APPROVED BLD WSEC LTG BLD2019-09512015 Washinqton State Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised Nov 2017
Project Info
Project Title: Edmonds Crossing Apartments
Date 7/26/19
Compliance
forms do not
Applicant Information. Provide contact information for individual who can respond
to inquiries about compliance form information provided.
For Building Department Use
require a
password to
Company Name: Haynes Wilson Lund Architects LLC
Company Address: 385 101st Avenue SE, Bellevue WA 98004
use. Instructional
and calculating
Applicant Name: Haynes Lund
cells are write-
protected.
Applicant Phone: 425-643-3921
Applicant Email: hwlarch@comcast.net
Project Description
2 New Building [Addition [ Alteration C No Lighting Scope
Include PROJ-SUM form (included in envelope forms workbook) with lighting compliance forms.
Interior Lighting System
General lighting to be ceiling mounted recessed LED downlights with supplementary wall
Description
sconsces in bathrooms.
® Interior Lighting Plans Included
Interior Lighting Power
® Building Area Method El Space -by -space Method
Allowance Method
Select method used in project.
Interior Lighting Controls
® All C405.2.1 - C405.2.8 Lighting Controls CC405.2 Exception 5 Luminaire Level
Lighting Controls (LLLC)
CAdditional Efficiency Package Option
C406.4 Enhanced Digital Lighting Controls
To comply with C406.4, no less than 90% of the total installed interior lighting power shall comply with the
required controls per C406.4.
Dwelling Unit Interior
Permanently installed interior lighting fixtures in dwelling units comply with: C No Dwelling
Lighting
C C405.2 thru C405.5 Commercial Lighting Controls and LPA Units
CC406.3 High Efficacy Lighting
C R404.1 Residential High Efficacy Lighting. Dwelling unit lighting complies with WSEC Residential
provisions in lieu of WSEC Commercial provisions.
Exterior Lighting System
Description
® Exterior Lighting Plans Included
Building Additions
Compliance Method
Interior lighting
Exterior lighting
Lighting systems in addition area comply with all applicable
provisions as a stand alone new construction project
Refer to Section C502.2.6 for additional
requirements.
Lighting systems in addition are combined with existing
r
L
building lighting systems to demonstrate compliance
Addition is combined with existing:
For interior lighting projects, include new + existing -to -remain interior lighting fixture wattage in Proposed
Lighting Wattage table in LTG-INT-BLD or LTG-INT-SPACE form.
For exterior lighting projects, include new + existing -to -remain exterior fighting fixture wattage in Proposed
Tradable and Proposed Non -Tradable Lighting Wattage tables in LTG-EXT form.
PLAN REVIEW ACCEPTANCE
FOR COMPLIANCE WITH THE APPLICABLE
CONSTRUCTION CODES IDENTIFIED BELOW.
® BUILDING ® STRUCTURAL
® MECHANICAL ® PLUMBING
ELECTRICAL ® ENERGY
® ACCESSIBILITY FIRE
PLAN REVIEW ACCEPTANCE OF DOCUMENTS
DOES NOT AUTHORIZE CONSTRUCTION TO
PROCEED IN VIOLATION OF ANY FEDERAL,
STATE, OR LOCAL REGULATIONS.
BY: ��� DATE:07/29/2020
WEST COAS CODE CONSULTANTS, INC.
Lighting Summary, cont.
2015 Washinqton State Enerqv Code Compliance Forms for Commercial Buildinqs includinq R2, R3, R4 over 3 stories and all R1 Revised Nov 2017
Project Title: Edmonds Crossing Apartments
Date 7/26/19
Change of Space Use
Existing interior lighting systems in areas under -going a change in space use are upgraded to
comply with LPAs for the new space types per Tables C405.4.2(1) or C405.4.2(2).
Identify interior spaces requiring LPD upgrade to the current Code in Proposed Lighting Wattage table in
LTG-INT-BLD or LTG-INT-SPACE form.
Interior and Exterior
Lighting Power
Interior lighting
Parking garage
Exterior lighting
Lighting Alterations
50% or more of existing are replaced
C
C
C
Select all Lighting Power and Lighting
Control elements that apply to the scope of
Less than 50% of existing are replaced
r
L
r
L
r
L
the retrofit project. If project includes a
combination of spaces where less than
50% of the existing fixtures are replaced in
Lamp and/or ballast replacement only —
existing total wattage not increased
r
L
r
L
r
L
some spaces, and 50% or more of the
fixtures are replaced in others, then
50% or more replaced - Total lighting power of new + existing -to -remain fixtures shall comply with total
LPA per Sections C405.4.2 and C405.5.2. Include new + existing -to -remain fixtures in Proposed Lighting
provide separate lighting power
compliance forms for the two retrofit
conditions. Spaces undergoing the same
type of retrofit may be combined into one
lighting power compliance form.
Wattage table in LTG-INT-BLD, LTG-INT-SPACE or LTG-EXT form.
Less than 50% replaced - Total lighting power of new + existing -to -remain fixtures shall not exceed the
total lighting power prior to alteration. Include new + existing -to -remain fixtures in the Proposed Lighting
Wattage table in LTG-INT-BLD, LTG-INT-SPACE or LTG-EXT form.
50% threshold applies to number of luminaires for interior spaces and parking garages, and total installed
Refer to Section C503.6 for additional
wattage for exterior luminaires.
requirements.
Lighting Controls
Interior lighting
Parking garage
Exterior lighting
All alteration lighting controls shall be
commissioned per C408.3.
New wiring installed to serve added
fixtures and/or fixtures relocated to new
r
L
r
L
r
L
circuit(s)
New or moved lighting panel
C
C
C
Interior space is reconfigured -
r
luminaires unchanged or relocated only
L
New wiring or circuit - For interior lighting, provide required manual controls per C405.2.3, occupancy
sensor controls per C405.2.1, daylight responsive controls per C405.2.4 and application specific lighting
CNo changes are being made to
the interior or exterior lighting
systems and existing space uses
controls per C405.2.5. For exterior lighting, provide required controls per C405.2.7.
New or moved panel - Provide all applicable lighting controls as noted for New Wiring and automatic time
switch controls per C405.2.2.
and configuration are not
Reconfigured interior space - Provide all required lighting controls that apply to a new interior space.
changed.
Application specific lighting control provisions per C405.2.5 do not apply to reconfigured spaces.
2015 Washington State Enerav Code Compliance Forms for Commercial Buildings includina R2. R3. R4 over 3 stories and all R1 Revised Nov 2017
Project Title: Edmonds Crossing Apartments
Date 7/26/19
Calculation
aew Construction C Addition - CAddition
For Building Department Use
Area NOTE 9
stand alone + existing
paces where < 50% of Spaces where z 50% of Spaces where the Use
uminaires are replaced luminaires are replaced is changing (C505)
LPA
/-- and CAdditional Efficiency Package Option
Calculation
C406.3 Reduced Interior Lighting Power
User Note
Type
To comply with C406.3, the Proposed LPD shall be 25% lower than the Target LPA.
Refer C406.3 for
to additional requirements.
Maximum Allowed Li hting Wattage NOTE 1
Watts Allowed
Location (plan #,
Gross Interior
Allowed
(watts/ft2 x area)
Building Area
room #, or ALL)
Area Description
Area in ft2
Watts per ft2
NOTE 2
Multifamily
A21, A70
Floor 1 dwelling units: 10, 11, 12, 13 & support
2895
0.41
1187
Multifamily
A22
Floor 2 dwelling units: 21 ,22, 23 & storage
2516
0.41
1032
Multifamily
IA23
Floor 3 dwelling units: 31, 32, 33 & storage
2516
0.41
1032
Total
7927
Proposed Lighting Wattage
Building Area
Location (plan #,
room #)
Fixture Description NOTE 3, 4, 5, 6
Number of
Fixtures
Watts ptil
Fixture NOTE 7
Watts Proposed
Multifamily
A21, A70
recessed LED downlights
43
13
559
Multifamily
A21, A70
bathroom wall sconce
5
14
70
Multifamily
A22
recessed LED downlights
33
13
429
Multifamily
A22
bathroom wall sconce
4
14
56
Multifamily
A23
recessed LED downlights
33
13
429
Multifamily
A23
bathroom wall sconce
4
14
56
Compliance by Building Area"" 8
Building Area
Warnings
Total Allowed
Watts
Total Proposed
Watts
Interior Lighting
Power Allowance
Multifamily
Confirm all fixtures are reported under proposed lighting - low watts relative
to maximum allowed.
3251
1599
COMPLIES
Note 1 - List all unique building areas per Table C405.4.2(1) that occur in the Totals 3251 1 1599
project scope. Select building area category from drop down menu.
Note 2 - Unfit Message - Enter lighting fixture information for this building area surface in Proposed Lighting Wattage table to generate Lighting
Power Allowance.
Note 3 - Proposed fixtures must be listed in the building area in which they occur. List all proposed lighting fixtures including exempt
lighting equipment and existing -to -remain fixtures.
Note 4 - For proposed Fixture Description, indicate fixture type, lamp type (e.g. T-8), number of lamps in the fixture, and ballast type (if included).
For track lighting, list the length of the track (in feet) in addition to the fixture, lamp, and ballast information.
Note 5 - For lighting equipment eligible for exemption per C405.4.1, note exception number and leave Watts/Fixture blank.
Note 6 - Existing -to -remain fixtures shall be included in the Proposed Lighting Wattage table in the same manner as new fixtures. Identify as
existing in fixture description.
Note 7 - For proposed Watts/Fixture enter the luminaire wattage for installed lamp and ballast using manufacturer or other approved source. For
luminaires with screw -in lamps, enter the manufacturer's listed maximum input wattage of the fixture (not the lamp wattage). For low voltage
lighting, enter the wattage of the transformer. For line voltage tracklbusway systems, enter the larger of the attached luminaire wattage or
50 watts/lineal foot, or enter the wattage limit of permanent current limiting device.
Note 8 - Proposed Wattage for each Building Area type shall not exceed the Allowed Wattage for that Building Area type. Trading wattage
between Building Area types is not allowed under the Building Area Method compliance path.
wore m - i.aIcwaoon Area UWaos:
a. Lighting fixtures in a building addition may comply as a stand alone project, or they may be combined with the overall existing building
lighting systems to demonstrate compliance. Refer to C502.1.
b. For alterations and building additions, provide Building Area types and gross interior areas in the Maximum Allowed Lighting Wattage
table. If a building addition will comply as combined with the overall existing building lighting systems, include all applicable existing
Ruildina Area tvnes and arnss interim areas_
2015 Washinqton State Energy Code Compliance Forms for Commercial Buildinqs includinq R2, R3, R4 over 3 stories and all R1 Revised Nov 2017
Project Title: Edmonds Crossing Apartments
Date 7 /2 6 / 19
Exterior Lighting
Zone
co Zone 1 OZone 2 CZone 3 O Zone 4
Exterior Lighting Zone selection required to enable LTG-EXT form. Zones
are defined in Table C405.5.2(1) and specified by the jurisdiction.
For Building Department Use
Calculation Area
Co New construction CAddition - stand alone CAddition
+ existing
CAlteration with < 50% i�AIteration with >_ 50% ext.
ext. wattage replaced wattage replaced
User Note
Building Grounds
Applies to individual
luminaires > 100 Watts
D( Efficacy > 80 lumens/watt C Exemption
Controlled by motion sensor
Tradable Maximum Allowed Lighting Wattage NOTE 1 Base Site Allowance:
500
Tradable Surfaces
Surface Description
Area (ft), perimeter (If)
or # of items
Allowed Watts
per ftZ or per If
Allowea Watts
x ftZ (or x If) 11T12
Uncovered Parking and drives
parking lot
6243
0.04 W/ft2
250
Grounds Walkways <10 wide
entry walkway & circulation within structure
1950
0.7 W/LF
1365
Main Entry Door
unit entries
225
20W/LF door
4500
Other Entry Door
unit patios & decks
727
20W/LF door
14540
Total Allowed Tradable + Site Allowance Watts:
21155
Tradable Proposed Lighting Wattage NOTE 3
Tradable Surface
Fixture Description NOTE4, 5
Number of
Fixtures
VVdLLZS Pt:1Watts
Fixture NOTE 6
Proposed
Uncovered Parking and drives
pole mounted LED light
3
78
234
Grounds Walkways <10 wide
bollard light fixture
1
25
25
Grounds Walkways <10 wide
exterior wall sconce
15
14
210
Main Entry Door
exterior wall sconce
1 10
114
1140
Other Entry Door
exterior wall sconce
1 10
114
1140
Total proposed tradable watts may not exceed the sum of total allowed tradable watts Total Proposed Tradable Watts: 749
plus the base site allowance. Any base site allowance not needed to make tradable
watts comply can be applied to individual non -tradable categories.
Non -Tradable Maximum Allowed Lighting Wattage NOTE' Site Allowance Remaining:
500
Non -Tradable Surfaces
Surface Description
Area (ftZ), perimeter (If)
or # of items
Allowed Watts
per ftZ, If or item
Allowed Watts
x ftZ (or x If) Nore 2
Non -Tradable Proposed Lighting Wattage NOTE 3,7
Non -Tradable Surface
Fixture Description NOTE 4, 5
Number of
Fixtures
Watts per
Fixture NOTE 6
Watts
Proposed
Non -tradable proposed watts may not exceed allowed watts for any individual surface Non -Tradable Watts Exceeding LPA: 0
unless the total excess watts for all non -tradable surfaces are less than the remaining
site allowance. Remaining Site Allowance: 500
Exterior Lighting COMPLIES WITH MAX. ALLOWANCE
Note 1- List all exterior surfaces per Table C405.5.2(2) that occur in the project scope. Select exterior surface categories from drop down menu.
Note 2 - Unlit Message - Enter lighting fixture information for this surface in Proposed Lighting Wattage table to generate Lighting Power Allowance.
Note 3 - List all proposed lighting fixtures including existing -to -remain fixtures.
Note 4 - For proposed Fixture Description, indicate fixture type, lamp type, number of lamps in the fixture, and ballast type (if applicable).
Note 5 - Existing -to -remain fixtures shall be included in the Tradable and Non -Tradable Proposed Lighting Wattage tables in the same manner
as new fixtures. Identify as existing in fixture description.
Note 6 - For proposed Watts/Fixture enter the luminaire wattage for installed lamp and ballast using manufacturer or other approved source. For
luminaires with screw -in lamps, enter the manufacturer's listed maximum input wattage of the fixture (not the lamp wattage). For low
voltage lighting, enter the wattage of the transformer.
Note 7 - Automated Teller and Night Depositories - For each location, enter the number of ATM machines or depositories within that location. If
there are multiple locations in the project, enter each location individually in the Non -Tradable Maximum Allowed Lighting Wattage table
and identify the location in the Surface Description section.
Lighting, Motor,and Electrical Permit ' •
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised Nov 2017
Project Title: Edmonds Crossing Apartments
Date 7/26/19
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the Washington
State Energy Code, Commercial Provisions.
Applicability
Location in
Building Department
(yes,no,na)
Code Section
Component
Compliance information required in permit documents
Documents
Notes
LIGHTING CONTROLS
No
C405.2
Lighting controls,
For all lighting fixtures, indicate lighting control method on plans for
general
spaces and lighting zones served, or exception taken
Luminaire level
Indicate on plans all fixtures provided with LLLC in lieu of C405.2
NA
C405.2
lighting controls
lighting controls; provide description of control capabilities and
(LLLC)
performance parameters
Lighting in dwelling
For permanently installed lighting fixtures in dwelling units, indicate
No
C405.1
units
lighting control method on plans for spaces and lighting zone(s)
served, or demonstrate compliance with high efficacy exception
C405.2.3
C405.2.1.1
Indicate on plans the method of manual lighting control (whether
No
C405.2.2.2
Manual controls
combined with occupancy sensor, automatic light reduction,
C405.2.4
daylight responsive or specific application controls), location of
C405.2.5
manual control device and area or specific application it serves
C405.2.2.1
Manual interior light
Indicate on plans which method of manual 50% lighting load
NA
C405.2.2.2
reduction controls
reduction is provided, or whether lighting load is reduced via
C405.2.3
occupancy sensors or daylight responsive controls
Indicate on plans the method of automatic shut-off control during
unoccupied periods (occupancy sensor, time switch or digital timer
NA
C405.2.2
Method of automatic
switch) for all lighting zones;
Indicate locations where automatic shutoff is provided by other
shut-off control
methods (occupancy sensor or digital timer switch) or which time
switch control exception applies
Indicate on plans the spaces served by occupancy sensors;
Indicate whether occupancy sensor controls are configured to be
NA
C405.2.1
Occupancy sensor
C405.2.1.1
controls
manual -on, automatic 50%-on, or serve a space eligible for
automatic 100%-on per exception
NA
C405.2.1.2
Occupancy sensor
Indicate aisleways and open areas in warehouse spaces provided
controls - warehouses
with occupancy sensor controls that reduce lighting power by 50%
NA
C405.2.2.1
Automatic time switch
Indicate locations of override switches on plans and the lighting
controls
zones served, include areas . ft.
C405.2.6
Digital timer switch
Indicate digital timer switch control includes: manual on/off, time
delay, audible and visual indication of impending time-out
Indicate primary and secondary sidelight daylight zone areas on
plans, include sq. ft.;
C405.2.4.2
Daylight zones -
Indicate toplight daylight zone areas on plans, include sq. ft.;
For small vertical fenestration assemblies (rough opening less than
NA
C405.2.4.3
Sidelight and toplight
10 percent of primary daylight zone) where daylight responsive
controls are not required, provide fenestration area to daylight zone
calculation(s)
Indicate on plans lighting zone(s) served by daylight responsive
controls;
Identify sidelight and toplight daylight zones that are not provided
Daylight responsive
with daylight sensing controls and the exception(s) that apply;
Indicate on plans the lighting load reduction method - continuous
NA
C405.2.4
controls
dimming, or stepped dimming that provides at least two even steps
between 0%-100% of rated power;
Indicate that daylight sensing controls are configured to completely
shut off all controlled lights in the lighting zone
Additional controls
Identify spaces and lighting fixtures on plans that require specific
NA
C405.2.5
Specific application
application lighting controls per this section
lighting controls
Indicate on plans that display and accent lighting, and display case
NA
C405.2.5 -
Display and accent
lighting are controlled independently from both general area
Items 1&2
lighting
lighting and other lighting applications within the same space;
Indicate manual and automatic lighting control method
Lighting, Motor,and Electrical Permit ' •
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised Nov 2017
Project Title: Edmonds Crossing Apartments
Date 7126119
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the Washington
Applicability
Location in
Building Department
(yes,no,na)
Code Section
Component
Compliance information required in permit documents
Documents
Notes
C405.2.5 -
Hotel/motel guest
Indicate method of automatic control - vacancy or captive key
NA
Item 3
control of all installed luminaires and switched receptacles in guest
rooms
room
C405.2.5 -
Supplemental task
Indicate method and location of automatic shut-off vacancy control
NA
Item 4
lighting
for supplemental task lighting, including under -shelf or under -
cabinet lighting
Indicate on plans eligible non -visual lighting applications, include
sq. ft. area of each lighting control zone;
Indicate on plans that non -visual lighting are controlled
C405.2.5 -
Lighting for non -visual
NA
Item 5
applications
independently from both general area lighting and other lighting
applications within the same space;
Indicate method of manual lighting control and applicable
automatic lighting control
Indicate on plans that lighting equipment for sale or demonstration
C405.2.5 -
Lighting equipment for
are controlled independently from both general area lighting and
NA
Item 6
sale or demonstration
other lighting applications within the same space;
Indicate method of manual lighting control and applicable
automatic lighting control
Identify on plans egress fixtures that function as both normal and
emergency means of egress illumination;
Provide calculation of lighting power density of total egress lighting;
C405.2.5 -
Means of egress
Yes
Item 7
lighting
If total egress lighting power density is greater than 0.02 W/sq. ft.,
indicate on plans egress fixtures requiring automatic shut-off
during unoccupied periods;
Indicate method of automatic shut-off control
Indicate on exterior lighting plans and fixture schedules the
automatic lighting control method, control sequence, and locations
served;
For building facade and landscape lighting, indicate automatic
Exterior lighting
controls shut off lighting as a function of dawn/dusk and fixed
No
C405.2.7
controls
opening/closing time;
For all other exterior lighting, indicate automatic controls shut off
lighting as a function of available daylight; include control sequence
that also reduces lighting power by at least 30% between 12am-
6am, or from 1 hour after closing to 1 hour before opening, or
based upon motion sensor
Exterior building
For building grounds fixtures greater than 100 watts, indicate on
No
C405.5.1
grounds lighting
plans whether fixtures have efficacy greater than 80 lumens or; are
controls
controlled by motion sensor, or are exempt lighting per C405.5.2
Indicate location(s) of master control switch(es) intended to control
C405.2.5
Area controls - Master
multiple independent switches; circuit breaker may not be used as
NA
(listed after
control switches and
a master control switch;
C405.2.7)
circuit power limit
Verify that no 20 amp circuit controlled by a single switch or
automatic control is loaded beyond 80%
ADDITIONAL EFFICIENCY PACKAGE OPTION - ENHANCED DIGITAL LIGHTING CONTROLS
To comply with additional efficiency package option, indicate on
plans all interior lighting fixtures that are individually addressed and
NA
C406.4
Enhanced digital
provided with continuous dimming, or exception taken;
Include calculation of percent total installed interior lighting power
lighting controls
that is configured with required enhanced lighting control functions
(min 90% to comply with additional efficiency package option)
Lighting, Motor,and Electrical Permit ' •
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised Nov 2017
Project Title: Edmonds Crossing Apartments
Date 7126119
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the Washington
pp ica i dy
Location in
Building Department
(yes,no,na)
I Code Section
Component
Compliance information required in permit documents
Documents
Notes
INTERIOR LIGHTING
POWER & EFFICACY
Include all luminaires in lighting fixture schedule; indicate fixture
A70
types, lamps, ballasts, and manufacturer's rated watts per fixture;
Identify spaces eligible for lighting power exemption on plans and
in compliance forms; indicate the exception applied;
Yes
..
C40541
C405.4.2
Total connected
interior lighting power
Identify lighting equipment eligible for lighting power exemption in
fixture schedule and in compliance forms; indicate the exception
applied;
Indicate that exempt lighting equipment is in addition to general
area lighting and is controlled independent)
NA
C405.3
Exit signs
Indicate location of exit signs on plans and rated watts per fixture in
lighting fixture schedule (maximum 5 watts per side)
If high efficacy exception is applied to permanently installed lighting
Lighting in dwelling
fixtures in dwelling units, indicate in lighting fixture schedule if
NA
C405.1
units -lamp efficacy
lamps in fixtures are high efficacy per R404.1. Calculate
percentage of fixtures with high efficacy lamps in project (min 75%
to comply with exception).
Interior Li h ng Power Calculation - Indicate compliance path taken
Complete required compliance forms — proposed wattage per
Yes
C405.4.2.1
Building Area Method
building area does not exceed maximum allowed wattage per
LTG-INT-BLD
building area; identify locations of building areas on plans
Complete required compliance forms — total proposed wattage
NA
C405.4.2.2
Space -By -Space
does not exceed maximum allowed wattage; identify locations of
Method
space types on plans, including retail display areas, lobby art &
exhibit display areas, and ceiling heights as applicable
ADDITIONAL EFFICIENCY PACKAGE OPTION - REDUCED INTERIOR LIGHTING POWER
DENSITY
To comply with additional efficiency package option, demonstrate in
NA
C406.3
Reduced lighting
compliance forms that total connected interior lighting wattage is
power density
25% less than the total maximum allowed lighting wattage via
Building Area Method or Space -By -Space Method
Reduced lighting
For project with dwelling units, to comply with additional efficiency
power density -
package option indicate in lighting fixture schedule if lamps in
NA
C406.3
dwelling unit lamp
interior fixtures have efficacy rating of 60 lumens per watt or more.
efficacy
Calculate percentage of fixtures with lamps that have this efficacy
rating (min 95 /o to comply with option)
EXTERIOR LIGHTING POWER & EFFICACY
Include all luminaires in lighting fixture schedule; indicate fixture
A70
types, lamps, ballasts, and manufacturer's rated watts per fixture;
Identify exterior applications eligible for lighting power exemption
Total connected
Yes
C405.5.2
exterior lighting power
on plans and in compliance forms; indicate exception applied;
Indicate that exempt exterior lighting is controlled independently
from non-exempt exterior lighting; include exception claimed for
each fixture or group of fixtures under exception category
Yes
Table
C405.5.2 1
Exterior lighting zone
Indicate building exterior lighting zone as defined by the AHJ
A70
Exterior building
For building grounds fixtures rated at greater than 100 watts that
NA
C405.5.1
grounds lighting
are complying based on efficacy, indicate rated lamp efficacy (in
lumens per watt) in fixture schedule
Exterior lighting power
Complete required compliance form — proposed wattage for
Yes
C405.5.2
calculations
exterior lighting plus base site allowed does not exceed maximum
LTG-EXT
allowed
Lighting, Motor,and Electrical Permit ' •
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised Nov 2017
Edmonds Crossing Apartments
Date 7/26/19
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the Washington
pp ica i dy
Location in
Building Department
(yes,no,na)
Code Section
Component
Compliance information required in permit documents
Documents
Notes
LIGHTING ALTERATIONS
Where >_ 50% of existing luminaires in interior space(s) or parking
garage are replaced; indicate compliance path (building area or
space -by -space method); include all new and existing -to -remain
luminaires in compliance form (LTG-INT-BLD or LTG-INT-SPACE);
Interior and parking
indicate proposed lighting wattage does not exceed maximum
NA
C503.6
garage lighting fixture
allowed per compliance path
Where < 50% of existing luminaires in interior space(s) or parking
alterations
garage are replaced; indicate total existing lighting wattage in each
space prior to alteration; include all new and existing -to -remain
luminaires in LTG-INT-SPACE form; indicate proposed total lighting
wattage in alteration area does not exceed total existing lighting
wattage prior to alteration
Where >_ 50% of existing exterior lighting wattage is replaced;
include all new and existing -to -remain luminaires in LTG-EXT form;
indicate proposed total exterior lighting wattage does not exceed
NA
C503.6
Exterior lighting fixture
maximum allowed
alterations
Where < 50% of existing exterior lighting wattage is replaced;
indicate total existing lighting wattage prior to alteration; include all
new and existing -to -remain luminaires in LTG-EXT form; indicate
proposed total exterior lighting wattage does not exceed total
existing wattage prior to alteration
Where new wiring is installed to serve new interior luminaires and
Interior lighting wiring
/or luminaires are relocated to a new circuit; indicate lighting
NA
C503.6
alterations
controls are provided (as applicable) - manual (C405.2.3);
occupancy sensor (C405.2.1); daylight responsive (C405.2.4);
specific application (C405.2.5); exit signs (C405.3)
NA
C503.6
Exterior lighting wiring
Where new wiring is installed to serve new exterior luminaires and
/or luminaires to indicate lighting
alterations
are relocated new circuit; exterior
controls are provided (C405.2.7)
Where a new lighting panel is installed or an existing panel is
Lighting panel
moved (all new raceway and conductor wiring); indicate lighting
NA
C503.6
alterations
controls are provided (as applicable) - same provisions as wiring
alterations; time switch controls and manual light reduction controls
(C405.2.2)
Interior space
Where interior space(s) is reconfigured (permanently installed walls
NA
C503.6
reconfiguration
or ceiling -height partitions); indicate lighting controls are provided
(as applicable) - same provisions as lighting panel alterations
Identify existing luminaires being upgraded with bulb and / or
NA
C504.2
Lighting repairs
ballast replacement; indicate fixture alteration does not increase
existing fixture wattage
Identify spaces on plans where the building area type or space use
type is being changed from one type to another per Tables
C405.4.2(1) or (2)
Indicate compliance path (building area or space -by -space
NA
C505.1
Change of space use
method); include all new and existing -to -remain luminaires in
compliance form (LTG-INT-BLD or LTG-INT-SPACE); indicate
proposed lighting wattage does not exceed maximum allowed per
compliance path
RECEPTACLES
Identify all controlled and uncontrolled receptacles on electrical
plans in each space in which they are required; include receptacle
configuration such as spacing between controlled and uncontrolled,
No
C405.10
Controlled receptacles
duplex devices, etc;
Indicate on plans whether the method of automatic control for each
controlled receptacle zone is by occupant sensor or programmable
time -of -day control
Lighting, Motor,and Electrical Permit ' •
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised Nov 2017
Edmonds Crossing Apartments
Date 7126119
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the Washington
pp ica i dy
Location in
Building Department
(yes,no,na)
Code Section
Component
Compliance information required in permit documents
Documents
Notes
MOTORS, TRANSFORMERS, ELECTRIC METERS, INTERIOR TRANSPORTATION
No
C405.6
Electrical transformers
Include electrical transformer schedule on electrical plans; indicate
transformer size, efficiency, or exception taken
No
C405.7
Dwelling unit electrical
Indicate on electrical plans that each dwelling unit in Group R-2
energy consumption
has a separate electrical energy meter
Electric motor
Include all motors, including fractional hp motors, in electric motor
No
C405.8
efficiency
schedule on electrical plans; indicate hp, rpm, rated efficiency, or
exception applied
For luminaires in each elevator cab, provide calculated average
efficacy of combined fixtures that indicates efficacy is not less than
35 lumens per watt;
NA
C405.9.1
Elevator cabs
Indicate rated watts per cfm for elevator cab ventilation fans do not
exceed 0.33 watts per cfm;
Indicate automatic controls that de -energize lighting and ventilation
fans when elevator is stopped and unoccupied for a period of 15
minutes or more
Escalators and
Indicate escalators comply with ASME A17.1/CSA B44; automatic
NA
C405.9.2
moving walks
controls are configured to reduce operational speed to the
minimum permitted when not in use
NA
C405.9.3
Regenerative drive
Indicate all one-way down or reversible escalators are provided
with a variable frequency regenerative drive
DOCUMENTATION AND
SYSTEM REQUIREMENTS TO SUPPORT COMMISSIONING (Cx)
Indicate that all electrical systems (receptacles, transformers,
motors, vertical and horizontal transportation) for which the WSEC
requires control functions and / or configuration to perform specific
Scope of electrical
functions are required to be commissioned;
Where total building lighting load is > 20 kW, or where total lighting
NA
C408.3
power and lighting
systems
load of luminaires requiring daylight sensing and / or occupancy
commissioning
control > 10 kW, indicate that all automatic lighting control systems
are required to be commissioned; or provide building lighting power
calculation demonstrating eligibility for exception;
Indicate Cx requirements in plans and specifications for all
applicable electrical and lighting control systems per C408;
Include general summary with at minimum Items 1 thru 4 of the Cx
C405.13
Commissioning
plan per C408.1.2 including: narrative description of activities,
C408.1.1
requirements in
responsibilities of the Cx team, schedule of activities including
NA
C408.1.2
construction
verification of project close out documentation per C103.6, and
C408.1.4.2
documents
conflict of interest plan (if required);
Include in general summary that a Cx project report or Compliance
C103.6
Checklist (Figure C408.1.4.2) shall be completed by the Certified
Cx Professional and provided to the owner prior to the final
electrical inspection
Functional
Identify in plans and specifications the intended operation of all
NA
C408.3.1
performance testing
equipment and controls during all modes of operation, including
criteria
interfacing between new and existing -to -remain systems
PROJECT CLOSE OUT DOCUMENTATION
Project close out
Indicate in plans that project close out documentation is required
NA
C103.6.3
documentation
including WSEC lighting compliance forms and calculations that
requirements
document all interior and exterior lighting area and / or surface
types, lighting power allowances and installed densities
If "no" is selected for any question, provide explanation:
All controls for lighting will be shown on Electrical plans under separate permit application.
All motors, transformers and meters will be shown on Electrical plans.
End of Lighting, Motor & Transformer Permit Documents Checklist