REVIEWED BLD2022-0174+Structural_Analysis_or_Calculations+2.15.2022_1.44.26_PM+26823201 of 25 REVIEWED BY CITY OF EDMONDS ri LONGITUDE ONE TWENTY° ENGINEERING, & DESIGN Calculation Package for Foundation Stabilization/Lift STRUCTURAL ENGINEER L120 ENGINEERING & DESIGN 13150 91s' PL NE KI RKLAN D, WA 98034-5901 7719173'd St SW Edmonds, WA 98026 Project no: S211026-2XR ,January 171 202I Prepared for: R&R Foundation Specialist 3409 McDougall Ave, suite 204 Everett, WA 98201 P: 425.760.5077 CONTACT: MANS THURFJELL, PE EMAIL: MTHURFJELL@L120ENGINEERING.COM RECEIVED Feb 15 2022 �..._._._._" PRLINE ._._.�.�.�._.L .._..............._._._._._ 91.RTYOPE I I I ) � � I I ( PARCEL NO. i00681fi00000100 i LEGAL DESCRIPTION TALBOT GLEN BLK DOD i D-00-LOT1 i OWNER NAME & ADDRESS GRID E DONALD C ]]151]3RD STREET SW EDMONDS, WA 98036 (E) CHIMNEY EA OF WORK \, II �,I RESIDENCE 1L ]]151]3RD STREET SW EDMONDS, WA 98026 113RD ST SW o� SITE PLAN LEGEND EXISTING RESIDENCE STRUCTURE EXISTING ADJACENT STRUCTURE AREA OF PROPOSED WORK PROPERTY LINE ---- APPROXIMATE DIMENSION PILE SPACING & LOAD REQUIREMENTS TABLE MAXO.C.SPACING,ft MIN VERTICALCAPACRY, kips PROOF TESTING LOAD, kips PILE III PILE TYPE BTWN PILESEND OFFSET ALLOWABLE LOADING 20WLMIN VERTICAL CAPACITY (MIN ULTIMATE CAPACITY LOCATION 173 4fi 172 HELICAL CONCENTRIC 6'-0" PER PLAN PER PLAN 11.0 k/PILE 22.0 k/PILE EXTERIOR', 14.0 k/PILE 28.0 k/PILE --- R EXTERIOR 24.0 k/PILE 48.0 k/PILE CHIMNEY a. MINIMUM AND MAXIMUM INSTALLATION TORQUE FOR HELICAL ASSEMBLIES SHALL BE SPECIFIED BY THE PILE MANUFACTURER. THE MINIMUM INSTALLATION TORQUE SHALL BE HIGH ENOUGH TO ACHIEVE THE REQUIRED BEARING CAPACITY LOADING, INCLUDING A SAFETY FACTOR NO LESS THAN 2. THE MAXIMUM INSTALLATION TORQUE SHALL NOT EXCEED THE ALLOWABLE TORSIONAL CAPACITY OF THE PILE SHAFTS OR ANY PART OF THE PILE ASSEMBLY. MAXIMUM INSTALLATION TORQUE RATING OF 8,300FT-LBS FOR A 2-7/8 INCH DIAMETER HELICAL PILE WITH 0.203 INCH SHAFT WALL THICKNESS PER ESR-3750. b. FOR HELICAL PILES, PER IDEAL GROUP DWG NO.:2]8TFG, THE ALLOWABLE STRUCTURAL CAPACITY FOR THE 27AE TRU-FORCE UNDERPINNING BRACKET IS LIMITED TO 30 KIPS. c. HELICAL ASSEMBLIES AS MANUFACTURED BY IDEAL MANUFACTURING, INC., IN ACCORDANCE WITH ESR-3150. d. PILE OR ANCHOR LOADS NOT TO EXCEED MAXIMUM CAPACITY AS DETERMINED BY THE MANUFACTURER FOR ANY PART OF THEASSEMBLY. e. MAXIMUM ON -CENTER SPACING LISTED FOR TYPICAL PILE INSTALLATION UNLESS NOTED OTHERWISE ON PLAN. 1. VERIFY ALL DIMENSIONS ON SITE. 2 FOUNDATION DIMENSIONS ARETO OUTSIDE FACE OF CONCRETE STEM WALL PER FAR LEVEL SURVEY. 3. REFERTOTHEFOLLOWING DETAILS FOR ADDITIONAL INFORMATION: HELICAL PILES ....................................... MG-1.1 DRIVEN PILES ......................................... ZSD1.1 4. REFER TO STRUCTURAL CALCULATONS PACKAGE DATED JANUARY I7IH,2022, FOR ADDITIONAL INFORMATION, SPECIFICATIONS, AND TL1 REQUIREMENTS. I� B ADDLEVELTONAL REQUIREMENTS RFAR EMENTSAIR PLAN DATED SEPTEMBER 30TH, 2021, REFER TO STRUCTURAL CALCUTATIONS PACKAGE FOR MODIFICATIONS AND ✓� ADDITIONAL REQUIREMENTS FOR REPAIR PLAN. 6. MINIMUM PILE DIAMETER SHALL BE 2-7Ie'. ]. IT IS ACCEPTABLE TO INSTALL PILES AT THE SPACING SHOWN WITH 3 O'6"TOLERANCE TO ALLOW FOR UNEXPECTED OBSTRUCTIONS ENCOUNTERED DURING PILE INSTALLATION PROVIDED THAT NOTING ADJACENTSPPNS EXCEED THE SPACING LIMITATION AS INDICATED ON LEVEL SURVEY. 8. IF REQUIRED, ALL SUPPLEMENTAL CHANNELS TO SPPN FROM PILETO PILE AND EXTEND MIN 6' PAST SUPPORTING PILE EA ENO. 8. IF REOUIRED, ALL SUPPLEMENTALCHANNELS TO BE ANCHORED TO THE FOUNDATION WITH LB" DIAM. x 4' SIMPSON TTEN HD SCREW ANCHORS (OR ED EQUIVA APPROVED ATA MAXIMUM SPACING 1EOC, ANCHORS TO BE CENTERED ON OR INSTALLED ABOVE THE CENTER LINE OF THE CHANNEL. 10. FIELD VERIFY ALL EXISTING STEM WALLS AT AND BETWEEN PILE ATTACHMENT LOCATIONS ARE B"THICK MINIMUM WITH THE HEIGHT (MEASURED FROM BIFTG TO TIGONC) MINIMUM, 11. PARCEL DIMENSIONS PROVIDED BY SNOHOMISH COUNTY. NOT TO SCALE. PROPERTY LINE AND RESIDENCE LOCATING DIMENSIONS (WITH ASTERISK, (APPROXIMATED PER SNOHOMISH COUNTY GIB MAPPING TOOLS. NOT TO BE USED FOR LEGAL PURPOSES. 12. SITE FEATURES AND EXISTING STRUCTURES ON ADJACENT PARCELS NOT SHOWN FOR CLARITY. 13. PILES SHALL BE INSTALLED TO A MINIMUM EMBEDMENT OF —OR UNTIL REFUSAL, WHICHEVER IS SHALLOWER. HELICAL PILE REFUSAL CRITERIA: TORQUING OF THE PILE SHALL CONTINUE UNTLA HYDRAULIC PRESSURE IS ACHIEVED TO PROVIDE THE SPECIFIED MINIMUM VERTGAL CAPACITY WITH A SAFETY FACTOR OF NO LESS THAN TWO. ADVANCEMENT SNALL BE HALTED IMMEDIATELY IF THE STRUCTURE BEGINS TO EXPERIENCE UPLIFT FLEXURE. DRIVEN PILE REFUSAL CRITERIA: ADVANCEMENTOF THE PILE SHALL CONTINUE UNTIL A WORKING PRESSURE IS ACHIEVED TO PROVIDE THE SPECIFIED MINIMUM VERTICAL CAPACITY WITH ASAFETY FACTOR OF NO LESS THAN TWO. ADVANCEMENT SHALL BE HALTED IMMEDIATELY IF THE STRUCTURE BEGINS TO EXPERIENCE UPLIFT FLEXURE. (1)PILEM� LOCATE PILEtjL, Y=3"Helical Pile N 0 Iry i'o=3"Stabil-Loc Pier FMOPENING 0' ❑ = Pdty ,r ane Lilt 3 SB 38 0 ROm o E 2 OE6A C MA% 3l4 �i 1 2 - Sl8 -1Y2 '1 tl4 IB -]/B -S. -11 R&R LEVEL SURVEY See Structural Calculation Packa a for Additional Requirements NOTE: THE PROJECT WILL NOT RESULT IN CHANGING OF SITE TOPOGRAPHY OR EXISTING DEVELOPED AREAS. SITE PLAN LONGITUDE ONE TWENTY ENGINEERING & DESIGN PROJECT SUBJECT BY JT 3of25 PROJECT NO. NO. S211026-2XR 7715 173rd St SW Edmonds WA 98026 Foundation Stabilization/Jacking DATE 01 /17/2021 Scope/Objective: To determine the required pile spacing and geometry to stabilize and lift (where required) the existing structural foundation. These findings have been based upon the calculated strength of the existing foundation system and the current vertical loading from the existing structure above (based on as -built assessments). The R&R Foundation Specialists' (R&R) proposed pile layout can be found in the following pages with structural recommendations based upon the findings of L120 Engineering & Design. Note that cosmetic damages to rigid wall coverings/members and siding are expected during a foundation lift. Such cosmetic damages/cracks are to be repaired by others following the completion of the foundation stabilization and lifting and are not included in the structural scope presented here. It should be further noted that L120's scope is limited to the perimeter support systems/continuous footings. The interior crawl -space support system for the first floor shall be installed per R&R. This could include the use of some or all of the following: longer support posts, adjustable post -base hardware, and/or the addition of taller wood support members. Settlement in these interior support areas shall be monitored and further adjustments shall be made if necessary. Structural Summary: - The foundation of the residence consists of continuous cast -in -place concrete stem wall and concrete strip footings. Below the footings, piles are to be spaced at a distance no larger than 6-0" o.c. as indicated on the attached Level Survey. - End piles shall not exceed the maximum corner offset as specified on the attached Level Survey. - A maximum allowable loading of 1,940 plf was utilized in this analysis. This was determined through inspection of building geometry and conservative span/tributary loading assumptions based on standard construction practices - The following load values represent the maximum expected pile loads for the indicated spacing. R&R to provide pile and equipment assemblies with capacities equal to or greater than the indicated load values. Allowable Load Capacity Requirement: Helical Pile #1-3 @ 6'-0" o.c. ................. 11.0 kip minimum vertical capacity (allowable load) Helical Pile #4-6 @ 6-0" o.c. ................. 14.0 kip minimum vertical capacity (allowable load) Concentric Pile #1-2 @ Chimney ........... 24.0 kip minimum vertical capacity (allowable load) Note: Refer to the attached General Notes for additional requirements. - As determined by R&R, the site appears to have no lateral (horizontal) displacements or concerns. As such, the analysis and recommendations presented in this report have been strictly limited to vertical stabilization/jacking. If lateral movement is observed or expected additional structural analysis will be required. - Structural recommendations contained in this package are based on site photographs dated September 30th, 2021, provided by R&R. To the knowledge of L120, a geotechnical investigation was not performed on this site. Consequently, all structural recommendations assume adequate soil conditions to obtain the required pile capacities. Please inform L120 of site -specific conditions that were unconsidered by, may conflict with, or otherwise compromise the recommendations contained within this package, including, but not limited to, water drainage, slope stability, existing structural damage, or existing subsurface obstructions. In this instance, the structural assumptions, recommendations, and scope for this project will need to be revisited to consider and address the new findings Refer to the following pages for pile and connection specifications. L120 ENGINEERING & DESIGN 4 of 25 GENERAL NOTES HELICAL PILES 1. HELICAL PILES SHALL BE DESIGNED AND MANUFACTURED IN ACCORDANCE WITH THE 2018 INTERNATIONAL BUILDING CODE (IBC). 2. HELICAL PILES SHALL BE DESIGNED AND MANUFACTURED BY IDEAL MANUFACTURING, INC., AND SHALL BE IN ACCORDANCE WITH ESR-3750. 3. ALL MATERIAL PROPERTIES OF HELICAL PILE COMPONENTS SHALL BE IN ACCORDANCE WITH ESR-3750. 4. CORROSION PROTECTION OF ALL PILE COMPONENTS SHALL COMPLY WITH THE ICC-ES ACCEPTANCE CRITERIA FOR CORROSION PROTECTION OF STEEL FOUNDATION SYSTEMS USING POLYMER (EAA) COATINGS (AC228). 5. ALL HELICAL FOUNDATION COMPONENTS SHALL BE GALVANICALLY ISOLATED FROM CONCRETE REINFORCING STEEL, BUILDING STRUCTURAL STEEL, OR ANY OTHER METAL BUILDING COMPONENTS PER AC358 SECTION 3.9. 6. THE SHAFT SHALL BE DESIGNED AND FABRICATED TO SUPPORT THE SPECIFIED DESIGN LOADS. 7. ONLY MANUFACTURER -APPROVED CONNECTORS, ADAPTORS, AND ACCESSORIES MAY BE USED. 8. HELICAL PILES SHALL BE INSTALLED VERTICALLY INTO THE GROUND WITH AN ALLOWABLE ANGLE OF INCLINATION OF +/- 1 DEGREE FROM VERTICAL PER SECTION 4.2.1 OF ESR-3750. 9. MONITOR AND RECORD DEPTH OF PILE PENETRATION. PROVIDE TORQUE MONITORING DEVICE AS PART OF THE INSTALLING UNIT. MONITOR AND RECORD TORQUE APPLIED DURING THE INSTALLATION OF EACH PILE AT SPECIFIC DEPTHS. 10. HELICAL PILES SHALL BE INSTALLED TO THE MINIMUM TORQUE VALUE REQUIRED TO PROVIDE THE MINIMUM REQUIRED LOAD CAPACITIES INDICATED ON PLAN INCLUDING A FACTOR OF SAFETY NO LESS THAN TWO (2). THE MAXIMUM INSTALLATION TORQUE SHALL NOT EXCEED THE ALLOWABLE TORSIONAL CAPACITY OF ANY INDIVIDUAL COMPONENT OF THE PILE ASSEMBLY. 11. ALL BRACKETS AND HELICAL PILE ASSEMBLY COMPONENTS SHALL HAVE ADEQUATE CAPACITY TO ACHIEVE THE MINIMUM REQUIRED BEARING CAPACITY INCLUDING A FACTOR OF SAFETY NO LESS THAN TWO (2). 12. REPAIR BRACKETS MUST BE CONCENTRICALLY LOADED AND THE BRACKET PLATE MUST BE FULLY ENGAGED WITH BOTTOM OF CONCRETE FOUNDATION. 13. ALL HELICAL PILE ASSEMBLY COMPONENTS MUST HAVE ADEQUATE STRENGTH TO DEVELOP THE TORQUE REQUIRED FOR INSTALLATION AND ALL INDUCED STRESSES. 14. THE PILE QUANTITY, LAYOUT, AND SPACING INDICATED ON PLAN SHALL NOT BE CHANGED WITHOUT WRITTEN APPROVAL FROM THE ENGINEER -OF -RECORD PRIOR TO INSTALLATION. 15. CONTINUOUS SPECIAL INSPECTION IN ACCORDANCE WITH 2O18 AND 2012 IBC SECTION 1705.9 MUST BE PROVIDED FOR THE INSTALLATION OF THE HELICAL PILES AND FOUNDATION BRACKETS. ITEMS TO BE RECORDED AND CONFIRMED BY THE SPECIAL INSPECTOR MUST INCLUDE THE FOLLOWING: A. PRODUCT MANUFACTURER B. MANUFACTURER'S CERTIFICATION OF THE INSTALLERS C. PRODUCT TYPE AND CONFIGURATIONS FOR HELICAL PILE LEAD SHAFT SECTIONS, EXTENSIONS, BRACKETS, BOLTS, THREADED RODS, NUTS, WASHERS, AND TORQUES AS SPECIFIED IN THIS REPORT AND THE CONSTRUCTION DOCUMENTS D. INSTALLATION PROCEDURES FOR THE HELICAL PILE SHAFT, INSTALLATION EQUIPMENT USED, AND THE IDEAL FOUNDATION SYSTEMS INSTALLATION INSTRUCTIONS E. ANTICIPATED AND ACTUAL PILING DEPTH F. REQUIRED TARGET INSTALLATION TORQUE OF PILES AND MINIMUM DEPTH OF INSTALLATION G. INCLINATION AND POSITION OF PILES, TOP OF PILE EXTENSION IN FULL CONTACT WITH BRACKET, TIGHTNESS OF ALL BOLTS AND EVIDENCE THAT THE PILE FOUNDATION SYSTEMS ARE INSTALLED BY AN APPROVED IDEAL FOUNDATION SYSTEMS INSTALLER. 16. PILES IMPROPERLY INSTALLED BECAUSE OF MISLOCATION, MISALIGNMENT, OR FAILURE TO MEET OTHER SPECIFIED DESIGN/INSTALLATION CRITERIA ARE NOT ACCEPTABLE. ABANDON REJECTED PILES AND INSTALL ADDITIONAL PILES AS REQUIRED. HELICAL PILE PROOF TESTING THE CAPACITY OF THE INSTALLED PILES SHALL BE VERIFIED BY FIELD TESTING OF A MINIMUM THREE (3) PERCENT OF PILES UP TO FIVE (5) PILES MAXIMUM (ONE (1) MINIMUM) IN ACCORDANCE WITH THE PROCEDURE OUTLINED IN ASTM D1143 AND/OR THE 2018 SEATTLE BUILDING CODE (SBC). THE MAXIMUM TEST LOAD SHALL BE TWO -HUNDRED (200) PERCENT OF THE SPECIFIED DESIGN LOAD. 5 of 25 GENERAL NOTES CONCENTRIC/DRIVEN PILES 1. "CONCENTRIC" OR DRIVEN PILES SHALL BE DESIGNED AND MANUFACTURED IN ACCORDANCE WITH THE 2018 INTERNATIONAL BUILDING CODE (IBC). 2. IT IS RECOGNIZED THAT THE SEATTLE BUILDING CODE (SBC) REQUIRES 8 INCH MINIMUM DIAMETER PIPE FOR PIPE PILE INSTALLATION. THE APPROPRIATE ANALYSIS/EVALUATION AND TESTING REQUIREMENTS IN ACCORDANCE WITH SEATTLE DEPARTMENT OF CONSTRUCTION & INSPECTIONS (SDCI) DIRECTOR'S RULE 10-2009 ARE PROVIDED TO ALLOW FOR USE OF PILES LESS THAN 8 INCHES IN DIAMETER AS REQUIRED BY SECTION 104.5 OF THE SBC. 3. DRIVEN PILES SHALL BE DESIGNED AND MANUFACTURED BY STABIL-LOC SYSTEMS, LLC, AND SHALL BE IN ACCORDANCE WITH ESR-4121. 4. ALL MATERIAL PROPERTIES OF DRIVEN PILE COMPONENTS SHALL COMPLY WITH ESR-4121. 5. CORROSION PROTECTION OF ALL PILE COMPONENTS SHALL COMPLY WITH THE ICC-ES ACCEPTANCE CRITERIA FOR CORROSION PROTECTION OF STEEL FOUNDATION SYSTEMS USING POLYMER (EAA) COATINGS (AC228). 6. ALL PILE COMPONENTS SHALL BE GALVANICALLY ISOLATED FROM CONCRETE REINFORCING STEEL, BUILDING STRUCTURAL STEEL, OR ANY OTHER METAL BUILDING COMPONENTS PER AC358 SECTION 3.9. 7. THE SHAFT SHALL BE DESIGNED AND FABRICATED TO SUPPORT THE SPECIFIED DESIGN LOADS. 8. ONLY MANUFACTURER -APPROVED CONNECTORS, ADAPTORS, AND ACCESSORIES MAY BE USED. 9. DRIVEN PILES SHALL BE INSTALLED VERTICALLY INTO THE GROUND WITH AN ALLOWABLE ANGLE OF INCLINATION OF 1 DEGREE FROM VERTICAL PER SECTION 5.7 OF ESR-4121. 10. DRIVEN PILES SHALL BE INSTALLED TO THE MINIMUM FORCE REQUIRED TO PROVIDE THE MINIMUM REQUIRED LOAD CAPACITIES INDICATED ON PLAN INCLUDING A FACTOR OF SAFETY NO LESS THAN TWO (2). THE MAXIMUM INSTALLATION FORCE SHALL NOT EXCEED THE ALLOWABLE CAPACITY OF ANY INDIVIDUAL COMPONENT OF THE ASSEMBLY. 11. ALL BRACKETS AND PILE ASSEMBLY COMPONENTS SHALL HAVE ADEQUATE CAPACITY TO ACHIEVE THE MINIMUM REQUIRED BEARING CAPACITY INCLUDING A FACTOR OF SAFETY NO LESS THAN TWO (2). 12. THE PILE QUANTITY, LAYOUT, AND SPACING INDICATED ON PLAN SHALL NOT BE CHANGED WITHOUT WRITTEN APPROVAL FROM THE ENGINEER -OF -RECORD PRIOR TO INSTALLATION. 13. SPECIAL INSPECTION IN ACCORDANCE WITH IBC SECTION 1705.7 IS REQUIRED FOR INSTALLATION OF THE STABILLOC FOUNDATION PIERING SYSTEM. A GEOTECHNICAL SPECIAL INSPECTOR MUST VERIFY AND RECORD THE FOLLOWING: A. VERIFICATION OF MANUFACTURER PRODUCT MODEL NUMBERS B. TYPES, CONFIGURATIONS, AND IDENTIFICATIONS OF HYDRAULICALLY DRIVEN STEEL PIER SEGMENT AND ADJUSTABLE HEAD ASSEMBLY AS SPECIFIED IN ESR-4121 AND THE CONSTRUCTION DOCUMENTS. C. INSTALLATION PROCEDURES, ANTICIPATED AND ACTUAL PILING DEPTH D. TIP ELEVATIONS, THE INSTALLATION PRESSURE AND FINAL DEPTH OF THE DRIVEN FOUNDATION SYSTEM E. INCLINATION AND POSITION/LOCATION OF HYDRAULICALLY DRIVEN PIER SEGMENTS H. COMPLIANCE OF THE INSTALLATION WITH THE APPROVED CONSTRUCTION DOCUMENTS AND THIS EVALUATION REPORT. 14. PILES IMPROPERLY INSTALLED BECAUSE OF MISLOCATION, MISALIGNMENT, OR FAILURE TO MEET OTHER SPECIFIED DESIGN/INSTALLATION CRITERIA ARE NOT ACCEPTABLE. ABANDON REJECTED PILES AND INSTALL ADDITIONAL PILES AS REQUIRED. DRIVEN PILE PROOF TESTING THE CAPACITY OF THE INSTALLED PILES SHALL BE VERIFIED BY FIELD TESTING OF A MINIMUM THREE (3) PERCENT OF PILES UP TO FIVE (5) PILES MAXIMUM (ONE (1) MINIMUM) IN ACCORDANCE WITH THE PROCEDURE OUTLINED IN ASTM D1143 AND/OR THE 2018 SEATTLE BUILDING CODE (SBC). THE MAXIMUM TEST LOAD SHALL BE TWO -HUNDRED (200) PERCENT OF THE SPECIFIED DESIGN LOAD. 6 of 25 GENERAL NOTES STRUCTURAL STEEL 1. REFERENCE STANDARDS: DESIGN, FABRICATION AND ERECTION ARE TO BE IN ACCORDANCE WITH THE LATEST EDITION OF THE AISC "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES". 2. MATERIALS: BOLTS - ASTM A307, UNLESS OTHERWISE NOTED ALL OTHER STEEL - ASTM A36 (Fy = 36,000 PSI) 3. ALL WELDING SHALL BE PERFORMED BY CERTIFIED WELDERS AND CONFORM TO AWS CODES D1.1 AND D1.3. WELDS NOT SPECIFIED ARE TO BE 1/4" CONTINUOUS FILLET MINIMUM. USE DRY E70 ELECTRODES. WHERE ON -SITE WELDING IS REQUIRED, SPECIAL INSPECTION IN ACCORDANCE WITH 2O18 AND 2012 IBC SECTION 1705.2 IS ALSO REQUIRED. CONCRETE 1. REFERENCE STANDARDS: ACI 301, ACI 318, IBC. 2. MINIMUM CONCRETE STRENGTH (28 DAYS): FOOTINGS AND STEM WALLS..................................................3,000 PSI - 5 SACK MIX BASEMENT FOUNDATION RETAINING WALLS .......................3,000 PSI - 5 SACK MIX SLAB-ON-GRADE........................................................................2,500 PSI - 5 SACK MIX SLAB -ON -GRADE... EXPOSED WEATHERING SURFACES ...... 3,000 PSI AIR -ENTRAINMENT 2.5% TO 5.5% FOR EXPOSED CONCRETE 3. MIXING: COMPLY WITH ACI 301. DO NOT EXCEED THE AMOUNT OF WATER SPECIFIED IN THE APPROVED MIX. PROPORTIONS OF AGGREGATE TO CEMENT SHALL BE SUCH AS TO PRODUCE A DENSE, WORKABLE MIX WHICH CAN BE PLACED WITHOUT SEGREGATION OR EXCESS FREE SURFACE WATER. 4. PLACING: COMPLY WITH ACI 301. PROVIDE A 3/4 INCH CHAMFER AT ALL EXPOSED CONCRETE EDGES, UNLESS INDICATED OTHERWISE ON ARCHITECTURAL DRAWINGS. 5. SLUMP: 4 INCHES PLUS OR MINUS 1 INCH. DO NOT ADD WATER TO MIX TO INCREASE SLUMP. GREATER SLUMP, ACCELERATED SET, OR HIGH EARLY STRENGTH MAY BE ACHIEVED BY USING APPROVED ADMIXTURES. 6. CURING: COMPLY WITH ACI 301. KEEP CONCRETE MOIST FOR SEVEN DAYS MINIMUM. 7. JOINTING: PROVIDE ADEQUATE JOINTING TO MINIMIZE EFFECTS OF VOLUME CHANGE. JOINTS SHOWN MAY BE ADJUSTED AT CONTRACTOR'S OPTION WITH PRIOR APPROVAL FROM ENGINEER. 8. WEATHER EXTREMES: COMPLY WITH ACI 305R FOR HOT WEATHER. COMPLY WITH ACI-306R FOR COLD WEATHER. 9. WATER/CEMENT RATIO SHALL NOT EXCEED 0.50 (BY WEIGHT), TYPICAL. 10. ALL SPECIFIED CONCRETE ANCHORS SHALL BE SIMPSON STRONG -TIE, HILTI, OR EQUIVALENT. SPECIAL INSPECTIONS REQUIRED. ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH MINIMUM EMBEDMENT, SPACING, EDGE DISTANCE, AND REQUIREMENTS PER MANUFACTURER. PROJECT LONGITUDE SUBJECT ONE TWENTYO ENGINEERING & DESIGN BY JT 7 of 25 PROJECT NO. NO. S211026-2XR 7715 173rd St SW Edmonds WA 98026 Foundation Stabilization/Jackin DATE 01/17/2021 ]deal FouadtrtFan Systems 2-7f 8"0 Helical Pile (0.203-irlth wall thickness) ' -Soil Capacity per ESR-3750 DIGGA 10K Drive Head Pressure (psi) Torque, T flq'1bsJ ]argue Correlation Factor, BC, j[ompressiorrj Ultimate Axial Compressive Capacity, P. = I(,''F jkrpsj AllawableAxral Compressive Caporrfy, P, = 0-50P„ (kips) L120 ENGINEERING &DESIGN LONGITUDE ONE TWENTYO ENGINEERING & DESIGN PROJECT SUBJECT 8 of 25 PROJECT NO. NO. S211026-2XR 7715 173rd St SW Edmonds WA 98026 Foundation Stabilization/Jacki DATE 01 /17/2021 (deaf Foundation Systems 2-7{$ 0 Helical Pile (0.203-inciiwall thickness} - Soil Capacity per ESR-3750 DIGGA 6K Drive Head L120 ENGINEERING &DESIGN LONGITUDE ONE TWENTYO ENGINEERING & DESIGN PROJECT SUBJECT BY - 9 of 25 PROJECT NO. NO. S211026-2XR 7715 173rd St SW Edmonds WA 98026 Foundation Stabilization/Jackin DATE 01 /17/2021 Stubil-ioc 2-7/S"Concentric Pier - Soil i.) Power Team C25C Hydraulic Cylinder effective cylinder area has from manufacturer cut sheets ii.) Piles shall reach a pressure that correlates with an allowable capacity that meets or exceeds the maximum allowable load demand as listed in the structural package, but shall not exceed the maximum allowable capacity for any part of the pile assembly. iii.) Referto ESR-4121 and Stabr{-Loc, Mc. documents for additional information and requirements. iv.) 1 kip =1,000 Ibs Capacity per by Installation Pressure PawerTeamC25C Hydraulic Cylinder Pressure, p (Fsr� f CylirlderEffectrve,4reQ, A� (in� tiltlmQteAxial Compressive Capacity, P„ _ p *A (kiFs� AffoxrableAxial Compressive CQPQcrty, Pa = 4.5*P„ (kiFs� 1,000 5.15 5.2 2.6 1,50U 5.15 7.7 3.9 2,000 5.15 10.3 5.2 2,500 5.15 12.9 6.4 3,000 5.15 15.5 7.7 3,500 5.15 18.0 9.0 4,000 5.15 20.6 10.3 4,500 5.15 23.2 11.6 5,000 5.15 25.8 12.9 5,540 5.15 28.3 14.2 6,000 5.15 30.9 15.5 5,500 5.15 33.5 16.7 7,000 5.15 36.1 18.0 7,500 5.15 38.6 19.3 8,000 5.15 41.2 20.6 8,540 5.15 43.8 21.9 9,000 5.15 46.4 23.2 9,500 5.15 48.9 24.5 L120 ENGINEERING &DESIGN 10of25 Thursday, September 30, 2021 SCOPE OF WORK Crew will install 3" Helical Piles, as well as 3" Stabil-Loc Piers, and lift home to maximum practical recovery. Crew will drive piles to a maximum 25' after there will be a $20 a foot charge per pile. Crew will remove and replace concrete holes. Customer will need to have WABO Certified Inspector to monitor Piles as being driven at a cost to homeowner. Crew will drill 3/8" holes and inject Polyurethane Foam to lift and support slab. Crew will pump a maximum amount of 180lbs, after there will be a $7 charge per lb. L120 is in concurrence with pile layout recommended by R&R provided that the proposed layout is followed as marked and piles are installed with a maximum pile spacing of 6-0" o.c. per the attached SSK-01 & SSK-02. NOTES: 1. It is acceptable to install piles at the spacing shown with ± 0'-6" tolerance to allow for unexpected obstructions encountered during pile installation provided that no two adjacent spans exceed the spacing limitation of 6'-0" o.c. UNO. 2. End piles are to be placed within 3'-0" from corner as specified below LINO. _EVI SURVEY ........................................ ...... � 1 I► ■■■■■■■ .. ..■■■SOON. ..■■■■■■■■■■■■■■■ .■■■. MESS ■■■■O■ .. .■ ■ . -MYRIIiO■■N■■N■■■■■ 1 . FROM . • ■■■■■■■■■N■■■■■ . - - .MEN ■ ■ 1'll %MMM■■■■■■■■■ .■■■. ■■ I�u■■■■■■■■■■■■■ o .. - - N■ Q'-1i�i�O■■■■■■■■■■ ■■ � ■■■■■■■\■■■■■■■■■ SOON LOCATE PIL■■■■■■■■i■■■■■■■■■■■lair:■ FROM COR. INN ■■ NON . 1 OC MAX■■■■■ � i� � - SS ■■ ■■O■■NO■■■■ ■■■N■■■■O■■■■■■■■■■■ ■■■■■■■■■■■■■■■■■■■■■■■ ■ ■■■■■■■■■■■■ ■NONN■■NO■■■NNO■■■■■■■N■■O■■■■■NMOO■N■■■ ■■■■■■■■■■■■■■■■■■■■■■■■■■O■■■■■■■■■■■■■■ N■■■■■O■■O■■N■■O■O■■■ONSOOOONOON■■■■■■■■NOS■ ■■ ..- N . .- - O■■■■S■■O■■■■■■■■■■ON'.'J■■■O■■■■■■■■O■■■■■■■ ■■■■■ MEMO ......................■■■iNO■■O■■■mmomNV ......................... ■■■■■■■■■■■■■■■■= ......................................... ............... .........................■■....■......SO■ ■■■■■■..........�....■ ■■O■■...............■........■...... .. .■■■■. .................................... .. ■■■■■MOVES ■■■■■...............■■....■..■■..... NOTE: L120's scope is limited to the perimeter support systems/continuous footings of the primary structure. All stabilization and replacement efforts of interior elements, exterior decks, and deck supporting elements are outside of 1-120's contract and scope and are not addressed in this package. - L120 11 of 25 Thursday, September 30, 2021 Jub F,I-1U I OS North side of home, Piles 4-6 will be installed her Dingo accessible. Crew will remove and replace concrete holes. Northwest interior corner of home, Crew will drill 3/8" holes here and inject Polyurethane Foam to lift and support slab. West side of home, Piles 1-3 will be installed here. West side of home, Dingo accessible. Photographs provided by R&R Foundation Specialists. Note that analysis assumptions such as building geometry, tributary areas, and loading were determined through examination of these photographs and industry knowledge of standard construction practices. - L120 PROJECT LONGITUDE SUBJECT ONE TWENTYO ENGINEERING & DESIGN �ry �0LL =QLLJ Fy z�> z 0 N 0 ~ U N BY 1T (E) WOOD FRAMED FLOOR SYSTEM, FIELD VERIFY 8" MIN THICKNESS, CONTRACTOR TO VERIFY 12 of 25 PROJECT NO. NO. S211026-2XR SSK-01 7715 173rd St SW Edmonds WA 98026 Installation Detail - Ideal Helical Pile �'ll _IIII—IIII—IIII (E) CONTINUOUS l l —""—IIII =IIII CONIC FOOTING NOTES: 1. CONTRACTOR TO VERIFY NOTED MINIMUM EXISTING FOUNDATION DIMENSIONS PRIOR TO INSTALLATION. ENGINEER -OF -RECORD TO BE NOTIFIED PRIOR TO INSTALLATION IF MINIMUMS NOT MET. 2. ALL ASSEMBLY COMPONENTS SHALL BE FULLY SEALED BY A CORROSION RESISTANT SYSTEM. THIS INCLUDES ALL FINAL CUT ENDS AND DRILLED HOLES. CORROSION PREVENTION COATING SYSTEM BY OTHERS. PRIME AND PAINT PER MFR OR GALVANIZATION PER ASTM 153/A123. 3. AT CUT INSTALLATION POCKET ALL EXPOSED STEEL REINFORCEMENT SHALL BE SEALED OR COATED TO PREVENT CORROSION. DATE 01 /17/2021 (E) CONC STEM WALL T/STEM WALL = FIELD VERIFY T/FIN GRADE =OL VARIES IF IIII — IIII — I' IIII =IIII =IIII = (E) FTG TO BE CUT FLUSH I =IIII =IIII = WITH FACE OF STEM WALL IIII=IIII=IIII= WITH A 12" MAX WIDTH FOR 1=IIII=IIII IIII INSTALLATION POCKET •- IIII=IIII= 11= ' 1=IIII-11 III. II =IIII _IIII - T/CONC FTG = 1=IIII=III FIELD VERIFY • IIII=IIII= 1=IIII=III IIII=IIII I=IIII= IIII=IIII=ii IDEAL HELICAL PILE & REPAIR BRACKET ASSEMBLY PER R&R FOUNDATION SPECIALIST TO CONFORM TO ESR-3750 L120 ENGINEERING & DESIGN LONGITUDE ONE TWENTYO ENGINEERING & DESIGN PROJECT SUBJECT CHIMNEY ASSUMED TO BE LATERALLY BRACED BY PRIMARY STRUCTURE ABOVE. CONTRACTOR TO CAREFULLY OBSERVE CHIMNEY DURING LIFT AND SUSPEND ALL JACKING IF CHIMNEY APPEARS TO BE UNSTABLE OR TO SHIFT AWAY FROM THE PRIMARY STRUCTURE (E) CONIC FOOTING 13 of 25 PROJECT NO. NO. S211026-2XR SSK-02 7715 173rd St SW Edmonds WA 98026 Installation Detail - Chimney Pile 1�11=IIII—IIII " " ' d ' d IIII=11 IIII . - " " IIII= DATE 01 /17/2021 (E) CHIMNEY T/FIN GRADE _ IIII=IIII=IIII= VARIES IIII=IIII=111� IIII=IIII=11 IIII=IIII=IIII IIII=IIII=IIII IIII=IIII=IIII=1 IIII=IIII=1111� IIII=IIII=IIII=' 1111E1111DIII, 11=IIII=IIII=III, T/CONC FTG = d. =1111=1111=1111= FIELD VERIFY , 1111EIIII=IIII=IIII IIII=IIII=IIII= 1111EIIII=IIII=III' " _IIII=IIII=IIII- IIII=IIII=IIII=IIII= III=IIII=IIII="'' NOTES: 1. ALL ASSEMBLY COMPONENTS SHALL BE FULLY SEALED BY A CORROSION RESISTANT SYSTEM. THIS INCLUDES ALL FINAL CUT ENDS AND DRILLED HOLES. CORROSION PREVENTION COATING SYSTEM BY OTHERS. PRIME AND PAINT PER MFR OR GALVANIZATION PER ASTM 153/A123. 2. AT CUT INSTALLATION POCKET ALL EXPOSED STEEL REINFORCEMENT SHALL BE SEALED OR COATED TO PREVENT CORROSION. L120 ENGINEERING & DESIGN 11/2X1 SLOT (TYP) 2 7/8" TRUFORCE BRKT BASE GALV. TOP 2 7/8 TRUFORCE BRKT BASE GALV. FRONT" TRUFORCE UNDERPINNING BRACKET FOR 2 7/8'' PILE SHAFT 7% 1 1/2 X 1 2 7/8" TRUFORCE BRKT T-BRKT GALV. SLOT (TYP) TOP 2 7/8" TRUFORCE BRKT T-BRKT GALV. FRONT NOTES: 1. PLATE STEEL TO MEET OR EXCEED REQUIREMENTS OF ASTM A572/A1018/A656, 50 KSI. 2. ALL WELDING TO BE PERFORMED BY SHOP QUALIFIED WELDOR TO AWS D1.1 STRUCTURAL WELDING CODE - STEEL. 3. GALVANIZING PER ASTM A153/ASTM A123. BARE STEEL IS ALSO AVAILABLE. 4. ULTIMATE STRUCTURAL CAPACITY IS 60 KIPS. 5. (2) 7/8"-9 X 3' GALVANIZED THREADED ROD - ASTM A193 (GRADE B7). 6. (4) 7/8" GALVANIZED HEX NUT - ASTM A194. 7. (6) 7/8" GALVANIZED FLAT WASHERS - ASTM F436. (2) WASHERS MUST BE USED ON THE TOP OF EACH THREADED ROD (ABOVE THE 'T' BRACKET) TO OBTAIN THE FULL BRACKET CAPACITY. 8. HELICAL PILE ASSEMBLIES MANUFACTURED IN ACCORDANCE WITH ICC-ES AC358 ACCEPTANCE CRITERIA FOR HELICAL FOUNDATION SYSTEMS AND DEVICES. �K 4 22 2020 m �ED D Ec A L 4 23 2020 1 kL MANUFACTURING, INC. PICTURE PARKWAY STER, NY 14580 Group 789-4810 1 WWW.IDL-GRP.COM NOT TO SCALE SIZE DWG NO R ALL UNITS IN INCHES U.N.O. B I 278TFG THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF IDEAL MANUFACTURING, INC. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT WRITTEN PERMISSION OF IDEAL MANUFACTURING, INC. IS PROHIBITED. SHEET 1 OF 1 A O N Ot MAXIMUM TORQUE NOT TO EXCEED 8,300 FT-LBS. ULTIMATE CAPACITY IS 74.7 KIPS BASED ON A CAPACITY TO TORQUE RATIO OF kc = 9 FT-1 [L] ILI D� �p3 � �p3 ` L COUPLING m. BOLTS & NUTS EXTENSION FLIGHTED EXTENSION FLIGHTED EXTENSION (EX: 278203EXT[L]G) SINGLE HELIX (SH) DOUBLE HELIX (DH) (EX: 278203FESH[L][DI]X[T]G) (EX: 278203FEDH[Q[DiD�]X[T]G) NOTES: 1. PILE SHAFT TO MEET OR EXCEED REQUIREMENTS OF ASTM A500, 80 KSI. 2. PLATE STEEL TO MEET OR EXCEED REQUIREMENTS OF ATSM A572, GRADE 50. 3. ALL HELICES ARE FORMED BY PRESS DIE. LEADING EDGE OF HELICES ARE TAPERED TO IMPROVE INSTALLATION CAPABILITIES. 4. HELIX SPACING IS THREE (3) TIMES THE DIAMETER OF THE LOWER HELIX. B SPACING OF LEADING HELIX ON FLIGHTED EXTENSIONS IS THREE (3) TIMES THE DIAMETER OF THE LAST HELIX ON THE PRECEDING SHAFT. 5. STANDARD HELIX DIAMETERS ARE 8", 10", 12", & 14". STANDARD HELIX THICKNESS IS 3/8". 6. ALL WELDING TO BE PERFORMED BY CERTIFIED WELDOR IN ACCORDANCE WITH AWS D1.1 STRUCTURAL WELDING CODE - STEEL. 7. HOT DIP GALVANIZING PER ASTM A153/ASTM A123. BARE STEEL IS ALSO AVAILABLE. 8. (2) 3/4" DIAMETER X 4 1/2" LONG GALVANIZED HEAVY HEX BOLT ASTM A325 AND (2) 3/4" GALVANIZED HEAVY HEX NUT ASTM A194 (GRADE 2H). 9. HELICAL PILE ASSEMBLIES MANUFACTURED IN ACCORDANCE WITH ICC-ES AC358 (IDEAL REPORT #ESR-3750) ACCEPTANCE CRITERIA FOR HELICAL FOUNDATION SYSTEMS AND DEVICES. � W 57/8 (TYP) 2 7/8" O.D. X 0.203" W.T. HELICAL LEADS & EXTENSIONS ICC-ES AC358 - REPORT #ESR-3750 � I I D4 D3 �p3 r D= SINGLE HELIX (SH) DOUBLE HELIX (DH) TRIPLE HELIX (TH) QUAD HELIX (QH) LEAD LEAD LEAD LEAD (EX: 278203SH[L][D3]X[T]G) (EX: 278203DH[L][D3D2]X[T]G) (EX: 278203TH[L][DiD2D3]X[T]G) (EX: 278203QH[L][WD2D3D4]X[T]G) 2% O.D. X 2 4 IDEAL PART # ABREVIATIONS: 0.203 W.T. 278 = SHAFT DIAMETER] 3 PITCH 203 = SHAFT WALL THICKNESS (TYP) EXT = EXTENSION FE = FLIGHTED EXTENSION 015/16 SH, DH, TH, QH = SINGLE, DOUBLE, TRIPLE, OR QUAD. HELIX [L] = SHAFT LENGTH IN FEET BOLT HOLE HELIX FORMED BY (EXAMPLE: 7' = 7) DETAIL PRESS DIE [D] = HELIX DIAMETER(S) IN INCHES DRAWN (EXAMPLE: 10" = 10) X— X (SEPARATES HELIX DIAMETER(S) AP 4/3/ 2 CHECKED LRS 4/7/ 2 AND HELIX THICKNESS) [T] — HELIX THICKNESS IDEAL MANUFACTURING, INC. (EXAMPLE: 3/8" = 38) 999 PICTURE PARKWAY G = GALVANIZED WEBSTER, NY 14580 800-789-4810 1 WWW.IDL-GRP.COM NOT TO SCALE ALL UNITS IN INCHES U.N.O. � ii)��1L Group 278203 :NSION SINGLE HELIX (TENSION IPLE =LIX -AD CUT 45° TYPICAL PILE ASSEMBLY THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF IDEAL MANUFACTURING, INC. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT WRITTEN PERMISSION OF IDEAL MANUFACTURING, INC. IS PROHIBITED. SHEET 1 OF 1 B 16 of 25 ESR-4121 I Most Widely Accepted and Trusted +- FQ"G I W7 OMEADT ESR IM NOW AM---W S I f[NCIR - PIAIE PLATE Rd.NO F -i N>92,3714atee I I CUT ro FIT a MIT r4mm k INSTAL AF70 CpPFIm -v I O lFR HSS AT MS'NLATIOh !7' 1i70Y I TYPWAL OUTER FppnvC MEN SEGMENT ROOM H s F A51W 3 3 11 hY*- J�13 ASSfNRIMB INNER a IT f a OUTER PIER SE6MMENN 1111M INNER PER SEMIENT t RWNU Ifs ASIN A500�-13 CH. N OR OTHER STRA-A PIER ASSEMBLY SLABIL-LOC SYSTEMS, L1.0 DATE: 8-12-18 FIGURE 1—STABIL-LOC" FOUNDATION PIERING SYSTEM HOLES j- T-- I QUTLINL OL It PLAN IAEW fl0x+hx18 B-TWEEN RFARIN0 BRG E do =04T1NG PLATE FOOTING �a - k a 2-yy�A_LO x+ 3,5"WIN, •. (2��! LM OLQNEN I ESR 1396 WEDG= ANCHORS BEARING - PLATE 51-II+A BLOCK 1 I I HEAD ROUND I I� 11 PLATE HSS2.375x0.188 A55EMBLEO INNER OJT TO FIT k I I & OUTER PIER INSTALL AFTER SEGMENTS COMPLETED PIER INSTALLATION H LALD AS SEMBLY 5'A3L-i.c MIMI LLO FIGURE 2—STABIL-LOC'lK' FOUNDATION PIERING SYSTEM ADJUSTABLE HEAD ASSEMBLY LONGITUDE ONE TWENTYO ENGINEERING & DESIGN O O N Perspective Support below (E) Chimney PROJECT SUBJECT 17 of 25 PROJECT NO. NO. S211026-2XR 7715 173rd St SW Edmonds WA 98026 Foundation Stabilization/Jacking Elevation DATE 01 /17/2021 - Unit weight of existing bricks = 39 psf (4" clay brick) - Unit weight of CM lower level = 104 psf (assume 10" normal weight solid grouted) - Est. length of chimney perimeter = 16'-0" (conservative) - Est. height of brick veneer = 20'-0" - Est. max height of chimney = 20'-0" Total Weight = 104psf (16'-0" perim x 20' tall) + 40psf (16'-0" perim x 20' tall) = 46,080 Ibs ==> Assume Pile #1 & #2 each takes 1/2 of chimney load = 46.08 k / 2 = 23.1 k Hip L120 ENGINEERING & DESIGN PROJECT LONGITUDE SUBJECT ONE TWENTYO ENGINEERING & DESIGN Maximum loading on grade beam determined based on building geometry, and through conservative assumptions regarding span lengths and support walls/foundation. Basically, all concrete walls assumed full tributary span of floor members and roof members. Design code: IBC 2018 Roof LL (snow ground): 25 psf Floor LL: 40 psf Patio/Deck LL: 60 psf Floor/Roof DL: 15 psf Wall DL: 12 psf Conc Wall DL: 150pcf x 240 in2 = 250 plf * see following pages for area calc Helical Pile #1-3 Roof Trib = 2' trib + 2' overhand = 4' Floor Trib = 0.5*20' = 10' Typical Flr Ht = 20' Helical Pile #4-6 Roof Trib = 0.5*30' = 15' Floor Trib = 0.5*20' = 10' Typical Flr Ht = 20' Helical Pile#1-3 Case 1: Point Load (6' Span) Pile Reaction = 1500 plf * 6' = 9.0 k Pile Reaction w/ SW = 1750 plf * 6' = 10.5 k Case 2: Uniform Load DL = 12*20+15*(4+10*2) = 600 plf LL = 40*10*2 = 800 plf SL (snow) = 25*4 = 100 plf Total load = DL+LL+SL = 1500 plf Total load w/ SW = DL+LL+SL = 1750 plf Refer to attached calculations for analysis. BY JT 18 of 25 PROJECT NO. NO. S211026-2XR 7715 173rd St SW Edmonds WA 98026 Foundation Stabilization/Jackin DATE 01 /17/2021 W L/2 L/2 Pile and connection requirements per Pile and connection requirements per contractor - contractor Helical Pile#4-6 Case 1: Point Load (6' Span) Pile Reaction = 1940 plf * 6' = 11.7 k Pile Reaction w/ SW = 2190 plf * 6' = 13.2 k Case 2: Uniform Load DL = 12*20+15*(15+10*2) = 765 plf LL = 40*10*2 = 800 plf SL (snow) = 25*15 = 375 plf Total load = DL+LL+SL = 1940 plf Total load w/ SW = DL+LL+SL = 2190 plf Refer to attached calculations for analysis. 2'-2" (18" + 811) Conclusion: Based on the loading and geometry of the structure we conclude that the foundation may be stabilized through the use of piles and connections per R&R. These are to be attached to the stem -wall (grade -beam) at an on -center (o.c.) spacing no greater than 6'-0" o.c.. L120 ENGINEERING & DESIGN 19of25 Project Number: Plan Name: Sheet Number: S211026-2XR Foundation Stabilization Engineer: Subject: Date: JT Unreinforced Conc Design Check 1/11/22 DEMAND CALCULATION number ofstories # 1stories span L 6.0 ft concrete area A 216 in2 concrete self weight SW 250 plf Pt DL DL 4.59 k = 6.0 ft * 765 Pt LL LL 4.80 k = 6.0 ft * 800 Pt LLr LLr 2.25 k = 6.0 ft * 375 momentfrom DL MDL 8,010 lb-ft 96.1 k-in moment from LL MLL 7,200 lb-ft 86.4 k-in momentfrom SL MLLr 3,375 lb-ft 40.5 k-in factored moment MLRFD 134.6 k-in 1.4DL MLRFD 273.8k-in 1.2DL + 1.6LL + 0.5SL MLRFD 266.5k-in 1.2DL + 1.6SL + LL controlling factored moment Mu 273.8 k-in factored shear VLRFD 4.3 k 1.4DL VLRFD 8.1k 1.2DL + 1.6LL + 0.5SL VLRFD 7.9k 1.2DL + 1.6SL + LL controlling factored shear V„ 8.1 k controlling factored bearing B„ 8.1 k STRENGTH CALCULATION concrete strength Pc 2.5ksi assumed light wt concrete mod. factor 1L 1 normal weight concrete flexure strength red. factor Nr 0.9 tension -controlled shear strength red. factor 0.75 bearing strength red. factor ,, RRChear (bearing 0.65 moment ofineritia I„ 11,016in4 elastic section modulus Sm 1,001in3 tens fiber to NA c 11.0 in nom flexure strength (Tcontrols) Mn 250.4 k-in Mn = 5A f'cS,,,. nom flexure strength(C controls) Mn 2,128.1k-in Mn=085f'S, RESIDENTIAL CONCRETE M" 375.5 k-in Mn = 7.55AFfFcSm CONTROLS flexure strength I 'I'Mn 338.0 k-in > Mu OK nom shear strength V" 14.41< n V=3AVf c*A shear strength I On 10.8 k > Vu OK loaded bearing area A, 74 in2 supporting surface bearing area Az 74 in2 nom bearing strength B" 156.6k 0.85f'AI bearing strength I �Bn 101.8 k > Bu OK Additional Verification Calc: max concrete tensile strength f, 375 psi Jr, = 7.SA max beam tensile stress Ft 273 psi __ (M * c) Ft /Ixx fr > Ft OK [max on -center pile spacing] *see attached [Includes total height w/o ACI14 §14.5.1.7 redux] [1-story loading] [1-story loading] [1-story loading] [R=V for SS beam] ACI14 [Table 21.2.1] ACI14 [Table 21.2.11 ACI14 [Table 21.2.1] *see attached *see attached *see attached ACI 318-14 [Eq. 14.5.2.1a] ACI 318-14 [Eq. 14.5.2.1b] ACI 332-14 [Eq. 8.2.1.1] D/C= 81.02% AC114 [Table 14.5.5.1 (a)] D/C= 74.60% [IDEAL 2-7/8" Tru-Force Underpinning Bracket] [If the supporting surface is > than loaded area] ACI14 [Table 14.5.6.1(c)] D/C= 7.91% ACI 14 [Eq. 19.2.3.1] 20 of 25 Project Number: Plan Name: Sheet Number: S211026-2XR Foundation Stabilization Engineer: Subject: Date: JT Unreinforced Conc Design Check 1/11/22 Final Section Prouerties Total Area - 216-0 in12 Ixx = 11,016-0 in^4 Sxx : - V 1,001 .4.5 in"3 1yy 1,631 .93 in14 Sxx : +Y 847.38 in13 Calculated final C.G. distance from Datum : * cq Dim. 0-0 in Zxx 1,349.99 in13 SYY - X - 271-988 in"3 SYY +x 271.968 in"3 Y cg Disi. = 0-0 in Zyy = 504-0 in^3 Edge Distances from CG.: r xx = 7-141 in +X 6.0 in +Y 13.0 in r yy 2.749 in -x -6-0 in -Y In Rotation of All Components @ . 0.00 deg CCVV Y Per AC114 §14.5.1.7 General Shapes - I . #1 Xcg = D.DOQ in Yog = O.DOO in Rotation = 0 deg GGW Top Flange Widlh = 8.000in Top Flange Thick = S.ODOin Wet) Thickness = 8ADOin Bottom Flange Wid 12.000in Bottom Flange Thi, 6.400in Top Height = 24ADOIn 21 of 25 Appendix Parcel Details Photographs 22 of 25 nod' om 1 h Online Government Information S Sarvicea County4O Washington Property Account Summary Parcel Number 100681600000100 lProperty Address 7715 173RD ST SW, EDMONDS, WA 98026-5017 General Information Category Code Area :BOT GLEN BLK 000 D-00- LOT 1 d and Improvements ive, Locally Assessed 17 Property Characteristics Use Code I 111 Single Family Residence - Detached Unit of Measure Acre(s) Related Properties No Related Properties Found Parties Role Percent Name Address 100 GROME 7715 173RD STREET S W, EDMONDS, WA 98026 Taxpayer DONALD C United States Owner 100 GROME 7715 173RD STREET S W, EDMONDS, WA 98026 DONALD C United States Property Values Value Type Tax Year 2021 Tax Year 2020 Tax Year 2019 Tax Year 2018 Tax Year 2017 Taxable Value Regular $812,900 $766,600 $717,600 $658,400 $598,300 Exemption Amount Regular Market Total $812,900 $766,600 $717,600 $658,400 $598,300 Assessed Value $812,900 $766,600 $717,600 $658,400 $598,300 Market Land $477,000 $441,000 $395,000 $365,000 $334,000 Market Improvement $335,900 $325,600 $322,600 $293,400 $264,300 Personal Property Active Exemptions No Exemptions Found Events Effective Date Entry Date -Time Type Remarks 09/14/1999 03/10/2000 11:31:00 Owner Terminated Property Transfer Filing No.: 898 09/14/1999 03/10/2000 11:31:00 Owner Added Property Transfer Filing No.: 898 09/14/1999 09/17/1999 11:48:00 Excise Processed Property Transfer Filing No.: 898, Statutory Warranty Deed 09/14/1999 09/17/1999 11:48:00 Taxpayer Changed Property Transfer Filing No.: 898 Tax Balance 23 of 25 IDistribution of Current Taxes I I r District Rate Amount Voted Amount Non -Voted Amount CENTRAL PUGET SOUND REGIONAL TRANSIT AUT 0.20 $160.21 $0.00 $160.21 CITY OF EDMONDS 1.26 $1,027.26 $290.58 $736.68 EDMONDS SCHOOL DISTRICT NO 15 2.80 $2,275.17 $2,275.17 $0.00 PUB HOSP #2 0.06 $50.21 $0.00 $50.21 SNO-ISLE INTERCOUNTY RURAL LIBRARY 0.42 $345.01 $0.00 $345.01 SNOHOMISH COUNTY-CNT 0.64 $517.15 $0.00 $517.15 STATE 2.83 $2,296.73 $0.00 $2,296.73 SNOHOMISH CONSERVATION DISTRICT $8.03 $0.00 $8.03 TOTAL 1 8.21 $6,679.77 $2,565.75 $4,114.02 Pending Property Values Pending Tax Year Market Land Value Market Improvement Value Market Total Value Current Use Land Value Current Use Improvement Current Use Total Value 20221 S471,000.001 $376,000.001 $847,000.00 $0.00 $0.00 $0.00 Levy Rate History Tax Year 2021 2020 2019 Total Levy Rate 8.207334 9.276512 9.204494 Real Property Structures Description IType Year Built Imore Information 1 Story w/Basement IDwelling 11979 IView Detailed Structure Information Receipts Date Receipt No. Amount Tendered Amount Due 10/19/2021 00:00:00 11782213 $3,339.89 $3,339.89 04/22/2021 00:00:00 11535363 $3,339.88 $6,679.77 10/23/2020 00:00:00 11224629 $3,559.70 $3,559.70 04/17/2020 00:00:00 11047041 $3,559.69 $7,119.39 10/25/2019 00:00:00 10774955 $3,306.09 $3,306.09 04/24/2019 00:00:00 10524678 $3,306.08 $6,612.17 10/24/2018 00:00:00 10226324 $3,510.93 $3,510.93 04/17/2018 00:00:00 9796358 $3,510.93 $7,021.86 10/27/2017 00:00:00 9679539 $3,045.98 $3,045.98 04/21/2017 00:00:00 12386821 1 $3,045.98 $6,091.96 Sales History Sale Date Entry Recording Recording Sale Excise Deed Transfer Grantor(Seller) Grantee(Buyer) Other Date Date Number Amount Number Type Type Parcels RODDY GROME 09/14/1999 09/17/1999 09/14/1999 $410,000.00 898 W S TIMOTHY M & DONALD C No DENA F 0162794 Property Maps Code ITownship Range section lQuarter Parcel Map INeighborhood 1504000 127 104 107 ISE lYiew parcel maps for this Township/Range/Section I 7715 173rd St SW Edmonds WA 98026 � `tom fS � ��• � ,4' ,. � -' �^� - t _ t .. i v or IL 56 113 Feet 1/10/2022 O 4 Snohomish County Assessor Washington t { ♦e,+y'f �+ �� r� x ir' Legend Parcel Recent Sales 2021 Recent Sales 2020 Recent Sales 2019 f._._._._._- f ! City Boundary L._._._._.a County Park National Forest Water Street Types Interstate State Route Local Road All maps, data, and information set forth herein ("Data"), are for illustmfive purposes only and are not to be considered an official citation to, or representation of, the Snohomish County Code. Amendments and updates to the Data, together with other applicable County Code provlslons, may apply which are not depicted herein. Snohomish Countymakes no representation or renty concerning the content. accuracy, currency, completeness or quality of the Data contained herein and expressly disclaims any warranty of merchantability or ftness for any rticular purpo pase. All persons accessing or otherwise using this Data assume all responsibility for use thereof and agree to hold Snohomish County harmless from and against any damages, loss, claim or liability arising out of any error, defect or l omis contained within said Data. Washington State Law, Ch. 42.56 RCW, prohibits state and local agencies from providing access to lists of individuals intended for use for commercial purposes antl, thus, no—unnutial use may be made of any Data comprising lists of Individuals cmmenetl herein. N A 0 N Ln r 1 � fl ' ill I E-. ? 3 � <<. ; 4i�a �`. • s. 5 , r , �a i�.v ?a�; :. 7