APPROVED PLANS 4.27.20 (2)NORTHWEST ENGINEERING GROUP Ms. Carley Davis Ram Jack West 862 Bethel Drive Eugene, OR 97402 Re: Ms. Catherine Ross Site Inspection 19608 88t' Ave W Edmonds, WA Dear Ms. Davis, April 9, 2020 Per your request, a site inspection was performed at the above residence on March 31, 2020. The purpose of the site inspection was to provide a general assessment of the structural condition of the foundation at the residence. The inspection was strictly visual and limited to the exposed areas of the structure. Documents detailing the construction of the residence were not available for review. The residence is estimated to be approximately fifty-eight (58) years old and for orientation purposes is assumed to face east. Image 1: Front Elevation The residence is a one-story wood framed structure. The residence has wood and brick siding covering the exterior walls. The foundation of the residence is a wood floor system supported by piers and concrete beams. The roof consists of composite asphalt shingles and has rain gutters on the east and west sides of the residence. Removal of any floor or wall coverings to inspect for cracking was beyond the scope of this investigation. P.O. Box 10393/ Eugene, OR, 97440/ 541.393.7363 / WWW.NWENGGROUP.COM Ms. Catherine Ross April 9, 2020 Foundation Inspection Page 12 19508 88th Ave W Edmonds, WA GEOLOGICAL SETTING AND SOILS The geologic setting in this area is comprised of deposits of clay, silt, and sand defined as Vashon Till deposits of the Pleistocene (USGS National Geologic Map Database). It is our opinion that the settlement is a result of improper foundation drainage and/or undersized foundations. We believe that a suitable support can be achieved by installing helical piles. Based on the site conditions, a full geotechnical report is not necessary OBSERVATIONS Vegetation around the residence consists primarily of grassy areas with small to medium shrubs. The residence does not appear to have a sprinkler system. The surface grades on all sides of the residence appear relatively flat. Area of ponding water were observed on the east and west sides of the residence. The areas of ponding are shown on the attached Foundation and Elevation Assessment Plan (SK-1). Some evidence of foundation movement was observed during the inspection which is noted on the attached Foundation and Elevation Assessment Plan (SK-1). The evidence consisted primarily of grade beam cracks, doors out of plumb, and sloping floors. Relative floor elevations were provided by Ram Jack West. The floor elevations were reportedly taken on March 27, 2020 with a Ziplevel. The Ziplevel is a pressurized hydrostatic altimeter and works by measuring the difference in elevations between the base unit and the handheld unit. The basepoint was reportedly set to 0.0 inch and located near the northwest corner of the residence. Negative elevations referenced are below the basepoint, and positive elevations are higher than the basepoint. The lowest point was recorded near the southwest corner of the residence. The high point was recorded along the north exterior wall of the residence. The elevation differential between the low and high points of the residence was found to be about 2 % inches. These elevations are shown on the attached Foundation and Elevation Assessment Plan (SK-1). RECOMMENDATIONS I recommend a total of seven (7) helical steel piles be installed at the residence. Pile locations are shown on the Foundation and Elevation Assessment Plan (SK-1). The steel piling system used should have an evaluation service report (ESR) recognized by ICC-ES showing compliance with the currently adopted International Building Code (IBC). The steel piling system should also have a minimum allowable working load of 10.7 kips and be capable of uniformly raising the foundation as applicable. The minimum installation torque is 2,400 ft-lbs. The purpose of underpinning the foundation is to support portions of the structure that has experienced some differential settlement. The underpinning piles are designed to support the structural loads in the immediate areas where they are placed and not to prevent uplift from soil heave. Maintaining uniform moisture around the foundation is very important. The landscape grades around the residence should be maintained to slope away from the residence where required. P.O. BOX 10393/ Eugene, OR, 97440 / 541.393.7363 / WWW.NWENGGROUP.COM Ms. Catherine Ross April 9, 2020 Foundation Inspection Page 13 19508 8V1 Ave W Edmonds, WA The landscape grades should slope away from the foundation at a minimum of Y2" per foot for six (6'-0) feet. The top soil should extend a minimum of one (V-0) foot above the bottom of the grade beam and should not extend above four (4") inches below the bottom of the siding. All new fill soil should be clayey sand with a minimum Plasticity Index (PI) of twenty-five (25). Watering the soil around the foundation is also important during dry periods to help maintain uniform moisture in the soil. This concludes this report. Observations made in this report pertain to the condition of the residence on the date of the inspection which is subject to change. No foundation warranty is expressed or implied by this report. If I can be of further assistance or should you have any questions about this report, please do not hesitate to contact me. Sincerely, 1410 ]DE STEpp wC A - WA .� c m v � 3jO rAL James Hogan, E.I.T. Charles J. Steffensmeier, P.E. Engineering Technician Civil Engineer Attachment: Site Plan (SK-0) Foundation and Elevation Assessment Plan (SK-1) Ram Jack Helical Pile Detail with 4038 Bracket (SK-2) Footing & Pile Calculations Ram Jack 4038 Bracket Shop Drawing Ram Jack 2 7/8" Helical Pile Specification P.O. BOX 10393/ Eugene, OR, 97440 / 541.393.7363 / WWW.NWENGGROUP.COM 120.2 APPROVED � PLANS MUST BE ON JOB SITE ALL WORK SUBJECT TO FIELD INSPECTION FOR CODE COMPLIANCE 91.5' +/- PROPERTY LINE 93.5 +/- SITE PLAN ENTRY 19508 88TH AVE W SI Report required for this project I i CITY OF EDMONDS BUILDING DIVISION APPROVED PLAN City Of Edmonds Building Department work Foundation Repair Address 19508 88th Ave. West Owner Ross, Catherine Approved Date 4/27/2020 Building Official LFcrysAyyeELjc Permit Number BLD2020-0400 TREE PRESERVATION NOTES: 1. ALL HOLES ARE EXCAVATED NEXT TO THE STRUCTURE FOUNDATION NORTH 2. THE TOTAL AREA OF EXCAVATED HOLES < 25 SQFT NORTHWEST ENGINEERING GROUP P.O. BOX 10393 EUGENE, OR 97440 54� 1) 393-7363 CATHERINE ROSS SHEET: 19508 88TH AVE W S K - 0 EDMONDS, WA SCALE: DATE: 1 /30" =1'-0 04/09/2020 APPROVED WOODEN CONCRETE DECK PATI01 PLANS MUST BE 2'-0" 8'-o" 8'-0" ON JOB SITE 05 04 o -1 i2" -2 A" -1 y" 07 -1" ELECTRICAL PANEL yt6 s'pE S CO F wa of �~Qy� IT �m f m 1 Y" GRADE BEAM CRACK PONDING WATER 03�--�(Typ) -1 y" Y" 0" n. u- _1 y„ _1o„ COVERED GRAVEL PATIO ENTRY----4 -Y4" _1„ _1 y„ 4" —*—,CONCRETE 7 PATIO 02 j e � y2' -Nz" -Y4" -1" -1 y1' 0 014 y" GRADE BEAM CRACK 2'-0" FOUNDATION & ELEVATION ASSESSMENT PLAN LEGEND -Y4" - - - - FLOOR ELEVATIONS TAKEN BY RAM JACK ON 3/27/2020 ® - - - - HELICAL STEEL PILE (10.7 KIP CAPACITY) I 0 - - - - HELICAL STEEL PILE THROUGH CONCRETE (10.7 KIP CAPACITY) NORTH - - 6x6x3/8" x 3'-0" ANGLE NORTHWEST CATHERINE ROSS SHEET: 19508 88TH AVE W S K -1 ENGINEERING GROUP EDMONDS,WA P.O. BOX 10393 SCALE: DATE: EUGENE, OR 97440 541 393-7363 1 3/32" = l'-0 04/09/2020 EXISTING FLOOR JOISTS — BEAR ON FOUNDATION WALL EXISTING CONCRETE FOUNDATION L 6"x6"x3/" x 3'-0 LONG WHERE PILE SPACING EXCEEDS 6-0 O.C. (MAX. PILE SPACING 8'-0 O.C.) TABLE 1 PILE HELIX PILE MIN. BRACKET DIA. CONFIG. SERVICE INSTALL. LOAD TORQUE 4038 2 3V" 10" 10.7 KIP 2,400 FT-LBS y/q10 S E S TFA, 2� of wA�/y oy� rri 'SAL ENT EXISTING EXTERIOR WOOD FRAMED WALL APPROXIMATE EXTERIOR GRADE ELEVATION, SOIL OR CONCRETE PAVING. (VERIFY EXACT CONDITIONS IN FIELD) EXTENT OF EXISTING FOOTING BEYOND CHIP -OUT POCKET IN EXISTING FOOTING FLUSH WITH FOUNDATION WALL AS NEEDED TO INSTALL BRACKET. BRACKET MUST SUPPORT THE BOTTOM OF THE FOOTING AND SHALL NOT RELY ON POST -INSTALLED ANCHORS FOR GRAVITY SUPPORT. HELICAL PILE (REF. TABLE 1) APPROVED PLANS MUST BE ON JOB SITE TYPICAL HELICAL PILE DETAIL EXTERIOR GRADE BEAM NORTHWEST ENGINEERING GROUP P.O. Box 10393 Eugene, OR 97440 Design Loads: Dead: Roof = Third Floor = Second Floor = First Floor = Walls = Live: *Roof snow = *Roof live = Third Floor = Second Floor = First Floor = *(the greater of the two) Foundation dimensions: h= bw = b= hf = Vertical Design Loads: Tributary Widths: Roof = Third Floor = Second Floor = First Floor = Walls = Foundation self -weight = Live: Roof = Third Floor = Second Floor = First Floor = PILE CALCULATION Project: Catherine Ross 19508 88th Ave. W Edmonds, WA 15 psf 0 psf 15 psf 15 psf 12 psf 20 psf 20 psf 0 psf 40 psf 40 psf 24 in in 12 in 6 in Date: 4/6/2020 Designer: Charles Steffensmeier, P.E. y/�1�6 ,OE srE,�� wA$y��C 2tS' m L�.ng 16 ft » pif 0 ft » pif 6 ft » plf 4 ft » plf 18 ft » pif » plf DL plf ft » plf ft » plf ft » pif ft » pif LL pif (without roof LL) LL plf Page 1 NORTHWEST ENGINEERING GROUP ASD Loads: Load, w2 = IDL + ILL Load, w4 = IDL + ILL(0.75) Max. load w ASD= PILE CALCULATION Date: 4/6/2020 Designer: Charles Steffensmeier, P.E. 1194 pif (comb.#2 -without roof LL) OR 1334 pif (comb.#4 -with roof LL) 1334 plf Angle Cantilevered or Simply Supported? Cantilevered Concrete Analysis: ACI 318-14 LFRD Loads: Load, wl_ 1111 plf Load, w2= 1752 pif Load, w3= 1664 pif Load, w4= 1312 plf Max. load w LFRD= 1752 plf Max. beam span(o = 5 ft = Mmax = wU*12/8 = Shear.,, = (1/2)*wu*t= Foundation Width, bw = Foundation Depth, d = Cross Sectional Area, A = Section Modulus, Sxb = Gross Moment of Inertia, Ig = Assumed Conc, f C = yt = 65.71 in -kips = 4.38 kips 6 22 132 484 5324 2500 11 in in m .2 in in' psi in (comb 1) (Comb 2) (Comb 3) (Comb 4) 60 in 5.48 k-ft Code Reference (h-2") ACI14.5.1.7 Foundation Moment & Shear Capacity Per ACI 318-14 Code Reference Conc Modulus of Rupture,fr= 375 psi ACI 19.2.3.1 Cracking Moment, Mcr = 15.1 k-ft ACI 24.2.3.5 Flexure Reduction Factor, (0 = 0.6 ACI 21.2.1 Design Moment, 4)Mn = 6.1 k-ft OK ACI 14.5.2.1a & 14.5.2.1b Shear Strength, Vn = 8.8 kips ACI Table 14.5.5.1 Shear Reduction Factor, (b = 0.6 ACI 22.2.1 Design Shear, 4)Vn = 5.3 kips OK Notes: 1) Foundation analysis is based on having an unreinforced section 2) When calculating member in strength in flexure, combined flexure and axial load, or shear, the entire cross section shall be considered in design, except for concrete cast against soil where the overall thickness shall be taken as 2 in. less than the specified thickness. (ACI 14.5.1.7) Paige 2 NORTHWEST ENGINEERING GROUP Max. beam span(j _ Pile spacing (4) _ Angle total length (4 = 4 - 0 _ Angle loads: PILE CALCULATION Date: 4/6/2020 Designer: Charles Steffensmeier, P.E. ft = 60 in ft = 96 in ft = 36 in Pile Working Loads: Pile Service Load, Pn= 10668 Ibs (wall load x pile spacing) Pile Ultimate Load, PuLT = 21336 Ibs *Safety Factor of 2 Applied Point load = 3334 lb Max Load, w' = PTL/4 3556 plf Angle, Mmax = 6.50 ft-kips Angle Size: L6X6X3/8 Single And Design - Equal Legs Given Mmax = 6.50 ft-k (assumed to be loaded through the centroid through the geometric axis) L = 1.5 ft Lateral Unbraced Length Fy = 36 ksi Cb = 1 Angle Properties: t = 0.375 in b = 6 in Sx = 3.51 in^3 Design: AISC 14th Edition JASDi Yielding: Mn/0 = 113.72 in-k Lateral Torsional Buckline Me = 391.0 in-k = My = 126.4 in-k = Me > My Mn/0 = 95.14 in-k = 32.58 ft-k 10.53 ft-k Use Eqn F10-3 7.93 ft-k Code Reference AISC (F10-1) AISC (F10-6a) AISC (F10-3) Page 3 NORTHWEST ENGINEERING GROUP Leg Local Bucklinit Check Mn/Cl = 88.576 in-k = Moment check PILE CALCULATION Date: 4/6/2020 Designer: Charles Steffensmeier, P.E. ft-k AISC (F10-7) Mx/(Mn/0) = 0.881 OK Shear Check Angle, Vmax = 5.334 kips kv = 1.2 b = 6 in t = 0.375 in h/tw = b/t = 16 Cv = 1 Vn/f) = 48.50 kips Vmax/(Vn/f)) = 0.11 OK Deflection check Beam El = 3.18E+09 lb-in2 Angle El = 4.47E+08 lb-in2 Angle LL = 1920 pif Angle Total load = 4036 plf Angle tip deflection from total load= 0.079 in Beam deflection from total load = 0.086 in < 0.40 in OK Angle tip deflection from live load= 0.038 in Beam deflection from live load = 0.041 in < 0.27 in OK Minimum rile installation torque Quia Tmin Kr Required ultimate soil capacity (C,,it) = 2133E Ibs Pile 0 = 2 7/8" Torque factor (Kt) = 9 Minimum pile installation torque, (Tmin) = 2400 ft-Ibs Bracket = 4038 Bracket Allowable Capacity = 19,700 Ibs Page 4 NOTES: UNLESS OTHERWISE SPECIFIED 1. 3. 4. 5. 3 1/2" O.D. SLEEVE (FY=MIN. 65 KSI) FASTENING STRAP WF 1 " DIA. ALL THREADS AND NUTS TOP VIEW ►[NIIX.-5 APPROVED PLANS MUST BE OB SITE III ITII II I III 1111 II �i 1_1 l fh JilI � I o Kev No r f"1/IA IT \/I r1AI 3 1 /2" DI. 3/8" BRA( POLYETHYLENE COPOLYMER THERMOPLASTIC COATING PER ICC—ES AC 228 K MANUFACTURER TO HAVE IN EFFECT INDUSTRY RECOGNIZED WRITTEN cc QUALITY CONTROL FOR ALL MATERIALS AND MANUFACTURING PROCESSES. ALL WELDING IS TO BE DONE BY WELDERS CERTIFIED UNDER SECTION 5 OF THE AWS CODE D1.1. THE CAPACITY OF THE UNDERPINNING SYSTEM IS A FUNCTION OF MANY INDIVIDUAL ELEMENTS, INCLUDING THE CAPACITY OF THE FOUNDATION, BRACKET, PIER SHAFT, HELICAL PLATE, AND BEARING STRATA, AS WELL AS THE STRENGTH OF THE FOUNDATION BRACKET CONNECTION AND THE QUALITY OF THE INSTALLATION OF THE PILE. YOUR ACHIEVABLE CAPACITY COULD BE HIGHER OR LOWER THAN THOSE LISTED DEPENDING ON THE ABOVE FACTORS. RAM JACK ENGINEERING HANDBOOK FOR ALLOWABLE VALUES AND/OR CONDITIONS OF USE CONCERNING MATERIAL PRESENTED IN THIS DOCUMENT. ,q) MMJACK' JIUL VILW UNLESS OTHERWISE SPECIFIED • DIMENSIONS ARE IN INCHES • TOLERANCES: ANGLE t1' 3 PLACE DECIMALS t .010 2 PLACE DEC MALS t .02 • REMOVE ALL BURRS AND SHARP EDGES • PARENTHETICAL INFO FOR REF ONLY HOLE TOLERANCES .013 .126 .251 THRU.00 THRU THRU THRU+MI .125 .250 .500 .001 .501 +.o0a .751 +.010 1.001 +.012 THRU _ �1 THRU _ ooi THRU _ aol .750 1.000 2.000 2 7/8" DIA. 4107.78 NnM4038 PILE BKT. IFscMNo A -SIZE TITLE BLOCK WN 10-2-08 :N DARIN WILLIS R. DARIN WILLIS TYP. IN`. SCAL a z�ignati un ure led THIS DRAWING AND ITS CONTENTS ARE CONFIDENTIAL AND THE EXCLUSIVE PROPERTY OF RAM JACK SYSTEMS DISTRIBUTION, LLC. NO PUBLICATION, DISTRIBUTION OR COPIES MAY BE MADE WITHOUT THE EXPRESSED WRITTEN CONSENT OF RAM JACK SYSTEMS DISTRIBUTION, LLC. ALL RIGHTS RESERVED UNDER COPYRIGHT LAWS. 2 OF 7 1 11/2"=l' CHARLES T. MARVIN 4038 HELICAL PILE BRACKET JG NO 4038-02-07 2.875"0 HELICAL PILES AND ANCHORS - UPSET CONNECTION "D" / LEAD SECTION LEAD SECTION TABLE CAT. # "A" "B" "C" "D" 6125 5'-0 8" 6140 5'-0 8" 101, 6142 5'-0 101, 12" 6143 7'-0 101, 12" 6147 7'-0 8" 101, 12" 6148 7'-0 10" 12" 14" 6188 10'-0 10" 12" 14" * MULTI -HELIX ARE SPACED 3 DIAMETERS OF THE LOWEST HELIX. HELIX EXTENSION HELIX EXTENSIONS CAT # "A" "B" 8605-8 5'-0 8" 8605-10 5'-0 101, 8605-12 5'-0 12" 8607-10 7'-0 10" EXTENSIONS CAT # "A" 8605 5'-0 8607 7'-0 8610 10'-0 NOTES: 1. POLYETHYLENE POLYMER THERMOPLASTIC COATING PER ICC-ES AC 228.(GALVANIZED AND UNCOATED PILES AVAILABLE UPON REQUEST) 2. LEAD AND EXTENSION SECTION LENGTHS ARE NOMINAL. 3. SHAFT MATERIAL IS 2%" O.D., 0.217" WALL, MINIMUM Fy=65 KSI AND Fu=80 KSI, ASTM - A500. 4. HELIX BLADE MATERIAL IS HOT ROLLED, MINIMUM Fy=50 KSI AND Fu=80 KSI CARBON STEEL. PLATE THICKNESS IS AVAILABLE IN %" AND %" THICKNESSES. 5. NOMINAL SPACING BETWEEN HELICAL PLATES IS THREE TIMES THE DIAMETER OF THE LOWEST HELIX. 6. MANUFACTURER TO HAVE IN EFFECT INDUSTRY RECOGNIZED WRITTEN QUALITY CONTROL AND ASSURANCE FOR ALL MATERIALS AND MANUFACTURING PROCESSES. 7. MANUFACTURER SHALL BE ISO CERTIFIED. 8. ALL WELDING IS TO BE DONE BY WELDERS CERTIFIED UNDER SECTION 5 OF THE AWS CODE D1.1. 9. ALL COUPLING BOLTS TO BE %4 0, SAE J429 GRADE 8 BOLTS.(SAE J429 GRADE 5 IF GALVANIZED). PROVED PLANS MUST BE ON JOB SITE "A" EXTENSION MECHANICAL TORQUE RATING - 6,000 FT -LB ULTIMATE CAPACITY (TENS/COMP) - 54.0 KIP* ALLOWABLE CAPACITY TEN MP - 27.0 KIP* *BASED ON A TORQUE FACTOR (Kt) = 9 3/, I N $ I '/8" 0 HOLES TO l I ACCEPT %4" 0 1 ( THRU BOLTS I I I I 2%"O.D PILING CONNECTION DETAIL