REVIEWED BLD2022-0913+STRUCTURAL _Plan+7.11.2022_3.38.38_PM+2981966STRUCTURAL NOTES CODE ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE DRAWINGS, SPECIFICATIONS, AND THE INTERNATIONAL BUILDING CODE (IBC) AS AMENDED BY THE LOCAL JURISDICTION. SPECIFICATIONS AND STANDARDS WHERE REFERENCED ON THE DRAWINGS ARE TO BE THE LATEST EDITION. LATERAL DESIGN LOADS EARTHQUAKE LOADS: SITE CLASS D - DEFAULT SHORT PERIOD SPECTRAL RESPONSE (SDS) 1.023 ONE SECOND SPECTRAL RESPONSE (Spy) 0.520 OCCUPANCY CATEGORY ll SEISMIC IMPORTANCE FACTOR (10 1.00 SEISMIC DESIGN CATEGORY D BASIC SEISMIC FORCE -RESISTING -SYSTEM WOOD S.W. RESPONSE MODIFICATION FACTOR, (R) 6.5 SEISMIC RESPONSE COEFFICIENT (CS) 0.157 WIND LOADS ULT. BASIC WIND SPEED (3 SECOND GUST) 100 MPH EXPOSURE B KZT 1.00 SPECIAL INSPECTION SPECIAL INSPECTION SHALL BE PERFORMED PER CHAPTER 17 OF THE IBC ONLY WHERE REQUIRED BY THE LOCAL JURISDICTION FOR THE FOLLOWING ITEMS: • POST -INSTALLED ANCHOR BOLTS REFER TO IBC SECTION 1705.10 AND 1705.11 FOR ADDITIONAL INSPECTION REQUIREMENTS FOR THE STRUCTURAL COMPONENTS OF THE LATERAL FORCE RESISTING SYSTEM. COORDINATE WITH THE CITY OF BELLEVUE BUILDING INSPECTOR FOR REQUIREMENTS OF SPECIAL INSPECTION OF FIELD INSTALLED POST -INSTALLED CONCRETE EMBEDS PRIOR TO INSTALLATION. ALL INSPECTIONS SHALL BE PERFORMED BYA QUALIFIED TESTING AGENCY DESIGNATED BY THE OWNER. THE ARCHITECT, ENGINEER, AND BUILDING OFFICIAL SHALL BE FURNISHED WITH COPIES OF ALL INSPECTION REPORTS. IF ANY INSPECTION FAILS TO MEET THE REQUIREMENTS OF THE CONTRACT DOCUMENTS, IT SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE DESIGN TEAM. STRUCTURAL OBSERVATION STRUCTURAL OBSERVATION SHALL BE PERFORMED PER CHAPTER 17 OF THE IBC ONLY WHERE REQUIRED BY THE LOCAL JURISDITION. STRUCTURAL OBSERVATION DOES NOT INCLUDE OR WAIVE THE RESPONSIBILITY FOR ANY SPECIAL INSPECTIONS REQUIRED. NOTIFY THE ENGINEER A MINIMUM OF ONE WEEK PRIOR TO THE OBSERVATION. WOOD FRAMING ALL WOOD FRAMING SHALL BE PERFORMED IN ACCORDANCE WITH IBC CHAPTER 23, ANSI/AWC "NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION", AND AITC "TIMBER CONSTRUCTION MANUAL ". SAWN LUMBER SHALL BE IDENTIFIED BY THE GRADE MARK OF AN AGENCY APPROVED BYAN ACCREDITATION BODY COMPLIANT WITH DOC PS 20. ALL GRADES SPECIFIED IN THE STRUCTURAL DRAWINGS ARE MINIMUM STANDARDS AND SHALL BE AS FOLLOWS: • STUDS, PLATES, AND BLOCKING HEM -FIR STUD GRADE • JOISTS DOUG-FIR #2 • 4x OR SMALLER BEAMS AND HEADERS DOUG-FIR #2 • 6x OR LARGER BEAMS AND HEADERS DOUG-FIR #1 • POSTS AND TIMBERS DOUG-FIR #2 WOOD FRAMING SHALL BE KILN -DRIED TO A MAXIMUM MOISTURE CONTENT OF 19%. ALL WOOD IN CONTACT WITH CONCRETE OR MASONRY, OR EXPOSED TO EARTH OR WEATHER SHALL BE PRESSURE TREATED IN ACCORDANCE WITH AWPA STANDARD U1 AND M4 FOR THE SPECIES, PRODUCT, PRESERVATIVE, AND END USE REQUIRED. GLUED LAMINATED TIMBER SHALL BE MANUFACTURED AND IDENTIFIED IN CONFORMANCE WITH ANSI/AITC A190.1 AND ASTM D3737. UNLESS OTHERWISE SPECIFIED, ALL GLUED LAMINATED TIMBERS SHALL BE DOUGLAS FIR SPECIES. SINGLE SPAN BEAMS SHALL BE COMBINATION 24F-V4 AND MULTI -SPAN BEAMS OR BEAMS THAT CANTILEVER SHALL BE COMBINATION 24F-V8. ALL EXPOSED GLULAMS SHALL HAVE AN ADDITIONAL TENSION LAMINATION SUBSTITUTED FOR A CORE LAMINATION ON THE TENSION SIDE OF UNBALANCED 24F-V4 BEAMS AND ON BOTH SIDES OF BALANCED 24F-V8 BEAMS. STRUCTURAL WOOD PANEL SHEATHING USED ON WALLS, FLOORS, OR ROOFS SHALL CONFORM TO THEIR SPECIFIC REQUIREMENTS IN DOC PS 1, DOC PS 2, OR ANSI/APA PRP 210. PLYWOOD SHALL BE GRADE C-D WITH EXTERIOR GLUE. REFER TO IBC SECTIONS 2303.1.4, 2304.6, AND 2304.7 FOR ADDITIONAL COMPLIANCE REQUIREMENTS. PRE -MANUFACTURED JOISTS, BEAMS, AND TRUSSES PRE -MANUFACTURED JOISTS, BEAMS, AND TRUSSES SHALL BE SIZED, SPACED, AND DETAILED TO MATCH THE LOADING AND DIMENSIONAL REQUIREMENTS INDICATED ON THE STRUCTURAL DRAWINGS. TRUSSES SHALL COMPLY WITH IBC 2303.4, I -JOISTS SHALL COMPLY WITH IBC 2303.1.2, AND COMPOSITE BEAMS SHALL COMPLY WITH 2303.1.9. THE MANUFACTURER'S DESIGNER IS RESPONSIBLE FOR CODE COMPLIANCE AND SHALL PROVIDE SHOP DRAWING AND CALCULATION SUBMITTALS AS SPECIFIED. ENGINEER AND BUILDING OFFICIAL APPROVAL IS REQUIRED PRIOR TO FABRICATION OF PRE -MANUFACTURED COMPONENTS. REFER TO THE DESIGN LOADS FOR BASIC STRUCTURAL LOADING REQUIREMENTS. REFER TO THE ARCHITECTURAL, ELECTRICAL, AND MECHANICAL DRAWINGS FOR ADDITIONAL LOADING AND OPENING REQUIREMENTS NOT SPECIFICALLY NOTED ON THE STRUCTURAL DRAWINGS. DEFLECTIONS SHALL NOT EXCEED L/480 FOR LIVE LOADS OR L/360 FOR TOTAL LOADS UNLESS APPROVED IN WRITING BY THE ENGINEER. ALL TRUSSES WITH A DEPTH EQUAL TO OR GREATER THAN 24" SHALL BE DESIGNED FOR A BOTTOM CHORD LIVE LOAD OF 10PSF, NOT APPLIED CONCURRENT WITH THE TOP CHORD LIVE LOAD. PROVIDE TEMPORARY BRACING UNTIL SHEATHING AND PERMANENT BRACING IS INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS. THE MANUFACTURER SHALL PROVIDE ALL SPECIALTY ITEMS REQUIRED FOR A COMPLETE INSTALLATION OF THE SYSTEM (INCLUDING BUT NOT LIMITED TO FULL DEPTH BRIDGING, BLOCKING, WEB STIFFENERS, AND PRODUCT SPECIFIC CONNECTORS. ................................................. The following documentation shall be available on ....................................... E REVIEWEDBY■ site for the building inspector: CITY EDMONDS G DEPARTMENT BUILDING DEPARTMENT; ............................................... x� COE APPROVED ARCHITECTURAL PLAN SET ALL WORK SUBJECT COE APPROVED STRUCTURAL PLAN SET TO FIELD INSPECTION FOR COE REVIEWED CALCULATION PACKET CODE COMPLIANCE ENERGY CREDIT WORKSHEET SITE PLAN REVIEWED ❑ CIVIL PLAN i BY ■ • �: CITY OF EDMONDS ❑ _BUILDING DEPARTMENT - ❑ ...,.,.,.,.,.,.,............................... ■ CITY OF EDMONDS BUILDING DEPARTMENT 2021 1 NAILS, SCREWS, BOLTS, AND CONNECTORS REFER TO THE PLANS, NOTES, SCHEDULES, AND DETAILS FOR ALL NAILING REQUIREMENTS. NAILING NOT SPECIFIED SHALL BE PER IBC TABLE 2304.10.1. ALL NAILS SHALL CONFORM TO THE STANDARD DIMENSIONS OF COMMON NAILS AS DEFINED BY THE NDS AND SHALL MEET THE FOLLOWING MINIMUM GUIDELINES: • 8d = 0. 131 "0 x 2 112" • 10d = 0.148"0 X 3" • 16d = 0.162"0 x 3 1/2" 10d BOX NAILS (0.12870 x 3') MAY BE SUBSTITUTED FOR 8d COMMON NAILS WITH NO CHANGE IN NAIL SPACING. FRAMING MEMBERS MAY BE NAILED WITH 16d SINKERS (0.148"0 x 3 1/4'), BUT ONLY 16d COMMON NAILS SHALL BE USED WHERE 16d NAILS ARE INDICATED IN THE DRAWINGS. OTHER NAILS MAY BE SUBSTITUTED ONLY WITH THE ENGINEER'S APPROVAL PRIOR TO START OF CONSTRUCTION. ALL LAG SCREWS AND BOLTS IN WOOD MEMBERS SHALL CONFORM TO ASTM A307. PROVIDE STANDARD CUT WASHERS UNDER THE HEADS AND NUTS OF ALL LAG SCREWS AND BOLTS BEARING ON WOOD. LEAD HOLES FOR BOLTS SHALL BE PROVIDED AND SHALL BE A MINIMUM OF 1/32" AND A MAXIMUM OF 1/16" LARGER THAN THE BOLT DIAMETER. LEAD HOLES FOR LAG SCREW SHANKAND THREADS SHALL BE PER NDS 12.1.4.2. ALL WOOD CONNECTORS SHALL BE SIMPSON STRONG -TIE OR ENGINEER APPROVED EQUIVALENT. CONNECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS USING THEIR SPECIFIED NUMBER AND SIZE OF FASTENERS. IF STRAPS CONNECT TWO MEMBERS, PLACE 1/2 OF THE NAILS, SCREWS, OR BOLTS INTO EACH MEMBER. ALL NAILS, SCREWS, BOLTS, AND METAL CONNECTORS IN CONTACT WITH PRESSURE TREATED OR FIRE RETARDANT TREATED WOOD SHALL BE HOT DIP GALVANIZED IN ACCORDANCE WITH ASTM A153. WOOD FRAMING GENERAL NOTES SILL PLATES BEARING ON CONCRETE FOUNDATIONS SHALL BE PRESSURE TREATED AND SHALL ATTACH TO THE CONCRETE WITH 1/2"0 ANCHOR BOLTS EMBEDDED 7" MINIMUM. PLACE ANCHORS AT 4'-0" OC MAXIMUM FOR SHEAR WALLS AND AT 6'-0" OC FORBEARING AND PARTITION WALLS. USE A MINIMUM OF (2) ANCHOR BOLTS PER SILL PLATE AND PLACE ONE WITHIN 12" OF EACH END OF EACH PIECE. REFER TO THE SHEAR WALL SCHEDULE FOR MORE STRINGENT ANCHORAGE SIZE AND SPACING REQUIREMENTS. CONTRACTOR SHALL INSTALL 3 GAUGE PLATE WASHERS BENEATH EACH NUT AT EACH ANCHOR BOLT IN A SHEAR WALL THAT EXTEND TO WITHIN 1/2" OF SHEATHED EDGE. ALL SHEAR AND/OR BEARING WALLS SHALL BE FRAMED WITH 2x STUDS cr 16" OC. REFER TO PLAN NOTES FOR TYPICAL HEADER SIZES NOT SPECIFICALLY CALLED OUT. ALL HEADERS SHALL BE SUPPORTED BYA MINIMUM OF (1) CRIPPLE AND (1) FULL HEIGHT STUD. COLUMNS BELOW FLUSH FRAMED MULTIPLE JOIST BEAMS SHALL BE EQUAL IN WIDTH TO THE BEAM. ALL COLUMNS NOT CALLED OUT SHALL BE (2) STUDS. BEAMS SHALL HAVE FULL BEARING ON COLUMNS AND POSITIVE CONNECTION SHALL BE PROVIDED. PROVIDE SOLID BLOCKING BETWEEN JOISTS AND RAFTERS AT ALL SUPPORTS, AT 8'-0" OC MAXIMUM SPACING BETWEEN SUPPORTS, AND BENEATH PARTITIONS PERPENDICULAR TO THE DIRECTION OF FRAMING. INSTALL DOUBLE JOISTS UNDER PARTITIONS EXTENDING ONE HALF OR MORE OF THE JOIST SPAN. MINIMUM NAILING REQUIREMENTS SHALL BE PER IBC TABLE 2304.10.1. THE USE OF NAIL GUNS IS APPROVED IF NAILING INTO THE DIAPHRAGMS IS FLUSH WITH FACE OF SHEATHING. NAIL PENETRATIONS GREATER THAN 1/16" ARE NOT ACCEPTABLE. NOTCHES AND HOLES IN WALL STUDS ARE ALLOWED WITHIN THE PARAMETERS OF IBC SECTIONS 2308.5.9 AND 2308.5.10. NOTCHES AND HOLES IN JOISTS AND RAFTERS ARE ALLOWED WITHIN THE PARAMETERS OF IBC SECTIONS 2308.4.2 AND 2308.7.4. VERTICAL SHRINKAGE WILL OCCUR AND ACCUMULATE AT EACH LEVEL FROM THE WOOD DRYING OVER TIME. THIS IS ESTIMATED TO BE APPROXIMATELY 0.15" PER FLOOR AND ASSUMES THE WOOD HAS AN INITIAL MOISTURE CONTENT OF 19% OR LESS. ADDITIONAL SHRINKAGE WILL OCCUR IF THE MOISTURE CONTENT IS HIGHER. THE CONTRACTOR SHALL ALLOW FOR THIS MOVEMENT IN THEIR INSTALLATION OF ALL VERTICAL ASSEMBLIES INCLUDING BUT NOT LIMITED TO PLUMBING, ELECTRICAL, MECHANICAL, AND ARCHITECTURAL SYSTEMS. GENERAL NOTES STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE ARCHITECTURAL, CIVIL, ELECTRICAL, AND MECHANICAL DRAWINGS FOR BIDDING AND CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FOR ELEVATIONS, SLOPES, NON -BEARING WALLS, STAIRS, CURBS, DRAINS, RAILINGS, WATERPROOFING, FINISHES, ETC. REFER TO THE ARCHITECTURAL, CIVIL, ELECTRICAL, AND MECHANICAL DRAWINGS FOR SIZE AND LOCATION OF PIPES, VENTS, DUCTS, AND OTHER OPENINGS NOT SPECIFICALLY INDICATED ON THE STRUCTURAL DRAWINGS. CONTRACTOR SHALL VERIFYALL DIMENSIONS AND FIELD CONDITIONS FOR COMPATIBILITY WITH THE PLANS, SPECIFICATIONS, AND REFERENCED STANDARDS BEFORE PROCEEDING WITH ANY WORK. THE MOST STRINGENT REQUIREMENT SHALL GOVERN ANY CONFLICT UNLESS APPROVED IN WRITING OTHERWISE. ALL DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE DESIGN TEAM BEFORE PROCEEDING. CONTRACTOR SHALL BE RESPONSIBLE FOR STRENGTH AND STABILITY OF ANY PARTLY COMPLETED STRUCTURE. CONTRACTOR IS SOLELY RESPONSIBLE FOR JOB SITE SAFETY AND SHALL PROVIDE TEMPORARY SHORING AND SUPPORT AS REQUIRED UNTIL THE STRUCTURE HAS BEEN COMPLETED. CONTRACTOR INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO THE DESIGN TEAM FOR APPROVAL PRIOR TO FABRICATION OR CONSTRUCTION. CHANGES ON SHOP DRAWINGS DO NOT SATISFY THIS REQUIREMENT. REVIEW OF ALTERNATE SYSTEMS MAYBE AN ADDITIONAL SERVICE BY THE ENGINEER. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE NOT SPECIFICALLY INDICATED BUT ARE OF A SIMILAR CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS OF CONSTRUCTION SHALL BE USED, SUBJECT TO REVIEW AND APPROVAL BY THE DESIGN TEAM. STUD FRAMING PER PLAN OR NOTES. SHEATHING & NAILING, PER SW SCHEDULE PANEL EDGE NAILING PER SW SCHED TYP Ca BOT & SILL PL EXIST SILL PL W/ANCHOR BOLT SIZE AND SPACING PER STRUCTURAL NOTES, PLANS, OR SW SCHED FINISHED GRADE SLOPED AWAY FROM BLDG PER ARCH TE NAILING PER ED PTH BLKG AT ALL IS & HOLDOWN JOISTS \1 A35 Ca 4'-0" OC FEM WALL & a PER PLAN BEARING FOUNDATION DETAIL SCALE: 1 " = 1 '-0" FjA r� a HOLDOWN CHORD & NAILING PER SCHED FULL DEPTH BLKG AT ALL COLUMNS & HOLDOWN CHORDS EXIST 2x JOISTS GENTLY BEND STRAP TO LAP INSIDE OF STEM WALL ANCHORAGE PER HOLDOWN SCHED EXIST STEM WALL & FOOTING PER PLAN HOEDOWN DETAIL SHEAR WALL SCHEDULE MIN FRAMING NAILING RIM JOIST SILL PLATE SILL PLATE FOUNDATION SHEAR TYPE APA-RATED AT ADJOINING AT PANEL OR BLOCK NAILING TO ANCHOR BOLT TO SILL PLATE CAPACITY SHEATHING PANEL EDGES EDGES CONN TO RIM/BLKG SLAB OR SIZE (PLF) TOP PLATE BELOW FOUNDATION SW6 15/32" 2x STUD 0.131 "O x 2 1/2" LTP4 OR A35 0.131 "O x 3 1/4" 1/2"O AB Cad 3'-10" OC OR 2x 242 ONE SIDE AND BLKG Ca 6" OC Ca 26" OC Cad 6.5" OC URFP-SDS Cad 6'-4" OC SW4 15/32" 2x STUD 0.131 "O x 2 1/2" LTP4 OR A35 0.131 "O x 3 1/4" 1/2"0 AB 0 2'-8" OC OR 2x 353 ONE SIDE AND BLKG Cad 4" OC Cad 18" OC Cad 4.5" OC URFP-SDS Cad 4'-3" OC NOTES.- 1. REFER TO THE SHEAR WALL DETAIL IN THE TYPICAL WOOD FRAMING DETAILS. 2. THE VALUES IN THIS TABLE ARE BASED ON HF GRADE STUDS AND HF GRADE PLATES & RIM/BLOCKING. 3. NAILS AT ADJOINING PANEL EDGES SHALL BE STAGGERED EACH SIDE OF THE COMMON JOINT. 4. INTERMEDIATE FRAMING TO BE WITH 2x MINIMUM MEMBERS. FIELD NAILING 12" OC MAXIMUM. 5. AT ALL SILL PLATE ANCHOR BOLTS IN 2x6 WALLS, INSTALL 3 GA x 3" x 4 1/2" PLATE WASHERS WITH THE EDGE OF PLATE WASHER WITHIN 1/2" OF SHEATHED EDGE. FOR 2x4 STUD WALLS, INSTALL 3 GA. x 3" x 3" PLATE WASHERS. 6. PROVIDE A MINIMUM OF 7" EMBEDMENT FOR AB INTO FOUNDATION OR STEM WALL. PROVIDE 6" MIN. EMBED W/ SIMPSON SET-XP EPDXY IF POST INSTALLED UNO. 7. 7/16" SHEATHING MAY BE USED IN PLACE OF 15/32" SHEATHING PROVIDED ALL STUDS ARE SPACED 16" OC OR PANELS ARE APPLIED WITH LONG DIMENSION ACROSS STUDS. HOLDOWN & FASTENERS PER PLAN & SCHED FILL JOIST SPACE WITH BLKG TO MATCH TOTAL WIDTH OF STUD COLUMN ABOVE FLOOR FRAMING PER PLAN ADDITIONAL TRIMMER STUD WHERE READ AT FACE OF OPENING FULL HEIGHT CHORD PER HOLDOWN SCHED. SISTER TOGETHER PER TYP BUILT-UP STUD DETAIL CONT 2x RIM BOARD 10 4" OC EA BLOCK 10d END NAILS EA END 4 BLOCK G Ca 4' 0" TO I DEPTH & GRADE ST FRAMING _JN A35 EACH BLOCK NOTE: REFER TO BEARING FOUNDATION AT CRAWLSPACE DETAIL FOR INFORMATION NOT SPECIFICALLY CALLED OUT. NON -BEARING FOUNDATION DETAIL SCALE: 1 " = 1 '-0" SHEAR WALL W/ SHEATHING NOT HOLDOWN, FASTENERS, & SHOWN FOR CLARITY. CHORD PER PLAN & SCHED. CENTER HOLDOWN SO AN EQUAL NUMBER OF NAILS ARE DRIVEN INTO STUDS & BEAM. •I• FILL JOIST SPACE WITH BLKG • I TO MATCH TOTAL WIDTH OF •40• STUD COLUMN ABOVE FLOOR LEVEL HOEDOWN DETAILS SCALE: 1 "= Y-0" 0 HEADER PER PLAN HOLDOWN AT BEAM END CENTERED Cad BOT OF BEAM. IF STRAP IS TOO LONG TO • BE CENTERED, PLACE TOP OF STRAP AT I' TOP OF BEAM. JACK STUDS EQUAL TO HOLDOWN CHORD ABOVE, (2) STUDS MIN. REFER TO TYPICAL BUILT UP STUD COLUMN DETAIL FOR FASTENING REQUIREMENTS BETWEEN JACK & FULL HEIGHT STUDS HOEDOWN SCHEDULE MIN ANCHOR CAPACITY MARK TYPE CHORD STUD NAILS OR BOLTS BOLT (SEE (LB) SIZE NOTE 2) 1 MST37 (2) 2x (11) 16d EA END - 2,345 2 DTT2Z-SDS (2)2x (8) 1/4"x21/2"SDS 1/2"0 1,841 (16) 16d ONE END W/ (3) 1/2" O x 3 MST48 (2) 2x 3.5" TITEN HD ANCHORS INTO - 3,745 STEM (NOTE 5) (19) 16d ONE END W/ (4) 1/2" O x 4 MST60 (2) 2x 3.5" TITEN HD ANCHORS INTO 4,830 STEM (NOTE 5) NOTES: 1. REFER TO THE LATEST SIMPSON STRONG -TIE CATALOG FOR ADDITIONAL INSTALLATION REQUIREMENTS. 2. ANCHOR BOLTS SHALL EXTEND INTO FOOTING OR FOUNDATION WALL PER DETAIL 6/S3.1. USE PABX-12 ANCHORS AT INTERIOR FOOTINGS AND PABX-24 ANCHORS EXTENDING THRU THE STEM AT EXTERIOR FOOTINGS. INCREASE FOOTING DEPTHS AS REQUIRED FOR ANCHORAGE. 3. AT ALL HOLDOWN CHORDS, PROVIDE PANEL EDGE NAILING PER SHEAR WALL SCHED. 4. POST INSTALLED HOLDOWN ANCHOR BOLTS SHALL EXTEND A MINIMUM OF 12" INTO FOOTING OR FOUNDATION WALL WITH SIMPSON SET-XP EPDXY OR APPROVED EQUIVALENT. 5. FOUNDATION LEVEL MST48 AND MST60 STRAPS SHALL OVERLAP SIDE OF STEM WALL. FIRST ANCHOR SHALL BE 6" MIN DOWN FROM TOP OF STEM WALL. BLD2022-0913 � Z o 0 a 1--1 � o W W C\1 Z W o c �• I■■U Q) • 3 3 3 V Q) O ~ Q) W � Q O Mo N O OI11 W V U LU O cic A • 8 �F WAS$ o ff,` Ls sIONAL 07/08/22 REV. DATE DESCRIPTION 0 07108122 PERMIT SUBMITTAL PROJECT NO.: 22061.01 DESIGNED BY JMD DRAWN BY.- JMD CHECKED BY: CAB SHEET TITLE: STRUCTURAL NOTES & DETAILS SHEET NO.: S1.1 RECEIVED Jul 12 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT