSTBL MODELS. SHEATHING PER SW SCHEDULE z ONE-SIDED Fo-1 SHEARWALL SHEATHING PER SW =E F SCHEDULE TWO-SIDED OO STAGGER ANCHORS SHEARWALL AT TWO—SIDED SHEARWALLS x Q ANCHOR BOLT WITH PLATE —SHEATHING PER SW WASHER PER SW SCHEDULE SCHEDULE (0.229" x 3" SQUARE) 1 TYPICAL SHEARWALL ANCHOR BOLT PLACEMENT 1-1/2" = 1'-0" 2 n 77 SHEARWALL PER PLAN C - PIROVIDE HALF OF SPECIFIED W IN EACH END LENGTH — —NAILS ___EF___— 1�1= — ____ __ ------ II -rfi ----u---- II II 11I Ji - II - - - ---- II -- IT T T-- :. t --T-1 _T7-- � o I II PROVIDE I II 15/8" MIN. END Z W DISTANCE FOR NAILS SHEARWALL PER II II PLAN � II II II III III II II II II TYPICAL STRAP HOLDOWN AT FLOOR 3/4" = 1'-0" 6 SHEARWALL PER PLAN AT EX. CONC. WALL PROVIDE ALL —THREAD AND EMBED IN EPDXY GROUT PER SCHEDULE (2) STUDS MIN. — REFER TO PLAN FOR LOCATIONS WHERE BUILT—UP POST CONSISTS OF MORE STUDS HOLDOWN PER PLAN W/ SCREWS PER MFR. SPECS. (OR NAILS SIMILAR) CONCRETE STEMWALL PER PLAN (6" MIN. THICKNESS) II ° II AT NEW CONCRETE WALL PROVIDE ALL —THREAD AND UJ HEX NUT OR HEADED BOLT W � NOTE: AND EMBED PER SCHEDULE PROVIDE 5" END (HOOKED J—BOLT MAY BE AND 13/4" EDGE USED FOR LTT HOLDOWNS) DISTANCE FOR ANCHORS (MIN.) TYPICAL HOLDOWN AT CONCRETE 3/4" = 1'-0" SHEARWALL SCHEDULE (NOT ALL USED ON PLANS) MARK SHEATHING' STUDS AT ABUTTING PANEL EDGES2 PANEL EDGE NAILING3,4 RIM JOIST OR BLOCKING TO TOP PLATE BOTTOM PLATE ATTACHMENT SOLID RIM TJI RIM BOTTOM PLATE TO RIM JOIST BELOW 4 ANCHOR BOLT TO CONCRETE' SILL PLATE AT FOUND. SW1 15/32" CDX PLYWOOD 2x 8d @ 6" oc A35 @ 24"oc 16d @ 6" oc 16d @ Coc 5/8" 0 @ 48"oc 2x SW2 15/32" CDX PLYWOOD 2x 8d @ 4"oc A35 @ 15"oc 16d @ 4"oc 16d @ 4"oc 5/8"0 @ 32"oc 2x SW3 15/32" CDX PLYWOOD 3x 8d @ 3" oc A35 @ 12"oc N/A — USE SOLID RIM 16d @ Yoc 5/8" 0 @ 16"oc 2x SW4 15/32" CDX PLYWOOD 3x 8d @ 2"oc A35 @ 9"oc N/A — USE SOLID RIM 16d @ 2"oc 5/8" 0 @ 12"oc 2x SW5 15/32" CDX PLYWOOD BOTH SIDES 3x 8d @ 3" oc A35 @ 6" oc N/A — USE SOLID RIM (2) ROWS 16d @ 3" oc 5/8" 0 @ 12"oc 3x SW6 15/32" CDX PLYWOOD BOTH SIDES 3x 8d @ 2"oc A35 @ 41/2"oc N/A — USE SOLID RIM (2) ROWS 16d @ 2"oc 5/8"0 @ 12"oc 3x 1. WALL SHEATHING SHALL CONSIST OF APA RATED PLYWOOD WITH SPAN RATING 24/0. ALLOW 1/8" SPACING AT ALL PANEL EDGES AND ENDS OF PANELS. 7/6" APA RATED SHEATHING (OSB) MAY BE USED IN PLACE OF 15/32" CDX. 2. STUDS AT ABUTTING PANEL EDGES MAY CONSIST OF (2)2x STUDS IN PLACE OF 3x STUDS — NAIL (2)2x STUDS TOGETHER WITH BOTTOM PLATE ATTACHMENT NAILING. 3. BLOCK ALL PANEL EDGES W/ 2x4 FLAT, ATTACH W/ PANEL EDGE NAILING. TWO STUDS MINIMUM ARE REQUIRED AT EACH END OF ALL SHEARWALLS. END STUDS SHALL RECEIVE PANEL EDGE NAILING. INTERMEDIATE STUDS SHALL BE 2x STUDS. NAIL SHEATHING TO INTERMEDIATE FRAMING MEMBERS WITH 8d @ 12"oc. 4. 8d NAILS SHALL BE 0.131" DIAMETER x 21/2" (COMMON). 16d NAILS SHALL BE 0.135" DIAMETER x 31/2" (BOX). 5. ANCHORS TO CONCRETE SHALL CONSIST OF CAST —IN —PLACE ANCHOR BOLTS, EXPANSION BOLTS, EPDXY GROUTED ALL —THREADS, OR TITEN HD HEAVY DUTY SCREW ANCHORS. CAST —IN —PLACE ANCHOR BOLTS HAVE A 7" EMBED AND SHALL BE J—BOLTS OR SHALL HAVE A HEX NUT AT THE BOTTOM END. EXPANSION BOLTS SHALL HAVE 5" EMBED AND SHALL NOT BE USED AT STEM WALL LOCATIONS WITH EDGE DISTANCE LESS THAN 5" (INSTEAD, USE EPDXY GROUTED ALL —THREADS OR TITEN HD ANCHORS). EPDXY GROUTED ANCHORS SHALL HAVE 5" EMBED AND 21/2" MIN. EDGE DISTANCE. TITEN HD ANCHORS SHALL HAVE 31/2" EMBED AND 13/4" MIN. EDGE DISTANCE. AT ALL ANCHOR BOLTS, PROVIDE STEEL PLATE WASHERS THAT ARE A MINIMUM OF 0.229" (3 GAUGE) x 3% 3" (SIMPSON BP5/8-3 OR SIMILAR). PLACE BOLTS PER ANCHOR BOLT PLACEMENT DETAIL. SHEARWALL PER PLAN NAILING TO MATCH BOTTOM PLATE NAILING PER SW SCHEDULE SHEARWALL PER PLAN SHEARWALL PE" "' ""' INTERSECTING NON—SHEARWA PANEL EDGE NAILING PER SW SCHEDULE NAILING TO MATCH \BOTTOM PLATE NAILING PER SW SCHEDULE PANEL EDGE NAILING PER SW SCHEDULE "IAT' ING TO MATCH TOM PLATE NAILING SW SCHEDULE EL EDGE NAILING SW SCHEDULE TYPICAL SHEARWALL INTERSECTIONS TYPICAL DOUBLE TOP PLATE 'LAN MULTI —STUD PER PLAN WITH NAILING PER GEN. NOTES TYPICAL MULTIPLE -STUD POST CONSTRUCTION 10 3/4" = 1'-011 11 BLOCKING (OR JOIST) PER FLOOR AND ROOF DETAILS JOISTS PER PLAN (DIR. VARIES) FULL DEPTH BLOCKING (OR RIM AT EXTERIOR) BLOCK ALL PANEL EDGES SILL PLATE PER SW SCHEDULE BOTTOM PLATE NAILING PER SW SCHEDULE TOP PLATE CONNECTION PER SW SCHEDULE PANEL EDGE NAILING PER SW SCHEDULE ANCHOR BOLTS & WASHERS PER SW SCHEDULE r PANEL EDGE NAILING PER SW SCHEDULE a III TYPICAL SHEARWALL SECTI ON 3/4" = 1'-0" (8) 16d @ 4"oc STAGGERED EACH SIDE OF SPLICE (16d @ 12"oc ELSEWHERE) CENTER SPLICE OVER S 6'-0" MIN. BETWEEN SPLICES BLD2021-1590 TYPICAL TOP PLATE SPLICE CONSTRUCTION 3/4" = 1'-0" 12 Harriott Valentine Engineers Inc. 1932 First Avenue, Suite 720 Seattle, Washington 98101-2447 tel 206 624 4760 fax 206 447 6971 www.harriottvalentine.com REVISED PLAN APPROVED CITY OF EDMONDS BUILDING DIVISION ErGtu^f�- Jun 27 2022 APPROVED DATE 4127122 Project Contact Jim Harriott tel 206 778 2990 jharriott@harriottvalentine.com Project Architect Maggie Hanna — WAKEdesign, LLC 1752 NW Market St, #203 Seattle, WA 98107 Project Dunn Residence 315 8th Ave N Edmonds, WA 98020 Issue Date Issue Description 11/10/2021 Permit 02/11/2022 Corrections 02/28/2022 Coordination 1� 4/27/2022 Construction Set A2 Building Department Approval REVISION Jun 08 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Drawing Title STRUCTURAL DETAILS w z w 0 Drawing Number w % S4mO o