APPROVED PLN BLD2023-0357+Manufacturer_Specifications_and_Installation_Instructions+3.23.2023_7.23.10_AM+3438318
0 TRANE0 Product Data Single Packaged Convertible Gas/Electric 14 SEER 2-5 Ton 4YCC4024A106OA 4YCC403OAl070A 4YCC4036A1070A 4YCC4036A109OA 4YCC4042A1060A 4YCC4042A1090A 4YCC4048A1070A 4YCC4048A1090A 4YCC406OAl090A 4YCC406OAl 1 15A ,June 2020 22-1901-1 J-EN 1 7� n N = T E C H N 0 L 0 G I ES' SAFETY SECTION Important — This document contains a wiring diagram, a parts list, and service information. This is customer property and is to remain with this unit. Please return to service information pack upon completion of work. HAZARDOUS GASES! Exposure to fuel substances or by-products of incomplete fuel combustion is believed by the state of California to cause cancer, birth defects, or other reproductive harm. This warning complies with state of California law, Proposition 65. HAZARDOUS VOLTAGE! Failure to follow this Warning could result in property damage, severe personal injury, or death. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. SAFETY AND ELECTRICAL HAZARD! Failure to follow this Warning could result in property damage, severe personal injury, or death. These servicing instructions are for use by qualified personnel only. To reduce the risk of electrical shock, do not perform any servicing other than that contained in these operating instructions unless you are qualified to do so. GROUNDING REQUIRED! Failure to inspect or use proper service tools may result in equipment damage or personal injury. Reconnect all grounding devices. All parts of this product that are capable of conducting electrical current are grounded. If grounding wires, screws, straps, clips, nuts, or washers used to complete a path to ground are removed for service, they must be returned to their original position and properly fastened. UNIT CONTAINS R-410A REFRIGERANT! Failure to use proper service tools may result in equipment damage or personal injury. R-410A operating pressure exceeds the limit of R-22. Proper service equipment is required. Service using only R-410A Refrigerant and approved POE compressor oil. SAFETY HAZARD! Operating the unit without the access panels properly installed may result in severe personal injury or death. Do not operate the unit without the evaporator fan access panel or evaporator coil access panel in place. ©2020 Trane 22-1901-1 J-EN 0 MAKE SAFETY SECTION 1Ti%1:l L1 I I L1 [H1 This product can expose you to chemicals including lead, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov. Important: Wear appropriate gloves, arm sleeve protectors and eye protection when servicing or maintaining this equipment. Important: Air filters and media wheels or plates shall meet the test requirements in UL 900. 22-1901-1J-EN 0 TIP4UIIE Table of Contents Single Packaged Convertible Gas/Electric Systems ............................ 5 Optional Equipment Listing .................................................... 6 Product Specifications......................................................... 8 Indoor Fan Performance...................................................... 13 Field Wiring Diagram......................................................... 20 Wiring— 4YCC4.............................................................. 21 Full Perimeter Roof Mounting Curb ........................................... 27 Optional Equipment — Economizer ........................................... 29 Optional Equipment — Outside Air Damper .................................. 30 Optional Equipment — Filter Rack ............................................ 31 OutlineDrawings............................................................. 32 4 22-1901-1J-EN 0 TRANE® Single Packaged Convertible Gas/Electric Systems Trane offers a complete family of packaged gas/electric heating and cooling systems, designed to provide the unbeatable combination of energy efficiency and lower operating costs. In warm weather, the package gas/electric system functions as an all -electric, high efficiency air conditioner. In cold weather, it operates as a natural gas or propane gas furnace, offering the best of both energy worlds. Because cooling and heating functions are all contained in a single cabinet, a single packaged convertible gas/electric system is easy to install and service. It can be flush mounted beside your home at ground level or placed on the roof for horizontal or downflow installation. When connected to an optional American Standard thermostat control, and air distribution ducts, you have a highly efficient, total home comfort system. Single Packaged Convertible Gas/Electric Systems are unmatched in quality and reliability. All major components on these products, including the compressor, have been designed and manufactured for maximum service. Every compressor is designed and manufactured to exacting specifications. Each design is life tested in extreme environments to ensure reliable and long lasting operation in normal applications. Each compressor has internal motor protection for added reliability. Single Packaged Convertible Gas/Electric Systems provide better performance. Our single packaged cooling/heating units offer cooling/heating efficiencies that are unmatched in the industry and provide you with a product far superior in performance than the competition. 22-1901-1J-EN 0 TRIUNE Optional Equipment Listing *=T,W,orY Hinged Filter Access Door (4*CC4024-036) (4*CY4024-4036) BAYCCDORIA [ ] Hinged Filter Access Door (4*CC4042-060) (4*CY4042-4060) BAYCCDOR2A [ ] Roof Curb Full Perimeter (4*CCO24-036A) (4*CY4024-4036) BAYCURB050A [ ] Roof Curb Full Perimeter (4*CC042-060A) (4*CY4042-4060) BAYCURB051A [ ] Roof Curb Utility Extension Kit (BAYCURB050A) BAYUTIL101B [ ] Roof Curb Utility Extension Kit (BAYCURB051A) BAYUTIL101B [ ] 0-25% Manual Fresh Air Damper (4*CC4024-36A) (4*CY4024-4036)(a) BAYOSAH001A [ ] 0-25% Manual Fresh Air Damper (4*CC4042-60A) (4*CY4042-4060)(a) BAYOSAH002A [ ] Motorized Fresh Air Damper (4*CC4024-036A) (4*CY4024-4036)(a) BAYDMPR101A [ ] Motorized Fresh Air Damper (4*CC4042-060A) (4*CY4042-4060)(a) BAYDMPRI02A [ ] 16" Round Duct Adapter (2 per box) (4*CC4024-036A) (4*CY4024-4036)(b) BAYSQRD001A [ ] 18" Round Duct Adapter (2 per box) (4*CC4024-060A) (4*CY4024-4036)(b) BAYSQRD002A [ ] 0-100%Mod Economizerw/Baro. Relief(4*CC4024-036A) (4*CY4024-4036)(a)(c)(d) BAYECON101B [ ] 0-100%Mod Economizerw/Baro. Relief(4*CC4042-060A) (4*CY4042-4060)(a)(d) BAYECON102B [ ] 0-100% Horizontal Economizer (4*CC4024-36A) (4*CY4024-4036)(a) BAYECON200B [ ] 0-100% Horizontal Economizer (4*CC4042-60A) (4*CY4042-4060)(a) BAYECON201B [ ] Enthalpy Control for Economizer (ALL-BAYECON) BAYEENTH001A [ ] Remote Potentiometer (ALL-BAYECON) BAYSTAT023 [ ] 1"-2" Filter Frame (4*CC4024-036A) (4*CY4024-4036) (18 x 25 filter not included) BAYFLTR101C [ ] 1"-2" Filter Frame (4*CC4042-060A) (4*CY4042-4060) (two 18 x 20 filters not included) BAYFLTR201C [ ] Head Pressure Control (Low Ambient Cool) (208/240v) Kit BAYLOAM105A [ ] Quick Start Kit (4WCC4-Al)(4TCC4-Al) BAYQSTK300A [ ] Quick Start Kit (4YCC4-Al) BAYQSTK301A [ ] Crankcase Heater Scroll (4*CC4024-036) (4*CY4024-4036) (230v) BAYCCHT103A [ ] Crankcase Heater Scroll (4*CC4042-060) (4*CY4042-4060) (230v) BAYCCHT102A [ ] Crankcase Heater Scroll (4*CC4024-036) (4*CY4024-4036) (230v) BAYCCHT301A [ ] Crankcase Heater Scroll (4*CC4042-060) (4*CY4042-4060) (230v) BAYCCHT302A [ ] Adapter Curb (4*CC4024-36A) (4*CY4024-4036A) to BAYCURB030,38 BAYADAP050A [ ] Adapter Curb (4*CC4024-36A) (4*CY4024-4036A) to BAYCURB033 BAYADAP051A [ ] Adapter Curb (4*CC4042-60A) (4*CY4042-4060A) to BAYCURB030,38 BAYADAP052A [ ] Adapter Curb (4*CC4042-60A) (4*CY4042-4060A) to BAYCURB033 BAYADAP053A [ ] Adapter Curb (4*CC4042-60A) (4*CY4042-4060A) to BAYCURB034 BAYADAP054A [ ] 12" Duct Shroud Covers Horizontal (4*CC4024-060A) (4*CY4024-4060A) BAYCOVR112A [ ] 18" Duct Shroud Covers Horizontal (4*CC4024-060A) (4*CY4042-4060A) BAYCOVR118A [ ] Extreme Condition Mounting Kit — All BAYCURB & BAYADAP BAYEXMKOOIA [ ] Extreme Condition Mounting Kit — All BAYUTIL BAYEXMK002B [ ] Extreme Condition Mounting Kit — All Slab Mounts BAYEXMK003B [ ] Lifting Lug Kit BAYLIFI-00213 [ ] LP Conversion Kit (All 115K Models) BAYLPKT100A [ ] LP Conversion Kit (All 60K and 90K Models) BAYLPKT101A [ ] LP Conversion Kit (All 70K Models) BAYLPKT102A [ ] SUPPLEMENTARY HEATERS (1 PHASE) * = T or W Only (Does not apply to Gas/Electric dual fuel models) 3.76/5.0 KW Heater (208/240V 1 PH) (4*CC4024-060A1) BAYHTRV105F [ ] 6.0/8.0 KW Heater (208/240V 1 PH) (4*CC4024-060A1) BAYHTRV108F [ ] 7.50/10.0 KW Heater (208/240V 1 PH) (4*CC4024-060A1) BAYHTRV110F [ ] 11.27/15.0 KW Heater (208/240V 1 PH) (4*CC4030-060A1) BAYHTRV115F [ ] 15.0/20.0 KW Heater (208/240V 1 PH) (4*CC4048-060A1) BAYHTRV120F [ ] 18.78/25.0 KW Heater (208/240V 1 PH) (4*CC40060A1) BAYHTRV125F [ ] 22-1901-1 J-EN aMWE Optional Equipment Listing SUPPLEMENTARY HEATERS (3 PHASE) * = T or W Only (Does not apply to Gas/Electric dual fuel models) 3.76/5.0 KW Heater (208/240V 3 PH) (4WCY4036-060A3) BAYHTRV305F [ ] 3.76/5.0 KW Heater (208/240V 3 PH) (4WCY4036-060A3) BAYHTRV308F [ ] 7.50/10.0 KW Heater (208/240V 3 PH) (4WCY4024-048A3) BAYHTRV310F [ ] 11.27/15.0 KW Heater (208/240V 3 PH) (4WCY4036-060A3) BAYHTRV315F [ ] 15.0/20.0 KW Heater (208/240V 3 PH) (4WCY4048-060A3) BAYHTRV320F [ ] 18.78/25.0 KW Heater (208/240V 3 PH) (4WCY4048-060A1) BAYHTRV325F [ ] Single Power Entry Kit (e) BAYSPEK060F [ ] Single Power Entry Kit (e) BAYSPEK061E [ ] Single Power Entry Kit (e) BAYSPEK062F [ ] Single Power Entry Kit (e) BAYSPEK063F [ ] Single Power Entry Kit (e) BAYSPEK064E [ ] Single Power Entry Kit (e) BAYSPEK065E [ ] (e) Must use internal filter frame when economizer or fresh air kit is used. (b) It is the responsibility of the installing dealer to properly size the ductwork for each specific application. W Dry bulb control standard with economizer. (d) Downflow only. (e) Must be selected per unit and heater model 22-1901-1J-EN 0 TRANS° Product Specifications MODEL 4YCC4024A1060A 4YCC4030A1070A 4YCC4036A1070A 4YCC4036A1090A RATED Volts/PH/Hz 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 Performance Cooling BTUH (a) 24600 28200 37000 37000 Indoor Airflow (CFM) 805 870 1190 1190 Power Input (KW) 1.99 2.39 3.08 3.08 EER/SEER (BTU/Watt-Hr.) 12.0 / 14.00 12.0 / 14.00 12.0 / 14.00 12.0 / 14.00 Sound Power Rating [dB(A)] (b) 66.6 70.0 69.3 69.3 PERFORMANCE HEATING(c) InputBTUH-1st Stage (Natural Gas) (d) 60000 70000 70000 90000 AFUE 81 81 81 81 Temp. Rise - Min/Max (IF) 30 / 60 30 / 60 30 / 60 35 / 65 Orifice Qty/Drill Sz. (Natural Gas) 2 / #37 2 / #33 2 / #33 3 / #37 POWER CONN. - V/Ph/Hz 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 Min. Brch. Cir. Ampacity (e) 19.1 22.6 24.5 24.5 Fuse Size - Max. (amps) 30 35 40 40 Fuse Size - Recmd. (amps) 30 35 40 40 COMPRESSOR SCROLL SCROLL SCROLL SCROLL VOLTS/PH/HZ 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 R.L. Amps - L.R.Amps 12.8/58.3 14.1/73.0 15.4/83.9 15.4/83.9 OUTDOOR COIL - TYPE SPINE -FIN SPINE -FIN SPINE -FIN SPINE -FIN Rows/F. P.I 2 / 24 2 / 24 2 / 24 2 / 24 Face Area (sq. ft.) 13.32 13.32 15.49 15.49 Tube Size (in.) 3/8 3/8 3/8 3/8 INDOORCOIL-TYPE MCHE MCHE MCHE MCHE Rows/F.P.I 2/16 2/16 2/16 2/16 Face Area (sq. ft.) 2.7 2.7 2.7 2.7 Tube Size Width (in.) .81 .81 1" 1" Refrigeration Control EXPANSION VALVE EXPANSION VALVE EXPANSION VALVE EXPANSION VALVE Drain Conn. Size (in.) 3/4 FEMALE NPT 3/4 FEMALE NPT 3/4 FEMALE NPT 3/4 FEMALE NPT OUTDOOR FAN - TYPE SWEPT SWEPT SWEPT SWEPT DIA. (IN.) 23.4 23.4 23.4 23.4 DRIVE/NO. SPEEDS DIRECT/ 1 DIRECT/ 1 DIRECT/ 1 DIRECT/ 1 CFM @ 0.0 in. w.g. M 2350 2800 3080 3080 Motor - HP/R.P.M 1/12 / 810 1/6/ 825 1 / 5 / 825 1 / 5 / 825 Volts/Ph/Hz 208-230/1/60 208-230/1/60 208-230 / 1 / 60 208-230 / 1 / 60 F.L. Amps/L.R Amps .54 / .82 .85 / 1.65 1.1 / 2.0 1.1 / 2.0 INDOOR FAN - TYPE CONSTANT TORQUE ECM CONSTANT TORQUE ECM CONSTANT TORQUE ECM CONSTANTTORQUE ECM Dia. x Width (in.) 10.62 X 10.62 10.62 X 10.62 10.62 X 10.62 10.62 X 10.62 Drive/No.Speeds DIRECT-3 DIRECT-3 DIRECT-3 DIRECT-3 CFM @ 0.0 in. w.g. (9) SEE FAN PERF TABLE SEE FAN PERF TABLE SEE FAN PERF TABLE SEE FAN PERF TABLE Motor - H P/R. P. M. 1/3 / 1050 1/2 / 1050 1/2 / 1050 1/2 / 1050 Volts/Ph/Hz 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 F.L. Amps 2.6 4.1 4.1 4.1 COMBUSTION FAN - TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL Drive/No. Speeds DIRECT/ 1 DIRECT/ 1 DIRECT/ 1 DIRECT/ 1 22-1901-1 J-EN a MWE' Product Specifications MODEL 4YCC4024A1060A 4YCC403OA1070A 4YCC4036A1070A 4YCC4036A1090A Motor - HP/R.P.M. 1/34 / 3350 1/34 / 3290 1/34 / 3290 1/34 / 3075 Volts/Ph/Hz 230/1/60 230/1/60 230/1/60 230/1/60 FLA .20 .20 .20 .24 FILTER / FURNISHED NO NO NO NO Type Recommended THROWAWAY THROWAWAY THROWAWAY THROWAWAY Recmd. Face Area (sq. ft) (h) 4.0 4.0 4.0 4.0 REFRIGERANT R-410 R 410 R-410 R-410 Charge (lbs.) 5.24 6.94 7.2 7.2 CHARGING SPECIFICATIONS Subcooling 121 11° 11° 110 GAS PIPE SIZE (in.) 1/2 1/2 1/2 1/2 DIMENSIONS HXDXW HXDXW HXDXW HXDXW Crated (in.) 46 X 45 X 52 46 X 45 X 52 48 X 45 X 52 48 X 45 X 52 WEIGHT Shipping (lbs.) / Net (lbs.) 432 / 358 451 / 377 438 / 374 453 / 379 (a) Rated in accordance with AHRI Standard 210/240. AHRI standard rating conditions are: 80 D.B.67 W.B. entering air to indoor coil. 95 D.B. entering air to outdoor coil. (b) Sound Power values are not adjusted for AHRI 270-95 tonal corrections. (0 Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a rate of 4% per 1000 ft. elevation. (d) Convertible to LPG. (e) This value is approximate. For more precise value, see Unit Nameplate. (f) Standard Air - Dry Coil - Outdoor. (g) Based on U.S. Government Standard Tests. (h) Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendation with a clean resistance of 0.05" W.C. MODEL 4YCC4042A1060A 4YCC4042A1090A 4YCC404BA1070A RATED Volts/PH/Hz 208-230/1/60 208-230/1/60 208-230/1/60 Performance Cooling BTUH (a) 40500 40500 46500 Indoor Airflow (CFM) 1450 1450 1600 Power Input (KW) 3.4 3.4 4.06 EER/SEER (BTU/Watt-Hr.) 12.0 / 14.00 12.0 / 14.00 11.50 / 14.00 Sound Power Rating [dB(A)] (b) 74.6 74.6 72.5 PERFORMANCE HEATING(c) Input BTUH-1st Stage (Natural Gas) (d) 60000 90000 70000 AFUE 81 81 81 Temp. Rise - Min/Max (IF) 30 / 60 35 / 65 30 / 60 Orifice Qty/Drill Sz. (Natural Gas) 2 / #37 3 / #37 2 / #33 POWER CONN. - V/Ph/Hz 208-230/1/60 208-230/1/60 208-230/1/60 Min. Brch. Cir. Ampacity (e) 28.5 28.5 32.0 Fuse Size - Max. (amps) 45 45 50 Fuse Size - Recmd. (amps) 45 45 50 COMPRESSOR SCROLL SCROLL SCROLL VOLTS/PH/HZ 208-230/1/60 208-230/1/60 208-230/1/60 R.L. Amps - L.R. Amps 16.7 / 109.0 16.7 / 109.0 19.6 / 130.0 OUTDOOR COIL - TYPE SPINE -FIN SPINE -FIN SPINE -FIN Rows/F. P.I 2 / 24 2 / 24 2 / 24 Face Area (sq. ft.) 15.63 15.63 20.54 Tube Size (in.) 3/8 3/8 3/8 INDOOR COIL - TYPE MCHE MCHE MCHE Rows/F. P.I 2 / 16 2 / 16 2 / 16 22-1901-1J-EN aMANE Product Specifications MODEL 4YCC4042A1060A 4YCC4042A1090A 4YCC404BA1070A Face Area (sq. ft.) 3.9 3.9 3.9 Tube Size Width (in.) .81 .81 .81 Refrigeration Control EXPANSION VALVE EXPANSION VALVE EXPANSION VALVE Drain Conn. Size (in.) 3/4 FEMALE NPT 3/4 FEMALE NPT 3/4 FEMALE NPT OUTDOOR FAN - TYPE SWEPT SWEPT SWEPT DIA. (IN.) 28.25 28.25 28.25 DRIVE/NO. SPEEDS DIRECT/ 1 DIRECT/ 1 DIRECT/ 1 CFM @ 0.0 in. w.g. M 3400 3400 4800 Motor - H P/R. P. M 1/4 / 825 1/4 / 825 1/4 / 825 Volts/Ph/Hz 208-230/1/60 208-230/1/60 208-230 / 1 / 60 F.L. Amps/L.R Amps 1.51 / 3.07 1.51 / 3.07 1.51 / 3.07 INDOOR FAN - TYPE CONSTANTTORQUE ECM CONSTANTTORQUE ECM CONSTANTTORQUE ECM Dia. x Width (in.) 10.62 X 10.62 10.62 X 10.62 10.62 X 10.62 Drive/No. Speeds DIRECT/ 3 DIRECT/ 3 DIRECT/ 3 CFM @ 0.0 in. w.g. (9) SEE FAN PERF TABLE SEE FAN PERF TABLE SEE FAN PERF TABLE Motor - HP/R.P.M. 3/4 / 1050 3/4 / 1050 3/4 / 1050 Volts/Ph/Hz 208-230/1/60 208-230/1/60 208-230/1/60 F.L. Amps 6 6 6 COMBUSTION FAN - TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL Drive/No. Speeds DIRECT/ 1 DIRECT/ 1 DIRECT/ 1 Motor - HP/R.P.M. 1/34 / 3345 1/34 / 3075 1/34 / 3290 Volts/Ph/Hz 230/1/60 230/1/60 230/1/60 FLA .20 .24 .20 FILTER / FURNISHED NO NO NO Type Recommended THROWAWAY THROWAWAY THROWAWAY Recmd. Face Area (sq. ft) (h) 5.3 5.3 5.3 REF RIG E RANT R-410 R-410 R-410 Charge (lbs.) 7.3 7.3 7.5 CHARGING SPECIFICATIONS Subcooling 10° 10° 100 GAS PIPE SIZE (in.) 1/2 1/2 1/2 DIMENSIONS HXDXW HXDXW HXDXW Crated (in.) 46 X 47 X 62 46 X 47 X 62 50 X 47 X 62 WEIGHT Shipping (lbs.) / Net (lbs.) 555/ 452 561 / 457 552 / 448 cal Rated in accordance with AHRI Standard 210/240. AHRI standard rating conditions are: 80 D.B.67 W.B. entering air to indoor coil. 95 D.B. entering air to outdoor coil. (b) Sound Power values are not adjusted for AHRI 270-95 tonal corrections. (c) Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a rate of 4% per 1000 ft. elevation. (d) Convertible to LPG. (e) This value is approximate. For more precise value, see Unit Nameplate. (f) Standard Air - Dry Coil - Outdoor. (g) Based on U.S. Government Standard Tests. (h) Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendation with a clean resistance of 0.05" W.C. MODEL 4YCC4048A1090A 4YCC4060A1090A 4YCC4060A1115A RATED Volts/PH/Hz 208-230/1/60 208-230/1/60 208-230/1/60 Performance Cooling BTUH (a) 46500 58000 58000 Indoor Airflow (CFM) 1600 1760 1760 Power Input (KW) 4.09 4.94 4.94 10 22-1901-1 J-EN aMWE Product Specifications MODEL 4YCC4048A1090A 4YCC4060A1090A 4YCC4060A1115A EER/SEER (BTU/Watt-Hr.) 11.50 / 14.00 11.50 / 14.00 11.50 / 14.00 Sound Power Rating [dB(A)] (b) 72.5 73.1 73.1 PERFORMANCE HEATING(c) Input BTUH-1st Stage (Natural Gas) (d) 90000 90000 115000 AFUE 81 81 81 Temp. Rise - Min/Max (OF) 35 / 65 30 / 60 30/ 60 Orifice Qty/Drill Sz. (Natural Gas) 3 / #37 3 / #37 3 / #33 POWER CONN. - V/Ph/Hz 208-230/1/60 208-230/1/60 208-230/1/60 Min. Brch. Cir. Ampacity (e) 32.0 39.1 39.1 Fuse Size - Max. (amps) 50 60 60 Fuse Size - Recmd. (amps) 50 60 60 COMPRESSOR SCROLL SCROLL SCROLL VOLTS/PH/HZ 208-230/1/60 208-230/1/60 208-230/1/60 R.L. Amps - L.R. Amps 19.6 / 130.0 24.4 / 144.2 24.4 / 144.2 OUTDOOR COIL - TYPE SPINE -FIN SPINE -FIN SPINE -FIN Rows/F. P.I 2/24 2/24 2/24 Face Area (sq. ft.) 20.54 22.99 22.99 Tube Size (in.) 3/8 3/8 3/8 INDOOR COIL - TYPE MCHE PLATE FIN PLATE FIN Rows/F. P.I 2 / 16 4/ 15 4 / 15 Face Area (sq. ft.) 3.9 5.0 5.0 Tube Size Width (in.) .81 3/8 3/8 Refrigeration Control EXPANSION VALVE EXPANSION VALVE EXPANSION VALVE Drain Conn. Size (in.) 3/4 FEMALE NPT 3/4 FEMALE NPT 3/4 FEMALE NPT OUTDOOR FAN - TYPE SWEPT SWEPT SWEPT DIA. (IN.) 28.25 28.25 28.25 DRIVE/NO. SPEEDS DIRECT/ 1 DIRECT/ 1 DIRECT/ 1 CFM @ 0.0 in. w.g. M 4800 4800 4800 Motor - HP/R.P.M 1/4 / 825 1/3/ 825 1/3/ 825 Volts/Ph/Hz 208-230 / 1/60 208-230/1/60 208-230 / 1/60 F.L. Amps/L.R Amps 1.51 / 3.07 1.7 / 3.5 1.7 / 3.5 INDOOR FAN - TYPE CONSTANTTORQUE ECM CONSTANTTORQUE ECM CONSTANTTORQUE ECM Dia. x Width (in.) 10.62 X 10.62 11.87 X 10.68 11.87 X 10.68 Drive/No. Speeds DIRECT/ 3 DIRECT/ 3 DIRECT/ 3 CFM @ 0.0 in. w.g. (9) SEE FAN PERF TABLE SEE FAN PERF TABLE SEE FAN PERF TABLE Motor - HP/R.P.M. 3/4 / 1050 1 / 1050 1 / 1050 Volts/Ph/Hz 208-230/1/60 208-230/1/60 208-230/1/60 F.L. Amps 6 6.9 6.9 COMBUSTION FAN - TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL Drive/No. Speeds DIRECT/ 1 DIRECT/ 1 DIRECT/ 1 Motor - HP/R.P.M. 1/34 / 3075 1/34 / 3075 1/34 / 3055 Volts/Ph/Hz 230/1/60 230/1/60 230/1/60 FLA .24 .24 .25 FILTER / FURNISHED NO NO NO Type Recommended THROWAWAY THROWAWAY THROWAWAY Recmd. Face Area (sq. ft) (h) 5.3 5.3 5.3 REFRIGERANT R-410 R-410 22-1901-1J-EN aMANE Product Specifications MODEL 4YCC404BA1090A 4YCC4060A1090A 4YCC4060A1115A Charge (lbs.) 7.5 9.65 9.65 CHARGING SPECIFICATIONS Subcooling 100 110 110 GAS PIPE SIZE (in.) 1/2 1/2 1/2 DIMENSIONS HXDXW HXDXW HXDXW Crated (in.) 50 X 47 X 62 50 X 47 X 62 50 X 47 X 62 WEIGHT Shipping (lbs.) / Net (lbs.) 557 / 453 580 / 476 586 / 482 (a) Rated in accordance with AHRI Standard 210/240. AHRI standard rating conditions are: 80 D.B.67 W.B. entering air to indoor coil. 95 D.B. entering air to outdoor coil. (b) Sound Power values are not adjusted for AHRI 270-95 tonal corrections. (c) Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a rate of 4% per 1000 ft. elevation. (d) Convertible to LPG. (e) This value is approximate. For more precise value, see Unit Nameplate. M Standard Air — Dry Coil — Outdoor. (e) Based on U.S. Government Standard Tests. (h) Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendation with a clean resistance of 0.05" W.C. 12 22-1901-1 J-EN Indoor Fan Performance Table 1. Horizontal Airflow 4YCC4024A1060A EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED Number 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 CONSTANT CIRCULATION I CFM APPROXIMATELY 40 - 50 % COOLING OR HEATING AIRFLOW WATTS COOLING -LOW 2 CFM 954 900 846 794 729 650 588 535 488 - - WATTS 107 114 121 128 138 147 152 157 161 COOLING -HIGH 3 CFM 1041 993 938 890 836 777 707 644 594 WATTS 135 142 150 158 167 175 185 191 196 HEAT -LOW 4 CFM 1123 1059 994 943 889 - - - - WATTS 143 152 160 167 175 - - - - - - HEAT -HIGH 5 CFM - - 1122 1069 1022 974 922 871 809 WATTS - - 213 1 221 1 229 1 238 1 245 253 261 - - Table 2. Down Airflow 4YCC4024AI060A EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED Number 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 CONSTANT CIRCULATION 1 CFM APPROXIMATELY 40 - 50 % COOLING OR HEATING AIRFLOW WATTS COOLING -LOW 2 CFM 945 891 838 786 722 643 582 530 483 - - WATTS 108 115 122 129 138 148 153 158 162 - - COOLING -HIGH 3 CFM 1031 983 929 881 828 769 700 637 588 - - WATTS 136 143 151 159 167 176 186 192 197 - - HEAT -LOW 4 CFM 1123 1059 994 943 889 - - - - - - WATTS 143 152 160 167 175 - - - - - - HEAT -HIGH 5 CFM 1240 1184 1122 1069 1022 974 922 871 - - - WATTS 193 202 213 221 229 238 245 253 - - - Table 3. Horizontal Airflow 4YCC4030AI070A EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED Number 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 CONSTANT CIRCULATION I CFM APPROXIMATELY 40 - 50 % COOLING OR HEATING AIRFLOW WATTS COOLING -LOW 2 CFM 1051 994 939 889 840 775 708 642 582 - - WATTS 126 134 142 150 158 167 176 184 188 - - COOLING -HIGH 3 CFM 1278 1236 1187 1141 1099 1059 1017 968 - WATTS 221 230 240 250 259 268 278 289 - - - HEAT -LOW 4 CFM 1148 1103 1061 1022 982 932 - - - - - WATTS 199 208 216 224 233 243 - - - - - HEAT -HIGH 5 CFM - - - 1158 1122 1084 1039 988 - WATTS - - - 301 310 320 331 343 - - - Table 4. Down Airflow 4YCC4030A1070A EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED Tap 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 Number CONSTANT CFM 1 APPROXIMATELY 40 50 %COOLING OR HEATING AIRFLOW WATTS CIRCULATION 22-1901-1J-EN aTRANS° Indoor Fan Performance Table 4. Down Airflow (continued) COOLING -LOW 2 CFM 1041 984 930 880 831 768 701 635 576 WATTS 126 135 143 150 158 168 177 184 189 — — COOLING -HIGH 3 CFM 1266 1224 1175 1129 1088 1048 1007 959 — — — WATTS 222 231 241 251 260 270 279 290 — — — HEAT -LOW 4 CFM 1136 1091 1050 1012 972 922 — — — WATTS 197 205 214 222 230 241 — — — — — HEAT -HIGH 5 CFM — — — 1147 1111 1073 1028 978 — — — WATTS — — — 298 307 317 328 339 — — — Table 5. Horizontal Airflow 4YCC4036A1070A EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED Number 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 CONSTANT CIRCULATION 1 CFM APPROXIMATELY 40 - 50 % COOLING OR HEATING AIRFLOW WATTS CFM 1256 1223 1193 1167 1136 1101 1065 1026 955 — — COOLING -LOW 2 WATTS 339 350 358 366 374 383 391 399 386 CFM 1402 1372 1344 1316 1289 1241 1144 1025 — — — COOLING -HIGH 3 WATTS 471 479 488 497 506 499 454 406 — — — CFM 1185 1141 1099 1055 1009 968 920 854 808 731 624 HEAT -LOW 4 WATTS 241 251 260 270 279 289 299 311 320 306 284 CFM 1386 1354 1311 1276 1238 1198 1164 1069 805 689 596 HEAT -HIGH 5 WATTS 386 399 409 419 430 441 452 432 320 303 298 4YCC4036A1090A EXTERNAL STATIC PRESSURE (IN. WG) CONSTANT CIRCULATION 1 CFM APPROXIMATELY 40 - 50 % COOLING OR HEATING AIRFLOW WATTS CFM 1288 1254 1225 1193 1158 1117 1070 956 806 639 — COOLING -LOW 2 WATTS 340 348 357 366 375 385 395 365 320 273 — CFM 1358 1326 1300 1271 1241 1201 1107 933 739 643 — COOLING -HIGH 3 WATTS 402 410 419 427 437 447 423 361 293 271 — CFM 1292 1259 1230 1199 1163 1124 1071 963 799 638 — HEAT -LOW 4 WATTS 343 351 360 369 378 388 398 370 316 293 — CFM 1367 1341 1310 1282 1250 1212 1075 928 781 631 — HEAT -HIGH 5 WATTS 1 404 413 421 431 439 448 404 346 302 282 — Table 6. Down Airflow 4YCC4036A1070A EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 Number CONSTANT CFM 1 APPROXIMATELY 40 50 % COOLING OR HEATING AIRFLOW WATTS CIRCULATION 14 22-1901-1 J-EN aMWE Indoor Fan Performance Table 6. Down Airflow (continued) COOLING -LOW 2 CFM 1249 1216 1185 1155 1122 1089 1054 1016 934 WATTS 343 351 359 367 376 384 392 400 379 — — COOLING -HIGH 3 CFM 1390 1357 1329 1301 1273 1212 1125 1008 — WATTS 476 485 493 501 508 488 449 398 — — — HEAT -LOW 4 CFM 1173 1130 1088 1044 999 958 911 846 800 724 618 WATTS 238 248 258 267 277 286 296 308 316 303 282 HEAT -HIGH 5 CFM 1373 1340 1298 1263 1225 1186 1153 1058 797 682 590 WATTS 382 395 405 415 425 437 448 428 317 300 295 4YCC4036A1090A EXTERNAL STATIC PRESSURE (IN. WG) CONSTANT CIRCULATION 1 CFM APPROXIMATELY 40 - 50 % COOLING OR HEATING AIRFLOW WATTS COOLING -LOW 2 CFM — 1238 1207 1176 1143 1091 1036 928 770 — — WATTS — 348 357 366 375 385 395 365 320 — — COOLING -HIGH 3 CFM 1350 1320 1294 1263 1234 1196 1102 928 735 WATTS 402 410 419 427 437 447 423 361 293 HEAT -LOW 4 CFM 1285 1252 1222 1186 1148 1111 1060 954 781 — — WATTS 343 351 360 369 378 388 398 370 316 — — HEAT -HIGH 5 CFM 1355 1326 1295 1267 1235 1183 1056 913 — — — WATTS 404 413 421 431 439 448 404 346 — — — Table 7. Horizontal Airflow 4YCC4042A1060A EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 Number CONSTANT CFM 1 APPROXIMATELY 40 50 % COOLING OR HEATING AIRFLOW WATTS CIRCULATION CFM 1358 1393 1348 1296 1253 1204 1157 1096 1057 988 — COOLING -LOW 2 WATTS 224 233 242 252 262 272 283 295 305 319 — CFM 1521 1490 1448 1391 1362 1338 1315 1307 1254 1148 — COOLING -HIGH 3 WATTS 306 316 327 337 348 359 369 382 395 407 — CFM 1104 1042 977 911 841 764 687 598 — — — HEAT -LOW 4 WATTS 109 116 124 134 142 152 161 171 — CFM — 1171 1112 1050 990 927 851 779 704 — — HEAT -HIGH 5 WATTS — 154 162 172 182 192 203 214 225 — — 4YCC4042A1090A EXTERNAL STATIC PRESSURE (IN. WG) CONSTANT CFM 1 APPROXIMATELY 40 50 % COOLING OR HEATING AIRFLOW WATTS CIRCULATION CFM 1358 1393 1348 1296 1253 1204 1157 1096 1057 988 — COOLING -LOW 2 WATTS 224 233 242 252 262 272 283 295 305 319 — CFM 1521 1490 1448 1391 1362 1338 1315 1307 1254 1148 — COOLING -HIGH 3 WATTS 1 306 316 327 337 348 359 369 382 395 407 — 22-1901-1J-EN aTRANS° Indoor Fan Performance Table 7. Horizontal Airflow (continued) HEAT -LOW 4 CFM 1419 1380 1341 1295 1249 1204 1160 1115 1069 1015 961 WATTS 240 250 259 269 279 291 302 312 323 333 348 HEAT -HIGH 5 CFM 1559 1524 1483 1443 1401 1363 1319 1276 1233 1195 1147 WATTS 313 324 335 346 356 367 379 392 403 415 428 Table 8. Down Airflow 4YCC4042A1060A EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED Number 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 CONSTANT CIRCULATION 1 CFM APPROXIMATELY40 50%COOLING OR HEATING AIRFLOW WATTS CFM 1345 1379 1334 1283 1241 1192 1145 1085 1046 979 — COOLING -LOW 2 WATTS 228 238 247 257 267 278 289 301 312 325 — CFM 1506 1475 1433 1377 1348 1325 1302 1293 1241 1136 — COOLING -HIGH 3 WATTS 312 322 333 344 354 366 377 389 403 415 — CFM 1109 1047 982 916 845 767 690 601 — — — HEAT -LOW 4 WATTS 109 117 125 134 143 153 162 172 — — — CFM — 1177 1117 1055 995 931 856 783 707 — — HEAT -HIGH 5 WATTS — 155 163 173 1 182 1 193 204 215 226 — — 4YCC4042A1090A EXTERNAL STATIC PRESSURE (IN. WG) CONSTANT CIRCULATION 1 CFM APPROXIMATELY 40 50 % COOLING OR HEATING AIRFLOW WATTS CFM 1345 1379 1334 1283 1241 1192 1145 1085 1046 979 — COOLING -LOW 2 WATTS 228 238 247 257 267 278 289 301 312 325 — CFM 1506 1475 1433 1377 1348 1325 1302 1293 1241 1136 — COOLING -HIGH 3 WATTS 312 322 333 344 354 366 377 389 403 415 — CFM 1426 1387 1348 1301 1255 1210 1166 1120 1074 1020 966 HEAT -LOW 4 WATTS 241 251 260 270 281 292 303 314 325 335 349 CFM 1567 1531 1491 1450 1408 1370 1326 1282 1239 1201 1152 HEAT -HIGH 5 WATTS 315 325 337 347 358 368 381 394 405 417 430 Table 9. Horizontal Airflow 4YCC4048A1070A EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 Number CONSTANT CFM CIRCULATION 1 APPROXIMATELY 40 50 % COOLING OR HEATING AIRFLOW WATTS CFM 1583 1542 1502 1460 1415 1371 1326 1282 1230 1181 — COOLING -LOW 2 WATTS 302 313 324 332 345 353 368 376 394 406 — CFM 1763 1723 1689 1648 1609 1568 1527 1488 1447 1404 — COOLING -HIGH 3 WATTS 414 426 436 448 459 471 483 495 510 524 — 16 22-1901-1 J-EN aMWE Indoor Fan Performance Table 9. Horizontal Airflow (continued) HEAT -LOW 4 CFM 1120 1047 980 914 840 758 674 581 — WATTS 117 126 135 145 156 168 179 188 — — — HEAT -HIGH 5 CFM — 1204 1149 1095 1043 989 926 858 798 — — WATTS — 176 185 195 205 216 227 239 249 — — 4YCC4048A1090A EXTERNAL STATIC PRESSURE (IN. WG) CONSTANT CIRCULATION 1 CFM APPROXIMATELY 40 - 50 % COOLING OR HEATING AIRFLOW WATTS COOLING -LOW 2 CFM 1583 1542 1502 1460 1415 1371 1326 1282 1230 1181 — WATTS 302 313 324 332 345 353 368 376 394 406 — COOLING -HIGH 3 CFM 1763 1723 1689 1648 1609 1568 1527 1488 1447 1404 — WATTS 414 426 436 448 459 471 483 495 510 524 — HEAT -LOW 4 CFM 1419 1380 1341 1295 1249 1 1204 1160 1115 1069 1015 1 961 WATTS 240 250 259 269 279 291 302 312 323 333 348 HEAT -HIGH 5 CFM 1559 1524 1483 1443 1401 1363 1319 1276 1233 1195 1147 WATTS 313 324 335 346 356 367 379 392 403 415 428 Table 10. Down Airflow 4YCC4048A1070A EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED Number 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 CONSTANT CIRCULATION 1 CFM APPROXIMATELY 40 50 % COOLING OR HEATING AIRFLOW WATTS CFM 1567 1526 1487 1445 1401 1358 1312 1270 1218 1169 — COOLING -LOW 2 WATTS 308 320 330 339 352 360 375 384 402 413.9 — CFM 1745 1706 1672 1632 1593 1552 1512 1473 1433 1390 — COOLING -HIGH 3 WATTS 422 434 444 457 468 480 493 505 520 534 — CFM 1126 1052 985 918 845 762 677 584 — — — HEAT -LOW 4 WATTS 117 127 136 146 156 168 180 189 — — CFM — 1210 1154 1100 1048 994 930 862 802 — — HEAT -HIGH 5 WATTS — 177 186 196 206 217 228 240 250 — — 4YCC4048A1090A EXTERNAL STATIC PRESSURE (IN. WG) CONSTANT CIRCULATION 1 CFM APPROXIMATELY 40 50 % COOLING OR HEATING AIRFLOW WATTS CFM 1567 1526 1487 1445 1401 1358 1312 1270 1218 1169 — COOLING -LOW 2 WATTS 308 320 330 339 352 360 375 384 402 413.9 — CFM 1745 1706 1672 1632 1593 1552 1512 1473 1433 1390 — COOLING -HIGH 3 WATTS 422 434 444 457 468 480 493 505 520 534 — CFM 1426 1387 1348 1301 1255 1210 1166 1120 1074 1020 966 HEAT -LOW 4 WATTS 241 251 260 270 281 292 303 314 325 335 349 CFM 1567 1531 1491 1450 1408 1370 1326 1282 1239 1201 1152 HEAT -HIGH 5 WATTS 315 325 337 347 358 368 381 394 405 417 430 22-1901-1J-EN aTRANS° Indoor Fan Performance Table 11. Horizontal Airflow 4YCC4060A1090A EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED Number 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 CONSTANT CIRCULATION 1 CFM APPROXIMATELY 40 50 % COOLING OR HEATING AIRFLOW WATTS CFM 1857 1831 1800 1766 1737 1692 1655 1617 — — — COOLING -LOW 2 WATTS 515 523 533 544 554 569 582 595 — — — CFM 2083 2058 2032 2003 1974 1943 1911 1877 1843 1807 — COOLING -HIGH 3 WATTS 749 759 769 779 788 803 816 830 845 860 — CFM 1534 1489 1445 1403 1361 1314 1275 1234 — — — HEAT -LOW 4 WATTS 281 292 304 314 325 337 348 358 — CFM — 1594 1551 1511 1471 1430 1386 1344 1305 1265 — HEAT -HIGH 5 WATTS — 348 361 373 384 396 409 420 432 443 — 4YCC4060A1115A EXTERNAL STATIC PRESSURE (IN. WG) CONSTANT CIRCULATION 1 CFM APPROXIMATELY 40 50 % COOLING OR HEATING AIRFLOW WATTS CFM 1857 1831 1800 1766 1737 1692 1655 1617 — — — COOLING -LOW 2 WATTS 515 523 533 544 554 569 582 595 — — — CFM 2083 2058 2032 2003 1974 1943 1911 1877 1843 1807 — COOLING -HIGH 3 WATTS 749 759 769 779 788 803 816 830 845 860 — CFM 1827 1792 1757 1721 1685 1646 1605 1570 — — — HEAT -LOW 4 WATTS 492 505 517 529 541 553 566 577 — — — CFM — 1927 1894 1861 1824 1788 1750 1711 1674 1639 — HEAT -HIGH 5 WATTS — 614 627 639 651 664 677 689 702 715 Table 12. Down Airflow 4YCC4060A1090A EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED Number 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 CONSTANT CFM CIRCULATION 1 APPROXIMATELY 40 - 50 % COOLING OR HEATING AIRFLOW WATTS CFM 1857 1831 1800 1766 1737 1692 1655 1617 — — — COOLING -LOW 2 WATTS 515 523 533 544 554 569 582 595 — — — CFM 2083 2058 2032 2003 1974 1943 1911 1877 1843 1807 — COOLING -HIGH 3 WATTS 749 759 769 779 788 803 816 830 845 860 — CFM 1541 1497 1452 1410 1367 1321 1281 1240 — — — HEAT -LOW 4 WATTS 282 293 305 316 327 339 349 360 — — — CFM — 1602 1558 1518 1478 1437 1392 1351 1311 1271 — HEAT -HIGH 5 WATTS — 350 363 374 386 398 411 423 434 445 — 4YCC4060A1115A EXTERNAL STATIC PRESSURE (IN. WG) CONSTANT CIRCULATION 1 APPROXIMATELY 40 - 50 % COOLING OR HEATING AIRFLOW WATTS 18 22-1901-1 J-EN 0 MAKE Indoor Fan Performance Table 12. Down Airflow (continued) COOLING -LOW 2 CFM 1857 1831 1800 1766 1737 1692 1655 1617 WATTS 515 523 533 544 554 569 582 595 - - - COOLING -HIGH 3 CFM 2083 2058 2032 2003 1974 1943 1911 1877 1843 1807 - WATTS 749 759 769 779 788 803 816 830 845 860 - HEAT -LOW 4 CFM 1815 1790 1757 1712 1679 1648 1613 1574 - - - WATTS 510 520 532 549 560 570 582 596 HEAT -HIGH 5 CFM - 1910 1875 1839 1803 1773 1736 1704 1661 1622 - WATTS - 630 634 647 660 672 685 698 712 726 - 22-1901-1J-EN 0 TRIUNE Field Wiring Diagram GROUND WIRE Figure 1. 4YCC4 — Field Wiring Diagram PACKAGED GAS —ELECTRIC UNIT TUNIT CONTROL BOX TWO STAGE HEAT I THERMOSTAT CONNECTIONS I I I I I ! — — — — — — — — 36(BL) B COMMON 47A(BK) G FAN 44A(YL) Y COMPRESSOR - - --41A(BR) W1 HEAT FIRST STAGE - - 41C(BR) W2 HEAT SECOND STAGE --35A(RD) R 24V UNIT LOW VOLTAGE AREA - 1 PH B G Y W1 W R POWER J TYPICAL 2 STAGE Y HEAT THERMOSTAT 3 PH POWER UNIT NOTE 1 _J SINGLE STAGE ECONOMIZER ACCESSORY THERMOSTAT CONNECTIONS CONNECTIONS FT. ECONOMIZER AR PROVIDED IELDINSTALLED F WIRES � / 1 I I I I - --36(BL) B COMMON I L 36EIBL1� - - - - - - - - - - - 368(BL) B ---47A(13K) G FAN IGR) - r (CONSTANT CIRCUTATION) L - - ----44A(YL) Y CONTACTOR/COMPRESSOR/FANL-___I47A(BKI G --41AfBR1 Wl IHFAT FIRSTSTAGEIWHI I`--41C(BR) W2 xFATSECONDSTAGE (WN)L-----(PR) 44AIYL1 Y --35A(RD) R 20 I 41A UNIT LOW VOLTAGE AREA - - 35A(RDI R1 UNIT LOWL 41CI BR 1 W2 VOLTAGE AREA B I G I Y I W 1 I R TYPICAL 1 STAGE HEAT THERMOSTAT NOTE 6 I I I II Notes: 1. FUSED DISCONNECT SIZE, POWER WIRING AND GROUNDING OF EQUIPMENT MUST COMPLY WITH CODES. 2. BE SURE POWER SUPPLY AGREES WITH EQUIPMENT AND HEATER NAMEPLATE. 3. LOW VOLTAGE WIRING TO BE 18AWG MINIMUM CONDUCTOR. 4. SEE UNIT DIAGRAM FOR ELECTRICAL CONNECTION DETAILS. A 5. THE GAS ELECTRIC UNIT WILL PROVIDE CONSTANT CIRCULATION REGARDLESS OF COOLING OR HEATING STATUS WITH A'G' SIGNAL ONLY FROM THE THERMOSTAT. 6. FOR SINGLE STAGE THERMOSTATS, JUMPER W1 AND W2 TOGETHER. SECOND STAGE HEAT WILL BEGIN 10 MINUTES AFTER FIRST STAGE. FIELD INSTALLED JUMPER TYPICAL 2-STAGE THERMOSTAT DWG. C757192REVA INTER -COMPONENT WIRING - - - - - - - 24V. FACTORY - - - - - - - LINE V. WIRING 24V. J I FELD LINE V. WRING WIRE COLOR DESIGNATION ABBR COLOR BK PURPLE EL RED BR AUER WHITE GR YELLOW OR 20 22-1901-1 J-EN 0 TRIUNE Wiring — 4YCC4 LPCO YELLOW Y ELLOWK HPCO BLAC BLACK Figure 2. 4YCC4024-042 o M 7A(PRI CFI CR 9A(BR) F H ORANGE a m m ta: IDM 36E(BL) Y � m � C — �EATNEp xF CFRT BLACK TELL PS C TCO u�dln\l N0 37A(OR) m= 39A(OR) CN-6 36A(BLI# 36C(BL) 36K(BL) 21A(YL) LOAD INDUCER IC(RD) IN 35C(RD)14 BLOWER 73A(PR) LOAD LITE WE sslus O' c' rm LED g.!- xEAi COOL 51A(6Yl L 43A(BR) GV 39BtOR1 I RO 49B(PR) CN-7 YELLOW H65A(YL) CN-9 67A(YL)—f�BLACK ams IGN RANGE ION G�jD 40A(GR) 2A(BK) COM IA(RD) 230V TNSI a 57A(OR) [8V 24V 36A(BL) 38A(GR) K41AcNH) CN-8 BLACK-ftYELLOW B 36B. VEIL Tx 57A(ORI TR 36K(BLI FTBA B 59A(BK1 47BI YL) C 3A(BL) 47A(GR) D IA(RD) 3 8 A ( G R )--0-777 36B(BL)-� 47AIGR) B 45AlBK) —.= I CS` CSR ><... 67A(YL )E" -G ;�\ L12 4B(BK): y Opl ioDo1 41A(WH)� i Field -� o, w a, OD 358fRD) o Up _av n CO In Dlol led, Slarl Kill: -R A Co V ROTES) CONNECTIONS SHOWN ARE F R A TYPICAL THERMOSTAT, SEE SCHEMATIC SUPPLIED �' TH THERMOSTAT FOR PROPER CONNECTIONS, 0 yOLTAG€I 1R1 NG TO U417 MAY BE NEC CLASS 2 AND �U T BE A MI�IMUM OF 18 A,�,G, SET TH[R OSTAT HEAT ANTICIPATOR TO ,3 MPS, 2, MA% MUM ADDITIONAL EXTERNAL OAD (PILOT DUTY) BETWEEN 'B' AND 'R' OF 0,5 A�PS, 24 yAC IS AVAILABLE 14 THE COOLING MODE ONLY, FOR 208 VOLT OPERATION MAKE THE FOLLOWING FIRING CHANGES, A; AT TNSI REMOVE IA(RD) IRE AND CONNECT TO 208V TERMINAL ON TRANSFORME , C jIF ANY OF THE ORIGINAL MIRE AS SUPPLIED IN THIS �41TNGUMATERT BE REPLACEED,D AjT�EPLACE105�CIT WITH APPLIANCE C = LOI VOLTAGE COMMON G = AL ERNATE GROUND LOCATION L = LINE yOLTAGE N = NEUTRAL I = FAN/COOLING 0 2 FAN/COOLING �E 3 = FAN/C0041NG HIGH 4 = HEAT LOW 5 = HEAT HI H L1mW. M-mmLm m '(B'' �i•ti7�•1���7� r r• D 36E(BL1 IF(RD1 2D(BKI MMM a000a 6IA( RD 63A(BL 59AtBK) 73A(PR) DrW.D758084POI 22-1901-1J-EN 21 a MANE' Wiring — 4YCC4 CAUTION -NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150 VOLTS TO GROUND, ATTENTION; NE CONVENT PAS POUR LES INSTALLATIONS DE PLUS DE 150V. A TERRE. UNIT FACTORY WIRED FOR 230V SEE *4R ING DIAGRAM NOTES FOR IGES WEN NSTALLED ONIAGZ 08VN POWERH SUPPLY, Figure 3. 4YCC4024-042 MODELS 4YCC4024A* 4YCC4030A• 4YCC4036A• 4YCC4042A* POWER SUPPLY PER LOCAL CODES SEE NAMEPLATE FOR LINE VOLTAGE, _ 88(OR) CSR AB(BK)5 �Li 2LX d6AtBR CS 3D(RD) - a _ R2 OPTIONAL START IOT WARNING HAZARDOUS VOLTAGE! DISCON14CLUDNNGTREMOTELDIiSCONNEOCTSR BEFORE SERVICING. FAILURE TO DISCONNECT PO ER SUPPLY BEFORE SERVICING CAN CAU E SEVERE PERSONAL INJURY OR DEATH, DAVERTISSEMENT VOLTAGE HASARDEUX! DECONNECTEZ TOUTES LES SOURCES ELECTRIOUES INCLUANT LES DISJ04CTEURS SITUES A DISTANCE AVANT D'EFFECTUER L'ENTRETIEN, FAUTE DE DECONNECTER LAENTRETSOURC EELECTRIEN PEUT EUNTRAANERNT DDESFECTUER BLESSURES CORPORELLES SEVERES OU LA MORT, 0 CAUTION USE COPPER CONDUCTORS ONLY! UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS, FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT, PRINTED FROM D758084PO I 22 22-1901-1 J-EN aMWE Wiring — 4YCC4 Figure 4. 4YCC4048 OEITnoog frcTInN ^NnnnR crCTlnk ('pNTRnI flOX CN-7 CN-8 ODM CN-6 IW = SCR\ YELLOW —ft65A(YLI BLACK YELLOW 3B(RD)ORANGE 36A(BLI#36C(BLJ CN-9 aa0 36K(BL> x w ma m 3C(RD) CFT 67A(YL) BLACK J ¢ CF[n�P[? 7A(PR)9AfBR> m 2 ex \\�� 21A(YL) LOAp ex INDUCER IGN RANGE IC(RD) IN x -- a as a G;D /OA(GR) 35C(RD) IN ION m T CPR � � ,� SLOWER ., v m .. C 73A(PR) LOAD a S R WE ml sE1E} PP ^"� w _ 0 IDM 36E(BL) O O R 35B,C(RD) LED un CC s� w B��567AIOR) 36BD(BL) W �° ~ _ COOL ® o Tx rT „0 O m o 5 TR3K(BL) J J T N m co �EpTEp .. co 0 � X r e � Q CFM �M, m BLACK YELL a a 2A (BK) COM FTBA C IAIRD) 230V B 59Al'K) TCO N NO, TNS1 a A7BtYL) c 3A(6u T�CO\ 37A(OR) 57A(OR) 47A(GR) D IA(RD) 208y 24y 39At0A1 LPCO 36A(BL 1 38A(GR YELLOW 38A(GR) 36B(BL)� YELLOjNK 51Am) -- A7A(GR)K -B 43A(BR) ay.R—��YR [O TROI fl*% 15A(BK) �� f CS CSR II 67A(YL ID -G HC GV 39B(ORI FD 5 AB(BK) /��� Y BLACK I \I I/ 1 2 0,,i0n01 41A(WH) BLACK RO m w ao Field -W I nsI011ed, 35BtRD)� o IP sv s In Si0r1 Kii -R I�A m o A981 PR) ROTES) CONNECTIONS SHOt4 ARE F R A TYPICAL THERMOSTAT, SE SCHEMATIC $ PPLIED �ITH THERMOSTAT FOR PROPER CO4NECTIONS,�OW VOLTAGEIRING TO UNIT MAY BE NEC CLASS 2 ND U T BE A IMU OF 18 A, ,G, SET TH[R OSTAT HEAT ANTIC. YIIPATOR TO ,3 MPS, 2, MAXIMUE ADDITIONAL EXTERNAL OAD (PILOT DUTY) BETWEEN -B' AND -R' OF 0,5 A�PS, 24 VAC IS AVAILABLE IN THE COOLING MODE ONLY, FOR 208 VOLT OPERATION MAKE THE FOLLOWING FIRING CHANGES, A, M TER INAL ON REMOVE IA(RD)4SFORMEtIRE AND CONNECT TO 208Y A, IF ANT OF THE ORIGINAL MIRE AS SUPPLIED IN THIS '�IR INGUMATERI REPLACED AT EP05CEC IT WITH APPLIANCEI. C = LOW VOLTAGE COMMON G = ALTERNATE GROUND LOCATION L = LINE VOLTAGE N = NEUTRAL I = FAN/COOLING 0 2 = FAN/COOLING �E 3 - FAN/C00 ING HIGH A - HEAT LO� 5 = HEAT HIGH IRE COLOR DESIG TIO BBR COLOR BBR COLOR BK ELAN PR PURPLE BL BLUE AD RED BR BR x HITE GA GHEE YL YELL On OA GE GT GR Y 2A VOLT TRANSFORMER FUSE REPLACEMENT FU 36VOL TT PE ATC-5 A P 36E(BL) IF(RDI 2D(BKI NNE ME 11AlRD 63A(BL K) 59A(B13A(PR) Drw.D758082POI 22-1901-1J-E N 23 aMANE Wiring — 4YCC4 CAUTION -NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150 VOLTS TO GROUND, A TTENTIO ; NE CONVIENT PAS POUR LES INST LLATIONS DE PLUS DE 150V, A TERRE, UNIT FACTORY WIRED FOR 230V SEE WIRIN DIAGRAM NOTES FOR INSTILLEDREOU�ON1CHAGES AG208VNPOWER RSUPPLY, POWER SUPPLY PER LOCAL CODES SEE NAMEPLATE FOR LINE VOLTAGE, Figure 5. 4YCC4048 MODELS 4YCC4048A• - -- - -- - -- - -- - -- - -- - -- 88(OR )----- ^� -- 48(BK)5u2 ,- S�RCS JWBR 3D(RD) R2 OPTIONAL START KIT WARNING HAZARDOUS VOLTAGE! DISCONI NCLUDNNGTREMOTEL DCI SCONNEOC�TSR BEFORE SERVICING. FAILURE TO DISCONNECT POWER SUPPLY BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. zhAVERTISSEMENT VOLTAGE HASARDEUX! DECONNECTEZ TOUTES LES SOURCES ELECTRIOUES INCLUANT LES DISJONCTEURS SITUES A DISTANCE AVANT D'EFFECTUER L'ENTRETIEN, FAUTE DE DECONNECTER LA SOURCE ELECTRIOUE AVANT D'EFFECTUER L'ENTRETIEN PELT ENTRAINER DES BLESSURES CORPORELLES SEVERES OU LA MORT, 0 CAUTION USE COPPER CONDUCTORS ONLY! UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT, PRINTED FROM D758082PO I 24 22-1901-1 J-EN aMWE Wiring — 4YCC4 Figure 6. 4YCC4060 OUTDOOR SECTION iHHOOR SECTION (OkTROL BOX CN-7 CN-8 ODM CN-6 Ip3 S�CR\\ YELLOW �65A(YLI BLACK YELLOW 3B(RD)ORANGE 36A(BL)#36C(BL) CN-9 z Vap 36K(BL) Y o CFI V w mn m 3CtRD) 67A(YL)BLACK J iy SS F[OuPf 7A(PRI\\//9AfBR) m ., 21A(YL) LOAD cr INDUCER IGN RAIIGE x� IC(RD) IN v Y ^ a as a 35C(RD)IN ION G�D /OAtGRI J m J a BLOWER CP00 e M a C 73A(PR)LOAD /IAt�'HI w S R LITE WE !E!up! PM IDM 36E(BL) c' c° R 358,C(RD) LED LE! g 36B.D(BLI CC cc HEM Lill. Y W N J rT ¢ m m COOL ®_ �o 5TA(OR) ,� .. mTxo m a _ ! ! TR 36X(BLI Eo m v CFM AK TELL 2A(BK) COM FTBA N - C IAtRD> 230V TCO B 59A(BK) Np, TNSI a A7B(YLI C 3AtBLl CO �\ 57A(OR)A7AIORI D IA(RD) 37A(OR) 208V 39A(OR) 24V LPCO 36A(BL) 38A(GR)�,� YELLOW � 38A(GR) 36B(BL1� YELLOjIj� 51A16T1 --IR (•n TROI B�i)y 47A(GR)� -B A3A(BR) 15AtBK) �0 0-- -- CS CSR 67A(YLI� _G HPCO OV 39Bl OR) ID 521 AB(BK): _Y BLACK I \I I/ I 2 Oplionol AIA(WHI BLACK l�Jl w Field �1 0 OTT I" nslolled. 35B(RD)� c IP so > 0° Start Kit -R Im� m o J I980R) z c z A NOTESI a CONNECTIONS $HOtN ARE F R A TYPICAL THERMOSTAT, SEE SCHEMATIC $ PPLIED �ITH THERMOSTAT FOR PROPER CoNNECTIONS,�Oj VOLTAG[ �I ,I G TO UNIT MAY BE NEC CLASS 2 qND U T BE A E I U OF 18 A,yp,G. SET TH RMOSTAT HEAT ANTICIPATOR TO ,3 AMPS, 2, MAXIA ADDITIONAL EXTERNAL OAD (PILOT DUTY) BETWEEN -B' AND 'R' OF 0,5 A�PS, 24 VAC IS AVAILABLE IN THE COOLING MODE ONLY, FOR 208 VOLT OPERATION MANE THE FOLLOWING FIRING CHANGES, A, AT I TERMINAL 0, TRANSFOAMEtIRE AND CONNECT TO 208y A, IF ANY OF THE ORIGINAL LIRE AS SUPPLIED IN THIS '�NIT MUST BE REPLACED, [PLACE IT WITH APPLIANCE IRING MATERIAL RATED AT I05° C, C = LOW VOLTAGE COMMON G = ALTERNATE GROUND LOCATION L LINE VOLTAGE N = NEUTRAL I FAN/COOLING 0 2 = FAN/COOLING �E 3 FAN/COO4ING HIGH A = HEAT LOW 5 = HEAT HI H IRE COLOR DESIGIAT101 BBR COLOR BBR COLOR BK BLACK PA PURPLE BL BLUE AD RED BR BA H HI TE GR GAEE TL TELL OR OA GE GY GRAY 2A VOLT TRANSFORMER FUSE REPLACEMENT FU 36VOL TYPE ATC-5 A P 36E(BLI IF(RDI 2D(BKI C L 0 N HNNH ME 6ptBL3573A(PR) 9AtB6) FUSE Drw.D758083PO1 22-1901-1J-EN 25 a MANE' Wiring — 4YCC4 CAUTION -NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150 VOLTS TO GROUND, ATTENTION: NE CONVIENT PAS POUR LES INSTALLATIONS DE PLUS DE 15OV, A TERRE. UNIT FACTORY WIRED FOR 230V SEE WIRING DIAGRAM NOTES FOR REQUIRED WIRING CHANGES WHEN INSTALLED ON A 208V POWER SUPPLY, POWER SUPPLY PER LOCAL CODES SEE NAMEPLATE FOR LINE VOLTAGE, Figure 7. 4YCC4060 MODELS 4YCC4060A* 8B(OR C>----- 4BIBK) n CSIR 6A(BR CS 3D(RD) 5 2 2 I R2 17 - OPTIONAL START KIT BLACK CC-2 I O WARNING HAZARDOUS VOLTAGE! I CLUDNTALL ELECTRIC CPOWER R NGREMOTEDISCONNECTS BEFORE SERVICING. FAILURE TO DISCONNECT POj�ER SUPPLY BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH, AMERTISSEMENT VOLTAGE HASARDEUX! DECONNECTEZ TOUTES LES SOURCES ELECTRIOUES INCLUANT LES DISJONCTEURS SITUES A DISTANCE AVANT D'EFFECTUER L'ENTRETIEN. FAUTE DE DECONNECTER LAENTRETSOURC EELECTRIEN PEUTOENTRAUE ANERNT DDESFECTUER BLESSURES CORPORELLES SEVERES OU LA MORT, 0 CAUTION USE COPPER CONDUCTORS ONLY' UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EOUIPMENT. PRINTED FROM D758083PO I 26 22-1901-1 J-EN Full Perimeter Roof Mounting Curb 0 CHANNELEND Figure 8. 2.0 — 3.0 Ton Models BAYCURB050A Full Perimeter Roof Mounting Curb 38 i I I I II< 357 - 3 5/8 3/16 The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. / C CHANNEL SIDE WOOD NAILER I I I I I I I HOLE IN; ROOF I I 43 3/8 SERVICE CLEARANCE DIMENSIONS A B C D WC*/TC* 42.00 36.00 12.00** 24.00 DC*/YC* 42.00 36.00 12.00** 36.00 ** 42.00 WITH ECONOMIZER WITH 25% FRESH AIR ACCESSORY 22-1901-1J-EN 27 aTRANE` Full Perimeter Roof Mounting Curb Figure 9. 3.5 — 5.0 Ton Models BAYCURB051A Full Perimeter Roof Mounting Curb 10 7/8 14 The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the i \ items depicted in the drawings. The manufacturer i \ is not responsible for the unauthorized use of these i \ drawings and expressly disclaims any liability for damages resulting from such unauthorized use. \ RETURN i \ AIR i SUPPLY D � AIR Ci i \. CHANNEL SIDE CHANNEL END \ /\ WOOD NAILER HOLE IN ROOF i 38718 53 1/8 SERVICE CLEARANCE DIMENSIONS A B C D WC*/TC* 42.00 36.00 12.00** 24.00 DC*/YC* 42.00 36.00 12.00** 36.00 ** 42.00 WITH ECONOMIZER WITH 25% FRESH AIR ACCESSORY 28 22-1901-1 J-EN 0 TRIUNE Optional Equipment —Economizer Table 13. BAYECON101,102A Down Discharge Economizer and Rain Hood (Mounts Over Horizontal Return Air Opening) HVAC Unit Economizer Unit Application Models Economizer eeeeeeeeee'�` BBeeeBeeeee rain hood e e e e e e e e e e e BAYECON101A 2.0 — 3.0 Ton Models Outside air dampers Return air dampers Required o filter kit, order Mist separately eliminator o �J BAYECON102A 3.5 — 5.0 Ton Models Return Relief damper Duct Roofcurb Table 14. BAYCON200, 201A Horizontal Economizer and Rain Hood ' Economizer A \B\ 0 s C Gaskets (2) Duct E Rain Hood Mixed Air Sensor Economizer Models A B C D E F BAYECON200A 2.0 — 3.0 Ton 22" 20" 16-7/8" 15-11/16" 11-11/16" 15" BAYECON201A 3.5 — 5.0 Ton 26" 22-21/32" 19" 17-11/16" 14-11/16" 21-3/8" Note: The drawings on this page are prepared by the manufacturerin order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. 22-1901-lJ-EN 29 0 TIP4UIIE Optional Equipment —Outside Air Damper Table 15. BAYOSAH001 and 002A A r, FULLY OPEN Manual Fresh Air Model Unit Application Models A B C D BAYOSAH001A 2.0 — 3.0 Ton 22-7 16" / 20-1116" / 12-3 8' / 9-3 16" / �D /C o/3 C B FULLY CLOSED BAYOSAH002A 3.5 — 5.0 Ton 25-3/16" 20-11/16" 12-3/8" 9-3/16" Table 16. BAYDMPR101 and 102A, 25%O Motorized Outside Air Damper (Mounts Over Horizontal Return Air Opening) N Manual Fresh Air Model Unit Application Models A B C D E BAYDM- 2.0 — 3.0 15-13/16" 11-13/16" 10-1/4" 11-1/2" 12-1/4" PR101A Ton C D E BAYDM- 3.5 — 5.0 18-3/16" 15-1/8" 10-1/4" 11-1/2" 12-1/4" D PR102A Ton Note: The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. 30 22-1901-lJ-EN 0 TIP4UIIE Optional Equipment —Filter Rack Figure 10. BAYFLTR101 Filter Rack (2.0 - 3.0 Ton Models) BAYFLTR201 (3.5 - 5.0 Ton Models) (Mounts in Filter/Coil Section) Figure 11. BAYACCD0R1A Hinged Filter Access Door (2.0 - 3.0 Ton Models) BAYACCD0132A (3.5 - 5.0 Ton Models) Replaces Filter/Coil Access Panel Note: The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. 22-1901-1J-EN 31 0 TRIUNE Outline Drawings I I (DUCT F 10� [41 J 18.03 18.29 [23/321 [23/32] 14.22 SECTION Y-Y TYPICAL (8) SIDES OF DOWNFLOW DUCT OPENINGS M LEFT SIDE Figure 12. 4YCC4024-4036 Note: The view labeled "Bottom side" represents the base as viewed looking up from underneath the unit. 4 OUTLET FRONT SIDE BOTTOM SIDE RA UE OD 32 22-1901-1 J-EN 79.50 - [3-I/8] 398.22 115-11/161 (OUTSIDE) Figure 13. 4YCC4024-4036 296.62 [11-II/16] (OUTSIDE) RETURN [2-9/32] 1 77. 55 SUPPLY E7] 398.22 [15-II/16] (OUTSIDE) 176.01 [6-15/16] BACK DUCT OPENINGS I T. 78 [II/16] TI N TYPICAL (8) SIDES OF SIDEFLOW DUCT OPENINGS BACK SIDE aMME Outline Drawings Height mm/in Flu Hood w/brkt mm in Approx. Corner Weight - kg / Ibs Shipping Weight kg/Ibs Total Unit Weight kg/Ibs Center of Gravity mm/in A D W1 W2 W3 W4 B C 4YCC4024 (060) 898.53 [35-3/8] 157.16 [6-3/16] 58.3 [129] 36.8 [811 26.1 [58] 41.0 [90] 196.1 [432] 162.4 [358] 479.8 [18.9] 527.8 [20.8] 4YCC4030 (070) 898.53 E35-3/83 157.16 [6-3/16] 61.3 [135] 38.7 [85] 27.5 [61] 43.1 [95] 204.8 [451] 171.1 [377] 406.5 [16.0] 594.1 [23.4] 4YCC4036 (070) 949.33 [37-3/8] 157.16 [6-3/16] 61.1 [134] 38.3 [841 27.1 [601 43.2 [95] 203.4 [438] 169.7 [374] 1 414.3 [16.3] 697.6 [27.5] 4YCC4036 (090) 949.53 [37-3/8] 157.16 [6-3/16] 61.7 [136] T3,.9 [86] 17.7 [611 43.7 [96] 205.7 [453] 172.0 [379] 414.3 [16.3] 697.6 [27.5] 22-1901-1J-E N 33 aTRANE` Outline Drawings RECOMMENDED SERVICE CLEARANCE MM/IN. WITH ECONOMIZER BACK SIDE 304.8 1121 762.0 1301 LEFT SIDE 762.0 [301 914.4 [361 RIGHT SIDE 9I4.4 [361 - FRONT SIDE 1066.8 (421 - CLEARANCE TO COMBUSTIBLE MATERIAL MMIIN. 304.E 1121 (INSIDE 75.41 E2-31/3 24V ENTR 359.80 1 [14-5/321 294.02 111-9/161 178.66 1 17-1/321 84.96 E3-II/321 127.84 E5-1/321 Figure 14. 4YCC4024-4036 1321 406.40 1161 1(INSIDE) »'1'6.", ( I NSIDE ) BOTTOM DUCT OPENINGS POWER ENTRY 34.13 DIA. HOLE 11-3/321 GAS LINE ENTRY FOR 12.70 11121 N.P.T. 98.66 GAS CONNECTION RIGHT SIDE 34 22-1901-1 J-EN 304.E 1121 (INSIDE 75.41 E2-31/3 24V ENTR 359.80 1 [14-5/321 294.02 111-9/161 178.66 1 17-1/321 84.96 E3-II/321 127.84 E5-1/321 Figure 14. 4YCC4024-4036 1321 406.40 1161 1(INSIDE) »'1'6.", ( I NSIDE ) BOTTOM DUCT OPENINGS POWER ENTRY 34.13 DIA. HOLE 11-3/321 GAS LINE ENTRY FOR 12.70 11121 N.P.T. 98.66 GAS CONNECTION RIGHT SIDE 34 22-1901-1 J-EN Figure 15. 4YCC4042-4060 7. 78 II/I61 N TYPICAL (8) SIDES OF SIDEFLOW DUCT OPENINGS J- 18.03 18.29 12382 ] [ 23' 321 1IA.22 9/161 SECTION Y-Y TYPICAL (8) SIDES OF DOWNFLOW DUCT OPENINGS a RECOMMENDED SERVICE CLEARANCE MM/IN. WITH O.A. DAMPERIECON. OUTLET Note: the view labeled "Bottom Side" represents the base as viewed looking up from underneath the unit. BOTTOM SIDE aMWE Outline Drawings 22-1901-1J-EN 35 aTRANE` Outline Drawings Figure 16. 4YCC4042-4060 372.82 0 lull [14-II/16] (OUTSIDE) lid f 449.02 r [17-II/I6] 79.50 (OUTSIDE) [3-1/8) 449 02 176.07 [17-II/I6] [6-15/I6] (OUTSIDE) BACK DUCT OPENINGS 1402.34 (55-7/32] (SURFACE AREA) BACK SIDE 0 /8] Model Height mm/in Approx. Corner Weight - kg / Ibs Shipping Weight kg/Ibs Total Unit Weight kg/Ibs Center of Gravity mm/in A W1 W2 W3 W4 B C 4YCC4042 (060) 898.53 [35-3/8] 71.2 [157] 46.6 [103] 34.6 [76] 53.1 [117] 252.2 [555] 202.0 [452] 470.0 [18.5] 731.0 [28.8] 4YCC4042 (090) 898.53 [35-3/8] 71.8 [158] 47.2 [104] 35.2 [78] 53.6 [1181 254.5 [561] 207.3 [4571 470.0 [18.5] 731.0 [28.8] 4YCC4048 (070) 1000.13 [39-3/8] 71.4 [157] 44.6 [98] 33.2 [73] 53.9 [119] 250.3 [552] 202.1 [448] 433.0 [17.0] 743.3 [29.3] 4YCC4048 (090) 1000.13 [39-3/8] 72.0 [159] 45.0 [99] 33.8 [75] 54.4 [120] 252.6 [557] 205.4 [453] 433.0 [17.0] 743.3 [29.3] 4YCC4060 (090) 1000.13 [39-3/8] 77.1 [170] 45.8 [101] 34.4 [76] 58.3 [128] 263.1 [580] 215.9 [476] 433.0 [17.0] 743.3 [29.3] 4YCC4060 (115) 1000.13 [39-3/8] 78.0 [172] 46.3 [102] 34.9 [77] 59.0 [130] 265.8 [586] 218.6 [482] 414.0 [16.3] 635.0 [25.0] 36 22-1901-1 J-EN Figure 17. 4YCC4042-4060 457.20 1181 (INSIDE) 75.41 [2-31/32 [151VV (INSIDE) BOTTOM DUCT OPENINGS 24V ENTRY �o 359.80 294.02 [14-5/321 111-9/161 178.66 1 1 [1-1/321 84.96 GAS LINE ENTRY [3 II/32] I FOR 12.70 [1121 N.P.T. GAS CONNECTION 98.66 [3-7/81 aMME Outline Drawings POWER ENTRY 27.78 DIA. HOLE [1-3/321 127.84 RIGHT SIDE [5-1/321 381.00 [151 (INSIDE) 75 9/161 20 >IDE) 09 /81 22-1901-1J-E N 37 Notes 38 22-1901-1J-EN Notes 22-1901-1J-EN 39 TRANS Trane - by Trane Technologies (NYSE: TT), a global innovator - creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane. com or tranetechnologies.com. 0%.-s Intertek The AHRI Certified mark indicates Trane U.S. Inc. participation in the AHRI Certification program. For verification of individual certified products, go to ahridirectory. org. Trane has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices. 22-1901-1J-EN o7 Jun 2020 Supersedes22-1901-1H-EN (June2019) ©2020Trane