BLD2022-1687_Manufacturer_Specifications_and_Installation_Instructions_12.13.2022_6.09.31_AM_3265356
MODEL 126B PREFERRED TM SERIES AIR CONDITIONER bryant WITH PURON® REFRIGERANT 14/2 TO 5 NOMINAL TONS Product Data Pu on. Preferred" Bryant Air Conditioners with Puron o refrigerant provide a collection of features unmatched by any other family of equipment. The 126B has been designed utilizing Bryant's Puron refrigerant. The environmentally sound refrigerant allows you to make a responsible decision in the protection of the earth's ozone layer. NOTE: Ratings contained in this document are subject to change at any time. Always refer to the AHRI directory (www.ahridirectory.org) for the most up—to—date ratings information. INDUSTRY LEADING FEATURES / BENEFITS Efficiency • 14 — 16.5 SEER / 11.5— 13.5 EER • Microtube Technology'" refrigeration system • Indoor air quality accessories available Sound • Sound level as low as 72 dBA • Compressor sound blanket standard Comfort • System supports thermidistat or standard thermostat controls Reliability • Puron@ refrigerant — environmentally sound, won't deplete the ozone layer and low lifetime servce cost. • Scroll compressor • Internal pressure relief valve • Internal thermal overload • Filter drier • High and low pressure switches • Balanced refrigeration system for maximum reliability Durability DuraGuard Plus'" protection package: • Solid, durable sheet metal construction • Louvered coil guard • Baked —on, complete outer coverage, powder paint Applications • Long —line — up to 250 feet (76.20 m) total equivalent length, up to 200 feet (60.96 m) condenser above evaporator, or up to 80 ft. (24.38 m) evaporator above condenser (See L.ongline Guide for more information.) • Low ambient (down to—20°F/-28.9°C)) with accessory kit MODEL NUMBER NOMENCLATURE 1 2 3 4 5 6 7 8 9 10 11 12 14 N N N A A/N N N N N A/N A/N N A 1 2 6 B N A 0 3 6 0 0 0 A Product Tier SEER Major Voltage Variations Cooling Capacity Open Open Open Minor Family Series Series 1=AC 2= 6=16 B=Puron N= A = 0= 0= 0= A = Legacy SEER 208-230-1 Standard Not Not Not Original or Defined Defined Defined Series 208/230-1 Use of the AHRI Certified TM Mark indicates a manufacturer's participation In the program For verification of certification for individual products, go to www.ahridirectory.org. Feature Puron Refrigerant Maximum SEER * Scroll Compressor Field Installed Filter Drier Front Seating Service Valves Internal Pressure Relief Valve Internal Thermal Overload Long Line capability Low Ambient capability with Kit High Pressure Switch Low Pressure Switch Compressor Sound Blanket Louvered Coil Guard * With approved combinations X = Standard c@usUOL STANDARD FEATURES 018 024 030 X X X 16.0 16.0 16.5 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X PHYSICAL DATA 036 042 048 060 X X X 16.5 16.0 16.0 16.0 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X UNIT SIZE -VOLTAGE, SERIES 0018-A 024-A 030-A 036-A 042-A 048-A 060-A Operating Weight lb (kg) 136 (61.7) 163 (73.9) 167 (75.7) 180 (81.6) 234 (106.1) 248 (112.5) 337 (152.9) Shipping Weight lb (kg) 163 (73.9) 198 (89.8) 204 (92.5) 219 (99.3) 281 (127.5) 291 (132.0) 372 (188.7) Compressor Type Scroll REFRIGERANT Puron® (R-410A) Control TXV (Puron® Hard Shutoff) Charge lb (kg) 4.60 (2.09) 6.00 (2.72) 6.81 (3.09) 7.00 (3.18) 8.62 (3.91) 10.50 (4.76) 14.50 (6.58) COND FAN Propeller Type, Direct Drive Air Discharge Vertical Vertical Air City (CFM) 1881 2614 2614 3223 3810 4046 4046 Motor HP 1/12 1/10 1/10 1/12 1/5 1/4 1/4 Motor RPM 1100 800 800 800 800 800 800 COND COIL Face Area (Sq ft) 11.50 15.10 17.20 17.60 25.15 20.10 30.15 Fins per In. 25 25 25 25 25 20 20 Rows 1 1 1 1 1 2 2 Circuits 3 4 4 4 6 7 8 VALVE CONNECT. (In. ID) Vapor 3/4 3/4 3/4 7/8 7/8 7/8 7/8 Liquid 3/8 3/8 3/8 3/8 3/8 3/8 3/8 REFRIGERANT TUBES (In. OD) Rated Vapor* 3/4 7/8 1 1/8 Max Liquid Line 3/8 3/8 * Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset. Note: See unit Installation Instruction for proper installation. t See Liquid Line Sizing For Cooling Only Systems with Puron Refrigerant tables. 2 REFRIGERANT PIPING LENGTH LIMITATIONS Liquid Line Sizing and Maximum Total Equivalent Lengthst for Cooling Only Systems with Puron® Refrigerant: The maximum allowable length of a residential split system depends on the liquid line diameter and vertical separation between indoor and outdoor units. See Table below for liquid line sizing and maximum lengths: Maximum Total Equivalent Length Outdoor Unit BELOW Indoor Unit Size Liquid Line Connection Liquid Line Diam. W/TXV AC with Puron Refrigerant Maximum Total Equivalent Lengtht: Outdoor unit BELOW Indoor Vertical Separation ft (m) 0-5 (0-1.5) 6-10 (1.8-3.0) 11-20 (3.4-6.1) 21-30 (6.4-9.1) 31-40 (9.4-12.2) 41-50 (12.5-15.2) 51-60 (15.5-18.3) 61-70 (18.6-21.3) 71-80 (21.6-24.4) 18000 1/4 150 150 125 100 100 75 -- -- -- AC with 3/8 5/16 250* 250* 250* 250* 250* 250* 250* 225* 150 Puron 3/8 250* 250* 250* 250* 250* 250* 250* 250* 250* 24000 1/4 75 75 75 50 50 -- -- -- -- AC with 3/8 5/16 250* 250* 250* 250* 250* 225* 175 125 100 Puron 3/8 250* 250* 250* 1 250* 250* 250* 250* 250* 250* 30000 1/4 30 -- -- -- -- AC with 3/8 5/16 175 225* 200 175 125 100 75 -- Puron 3/8 250* 250* 250* 250* 250* 250* 250* 250* 250* 36000 AC with 3/8 5/16 175 150 150 100 100 100 75 -- -- Puron 3//8 250* 250* 250* 250* 250* 250* 250* 250* 250* 42000 AC with 3/8 5/16 125 100 100 75 75 50 -- -- -- Puron 3/8 250* 250* 250* 250* 250* 250* 250* 250* 150 48000 AC with Puron 3/8 3/8 250* 250* 250* 250* 250* 250* 230 160 -- 60000 AC with Puron 3/8 3/8 250* 250* 250* 225* 190 150 110 -- * Maximum actual length not to exceed 200 ft (61 m) t Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details. -- = outside acceptable range Maximum Total Equivalent Length Outdoor Unit ABOVE Indoor Unit Size Liquid Line Connection Liquid Line Diam. w/TXV AC with Puron Refrigerant Maximum Total Equivalent Lengtht: Outdoor unit ABOVE Indoor Vertical Separation ft (m) 25 (7.6) 26-50 (7.9-15.2) 51-75 (15.5-22.9) 76-100 (23.2-30.5) 101-125 (30.8-38.1) 126-150 (38.4-45.7) 151-175 (46.0-53.3) 176-200 (53.6-61.0) 18000 1/4 175 250* 250* 250* 250* 250* 250* 250* AC with 3/8 5/16 250* 250* 250* 250* 250* 250* 250* 250* Puron 3/8 250* 250* 250* 250* 250* 250* 250* 250* 24000 1/4 100 125 175 200 225* 250* 250* 250* AC with 3/8 5/16 250* 250* 250* 250* 250* 250* 250* 250* Puron 3/8 250* 250* 250* 250* 250* 250* 250* 250* 30000 1/4 30 -- -- -- -- AC with 3/8 5/16 250* 250* 250* 250* 250* 250* 250* 250* Puron 3/8 250* 250* 250* 250* 250* 250* 250* 250* 36000 AC with 3/8 5/16 225* 250* 250* 250* 250* 250* 250* 250* Puron 3/8 250* 250* 250* 250* 250* 250* 250* 250* 42000 AC with 3/8 5/16 175 200 250* 250* 250* 250* 250* 250* Puron 3/8 250* 250* 250* 250* 250* 250* 250* 250* 48000 C with uron 3/8 3/8 250* 250* 250* 250* 250* 250* 250* 250* 60000 AC with Puron 3/8 3/8 250* 250* 250* 250* 250* 250* 250* 250* * Maximum actual length not to exceed 200 ft (61 m) t Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details. -- = outside acceptable range REFRIGERANT CHARGE ADJUSTMENTS Liquid Line Size Puron Charge oz/ft 3/8 0.60 (Factory charge for lineset = 9 oz) 5/16 0.40 1/4 0.27 Units are factory charged for 15 ft (4.6 m) of 3/8" liquid line. The factory charge for 3/8" lineset 9 oz. When using other length or diameter liquid lines, charge adjustments are required per the chart above. Charging Formula: [(Lineset oz/ft x total length) — (factory charge for lineset)] = charge adjustment Example 1: System has 15 ft of line set using existing 1/4" liquid line. What charge adjustment is required? Formula: (.27 oz/ft x 15ft) — (9 oz) = (-4.95) oz. Net result is to remove 4.95 oz of refrigerant from the system Example 2: System has 45 ft of existing 5/16" liquid line. What is the charge adjustment? Formula: (.40 oz/ft. x 45ft) — (9 oz.) = 9 oz. Net result is to add 9 oz of refrigerant to the system LONG LINE APPLICATIONS An application is considered Long Line, when the refrigerant level in the system requires the use of accessories to maintain acceptable refrigerant management for systems reliability. See Accessory Usage Guideline table for required accessories. Defining a system as long line depends on the liquid line diameter, actual length of the tubing, and vertical separation between the indoor and outdoor units. For Air Conditioner systems, the chart below shows when an application is considered Long Line. AC WITH PURON® REFRIGERANT LONG LINE DESCRIPTION ft (m) Beyond these lengths, long line accessories are required Liquid Line Size Units On Same Level Outdoor Below Indoor Outdoor Above Indoor 1/4 No accessories needed within allowed lengths No accessories needed within allowed lengths 175 (53.3) 5/16 120 (36.6) 50 (15.2) 120 (36.6) 3/8 80 (24.4) 35 (10.7) 80 (24.4) Note: See Long Line Guideline for details VAPOR LINE SIZING AND COOLING CAPACITY LOSS Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessive capacity loss. The suction line diameters shown in the chart below are acceptable for AC systems with Puron refrigerant: Unit Maximum Vapor Line Cooling Capacity Loss (%) Nominal Liquid Line Diameters Total Equivalent Line Length ft. (m) (79 5 151-175 0 0 Size (Btuh) Diameters (In. OD) (In. OD) 15 2) (15.5-24.4) (417 30 5) (30.8-38.-100 (38.4-45.0 (46.0-53.3) (53.6-610) (61.3-68.) (68.9-76.2) 18000 1/2 1 2 3 5 6 7 8 9 11 1 Stage AC with 3/8 5/8 0 1 1 1 2 2 2 3 3 Puron 3/4 0 0 0 0 1 1 1 1 1 24000 5/8 0 1 2 2 3 3 4 5 5 1 Stage AC with 3/8 3/4 0 0 1 1 1 1 1 2 2 Puron 7/8 0 0 0 0 0 1 1 1 1 30000 5/8 1 2 3 3 4 5 6 7 8 1 Stage AC with 3/8 3/4 0 0 1 1 1 2 2 2 3 Puron 7/8 0 0 0 0 1 1 1 1 1 36000 5/8 1 2 4 5 6 8 9 10 12 1 Stage AC with 3/8 3/4 0 1 1 2 2 3 3 4 4 Puron 7/8 0 0 0 1 1 1 1 2 2 42000 3/4 0 1 2 2 3 4 4 1 5 6 1 Stage 3/8 7/8 0 0 1 1 1 2 2 1 2 3 AC with rp 1 1 /8 0 0 0 0 0 0 0 0 0 48000 3/4 0 1 2 3 4 5 5 6 7 1 Stage AC with 3/8 7/8 0 0 1 1 2 2 2 3 3 Puron 11/8 0 0 0 0 0 0 0 1 1 0 3/4 1 2 4 5 6 7 9 10 11 1 Stage 3/8 7/8 0 1 2 2 3 4 4 5 5 AC with Puron 11/8 1 0 1 0 1 0 1 1 1 1 1 1 Applications in this area may be long line and may have height restrictions. See the Residential Piping and Long Line Guideline. ACCESSORY THERMOSTATS PART NUMBER PROGRAM GAS ELECTRIC HEAT COOL T6—PAC01 7—Day J J 1 1 T6—NAC01 NP J J 1 1 THERMOSTAT ACCESSORIES PART NUMBER BRIEF DESCRIPTION THERMOSTATS USED WITH SYSTXBBRRS01 Indoor Remote Room Temperature Sensor All T6— thermostats T6—EXP01—A ExP® Computer Programming Accessory T6—P thermostats TSTATXXCNV10 Thermostat Conversion Kit (4 to 5 wire) —10 pack All Bryant® branded thermostats TX—LBP01 Large Decorative Backplate T6—Pxx, T6—Nxx, and T2—Pxx TSTATXXSEN01—B Outdoor Air Temperature Sensor All T6— thermostats ACCESSORIES KIT NUMBER DESCRIPTION Size — Voltage & Series 0018—A 024—A 030—A 036—A 042—A 048—A 060—A KAAFT0101AAA FREEZE THERMOSTAT X X X X X X X KAATD0101TDR TIME DELAY RELAY X X X X X X X KSALA0301410 LOW AMBIENT PSW X X X X X X X KSALA0601AAAt MOTORMASTER 230V X X X X X X X HC32GE234 MOTOR FAN BALL BEARING X HC34GE240 MOTOR FAN BALL BEARING X X HC32GE229 MOTOR FAN BALL BEARING X HC38GE228 MOTOR FAN BALL BEARING X HC40GE228 MOTOR FAN BALL BEARING X X KSAHS1701AAA HARD START (CAP/RELAY) X X X X X X X KSACY0101AAA CYCLE PROTECTOR X X X X X X X KSASF0101AAA SUPPORT FEET X X X X X X X KAACS0201 PTC START ASSIST PTC X X X X X X X KAALS0201 LLS LIQUID LINE SOLENOID X X X X X X X KAAWS0101AAA WINTER START X X X X X X X KAACH1701AAA CRANKCASE HTR X X X X KAACH1601AAA CRANKCASE HTR X S S KSATX0201 PUR TXV PURON HSO X X X KSATX0301 PUR TXV PURON HSO X KSATX0401PUR TXV PURON HSO X KSATX0501 PUR TXV PURON HSO X X t Required accessories include ball bearing fan motor, compressor start assist (CAP / Relay), crankcase heater, evaporator freeze stat, hard shut—off TXV. X = Accessory / S — Standard ACCESSORY USAGE GUIDELINE REQUIRED FOR LOW-AMBI- REQUIRED FOR LONG REQUIRED FOR ACCESSORY ENT COOLING APPLICATIONS LINE APPLICATIONS* SEA COAST APPLICATIONS (Below 55017/12.80C) (Over 80 ft./24.38 m) (Within 2 miles/3.22 km) Ball Bearing Fan Motor Yest No No Compressor Start Assist Capacitor and Relay Yes Yes No Crankcase Heater Yes Yes No Evaporator Freeze Thermostat Yes No No Hard Shut -Off TXV Yes Yes Yes Liquid Line Solenoid Valve No No No Motor Master Control or Yes No No Low -ambient Pressure Switch Support Feet Recommended No Recommended Winter Start Control Yes No No * For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Split —System Longline Application Guideline. t Required for Low —Ambient Controller (full modulation feature) MotorMasterm Control. Accessory Description and Usage (Listed Alphabetically) 1. Ball —Bearing Fan Motor A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication. Usage Guideline: Required on all units when MotorMaster@ is used. 2. Compressor Start Assist — Capacitor and Relay Start capacitor and relay gives a "hard" boost to compressor motor at each start up. Usage Guideline: Required for reciprocating compressors in the following applications: Long line Low ambient cooling Hard shut off expansion valve on indoor coil Liquid line solenoid on indoor coil Required for single—phase scroll compressors in the following applications: Long line Low ambient cooling Suggested for all compressors in areas with a history of low voltage problems. 3. Compressor Start Assist — PTC Type Solid state electrical device which gives a "soft' boost to the compressor at each start—up. Usage Guideline: Suggested in installations with marginal power supply. 4. Crankcase Heater An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes the chance of liquid slugging. Usage Guideline: Required in low ambient cooling applications. Required in long line applications. Suggested in all commercial applications. 5. Cycle Protector The cycle protector is designed to prevent compressor short cycling. This control provides an approximate 5—minute delay after power to the compressor has been interrupted for any reason, including power outage, protector control trip, thermostat jiggling, or normal cycling. 6. Evaporator Freeze Thermostat An SPST temperature —actuated switch that stops unit operation when evaporator reaches freeze—up conditions. Usage Guideline: Required when low ambient kit has been added. 7. Low —Ambient Pressure Switch Kit A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure within normal operating limits (approximately 100 psig to 225 psig). The control will maintain working head pressure at low —ambient temperatures down to 0°F (-18°C) when properly installed. Usage Guideline: A Low —Ambient Pressure Switch or MotorMaster° Low —Ambient Controller must be used when cooling operation is used at outdoor temperatures below 55°F (12.8°C). 8. MotorMaster® Low —Ambient Controller A fan —speed control device activated by a temperature sensor, designed to control condenser fan motor speed in response to the saturated, condensing temperature during operation in cooling mode only. For outdoor temperatures down to —20°F (-28.9°C), it maintains condensing temperature at 100°F ±10°F (37.8°C ± 5.5 ° C). Usage Guideline: A MotorMaster® Low Ambient Controller or Low —Ambient Pressure Switch must be used when cooling operation is used at outdoor temperatures below 55°F (12.8°C). Suggested for all commercial applications. 9. Outdoor Air Temperature Sensor Designed for use with Bryant Thermostats listed in this publication. This device enables the thermostat to display the outdoor temperature. This device also is required to enable special thermostat features such as auxiliary heat lock out. Usage Guideline: Suggested for all Bryant thermostats listed in this publication. Accessory Description and Usage (Listed Alphabetically) 10. Support Feet Four stick —on plastic feet that raise the unit 4 in. (101.6 mm) above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base, minimizing corrosion. Usage Guideline: Suggested in the following applications: Coastal installations. Windy areas or where debris is normally circulating. Rooftop installations. For improved sound ratings. 11. Thermostatic Expansion Valve (TXV) A modulating flow —control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Hard shut off types are available. NOTE: When using a hard shut off TXV with single phase reciprocating compressors, a Compressor Start Assist Capacitor and Relay is required. Usage Guideline: Required to achieve AHRI ratings in certain equipment combinations. Refer to combination ratings. Hard shut off TXV or LLS required in air conditioner long line applications. Required for use on all zoning systems. (Continued) 12. Time —Delay Relay An SPST delay relay which briefly continues operation of indoor blower motor to provide additional cooling after the compressor cycles off. NOTE: Most indoor unit controls include this feature. For those that do not, use the guideline below. Usage Guideline: For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to AHRI Unitary Directory. 13. Winter Start Control This control is designed to alleviate nuisance opening of the low—pressure switch by bypassing it for the first 3 minutes of operation. ELECTRICAL DATA UNIT SIZE V/PH OPER VOLTS* MAX MIN COMPR LRA RLA FAN FLA MCA MIN WIRE SIZEt 60' C MIN WIRE SIZEt 75° C MAX LENGTH GT GTH . ( ) MAX LE m$ 75�) MAX FUSE** or CKT BRK AMPS 018-A 208/230/1-60 253 197 48.0 9.0 0.50 11.8 14 14 67 (20.4) 64 (19.5) 20 024-A 58.3 13.5 0.70 17.6 14 14 46 (14.0) 43(13.1) 25 030-A 64.0 12.8 0.70 16.7 14 14 44 (13.4) 41 (12.5) 25 036-A 77.0 14.1 0.50 18.1 12 12 57 (17.4) 54 (16.5) 30 042- 112.0 17.9 1.20 23.6 10 10 85 (25.9) 81 (24.7) 40 048-A 109.0 19.9 1.20 26.1 10 10 70 (21.3) 67 (20.4) 40 060-A 135.0 21.4 1.20 28.0 8 10 91 (27.7) 56 (17.1) 40 * Permissible limits of the voltage range at which the unit will operate satisfactorily t If wire is applied at ambient greater than 30°C, consult table 310-16 of the NEC (NFPA 70). The ampacity of non -metallic -sheathed cable (NM), trade name ROMEX, shall be that of 60oC conditions, per the NEC (NFPA 70) Article 336-26. If other than uncoated (no -plated), 60 or 75°C insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70). t Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%. ** Time -Delay fuse. FLA - Full Load Amps LRA - Locked Rotor Amps MCA -Minimum Circuit Amps RLA - Rated Load Amps NOTE: Control circuit is 24-V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection. Complies with 2010 requirements of ASHRAE Standards 90.1 A -WEIGHTED SOUND POWER LEVEL (dBA) Unit Size - Voltage, Series Standard Rating (dBA) TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment) 125 250 500 1000 2000 4000 8000 018-A 73 49.5 58.5 64.5 69.0 63.0 59.5 52.4 024-A 74 54.5 62.0 67.0 71.5 66.0 62.0 53.0 030-A 74 56.0 62.5 66.0 68.5 64.5 61.0 53.5 036-A 72 52.0 61.0 64.0 66.0 61.0 58.5 51.5 042-A 74 56.5 61.5 65.0 66.5 163.5 61.0 56.5 048-A 73 58.0 61.0 65.0 66.0 62.0 58.0 51.0 -A 74 56.5 62.5 66.5 68.0 63.0 59.5 51.5 NOTE: Tested in accordance with AHRI Standard 270-08 (not listed in AHRI). CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE) UNIT SIZE -VOLTAGE, SERIES REQUIRED SUBCOOLING °F (°C) 018-A 10(5.6) 024-A 10(5.6) 030-A 10(5.6) 036-A 10(5.6) 042-A 9(5.0) 048-A 10(5.6) 60- 9(5.0) V DIMENSIONS - ENGLISH UNIT SERIES ELECTRICAL CHARACTERISTICS A B C D E F G K L M N P OPERATING WEIGHT (Ibs) SHIPPING WEIGHT (Ibs) SHIPPING DIMENSIONS (L x W x H) 1268NA018 A X 0 0 0 25 3/4" 28 11/16" 3 3/4" 3/4" 4 7/16" 21 1/4" 7 13/16" 2 13/16" 1/2" 13 114" 13 314" 12 3/4" 136 163 26 7/8" X 30 1/16" X 32 9/16" 1268NA024 A X 0 0 0 31 3/16" 28 5/16" 3 3/4" 3/4" 6 9/16" 24 11/16" 9 1/8" 2 13/16" 1/2" 15 5/8" 15 1/2" 14" 163 198 32 3/8" X 35 1/2" X 32 9/16" 126BNA030 A X 0 0 0 31 3/16" 32 5/16" 3 314" 3/4" 6 9/16" 24 11/16" 9 1/8" 2 13116" 112" 16 1/2" 15" 14 314" 167 204 32 3/8" X 35 1/2" X 35 15/16" T265NA035 A X 0 0 0 35" 28 5/16" 3 718" 7/8" 6 9116" 28 7/16" 9 1/8" 2 15/16" 518" 18 1/4" 16 7/8" 14" 180 219 36 1/8" X 39 5116" X 32 9116" 1 A X 0 0 0 35" 39 1/8" 3 7/8" 1/8" 6 9/16" 28 7/16" 9 1/8" 2 15/16" 5/8" 18" 16" 17 1/2" 234 281 36 1/8" X 39 5/16" X 42 3/4" 126BNA048 A X 0 0 0 35" 32 5/16" 3 7/8" 1/8" 6 9/16" 28 7/16" 9 1/8" 2 15/16" 5/B" 17" 11 1/2" 14" 248 291 36 1/8" X 39 5/16" X 35 15/16" 1268NA060 A X 0 0 0 35" 45 15/16" 3 7/8" 1 7/8" 1 6 9/16" 28 7/16" 9 1/8" 2 15/16" 1 5/8" 17 718" 18 5/8" 20 1/4" 337 372 36 1/8" X 39 5/16" X 49 9/16" C> C) X = YES C)M C) O=NO co �7 CIJ C:)O m O N Co C)N N FIELD CONTROL SUPPLY CONN. 07/8" HOLE FIELD POWER SUPPLY CONN. 0 7/8" HOLE WITH 01 1/8" KNOCKOUT o 03/8" LIQUID LINE CONN. �[E C 3 112" O D VAPOR LINE CONN MINIMUM UNIT SIZE MOUNTING PAD DIMENSIONS 18 26" X 26' 24,30 31 1/2" X 31 1/2" 36 THRU 60 35" X 35' SQ. AI\SCHARGE/ 1 7/8" (2) PLACES NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW. 2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE IS W F, MAX. 125'F. 3. SERIES DESIGNATION IS THE 10TH POSITION OF THE UNIT MODEL NUMBER. 4. CENTER OF GRAVITY �. 5. ALL DIMENSIONS ARE IN "INCHES" UNLESS NOTED. AIR IN DIMENSIONS - SI UNIT SERIES ELECTRICAL CHARACTERISTICS A B C D E F G K L M N P OPERATING WEIGHT (K sl SHIPPING WEIGHT (K s) SHIPPING DIMENSIONS IL x W x H) 126BNA018 A X 0 0 0 654.0 728.7 95.2 19.0 112.7 539.8 198.4 71.4 12.7 336.6 349.3 323.9 61.7 73.9 682.6 X 763.6 X 827.1 1260NA024 A X 0 0 0 792.2 719.2 95.2 19.0 166.7 627.1 231.8 71.4 12.7 396.9 393.7 355.6 73.9 89.8 822.3 X 901.7 X 827.1 1268NA030 A X 0 0 0 792.2 820.8 95.2 19.0 166.7 627.1 231.8 71.4 12.7 419.1 381.0 374.7 75.7 92.5 822.3 X 901.7 X 912.8 1268NA036 A X 0 0 0 889.0 719.2 98.6 22.2 166.7 722.3 231.8 74.6 15.9 463.6 428.6 355.6 81.6 99.3 917.6 X 998.6 X 827.1 jjjDA&ULj A X 0 0 0 889.0 993.8 98.fi 22.2 166.7 722 231.8 74.6 15.9 451.2 406.4 444.5 106.1 121.5 917.6 X 998.6 X 1085.8 126E NA048 A X 0 0 0 889.0 820.8 98.6 22.2 166.7 722.3 231.8 74.6 15.9 431.8 444,5 355.6 112.5 132.0 917.6 X 998.6 X 912.6 126B A 660 A X 0 0 0 889.0 1166.8 96.6 22.2 166.7 722.3 231.8 74.6 15.9 454.0 473.1 514.4 152.9 168.7 917.6 X 998.6 X 1258.9 coo O o X = YES O (D T 0 O = N O o M N M N O CD 0 N 00 N N MINIMUM UNIT SIZE MOUNTING PAD DIMENSIONS 18 660.4 X 660.4 24,30 800.1 X 800.1 36 THRU 60 889.0 X 889.0 NOTES: 1. ALLOW 762.0 CLEARANCE TO SERVICE SIDE OF UNIT, 1219.2 ABOVE UNIT, 152.4 ON ONE SIDE, 304.8 ON REMAINING SIDE, AND 609.6 BETWEEN UNITS FOR PROPER AIRFLOW. 2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE IS 13-C, MAX. 52°C. 3. SERIES DESIGNATION IS THE 10TH POSITION OF THE UNIT MODEL NUMBER. 4. CENTER OF GRAVITY �. 5. ALL DIMENSIONS ARE IN "MM" UNLESS NOTED. AIR IN CLEARANCES wall 6" 52.4 m 24" (609.6) Service 12" (304.8) 24" (609.6) Service 24" (609.6) Clearances (various examples) 12" (304.8) 24" (609.6) Note: Numbers in () = mm M 24" (609.6) Service 12" (304.8) 24" (609.6) Wall 24" Service 12" (304.8) 24" (609.6) Service 6" 52.4) IMPORTANT: When installing multiple units in an alcove, roof well, or partially enclosed area, ensure there is adequate ventilation to prevent re —circulation of discharge air. TESTED AHRI COMBINATION RATINGS* NOTE: Ratings contained in this document are subject to change at any time. For AHRI ratings certificates, please refer to the AHRI directory www.ahridirectory.org Additional ratings and system combinations can be accessed via the Bryant database at: http //cactaxcredits infolbrryant-ratings/hp ratings srch php Equipment performance calculator can be accessed at: http://rpmobbry.wrightsoft.com/ Model Number Indoor Model Furnace Model Capacity EER SEER 126BNA024****A** CNPV*3117A**+TDR 23,600 12.0 14.5 126BNA030****A** CNPV*3117A**+TDR 28,600 12.0 14.5 126BNA036****A** CNPV*3717A**+TDR 34,400 12.0 14.5 126BNA042****A** CNPV*4324A**+TDR 41,500 12.0 14.5 126BNA048****A** CNPV*6124A**+TDR 46,500 12.8 14.6 126BNA060****A** CNPV*6124A**+TDR 55,000 13.0 15.1 * AHRI = Air Conditioning, Heating & Refrigeration Institute EER — Energy Efficiency Ratio SEER — Seasonal Energy Efficiency Ratio TOR — Time —Delay Relay. In most cases, only 1 method should be used to achieve TOR function. Using more than 1 method in a system may cause degradation in performance. Use either the accessory Tlme—Delay Relay KAATDO101TOR or a furnace equipped with TOR. Most Bryant furnaces are equipped with TDR. NOTES: 1. Ratings are net values reflecting the effects of circulating fan motor heat. Supplemental electric heat is not included. 2. Tested outdoorfndoor combinations have been tested in accordance with DOE test procedures for central air conditioners. Ratings for other combinations are determined under DOE computer simulation procedures. 3. Determine actual CFM values obtainable for your system by referring to fan performance data in fan coil or furnace coil literature. 4. Do not apply with capillary tube coils as performance and reliability are affected. 12 DETAILED COOLING CAPACITIES# EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F CC) 75 (23.9) 85 (29.4) 95 (35) 1 105 (40.6) 115 (46.1) 125 (51.7) CFM EWB °F (°C) Capacity MBtuh Total System KW** Capacity MBtuh Total System FON*' Capacity MBtuh Total System KW** Capacity MBtuh Total System KW** Capacity MBtuh Total System KW** Capacity MBtuh Total System KW** Total Sons* Totet Sens$ Total Sens# i Total Sens# Total Sens$ Total Sens$ 72 (22.2) 21.52 10.39 1.18 20.55 10.05 1.32 19.48 9.68 1.48 18.35 9.29 1.65 17.15 8.88 1.84 15.88 8.46 2 06 67 (19.4) 19.59 12.69 1.18 18.66 12.32 1.32 17.68 11.95 1.47 16.64 11.56 1.64 15.54 11.14 1.83 14.37 10.72 2.05 525 63 (17.2)tt 18.14 12.20 1.18 17.28 11.84 1.32 16.37 11.47 1.47 15.40 11.07 1.63 14.37 10.66 1.82 13.27 10.22 2.04 62 (16.7) 17.80 14.92 1.18 16.97 14.56 1.31 16.08 14.18 1.47 15.17 13.78 1.63 14.30 14.30 1.82 13.42 13.42 2.04 57 (13.9) 17.19 17.19 1.18 16.54 16.54 1.31 15.84 15.84 1.46 15.09 15.09 1.63 14.27 14.27 1.82 13.40 13.40 2.04 72 (22.2) 21.94 10.93 1.21 20.92 10.58 1.35 19.82 10.21 1.51 18.63 9.81 1.68 17.39 9.40 1.87 16.07 8.97 2.09 67 (19.4) 19.99 13.55 1.20 19.03 13.19 1.35 18.00 12.80 1.50 16.92 12.40 1.67 15.78 11.98 1.86 14.57 11.54 2.08 600 63 (17.2)tt 18.55 13.02 1.20 17.64 12.65 1.34 16.68 12.26 1.49 15.68 11.86 1.66 14.60 11.44 1.85 13.47 10.99 2.07 62 (16.7) 18.25 16.11 1.20 17.39 15.72 1.34 16.55 16.55 1.49 15.74 15.74 1.66 14.87 14.87 1.85 13.93 13.93 2.07 57 (13.9) 17.99 17.99 120 17.28 1728 1.34 16.53 16.53 1.49 15.72 15.72 1.66 14.85 14.85 1.85 13.91 13.91 2.07 72 (22.2) 22.24 11.45 123 21.19 11.09 1.38 20.06 10.72 1.54 18.83 10.32 1.71 17.55 9.90 1.90 1620 9.47 2.12 67 (19.4) 20.29 14.38 123 19.30 14.01 1.37 18.24 13.62 1.53 17.13 13.22 1.70 15.95 12.79 1.89 14.72 12.34 2.10 675 63 (17.2)tt 18.85 13.79 1.23 17.91 13.42 1.37 16.92 13.03 1.52 15.88 12.61 1.69 14.78 12.18 1.88 13.63 11.73 2.10 62 (16.7) 18.68 18.68 1.23 17.93 17.93 1.37 17.12 17.12 1.52 16.26 16.26 1.69 15.33 15.33 1.88 14.35 14.35 2.10 57 (13.9) 18.66 18.66 1.23 17.90 17.90 1.37 17.09 17.09 1.52 16.24 16.24 1.69 15.31 15.31 1.88 14.33 14.33 2.10 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F CC) 75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7) CFM EWB `F ("C) Capacity MBtuh Total yst System Capacity MBtuh Told System KW** 126BNA024-A Capacity MBtuh Total System KW** With CNPV*3117A** Capacity MBtuh Total System KW** Capacity MBtuh Total System KW** Capacity MBtuh Total System KW** Total Sons* Total Sens# Total Sens# Outdoor Section Total Indoor Sens# Section Total Sens# Total Sens$ 72 (22.2) 28.21 13.70 1.55 26.92 13.25 1.74 25.54 12.78 1.94 24.09 1229 2.16 22.56 11.77 2.41 20.94 11.24 2.68 67 (19.4) 25.63 16.78 1.55 24.44 16.32 1.73 23.19 15.85 1.93 21.87 15.36 2.15 20.47 14.84 2.39 18.98 14.29 2.67 700 63 (17.2)tt 23.72 16.13 1.55 22.62 15.67 1.73 21.46 15.20 1.92 20.22 14.70 2.14 18.91 14.18 2.38 17.52 13.62 2.67 62 (16.7) 23.32 19.80 1.55 22.25 19.34 1.73 21.14 18.86 1.92 20.00 19.96 2.14 18.95 18.95 2.38 17.82 17.82 2.67 57 (13.9) 22.68 22.68 1.55 21.84 21.84 1.73 20.93 20.93 1.92 19.96 19.96 2.14 18.92 18.92 2.38 17.79 17.79 2.67 72 (22.2) 28.72 14.43 1.58 27.38 13.97 1.77 25.95 13.49 1.98 24.44 12.99 2.20 22.85 12.47 2.44 21.17 11.93 2.72 67 (19.4) 26.16 17.95 1.58 24.91 17.49 1.77 23.60 17.00 1.97 22.22 16.49 2.19 20.76 15.96 2.43 1923 15.41 2.71 800 63 (17.2)tt 24.23 17.22 1.58 23.08 16.75 1.77 21.86 16.27 1.96 20.58 15.76 2.18 19.21 15.22 2.42 17.78 14.66 2.70 62 (16.7) 23.91 21.38 1.58 22.85 22.74 1.77 21.85 21.85 1.96 20.81 20.81 2.18 19.69 19.69 2.42 18.49 18.49 2.71 57 (13.9) 23.70 23.70 1.58 22.79 22.79 1.76 21.82 21.82 1.96 20.78 20.78 2.18 19.66 19.66 2.43 18.46 18.46 2.71 72 (22.2) 29.09 15.12 1.62 27.72 14.67 1.81 26.23 14.18 2.02 24.68 13.67 2.24 23.05 13.15 2.48 21.32 12.60 67 (19.4) 26.54 19.08 1.62 25.25 18.60 1.81 23.90 18.11 2.01 22.48 17.59 222 20.98 17.05 2.47 19.42 16.48 900 63 (17.2)tt 24.61 18.27 1.62 23.42 17.79 1.80 22.16 17.30 2.00 20.84 16.78 2.22 19.45 16.23 2.46 17.98 15.65 E2.74 62(16.7) 24.60 24.60 1.62 23.62 23.62 1.80 22.58 22M 2.00 21.48 21.48 222 20.29 20.29 2.47 19.02 19.02 57(13.9) 24.56 24.56 1.62 23.59 23.59 1.80 22.55 22M 2.00 21.45 21.45 222 2027 20.27 2.47 18.99 18.99 See notes on pg. 16 DETAILED COOLING CAPACITIES# (CONT.) CONDENSER ENTERING AIR TEMPERATURES °F (°C) EVAPORATOR AIR 75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7) CFM EWB of �) Capacity MBtuh Total System KW** Capacity MBtuh Total System KW** Capacity MBtuh Total System KW** Capacity MBtuh TO�I System KW** Capacity MBtuh Total System KW** Capacity �Bl.uh Total System KW** Total Sens# Total Sens# Total Outdoor Sens$ Section126BNA030-A Total Indoor Son s# Section Total Sens# Total es# 72 (22.2) 34.09 17.01 1.91 32.58 16.48 2.11 31.00 15.93 2.33 29.32 15.36 2.59 27.51 14.75 2.88 25.53 14.09 67(19.4) 30.99 20.96 1.92 29.61 20.43 212 28.16 19.88 2.34 26.61 19.29 2.59 24.93 18.66 2.88 23.10 17.99 675 63 (17.2)1t 28.76 20.15 1.93 27.47 19.62 212 26.11 19.06 2.34 24.65 18.46 2.59 23.07 17.83 2.88 21.33 17.13 62(16.7) 28.31 24.86 1.93 27.08 24.31 2.12 25.80 23.72 2.34 24.56 24.56 259 23.28 23.28 2.88 21.87 21.87 a26 57(13.9) 27.76 27.76 1.93 26.76 26.76 2.12 25.69 25.69 2.34 24.52 24.52 2.59 23.25 2325 2.88 21.83 21.83 72(22.2) 34.67 17.91 1.96 33.09 17.37 2.15 31.45 16.82 2.38 29.71 16.24 2.63 27.83 15.62 2.93 25.79 14.9567(19.4) 31.55 22.41 1.97 30.10 21.86 216 28.60 21.30 2.38 27.00 20.71 2.64 25 227 20.07 2.93 23.39 19.37 1000 63 (17.2)jt 29.30 21.50 1.97 27.95 20.95 2.17 26.55 20.38 2.39 25.04 19.78 1 2.64 23.40 19.12 2.93 21.63 18.42 3.26 62 (16.7) 29.03 28.77 1.97 27.89 27.89 2.16 26.74 26.74 2.39 25.50 25.50 1 2.64 24.14 24.14 2.93 22.64 22.64 3.26 57 (13.9) 28.93 28.93 1.97 27.84 27.84 216 26.70 26.70 2.39 25.46 25.46 2.64 24.11 24.11 2.93 22.61 22.61 3.26 72 (22.2) 35.09 18.77 2.00 33.45 18.22 2.20 31.76 17.66 2.42 29.97 17.07 2.68 28.04 16.45 2.97 25.96 15.78 3.31 67 (19.4) 31.96 23.80 2.01 30.47 23.24 2.21 28.93 22.67 2.43 27.29 22.06 2.68 25.52 21.41 2.97 23.62 20.69 3.31 1125 63 (17.2)jt 29.70 22.78 2.02 28.32 22.23 2.21 26.87 21.65 2.43 25.32 21.03 2.69 23.66 20.36 2.98 21.87 19.61 3.31 62 (16.7) 29.93 29.93 2.02 28.78 28.78 2.21 27.57 27.57 2.43 26.26 26.26 2.68 24.83 24.83 2.97 23.26 23.26 3.31 57 (13.9) 29.89 29.89 2.02 28.74 28.74 221 27.53 27.53 2.43 26.22 26.22 2.68 24.80 24.80 2.97 23.23 23.23 3.31 CONDENSER ENTERING AIR TEMPERATURES °F CC) EVAPORATOR AIR 75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7) CFM EWB °F CC) Capacity MBtuh Total System System KW** Capacity MBtuh Total System KW** 126BNA036-A Capacity MBtuh Total System KW** With CNPV*3717A** Capacity MBtuh Total System KW** Capacity MBtuh TO�I System ICW** Capacity MBtuh Total System KW- Sens# Total Sens# Total Sens# Outdoor Section Total Indoor I Sens# Section Total Sens# Total I Sens# 72 (22.2) 34.09 17.01 1.91 32.58 16.48 2.11 31.00 15.93 2.33 29.32 15.36 2.59 27.51 14.75 2.88 25.53 14.09 3.22 67 (19.4) 30.99 20.96 1.92 29.61 20.43 212 28.16 19.88 2.34 26.61 19.29 2.59 24.93 18.66 2.88 23.10 17.99 3.22 875 63 (17.2)jt 28.76 20.15 1.93 27.47 19.62 212 26.11 19.06 2.34 24.65 18.46 259 23.07 17.83 2.88 21.33 17.13 3.22 62 (16.7) 28.31 24.86 1.93 27.08 24.31 212 25.80 23.72 2.34 24.56 24.56 2.59 23.28 2328 2.88 21.87 21.87 3.21 57 (13.9) 27.76 27.76 1.93 26.76 26.76 212 25.69 25.69 2.34 24.52 24.52 2.59 2325 23.25 2.88 21.83 21.83 3.21 72 (22.2) 34.67 17.91 1.96 33.09 17.37 2.15 31.45 16.82 2.38 29.71 16.24 2.63 27.83 15.62 2.93 25.79 14.95 3.26 67 (19.4) 31.55 22.41 1.97 30.10 21.86 216 28.60 21.30 2.38 27.00 20.71 2.64 25.27 20.07 2.93 23.39 19.37 326 1000 63 (17.2)tt 29.30 21.50 1.97 27.95 20.95 2.17 26.55 20.38 2.39 25.04 19.78 2.64 23.40 19.12 2.93 21.63 18.42 3.26 62 (16.7) 29.03 28.77 1.97 27.89 27.89 2.16 26.74 26.74 2.39 25.50 25.50 2.64 24.14 24.14 2.93 22.64 22.64 326 57 (13.9) 28.93 28.93 1.97 27.84 27.84 2.16 26.70 26.70 2.39 25.46 25.46 2.64 24.11 24.11 2.93 22.61 22.61 326 72 (22.2) 35.09 18.77 2.00 33.45 18.22 2.20 31.76 17.66 2.42 29.97 17.07 2.68 28.04 16.45 2.97 25.96 15.78 3.31 67 (19.4) 31.96 23.80 2.01 30A7 23.24 2.21 28.93 22.67 2.43 27.29 22.06 2.68 25.52 21.41 2.97 23.62 20.69 3.31 1125 63 (17.2)jt 29.70 22.78 2.02 28.32 22.23 2.21 26.87 21.65 2.43 25.32 21.03 2.69 23.66 20.36 2.98 21.87 19.61 3.31 62 (16.7) 29.93 29.93 2.02 28.78 28.78 2.21 27.57 27.57 2.43 26.26 26.26 2.68 24.83 24.83 2.97 2326 23.26 3.31 57 (13.9) 29.89 29.89 2.02 28.74 28.74 2.21 27.53 27.53 2.43 26.22 26.22 2.68 24.80 24.80 2.97 2323 23.23 3.31 See notes on pg. 16 U DETAILED COOLING CAPACITIES# (CONT.) EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES "F CC) 75 (23.9) 85 (29.4) 95 (35) 1 105 (40.6) 115 (46.1) 125 (51.7) CFM Eyyg IF(,C) Capacity MBtuh Total System KW** Ca ac' MBtuh p aY Total System KW- 126BNA042-A Capaci MBtuh ty Total System KW** With CNPV*4324A** Capacity MBtuh Total System KW** Capacity MBtuh Total System Kyy** Capacity M��� Total System ICW*+ Total Sens# Total Sens* Total Outdoor Sens# Section Total Indoor Sens# Section Total Sens# Total 72 (22.2) 4958 24.85 2.77 47.31 24.05 3.07 44.88 23.20 3.42 42.30 22.31 3.60 39.58 21.39E4.17 23 36.71 20.43 4.70 67 (19.4) 45.17 30.63 2.75 43.10 29.82 3.05 40.90 28.98 3.38 38.55 28.08 3.76 36.07 27.1519 33.47 26.18 4.66 1225 63 (17.2)tt 41.97 29.47 2.74 40.06 28.67 3.03 38.02 27.83 3.36 35.83 26.93 3.74 33.53 26.00 31.10 25.02 4.64 62(16.7) 41.32 36.33 2.74 39.49 35.51 3.03 37.56 34.61 3.36 35.65 35.65 3.74 33.78 33.7817 31.76 31.76 4.64 57(13.9) 40.45 40.45 2.73 38.96 38.96 3.03 37.34 37.34 3.36 35.60 35.60 3.74 33.73 33.7317 31.72 31.72 4.64 72(222) 50.40 26.14 2.85 48.02 25.31 3.15 45.48 24A5 3.49 42.82 23.55 3.87 39.99 22.6130 37.62 21.63 4.77 67 (19.4) 45.95 32.69 2.82 43.80 31.87 3.12 41.50 31.00 1 3.46 39.07 30.09 3.84 36.51 29.14 4.26 33.83 28.13 4.74 1400 63 (17.2)tt 42.74 31.39 2.81 40.75 30.58 3.10 38.61 29.71 3.44 36.36 28.80 3.82 33.97 27.84 4.24 31.47 26.83 4.71 62 (16.7) 42.31 39.06 2.81 40.65 40.55 3.10 38.82 38.82 3.44 36.94 36.94 3.82 34.93 34.93 425 32.78 32.78 4.72 57 (13.9) 42.10 42.10 2.81 40.50 40.50 3.10 38.76 38.76 3.44 36.89 36.89 3.82 34.89 34.89 4.25 32.74 32.74 4.72 72 (22.2) 50.98 27.35 2.92 48.52 26.51 3.22 45.91 25.64 3.56 43.16 24.73 3.95 40.25 23.78 4.37 3722 22.79 4.85 67 (19.4) 46.53 34.66 2.90 44.31 33.82 3.19 41.95 32.94 3.53 39.45 32.01 3.91 36.83 31.03 4.34 34.11 29.99 4.81 1575 63 (17.2)tt 43.31 33.22 2.88 41.25 32.39 3.17 39.06 31.51 3.51 36.74 30.57 3.89 34.30 29.58 4.31 31.77 28.52 4.78 62 (16.7) 43.52 43.52 2.88 41.82 41.82 3.18 39.96 39.96 3.52 37.98 37.98 3.90 35.86 35.86 4.33 33.58 33.58 4.80 57 (13.9) 43.46 43.46 2.88 41.76 41.76 3.18 39.91 39.91 3.52 37.93 37.93 3.90 35.81 35.81 4.33 33.55 33.55 4.80 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F CC) 75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7) CFM Eyyg ,F �) Capacity MBtuh P nY Total System KW** Capacity MBtuh P aY Total System KW.* 126BNA048-A Capacity MBtuh P tY Total System KW** With CNPV*6124A** Capacity MBtuh P �►Y Total System KW+* Capacity MBtuh P �►1/ Total System rw** Capacity MBtuh Total System KW** Total Sense Total Sens* Total Outdoor Sens* Section Total Indoor Sens* Section Total Sens* Total Sens# 72 (222) 56.17 28.26 1 2.67 53.35 27.27 3.12 50.45 26.26 3.57 47.46 25.24 4.03 44.32 24.18 4.51 41.00 23.07 5.02 67 (19.4) 50.88 34.78 2.84 48.38 33.81 3.25 45.79 32.82 3.66 43.11 31.80 4.09 40.30 30.75 4.55 37.32 29.64 5.04 1400 63 (17.2)tt 47.10 33.38 2.95 44.81 32.43 3.33 4244 31.45 3.72 39.99 30.45 4.13 37.39 29.40 4.57 34.65 28.30 5.05 62 (16.7) 46.38 41.24 2.96 44.21 40.25 3.34 42.02 41.63 3.72 40.01 40.01 4.12 37.89 37.89 4.56 35.59 35.59 5.05 57 (13.9) 45.57 45.57 2.98 43.79 43.79 3.35 41.92 41.92 3.72 39.95 39.95 4.13 37.83 37.83 4.56 35.54 35.54 5.05 72 (222) 57.16 29.78 2.70 54.20 28.77 3.16 51.18 27.74 3.62 48.04 26.69 4.09 44.79 25.61 4.58 41.35 24.49 5.10 67 (19.4) 51.83 37.21 2.88 49.20 36.22 3.30 46.50 35.20 3.72 43.71 34.16 4.16 40.79 33.07 4.62 37.73 31.93 5.12 1600 63 (17.2)tt 48.01 35.64 1 2.99 45.60 34.66 3.39 43.14 33.66 3.78 40.57 32.63 4.20 37.89 31.55 4.64 35.07 30.41 5.13 62 (16.7) 47.62 47.39 3.00 45.65 45.65 3.38 43.62 43.62 3.77 41.49 41.49 4.18 39.20 39.20 4.63 36.74 36.74 5.12 57 (13.9) 47.51 47.51 3.00 45.58 4558 3.38 43.56 43.56 3.77 41.43 41.43 4.18 39.15 39.15 4.63 36.69 36.69 5.12 72 (22.2) 57.88 31.22 2.74 54.82 30.20 3.21 51.68 29.15 3.68 48.44 28.08 4.15 45.10 26.99 4.64 41.56 25.85 5.17 67 (19.4) 52.53 39.54 2.92 49.82 38.53 3.35 47.03 37.48 3.78 44.15 36.41 4.22 41.17 35.29 4.69 38.05 34.08 5.19 1800 63 (17.2)tt 48.69 37.80 3.04 46.20 36.80 3.44 43.65 35.77 3.85 41.02 34.70 4.27 38.28 33.58 4.71 35.42 32.36 5.20 62 (16.7) 49.20 49.20 3.02 47.12 47.12 3.42 44.96 44.96 3.82 42.68 42.68 4.24 4026 40.26 4.1 37.65 37.65 5.19 57 (13.9) 49.13 49.13 3.03 47.06 47.06 3.42 44.90 44.90 3.82 42.63 42.63 4.24 4021 40.21 4.70 37.61 37.61 5.19 See notes on pg. 16 DETAILED COOLING CAPACITIES# (CONT.) CONDENSER ENTERING AIR TEMPERATURES °F (°C) EVAPORATOR AIR 75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7) CFM EWB °F (°C) Capacity MBtuh P t7l Total System KW** Capacity MBtuh P tY Total System KW** i.0 Capacity MBtuh P ty TO�I System KW** Ca ac' MBtuh P nY TO�I System KW** Ca ac" MBtuh P nY TO�I System KW** Capacity MStuh P nY Total System KW** Total Sens# Total Sens# Total • Sens# Total D' Indoor Sens# Section Total Sens# Total Sens# 72 (22.2) 66.03 33.71 3.54 62.8E 32.49 3.92 59.49 31.24 4.33 55.92 29.95 4.78 52.09 26.60 5.29 47.94 27.18 5.8E 67 (19.4) 60.16 42.01 3.52 57.34 40.81 3.90 54.33 39.55 4.30 51.12 38.25 4.75 47.67 36.88 5.26 43.93 35.42 5.83 1750 63 (17.2)tt 55.92 40.36 3.52 53.34 39.17 3.88 50.59 37.93 4.28 47.64 36.64 4.73 44.45 35.28 5.23 41.00 33.82 5.81 62 (16.7) 55.30 50.14 3.52 52.96 52.74 3.88 50.72 50.72 4.28 48.29 48.29 4.73 45.62 45.62 5.24 42.65 42.65 5.83 57 (13.9) 54.87 54.87 3.51 52.85 52.85 3.88 50.64 50.64 4.28 48.23 48.23 4.73 45.56 45.56 5.24 42.60 42.60 5.83 72 (22.2) 66.94 35.49 3.63 63.63 34.26 4.01 60.13 32.98 4.43 56.41 31.66 4.88 52.46 30.30 5.39 48.19 28.86 5.96 67 (19.4) 61.07 44.91 3.62 56.11 43.67 3.99 55.00 42.39 4.40 51.67 41.04 4.85 48.13 39.62 5.3E 44.32 38.0E 5.93 2000 63 (17.2)tt 56.81 43.05 3.61 54.12 41.83 3.98 51.26 40.56 4.38 48.20 39.22 4.83 44.93 37.80 5.34 41.42 36.25 5.91 62 (16.7) 57.02 57.02 3.61 54.82 54.82 3.98 52.43 52.43 4.39 49.82 49.82 4.84 46.96 46.96 5.35 43.79 43.79 5.93 57 (13.9) 56.95 56.95 3.61 54.75 54.75 3.98 52.36 52.36 4.39 49.76 49.76 4.84 46.90 46.90 5.35 43.74 43.74 5.93 72 (22.2) 67.58 37.19 3.73 64.15 35.93 4.11 60.53 34.64 4.53 56.72 33.31 4.98 52.67 31.92 5.49 48.30 30.47 6.06 67 (19.4) 61.73 47.68 3.71 58.69 46.41 4.09 55.48 45.08 4.50 52.08 43.68 4.95 48.49 42.18 5.4E 44.72 44.52 6.03 2250 63 (17.2)tt 57.47 45.62 3.71 54.69 44.3E 4.08 51.76 43.04 4.48 48.64 41.65 4.93 45.33 40.11 5.43 41.94 41.94 6.01 62 (16.7) 58.71 58.71 3.71 56.35 56.35 4.08 53.80 53.80 4.49 51.03 51.03 4.94 48.01 48.01 5.45 44.66 44.66 6.03 57 (13.9) 58.64 58.64 3.71 56.29 56.29 4.08 53.74 53.74 4.49 50.98 50.98 4.94 47.96 47.96 5.45 44.62 44.62 6.03 t Total and sensible capacities are net capacities. Blower motor heat has been subtracted. t Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80OF (270C), deduct 835 Btuh (245 kW) per 1000 CFM (480 US) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kW) per 1000 CFM (480 US) of indoor coil air per degree above 80OF (27°C). # Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per AHRI standard 210/240-2008. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. ** System kw is total of indoor and outdoor unit kilowatts. ttAt TVA rating indoor condition (75°F edb/63*F ewb). All other indoor air temperatures are at 80°F edb. NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice. EWB - Entering Wet Bulb CONDENSER ONLY RATINGS SST CONDENSER ENTERING AIR TEMPERATURES °F (°C) °F (°C) 55 (12.78) 65 (18.33) 75 (23.89) 1 85 (29.44) 1 95 (35.0) 105 (40.56) 1 115 (46.11) 1 125 (51.67) 30 TCG 15.70 1 14.90 14.10 1 13.20 12.30 11,30 10.20 9.20 (-111) SDT 66.60 76.20 85.80 95.30 104.80 114.30 123.70 133.10 KW 0.75 0.87 0.99 1.12 1.26 1.41 1.60 1.81 35 TCG 17.50 16.60 15.70 14.70 13.70 12.60 11.50 10.30 (1.67) SDT 67.80 77.30 86.80 96.30 105.70 115.10 124.40 133.80 KW 0.75 0.87 0.99 1.12 1.26 1.42 1.60 1.81 40 TCG 19.40 18.40 17.40 16.30 15.20 14.00 12.80 11.50 (4.44) SDT 69.00 78.50 87.90 97.30 106.60 115.90 125.20 134.50 KW 0.74 0.87 0.99 1.12 1.26 1.42 1.60 1.81 45 TCG 21.50 20.30 19.20 18.00 16.70 15.60 14.10 12.80 (7.22) SDT 70.40 79.70 89.00 98.30 107.60 116.90 126.10 135.30 KW 0.74 0.86 0.99 1.13 1.27 1.43 1.61 1.82 50 TCG 23.60 22.40 21.10 19.70 18.40 17.00 15.60 14.10 (10.0) SDT 71.60 80.90 90.10 99.40 108.60 117.80 127.00 136.20 KW 0.73 0.86 1.00 1.13 1.28 1.44 1.62 1.82 55 TCG 25.90 24.50 23.10 21.60 20.10 18.60 17.10 15.50 (12 78) SDT 73.00 82.10 91.30 100.50 109.70 118.80 128.00 137.10 KW 0.73 0.86 1.00 1.14 1.29 1.45 1.63 1.84 30 TCG 21.10 20.10 1 19.00 1 17.90 16.70 15.40 14.10 12.70 SDT 66.10 75.80 85.30 94.90 104.40 114.00 123.40 132.80 KW 1.00 1.15 1.31 1.47 1.65 1.86 2.09 2.37 35 TCG 23.40 22.20 21.00 19.80 18.50 17.10 15.60 14.10 (1.67) SDT 67.20 76.80 86.30 95.80 105.30 114.70 124.10 133.50 KW 0.99 1.15 1.31 1.47 1.66 1.86 2.10 2.37 40 TCG 25.80 24.60 23.20 21.80 20.40 18.90 17.30 15.70 (4.44) SDT 68.40 77.90 87.30 96.70 106.10 115.50 124.80 134.10 KW 0.98 1.14 1.31 1.48 1.66 1.87 2.10 2.37 45 TCG 28.50 27.00 25.50 24.00 22.40 20.80 19.10 17.40 (7.22) SDT 69.60 79.00 88.30 97.70 107.00 116.30 125.60 134.90 KW 0.97 1.14 1.31 1.48 1.67 1.87 2.11 2.37 50 TCG 31.20 29.60 28.00 26.30 24.60 22.80 21.00 19.10 (10.0) SDT 70.80 80.10 89.40 98.70 107.90 117.20 126.40 135.60 KW 0.96 1.14 1.31 1.49 1.67 1.88 2.12 2.38 55 TCG 34.20 32.40 1 30.60 28.80 26.90 25.00 23.00 20.90 (12.78) SDT 72.10 81.30 90.50 99.70 108.90 118.10 127.30 136.40 KW 0.95 1.13 1.31 1.49 1.69 i 1.9 i2.13 2.39 30 TCG 24.90 1 23.50 22.20 1 20.80 19.40 1 17.90 16.20 14.40 (-111) SDT 68.10 77.50 87.00 96.40 105.80 115.10 124.40 133.60 KW 1.27 1.43 1.60 1.78 1.99 2.23 2.50 2.81 35 TCG 27.50 26.00 24.50 23.10 21.50 19.90 18.10 16.20 (1.67) SDT 69.40 78.70 88.10 97.40 106.70 116.00 125.30 134.40 KW 1.28 1.44 1.61 1.79 2.00 2.24 2.51 2.82 40 TCG 30.30 28.60 27.10 25.50 23.80 22.00 20.10 18.10 (4.44) SDT 70.70 79.90 89.20 98.50 107.70 117.00 126.20 135.30 KW 1.29 1.44 1.61 1.80 2.01 2.25 2.52 2.83 45 TCG 33.30 31.50 29.80 28.00 26.20 24.30 22.30 20.10 (7.22) SDT 72.00 81.20 90.40 99.60 108.80 118.00 127.20 136.30 KW 1.29 1.44 1.61 1.80 2.01 2.26 2.53 2.85 50 TCG 36.50 34.50 32.60 30.70 28.80 26.70 24.50 22.20 (10.0) SDT 73.50 82.50 91.70 100.80 110.00 119.20 128.20 137.20 KW 1.29 1.44 1.61 1.80 2.02 2.26 2.54 2.86 55 TCG 39.90 37.80 35.70 33.60 31.50 29.30 26.90 24.40 (12.78) SDT 75.00 84.00 93.00 102.10 111.20 120.30 129.30 138.0 KW 1.29 1.44 1.61 1.80 2.02 2.27 2.54 2%6? 30 TCG 30.40 28.80 27.20 1 25.60 1 23.90 1 22.10 20.20 18.20 (-111) SDT 68.90 78.20 87.50 96.80 106.20 115.50 124.90 134.20 KW 1.49 1.72 1.95 2.21 2.49 2.81 3.20 3.64 35 TCG 33.50 31.80 30.10 28.30 26.50 24.50 22.50 20.30 (167) SDT 70.10 79.30 88.60 97.90 107.20 116.50 125.80 135.00 KW 1.49 1.73 1.96 2.22 2.50 2.82 3.20 3.65 40 TCG 37.00 35.10 33.20 31.20 29.20 27.10 24.90 22.60 (4.44) SDT 71.40 80.60 89.80 99.00 108.20 117.40 126.70 135.90 KW 1.50 1.73 1.97 2.23 2.51 2.84 3.21 3.65 45 TCG 40.60 38.60 36.50 34.30 32.10 29.80 27.40 24.90 (7,22) SDT 72.80 81.90 91.00 100.20 109.40 118.50 127.70 136.80 KW 1.51 1.75 1.99 2.24 2.53 2.85 3.23 3.66 50 TCG 44.50 42.30 40.00 37.70 35.20 32.70 30.10 27.40 (10.0) SDT 74.40 83.30 92.40 101.50 110.50 119.60 128.70 137.70 KW 1.53 1.76 2.01 2.26 2.55 2.87 3.24 3.67 55 TCG 48.70 46.20 43.70 41.20 38.50 35.80 33.00 30.00 (12 78) SDT 76.00 84.90 93.80 102.80 111.80 120.80 129.80 138.70 KW 1.55 1.79 2.03 2.29 1 2.57 2.90 3.26 3.69 See notes on page 18 17 CONDENSER ONLY RATINGS CONTINUED SST °F (°C) CONDENSER ENTERING AIR TEMPERATURES °F CC) 55(12.7 65 (18.33) 75 (23.89) 1 85 (29.44) 0. 95 (35.0) 105 (40.56) 115 (46.11) 125 (51.67) TCG 37.90 36.20 34.30 32.30 30.10 27.90 25.50 23.00 30 SDT 69.80 79.20 88.70 98.10 107.40 116.70 125.90 135.10 (-30 KW 1.83 2.03 2.26 2.54 2.86 3.22 3.63 4.09 TCG 41.90 40.00 37.90 35.70 33.30 30.80 28.30 25.60 35 SDT 71.20 80.60 89.90 99.20 108.40 117.70 126.80 136.00 (167) KW 1.84 2.04 2.28 2.56 2.88 3.24 3.65 4.10 TCG 46.10 44.00 41.70 39.20 36.70 34.00 31.20 28.30 40 SDT 72.70 81.90 91.20 100.40 109.60 118.70 127.80 136.90 (4.0 KW 1.85 2.05 2.30 2.58 2.90 3.26 3.67 4.13 TCG 50.70 48.30 45.80 43.10 40.20 37.30 34.30 31.10 5 45 SDT 74.20 83.30 92.50 101.60 110.80 119.80 128.90 137.90 (7 KW 1.86 2.07 2.32 2.60 2.92 3.29 3.70 4.15 TCG 55.50 52.90 50.10 47.10 44.00 40.80 37.50 34.10 50 SDT 75.80 84.80 93.90 103.00 112.00 121.00 130.00 138.90 (10.0) KW 1.87 2.09 2.34 2.63 2.95 3.32 3.73 4.19 TCG 60.70 57.70 54.60 51.30 47.90 44.40 40.80 37.10 55 SDT 77.40 86.40 95.40 104.40 113.40 122.30 131.20 140.00 (12 78) KW 1.89 2.11 2.36 2.66 = 0. 2.99 3.36 3.77 4.22 TCG 41.30 39,10 36.90 34.70 32.40 30,00 27.50 24.80 30 SDT 67.80 77.20 86.60 96.00 105.40 114.70 124.00 133.30 (- KW 2.01 2.31 2.59 2.89 3.19 3.54 3.93 4.38 TCG 45.60 43.20 40.80 38.30 35.80 33.20 30.40 27.60 35 SDT 69.00 78.30 87.70 97.00 106.30 115.60 124.80 134.10 (1.67) KW 1.94 2.27 2.58 2.89 3.21 3.56 3.95 4.39 TCG 50.50 47.70 45.00 42.20 39.40 36.60 33.60 30.50 40 SDT 70.40 79.60 88.80 98.00 107.20 116.50 125.70 134.80 (4.44) KW 1.84 2.20 2.54 2.87 3.21 3.57 3.97 4.41 TCG 55.70 52.60 49.50 46.50 43.40 40.20 36.90 33.50 45 SDT 71.80 80.80 90.00 99.10 108.30 117.40 126.60 135.70 (7.22) KW 1.69 2.09 2.46 2.83 3.19 3.57 3.98 4.43 TCG 61.40 57.90 54.50 51.00 47.60 44.10 40.50 36.70 50 SDT 73.20 82.20 91.30 100.30 109.40 118.50 127.50 136.50 (10.0) KW 1.50 1.94 2.36 2.76 3.15 3.55 3.98 4.44 TCG 67.60 63.60 59.80 55.90 52.10 48.20 44.20 40.10 55 SDT 74.70 83.70 92.60 101.60 110.60 119.60 128.50 137.40 (12.78) KW 1.26 1.75 2.21 2.65 i.0 3.08 3.51 3.97 4.44 TCG 45.10 43.80 42.30 40.50 38.50 36.20 33.50 30.50 30 SDT 69.00 78.40 87.70 97.10 106.40 115.60 124.80 134.00 (-30 KW 2.22 2.52 2.83 3.17 3.56 4.00 4.53 5.15 TCG 50.00 48.40 46.70 44.70 42.50 40.00 37.10 33.80 35 SDT 70.40 79.70 89.00 98.20 107.40 116.60 125.80 134.90 (1.5 KW 2.21 2.52 2.85 3.19 3.58 4.03 4.55 5.16 TCG 55.10 53.40 51.40 49.20 46.70 44.00 40.80 37.30 40 SDT 71.90 81.10 90.20 99.40 108.50 117.60 126.70 135.70 (4.0 KW 2.21 2.53 2.86 3.21 3.61 4.05 4.57 5.18 TCG 60.70 58.60 56.40 54.00 51.20 48.20 44.80 41.00 45 SDT 73.50 82.50 91.60 100.70 109.70 118.70 127.70 136.70 (7.22) KW 2.20 2.53 2.87 3.23 3.63 4.08 4.60 5.20 TCG 66.50 64.20 61.70 59.00 56.00 52.60 48.90 44.70 50 SDT 75.10 84.00 93.00 102.00 111.00 119.90 128.80 137.60 (10.0) KW 2.19 2.53 2.89 3.26 3.66 4.11 4.63 5.22 TCG 72.80 70.10 67.30 64.20 60.90 57.20 53.10 48.60 55 SDT 76.80 85.70 94.50 103.40 112.30 121.10 129.90 138.60 (12.78) KW 2.18 2.54 2.90 3.28 3.69 4.15 4.66 5.25 * AHRI listing applies only to systems shown in Combination Ratings table. KW - Outdoor Unit Kilowatts Only. SDT - Saturated Temperature Leaving Compressor ff) SST - Saturated Temperature Entering Compressor CF/'C) TCG - Gross Cooling Capacity (1000 Btuh) 18 GUIDE SPECIFICATIONS GENERAL System Description Outdoor —mounted, air—cooled, split —system air conditioner unit suitable for ground or rooftop installation. Unit consists of a hermetic compressor, an air—cooled coil, propeller —type condenser fan, and a control box. Unit will discharge supply air upward as shown on contract drawings. Unit will be used in a refrigeration circuit to match up to a packaged fan coil or coil unit. Quality Assurance Unit will be rated in accordance with the latest edition of AHRI Standard 210. — Unit will be certified for capacity and efficiency, and listed in the latest AHRI directory. — Unit construction will comply with latest edition of ANSI/ ASHRAE and with NEC. — Unit will be constructed in accordance with UL standards and will carry the UL label of approval. Unit will have c—UL—us approval. — Unit cabinet will be capable of withstanding Federal Test Method Standard No. 141 (Method 6061) 500—hr salt spray test. — Air—cooled condenser coils will be leak tested at 150 psig and pressure tested at 450 psig. — Unit constructed in IS09001 approved facility. Delivery, Storage, and Handling Unit will be shipped as single package only and is stored and handled per unit manufacturer's recommendations. Warranty (for inclusion by specifying engineer) — U.S. and Canada only. PRODUCTS Equipment Factory assembled, single piece, air—cooled air conditioner unit. Contained within the unit enclosure is all factory wiring, piping, controls, compressor, refrigerant charge PuronO (R-410A), and special features required prior to field start—up. Unit Cabinet Unit cabinet will be constructed of galvanized steel, bonderized, and coated with a powder coat paint. AIR—COOLED, SPLIT —SYSTEM AIR CONDITIONER 126B 1-1/2 TO 5 NOMINAL TONS Fans — Condenser fan will be direct —drive propeller type, discharging air upward. — Condenser fan motors will be totally enclosed, 1—phase type with class B insulation and permanently lubricated bearings. Shafts will be corrosion resistant. — Fan blades will be statically and dynamically balanced. — Condenser fan openings will be equipped with coated steel wire safety guards. Compressor — Compressor will be hermetically sealed. — Compressor will be mounted on rubber vibration isolators. Condenser Coil — Condenser coil will be air cooled. — Coil will be constructed of aluminum fins mechanically bonded to copper tubes which are then cleaned, dehydrated, and sealed. Refrigeration Components Refrigeration circuit components will include liquid —line shutoff valve with sweat connections, vapor —line shutoff valve with sweat connections, system charge of Puron@ (R-410A) refrigerant, and compressor oil. Unit will be equipped with high—pressure switch, low pressure switch and filter drier for Puron refrigerant. Operating Characteristics — The capacity of the unit will meet or exceed Btuh at a suction temperature of °F/°C. The power consumption at full load will not exceed kW. — Combination of the unit and the evaporator or fan coil unit will have a total net cooling capacity of Btuh or greater at conditions of CFM entering air temperature at the evaporator at °F/°C wet bulb and °F/°C dry bulb, and air entering the unit at °F/°C. — The system will have a SEER of Btuh/watt or greater at DOE conditions. Electrical Requirements — Nominal unit electrical characteristics will be v, single phase, 60 hz. The unit will be capable of satisfactory operation within voltage limits of v to V. — Unit electrical power will be single point connection. — Control circuit will be 24v. Special Features — Refer to section of this literature identifying accessories and descriptions for specific features and available enhancements. 19 SYSTEM DESIGN SUMMARY 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01—in. we. 2. Minimum outdoor operating air temperature for cooling mode without low —ambient operation accessory is 55°F (12.8°C). 3. Maximum outdoor operating air temperature is 125°F (51.7°C). 4. For reliable operation, unit should be level in all horizontal planes. 5. For interconnecting refrigerant tube lengths greater than 80 ft (23.4 m) and/or 35 ft (10.7 m) vertical differential, consult Residential Piping and Longline Guideline and Service Manual available from equipment distributor. 6. If any refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36 in. (914.4 mm) may be buried without further consideration. Do not bury refrigerant lines longer than 36 in. (914.4 mm), 7. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided. 8. Do not apply capillary tube indoor coils to these units. 9. Factory —supplied filter drier must be installed. © 2015 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 Edition Date: 08/15 Catalog No. PDS126B-05 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Replaces: PDS12613-04 20