FIR2020-0111+Fire_Alarm_Plan+12.15.2020_11.47.26_AML 4 D L 0 C U E F G ■ 1 GENERAL SYSTEM NOTES PANEL: 1. THE FIRE ALARM CONTROL PANEL (FACP) IS TO BE MOUNTED TO THE SURFACE. THE TOP OF THE PANEL SHALL NOT EXCEED 6 FEET ABOVE FINISHED FLOOR SURFACE. A MINIMUM CLEARANCE OF 36" WORKING SPACE SHALL BE MAINTAINED. 2. THE SUPPLEMENTAL NOTIFICATION APPLIANCE CONTROL PANEL (SNAC) IS TO BE MOUNTED SURFACE, BESIDE THE FACP. THE TOP OF THE PANEL SHALL NOT EXCEED 6 FEET ABOVE FINISHED FLOOR SURFACE. A MINIMUM CLEARANCE OF 36" WORKING SPACE SHALL BE MAINTAINED. 3. THE SNAC IS TO BE POWERED BY THE SAME DEDICATED 120 VAC CIRCUIT AS THE FACP. TWO CONDUCTORS TO 120 VAC, ONE CONDUCTOR TO ISOLATED GROUND, 20 AMP DEDICATED CIRCUIT. A HOUSE GROUND WILL NOT BE ACCEPTABLE. 4. NEITHER THE BOTTOM OF THE FACP NOR THE SNAC SHALL BE PENETRATED. DEVICES: 1. ALL MANUAL PULL STATIONS SHALL HAVE THE TOP OF THE STATION AT 48 INCHES ABOVE THE FINISHED FLOOR. 2. ALL SIGNALING DEVICES SHALL HAVE THE BOTTOM OF THE DEVICE PLACED AT 80 INCHES ABOVE FINISHED FLOOR WITHIN THE SPACE, OR THE TOP OF THE DEVICE 6 INCHES BELOW THE CEILING, WHICHEVER IS LOWER. 3. THE AUDIBLE DEVICES SIGNAL SHALL BE SET TO THE TEMPORAL SETTING. 4. ALL DEVICES ARE TO BE LOCATED PER THE DRAWINGS. 5. WHEN APPLICABLE, VERIFY WITH MECHANICAL CONTRACTOR THE EXISTENCE AND LOCATION OF ALL MOTORIZED SMOKE DAMPERS. THESE ARE TO BE 120 VAC DEVICES ON AS FEW CIRCUITS AS POSSIBLE. THESE DEVICE CIRCUITS ARE TO BE CONTROLLED BY THE FACP THROUGH AN INTERFACING RELAY. 6. WHEN APPLICABLE, VERIFY WITH SPRINKLER CONTRACTOR ALL LOCATIONS OF THE SPRINKLER WATERFLOW, DRY FLOW, HI/LO AIR, TAMPER SWITCHES AND PIV OR 0, S, & Y VALVES. 7. WHEN APPLICABLE, VERIFY WITH SPRINKLER CONTRACTOR THE EXISTENCE OF SPRINKLER HEAT TAPE. THIS HEAT TAPE SHALL BE MONITORED BY THE FACP AND SHALL REQUIRE AN APPROPRIATE RELAY THAT WILL PROVIDE SUPERVISION FOR HEAT TAPE GROUND FAULTS AND LOSS OF PRIMARY POWER. 8. WHEN APPLICABLE, VERIFY WITH SPRINKLER CONTRACTOR THAT ALL APPLICABLE INTERSTITIAL CEILING, ATTIC, OR FLOOR SPACES ARE PROTECTED WITH SPRINKLER HEADS. 9. ALL SPRINKLER WATERFLOW ZONES SHALL BE NON-SILENCEABLE PER U.L. 864. THE CONDITION MUST BE RETURNED TO A NORMAL CONDITION BEFORE THE FACP CAN BE SILENCED. WIRING: 1. TWO DEDICATED PHONE LINES TO BE INSTALLED BY OWNER TO TRANSMITTER. 2. ALL AUDIBLE / VISUAL CIRCUITS ARE TO BE 14 AWG FPL WIRE. (RISER OR PLENUM RATED WIRE WHERE REQUIRED PER NEC). 3. AUDIBLE / VISUAL CIRCUITS ARE TO HAVE AN END OF LINE RESISTOR (ELR) AS APPROPRIATE WITH THE FACP / SNAC. 4. THE DETECTION COMMUNICATION LOOP IS TO BE 16 AWG TWISTED, NON -SHIELDED, MID -CAP FPL WIRE. (RISER OR PLENUM RATED WIRE WHERE REQUIRED PER NEC). 5. THE DETECTION COMMUNICATION LOOP DOES NOT REQUIRE AN ELR AT THE END OF THE CIRCUIT. 6. WIRE TO WEATHERPROOF DEVICES SHALL BE STUBBED OUT ONLY. SURFACE WEATHERPROOF BACK BOXES SHALL BE PROVIDED WITH DEVICES. 7. ALL FIRE ALARM WIRES ARE REQUIRED TO BE IDENTIFIED AND APPROPRIATELY MARKED. 8. PER NEC, NO AC VOLTAGE WIRING OF ANY KIND SHALL BE RUN IN THE SAME CONDUIT OR RISER AS THE LOW VOLTAGE FIRE ALARM SYSTEM WIRING. 9. ALL JACKETED CABLE MUST INCLUDE A JACKET REMOVAL PULL STRING AS PART OF THE CABLE. 10. SHIELDED CABLE IS NOT AN ACCEPTABLE SUBSTITUTION FOR CABLE WITHOUT "SHIELDED" AS PART OF THE DESCRIPTION. GENERAL: 1. ALL FIRE ALARM JUNCTION BOXES ARE TO BE PAINTED RED. 2. ALL END OF LINE DEVICES SHALL HAVE AN IDENTIFYING E.O.L. STICKER AT THE E.O.L. LOCATION. 3. ONLY CONDUCTORS INTENDED FOR TERMINATION TO THE SPECIFIC DEVICE ON ANY GIVEN JUNCTION BOX SHALL BE LEFT OPEN FOR TERMINATION IN THAT JUNCTION BOX. ALL OTHER CONDUCTORS SHALL PASS THROUGH, OR BE SPLICED THROUGH, THAT JUNCTION BOX. WARRANTY ALL EQUIPMENT AND LABOR PROVIDED BY ABSCO SOLUTIONS, INC. HAS A WARRANTY OF ONE YEAR FROM DATE OF INVOICE. THIS WARRANTY EXCLUDES ALL COVERAGE FOR CONSEQUENTIAL DAMAGES, AND IS GIVEN IN LIEU OF ALL OTHER EXPRESS WARRANTIES OR IMPLIED WARRANTIES OF FITNESS, HABITABILITY, OR MERCHANTABILITY OTHERWISE PROVIDED UNDER THE LAWS OF WASHINGTON. ANY WARRANTY WORK PERFORMED BY ABSCO SOLUTIONS, INC. DOES NOT EXTEND THE WARRANTY OF ONE YEAR FROM THE DATE OF THE INVOICE. THIS WARRANTY SHALL BE VOID IF A PERSON OR FIRM OTHER THAN ABSCO SOLUTIONS, INC. OR THE CONTRACTOR AUTHORIZED BY ABSCO SOLUTIONS, INC. PERFORMS OR RE -PERFORMS ANY WORK IDENTIFIED WITHIN THE ORIGINAL SCOPE OF THE WORK OF THE CONTRACT WITH ABSCO SOLUTIONS, INC. LEGAL NOTICE: THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF ABSCO SOLUTIONS, INC. ANY REPRODUCTION IN PART OR IN WHOLE WITHOUT THE WRITTEN PERMISSION OF ABSCO SOLUTIONS, INC. IS PROHIBITED. PATENT RIGHTS (WHERE APPLICABLE) COPYRIGHTS AND ALL OTHER PROPRIETARY RIGHTS ARE EXPRESSLY RESERVED BY ABSCO SOLUTIONS, INC. VICINITY MAP Main Si Main St Mail, �i & Country vTown coMarkets Edmonds... Q 3tarbucks s Takeout Deliver, �E M Q AVery Taki 105 TIM Bar&Grill V ® takeout Glazed&Amazed ® A Pottery store �7 Fire&The Feast sse N oy � 518 M cn vEdmonds Bookshop Dekvery Pub ancial Group ©T kemams 115 Iced Twig Cafe and Bakery oga-Edmonds Takeout. Delivery Edmonds Masonic Temple ® Masonic Lodge 509 ® edmonds lodge no. 165 11J Anchor Chic Consignment �511Dayton St Dayton st Dayton St Dayton St TYPICAL MOUNTING HEIGHTS FINISHED CEILING WALL MOUNT CEILING MOUNT CEILING MOUNT -STROBE -HORN STROBE -SMOKE DETECTOR -HORN STROBE -HEAT DETECTOR -WP HORN STROBE CONTROL MANUAL FARA PANEL PULL STATION 80" 60" 48" 60" FINISHED FLOOR Approved by Fire 12/28/2020 AFM l<_/_F�tt-erer Approved with signs at exterior entrance to FACP and Knox type key box at same entrance. Need exterior horn -strobe at FACP exterior entrance. DEVICE LEGEND MANUFACTURER MODEL NUMBER DESCRIPTION BACK BOX SYMBOL QUANTITY GAMEWELL-FCI GWF-7075 ADDRESSABLE FIRE ALARM CONTROL PANEL PROVIDED FACP 1 GAMEWELL-FCI HPFF8 NAC EXPANDER POWER SUPPLY - 24VDC8 8 AMPS PROVIDED NAC 1 GAMEWELL-FCI OORA-1000R FIRE ALARM REMOTE ANNUNCIATOR PROVIDED FF—AR-A-1 1 SYSTEM SENSOR SWL WALL MOUNT STOBE, WHITE DOUBLE GANG ® 6 GAMEWELL-FCI P2WL WALL MOUNT HORN STROBE, WHITE DOUBLE GANG X� 23 SYSTEM SENSOR P2RK WALL MOUNT HORN STROBE, 12/24V, RED OUTDOOR INCLUDES BACKBOX DOUBLE GANG X�WP 1 SYSTEM SENSOR PC2WL CEILING MOUNT HORN STROBE, WHITE DOUBLE GANG + 2 GAMEWELL-FCI ASD-PL3-IV ANALOG PHOTOELECTRONIC SENSOR, VELOCITI/CLIP, IVORY COLOR WITH B300-6-IV B300-6-IV/4SQR W/ 3-0 RING 02 1 GAMEWELL-FCI ATD-L3R-IV THERMAL SENSOR RATE OF RISE 15 135, VELOCITI CLIP IVORY COLOR WITH B300-6-IV B300-6-IV/4SQR W/ 3-0 RING 35 GAMEWELL-FCI MS-7AF ADDRESSABLE DOUBLE ACTION PULL STATION DEEP 4-SQR 0 3 GAMEWELL-FCI AMM-2F ADDRESSABLE MONITOR MODULE DEEP 4-SQR 161 2 GRI 733919 GRI 195-12WG-W DPDT 3/4", WHITE RECESSED N 1 BY OTHERS BY OTHERS 4-SQR JUNCTION BOX PROVIDED Q 3 EXISTING EXISTING EXISTING ADDRESSABLE RELAY MODULE EXISTING ®E 1 EXISTING EXISTING EXISTING DUCT DETECTOR EXISTING � 1 EXISTING EXISTING EXISTING KEY OPERATED REMOTE TEST STATION EXISTING ,� E 1 WIRE LEGEND ABSCO DESIGNATION DESCRIPTION MANUFACTURER MODEL NUMBER MODEL NUMBER PLENUM MODEL NUMBER BURIAL A 16/2 SOLID FPLR, NON -SHIELDED BY OTHERS BY OTHERS B 14/2 SOLID FPLR, NON -SHIELDED BY OTHERS BY OTHERS P PROTECTOWIRE, REGULAR, RED, 155 DEGREE, 1' PROTECTOWIRE PHSC-155-EPC GENERAL SYSTEM LEGEND NOTIFICATION DEVICE ID INITIATING DEVICE ID WIRE ID ABBREVIATIONS REFERENCE WIRE LEGEND-ABSCO DESIGNATION E = EXISTING 111-5 1_200 N = NEW NOTIFICATION I RR = REMOVE & RELOCATE DEVICE CIRCUIT# DEVICE# WIRE ID QTY OF WIRE MULTIPLE TYPES/QTY W = WIRELESS NOTIFICATION DEVICE# cd = CANDELA RATING DEVICE TYPE "S"ENSOR C 2C 2C,26 � mA = MILLIAMPS V = ELR VOLTAGE END OF LINE LOOP# "M"ODULE = TFA= TO FLOOR ABOVE TFB= TO FLOOR BELOW PROJECT NOTES • TECHNICIAN TO AS -BUILD DEVICE ADDRESSES • INSTALL PULL STATION (1-1,M20) NEXT TO FACP PANEL • AMBIENT TEMPERATURE 701 IN ALL SPACES • AMBIENT SOUND LEVEL >40DB IN ALL SPACES SEQUENCE OF OPERATIONS Output Activated Alarm Device General Notification - Alarm Horn + Horn Strobe + Strobe Transmit Alarm* Transmit Supevsory* Transmit Trouble* HVAC Shutdown Keypad Annunciator Smoke Detector X X X Heat Detector X X X ProtectoWire X X X Manual Pull Station X X X Duct Detector X X X FACP Alarm X X X FACP Supervisory X X FACP Panel Trouble X X IF R2020-0111 RECEIVED Dec 15 2020 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Firm Name and Address QlAbsco olutions P.O. BOX 2246 LYNNWOOD, WA 98036 PH: 425.771.1166 FAX: 425.771 .4422 www.abscosolutions.com Project Name and Address U LEGAL NOTICE: THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF ABSCO SOLUTIONS, INC. ANY REPRODUCTION IN PART OR IN WHOLE WITHOUT THE WRITTEN PERMISSION OF ABSCO SOLUTIONS, INC. IS PROHIBITED. PATENT RIGHTS (WHERE APPLICABLE) COPYRIGHTS AND ALL OTHER PROPRIETARY RIGHTS ARE EXPRESSLY RESERVED BY A B S C 0 SOLUTIONS, INC. Designer of Record KEN DAY ABSCO SOLUTIONS, INC. 19023 36TH AVE W STE E LYNNWOOD, WA 98036 PHONE: (425) 771-1166 FAX: (425) 771-4422 EMAIL: KEN.DAY@ABSCOSOLUTIONS.COM NICET: IV # 97083 i.. 1-12/07/20 Submittal Set AP Rev.# -Date Revision By Drawn By A.P. Checked By D.H. Date 1 1 /1 6/20 Project Name EDMONDS MASONIC TEMPLE Project Number 21 267 System Type FIRE ALARM Sheet Name LEGENDS, D ETA LS, EI R E ALARM PLANS 1 L 1 7 A B D E F G H I L 1 3 1 4 1D 1 0 1 I 0 Firm Name and Address 'Q� Absco Solutions P.O. BOX 2246 LYNNWOOD, WA 98036 PH: 425.771.1166 FAX: 425.771 .4422 www.abscosolutions.com Project Name and Address W O W 1 O UZ U 0-� 77 CDQ U � Q � 2 U� 0 Ln77 UZ 7--0 0 L � 0 O W 0 W LEGAL NOTICE: THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF ABSCO SOLUTIONS, INC. ANY REPRODUCTION IN PART OR IN WHOLE WITHOUT THE WRITTEN PERMISSION OF ABSCO SOLUTIONS, INC. IS PROHIBITED. PATENT RIGHTS (WHERE APPLICABLE) COPYRIGHTS AND ALL OTHER PROPRIETARY RIGHTS ARE EXPRESSLY RESERVED BY A B S C 0 SOLUTIONS, INC. Designer of Record KEN DAY ABSCO SOLUTIONS, INC. 19023 36TH AVE W STE E LYNNWOOD, WA 98036 PHONE: (425) 771-1166 FAX: (425) 771-4422 EMAIL: KEN.DAY@ABSCOSOLUTIONS.COM NICET: IV # 97083 i.- Q5— e 1-12/07/20 Submittal Set AP Rev.# —Date Revision By Drawn By Drawn By A.P. Checked By D.H. Date 1 1 /1 6/20 Project Name EDMONDS MASONIC TEMPLE Project Number 21 267 System Type FIRE ALARM Sheet Name FIRE ALARM RISER, BATTERY CALCULATIONS, NOTIFICATION CIRCUIT CALCULATIONS Sheet Number FZ002 Ell/ D 15230 SHEET 2 OF 3 CITY OF EDM ND 1 ? L '7 RDEPARTMETT II13 4410 G 75cd A L1 S34 A STORAGE A A 2B r�------� r----�--7 RESTROOM Ll S32 Ll S35� L1 S33 u RESTROOM X B x15cd B 175cd j B A J 15cd STAIR uPo- S36 16 cd L1 S20 x iC 75cd B TO NAC1— B N1-1 MAIN LEVEL KITCHEN A --- A _ l I 15cd 1 L1 S26 B GAME/ I GREEN ROOM IA w 0) - O J ------------- A I L1 S23 75cd I � — IFL1 M22 N1-13 — A B ELR 1.065mA L1 S22 L1 S21 115CD L-- A— DINING AREA A B A i L1 S20 TFA L1 S28 I I I DISH WASHING L� L1 S31 I A L------L- 30cd B ?'C STORAGE 1AA L .C- — I 110cd HOT WATER TANK ROOM A Loo�ON16 L 1 6:0 BASEMENT LEVEL - FIRE ALARM PLAN SCALE: 1 /8"=1 10" TO NAC 1 CKT. N 1— BASEMENT LEVEL TO NAC1 CKT. N3— ATTIC LEVEL TO 120VAC (BY OTHERS) TO PHONE LINE (BY OTHERS) TO FARA P V W N2-13 ELR. 1.185mA MAIN LEVEL - FIRE ALARM PLAN Gpb SCALE: 1 /8"=1 '0" ATTIC LEVEL - FIRE ALARM PLAN Gpb SCALE: 1 /8"=1 10" RECEIVED Dec 15 2020 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Firm Name and Address 'Q� Absco Solutions P.O. BOX 2246 LYNNWOOD, WA 98036 PH: 425.771.1166 FAX: 425.771 .4422 www.abscosolutions.com Project Name and Address W O W ` N O lJ J � z < 0 � � �o Ln Z U� 0 � o W 0 W LEGAL NOTICE: THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF ABSCO SOLUTIONS, INC. ANY REPRODUCTION IN PART OR IN WHOLE WITHOUT THE WRITTEN PERMISSION OF ABSCO SOLUTIONS, INC. IS PROHIBITED. PATENT RIGHTS (WHERE APPLICABLE) COPYRIGHTS AND ALL OTHER PROPRIETARY RIGHTS ARE EXPRESSLY RESERVED BY A B S C 0 SOLUTIONS, INC. Designer of Record KEN DAY ABSCO SOLUTIONS, INC. 19023 36TH AVE W STE E LYNNWOOD, WA 98036 PHONE: (425) 771-1166 FAX: (425) 771-4422 EMAIL: KEN.DAY@ABSCOSOLUTIONS.COM NICET: IV # 97083 i.- Q5— e 1-12/07/20 Submittal Set AP Rev.# —Date Revision By Drawn By Drawn By A.P. Checked By D.H. Date 1 1 /1 6/20 Project Name EDMONDS MASONIC TEMPLE Project Number 21 267 System Type FIRE ALARM Sheet Name BASEMENT, MAIN & ATTIC LEVEL FIRE ALARM PLAN 1 L r1 Ai 1 7 1 R