DESCRIPTION DATE:
FOR QUESTIONS, CALL THE
Seattle [If fice
Reed Brown
PHONE: (425) 212-5996
EMAIL: reg85@captiveaire.com
1" LAYER OF INSULATI❑N
FACTORY INSTALLED IN
1.00' END STANDOFF MEETS
0" REQUIREMENTS CLEARANCE
TO C❑MBUSTIBLE SURFACES.
INSTALLER MUST C❑NFIRM HOOD IS INSTALLED SUCH
THAT THE SPECIFIED WALL, ACTING AS AN END PANEL,
IS MATED TIGHT TO THE CORRECT END OF HOOD TO
ACHIEVE A REDUCED MINIMUM EXHAUST CFM LISTING,
N❑N-C❑MPLIANCE WILL NULLIFY THE ETL LISTING,
V❑ID THE MANUFACTURER'S WARRANTY, AND HOLD THE
CONTRACTOR LIABLE FOR ANY AND ALL LOSSES, COSTS,
AND EXPENSES RELATED TO THE NON-CONFORMANCE OF
THE MANUFACTURER'S SPECIFIED INSTRUCTI❑N, THE
WALL ACTING AS AN END PANEL MUST EXTEND NO LESS
THAN 20' FROM THE INTERSECTING WALL ON WHICH HOOD
IS MOUNTED AND MUST EXTEND NO LESS THAN 20' UNDER
BOTTOM OF HOOD TO BE ELIGIBLE FOR REDUCED
MINIMUM EXHAUST CFM LISTING,
PATENT NUMBERS
AC-PSP (UNITED STATES) - US PATENT 7963830 B2.
AC-PSP WALL (CANADA) - CA PATENT 2820509.
AC-PSP ISLAND (CANADA) - CA PATENT 2520330,
1' LAYER OF INSULATI❑N FACTORY
INSTALLED IN INTERNAL BACK STANDOFF,
MEETS 0 INCH REQUIREMENTS FOR
CLEARANCE TO C❑MBUSTIBLE SURFACES,
1" LAYER OF INSULATI❑N FACTORY
INSTALLED IN INTERNAL BACK STANDOFF.
MEETS 0 INCH REQUIREMENTS FOR
CLEARANCE TO C❑MBUSTIBLE SURFACES.
1.5" I.P,S, DRAIN DROP
ENGINEER IS RESP❑NSIBLE FOR DRAIN LINE DESIGN BEYOND THE HOOD.
DRAIN LINE MUST BE INSTALLED PER LOCAL CODES, DRAIN LINE MUST
BE SLOPED (MINIMUM % INCH PER FOOT), AV❑ID ANY UNNECESSARY 90
DEGREE TURNS, IF C❑MBINED WITH OTHER DRAIN LINES, THEN PIPE SIZE
SHOULD BE INCREASED ACC❑RDINGLY, P-TRAPS SHOULD NOT BE USED IN
THE GREASE DRAIN LINE AND HEAT TAPE MUST BE USED WHERE DRAIN
LINE IS RUN IN ENVIR❑NMENTS THAT WOULD S❑LIDIFY GREASE.
/ SIZE BUILDING GREASE INTERCEPT❑R ACC❑RDINGLY.
BOTH ENDS
3
3"
15" I 12'
I
15"
15"
12"
1 12 "
15"
418°
016"
016„
4„
0-
O
O
I
U.L. LISTED
ROUND
RECESSED ALLANS❑N
LED FIXTURE AND LED LIGHT.
60"
78'
U.L. LISTED RECESSED ALLANS❑N
ROUND LED FIXTURE AND LED LIGHT,
❑
❑
3/4' .1
C❑NNEC
UTILITY
BY FAC
BOTH E
p 20'
20"
20' 0
20'
20"
20"
CABINET.
rol
.o.
..... 20' 20'
20'
12"-------------T
9"
12"-------
------T
9"
12"-------
------T
9"
12"-------
1
------T 12" -
9"
-----------T
9"
12"- - - - - - - ------T
9"
18"
T
20"
- -----------T2"- - - - - - - ------T2"-------
------�
48'
96„
48„
10 � 10 1L
®0
10"
®0
17 1/4'
34'
-�
33 3/4"
-
34"
-� 33 3/4'
-
34'
16' 0'N❑M./16'
0.00"❑D.
12
43 1/2"
43 1/2"
17'-0.00" OVERALL
LENGTH,
15 1/4" �� 28 3/4" 28 3/4"
PLAN
VIEW — HOOD
#2 Main — Right)
7' 3'N❑M./7' 3.00"❑D.
16'
0.00" LONG 603OND-2—PSP—F
NOTE:
ADDITI❑NAL
HANGING ANGLES PR❑VIDED FOR HOODS 12' AND LONGER,
7'-4.00" OVERALL LENGTH,
PLAN VIEW — HOOD #Main — Left)
7' 3.00" LONG 7830ND-2—PSP—F
.S. (N.P.T.) HOT WATER
FI❑N STUBS ARE PREFIT
F❑RY.
0S
Approved by Fire
03/17/2021 AFM fC_Fttterer
Hood needs to be interconnected into fire alarm
system
Hood needs gas and electrical shunts.
Drawing of approved system and appliances to be
laminated and attached in control box
Complete above for fire final, enter into Tegris fire
reporting system
9MMIYAIQIi
0
0
0
0
0
W,
0
u
s
Q
V)
s
d
O
CLI E
O 0
C d LLJ
DUE: 2/23/2021
ONGX:
4647383
UMN RTB - 85
BE
SOLE:
3/4" = 1 '-0"
MPSTERMWING
RECEIVED
Mar 05 2021
SHEET NO.
IEVSIONS
DESCRIPTION DATE:
FIRE
SYSTEM
NO
TAG
TYPE
SIZE
FLOW
POINTS
INSTALLATI❑N
SYSTEM
L❑CATI❑N ON HOOD
1
CORE PR❑TECTI❑N
0
0
FIRE CABINET RIGHT
RIGHT, HOOD 2
FTPF. .S Y,`'TFAJ PA PT.S' T,T.S T R Y
FIRE
QTY BY
QTY BY
SYSTEM
TAG
KEY NUMBER - PART DESCRIPTI❑N
FACTORY
DIST
NO
34 - 34 - A0019852 24VDC OR 120VAC SINGLE ACTI❑N MANUAL ACTUATI❑N DEVICE (PUSH/PULL
STATI❑N) WITH PR❑TECTIVE COVER, ONE (1) NORMALLY OPEN CONTACT.
1
0
26 - 26 - QSA-3/8 QUIK SEAL - 3/8" (UL),
9
0
16 - 16 - 3070-3/8H-10-SS NOZZLE - CORE PR❑TECTI❑N APPLIANCE COVERAGE NOZZLE (INCLUDES
METAL BLOW OFF CAP, LANYARD, AND CHROME -PLATED PIPE).
11
0
0 - 0 - SLPC❑N-30FT SUPERVISED LOOP C❑NNECTI❑N KIT, C❑NTAINS THE PARTS NEEDED TO
CONNECT THE SUPERVISED LOOP BETWEEN HOODS WITH UPT❑ 29' GAP. KIT C❑NTAINS 32 FEET
1
0
❑F BLACK MG WIRE, 32 FEET OF TAN MG WIRE, 30 FEET OF FLEXIBLE C❑NDUIT, AND TWO 7/8"
CONNECTORS.
0 - 0 - SLPC❑N-03FT SUPERVISED LOOP C❑NNECTI❑N KIT, C❑NTAINS THE PARTS NEEDED To
CONNECT THE SUPERVISED LOOP BETWEEN END TO END HOODS WITH LESS THAN A 2' GAP. KIT
1
0
C❑NTAINS 5 FEET OF BLACK MG WIRE, 5 FEET OF TAN MG WIRE, 3 FEET OF FLEXIBLE C❑NDUIT,
1
AND TWO 7/8" CONNECTORS.
0 - 0 - CBI-107 CHROME PLATED PIPE FITTING 3/8" NPT UNI❑N.
2
0
0 - 0 - CBI-106 CHROME PLATED PIPE FITTING 3/8" NPT 90 DEGREE ELBOW,
2
0
0 - 0 - CBI-104 CHROME PLATED PIPE FITTING 3/8" NPT TEE.
2
0
0 - 0 - CBI-102 CHROME PLATED PIPE FITTING 3/8" NPT 45 DEGREE ELBOW.
2
0
0 - 0 - A0029078 JUNCTI❑N BOX FOR CORE PR❑TECTI❑N MANUAL PULL STATI❑N, 1.5" DEEP
BACK BOX, BLUE.
1
0
0 - 0 - 59361-1/2 2X4 EXTENSI❑N RING.
4
0
0 - 0 - 12-H28021-005-OT-600 DUCT FIRE THERMOSTAT, NO, CLOSE ON TEMP RISE AT 600°F.
2
0
0 - 0 - 12-F28021-005360 DUCT FIRE THERMOSTAT. NO, CLOSE ON TEMP RISE AT 360°F.
2
0
0- 0- 100-BW 2X4 BLANK PLATE FOR J-BOX.
4
1 0
JOB #: 4647383.
JOB NAME: CHARCOAL ART STUDI❑ RESTAURANT - 2020 R1 HOODS,
SYSTEM SIZE: CORE TOTAL FP
HOOD # 1 7' 3,00" LONG x 78"
RISER # 1 SIZE: 0" x 0
HOOD # 2 16' 0,00" LONG x 60"
RISER # 1 SIZE: 0" x 0
RISER # 2 SIZE: 0" x 0".
REQUIRED: 0,
WIDE x 30" HIGH,
WIDE x 30" HIGH,
24V CMF BASIC OFEP=-I\G IfISTF'I.1S:TIONS
CORE PROTECTION FIRE SYSTEM
CORE PROTECTION FIRE SYSTEMS CAN BE INSTALLED FOR HOOD FIRE
PROTECTION, AS WELL AS POLLUTION CONTROL UNIT FIRE PROTECTION. IN THE
EVENT OF A FIRE, OR ON MANUAL ACTUATION CORE PROTECTION IS
ACTIVATED,
IF THE INSTALLED FIRESTAT IN THE AIRSTREAM SENSES A TEMPERATURE HOTTER
THEN ITS INTERNAL SET POINT OR IF THE MANUAL ACTUATION DEVICE IS PUSHED
THE FIRE SYSTEM IS ACTIVATED, IN KITCHEN HOODS AN ELECTRIC WATER
SOLENOID IS ENERGIZED ALLOWING THE FLOW OF WATER TO THE HOOD DUCT
AND PLENUM THROUGH THE SELF CLEANING HOOD SPRAY BAR. AT THE SAME
TIME A SECOND WATER SOLENOID IS ENERGIZED AND ALLOWS THE FLOW OF
WATER TO THE APPLIANCES, SURFACTANT IS CONTINUALLY INJECTED INTO THE
WATER STREAM TO HELP SUPPRESS THE FIRE, IN A POLLUTION CONTROL UNIT,
THIS ELECTRONIC SIGNAL ENERGIZES A SOLENOID ALLOWING THE FLOW OF
WATER INTO THE INDIVIDUALLY PIPED MODULES,
ONCE THE FIRE SYSTEM IS ACTIVATED, A `SIRE SYSTEM ACTIVATED" EIGHT IS
ILLUMINATED ON THE CORE CONTROL PANEL AND AN AUDIBLE ALARM SOUNDS.
FOR KITCHEN HOOD PROTECTION ALL GAS AND ELECTRIC APPLIANCES UNDER
THE HOOD MUST BE ELECTRICALLY INTERLOCKED TO SHUT OFF, THIS IS ACHIEVED
VIA A GAS VALVE RELAY AND/OR A SHUNT TRIP BREAKER. A TIMER IS ALSO
ENERGIZED UPON FIRE SYSTEM ACTIVATION, THE TIMER IS SET FOR 30 MINUTES
AND KEEPS THE WATER SPRAY SYSTEM RUNNING FOR A MINIMUM OF 30 MINUTES,
THIS IS NECESSARY TO HELP EXTINGUISH ALL REMAINING DUCT FIRE POTENTIAL.
THE FIRE SYSTEM IS ELECTRICALLY OPERATED AND THUS REQUIRES A BATTERY
BACKUP SYSTEM. IN THE EVENT OF A LOSS OF ELECTRICAL POWER, ALL GAS
AND ELECTRIC APPLIANCES UNDER THE HOOD MUST BE ELECTRICALLY
INTERLOCKED TO SHUT OFF, THIS IS ACHIEVED VIA A GAS VALVE RELAY AND/OR
A SHUNT TRIP BREAKER, THE BATTERY
BACKUP WILL AUTOMATICALLY ENERGIZE UPON A LOSS OF POWER, THE
BATTERY BACKUP WILL MONITOR THE FIRE SYSTEM CIRCUIT FOR ONE DAY AND BE
ABLE TO OPERATE THE FIRE SYSTEM CIRCUIT FOR A MINIMUM OF 30 MINUTES,
ONCE POWER IS RESTORED, THE BATTERY WILL AUTOMATICALLY RECHARGE,
THERE ARE MULTIPLE ACTIONS REQUIRED TO RESET THE FIRE SYSTEM, FIRST, THE
FIRESTAT MUST BE COOLED TO BELOW ITS INTERNAL SET POINT AND THE MANUAL
ACTUATION DEVICE MUST BE RESET BY TWISTING THE BUTTON IN A CLOCKWISE
DIRECTION, ONCE BOTH OF THESE DEVICES HAVE BEEN RESET, THE TIMER WILL
AUTOMATICALLY STOP THE FIRE SYSTEM ONCE ITS TIME DURATION HAS ENDED.
AN ALTERNATIVE METHOD TO BYPASSING THE TIMER IS TO PRESS THE FIRE SYSTEM
RESET BUTTON ON THE FACE OF THE CORE CONTROL CABINET. THIS WILL DE -
ENERGIZE THE TIMER AND RESET THE SYSTEM, NOTE: THE FIRESTAT MUST BE COOL
AND THE MANUAL ACTUATION DEVICE MUST BE RESET FOR THIS BUTTON TO
WORK,
THE FIRE SYSTEM MUST BE FILLED WITH SURFACTANT AND NOZZLE CAPS MUST BE
REINSTALLED.
AFTER A FIRE, FULL INSPECTION BY A CERTIFIED PROFESSIONAL MUST BE
CONDUCTED PRIOR TO RESTARTING THE FIRE SYSTEM.
0
0
0
MUM
CORE
APPLICATION
SPECIFIC
DETAILS
C
o
cv
SELF CLEANING HOODS
�
o
SELF CLEANING HOOD OPTION IS REQUIRED TO APPLY CORE PROTECTION,
00
HIGH EFFICIENCY, HIGH VELOCITY CARTRIDGE, SOLO, OR COMBO FILTERS ARE
0T)
REQUIRED. IF SUBSTITUTE FILTERS ARE UTILIZED, PRODUCT WARRANTY IS VOID
CLJ
AND THERE IS NO GUARANTEE IN PERFORMANCE.
r-k-1
SOLID FUEL APPLIANCES
o
Q
SOLID FUEL APPLIANCES PRODUCE SPARKS THAT CAN TRAVEL INTO DUCTWORK
THESE APPLIANCES REQUIRE SOLO FILTERS AND AN ADDITIONAL FIRESTAT AT THE
s
DUCT DISCHARGE NEAR THE FAN IF THE DUCTWORK EXCEEDS 10 FEET IN LENGTH
-�
OR CONTAINS HORIZONTAL DUCT RUNS, INDICATE ON DUCTWORK DRAWING
C
WHERE FIRESTAT IS TO BE INSTALLED WITH QUICK SEAL, ALL ADDITIONAL
O
FIRESTATS ARE WIRED INTO THE SUPERVISED LOOP WITH THE FIRST FIRESTAT, DUCT
C�j
SHOULD BE INSULATED PER CODE REQUIREMENTS. IF SUBSTITUTE FILTERS ARE
o
UTILIZED, PRODUCT WARRANTY IS VOID AND THERE IS NO GUARANTEE IN
cd
W
PERFORMANCE. SELF CLEANING HOODS AND ETL LISTED DUCTWORK ARE ALSO
REQUIRED.
DUCT FIRESTATS
A FIRESTAT MUST BE INSTALLED AT 50 FT INTERVALS WHEN THE DUCT LENGTH
EXCEEDS 50 FT.
I`•1f CG'Ti=f1T
ANY DEVIATION FROM ANY ❑F THE MANUFACTURER'S
RECOMMENDATIONS IN THIS DOCUMENT OR THE OPERATION AND
INSTALLATION MANUAL MUST BE APPROVED BY THE OWNER DE THIS
EQUIPMENT AND VOIDS THE WARRANTY AND PERFORMANCE
GUARANTEE OF THIS PRODUCT
DUE: 2/23/2021
ONGX:
4647383
UMN RTB - 85
BE
SOLE:
3/4" = 1 '-0"
MPSTERMWING
RECEIVED
Mar 05 2021
Es SHEET NO.
2
1.5' I.P.S. DRAIN DROP. 1.5' I.P.S. DRAIN DROP I-VSIONS
\
BOTH ENDS. DESCRIPTION I DATE:
� a � 7'
i 7.00"
24.00' 0181- r I t-�- -�
1 I.P.S. CON ONNECTION.
-
3/4 I,P,S, CONNECTION, 3/4 LP , CONNECTION, _ I_
❑ ❑
SLPCON-30FT
KIT O
HOOD # 1 (Main - Left) JOB # 4647383
MODEL: ND-2-PSP-F SIZE: 78'x30' LENGTH; 7' 3'
unnn ronN:T
MINIMUM 24' CLEARANCE 18' DIA.
ABOVE HOOD, REQUIRED HOOD DUCT
FOR MAINTENANCE. 1/4TT+TP1530+CP1325 DUCT NOZZLE.
12.00'�31.50` �31.50'
3070-3/8H-SS10 3070-3/8H-SS10 3070
ADJUST DUCT NOZZLE 5' -1
FROM VERTICAL TO POINT SLIGHTL
TOWARDS BACK OF RISE
EXHAUST RISER.
HANGING ANGLE.
20' CAPTRATE SOLO
FILTER WITH HOOK,
1' LAYER OF INSULATION FACTORY
INSTALLED IN 3' INTERNAL STANDOFF.
MEETS 0 INCH REQUIREMENTS FOR
CLEARANCE TO COMBUSTIBLE SURFACES.
IT IS THE RESPONSIBILITY
OF THE ARCHITECT/OWNER TO
ENSURE THAT THE HOOD CLEARANCE
FROM LIMITED -COMBUSTIBLE
AND COMBUSTIBLE MATERIALS
IS IN COMPLIANCE WITH
LOCAL CODE REQUIREMENTS.
1.5' I.P.S. FINAL DRAIN DROP LOCATION
ALL NECESSARY FITTINGS FROM THE VENTILATOR
TO THE BUILDING WASTE LINE(S), I.E. FLOOR
SINKS, AIR GAPS, OR OTHER DEVICES REQUIRED
BY THE GOVER DRAIN RNING CODES,
BY OTHERS.
ENGDRAIN ERNE MUST BE RESPONSIBLE IS INSTALLED ED PER LOCALE`EdDE" P; YRKEL�aE�HA�
BE SLOPED (MINIMUM W INCH PER FOOT), AVOID ANY UNNECESSARY 90
DEGREE TURNS, IF COMBINED WITH OTHER DRAIN LINES, THEN PIPE SIZE
SHOULD BE INCREASED ACCORDINGLY. P-TRAPS SHOULD NOT BE USED IN
THE GREASE DRAIN LINE AND HEAT TAPE MUST BE USED WHERE DRAIN LINE
IS RUN IN ENVIRONMENTS THAT WOULD SOLIDIFY GREASE.
d
24.00' 016[
ki
I.P.S. CONFECT
SLPC 1-03FT
KIT O 3/4 I.P.S. CONNECTION.
HOOD # 2 (Main - Right) JOB # 4647383
MODEL: ND-2-PSP-F SIZE; 60'x30' LENGTH; 16' 0'
16' DIA.
HOOD DUCT
1/4TT+TP1530+CP1325 DUCT NOZZLE.
E10' 12.00'J7::j 33.6 '
S10 3070-3/81H-SS10
I
0' I 26 01
CC CL'
~QZ
J Z p T
W a..
La E H ~ J Q
W a W U � L.j<
Wvo X o `o 0
W3p�
_ a-p�vx
U 110_J 0_mX
AIM
TOWARD
CENTER
TO APPLIANCE
(30' MIN)
33.60'
0-3/8H-SS10
SECTION VIEW - MODEL 783OND-2-PSP-F
HOOD - # 1
DUCT NOZZLE AND
PLENUM SPRAY BAR LOCATION
O
016'
-S. CONNECT
33.60'
3070-3/8H-SS10
p m
p�
J Z N
4-pxx
p H O J
~ W 0
W H = o
O El,L3.'D
U O_=
16' DIA.
HOOD DUCT
1/4TT+TP1530+CP1325 DUCT NOZZLE.
33.60' � 33.60'
3070-3/8H-SS10 3070-3/8H-SS10
RECESSED ALLANSON ROUND LED FIXTURE AND
I OUTPUT.
ADJUST DUCT NOZZLE 5' -1
FRUM VERTICAL TO POINT SLIGHTL
TOWARDS BACK OF RISE
J FACTORY INSTALLED
: 0 INCH
aRANCE TO COMBUSTIBLE
EXHAUST RISER.
HANGING ANGLE.
rTACHING PLATES.
UPPLY RISER WITH
IOLUME DAMPER.
23.5% OPEN STAINLESS 20' CAPTRATE SOLO
STEEL PERFORATED PANEL. FILTER WITH HOOK.
1' LAYER OF INSULATION FACTORY
INSTALLED IN 3' INTERNAL STANDOFF.
MEETS 0 INCH REQUIREMENTS FOR
CLEARANCE TO COMBUSTIBLE SURFACES.
700,A_a 1.5' WATER CONNECTION
7.00"
;ORE �uc Plenum Cov age DEDICATED WATER LINE
FOR CORE FIRE SYSTEM
30.00-70 PSI OPERATING PRESSURE
125 PSI MAXIMUM STATIC PRESSURE
36.9 GPM MINIMUM
K FACTOR 8.3,
WATER LINE FOR SELF
CLEANING SYSTEM
30-70 PSI OPERATING PRESSURE
125 PSI MAXIMUM STATIC PRESSURE
140 - 170 DEG F
16.3 GPM MINIMUM
K FACTOR 3.6
410110%wr�11� �.I.pilux millm
IMPORTANT,
DEDICATED WATER LINE FOR
SELF CLEANING MUST BE
MIN 45 PSI OPERATING
PRESSURE AT THE
BACKFLOW PREVENTER
INLET TO OVERCOME THE
PRESSURE LOSS DUE TO
FIELD PIPING.
NOZZLE HEIGHT
30-55' FROM
COOKING SURFACE.
E,-�MLIUNTEB
PULL STATION
IN PATH OF
EGRESS TOWARD
KITCHEN
IT IS THE RESPONSIBILITY
OF THE ARCHITECT/OWNER TO
ENSURE THAT THE HOOD CLEARANCE
FROM LIMITED -COMBUSTIBLE
AND COMBUSTIBLE MATERIALS
IS IN COMPLIANCE WITH
LOCAL CODE REQUIREMENTS.
1.5' I.P.S. FINAL DRAIN DROP LOCATION
ALL NECESSARY FITTINGS FROM THE VENTILATOR
TO THE BUILDING WASTE LINE(S), I.E. FLOOR
SINKS, AIR GAPS, OR OTHER DEVICES REQUIRED
BY THE GOVERNING CODES, BY OTHERS.
ENGINEER IS RESPONSIBLE FOR DRAIN LINE DESIGN BEYOND THE HOOD.
DRAIN LINE MUST BE INSTALLED PER LOCAL CODES, DRAIN LINE MUST
BE SLOPED (MINIMUM W INCH PER FOOT), AVOID ANY UNNECESSARY 90
DEGREE TURNS, IF COMBINED WITH OTHER DRAIN LINES, THEN PIPE SIZE
SHOULD BE INCREASED ACCORDINGLY. P-TRAPS SHOULD NOT BE USED IN
THE GREASE DRAIN LINE AND HEAT TAPE MUST BE USED WHERE DRAIN LINE
IS RUN IN ENVIRONMENTS THAT WOULD SOLIDIFY GREASE.
CORE APPLIANCE PIPING WATER FLOW SUMMARY
PIPE
MINIMUM FLOW
PRESSURE DROP
DIAMETER
RATE (GPM)
(PSD
FIELD PIPING BETWEEN ALL
1.5
36.9
0.00
HOOD GROUPS
HOOD INTERNAL PIPING
0.75
16.3
30
SELF CLEANING WATER FLOW SUMMARY
PIPE
DIAMETER
MINIMUM FLOW
RATE (GPM)
PRESSURE DROP
(PSI)
FIELD PIPING BETWEEN ALL
HOOD GROUPS
1.5000
16.3
0
HOOD INTERNAL PIPING
0.75
16.3
30
BACKFLOW PREVENTER
1 1/2'
16.3
15
TOTAL SYSTEM INLET REQUIREMENTS
WATER HEATER
MINIMUM FLOW
MINIMUM
INSTANTANEOUS
RATE (GPM)
PRESSURE (PSI)
DEMAND (MBH)
TOTAL CORE INLET REQUIREMENTS
36.9
30.00
TOTAL SELF-CLEANING INLET REQUIREMENTS
16.3
45
700
■ OPERATING PRESSURE RANGE AT CORE PANEL GAUGE IS 30.00 TO 70 PSI.
MAXIMUM STATIC PRESSURE IS 125 PSI.
■ OPERATING PRESSURE RANGE AT Self Cleaning PANEL GAUGE IS 45 TO 70 PSI.
MAXIMUM STATIC PRESSURE IS 125 PSI.
■ HOT WATER TEMPERATURE RANGE FOR SELF CLEANING 140-170°F.
SECTION VIEW - MODEL 603OND-2-PSP-F
HOOD - #2
DUCT NOZZLE AND
PLENUM SPRAY BAR LOCATION
I ROUND LED FIXTURE AND
WARM OUTPUT.
TTACHING PLATES.
:UPPLY RISER WITH
/OLUME DAMPER.
23.5% OPEN STAINLESS
STEEL PERFORATED PANEL.
NOTES
- FIELD PIPE DROPS AS SHOWN
ELBOWS, TEES, AND NOZZLES SUPPLIED BY CAS.
- RELOCATE NOZZLES IF FLOW PATTERN IS BLOCKED BY SHELVING,
SALAMANDERS, ETC.
- FACTORY PIPING EXTENDS A MAXIMUM OF 6" ABOVE THE TOP OF THE HOOD.
- APPLIANCE DIMENSIONS LISTED REPRESENT THE CO❑KING SURFACE
SIZE, NOT THE OVERALL APPLIANCE SIZE.
- THIS FIRE SYSTEM C❑MPLIES WITH U.L. 300 REQUIREMENTS.
- MINIMUM 24' CLEARANCE ABOVE HOOD, REQUIRED FOR MAINTENANCE.
- CORE / SELF CLEANING (UNITED STATES) - US PATENT 7963282 B2.
CORE / SELF CLEANING (EUROPE) - EP PATENT 2274069 Al.
CORE SUPERVISI❑N - US PATENT 8378834 B1,
CORE ELECTRICAL - US PATENT 8610601 B2.
JOB #: 4647383.
JOB NAME: CHARCOAL ART STUDI❑ RESTAURANT - 2020 R1 HEELS,
SYSTEM SIZE: CORE
HOOD # 1 7' 3.00' LONG x 78' WIDE x 30' HIGH.
RISER # 1 SIZE: 18' DIA.
HOOD # 1 METAL BLOW -OFF CAPS INCLUDED.
HOOD # 2 16' 0.00' LONG x 60' WIDE x 30' HIGH.
RISER # 1 SIZE: 16' DIA.
RISER # 2 SIZE: 16' DIA.
HOOD # 2 METAL BLOW -OFF CAPS INCLUDED.
- S❑LID-FUEL APPLIANCES (EXTRA HEAVY-DUTY RATED 700°F) REQUIRE AN
ADDITIONAL FIRESTAT AT END OF THE EXHAUST DUCT NEAR EXHAUST FAN
IF THE DUCT IS MORE THAN 10 FT LONG OR CONTAINS ANY HORIZONTAL
SECTI❑NS.
- SOLID -FUEL APPLICATI❑NS WHERE THE DUCTWORK EXCEEDS 50 FT IN
LENGTH WILL REQUIRE A THIRD FIRESTAT, MOUNTED IN A SERVICEABLE
L❑CATI❑N, IDEALLY AT THE END OF A H❑RIZ❑NTAL RUN OR TRANSITI❑N.
CONSULT ENGINEERING ON DUCT LENGTHS OVER 100 FT.
- HEAVY-DUTY APPLIANCES (RATED 600°F) WILL REQUIRE AN ADDITI❑NAL
DOWNSTREAM FIRESTAT IN THE EVENT THAT THE DUCTWORK C❑NTAINS ANY
HORIZ❑NTAL RUNS OVER 25 FT IN LENGTH.
- MEDIUM TO LIGHT -DUTY APPLIANCES (RATED 450°F) WILL NOT REQUIRE
ANY ADDITIONAL DOWNSTREAM DETECTI❑N.
Hood # 2
1/4TT+TP1530+CP1325
ADJUST DUCT NOZZLE 5` - 10°
TOWARDS BACK OF RISER.
13' t 1/2'
SPACING
(TYPICAL).
i
i�
1/4TT+TG-4.3W
(TYPICAL FOR ALL
PLENUM NOZZLES).
30' MAX
SPACING
OVER DUCT
v �i II
I I
i
II
II
36'
SPACING
MAX 3070-3/BH-10-SS
(TYPICAL). APPLIANCE PROTECTION NOZZLE
(TYPICAL FOR ALL APPLIANCE
PROTECTION NOZZLES).
NOZZLES FOR CORE PROTECTION
DESCRIPTION PART NUMBER A/X
RISER NOZZLE 1/411 +1 P1530+CP1325 A0002784
SPRAY BAR NOZZLE 1/41111U-4.3W A0025166
APPLIANCE NOZZLE I 3070-3/8H-10-SS A0019145
IS❑METRIC VIEWS ARE FOR GRAPHICAL REPRESENTATION OF TYPICAL NOZZLE
PLACEMENTS AND TYPE. QUANTITIES OF NOZZLES WILL VARY,
+�
0
D
O
W
+�
V
QJ
CD
�
v)
l__J
0
CD
�
CLJ
W
DUE: 2/23/2021
ONGX:
4647383
EFVWN RTB - 85
BE
SOLE:
1/2" = 1 '-0"
MPSTERMWING
RECEIVED
Mar 05 2021
-T-NT Es SHEET NO.
3
JOB NO MODEL NUMBER DRAWN BY SCIIEMAIIC TYPE
4647383 DCV-2111 INSTALL
JOB NAME DATE DWG Na
Charcoal Art Studio Restauran.,. 2/23/2021 ECP #1-3
1
CORE TOTAL FLOOD PROTECTION ELECTRICAL DETAIL
2
ELECTRICIAN:
1, WIRE MAIN CONTROL PANEL PER INCLUDED SCHEMATIC
_
2, WIRE ALL FANS PER INCLUDED SCHEMATIC
3 3. WIRE SHUNT TRIP BREAKER (OPTIONAL)
4, WIRE UDS APPLIANCE KILL SWITCH, IF EQUIPPED (OPTIONAL)
5, WIRE GAS VALVE
4
5
6
7
8
11LSCRIH 11UN UI UH'LKA 11UNI JOB NO MODEL NUMBER DRAWN BY SCHEMATC TYPE I 11L SCK1H' 11UN LIF UHLKA 11UNI
Fire System #1 CORE Protection. 1-1/2' CORE Appliance Manifold Package with Self Cleaning, Installed In Hood Utlllty DCV-2111 INSTALL Fire System #1 CORE Protection. 1-1/2' CORE Appliance Manifold Package with Self Cleaning. Installed in Hood Utlllty
Cabinet with Integral hood prewire panel. 4647383 JOB NAME BATE DWG NO Cabinet with Integral hood prewire panel.
Charcoal Art Studio Restauran... 2/23/2021 ECP #1-4
1
03/06/2017 Rev. 12 CORE TOTAL FLOOD PROTECTION LOW -VOLTAGE DETAIL 03/06/2017 Rev. 12
2
ALARM CUNTRACTORI r
F S- 1: M A S T E R L
2. COMPLETE L ACTUATIONL HOOKUP DEVICES), REMOTE FIRESTAT(S), CORE INTERLOCK(S), FIRE SENSOR(S) AND FIRE ALARM CONTACTS F S- 1: MASTER
3, PERFORM FINAL FIRE SYSTEM TEST
4, FILL SURFACTANT TANK
ELECTRICAL CONTRACTOR REQUIREMENT
ITEM
CONNECTION IN PANEL
CONNECTION IN DEVICE
VOLTAGE
AMPERAGE
COMMENTS
SHUNT TRIP BREAKER (OPTIONAL)
ST & N1
BREAKER COIL
(A1 & A2)
120 VAC
< 4 AMPS
ST TO Al ON SHUNT BREAKER COIL, AND NEUTRAL TO A2 ON SHUNT TRIP BREAKER COIL
CONTROL PANEL POWER
H1 & N1 + GROUND
CIRCUIT BREAKER
120 VAC
15 AMPS
CONTROL PANEL POWER MUST NOT BE RUN THROUGH SHUNT TRIP BREAKER
UDS APPLIANCE KILL SWITCH (OPTIONAL)
KTS & N1
KTS & N1
120 VAC
( 4 AMPS
KILL SWITCH TERMINALS MUST BE IN SERIES WITH OTHER KILL SWITCHES
REMOTE 120VAC ANSUL AUTOMAN (OPTIONAL)
AU1, AU2
SOLENOID
120 VAC
( 6 AMPS
120V TO AU1, AU2 TO ANSUL ELECTRIC AUTOMAN, ANSUL SOLENOID TO NEUTRAL
GAS VALVE
35 & N1D (IF 24 VDC)
GAS & Ni (IF 120 VAC)
RED/RED/GREEN
24 VDC
OR 120 VAC
< 1.0 AMPS
IF 24 VDC - 2 WIRES & GROUND, N1D TO RED, 35 TO RED, AND GREEN TO GROUND
IF 120 VAC - 2 WIRES & GROUND GAS TO RED, Ni TO RED, AND GREEN TO GROUND
9
10
11
12
13
SHUNT TRIP BREAKER (OPTIONAL)
-2 WIRES, 120VAC
14 -ST TO Al ON SHUNT BREAKER
-NEUTRAL TO A2 ON SHUNT TRIP
BREAKER
15
16
17
18 POWER TO ELECTRIC
APPLIANCE
19
— _ CONTROL PANEL POWER
------------� ---- — 2 WIRES & GROUND
-120 VAC, 15 AMP SERVICE
-WIRE TO H1 AND N1, GROUND
FROM -POWER
HUNT MUST NOT
BREAKERTE
EXHAUST HOOD
36 INCHES CLEARANCE REQUIRED IN FRONT
OF ALL UTILITY CABINET DOORS
THE PANEL SHALL ALSO BE LOCATED IN AN
ACCESSIBLE AREA WHERE THE AUDIBLE AND
VISUAL ALARMS CAN BE HEARD AND SEEN
20
_ — — ELECTRIC GAS
21
22
27
23
COOKING
APPLIANCE(S)
24
- NOTE: SEE INSTALLATION, OPERATION, AND MAINTENANCE MANUAL FOR FURTHER INSTRUCTIONS
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
JOB NO MODEL NUMBER DRAWN BY SCHEMATIC TYPE
4647383 DCV-2111 INSTALL
JOB NAME DATE DWG No
Charcoal Art Studio Restauran.,. 2/23/2021 ECP #1-5
CORE TOTAL FLOOD PROTECTION LOW -VOLTAGE FIGURES
USE BELDEN #6320UL
OR SIMILAR WIRE
J2-1 J10-1
J2-2 J10-2 MICROSWITCH/
MANUAL
ACTUATION
FIRE DEVICE
STAT-1 NO-WH BK-C Mk-M DOOR-FBREAK WIRE BK-C (OR RD) BREAK WIRE 1 2BEFORE BEFORE MANUAL
INSERTING INSERTING ACTUATIOINTO FIRE TERMINALS DEVICE
TERMINALS STAT-2 NO-WH BK-C �{� BK-C (OR RID 1 2 OR F
J2-3 J10-3
J2-4 J10-4
WIRING CONNECTIONS WIRING CONNECTIONS
FOR FIRESTAT LOOP FOR MANUAL ACTUATION LOOP
FIGURE 1 FIGURE lA
SHIELDED TWISTED PAIR
=RD
K BK A
RD
WIRING CONNECTIONS
FOR CORE INTERLOCK
FIGURE 3
NOTE: SEE INSTALLATION, OPERATION, AND MAINTENANCE MANUAL FOR FURTHER INSTRUCTIONS
BUILDING
FIRE ALARM CORE
CONTROL
PANEL
TROUBLE CONTACT
TOK TBL NO
TROUBLE
INPUT
TBC
GAS VALVE POWER
-2 WIRES & GROUND
-24 VDC WIRE TO 35 & N1D
-120 VAC WIRE TO GAS & N1
-STRAINER MUST BE
INSTALLED UPSTREAM
OF VALVE
Fire System #1 CORE Protection. 1-1/2' CORE Appliance Manifold Package with Self Cleaning. Installed In Hood Utility
Cabinet with Integral hood prewire panel.
02/05/2015 Rev. 16
ES-1: MASTER
BUILDING CONTROL
FIRE ALARM PANEL
FIRE
ALARM
CONTACT
ALARM AL2 N
INPUT OF
LINE
A DEVICE
WIRING CONNECTIONS FOR FIRE
ALARM CONTACT
FIGURE 2
PRV WATERLINE CORE WATER
SUPERVISION SUPERVISION SHUT-OFF
SWITCH SWITCH SWITCH
0 NC 1
C
WIRING CONNECTIONS FOR
TROUBLE CONTACT
FIGURE 4
4
5
6
7
8
9
10
ALARM CONTRACTOR
REQUIREMENT
ITEM
CONNECTION IN PANEL
CONNECTION ON DEVICE
VOLTAGE
AMPERAGE
COMMENTS
101 AND 104
WIRE MANUAL ACTUATION DEVICE TERMINAL 1 BETWEEN CORE PANEL TERMINALS 102 AND 103
MANUAL ACTUATION DEVICE(S)
102 AND 103
1 & 2
24 VDC
( 1.0 AMPS
WIRE MANUAL ACTUATION DEVICE TERMINAL 2 BETWEEN CORE PANEL TERMINALS 101 AND 104
JUMPER 101 TO 104 AND 102 TO 103 IF NO MANUAL ACTUATION DEVICE IS INSTALLED
MANUAL ACTUATION DEVICE COVER
N/A
N/A
N/A
N/A
MANUAL ACTUATION DEVICE COVER MUST BE INSTALLED
IF SURFACE MOUNTED, USE COVER EXTENSION STI-6531B
REMOTE FIRESTAT SENSOR(S)
21 AND 24
BLACK AND WHITE
24 VDC
( 1,0 AMPS
--WIRE FIRE SENSUR WHIIE WIRES BEIWEEN HUUB LURE HANEL IEKMINALS EE AND E3
WIRE FIRE SENSOR BLACK WIRE BETWEEN HOOD CORE PANEL TERMINALS 21 AND 24
22 AND 23
HIGH TEMP (842°F) #CW04427 (WHT) & #CW04427B (BUOWIRE OR SIMILAR ONLY IF RAN OVER TOP
OF HOODI OTHERWISE BELDEN #6320UL OR SIMILAR PLENUM RATED WIRE! SFF FIGURE I
FIRE ALARM CONTACT
ALL AL2
VARIES
50V MAX
UP TO 1 AMP
FIRE ALARM RELAY CONTACTS FOR BUILDING FIRE ALARM LOCATED IN THE
(AC/DC)
CORE ELECTRICAL CONTROL PANEL
CORE INTERLOCK(S)
ILA, ILB, ILC
ILA, ILB, ILC
RS-485 COMMUNICATIONS
CORE SYSTEM (1) ILA, TO CORE SYSTEM (2) ILA, CORE SYSTEM (1) ILB, TO CORE SYSTEM (2) ILB,
SIGNAL
CORE SYSTEM (1) ILC, TO CORE SYSTEM (2) ILC. USE BELDEN# 88760 OR SIMILAR WIRE
TROUBLE CONTACT
TBC, TBL, TOK
VARIES
MAX 120 VAC
UP TO 6 AMPS
WIRE TO TBL & TBC NORMALLY OPEN CONTACT, CLOSES IN TROUBLE CONDITION
CORE COMMUNICATIONS CABLE
RJ-45 Jack
INTERNET CONNECTION
SIGNAL
0.0 AMPS
TYPICAL CONNECTION CATS CABLE TO LOCAL AREA NETWORK VIA ETHERNET SWITCH OR
WIRELESS ROUTER WITH VALID INTERNET CONNECTION
11
FIRE ALARM CONTACT
-�i� — FIRE ALARM PANEL
CORE INTERLOCK
12
-2 WIRES WIRED TO NORMALLY
-2 WIRES + SHIELD
OPEN CONTACTS (CLOSES IN
f _ _ _
-USE BELDEN#88760 OR SIMILAR WIRE
FIRE CONDITION)
_ _ _ _ _ _ _ — —
I —
—
—
-SEE FIGURE 3
13 -CORE CONTROL PANEL AL1
— — — — —
—
AND AL2
-SEE FIGURE 2
14 TROUBLE CONTACT
�II
-2 WIRES TO NORMALLY
III
CORE COMMUNICATIONS CABLE
OPEN CONTACTS (CLOSE
-CATS CABLE
IN TROUBLE CONDITION)
MUST BE INSTALLED TO A LOCAL AREA
15
-CORE PANEL TERMINALS
NETWORK WITH VALID INTERNET ACCESS
TBL AND TBC
VIA ETHERNET SWITCH OR WIRELESS
- -SEE FIGURE 4
MANUAL I
ROUTER
s
ACTUATION I
DEVICE
SUPERVISED LOOP
EXHAUST HOOD
10 TO 20
17 -4 WIRES, 24VDC CONNECT BLACK
FEET FROM
WIRES BETWEEN 21 AND 24 IN PANEL,
CONNECT WHITE (OR RED) WIRES
HOOD LOCATED
BETWEEN 22 AND 23 IN PANEL
NEAR POINT
18 -ADDITIONAL FIRESTATS, WIRED IN
OF EGRESS I
MANUAL ACTUATION DEVICE WIRES
SUPERVISED LOOP
FROM HOOD
-4 WIRES, 24VDC WIRE (TERMINAL 1)
-USE HIGH TEMP (842°F) #CW04427
BETWEEN 1R2 AND 103
19 (WHT) & #CW04227B (BLK)WIRE ONLY
-WIRE (TERMINAL 2) BETWEEN 101 AND 104
IF RAN OVER TOP OF HOOD;
-ADDITIONAL PULL STATIONS WIRED IN
OTHERWISE BELDEN #6320UL OR
SUPERVISED LOOP
SIMILAR PLENUM RATED WIRE
-USE BELDEN #6320UL OR SIMILAR WIRE
20 -SEE FIGURE 1
-SEE FIGURE 2
42 TO 48 INCHES
ABOVE FLOOR
2t
36 INCHES CLEARANCE REQUIRED IN FRONT
LEVEL TO
MANUAL ACTUATION DEVICE
PART #STI-SS2431
OF ALL UTILITY CABINET DOORS
ELECTRIC GAS
CENTER OF PUSH
PROTECTIVE COVER MUST BE INSTALLED
THE PANEL SHALL ALSO BE LOCATED IN AN
STATION
22 ACCESSIBLE AREA WHERE THE AUDIBLE AND
VISUAL ALARMS CAN BE HEARD AND SEEN
23
COOKING
APPLIANCE(S)
24 ATTENTION: LOW -VOLTAGE DC OR
SIGNALING WIRE SHOULD
- BE ROUTED IN SEPARATE CONDUIT
FROM ALL AC SOURCES
NOTE: SEE INSTALLATION, OPERATION, AND MAINTENANCE
MANUAL FOR FURTHER INSTRUCTIONS
1 CORE APPLIANCE REV 1.8 ONE WH
HN1 BK
16AWG
o 1 PNi 1606-XLP-60EQ
LN1. Adjust power supply to 27.5
PSM-2 60W Volts with an accurate
Digital Volt Meter or with an
HMI plugged into the CORE
+- board.
2
3
4
DR�
Fire Re((
L R 6BKURFACTANT LOW
5 RD
FIRE IN ICATOR pp 0
RD' O IR
LL-1 Audible Alarm
BK BK
Liquid Level Sensor
RD BT-01PK
6 Prime / Reset
RDSW-05-20R
Test a rmed
Wat�er�//Valvea3sinGY
Supervl�Sionwitch
7 q
2 AlY1END RDSW-O BROF Door Tamper Switch
LINE RD-16
C DEVICE RD BL/RD
Hot Water Relay RD-19
RD RD/GN
Equipment Relay
ATTENTION: LOW -VOLTAGE DC OR SIGNALING WIRE SHOULD
BE ROUTED IN SEPARATE CONDUIT FROM ALL AC SOURCES
Auxiliary Interlock Relay
9 To Building Fire
Alarm Panel
FIRE ALARM SYSTEM DRY CONTACTS.
Termials ALI & AL2 make In FIRE.
+ RI
5 AMP FUSE
Q DISCONNECT J1 24 VOLT BATTERY PACK
FOR SHIPMENT + Ii Bk
-2
PCB-2
J3-
Jumper If water valve
supervision switch is used
PK RD RD
24V DC LLJ p Gas Valve
Rt Y11WH
Surfactant Pump
Plenum
Test
ATTENTI❑N: LOW -VOLTAGE DC OR SIGNALING WIRE SHOULD
BE ROUTED IN SEPARATE C❑NDUIT FROM ALL AC SOURCES,
FS-1: MASTER
s HIGH TEMP WIRE (842 F),
PN- SLPCON-.FT required
B� FS-01 I for all Supervised Loop
wiring in contact with a
FIRE STAT SUPERVISED LOOP hood. All other wiring
May be mixed factory and field Stnt shall be PN- 632OUL,
wiring. See Installation Schematic. Fire Belden or similar. Factory
Multiple fire sensors possible. FS-02 mounted hood sensors will
be terminated at junction
box on top of hood.
B J Fire Stat
R -
R� 7 Auxiliary Interlock (AUX-01),
MS-01 Wire AU1 / AU2 of adjacent Master CORE
BK C/ panel(s) in each manual activation loop
for simultaneous activation.
�
MANUAL
Micro - SW AU1/AU2 will have continuity for 10
SYSTEM LOOPATION LOOP / REMOTE FIRE AUX-01 seconds if adjacent panel goes Into fire
Multiple manual actuation possible. LAU, condition, activating this CORE Panel but
A Plug jumper with wires from pinl to djacen allowing for a reset after 10 seconds.
pin4 and from pint to pin3 should be CORE NOTE, AU1/AU2 terminals of CORE Panel
mounted on J10 If there Is no manual
actuation device and no microswltch. Panel should not be wired Into its own manual
�_ activation loop.
BK
Manual
Actuation
RD Device-
CAT-5 WIRING (MASTER ONLY)
J
FEEU WIRED IF REMOTE PREWIRE ECPM03
-PUT END OF LINE PLUG IN EMPTY RJ45
UNLESS VFD, PCU, OR OTHER COMPONENT IN SERIES.
SHIELDED TWISTED PAIR
BK BK CA RS-485 CORE INTERLOCK
NETWORK. Connection to
other CORE Panels or
RD RD CD Communication Module. See
Installation Schematic for
Connection.
Master CORE
DIP Switch totCLIP SW
OSED 8
position. Slave
1 2 3 4 5 6 7 8 CORE with
address 1 set
B DIP 8 to
• O O O • O O • CLOSED
,n position. All
O • • • O • • • other
CORES
OPEN set DIP SW 8
OPEN.
FIRE INDICATOR FAULT CONDITION FLASH CODES
2 CORE Plenum Water Solenoid
3 CORE Appliance Water Solenoid
4 Auxiliary Fault
5 Microcontroller Fault
6 CORE Surfactant Pump
7 Supervised Loop
8 Ground Fault
9 Surfactant Low
10 Battery Voltage Low
11 AC Power Failure
12 Door Tamper Switch
13 Test mode
14 CORE Interlock Network
15 Fault on Hood in Interlock Network
16 Fault on PCU in Interlock Network
GYL G 4WH
WASH I DICATOR
BK 16�AWG RD-16 OR RD -3 WH N1
Hot Water Wash Solenoid
FACTORY WIRING
SCHEMATIC
CORE FIRE
PROTECTION
R 0 VAC 24 @ DC
RELAY RELAY
NO 4 3 NO 4 3
NC 2 1 NC 2 1
COIL 8 7 COIL 8 7
COM 6 5 COM 6 5
PCB-2 CURE PCB
PCBCORE-APP
PSM-2 CURE POWER SUPPL
_ 1606-XLP-50E
WS-x Water Solenoid
-ries LT-06 24VRed Ind. Light
_ PNL-HG3-0UR
LL-01 Surf. Level Sensor
A05510
AA-01 Audible Alarn
_ SCE120LA3FPIB
PB-01 Prine/Reset Switch
D7-F2X11
SW-05 TEST/ARM Switch
ZB5A➢2
SW-04 Tanper Switch
_ BZ-2R01-A2
SP-1 Surfactant Pump
_ 50000-805
GV-1 24v DC Gas Valve
varles
-FS-XX Duct Fire Sensor
_ 12-F28021-000360
LT-05 24V YLW Ind Ligh
_ PNL-1163-OUY
PS-01 R—te Pull Statio
STI-SS2431
-PWS-01 24VDC Power Su l
_ 24VDC 18W POWER
RD-XX 24VDC Phoenix Relay
PLC-RPT-24➢C/21
- -WIIRING
—FIELD
FACTORY WIRING
BK- BLACK YW- YELLOW
BL- BLUE GY- GREY
BR- BROWN PR- PURPLE
OR- ORANGE RD- RED
WH- WHITE GR- GREEN
OR/BL- OR/DL STRIPE
DRY CONTACTS (SHOWN DE-ENGERGIZED)
-
RD- 20 1
BL/RD- FL/RD STRIPE
TROUBLE RELAY. Contact terminals
12 TBC & TBL make If there Is trouble.
RD/GN- RD/GN STRIPE
/BL- WH/BL STRIPE
14 Contact terminals TBC & TOK make IfWH
— 11 YW the system Is ok.
Jar NAME
RD-19-1 COOKING EQUIPMENT DISABLE RELAY.
Charcoal Art Stu
For UDS Kill Switch, wire EKC and
- 12 EKS terminals to like terminals in
DR AWING TITLE
14 UDS panel.
11 YW
DESCRPTIONI OF OPERATION
14 AWG RD-17-1 FIRE SYSTEM DRY CONTACTS.
Fire System #1 CORE
Protection. I-1/2' CORE
12 Dry contacts will make C2 to AR2
Appliance Manifold
14 when system Is armed.
package with Self
Cleaning. Installed in
11 YW
Hood Utility Cabinet with
Integral hood prewire
panel.
RD-18-1INTERLOCKFOR AUTOMAN ACTIVATION, 4647383 'm—
Used for activating 120V n.tom.m TYPE DATE
�14° or adjacent Master CORE panels 2/2
11 YW during active Fire Condition, DWG NO ECP #1-9
I-VSIONS
DESCRIPTION I DATE:
+�
0
CV
O
00
�
+�
rn
V '
QJ
CD
�i�
I
Q
.--C
0
CD
C d
LLJ
DUE: 2/23/2021
ONGX:
4647383
EFVWN RTB - 85
BE
SOLE:
3/4" = 1 '-0"
MPSTERMWING
RECEIVED
Mar 05 2021
— T—T Es SHEET NO.
4
IEVSIONS
DESCRIPTION DATE:
or
JOB NO
MODEL NUMBER 7� `'
DC v -����
DRAVIN BY
SCHEMATIC 7YPE
1NSTALL
DESCRIPTI❑N OF ❑PERATI❑N:
4647383
Fire System #1 CORE Protection. 1-1/2' CORE Appliance Mnnlfold Package with Self Clenning. Instnlled in Hood Utility
JOB NAME
DATE
DYfG NO
Cabinet with integral hood prewlre panel.
Charcoal Art Studio Restauran,.,
2/23/2021
ECP #1-7
1
CORE TOTAL FLOOD PROTECTION SPRINKLER DETAIL_
03/06/2017 Rev, 13
2
BUCONNECTPCORELWATER LINETTTO BUILDING WET SPRINKLER SYSTEM. STAINLESS STEEL, COPPER, OR STEEL PIPE ONLY
1.
r c
S - 1; MASTER
3
r
SPRINKLER CONTRACTOR REQUIREMENT
4
ITEM
CONNECTION
OPERATING PRESSURE
K-FACTOR
FLOW RATE
COMMENTS
5
WATER LINE MUST BE SUPERVISED AND HAVE NO UNSUPERVISED MANUAL SHUT-OFF
CORE WATER SUPPLY LINE
1.5 INCH NPT
30.00 PSI TO 70 PS
8.3
36.9 GPM
VALVES
MINIMUM PRESSURE AND FLOWRATE DEPENDENT ON LENGTH OF HOOD SYSTEM
s
1-1/2' MANIFOLD MINIMUM OPERATING PRESSURE REQUIREMENTS
PRESSURE REGULATOR VALVE (PRV)
-PRV NOT INCLUDED AND MUST BE PROVIDED INSTALLED AND ADJUSTED BY
MINIMUM INLET MINIMUM INLET
LENGTH OF WATER PRESSURE WATER PRESSURE
7
THE SPRINKLER CONTRACTOR TO MEET INCOMING PRESSURE REQUIREMENTS
HOOD (FT) FOR HOT WATER FOR CORE (DISCHARGE
-A REGULATOR SUCH AS THE ELKHART BRASS MODEL NUMBER URFA-20S-2,5'
(PSI) PROTECTION (PSI) (K-FACTOR)
OR THE UR-20 SERIES PARTS KITS SHOULD BE UTILIZED
4 30 30 1.3
-MUST BE CONFIRMED WITH THE FIRE MARSHAL OR LOCAL AUTHORITY
s
- - - -
HAVING JURISDICTION (AHJ)
8 30 30 2.7
12 30 30 4.0
9
16 30 30 5.4
20 30 30 6.7
CORE WATER SUPPLY LINE
24 30 30 8.1
10
-30.00 PSI TO 70 PSI UP RAT NG
28 30 30 9.4
PRESSURE
-125 PSI MAX STATIC
32 30 30 10.7
PRESSURE, 1.5 INCH NPT NPT
36 33 35 11,3
11
FITTING
-36.9 GPM (1,5 GPM
40 35 40 11,8
PER FOOT OF HOOD)
44 38 45 12,4
12
-CONNECTED TO
SUPERVISED, DEDICATED
48 40 50 12,9
LINE WITH NO UNSUPERVISED
MANUAL SHUT-OFF VALVES
!EXHAUST
TOTAL FLOWRATE = K FACTOR x PRESSUR�4a
13
-CONNECT TO BUILDING
FIRE SPRINKLER WATER LINE HOOD
(REDUCE PRESSURE) WHEN
REQUIRED
14
-STAINLESS STEEL, COPPER,
OR STEEL PIPE ONLY
15
36 INCHES CLEARANCE REQUIRED IN FRONT
OF ALL UTILITY CABINET DOORS
THE PANEL SHALL ALSO BE LOCATED IN AN
16
ACCESSIBLE AREA WHERE THE AUDIBLE AND
VISUAL ALARMS CAN BE HEARD AND SEEN
17
18
19
ELECTRIC
GAS
20
Y1
COOKING
NOZZLE HEIGHTS ABOVE HAZARD
APPLIANCES)
NOZZLE ABOVE
NOZZLE PART NUMBER HAZARD
22
MIN MAX
3070-3/8H-SS10 30' 1 55'
23
NOZZLES FOR CORE PROTECTION
DESCRIPTION PART NUMBER MACOLA FLOW RATE
24
RISER NOZZLE 1/4TT+TP1530+CP1325 A0002784 2.6 GPMMS@ 30
NOTE; SEE INSTALLATION, OPERATION, AND MAINTENANCE MANUAL FOR FURTHER INSTRUCTIONS
SPRAY BAR 1/4TT+TG-4,3W A0025166 0.7 GPM @ 30
NOZZLE PSI
PRESSURE REDUCING VALVE WITH SUPERVISION SWITCH, BALL VALVE
SUPERVISION SWITCH AND PRESSURE MONITORING SWITCH (OPTIONAL)
ATTENTION: LOW -VOLTAGE DC OR SIGNALING WIRE SHOULD
BE ROUTED IN SEPARATE CONDUIT FROM ALL AC SOURCES
PRV SUPERVISION SWITCH
-THE PRESSURE REDUCING VALVE MUST BE INSTALLED WITH AN APPROVED SUPERVISION SWITCH
-SWITCH PART NUMBERS AND SUPPORT BRACKETS ARE LISTED IN THE TABLE
-SWITCH COMES WITH TWO SINGLE POLE, DOUBLE THROW SWITCHES
-SWITCH MUST BE ATTACHED PER PRESSURE REDUCTION VALVE BRACKET INSTRUCTIONS
0 VALVE SUPERVISION SWITCH BRACKET WATER PRESSURE SUPERVISION SWITCH
-VALVE BRACKET CONTAINS NECESSARY PARTS -SWITCH IS AVAILABLE WITH A 1/2' NPT CONNECTION
AND INSTRUCTIONS TO ADAPT THE SUPERVISION -PRESSURE MONITORING VALVE COMES WITH
SWITCH TO THE VALVE, TWO SINGLE POLE, DOUBLE THROW SWITCHES, EACH
® ® WITH AN ADJUSTABLE SETPOINT
PRESSURE REDUCING VALVE-SETPOINT CAN BE BETWEEN 10 AND 60 PSI
-VALVE IS AVAILABLE IN 1-1/2' NPT CONNECTIONS -PART NUMBER PL-PS402
08/06/2014 Rev, 9
D
0
-PRESSURE REDUCING VALVE (IF REQUIRED) MUST
INSTALLED BEFORE THE CORE PROTECTION PANEL
TO REDUCE SPRINKLER LINE INCOMING PRESSURE
AND VOLUME
-PRESSURE REDUCTION IS BASED UPON THE
INCOMING PRESSURE AND VOLUME
-SEE TABLE FOR OUTLET PRESSURE
BE
COMPLETE
PARTS KIT
UR-20
VALVE
OUTLET
PRESSURE
PERCENTAGE
SUPERVISION
SWITCH
SWITCH
BRACKET
UR-20-W KIT
UR-20-W
28,77
PL-PC VS2
80574001
UR-20-X KIT
UR-20-X
33.87
PL-PC VS2
80574001
UR-20-Z KI
UR-20-Z
56.57
PL-PCVS2
80,574001
URFA-20-S
URFA-20 I
VARIABLE
I INCLUDED I
N/A
UR-20 VALVE
INCOMING
PRESSURE
(PSI)
50
1 60
70
80
90
100
110
120
130
140
150
160
170
UR-20-W
14.35
17.22
20.09
22.96
25.83
28.7
31.57
34.44
37.31
40.18
43.05
45.92
48.79
UR-20-X
16.9
20.28
23.66
27.04
30.42
33.8
37.18
40.56
43.94
47.32
50.7
54.08
57.46
OUTLET PRESSURE (PSI)
UR-20-Z
28.25
33.9
1 39.55
45.2
50.85
1 56.5
1 62.15
67.8
1 73.45
1 79.1
84.75
1 90.4
1 96.05
URFA-20-S
VARIABLE
THE CORE PANEL CONTAINS TWO ISOLATED INPUTS FOR AUXILIARY SUPERVISION OF
PRESSURE REDUCING VALVES AND PRESSURE SWITCHES, EACH SUPERVISION DEVICE
ABOVE HAS TWO SINGLE POLE, DOUBLE THROW SWITCHES. THESE SWITCHES MAY BE
WIRED IN PARALLEL TO THE CORE PANEL TERMINALS H1D AND 39.
WHEN A FAULT IS DETECTED, THE CORE BOARD WILL SHUT DOWN THE GAS VALVE AND SH
TRIGGER A LOCAL TROUBLE SIGNAL, AND ALERT ALL ATTACHED CORE PACKAGES.
ALTERNATIVELY, THE SWITCHES FROM EACH DEVICE COULD BE CONNECTED TO THE
TROUBLE INPUT OF THE BUILDING FIRE ALARM PANEL TO INDICATE A TROUBLE
CONDITION. BOTH METHODS ARE SHOWN BELOW.
CORE CONTROL CONNECTIONS
PRV SUPERVISION SWITCH
C� NC F_ 39 0
WATEPRESSURE
S PERVISION SWITCH
CORE WATER SHUT-OFF
SUPERVISION SWITCH
L--_C- - -_�
38 DN1D 0
BALL VALVE SUPERVISION SWITCH
-SWITCH IS AVAILABLE FOR 3/4' TO 2'
-MONITORS CORE WATER SHUTOFF
-SEE TABLE FOR PART NUMBERS
f ARTRNBMBER
PIPE SIZE
PL-RBVS-3/4
3/4'
PL-RBVS-1
1'
PL-RVBS-1-1/2
1-1/2'
PL-RBVS-2
2'
WIRING
CONNECTIONS
FOR TROUBLE
CORE
CONTACT
BUILDING
CONTROL
FIRE ALARM
PANEL
PRV
WATERLINE
TROUBLE
SUPERVISION
SUPERVISION
CONTACT
SWITCH
SWITCH
/-��
/---\
/--
TROUBLE
INPUT
CORE WATEI.
SHUT-OFF
SWITCH
TOK b b TBL NO b, b NC 10 02 1 U b 2
TBC
C
C
C
END
OIN LE
DEVICE
1
2
3
4
5
6
7
s
s
10
JOB NO MODEL NUMBER `' DRAWN BY SCHEMATIC TYPE JESCK1N 11LJN LJH LJNEKA I ILJNI
4647383 DC v -2111 INSTALL Fire System #1 CORE Protection. 1-1/2' CORE Appliance Manifold Package with Self Clenning. Instnlled In Hood Utility
JOB NAME I DATE DWG NO Cabinet with integral hood prewlre panel.
Charcoal Art Studio Restauran,., 2/23/2021 ECP #1-6
CORE TOTAL FLOOD PROTECTION PLUMBING DETAIL 03/06/2017 Rev, 15
PLUMBER,
1, CONNECT HOT WATER LINE; )PVC, COPPER OR STAINLESS STEEL PIPE ONLY
2, CONNECT HOOD DRAIN(S) STAINLESS STEEL, COPPER, OR STEEL PIPE ONLY � �11 ll�dd
3, CONNECT ALL END -TO -END AND BACK-TO-BACK HOOD WATER LINE CONNECTIONS (PLUMBING IS FIELD SUPPLIED FOR THIS) FIELD PLUMBING MUST NOT EXCEED HEIGHT OF VACUUM BREAKER IN MAI�UTIUItY C1AB S T E R
REMOVE PLUG FROM MAIN HOOD SPRAY BAR AND CONNECT TO NEXT HOOD STAINLESS STEEL, COPPER, OR STEEL PIPE ONLY
4, PLUMB GAS VALVE, STRAINER MUST BE INSTALLED UPSTREAM OF VALVE
5, INSTALL FLOOR DRAIN
6, INSTALL BACKFLOW PREVENTER IF CODE REQUIRES
PLUMBING CONTRACTOR REQUIREMENT
ITEM
CONNECTION
TEMPERATURE
PRESSURE
FLOW RATE
COMMENTS
HOT WATER LINE
L5 INCH NPT
140 to 170'F
30 PSI TO 70
PSI 163 GPM
INSULATE HOT WATER PIPE, MINIMUM PRESSURE DEPENDENT ON LENGTH AND CONFIGURATION OF HOOD SYSTEM
HOOD DRAINS)
1-1/2 INCH NPT
N/A
GRAVITY DRAIN
SEE ABOVE
2 DRAINS ON 24 INCH TALL HOODS WITH 20 INCH TALL FILTERS AND HOODS 10 FEET AND LONGER
END -TO -END CORE CONNECTION
VARIES
N/A
N/A
N/A
CONNECT WITH NPT PIPE SEAL ALL THREADS HOOD CONNECTION PROVIDED
BACK-TO-BACK CORE CONNECTION
VARIES
N/A
N/A
N/A
CONNECT WITH NPT PIPE, SEAL ALL THREADS, HOOD CONNECTION PROVIDED
GAS VALVE
VARIES
N/A
SEE TABLE
N/A
UP TO 2 INCHES NPT WITH 24V CONTROLS, 2-1/2 AND 3 INCH USE 120V CONTROL
FLOOR DRAINS)
1-1/2 INCH
N/A
GRAVITY DRAIN
N/A
USED TO HELP CLEAN UP FIRE SYSTEM DISCHARGE, GREASE INTERCEPTOR MAY BE REQUIRED
BACKFLOW PREVENTER DRAIN LINE
(OPTIONAL)
INLET/OUTLET
DRAIN
N/A
VARIES
N/A
INSTALLED WHEN PACKAGE HAS A BACKFLOW PREVENTER VALVE, SEE BACKFLOW PREVENTER VALVE MANUAL FOR
DETAILS
HOT
-125 PSI MAX STATIC PRESSURE
11 -16.3 GPM (0,7 GPM PER FOOT OF HOOD)
-1.5 INCH NPT INCH NPT FITTING
- INSULATED
12
END -TO -END OR BACK-TO-BACK
CONNECTION
13 -INSTALLED AND PROVIDED BY
PLUMBER
STAINLESS STEEL, COPPER, OR
- STEEL PIPE ONLY
14
HOOD DRAINS)
- -1-1/2 INCH NPT CONNECTED TO
15 BUILDING GREASE TRAP
-2 DRAINS ON 24 INCH TALL HOODS
_ WITH 20 INCH FILTERS
-2 DRAINS ON HOODS 10 FEET AND
1s LONGER
-STAINLESS STEEL, COPPER OR STE
PIPE ONLY
17 -SLOPED MINIMUM 1/4' PER FOOT,
AVOID ANY UNNECESSARY 90'
TURNS
-PIPE SIZE SHOULD BE INCREASED
18 WHEN COMBINED WITH OTHER
DRAINS
-P-TRAPS SHOULD NOT BE USED IN
19 THE GREASE DRAIN LINE AND HEAT
TAPE MUST BE USED WHERE DRAIN
LINE IS RUN IN ENVIRONMENTS THAT
WOULD SOLIDIFY GREASE
20
FLOOR DRAIN
-1-1/2 DRAIN INSTALLED IN
21 -FLOOR NDRAINSPMAY BCE USED TO
DRAIN HOOD
-GREASE INTERCEPTOR MAY BE
22 REQUIRED
23
24
PIPE ONLY
ELECTRIC
COOKING
APPLIANCE(S)
PRESSURE REGULATOR VALVE
REGULATORS ARE NOT INCLUDED TO MEET REQUIRED PRESSURE
AND MUST BE ORDERED SEPARATELY
- - - PART NUMBERS; X65BU(3/4'), X65BU(1'), OR X65BU(1-1/2')
CONSULT FACTORY FOR SIZING
I
1-1/2' MANIFOLD MINIMUM OPERATING PRESSURE REQUIREMENTS
EXHAUST HOOD
36 INCHES CLEARANCE REQUIRED IN FRONT
OF ALL UTILITY CABINET DOORS
THE PANEL SHALL ALSO BE LOCATED IN AN
ACCESSIBLE AREA WHERE THE AUDIBLE AND
VISUAL ALARMS CAN BE HEARD AND SEEN
GAS
NOTE, SEE INSTALLATION, OPERATION, AND MAINTENANCE MANUAL FOR FURTHER INSTRUCTIONS
VKPVC PIPING CANNOT BE WITHIN 10 FT OF HOOD, CONNECTIONS TO THE MANIFOLD MUST BE HARD PIPED WITH COPPER, OR STAINLESS STEEL.
LENGTH OF
HOOD (FT)
MINIMUM INLET
WATER PRESSURE
FOR HOT WATER
(PSI)
DISCHARGE
COEFFICIENTS
(K-FACTOR)
4
30
0.6
8
30
1.3
12
30
1.9
16
30
2.5
20
30
3.1
24
30
3.8
28
30
4.4
32
30
5.0
36
33
5.4
40
35
5.9
44
38
6.2
48
40
6.6
TOTAL FLOWRATE = K FACTOR x PRESSURE0.44
GAS VALVE
-THREADED NPT CONNECTION
VE
SIZE
MAX INLET
PRESSURE
(PSI)
VOLTAGE
BTU/HR
3/4'
5
24VDC
593,200
1'
24VDC
1,132,300
1-1/4'
24VDC
1,925,000
1-1/2'
24VDC
1 2,406,000
2'
24VDC
2,940,500
2-1/2'
120VAC
5,607,800
3'
120VAC
5,661,700
+,
O
�
CLI
O
00
01
a)
Q
o_
Q
C
CD
0
0
�
O
�
C-)
C d
LLJ
DUE: 2/23/2021
ONGX:
4647383
UMN RTB - 85
BE
SOLE:
3/4" = 1 '-0"
MPSTERMWING
RECEIVED
Mar 05 2021
°EPA T-NT Es SHEET NO.
5