Loading...
REVIEWED RESUB 1 BLD2022-1709+Manufacturer_Specifications_and_Installation_Instructions+1.26.2023_12.37.22_PM+3335554GENERAL Installation Guidelines 60 Hz Air -Cooled Generators 10 kW to 26 kW AWARNING Loss of life. This product is not intended to be used in a critical life support application. Failure to adhere to this warning could result in death or serious injury. (000209b) Register your Generac product at: WWW.GENERAC.COM 1-888-GENE RAC (888-436-3722) Para espanol, visita: http://www.generac.com/service-support/product-support-lookug Pour le frangais, visiter : http://www.generac.com/service-support/product-support-lookup Use this page to record important information about this generator. Model: Serial: Production Date: Volts: LPV Amps: NG Amps: Hz: Phase: Controller P/N: STA MAC I D: SSID: Record the information found on the unit data label on this page. See General Information for the location of the unit data label. The unit has a label plate affixed to the inside partition, to the left of the control panel console as shown in Figure 2-1, Figure 2-2, or Figure 2- 3. See Operation for directions on how to open the top lid and remove the front panel. Always supply the complete model and serial numbers of the unit when contacting an Inde- pendent Authorized Service Dealer (IASD) about parts and service. Operation and Maintenance: Correct main- tenance and care of the unit ensures a mini- mum number of problems, and keeps operating expenses at a minimum. It is the operator's responsibility to perform all safety inspections, to verify all maintenance for safe operation is performed promptly, and to have the equipment inspected periodically by an IASD. Normal maintenance, service, and replacement of parts are the responsibility of the owner/operator and are not considered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage may contribute to the need for additional maintenance or service. When the generator requires servicing or repairs, Generac recommends contacting an IASD for assistance. Authorized service tech- nicians are factory -trained and are capable of handling all service needs. To locate the near- est IASD, please visit the dealer locator at: www.generac.com/Dea/er-Locator. OWARNING CANCER AND REPRODUCTIVE HARM www. P65Warnings.ca.gov. (000393a) Installation Guidelines for 60 Hz Air -Cooled Generators Table of Contents Section 1: Safety Rules & Proximity to Utilities ....................... 16 General Information Verify Wi-Fi Range ............................17 Introduction ..................................... 1 Transportation Recommendations 17 Read This Manual Thoroughly ............1 Suitable Mounting Surface ............ 17 Safety Rules .................................... 1 Placement on Roofs, Platforms, and How to Obtain Service ........................1 Other Supporting Structures.......... 17 General Hazards ............................. 2 Exhaust Hazards ............................. 2 Section 4: Generator Placement Electrical Hazards ........................... 3 Generator Placement .................... 18 Fire Hazards .................................... 3 Fascia Installation Explosion Hazards .......................... 3 (If Applicable)................................. 18 Battery Hazards .............................. 4 Base Plug Installation (If Applicable) ................................. 19 General Rules ................................. 4 Before You Begin................................4 Section 5: Fuel Conversion/Gas NEC Requirements .............................5 Connections Standards Index..................................5 Fuel Requirements and Recommendations ......................... 20 Section 2: Unpacking and BTU Content......................................20 Inspection Fuel Pressure....................................20 General ........................................... 7 Fuel Conversion ............................ 20 Required Tools ................................ 7 Fuel Consumption ......................... 21 Unpacking ....................................... 7 Fuel Line Sizing ............................. 21 Opening the Lid...................................8 Flexible Fuel Line Extensions ............21 Enclosure Panel Removal ............... 8 Natural Gas Pipe Sizing ....................22 Front Access Panel Removal ..............8 LP Gas Pipe Sizing ...........................22 Intake Side Panel Removal .................9 Installing and Connecting Customer Connections and Loose Fuel Lines ...................................... 23 Parts ................................................ 9 Fuel Shutoff Valve .............................23 Rear Connections ........................... 9 Flexible Fuel Line..............................23 Main Line Circuit Breaker Sediment Trap...................................23 (Generator Disconnect) ................. 10 Checking Fuel Line Connections... 24 Parts Shipped Loose ..................... 10 Checking Fuel Pressure ....................24 Auxiliary Shutdown Switch ............ 11 Performing Fuel System Leak Test ...24 Natural Gas Installation (Typical) ..25 Section 3: Site Selection and LP Gas (Vapor) Installation Preparation (Typical) ......................................... 26 Site Selection ................................ 13 Carbon Monoxide .......................... 13 Section 6: Electrical Carbon Monoxide Detectors .............13 Connections Potential CO Entry Points .................14 Generator Connections ................. 28 Protect the Structure .........................14 Control Wiring ................................ 29 Fire Prevention .............................. 15 Main AC Wiring.............................. 30 Distance Requirements .....................15 Service Entrance Decals ............... 30 Fire Codes, Standards, and Common Alarm Relay (Option) ..... 30 Guidelines.........................................16 Battery Requirements.................... 31 Generator Maintenance ....................16 Fresh Air for Ventilation and Battery Installation ......................... 31 Cooling .......................................... 16 Connecting the Battery ......................31 Water Ingress Avoidance .............. 16 Battery Disposal ............................ 31 Installation Guidelines for 60 Hz Air -Cooled Generators Section 7: Control Panel Startup / Testing Control Panel Interface ................. 32 Using the AUTO/OFF/MANUAL Buttons..............................................32 Generator Setup ........................... 32 Activation...........................................32 Cold Smart Start................................34 Setting The Exercise Timer ...............34 Before Initial Startup ...................... 34 Install Wizard.....................................34 Interconnect System Self Test Feature..............................................35 Before starting, complete the following: ...........................................35 Checking Manual Transfer Switch Operation ........................... 38 Electrical Checks ........................... 38 Generator Tests Under Load ........ 38 Checking Automatic Operation ..... 39 Installation Summary ..................... 39 Shutting Generator Down While Under Load or During a Utility Outage..... 39 Section 8: Troubleshooting Generator Troubleshooting ........... 41 Section 9: Quick Reference Guide System Diagnosis ......................... 43 Section 10: Accessories Section 11: Diagrams Installation Drawing (A0002360608 rev A-1 of 2) ...........49 Installation Drawing (A0002360608 rev A-2 of 2) ...........50 iv Installation Guidelines for 60 Hz Air -Cooled Generators Safety Rules & General Information Section 1: Safety Rules & General Information Introduction Thank you for purchasing this compact, high performance, air-cooled, engine -driven gen- erator. It is designed to automatically supply electrical power to operate critical loads during a utility power failure. This unit is factory installed in an all-weather, metal enclosure intended exclusively for out- door installation. This generator will operate using either vapor withdrawn liquid propane (LP) or natural gas (NG). NOTE: This generator is suitable for supplying typical residential loads such as induction motors (sump pumps, refrigerators, air condi- tioners, furnaces, etc.), electronic components (computer, monitor, TV, etc.), lighting loads, and microwaves, when sized correctly. This unit is also equipped with a Wi-Fio module, which allows the generator owner to monitor generator status from anywhere they have Internet access. NOTE: Wi-Fi® is a registered trademark of Wi- Fi Alliance®. The information in this manual is accurate based on products produced at the time of publication. The manufacturer reserves the right to make technical updates, corrections, and product revisions at any time without notice. Read This Manual Thoroughly gaAWARNING Consult Manual. Read and understand manual completely before using product. Failure to completely understand manual and product could result in death or serious injury. (000100a) If any section of this manual is not under- stood, contact the nearest Independent Authorized Service Dealer (IASD) or Gen- erac Customer Service at 1-888-436-3722 (1-888-GENERAC), or visit www.gen- erac.com for starting, operating, and servic- ing procedures. The owner is responsible for correct maintenance and safe use of the unit. This manual must be used in conjunction with all other supporting product documentation supplied with the product. SAVE THESE INSTRUCTIONS for future ref- erence. This manual contains important instructions that must be followed during placement, operation, and maintenance of the unit and its components. Always supply this manual to any individual that will use this unit, and instruct them on how to correctly start, operate, and stop the unit in case of emergency. Safety Rules The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The alerts in this manual, and on tags and decals affixed to the unit, are not all inclusive. If using a procedure, work method, or operating technique that the manufacturer does not specifically recommend, verify that it is safe for others and does not render the equipment unsafe. Throughout this publication, and on tags and decals affixed to the unit, DANGER, WARN- ING, CAUTION, and NOTE blocks are used to alert personnel to special instructions about a particular operation that may be haz- ardous if performed incorrectly or carelessly. Observe them carefully. Alert definitions are as follows: LIQQW Indicates a hazardous situation which, if not avoided, will result in death or serious injury. (000001) AWARNING Indicates a hazardous situation which, if not avoided, could result in death or serious injury. (000002) ACAUTION Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. (000003) NOTE: Notes contain additional information important to a procedure and will be found within the regular text of this manual. These safety alerts cannot eliminate the haz- ards that they indicate. Common sense and strict compliance with the special instructions while performing the action or service are essential to preventing accidents. How to Obtain Service When the unit requires servicing or repairs, contact Generac Customer Service at 1-888- GENERAC (1-888-436-3722) or visit www.generac.com for assistance. Installation Guidelines for 60 Hz Air -Cooled Generators Safety Rules & General Information When contacting Generac Customer Service about parts and service, always supply the complete model and serial number of the unit as given on its data decal located on the unit. Record the model and serial numbers in the spaces provided on the front cover of this manual. General Hazards Loss of life. Property damage. Installation must always comply with applicable codes, standards, laws and regulations. Failure to do so will result in death or serious injury. (000190) Automatic start-up. Disconnect utility power and render unit inoperable before working on unit. Failure to do so will result in death or serious injury. (000191) WARNING Electrocution. Potentially lethal voltages are generated by this equipment. Render the equipment safe before attempting repairs or maintenance. Failure to do so could result in death or serious injury. WARNI Loss of life. This product is not intended to be used in a critical life support application. Failure to adhere to this warning could result in death or serious injury. (000209b) iiiiiiim Accidental Start-up. Disconnect the negative battery cable, then the positive battery cable when working on unit. Failure to do so could result in death or serious injury. (000130) AWARNIN Equipment damage. Only qualified service personnel may install, operate, and maintain this equipment. Failure to follow proper installation requirements could result in death, serious injury, and equipment or property damage. _ _ _ _ .. AWARNIN Equipment damage. This unit is not intended for use as a prime power source. It is intended for use as an intermediate power supply in the event of temporary power outage only. Doing so could result in death, serious injury, and equipment damage. (000247a) AWARNIN Electric shock. Only a trained and licensed electrician should perform wiring and connections to unit. Failure to follow proper installation requirements could result in death, serious injury, and equipment or property damage.,___, __ , AWARNING y` Moving Parts. Do not wear jewelry when Ti starting or operating this product. Wearing jewelry while starting or operating this product could result in death or serious injury. (0001, 5) AWARNING ` Moving Parts. Keep clothing, hair, and appendages away from moving parts. Failure to do so could result in death or serious injury. (000111) AWARNING Hot Surfaces. When operating machine, do not touch hot surfaces. Keep machine away from combustibles during use. Hot surfaces could result in severe burns or fire. AWARNING Equipment and property damage. Do not alter construction of, installation, or block ventilation for generator. Failure to do so could result in unsafe operation or damage to the generator. (000146) AWARNING Risk of injury. Do not operate or service this machine if not fully alert. Fatigue can impair the ability to operate or service this equipment and could result in death or serious injury. (onn215a1 AWARNING Environmental Hazard. Always recycle batteries at an official recycling center in accordance with all local laws and regulations. Failure to do so could result in environmental damage, death, or serious injury. (000228) AWARNING Injury and equipment damage. Do not use generator as a step. Doing so could result in falling, damaged parts, unsafe equipment operation, and could result in death or serious injury. 1000216) • Inspect the generator regularly, and contact the nearest IASD for parts needing repair or replacement. Exhaust Hazards OLN Asphyxiation. Running engines produce carbon monoxide, a colorless, odorless, poisonous gas. Carbon monoxide, if not avoided, will result in death or serious injury. N I . "r<a Asphyxiation. Carbon monoxide can kill in minutes. Operate this unit outdoors only. Failure to do so will cause death or serious injury. (000525) 2 Installation Guidelines for 60 Hz Air -Cooled Generators Safety Rules & General Information AWARNING Equipment and property damage. Do not alter construction of, installation, or block ventilation for generator. Failure to do so could result in unsafe operation or damage to the generator. (000146) AWARNIN Asphyxiation. Always use a battery operated carbon monoxide alarm indoors and installed according to the manufacturer's instructions. Failure to do so could result in death or serious injury. (000178a) Electrical Hazards Electrocution. Contact with bare wires, terminals, and connections while generator is running will result in death or serious injury. (000144) I = Electrocution. Never connect this unit to the electrical system of any building unless a licensed electrician has installed an approved transfer switch. Failure to do so will result in death or serious injury. i = Electrical backfeed. Use only approved switchgear to isolate generator from the normal power source. Failure to do so will result in death, serious injury, and equipment damage. (000237) A -Electrocution. Verify electrical system is properly grounded before applying power. Failure to do so will result in death or serious injury. (000152) .. Electrocution. Do not wear jewelry while working on this equipment. Doing so will result in death or serious injury. W . Electrocution. Water contact with a power source, if not avoided, will result in death or serious injury. (000104) LIQQM Electrocution. In the event of electrical accident, immediately shut power OFF. Use non-conductive implements to free victim from live conductor. Apply first aid and get medical help. Failure to do so will result in death or serious injury. (000145) Fire Hazards AWARNING Fire hazard. Do not obstruct cooling and ventilating airflow around the generator. Inadequate ventilation could result in fire hazard, possible equipment damage, death or serious injury. AWARNING Fire and explosion. Installation must comply with all local, state, and national electrical building codes. Noncompliance could result in unsafe operation, equipment damage, death, or serious injury. AWARNING Fire hazard. Use only fully -charged fire extinguishers rated "ABC" by the NFPA. Discharged or improperly rated fire extinguishers will not extinguish electrical fires in automatic standby generators. (000219) 1IIII WARNIN �J Electrocution. Refer to local codes and standards for safety equipment required when working with a live electrical system. Failure to use required safety equipment could result in death or serious injury. (000257) AWARNING Risk of Fire. Unit must be positioned in a manner that prevents combustible material accumulation underneath. Failure to do so could result in death or serious injury. (nnn1a71 Comply with regulations the local agency for workplace health and safety has established. Also, verify that the generator is installed in accordance with the manufacturer's instruc- tions and recommendations. Following proper installation, do nothing that might alter a safe installation and render the unit in non- compliance with the aforementioned codes, standards, laws, and regulations. Explosion Hazards I � . Explosion and fire. Fuel and vapors are extremely flammable and explosive. No leakage of fuel is permitted. Keep fire and spark away. Failure to do so will result in death or serious injury. i = Explosion and fire. Connection of fuel source must be completed by a qualified professional technician or contractor. Incorrect installation of this unit will result in death, serious injury, and property and equipment damage. Risk of fire. Allow fuel spills to completely dry before starting engine. Failure to do so will result in death or serious injury. Installation Guidelines for 60 Hz Air -Cooled Generators 3 Safety Rules & General Information AWARNING Risk of Fire. Hot surfaces could ignite combustibles, resulting in fire. Fire could result in death or serious injury. (000110) Battery Hazards Electrocution. Do not wear jewelry while working on this equipment. Doing so will result in death or serious injury. (000188) AWARNING Explosion. Do not dispose of batteries in a fire. 44 Batteries are explosive. Electrolyte solution can cause burns and blindness. If electrolyte contacts skin or eyes, flush with water and seek immediate medical attention. (000162) AWARNING Explosion. Batteries emit explosive gases while charging. Keep fire and spark away. Wear protective gear when working with batteries. Failure to do so could result in death or serious injury. I __ __ AWARNING Electrical shock. Disconnect battery ground terminal before working on battery or battery wires. Failure to do so could result in death or serious injury. (000164) �® AWARNING WEVRisk of burns. Batteries contain sulfuric acid and can cause severe chemical burns. Wear protective gear when working with batteries. Failure to do so could result in death or serious injury. , ® AWARNING Risk of burn. Do not open or mutilate batteries. Batteries contain electrolyte solution which can cause burns and blindness. If electrolyte contacts skin or eyes, flush with water and seek immediate medical attention. (000163a) AWARNING Environmental Hazard. Always recycle batteries at an official recycling center in accordance with all local laws and regulations. Failure to do so could result in environmental damage, death, or serious injury. (000228) Always recycle batteries in accordance with local laws and regulations. Contact your local solid waste collection site or recycling facility to obtain information on local recycling pro- cesses. For more information on battery recycling, visit the Battery Council Interna- tional website at: http://batterycouncii.org. General Rules LIQUW Loss of life. Property damage. Installation must always comply with applicable codes, standards, laws and regulations. Failure to do so will result in death or serious injury. mn01ani Electrical backfeed. Use only approved switchgear to isolate generator from the normal power source. Failure to do so will result in death, serious injury, and equipment damage. (000237) AWARNING Equipment damage. Only qualified service personnel may install, operate, and maintain this equipment. Failure to follow proper installation requirements could result in death, serious injury, and equipment or property damage. (000182a) 1 t AWARNING _l Electrocution. Refer to local codes and standards for visafety equipment required when working with a live electrical system. Failure to use required safety equipment could result in death or serious injury. (000257) gnAWARNING Consult Manual. Read and understand manual completely before using product. Failure to completely understand manual and product could result in death or serious injury. mnnlnna� • Follow all safety precautions in the owner's manual, installation guidelines manual, and other documents included with the equipment. • Never energize a new system without opening all disconnects and breakers. • Always consult local code for additional requirements for where unit is being installed. • Incorrect installation can result in personal injury and damage to the unit. It may also result in the warranty being suspended or voided. All instructions listed below must be followed including location clearances and pipe sizes. Before You Begin • Contact local inspector or city hall to be aware of all federal, state, and local codes which could impact installation. Secure all required permits before installing. • Fully comply with all relevant NEC, NFPA, and OSHA standards, as well as all federal, state, and local building and electric codes. This unit must be installed in accordance with current NFPA 37 and NFPA 70 standards, and any other federal, state, and local codes for minimum distances from other structures. 4 Installation Guidelines for 60 Hz Air -Cooled Generators Safety Rules & General Information • Verify capacity of NG meter or LP tank in regards to providing sufficient fuel for both the unit and other household and operating appliances. NEC Requirements Local code enforcement may require Arc Fault Circuit Interrupters (AFCIs) to be incor- porated into the transfer switch distribution panel. The transfer switch provided with this generator has a distribution panel which will accept AFCIs (pre -wired transfer switches only). Siemens Part No. Q115AF - 15A or Q120AF - 20A can be obtained from a local electrical wholesaler and will simply replace any of the single pole circuit breakers supplied in the pre -wired transfer switch distribution panel. Standards Index AWARNING Loss of life. This product is not intended to be used in a critical life support application. Failure to adhere to this warning could result in death or serious injury. (000209b) Strictly comply with all applicable national, state, and local laws, as well as codes or reg- ulations pertaining to the installation of this engine -generator power system. Use the most current version of applicable codes or standards relevant to the local jurisdiction, generator used, and installation site. NOTE: Not all codes apply to all products and this list is not all-inclusive. In the absence of pertinent local laws and standards, the follow- ing publications may be used as a guide (these apply to localities which recognize NFPA and ICC). 1. National Fire Protection Association (NFPA) 70: The NATIONAL ELECTRIC CODE (NEC) * 2. NFPA 10: Standard for Portable Fire Extinguishers * 3. NFPA 30: Flammable and Combustible Liquids Code * 4. NFPA 37: Standard for Stationary Combustion Engines and Gas Turbines 5. NFPA 54: National Fuel Gas Code * 6. NFPA 58: Standard for Storage and Handling Of Liquefied Petroleum Gases * 7. NFPA 68: Standard On Explosion Protection By Deflagration Venting * 8. NFPA 70E: Standard For Electrical Safety In The Workplace * 9. NFPA 110: Standard for Emergency and Standby Power Systems * 10. NFPA 211: Standard for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances * 11. NFPA 220: Standard on Types of Building Construction * 12. NFPA 5000: Building Code 13.International Building Code ** 14.Agricultural Wiring Handbook *** 15.Article X, NATIONAL BUILDING CODE 16.ASAE EP-364.2 Installation and Maintenance of Farm Standby Electric Power **** 17.ICC:IFGC This list is not all-inclusive. Check with the Authority Having Local Jurisdiction (AHJ) for any local codes or standards which may be applicable to your jurisdiction. The above listed standards are available from the follow- ing internet sources: * www.nfpa.org ** www.iccsafe.org *** www.rerc.org Rural Electricity Resource Council P.O. Box 309 Wilmington, OH 45177- 0309 **** www.asabe.org American Society of Agricultural & Biological Engineers 2950 Niles Road, St. Joseph, MI 49085 Installation Guidelines for 60 Hz Air -Cooled Generators 5 Safety Rules & General Information This page intentionally left blank. Installation Guidelines for 60 Hz Air -Cooled Generators Unpacking and Inspection Section 2: Unpacking and Inspection General NOTE: Carefully inspect contents for damage after unpacking. Unpack and inspect unit immediately upon delivery to identify any dam- age which may have occurred in transit. Any claims for shipping damage must be filed as soon as possible with freight carrier. This is especially important if unit will not be installed for a period of time. • This standby generator is ready for installa- tion with a factory supplied and pre - mounted base pad and has a weather pro- tective enclosure intended for outdoor installation only. • If any loss or damage is noted at time of delivery, have delivery person(s) note all damage on the freight bill, or affix their sig- nature under consignor's memo of loss or damage. • If a loss or damage is noted after delivery, separate damaged materials and contact freight carrier for claim procedures. • "Concealed damage" is understood to mean damage to contents of a package not evident at time of delivery, but discovered later. Required Tools • General SAE and Metric hand tools — Wrenches — Sockets — Screwdrivers • Standard electrician's hand tools — Drill and bits for mounting and rout- ing conduits • 4 mm hex key (for access to customer con- nections) • 3/16 in hex key (test port on fuel regulator) • Manometer (for fuel pressure checks) • Meter capable of measuring AC/DC voltage and frequency • Torque wrenches Unpacking Proceed as follows to unpack the generator: 1. Remove outer shipping carton. 2. See Figure 2-1. Remove wood frame. Figure 2-1. Crated Generator 3. See Figure 2-2. Lid will be locked. A set of keys is attached to the cardboard sheet on top of unit. An additional set is attached to the pallet bracket on the front intake end of unit. Remove keys from cardboard and pallet bracket. 006729 Figure 2-2. Keys As Shipped NOTE: The enclosed keys provided with this unit are intended for service personnel only. (Part number OG66240KEY) Installation Guidelines for 60 Hz Air -Cooled Generators 7 Unpacking and Inspection IMPORTANT NOTE: DO NOT perform next step until generator has been transported to installation site. 4. See Figure 2-3. Remove bolts and pallet brackets (A). Exercise caution when removing generator. Dragging it off pallet will damage base. The unit must be lifted from wooden pallet to remove. NOTE: Bolts and pallet brackets are provided only for shipping purposes and can be dis- carded after removal. 000426 Figure 2-3. Pallet Bracket Locations Opening the Lid Proceed as follows to open the generator lid: 1. Use keys to open generator lid. 2. See Figure 2-4. Two locks (A) secure lid; one on each side. Press down on lid above side lock, and unlock latch to correctly open lid. 400 Figure 2-4. Opening the Lid 3. Repeat for other side. Lid may appear stuck if pressure is not applied from the top. NOTE: Always verify side locks are unlocked before attempting to lift lid. Enclosure Panel Removal Generator installation requires removal of front panel and intake side panel. Remove these panels when necessary. Proceed as fol- lows to remove the panels. Front Access Panel Removal See Figure 2-5. Remove front access panel (A) by lifting straight up and out once lid is open. NOTE: Always lift front access panel straight up before pulling away from enclosure (B and C). Do not pull panel away from the enclosure before lifting up (D). nN• 009210 Figure 2-5. Remove Front Access Panel 8 Installation Guidelines for 60 Hz Air -Cooled Generators Unpacking and Inspection Intake Side Panel Removal See Figure 2-6. The intake side panel (A) must be removed to access battery compartment, fuel regulator, and sediment trap. 1. Raise lid and remove front panel. 2. Use a hex key to remove two mounting screws (B) and the hex screw (C) on the L- bracket. 3. Lift intake panel up and away from generator. 4. Inspect for any hidden freight damage. Contact freight carrier if damage is present. NOTE: Always lift intake side panel straight up before pulling away from enclosure. Do not pull panel away from enclosure before lifting up (D). 0 002961 Figure 2-6. Intake Side Panel Removal Customer Connections and Loose Parts See Figure 2-7 and Figure 2-8 for customer connections and loose parts location. Figure 2-10 illustrates parts shipped loose. A Customer electrical connection area (behind access panel) B Fuel regulator with sediment trap C Battery compartment (battery not supplied) (PN OH3421 S) D Positive (+) and negative (-) battery cables E Location of "Loose Shipped Parts" Figure 2-7. Customer Connection Area and Loose Parts Location Rear Connections 001360 A Wi-Fi module B Main AC/Control wiring hole for 1-1/4 in conduit C Main AC/Control wiring hole for 3/4 in conduit (if equipped) D Fuel connection hole E Auxiliary shutdown switch Figure 2-8. Rear Connections NOTE: Generator is equipped with a Wi-Fi module. See Wi-Fi module owner's manual for further instruction. Installation Guidelines for 60 Hz Air -Cooled Generators 9 Unpacking and Inspection Main Line Circuit Breaker (Generator Disconnect) See Figure 2-9. The 2-pole main line circuit breaker (MLCB) (generator disconnect) (A) is rated according to relevant specifications. ou, b, Figure 2-9. Generator Main Line Circuit Breaker Generator MLCB (generator disconnect) can be locked in OFF (OPEN) position for security during maintenance or transfer switch service. Use an appropriately -sized padlock (not included) with a shackle long enough to pass through both lock tabs (B). NOTE: DO NOT leave generator MLCB (gen- erator disconnect) locked in the OFF (OPEN) position during normal generator operation. Leaving the generator MLCB (generator dis- connect) in OFF (OPEN) position will prevent generator from powering structure during a power outage when placed in AUTO mode. Parts Shipped Loose A Keys B Flexible fuel line C Battery terminal cap D Rubber mounts (only for units including fascia) E Fascia (if applicable) F Base plugs (if applicable) G Decal —Service entrance warning (not shown) H Decal —Through conductors warning (not shown) J Decal —Service disconnect (not shown) K Owner's and installation manuals (not shown) L Wi-Fi manual (not shown) M Wi-Fi Quick Start Guide (not shown) Figure 2-10. Parts Shipped Loose 10 Installation Guidelines for 60 Hz Air -Cooled Generators Unpacking and Inspection Auxiliary Shutdown Switch ,&CAUTION Equipment Damage. The auxiliary shutdown switch is not to be used to power down the unit under normal operating circumstances. Doing so will result in equipment damage. (000399) All generators are equipped with an external means of shutting down the generator which complies with the latest NEC code require- ment. The primary generator shutdown sequence is described in Control Panel Startup / Testing. See Figure 2-11. An auxiliary shutdown switch (A) is located on the exterior of the generator back panel. This switch shuts down the gener- ator and disables restarts. ;492 Figure 2-11. Auxiliary Shutdown Switch (all models) NOTE: Whenever possible, perform primary shutdown procedure before disabling genera- tor with auxiliary shutdown switch. See Figure 2-12. 14-26 kW generators have an auxiliary shutdown switch (B) located inside the generator. Figure 2-12. Auxiliary Shutdown Switch (14-26 kW) NOTE: Generator will not start if either switch is OPEN (0). Controller displays an "Auxiliary Shutdown" alarm, and red LED "Alarm" light illuminates until switch or switches are CLOSED (1) and alarm is cleared by pressing OFF mode button, and then ENTER. Once cleared, generator can be placed back in AUTO or MANUAL. Installation Guidelines for 60 Hz Air -Cooled Generators 11 Unpacking and Inspection This page intentionally left blank. 12 Installation Guidelines for 60 Hz Air -Cooled Generators Site Selection and Preparation Section 3: Site Selection and Preparation Site Selection Site selection is critical for safe generator operation. It is important to discuss these fac- tors with the installer when selecting a site for generator installation: • Carbon monoxide • Fire prevention • Fresh air for ventilation and cooling • Water ingress prevention • Proximity to utilities • Suitable mounting surface The following pages describe each of these factors in detail. NOTE: The term "structure" is used throughout this section to describe the home or building where generator is being installed. Illustrations depict a typical residential home. However, instructions and recommendations presented in this section apply to all structures regardless of type. Carbon Monoxide Asphyxiation. Running engines produce carbon monoxide, a colorless, odorless, poisonous gas. Carbon monoxide, if not avoided, will result in death or serious injury. IMPORTANT NOTE: Move to fresh air immediately and seek medical attention if you feel sick, dizzy, or weak while the gen- erator is running or after it stops. Generator exhaust contains carbon monox- ide (CO) —a poisonous, potentially lethal gas that cannot be seen or smelled. The genera- tor must be installed in a well ventilated area away from windows, doors, and openings. The selected location should not allow exhaust gases to be drawn into structures where people or animals may be present. Carbon Monoxide Detectors See Figure 3-1. CO detectors (K) must be installed and used to monitor for CO and to warn individuals about the presence of CO. CO detectors must be installed and tested in accordance with the CO detector manufac- turer's instructions and warnings. Contact local building inspection department for any applicable requirements concerning CO detectors. See NFPA 72, National Fire Alarm and Signaling Code, and Section R315 in the ICC International Residential Code for more information. IMPORTANT NOTE: Common smoke alarms do NOT detect CO gas. Do not rely on smoke alarms to protect residents or animals from CO. The only way to detect CO is to have functioning CO alarms. Installation Guidelines for 60 Hz Air -Cooled Generators 13 Site Selection and Preparation Potential CO Entry Points See Figure 3-1. Generator exhaust can enter a structure through large openings, such as windows and doors. However, exhaust and CO can also seep into the structure through smaller, less obvious openings. 111 N-1-10 Protect the Structure Verify structure itself is correctly caulked and sealed to prevent air from leaking in or out. Voids, cracks, or openings around windows, doors, soffits, pipes, and vents can allow exhaust gas to be drawn into the structure. Some examples of potential entry points are described and included in, but not limited to, the accompanying table. 008781 Figure 3-1. Carbon Monoxide —Potential Entry Points ID Entry Point Description / Comments A Windows and Architectural details which can be (or are) opened to admit fresh air into the doors structure. B Garage door CO can leak into garage if door is open, or does not seal correctly when closed. C Attic vent Attic vents, ridge vents, crawl space vents, and soffit vents can all admit generator exhaust. D Basement windows Windows or hatches allowing ventilation to or from lower level of a structure. E Furnace intake / exhaust vent Air intake and exhaust pipes for furnace. F Wall cracks Includes (but not limited to) cracks in wall, foundation, mortar, or air gaps around doors, windows, and pipes. See Protect the Structure. G Dryer vent Exhaust duct for clothes dryer. Airflow Structural features, including but not limited to: corners, alcoves, fences, H restrictions courtyards, and areas with heavy vegetation can restrict correct airflow around unit. Exhaust gases can be collected in these areas. Do not direct generator discharge into HVAC components, including but not limited to: make up air systems, AC condensers, and window AC units. HVAC IMPORTANT NOTE: Mechanical and gravity outdoor air intake openings for components HVAC supply air systems shall be located according to Section 401 in the ICC Mechanical Code. See ICC Mechanical Code for any additional requirements. 14 Installation Guidelines for 60 Hz Air -Cooled Generators Site Selection and Preparation Fire Prevention The generator must be installed at a safe dis- tance away from combustible materials. Engine, alternator, and exhaust system com- ponents become very hot during operation. Fire risk increases if unit is not correctly ven- tilated, is not correctly maintained, operates too close to combustible materials, or if fuel leaks exist. Also, accumulations of flamma- ble debris within or outside the generator enclosure may ignite. U Distance Requirements See Figure 3-2. Minimum clearances must be maintained around the generator enclosure. These clearances are primarily for fire pre- vention, but also to provide sufficient room for removing front and end panels for mainte- nance purposes. Figure 3-2. Generator Distance Requirements ID Description Definition A Front and end Minimum clearance from the front and ends of generator must be 3 ft (0.91 m). clearance This includes shrubs, bushes, and trees. Fuel and electrical connections are made here. 18 in (457 mm) minimum B Rear clearance clearance per SwRI testing, labeling, and listing, unless state or local codes dictate otherwise. Windows, vents, No operable windows, doors, vents, window wells, or openings in the wall are C and openings permitted near any point of the generator. See Potential CO Entry Points for more information. D Existing wall The generator should not be placed closer than 18 in (457 mm) from existing walls. A removable barrier (non -permanent; without footings) installed as a visual E Removable fence surround. Removable fence panels for servicing cannot be placed less than 3 ft (0.91 m) in front of the generator. F Overhead 5 ft (1.52 m) minimum distance from any structure, overhang, or projections clearance from wall. Maneuvering space around generator for performing routine maintenance G Maintenance and tasks such as battery replacement and engine service. Do not attempt to servicing conceal generator with shrubs, bushes, or plants. See NEC Article 110.26 for more information. Installation Guidelines for 60 Hz Air -Cooled Generators 15 Site Selection and Preparation Fire Codes, Standards, and Guidelines Generator installation must comply strictly with ICC IFGC, NFPA 37, NFPA 54, NFPA 58, and NFPA 70 standards. These stan- dards prescribe the minimum safe clear- ances around and above the generator enclosure. NFPA 37 NFPA 37 is the The National Fire Protection Association's standard for the installation and use of stationary combustion engines. Its requirements limit the spacing of an enclosed generator set from a structure or wall, and require generator to be located where it is readily accessible for maintenance, repair, and first responders. ® SwRI ID N. 13204.OM 74 Clause of Sect un 4.14 of NFPA 37 LISTED BY. Southwest Research Iew stitute SAntono, Texas ®•—m -- NOTE 1 (30 CHAR MAXa•p—•—•-- ^—^^—•— NOTE 2 130 CHAR. MA* •—•••—•—^••• �•m••�—•—� NOTE 3 13D CHAR MAX) —•---- NOTE 4 (30 CHAR MAXF•—^^""• •— ••^—• ^—•• NOTE 5 (30 CHAR MAX)—•••----,- ---•--•• NOTE 6 (30 CHAR MA)I---- --- NOTE 7 (30 CHAR MAX)—------ OENERAC POWER SYSTEMS, INC WAUKESHA, M USA 53189 OL257 002158 Figure 3-3. Southwest Research Institute Marking NOTE: The Southwest Research Institute (SwRI) is a nationally recognized third party testing and listing agency. SwRI testing approves 18 in (457 mm) installation minimum from the rear panel of the generator to an adjacent structure for fire protection. The criteria was to determine the worst case fire scenario within the generator and to determine the ignitability of items outside the engine enclosure at various distances. The enclosure is constructed of non-combustible materials, and the results and conclusions from the independent testing lab indicated that any fire within the generator enclosure would not pose any ignition risk to nearby combustibles or structures, with or without fire service personnel response. Based on this testing and the requirements of NFPA 37, Sec 4.1.4, the guidelines for instal- lation of the generators listed above are changed to 18 in (457 mm) from the back side of the generator to a stationary wall or building. This offset reduction does not apply to clearances from openings in the structure. For adequate maintenance and airflow clear- ance, the area above the generator should be at least 5 ft (1.52 m) with a minimum of 3 ft (0.91 m) at the front and ends of the enclo- sure. This includes trees, shrubs, and bushes. Vegetation not in compliance with these clearance parameters could obstruct air flow. In addition, exhaust fumes from the generator could inhibit plant growth. See Fig- ure 3-2 and the accompanying descriptions. Generator Maintenance Regular maintenance is crucial for minimiz- ing exhaust emissions and reducing the risk of fire or equipment failure. For example: • A dirty air filter or low engine oil level may cause engine to overheat. • Incorrect spark plug gaps may cause engine backfiring and incomplete combustion. IMPORTANT NOTE: See Maintenance sec- tion of generator owner's manual to view a table of scheduled maintenance tasks and procedures. Perform all maintenance tasks as directed. Fresh Air for Ventilation and Cooling Install unit where air inlet and outlet openings will not become obstructed by leaves, grass, snow, etc. If prevailing winds will cause blow- ing or drifting, consider using a windbreak at a safe distance to protect the unit. Water Ingress Avoidance • Select a location on high ground where water levels will not rise and flood the generator. This unit should not operate in, or be subjected to, standing water. • Install unit where rain gutter downspouts, roof run-off, landscape irrigation, water sprinklers, or sump pump discharge does not flood unit or spray enclosure, including any air inlet or outlet openings. • Excess moisture can cause excess corrosion and decrease life expectancy of the unit. Proximity to Utilities Contact local utility providers and verify proposed site selection meets all required utility placement requirements before installation. This could affect warranty coverage. Remember, laws and or codes may regulate distance and location of unit to specific utilities. It is recommended to pick a location where the generator is as close as possible to the transfer switch and the fuel supply, while verifying the site location conforms to the rest of the Site Selection section. 16 Installation Guidelines for 60 Hz Air -Cooled Generators Site Selection and Preparation Verify Wi-Fi Range See Wi-Fi manual shipped with the unit if planning to use the Wi-Fi feature. Transportation Recommendations Use a suitable cart or equipment to carry generator, including wooden pallet, to instal- lation site. Place cardboard between cart and generator to prevent any damage or scratches to generator. Do not lift, carry, or move generator by grasping the louvers. Doing so may bend or damage the sheet metal. Suitable Mounting Surface Select non-combustible base type as desired or as required by local laws or codes. The generator is typically approved to be placed on pea gravel, crushed stone, or a concrete pad. Follow all applicable codes if a concrete pad is required. Aftermarket composite pads have not been tested or approved by Gen- erac. See Figure 3-4. Prepare a rectangular area approximately 5 in (127 mm) thick (A) and approximately 3 in (76.2 mm) longer and wider (B) than the footprint of the generator on all sides when using pea gravel or crushed stone. Ire .a Ire ►a 1`C ��I IBC OBI O � 000856 Figure 3-4. Pea Gravel or Crushed Stone Concrete pads must be appropriately sized in accordance with national, state, or local building codes. Verify surface where generator will be mounted is compacted, leveled, and will not erode over time. Generator must be level within 0.5 in (13 mm) all around. Recommended concrete pads: 10000007852 — 3 in (76.2 mm), 10000007848 — 4 in (102 mm). NOTE: Generac does not recommend the use of black composite pads. Placement on Roofs, Platforms, and Other Supporting Structures Where required to place generator on a roof, platform, deck, or other supporting structure, generator must be placed in accordance with the requirements in NFPA 37, Section 4.1.3. Generator can be located 18 in (457 mm) from structures having combustible walls and 5 ft (1.52 m) from any operable opening in the structure. Surface beneath the generator and beyond must be noncombustible to a minimum distance of 12 in (30.5 cm). Contact local building inspection department or fire department to determine which noncombusti- ble materials are approved for installation. Installation Guidelines for 60 Hz Air -Cooled Generators 17 Generator Placement Section 4: Generator Placement Generator Placement See Figure 4-1. All air-cooled generators come with an integrated composite pad. This inte- grated composite pad elevates the generator and helps prevent water from pooling around base. 000612a Figure 4-1. Integrated Composite Pad The integrated composite pad allows the gen- erator to be placed on two types of Generac approved surfaces: • on 5 in (12.7 cm) of compacted pea gravel or crushed stone • on a concrete pad See local codes to verify what type of site base is required. If a concrete pad is required, all federal, state, and local codes must be fol- lowed. Place generator, with integrated com- posite pad attached, and position correctly as per dimensional information given in Site Selection and Preparation. NOTE: Generator must be level within 0.5 in (13 mm). NOTE: See Figure 4-2. DO NOT remove inte- grated composite pad for mounting generator to concrete. The integrated composite pad is pre -drilled to accommodate mounting bolts. Figure 4-2. Mounting Hole Locations Three mounting holes are available if codes require securing generator to concrete. Mounting holes are located inside the genera- tor compartment —two in front and one in back. Three 3/8 in (or M10) lag bolts (not supplied) are recommended for securing generator to a concrete pad. NOTE: The top of the generator carton has a template which can be used to mark concrete pad to pre -drill the mounting holes. Fascia Installation (If Applicable) 1. Locate the four threaded black rubber bumpers supplied with loose parts. (See Parts Shipped Loose.) 2. See Figure 4-3. Remove rubber bumpers from bag and screw them into threaded holes located inside the end pieces of the fascia (two each) opposite one another (A). VJ Figure 4-3. Fascia Installation 3. Snap one of the end pieces into one of the front/rear pieces of fascia. Repeat this action with the other two remaining pieces of fascia (B). NOTE: Do not assemble all four pieces together at this point. 4. Place both assemblies at generator base and fit the rubber mounts into the lifting holes in the generator base (C). 5. Once aligned, snap together the two remaining connection points. 18 Installation Guidelines for 60 Hz Air -Cooled Generators Generator Placement Base Plug Installation (If Applicable) Proceed as follows to install base plugs: 1. Locate the four base plugs supplied with the loose parts. (See Parts Shipped Loose.) 2. Locate the four holes in the corners of the generator base. 3. See Figure 4-1. Install base plugs into generator base. 013381 Figure 4-1. Installing Base Plugs Installation Guidelines for 60 Hz Air -Cooled Generators 19 Fuel Conversion / Gas Connections Section 5: Fuel Conversion / Gas Connections Fuel Requirements and Recommendations Explosion and fire. Fuel and vapors are extremely flammable and explosive. No leakage of fuel is permitted. Keep fire and spark away. Failure to do so will result in death or serious injury. , NOTE: NG is lighter than air and will collect in high areas. LP gas is heavier than air and will settle in low areas. LP gas should only use a vapor withdrawal system. This type of system uses vapors formed above liquid propane in the storage tank. The unit will run on NG or LP gas, but has been factory -configured to run on NG. NOTE: Should the primary fuel need to be changed to LP gas, the fuel system must be reconfigured. See Fuel Conversion for instruc- tions on converting the fuel system. BTU Content Recommended fuels should lave a BTU co tent of at least 1,000 BTU/ft (N.26 MJ/m ) foS NG; or at least 2,500 BTU/ft (93.15 MY m ) for LP gas. NOTE: BTU fuel content information is avail- able from fuel supplier. Fuel Pressure Required fuel pressure for NG is 3.5-7.0 in water column (0.87-1.74 kPa) at generator fuel inlet. Required fuel pressure for LP gas is 10-12 in water column (2.49-2.99 kPa) at generator fuel inlet. NOTE: The primary regulator for LP gas sup- ply is NOT INCLUDED with generator. NOTE: All pipe sizing, construction, and lay- out must comply with NFPA 54 for NG applica- tions and NFPA 58 or ICC IFGC for LP gas n applications. Verify fuel pressure NEVER drops below required specification once gen- erator is installed. See the NFPA website at www.nfpa.org for further information regard- ing NFPA requirements. Always contact local fuel suppliers or fire mar- shal to verify codes and regulations for correct installation. Local codes will mandate correct routing of gaseous fuel line piping around gar- dens, shrubs, and other landscaping. Piping strength and connections should be given special consideration for installations in areas at risk for flooding, tornadoes, hurri- canes, earthquakes, and unstable ground. IMPORTANT NOTE: Use an approved pipe sealant or joint compound on all threaded NPT fittings. NOTE: All installed gaseous fuel piping must be purged and leak tested prior to initial startup in accordance with local codes, stan- dards, and regulations. Fuel Conversion Proceed as follows to convert from NG config- uration to LP gas. See Figure 5-1 for fuel conversion knob (A) locations. Orange fuel conversion knob is located beneath fuel mixer on 10 kW units (B) and above fuel mixer on 14 kW-26 kW units (C). To select fuel type, turn fuel conversion knob towards marked fuel source arrow until it stops. Fuel conversion knob will rotate 180° and slide into mixer body when converting to LP gas. NOTE: It may be necessary to remove intake snorkel to access fuel conversion knob on 26 kW units. NOTE: The fuel selection (LP/NG) must be entered on the controller during initial startup using the Install Wizard navigation menu, or in EDIT menu under "Fuel Selection." 014655 Figure 5-1. Fuel Conversion Knob Locations 20 Installation Guidelines for 60 Hz Air -Cooled Generators Fuel Conversion / Gas Connections Fuel Consumption Natural Gas* Propane** Generator 1/2 Load Full Load 1/2 Load Full Load 10kW 2.86/101 3.60/127 0.97/3.66/36 1.48/5.62/54 14 kW 5.52 / 195 7.25 / 256 1.81 / 6.87 / 65 3.07 / 11.61 / 112 18 kW 4.79 / 169 6.99 / 247 1.70 / 6.45 / 62 3.02 / 11.44 / 110 20 kW 4.64 / 164 8.13 / 287 2.36 / 8.95 / 86 3.74 / 14.15 / 136 22 kW 5.78 / 204 9.26 / 327 2.53 / 9.57 / 92 3.90 / 14.77 / 142 24 kW 5.75 / 203 8.66 / 306 2.53 / 9.57 / 92 3.90 / 14.77 / 142 26 kW 5.32 / 188 9.43 / 333 2.06 / 7.78 / 75 3.63 / 13.73 / 132 * Natural gas is in m3/h / ft3/h " Propane is in gal/h (LP) / L/h (LP) / ft3/h (LPV) ** Values given are approximate These are approximate values. Use the appropriate spec sheet or fuel data decal for specific values. Verify gas meter is capable of providing enough fuel flow to include household appliances and all other loads. NOTE: The fuel supply and pipe MUST be sized at 100% load BTU/h (Megajoule/h) rating. Always see fuel data decal for the correct BTU/h or Megajoule/h, and required fuel pressures: - Natural Gas: BTU/h = ft3/h x 1000 Megajoules/h = m3/h x 37.26 - Liquid Propane Gas (Vapor): BTU/h = ft3/h x 2500 Megajoules/h = m3/h x 93.15 Fuel Line Sizing Selecting the correct size fuel line is crucial to Flexible Fuel Line Extensions correct operation of the unit. IMPORTANT NOTE: Generator inlet size DOES NOT dictate size of gas pipe to be used! For further information, see NFPA 54 for NG, or NFPA 58 or ICC IFGC for LP. Measure distance from generator to fuel source on a low pressure gas system. IMPORTANT NOTE: Generator should be plumbed directly from the fuel source through an appropriately sized and cor- rectly placed fuel pressure regulator, not off the end of an existing low pressure sys- tem. Part # Length Interior Diameter 10000006498 24 in (61 cm) 1 in (25 mm) 10000000499 48 in (122 cm) 1 in (25 mm) 10000000500 72 in (183 cm) 1 in (25 mm) 10000009776 48 in (122 cm) 3/4 in (19 mm) 10000009777 72 in (183 cm) 3/4 in (19 mm) 10000009793 24 in (61 cm) 3/4 in (19 mm) Installation Guidelines for 60 Hz Air -Cooled Generators 21 Fuel Conversion / Gas Connections Natural Gas Pipe Sizing To determine correct NG pipe size, find the kW rating of generator in the left column, and trace to the right. The number to the right is maximum length (measured in ft / m) allowed for the pipe sizes on top. Pipe sizes are mea- sured by trade size diameter to include any fit- tings, valves (must be full flow), elbows, tees, or angles. NOTE: See Table B.3.2 in NFPA 54 or Table A.2.2 in the ICC IFGC, Equivalent Lengths of Pipe Fittings and Valves for the correct values to be added to overall fuel piping length. Tables are based on schedule 40 black pipe. If installing any other piping system, follow pipe sizing charts for selected piping system. Table 5-1. NG Pipe Sizing Pipe Size For 5-7 in Water Column (1.24-1.74 kPa) For 3.5-5 in Water Column (0.87-1.24 kPa) (in / mm) Allowable Pipe Distances (ft/m) 0.5/13 0.75/19 1/25 1.25/32 1.5/38 0.75/19 1/25 1.25/32 1.5/38 10 kW 10/3.1 60/18.3 200/61 750/228.6 - 20/6.1 60/18.3 175/53.3 - 14/18 kW - 10/3.1 55/16.7 200/60.9 450/137.1 - 30/9.1 125/38.1 200/61 20 kW - 10/3.1 35/10.7 140/42.3 300/91.4 - 10/3.1 60/18.3 125/38.1 22-26 kW - 10/3.1 30/9.1 115/35.1 250/76.2 - 10/3.1 60/18.3 125/38.1 LP Gas Pipe Sizing To determine correct LP gas pipe size, find the kW rating of generator in the left column, and trace to the right. The number to the right is maximum length (measured in ft / m) allowed for pipe sizes on top. Pipe sizes are measured by trade size diameter to include any fittings, valves (must be full flow), elbows, tees, or angles. See Table B.3.2 in NFPA 54 or Table A.2.2 in the ICC IFGC, Equivalent Lengths of Pipe Fittings and Valves for the correct values to be added to overall fuel piping length. NOTE: Pipe sizes are from the outlet of the second stage regulator to the fuel shutoff valve. Table is based on schedule 40 black pipe. If installing any other piping system, fol- low the pipe size charts for the selected piping system. NOTE: Recommended minimum LP tank size is 250 gal (946 L). Contact LP provider to cor- rectly size LP tank to generator. Vertical tanks, which are measured in pounds (or kilograms), are permitted if correctly sized for the genera- tor. Do not connect generator to a 20 or 30 Ibs LP tank. Table 5-2. LP Gas Pipe Sizing Pipe Size For 10-12 in Water Column (2.49-2.99 kPa) (in / mm) Allowable Pipe Distances (ft/m) 0.5/13 0.75/19 1/25 1.25/32 10 kW 30/9.1 175/53.3 400/121.9 - 14/18 kW - 80/24.4 350/106.7 600/182.9 20-26 kW - 40/12.2 175/53.3 550/167.6 22 Installation Guidelines for 60 Hz Air -Cooled Generators Fuel Conversion / Gas Connections Installing and Connecting Fuel Lines 't Explosion and fire. Fuel and vapors are extremely flammable and explosive. No leakage of fuel is permitted. Keep fire and spark away. Failure to do so will result in death or serious injury. IMPORTANT NOTE: NG and LP gas are highly volatile substances. Strictly adhere to all safety procedures, codes, standards, and regulations. Fuel line connections should be made by a certified contractor familiar with local codes. Always use AGA-approved gas pipe and a quality pipe sealant or joint compound. Verify capacity of NG meter or LP tank to pro- vide sufficient fuel for both the generator and other operating appliances. Fuel Shutoff Valve See Figure 5-2. The generator will require an external manual fuel shutoff valve (A) on the fuel line. NOTE: Fuel shutoff valve must be installed at a readily accessible location, and within 6 ft (1.8 m) of generator fuel inlet. Figure 5-2. Sediment Trap, Fuel Shutoff Valve with Manometer Port, and Flexible Fuel Line Figure 5-3 illustrates a fuel shutoff valve with a manometer port for making fuel pressure checks. This optional accessory fuel shutoff valve permits making pressure checks for diagnostic purposes without going into the generator enclosure. 000743 Figure 5-3. Fuel Shutoff Valve with Manometer Port Fuel shutoff valves available through an IASD: • 1/2 in ball valve, part number OK8752 • 3/4 in ball valve, part number OK8754 • 1 in ball valve, part number OK8184 • 1-1/4 in ball valve, part number OL2844 • 1-1/2 in ball valve, part number OL2845 Flexible Fuel Line See Figure 5-2. When connecting flexible fuel line (B) to generator, use a listed assembly meeting the requirements of ANSI Z21.75/ CSA 6.27—Connectors for Outdoor Gas Appliances and Manufactured Homes or AGA-approved flexible fuel line in accordance with local regulations. Flexible fuel line must not be connected directly to generator fuel inlet. Always connect flexible fuel line to an approved gas fitting. The purpose of flexible fuel line is to isolate vibration from the generator to reduce possi- bility of a gas leak at one of the connection points. Installation of a flexible fuel line is a fuel gas code and installation requirement. NOTE: Follow all installation instructions and warnings provided with the flexible fuel line. Do not remove any labels or tags. Flexible fuel line must be installed horizontally, and must be installed between fuel shutoff valve and generator fuel inlet. Sediment Trap See Figure 5-2. Some local codes require a sediment trap (C). The fuel regulator connec- tion has an integrated sediment trap. The sediment trap must be cleaned periodi- cally according to local codes. See owner's manual for more information. Installation Guidelines for 60 Hz Air -Cooled Generators 23 Fuel Conversion / Gas Connections Checking Fuel Line Connections Checking Fuel Pressure Proceed as follows to check fuel pressure at fuel regulator in the generator. 1. Close fuel supply valve. 2. See Figure 54. Remove top fuel pressure test port from fuel regulator and install fuel pressure tester (manometer). 7 Figure 5-4. Checking Pressure with Manometer 3. Open fuel supply valve and verify fuel pressure is within specified values. 4. Record static fuel pressure: NOTE: Fuel pressure can also be tested at manometer port on fuel shutoff valve shown in Figure 5-2. NOTE: See fuel data decal or spec sheet for correct fuel pressure specifications. Contact local fuel supplier if fuel pressure is not within specifications. 5. Close fuel supply valve when completed. Keep manometer connected for future tests of generator while starting, running, and under loads. Performing Fuel System Leak Test '* B= Explosion and fire. Fuel and vapors are extremely flammable and explosive. No leakage of fuel is permitted. Keep fire and spark away. Failure to do so will result in death or serious injury. , All products are factory -tested before ship- ping to verify the performance and integrity of the fuel system. However, it is important to perform a final fuel system leak test before starting the generator. The entire fuel system should be tested from supply to regulator. See Figure 5-5. Perform a final fuel system leak test after generator installation. The test will identify possible leaks at all connection points (A). It is best practice to perform a fuel system leak test during normally -scheduled mainte- nance. 004038 Figure 5-5. Connection Points to Leak Check Inspect for leaks by spraying all connection points with a non -corrosive gas leak detection fluid. The solution should not be blown away or form bubbles. 24 Installation Guidelines for 60 Hz Air -Cooled Generators Fuel Conversion / Gas Connections Natural Gas Installation (Typical) NG BTU/h = ft3/h X 1000 Megajoules/h = m3/h X 37.26 A Fuel data decal B Minimum distance from rear obstruction —see Distance Requirements C Manual fuel shutoff valve (pressure port optional) Must be located no more than 6 ft (1.83 m) away from fuel inlet D Pipe fittings (field supplied) E Flexible fuel line F Verify clearance with gas provider. Regulator should be a minimum of 5 ft (1.5 m) from gener- ator. Local codes and regulator manufacturer may have further clearance requirements. G Size gas meter for generator operating at FULL load plus all appliance loads H For underground installations, verify piping system for code compliance I Reinforcing rod with clamps J To gas main Figure 5-6. Natural Gas Installation (typical) Installation Guidelines for 60 Hz Air -Cooled Generators 25 Fuel Conversion / Gas Connections LP Gas (Vapor) Installation (Typical) LPG BTU/h = ft3/h X 2500 Megajoules/h = m3/h X 93.15 A Fuel data decal B Minimum distance from rear obstruction —see Distance Requirements C Manual fuel shutoff valve (pressure port optional) Must be located no more than 6 ft (1.83 m) away from fuel inlet. D Pipe fittings (field supplied) E Flexible fuel line F Verify minimum distance requirements for regulator vent according to local gas codes. Regu- lator should be a minimum of 5 ft (1.5 m) from generator. Local codes and regulator manufac- turer may have further clearance requirements. G Clamp H Secondary fuel pressure regulator J Manual shutoff valve K Primary fuel pressure regulator L Fuel tank —sized large enough to provide required MJ/BTU for generator operating at FULL load and ALL connected appliance loads. Be sure to correct for weather evaporation. Figure 5-7. LP Gas (Vapor) Installation (typical) 26 Installation Guidelines for 60 Hz Air -Cooled Generators Fuel Conversion / Gas Connections This page intentionally left blank. Installation Guidelines for 60 Hz Air -Cooled Generators 27 Electrical Connections Section 6: Electrical Connections Generator Connections See Figure 6-1. The electrical wiring enclosure is located behind an access panel on intake end of unit. Remove intake side panel as directed in Intake Side Panel Removal, and then remove access panel. Connect wires according to diagram and tables. 1. Remove main AC / control wiring knock- out plugs from back of generator. 2. Using appropriate wiring hole, install con- duit and main AC and control wires between generator and transfer switch. 3. Close unused hole with a NEMA 3R rated plug (field -supplied). NOTE: All conductors must be rated for mini- mum 300V. Control system interconnections may consist of N1, N2, and T1, and leads 23 and 194. All of the generator control wiring cir- cuits are Class 1 remote control or signaling circuits. Class 1 circuits are required to be installed in accordance with Part 1 of NEC Article 300 and with a NEC recognized Chap- ter 3 wiring method. The use of low voltage cables for the generator control circuit wiring is prohibited. See instruction manual of the specific engine generator for wiring connec- tion details. Recommended wire gauge sizes for this wiring depends on wire length, as rec- ommended in Table 6-3. Exception: Conductors of AC and DC cir- cuits, rated 1000 volts nominal or less, shall be permitted to occupy the same equipment, cable, or conduit. All conductors shall have an insulation rating equal to at least the maxi- mum circuit voltage applied to any conductor within the equipment, cable, or conduit. See NEC 300.3(C)(1). 4. See Figure 6-1. Strip insulation from wire ends. Do not remove excessive insulation. Route sense wires through supplied wire tie (Cl), and connect to sense wire termi- nal block (B). Push down on spring loaded connection point with a flat head screw- driver, insert wire, and release. 5. Using the same process, route control wires through second supplied wire tie (C2), and connect to control wire terminal block (A). 6. When all wires are securely connected to correct terminals, tighten wire ties and clip excess length. NOTE: Only bare wire should be inserted into each terminal. Do not insert any wire insula- tion into terminals. NOTE: Damage caused by mis-wiring of the interconnect wires is not warrantable. 28 Installation Guidelines for 60 Hz Air -Cooled Generators Electrical Connections Control Wiring Figure 6-1. Electrical Wiring Connections 005810 Table 6-1. Electrical Wiring Connection Points ID Description ID Description ID Description A Control wire terminal block D Neutral lug G Ground lug B Sense wire terminal block E1 Power lug E1 H Neutral stud C1 Wire tie for sense wires E2 Power lug E2 J Neutral bar C2 Wire tie for control wires F Ground stud — — Table 6-2. Customer Wiring Connections Terminal Wire Numbers No. Decal N1 & N2 - 240 VAC - Sensing YELLOW for utility dropout and pickup T1 - Fused 120 VAC for bat- BLUE * tery charger BLACK ** 0 - DC (-) Common ground wire RED 194 - DC (+) 12 VDC for trans- fer controls 23 - Transfer control signal WHITE wire Table 6-3. Control Wire Recommended Length and Size (Copper Conductors Only) Maximum Wire Length Recommended Wire Size 1-115 ft (0.3-35 m) No. 18 AWG 115-185 ft (35-56 m) No. 16 AWG 185-295 ft (56-89 m) No. 14 AWG 295-460 ft (89-140 m) No. 12 AWG * Must be connected to keep battery charged whether unit is running or not. ** Required if generator is paired with optional Digital Power Management (DPM) smart technology. Installation Guidelines for 60 Hz Air -Cooled Generators 29 Electrical Connections Table 6-4. Ground and Neutral Connections (Copper or Aluminum Conductors) See national and/or local codes to verify correct wire sizes. # Description Recommended Wire Size Torque Spec 1 Power wire 2/0 to 8 AWG 120 in-Ibs terminals (13.56 Nm) 2 Large neutral 2/0 to 14 AWG 120 in-Ibs lug (13.56 Nm) 3 Large ground 2/0 to 14 AWG 120 in-Ibs lug (13.56 Nm) 4-6 AWG 35 in-Ibs (3.95 Nm) 4 Neutral bus 8 AWG 25 in-Ibs bar (2.82 Nm) 10-14 AWG 20 in-Ibs (2.26 Nm) Main AC Wiring NOTE: Main AC wiring must be in accordance with local jurisdiction and codes. NOTE: Raceway connections to the generator must be flexible. Ridged raceway connections to the generator are only permitted where approved expansion fittings are installed. NOTE: If used, splices must be rated for mini- mum 167 °F (75 °C) (copper or aluminum). NOTE: Generator lugs are rated at 167 °F (75 °C), copper or aluminum. 1. Strip insulation off wire ends. Do not remove excessive insulation. 2. See Figure 6-1. Loosen lugs at neutral (D), ground (G), and power wire (mains) termi- nals (El, E2). 3. Connect ground wire to ground lug and tighten to required specification. See Table 6-4. 4. Connect neutral wire to neutral lug, if appli- cable. Tighten to required specification. See Table 6-4. 5. Insert power wires (El and E2) into their corresponding lugs. Tighten to required specification. 6. Verify factory -installed ground array and neutral connections are correctly tightened to 25 in-Ibs (2.82 Nm). NOTE: Neutral wire must remain connected to keep battery charged whether generator is running or not. NOTE: Neutral bonding — For installations requiring neutral to be bonded to ground, this is done on the customer connections termi- nals inside generator. See Figure 6-1. Connect a suitably sized sys- tem bonding jumper in accordance with NEC Table 250.102(C)(1) from neutral bar (J) to ground stud (F). Tighten ground stud nut to 35 in-Ibs (3.95 Nm). This is required when gen- erator is installed as a separately derived sys- tem. Generator will also require a connection to a grounding electrode system in accor- dance with NEC Article 250.64. It is not required when generator is a backup source in a utility supplied electrical system with a 2- pole transfer switch. Installation must be made in accordance with NEC Articles 250.30 and 250.35(A) if generator will be installed as a separately derived system. NOTE: Tighten all wiring lugs, bus bars, and connection points to required torque specifica- tions. Conductors of AC and DC circuits, rated 1,000 volts nominal or less, shall be permitted to occupy the same equipment, cable, or con- duit. All conductors must have an insulation rating equal to at least the maximum circuit voltage applied to any conductor within the equipment, cable, or conduit. See NEC 300.3(C)(1). Service Entrance Decals See Figure 2-10. Locate service entrance - related decals in the loose parts bag. • Place service disconnect decal next to gen- erator MLCB (generator disconnect) (if required by local codes). • Place service entrance warning decal in an appropriate location according to instruc- tions printed on the decal. Common Alarm Relay (Option) Alarms relating to generator and engine per- formance appear on the controller and in the Mobile LinkR application (if used). The control- ler is equipped with a common alarm relay, providing contacts for an optional customer - supplied external alarm indicator. The common alarm relay is normally open until an alarm occurs, triggering relay to close contacts. Terminals for common alarm relay are pro- vided in the wiring harness near the controller plug (Wires 209 and 210). Contact rating is for resistive load only: Contact rating 200 mA at 12 VDC 30 Installation Guidelines for 60 Hz Air -Cooled Generators Electrical Connections Battery Requirements 12 volts, Group 26R Wet Cell 540CCA mini- mum, or Group 35 AGM 650CCA minimum. Recommended part number O1-13421S. NOTE: Do not use external battery chargers. Battery Installation 44 AWARNING Explosion. Batteries emit explosive gases while charging. Keep fire and spark away. Wear protective gear when working with batteries. Failure to do so could result in death or serious injury. ® AWARNING Risk of burns. Batteries contain sulfuric acid and can cause severe chemical burns. Wear protective gear when working with batteries. Failure to do so could result in death or serious injury. (000138a) AWARNING Explosion. Batteries emit explosive gases. Always connect positive battery cable first to avoid spark. Failure to do so could result in death or serious injury. (000133) �® AWARNING Risk of burn. Do not open or mutilate batteries. Batteries contain electrolyte solution which can cause burns and blindness. If electrolyte contacts skin or eyes, flush with water and seek immediate medical attention. (000163a) • (Unsealed 26R batteries only): Fill battery with the correct electrolyte fluid, if neces- sary. • Fully charge battery before installing it. Complete the following steps before installing and connecting battery: 1. Verify generator is OFF. 2. Turn off utility power supply to transfer switch. 3. Remove 7.5A fuse from generator control panel. Connecting the Battery AWARNING Explosion. Batteries emit explosive gases. Always connect positive battery cable first to �--� avoid spark. Failure to do so could result in death or serious injury. (000133) L 4 ACAUTIONA Equipment damage. Do not make battery connections in reverse. Doing so will result in equipment damage. See Figure 6-2. Battery cables (A, B) were fac- tory connected at the generator. 001832 Figure 6-2.Battery Cable Connections Proceed as follows to connect battery cables to battery posts: Connect red positive battery cable (A: from starter contactor) to positive battery post. Tighten to 70 in-Ibs (8 Nm). Connect black negative battery cable (B: from frame ground) to negative battery post. Tighten to 70 in-Ibs (8 Nm). Install red battery post cover (shipped with loose parts). NOTE: Apply dielectric grease to battery posts to prevent corrosion. NOTE: In areas where temperatures fall below 0 °F (-18 °C), a pad type battery warmer is recommended to aid in cold climate starting. The battery warmer is available as part of a cold weather kit (PN: G007101-0) from any IASD. NOTE: A battery warmer is not necessary for AGM -style batteries. Battery Disposal AWARNING Environmental Hazard. Always recycle batteries at an official recycling center in accordance with all local laws and regulations. Failure to do so could result in environmental damage, death, or serious injury. (000228) Always recycle batteries in accordance with local laws and regulations. Contact your local solid waste collection site or recycling facility to obtain information on local recycling pro- cesses. For more information on battery recy- cling, visit the Battery Council International website at: http://batterycouncil.org. Installation Guidelines for 60 Hz Air -Cooled Generators 31 Control Panel Startup / Testing Section 7: Control Panel Startup / Testing Control Panel Interface The control panel interface is located under the enclosure lid. Verify both left and right side locks are unlocked before attempting to lift enclosure lid. Open lid as directed in Opening the Lid. Using the AUTO/OFF/MANUAL Buttons Button Description of Operation Activates fully automatic system operation. Automatic operation AUTO allows unit to automatically start and exercise generator according to exercise timer settings (see Set- ting The Exercise Timer). Shuts down engine and also pre - OFF vents automatic operation and exercise of unit. Cranks and starts generator. MANUAL Transfer to standby power will not occur unless there is a utility fail- ure. a AUTO ZEEN777ANWAL a OFF 0 OO o Q ENTER ESCAPE 000425 Figure 7-1. Generator Control Panel Generator Setup The controller illuminates when battery power is applied to generator during the installation process. Generator must be acti- vated before it will automatically run in the event of a power outage. Activation To activate the generator, go to www.activat- egen.com and follow the instructions. Activation is a simple, one-time process. The generator will not prompt to activate again once the unit is activated, even if the genera- tor battery, fuse, and battery charge circuit (T1) are disconnected. NOTE: The generator must be connected to the home Wi-Fi network for automatic authentication to be completed successfully. See Wi-Fi manual for more information. NOTE: If home Wi-Fi network is not available, follow instructions on www.activategen.com. Proceed as follows after activating generator on-line: 1. The display interface will launch Install Wizard upon first power -up of the generator. 2. Follow on -screen instructions on the gen- erator along with Quick Start Guide sup- plied with the unit to connect generator to home Wi-Fi network. 3. Wait for on-line authentication of generator activation through connected home Wi-Fi network. 4. Follow on -screen instructions to complete the Install Wizard. NOTE: See Figure 7-2. If generator screen shows message shown below, press ESC and then ENTER to reset to Install Wizard. NOT ACTIVATED! XXX (H) AUTO a MANQDA� a ®FF OD >> ENTER ESCAPE 009102 Figure 7-2. Not Activated Screen NOTE: Generator can only be placed in AUTO mode after completing activation process. IMPORTANT NOTE: Fuel selector knob must be set to the correct fuel for genera- tor to function correctly. 32 Installation Guidelines for 60 Hz Air -Cooled Generators Control Panel Startup / Testing Display Reads Troubleshooting Language English + Use arrow keys to scroll to desired Ian- Language can be a AUr® a wNUAL� 0 O 'W147 guage. Press ENTER to changed later using the EDIT menu. ENTER ESCAPE select. 002227 Enable Wi-Fi? - Yes + Use arrow keys to either enable or dis- c AUTO a MANUAL a ®fF able Wi-Fi. If YES, see Wi-Fi manual. ENTER ESCAPEIf NO, continue. 004498 If ESCAPE is pressed Activate me (ENT) or instead of ENTER, gener- ESC to run in manual ator will only run in man - Press ENTER to ual mode (for test a AUTO a MANUAL� O 0 begin activation pro- cess. purposes) and NOT ACTIVATED will be dis- ENTER played. Press ESC and ESCAPE then ENTER to reset 002228 Install Wizard. To Activate go to If unit has not been www.activategen.com activated, go to www.activate- gen.com If unit has been acti- 77+>CO2229 vated, press ESC and then ENTER. Installation Guidelines for 60 Hz Air -Cooled Generators 33 Control Panel Startup / Testing Display Reads Troubleshooting Select Hour(0-23) Activation is com- plete when this a AUTO a 6WANU AL a ®�� screen is displayed. Follow controller O O prompts to complete MN4tK FSCAPF installation. 002231 Cold Smart Start The Cold Smart Start feature is factory - enabled, and can be disabled in the EDIT menu. Generator will monitor ambient tem- perature and adjust its warm-up delay accordingly when Cold Smart Start is enabled. If ambient temperature is below a fixed temperature upon startup in AUTO mode (per chart below), generator will warm up for 30 seconds, allowing engine to warm before load is applied. If ambient temperature is at or above fixed temperature, generator will start up with normal warm-up delay of six seconds. See Cold Smart Start section in owner's manual. Table 7-1. Cold Smart Start Set Points Generator Size 10-20 kW 22-26 kW 50 °F 20 °F Fixed Temperature °C) °C) (10 (-7 Setting The Exercise Timer This generator is equipped with a configu- rable exercise timer. There are two settings for the exercise timer: • Day/Time: Generator will start and exercise for period defined, on day of week and at time of day specified. During this exercise period, unit runs for five minutes on all mod- els, and then shuts down. • Exercise frequency (how often exercise will take place): Can be set to Weekly, Biweekly, or Monthly. If Monthly is selected, day of the month must be selected from 1- 28. Generator will exercise on that day each month. Transfer of loads to generator output does not occur during exercise cycle unless utility power is lost. NOTE: If installer tests generator prior to installation, press ENTER button to skip set- ting up exercise timer. NOTE: The exercise feature will operate only when generator is placed in AUTO mode, and will not work unless this procedure is per- formed. If Wi-Fi is not enabled, current date/ time must be reset every time power is removed from controller via the controller fuse and T1 circuit and/or battery connections. NOTE: If Wi-Fi is enabled, exercise timer will automatically adjust for Daylight Saving Time. NOTE: If using Wi-Fi feature, exercise time will be set to a random weekday during day- light hours. This setting can be changed later. See Wi-Fi manual for details. Before Initial Startup ACAUTION Engine damage. Verify proper type and quantity of engine oil prior to starting engine. Failure to do so could result in engine damage. (000135) NOTE: The unit comes filled with 5W-30 weight organic oil from the factory. Check oil level and add appropriate viscosity and amount of oil if necessary. After the 25 hour break-in period, it is recom- mended to use Generac's proprietary 5W-20 gaseous engine oil (GEO) for continuous use. It is specifically formulated for use in gaseous powered Generac generators. Install Wizard See Figure 7-3. The Install Wizard immedi- ately appears upon initial startup. It allows user to input generator settings. The Install Wizard starts every time AC and DC power are removed and reapplied to gen- erator. 34 Installation Guidelines for 60 Hz Air -Cooled Generators Control Panel Startup / Testing Interconnect System Self Test Feature This controller goes through a system self test at startup, which checks for utility voltage on DC circuits. This test prevents damage if installer incorrectly connected AC utility power sense wires into the DC terminal block. The controller will display a warning message and lock out the generator if utility voltage is detected at the DC terminal block, preventing damage to the controller. Power to controller must be removed to clear this warning. Utility voltage must be turned on and present at the N1 and N2 terminals inside the genera- tor control panel for this test to be performed and pass. NOTE: All appropriate panels must be in place during any operation of generator. This includes operation by a servicing technician, while conducting troubleshooting procedures. Before starting, complete the following: 1. Verify generator is OFF. 2. Set generator MLCB (generator discon- nect) to OFF (OPEN). 3. Turn OFF all breakers to be supplied by generator. 4. Verify auxiliary shutdown switch(es) are CLOSED (1). 5. Check engine crankcase oil level and, if necessary, fill to oil dipstick FULL mark with recommended oil. Do not overfill. 6. Inspect fuel supply. Gaseous fuel lines must have been correctly purged and leak tested in accordance with applicable fuel - gas codes. All fuel shutoff valves in the fuel supply lines must be open. During initial startup only, generator may exceed normal number of start attempts and experience an "OVERCRANK" fault. This is due to accumulated air in the fuel system during installation. Reset control board by pressing OFF mode button and ENTER but- ton, and restart up to two more times if nec- essary. If unit fails to start, contact an IASD for assistance. Installation Guidelines for 60 Hz Air -Cooled Generators 35 a Note: If language was previously programmed this goes directly to "Select Hour' Power Up Unit FIRMWARE V X.XX HARDWARE V X.XX Language + English - Install Wizard + Espanol - + Francais - + Portuguese Defaults to English. + ...... Select desired language by scrolling through list. ENTER Setup Wi-Fi? Yes Follow setup WIFI Signal XX% + Yes or No - process in manual No Use UP and DOWN Fuel Selection "' arrows to select fuel type, + NG or LP - then press "ENTER". V Use UP and DOWN arrows. Cold Smart Start? ---' -to select YES or NO. F YES or NO 4 Press ENTER. Select Hour (0-23) *Holding the Up or Down arrow button for 2 seconds - 14 + * will speed dial through the selections ENTER 1 a AUTO ® MANUAL a OFF UP ARROW = + Q O O ENTER Fuel Selection + NG or LP - Exercise Time HH:MM Day Biweekly ENTER Update From: WIFI <Enter> to Begin :ENTER ESC SYSTEM DATE/TIME WIFI SUB MENUS ENTER i ENTER Install Wizard f Set Exercise... DOWN ARROW = - Cold Smart Start? F YES or NO 4 ENTER Time Zone XXXXXX WIFI Signal XX% ENTER Update From Server Continue? (ENTER ontroller X.XX.XX: Server X.XX.XXX 006668 n 0 Z5 o_ v m sv c m a N v O 7 G) CL m Z (D U) O O') 0 2 N D C) O O (D Q t7 (D 7 (D N O U) W v ENTER 1 Select Minute (0-59) ENTER Select Month (1-12) ENTERS Select Date (1-31) ENTERS Select Year (0-99) - 0 + * - 2 + * - 13 + * - 13 + f ESC SYSTEM DATE/TIME USB Only —No WiFi <Enter> to Begin SETUP WIFI SUB MENUS ENTER ENTER t 1 Switched to OFF Firmware Update Hours of Protection <- Insert USB -> 0 (H) Possible Message(s): Corrupted File TENTER 1 —ENTER Exercise Time Install Wizard HH:MM Day Biweekly Set Exercise... Controller assigns -- random date and time for biweekly exercise. --k ENTER Current: V X.XX ENTER Are You Sure? USB: X.XX - Yes or No + ENTER 1 Invalid File Select "Yes' then Press "Enter" to continue or Press "ESCAPE" to escape out of updating. File Not Found Unsupported Device' During update process the Blue "Manual' light flashes, then the Green "Auto' light flashes. Sequence does this twice. When update is complete the unit returns to Install Wizard menu. * using a higher quality dri USBSB drive. File names on the USB When the controller powers up the very first screen displays the version number for a few seconds. cannot have more than 8 characters. When update is complete remove Thumb Drive, then follow the Install Wizard Menu. 006668 Control Panel Startup / Testing Checking Manual Transfer Switch Operation �A 0= Electrocution. High voltage is present at transfer switch and terminals. Contact with live terminals will result in death or serious injury. See Manual Transfer Operation section of owner's manual for procedures. Electrical Checks �Jk 0= Electrocution. High voltage is present at transfer switch and terminals. Contact with live terminals will result in death or serious injury. (000129) Proceed as follows to complete electrical checks: 1. Verify generator is in OFF mode. 2. Set generator MLCB (generator discon- nect) to OFF (OPEN). 0 4. 5. 6. VA Turn off all circuit breakers/electrical loads to be supplied by generator. Turn on utility power supply to transfer switch using means provided (such as a utility MLCB). Use a calibrated AC voltmeter to verify util- ity power source voltage across transfer switch terminals N1 and N2. Nominal line - to -line voltage should be 240 volts AC. If voltage is incorrect, verify AC output and wiring from utility source to N1 and N2 lugs at transfer switch. Verify utility power source voltage across terminals N1 and transfer switch neutral lug; then across terminal N2 and neutral. Nominal line -to -neutral voltage should be 120 volts AC (if wired with a neutral). If voltage is incorrect, verify AC output and wiring from utility source to N1 and N2 lugs at transfer switch. Turn off utility power supply to transfer switch when utility supply voltage is veri- fied to meet specification provided in Step 6. 8. Press MANUAL mode button on generator panel. The engine will crank and start. Record cranking fuel pressure: 9. Allow engine to warm up for approximately five minutes for internal temperatures to stabilize. Then set generator MLCB (gen- erator disconnect) to ON (CLOSED). Record running fuel pressure: 10. Connect a calibrated accurate AC voltme- ter and a frequency meter across transfer switch terminal lugs E1 and E2. Voltage should be 238-242V at a frequency of 59.5-60.5 Hz. If voltage is incorrect, verify generator MLCB (generator disconnect) is closed, and verify AC output and fre- quency (Hertz or Hz) at generator MLCB (generator disconnect). Verify wiring from generator to E1 and E2 lugs at transfer switch. 11. Connect AC voltmeter test leads across terminal lugs E1 and neutral, then across E2 and neutral (if wired with a neutral). In both cases, voltage reading should be 119-121 volts AC. If voltage is incorrect, verify generator MLCB (generator discon- nect) is closed, and verify AC output between E1 and E2 of generator MLCB (generator disconnect) and neutral at gen- erator. 12. Verify wiring from generator to E1, E2, and neutral lugs at transfer switch. 13. Set generator MLCB (generator discon- nect) to OFF (OPEN). 14. Press generator OFF mode button. The engine will shut down. IMPORTANT NOTE: DO NOT proceed until generator AC voltage and frequency are correct and within stated limits. Generator Tests Under Load NAElectrocution. Do not manually transfer under load. Disconnect transfer switch from all power sources prior to manual transfer. Failure to do so will result in death or serious injury, and equipment damage. (000132) Proceed as follows to test generator with electrical loads applied: 1. Verify generator is in OFF mode. 2. Set generator MLCB (generator discon- nect) to OFF (OPEN). 3. Turn off all circuit breakers/electrical loads to be supplied by generator. 4. Turn off utility power supply to transfer switch using means provided (such as a utility MLCB). 5. Manually set transfer switch to STANDBY, with load terminals connected to genera- tor's E1/E2 terminals. Transfer switch operating lever should be down. 6. Press generator MANUAL button. Engine will crank and start immediately. 7. Verify fuel pressure while cranking. Record cranking fuel pressure: 8. Allow engine to stabilize and warm up for a few minutes. 38 Installation Guidelines for 60 Hz Air -Cooled Generators Control Panel Startup / Testing 9. Verify fuel pressure while running. Record running fuel pressure: 10. Set generator MLCB (generator discon- nect) to ON (CLOSED). Loads are now powered by standby generator. 11. Turn on circuit breakers/electrical loads to be supplied by generator one by one. 12. Connect a calibrated AC voltmeter and a frequency meter across terminal lugs E1 and E2. Voltage should be approximately 240 volts and frequency should be approx- imately 60 Hz. If voltage and frequency are rapidly dropping as loads are applied, generator may be overloading, or there may be a fuel issue. Verify output current measurement of loads and/or fuel pres- sure. 13. Allow generator to run at full rated load for 20-30 minutes. Listen for unusual noises, vibration, or other indications of abnormal operation. Inspect for oil leaks, evidence of overheating, etc. 14. Verify fuel pressure while under full load. Record loaded fuel pressure: 15. Turn off circuit breakers/electrical loads when testing under load is complete. 16. Set generator MLCB (generator discon- nect) to OFF (OPEN). 17. Allow engine to run at no-load for 2-5 min- utes. 18. Press generator OFF button. Engine will shut down. NOTE: If fuel pressure under full load is below minimum operating fuel pressure guideline, generator may not function correctly. The fuel pressure gauge needle should also remain steady while testing. A fluctuating fuel pres- sure gauge needle indicates gas piping may be undersized or restricted. It may also indi- cate a step-down gas regulator is too small, or too close to unit. Checking Automatic Operation Proceed as follows to check system for cor- rect automatic operation: 1. Verify generator is OFF. 2. Install front cover of transfer switch. 3. Turn on utility power supply to transfer switch using the means provided (such as a utility MLCB). NOTE: Transfer switch will transfer to utility position. 4. Set generator MLCB (generator discon- nect) to ON (CLOSED). 5. Press generator AUTO button. The system is now ready for automatic operation. 6. Turn off utility power supply to transfer switch. The generator is ready for automatic opera- tion. The engine will crank and start when utility source power is turned off after a five second delay (factory default setting). After starting, transfer switch will connect load cir- cuits to the standby side after a 5 or 30 sec- ond delay (dealer programmable). See Cold Smart Start. Allow system to operate through entire automatic sequence of operation. With generator running and loads powered by generator AC output, turn on utility power supply to transfer switch. The following will occur: After approximately 15 seconds (dealer programmable), the transfer switch will transfer loads to the utility power source. Approximately one minute after transfer, engine will shut down. Installation Summary 1. Verify installation has been performed correctly as outlined by the manufacturer and that it meets all applicable laws and codes. 2. Test and verify correct operation of the system as outlined in the appropriate installation and owner's manuals. 3. Educate end -user on correct operation, maintenance, and service call procedures. Shutting Generator Down While Under Load or During a Utility Outage Automatic start-up. Disconnect utility power and render unit inoperable before working on unit. Failure to do so will result in death or serious injury. (000191) IMPORTANT NOTE: To avoid equipment damage, follow these steps, in order, during utility outages. Shutdowns may be required during utility outages to perform routine maintenance or to conserve fuel. To turn generator OFF: 1. Set utility MLCB to OFF (OPEN). 2. Set generator MLCB (generator discon- nect) to OFF (OPEN). 3. Allow generator to run for cool -down for approximately one minute. 4. Set generator to OFF at the controller. 5. Remove 7.5A fuse from controller. To turn generator back ON: 1. Install 7.5Afuse in controller. Installation Guidelines for 60 Hz Air -Cooled Generators 39 Control Panel Startup / Testing 2. Verify generator MLCB (generator discon- nect) is OFF (OPEN). 3. Set generator to AUTO mode at the con- troller. 4. Generator will start and run. Allow genera- tor to run and warm up for a few minutes. 5. Set generator MLCB (generator discon- nect) to ON (CLOSED). 6. Set utility MLCB to ON (CLOSED). The system now operates in automatic mode. 40 Installation Guidelines for 60 Hz Air -Cooled Generators Troubleshooting Section 8: Troubleshooting Generator Troubleshooting Problem Cause Correction Correct short circuit condition by Blown fuse. replacing 7.5A fuse in generator control panel. Contact an IASD if fuse continues to blow. Engine will not Loose, corroded, or faulty battery crank cables. Tighten, clean, or replace as necessary.* Faulty starter contact. Faulty starter motor. Discharged battery. Charge or replace battery. No fuel. Replenish fuel / turn on fuel shutoff valve. High fuel pressure. Check and adjust fuel pressure. Set fuel conversion valve to correct Fuel selector in wrong position. position and program controller for fuel Engine cranks type, if necessary. but will not Faulty fuel solenoid (FS). start Contact an IASD for assistance. Harness/wiring issue. Faulty spark plug(s). Replace spark plug(s). Valve clearance out of adjustment. (If applicable. See Specification section Inspect and adjust valve clearance. in owner's manual.) Plugged or damaged air cleaner. Inspect and clean or replace air cleaner. Faulty spark plug(s). Replace spark plug(s). Verify fuel pressure to fuel regulator is Incorrect fuel pressure. 10-12 in water column (2.49-2.99 kPa) for LP, and 3.5-7.0 in water column Engine starts (0.87-1.74 kPa) for NG. hard and runs Set fuel conversion valve to correct rough Fuel selector in wrong position. position and program controller for fuel type, if necessary. Valve clearance out of adjustment. (If applicable. See Specification section Inspect and adjust valve clearance. in owner's manual.) Internal engine issue. Contact an IASD for assistance. Installation Guidelines for 60 Hz Air -Cooled Generators 41 Troubleshooting Problem Cause Correction Unit is set to Controller wired incorrectly. OFF, but engine Contact an IASD for assistance. continues to Faulty control board. run Generator MLCB (generator Set generator MLCB (generator No AC output disconnect) is OFF (OPEN). disconnect) to ON (CLOSED). from Generator internal failure. Contact an IASD for assistance. generator Engine may be warming up. See Cold Smart Start. Check controller screen to verify status. Generator MLCB (generator Set generator MLCB (generator disconnect) is OFF (OPEN). disconnect) to ON (CLOSED). Faulty transfer switch coil. No transfer to Faulty transfer relay. standby after utility source Contact an IASD for assistance Transfer relay circuit open. failure Faulty control logic board. Engine may be warming up. See Check controller screen to verify status. Cold Smart Start. Adjust oil to correct level. See checking Excessive engine oil. engine oil level section in owner's manual. Unit Faulty engine breather. Contact an IASD for assistance consumes large amounts Incorrect type or viscosity of oil. See engine oil requirements in owner's of oil manual. Damaged gasket, seal, or hose. Inspect for oil leaks. Restricted air filter. Replace air filter. Wi-Fi network connection Various. See Wi-Fi module owner's manual. broken or intermittent * Contact an IASD or visit www.generac.com for assistance. 42 Installation Guidelines for 60 Hz Air -Cooled Generators Quick Reference Guide Section 9: Quick Reference Guide System Diagnosis To clear an active alarm, press ENTER button twice and then press AUTO. If alarm reoccurs, contact an IASD. Active Alarm LED Problem Action Solution Check Unit running in generator Check generator MLCB NONE FLASHING AUTO but no MLCB (generator disconnect). If it GREEN power in house. (generator is ON, contact an IASD. disconnect). Inspect ventilation around HIGH Unit shuts down Check LED's / generator, intake, exhaust, RED during Screen for and rear of generator. If no TEMPERATURE operation. alarms. obstructions are present, contact an IASD. Clear alarm and remove OVERLOAD Unit shuts down Check LED's / household loads from RED during Screen for REMOVE LOAD generator. Put back in operation. alarms. AUTO and restart. Clear alarm and remove Unit was household loads from running and Check LED's / RPM SENSE generator. Put back in LOSS RED shuts down, Screen for AUTO and restart. If attempts to alarms. generator does not start, restart. contact an IASD. Unit will not Verify if screen NOTACTIVATED NONE start in AUTO says unit not See Activation. with utility loss. activated. Unit will not Check screen If startup delay is greater NONE GREEN start in AUTO for start delay than expected, contact an IASD to adjust between 2 to with utility loss. countdown. 1500 seconds. Unit will not Check LED's / Check oil level and add oil LOW OIL RED start in AUTO Screen for as needed. If oil level is PRESSURE with utility loss. alarms. correct, contact an IASD. Clear alarm. Using control panel, check battery by navigating to BATTERY Unit will not Check LED's / MENU option from MAIN RPM SENSE RED start in AUTO Screen for MENU. If battery condition LOSS with utility loss. alarms. displays GOOD, contact an IASD. If control panel displays CHECK BATTERY, replace battery. Installation Guidelines for 60 Hz Air -Cooled Generators 43 Quick Reference Guide Active Alarm LED Problem Action Solution Verify fuel line shutoff valve Unit will not Check LED's / is ON. Clear alarm. Start OVERCRANK RED start in AUTO Screen for unit in MANUAL. If it does with utility loss. alarms. not start, or starts and runs rough, contact an IASD. Clear alarm and remove Unit will not Check LED's / LOW VOLTS household loads from RED start in AUTO Screen for REMOVE LOAD generator. Put into AUTO with utility loss. alarms. and restart. Unit will not Check LED's / OVERSPEED RED start in AUTO Screen for Contact an IASD. with utility loss. alarms. Unit will not Check LED's / UNDERVOLTAGE RED start in AUTO Screen for Contact an IASD. with utility loss. alarms. Unit will not Check LED's / UNDERSPEED RED start in AUTO Screen for Contact an IASD. with utility loss. alarms. Unit will not Check LED's / STEPPER RED start in AUTO Screen for Contact an IASD. OVERCURRENT with utility loss. alarms. Unit will not Check LED's / WIRING ERROR RED start in AUTO Screen for Contact an IASD. with utility loss. alarms. Unit will not Check LED's / OVERVOLTAGE RED start in AUTO Screen for Contact an IASD. with utility loss. alarms. Check auxiliary AUXILIARY Unit will not Set auxiliary shutdown RED shutdown SHUTDOWN start. switch(es) to CLOSED (I). switch(es). Clear alarm. Using control panel, check battery by navigating to BATTERY Yellow LED Check screen MENU option from MAIN LOW BATTERY YELLOW illuminated in for additional MENU. If battery condition any state. information. displays GOOD, contact an IASD. If control panel displays CHECK BATTERY, replace battery. Yellow LED Check screen BATTERY YELLOW illuminated in for additional Contact an IASD. PROBLEM any state. information. Yellow LED Check screen CHARGER YELLOW illuminated in for additional Contact an IASD. WARNING any state. information. 44 Installation Guidelines for 60 Hz Air -Cooled Generators Quick Reference Guide Active Alarm LED Problem Action Solution Yellow LED Check screen CHARGER YELLOW illuminated in for additional Contact an IASD. MISSING AC any state. information. Yellow LED Check screen Perform SERVICE A SERVICE A YELLOW illuminated in for additional maintenance. Press ENTER any state. information. to clear. Yellow LED Check screen Perform SERVICE B SERVICE B YELLOW illuminated in for additional maintenance. Press ENTER any state. information. to clear. Yellow LED Check screen INSPECT Inspect battery. Press YELLOW illuminated in for additional BATTERY ENTER to clear. any state. information. Installation Guidelines for 60 Hz Air -Cooled Generators 45 Accessories Section 10: Accessories Performance enhancing accessories are available for air-cooled generators. Accessory Description Cold Weather Accessories*— • Battery Pad Warmer • Recommended in areas where temperatures fall below 0 °F (- 18 °C). (Not necessary for use with AGM -style batteries) • Oil Warmer • Recommended in areas where temperatures fall below 0 °F (- 18 °C). • Breather Warmer • Recommended in areas where heavy icing occurs. * each sold separately Scheduled Maintenance Kit Provides all items necessary to perform complete routine main- tenance on a generator, along with oil recommendations (oil not included). Fascia Base Wrap The fascia base wrap snaps together around the bottom of the new air-cooled generators. This offers a sleek, contoured appearance as well as offering protection from rodents and insects by covering lifting holes located in the base. Requires use of the mounting pad shipped with the generator. Touch -Up Paint Kit If the generator enclosure is scratched or damaged, it is import- ant to touch-up the paint to protect from future corrosion. The touch-up paint kit includes the necessary paint to correctly main- tain or touch-up a generator enclosure. Extended Warranty Coverage Extend generator warranty coverage by purchasing extended warranty coverage. Covers both parts and labor. Extended cov- erage can be purchased within 12 months of end -users pur- chase date. This extended coverage is applicable to registered units, and end -user proof of purchase must be available upon request. Available for Generac® and Guardian® products. Not available for Corepower TM, PowerPacP, or EcoGenTM prod- ucts, or all international purchases. LTE LP Tank Fuel Level The LTE enabled LP tank fuel level monitor provides constant Monitor monitoring of the connected LP fuel tank. Monitoring the LP tank's fuel level is an important step in verifying the generator is ready to run during an unexpected power failure. Status alerts are available through a free application to notify users when the LP tank needs a refill. Mobile Link® Cellular Mobile Link family of Cellular Accessories allow users to monitor Accessories generator status from anywhere in the world, using a smart - phone, tablet, or PC. Easily access information such as the cur- rent operating status and maintenance alerts. Users can connect an account with an authorized service dealer for fast, friendly, and proactive service. With Mobile Link, users are taken care of before the next power outage. 46 Installation Guidelines for 60 Hz Air -Cooled Generators Accessories Smart Management Module Smart Management Modules (SMM's) are used to optimize the (50 and 100 amps) performance of a standby generator. They manage large electri- cal loads upon startup, and shed them to aid in recovery when overloaded. In many cases, using SMM's can reduce the overall size and cost of the system. Base Plug Kit Base plugs snap into the lifting holes on the base of air-cooled home standby generators. This offers a sleek, contoured appearance, as well as offers protection from rodents and insects by covering the lifting holes located in the base. Base plug kit contains four base plugs, sufficient for use on a single air-cooled home standby generator. High Altitude Kit A high altitude kit may be required when operating over 2,000 ft (610 m) above sea level per U.S. EPA regulations. Operating the engine with the incorrect engine configuration at a given alti- tude may increase emissions and decrease fuel efficiency and performance. NOTE: Contact an IASD or visit www.generac.com for additional information on accessories and extended warranties. Installation Guidelines for 60 Hz Air -Cooled Generators 47 Accessories This page intentionally left blank. 48 Installation Guidelines for 60 Hz Air -Cooled Generators Diagrams Section 11: Diagrams Installation Drawing (A0002360608 rev A-1 of 2) O MOUNTING TO CONCRETE PAD 766 6l9 HOLE LOCATIONS FO [30.21 (26.81 OPTIONAL MOUNTING TO A CONCRETE PAD 1[20.51 1 16 [618] DIA. CLEARANCE HOLE (3) PLACES, 10 [3181 DIA. MASONRY ANCHOR BOLTS RECOMMENDED CAU 197 393 68 [27] FRONT OF UNIT--'267 [10.5] 356 [14.01 TRANSFER SWITCH (IF SUPPLIED) AIN AC/CONTROL WIRING HOLE FOR 1 1l4' CONDUIT IF EQUIPPED REMOVE FACTORY PLUGS AND DISCARD AIN AC/CONTROL WIRING HOLE FOR 3l4' CONDUIT -CLOSE ANY UNUSED HOLE WITH A NEMA (IF EQUIPPED) 3R RATED PLUG (FIELD SUPPLIED) AUXILIARY SHUTDOWN SWITCH WIRELESS MODULE UEL INLET: 1l2' NPT (10kW) : 3l4' NPT (14, 1&26kW) 635 REQUIRED FUEL PRESSURE :NATURAL GAS: 3.5-7" WATER COLUMN LIQUID PROPANE (VAPOR): 10-12' WATER COLUMN 733 128.81 345 [13.6] O O 216 REAR VIEW [25S] [8.6] LEFT SIDE VIEW Installation Guidelines for 60 Hz Air -Cooled Generators 49 Diagrams Installation Drawing (A0002360608 rev A-2 of 2) AIR INTAKE 457 [18.01 MINIMUM OPEN AREA 9[36.0] MINI MUMM OPEN AREA AIR OUTLET W O U AIR INTAKE 914 [36.0] MINIMUM OPEN AREA TOP VIEW 914 [36.0] MINIMUM OPEN AREA "DO NOT LIFT BY ROOF" � o • � 8 RIGHT VIEW LIFTING HOLES 4 CORNERS:030 01.2] INTAKE PANEL REMOVED - MUST BE LIFTED WITH STEEL RODS - RECOMMENDED LIFTING ROD SIZE: 025 1.0] 21 [48.0] Q 0 1232 RIGHT SIDE VIEW [48.5] 0] FRONT VIEW GRAVEL COMPACTED SOIL 50 Installation Guidelines for 60 Hz Air -Cooled Generators Part No. A0001846478 Rev. B 09/22/2022 ©2022 Generac Power Systems, Inc. All rights reserved Specifications are subject to change without notice. No reproduction allowed in any form without prior written consent from Generac Power Systems, Inc. GENERAL' Generac Power Systems, Inc. S45 W29290 Hwy. 59 Waukesha, WI 53189 1-888-GENERAC (1-888-436-3722) www.generac.com