GENERAL NOTES 1. All electrical materials shall be new and listed by recognized electrical testing laboratory Custom made equipment shall have complete test data submitted by the manufacturer attesting to its safety 2. Outdoor equipment shall be NEMA 3R rated or equivalent 3. All metallic equipment shall be grounded 4. Contractor shall obtain electrical permits prior to installation and shall coordinate all inspections, testing commissioning and acceptance with the client, utility co. and city inspectors as needed. 5. The electrical contractor shall verify the exact locations of service points and service sizes with the serving utility company and comply with all utility companies requirements. 6. Drawings are diagrammatic only, routing of raceways shall be option of the contractor unless otherwise noted and shall be coordinated with other trades. 7. If the roof material or the roof structure not adequate for PV installation, call the engineer of record prior to installation. The contractor is responsible to verify that the roof is capable of withstanding the extra weight. 8. If the distances for cable runs are different than shown, the contractor shall notify the electrical engineer to validate the wire size. Final drawings will be red -lined and updated as appropriate. 9. Whenever a discrepancy in quality of equipment arises on the drawing or specifications, the contractor shall be responsible for providing and installing all materials and services required by the strictest conditions noted on the drawings or in the specifications to ensure complete compliance and longevity of the operable system required by the engineer of record. PHOTOVOLTAIC NOTES: 1. Rooftop mounted photovoltaic panels and modules shall be tested, listed and identified by recognized testing laboratory 2. Solar system shall not cover any plumbing or mechanical vents 3. Modules and support structures shall be grounded unless racking has integrated ground. 4. Removal of an interactive inverter or other equipment shall not disconnect the bonding connection between the grounding electrode conductor and the photovoltaic source and/or output circuit grounded conductors. 5. All PV modules and associated equipment and wiring shall be protected from physical damage. 6. Live parts of PV source circuits and PV output circuits over 150v to ground shall not be accessible to other than qualified persons while energized. 7. Inverter is equipped with integrated DC disconnect, thus providing ground fault protection 8. All conductors shall be copper and 75 deg rated 9. A single conductor shall be permitted to be used to perform the multiple functions of do grounding, AC grounding and bonding between AC and DC systems. 10. Non -current carrying metal parts of equipment shall be effectively bonded together. Bond both ends of raceways. SHEET INDEX CONTRACTOR SITE MAP & PV LAYOUT PV 1.0 Northwest Electric and Solar ELECTRICAL 1-LINE DIAGRAM PV 2.0 Address: 18001 73rd Ave NE Kenmore WA 98028 SYSTEM LABELING DETAIL PV 3.0 Phone number: 206-356-0601 PROPERTY PLAN PV 4.0 Appointments: nwsolar.com ATTACHMENT LAYOUT INVERTER DATA SHEET_ RSD DATA SHEET MODULE DATA SHEET RACKING DATA SHEET_ ATTACHMENT DATA SHEET ENPHASE IQ COMBINER GOVERNING CODES PV 5.0 D 6.0 Owner: 7215 - Drown D 7.0 Property Address: 1046 3rd Ave S, Edmonds, WA 98020 Property Type: Single Family Residence D 8.o Drawn by: New@engineerinc.io D 9.0 Date: 0212812023 D 10.0 VICINITY MAP (SCALE: NTS) D 11.0 \ Q Designs by Sylvan Willow Creek salmon & Watershed... `m I to pine st Pine St I Plnc SI i THE INSTALLATION OF SOLAR ARRAYS AND PHOTOVOLTAIC POWER SYSTEMS SHALL COMPLY WITH THE FOLLOWING CODES: • 2020 National Electrical Code 2018 International Building Code • 2018 International Fire Code AS ADOPTED BY THE STATE OF WASHINGTON ALL OTHER ORDINANCE ADOPTED BY THE LOCAL GOVERNING AGENCIES SYSTEM RATING DC 12.96KW STC AC 10.40KW STC EQUIPMENT SUMMARY 32 REC 405 WATT MODULES WITH IQ8M MICROINVERTERS ELECTRICAL INFORMATION EXISTING MAIN SERVICE PANEL BUS SIZE: 200A MAIN SERVICE BREAKER SIZE: 200A MOUNTING SYSTEM: IRONRIDGE BUILDING INFORMATION CONSTRUCTION TYPE: V-B OCCUPANCY: R3 ROOF:COMP. SHINGLE Truss 2 x 6 @ 24" O.C. SATELLITE VIEW (SCALE: NTS) Forsyth In Maplevine CommMaY9 s 5 H g s y vSharnrock Plaza Condo Po PI a W 270 N 0° E 90, SCALE: 1/8" = V-0" Solar PV Array 1 Total Roof Area: 2982 12 -REC 405W Modules Total Module Area: 704 12 - IQ8M Microinverters 23.60% of Coverage Pitch: 18 Deg Orientation:270 De 36" fire setback 36" fire setback . — — —P F - ---- OWN -6 iWIS, O I I � �J!32 Solar PV Array 2 12 -REC 405W Modules 12 -IQ8M Microinverters Pitch: 18 Deg Orientation: 90 Deq I 18" fire setback JB3- P �C C �C O Solar PV Array 3 8 -REC 405W Modules 8 - IQ8M Microinverters Pitch: 18 Deg Orientation:180 Dea OSP M INDEX O I I � �J!32 Solar PV Array 2 12 -REC 405W Modules 12 -IQ8M Microinverters Pitch: 18 Deg Orientation: 90 Deq I 18" fire setback JB3- P �C C �C O Solar PV Array 3 8 -REC 405W Modules 8 - IQ8M Microinverters Pitch: 18 Deg Orientation:180 Dea OSP M INDEX SOLAR MODULES MM.........................(E) Main Meter 32 Rec 405 Watt MSP (E)200AMain Service Panel Model #Rec405AA AC............ (N) 60A AC Disconnect INVERTER ECB .... (N) Enphase IQ Combiner INVERTER TYPE: Micro: 32 Enphase IQ8M JB.......................(N) Junction Box Model # IQ8M-72-2-US(240V) []........................(N) Microinverter ..................... Solar Module ............. EMT type Conduit ............• Fire Setback Line Cn m Q M CONTRACTOR Northwest Electric and Solar Address: 18001 73rd Ave NE Kenmore WA 98028 Phone number: 206-356-0601 Appointments: nwsolar.com Northwest & Solar SITE MAP & PV LAYOUT CNGINCCZINC Drawn by: New@engineerinc.io DATE.• 02/28/2023 Project Name: 7215 -Drown Property Adress: 1046 3rd Ave S, Edmonds, WA 98020 Project: Scale: PV SYSTEM AS INDICATED [—Pv 1.0 NOTE: Service Panel does not contain center fed Main Breaker- (6) #10 AWG THWN/THWN-2 LINE SIDE TAP (1) #10 AWG GND 3/4" EMT 15 FEET PV MONITORING DEVICE 15A 2-POLE 2 #14 AWG THWN/THWN-2 60A FUSED AC DISCONNECT, EXISTING WITH 60A FUSES NON CENTER 200A MAIN METER ® LOCKABLE,BLADE TYPE, MAIN C/B 71 J BOX 3 NEMA3R NEMA3 120 / 240V UiL@rl-l ❑+ .......... a ❑+ INSTALL (3)20A PV (UTILITY REQUIRED) _ muse■■Damon 2-POLE C/Bname am ONE so NONE ■■■■■ m woman swung L2J so ■■■ .. • ....••. L8J■■■ J BOX 2 NEMA3 0000 0000 U in: ENPHASE AC COMBINER 4120/240V, NEMA 3R GECUz — ■mwm8g U ■■w■■ (6) #10 AWG THWN/THWN-2 (3) #6 AWG THWN/THWN-2 GEC m wager E) GROUNDING L2�wB■ (1) #10 AWG GND (1) #10 AWG GND (N) GROUNDING ELECTRODE SYSTEM 3/4" EMT 21 FEET 3/4" EMT 2 FEET ELECTRODE SYSTEM m ❑+ ■ ■ ❑+ m .......... ❑+ U owns ■ woman: uuewD (3) #6 AWG THWN/THWN-2 ■Brow ■wwBB■ ■wwge (4) #10 AWG THWN/THWN-2 1" PVC 2 FEET z ■non■ ■wwBB■ ■wwB■ (1) #10 AWG GND ■BBB■ ■wwBB■ ■BBB■ U Bmmm■ ■wwooa ■■■■■ 3/4" EMT 15 FEET m owns ■ ■■mm■ .... Boiii U iii L2�wB■ �Owa■ JBOX 1 NEMA3 m ❑+ a _ Bases z � ■wmmo Q U woman ■am■■ m — ,1mmm■ U Qi1!j:::: ■ ❑+ m .......... ■ ❑+ 2 ■aww■■ woman ,a Los U ■■gam■gal ■■woma ■■MIm �■■mm■ Ba■B■ L2Jma■ - ■w■ 32 REC 405 WATT MODULES 32 ENPHASE IQ8M MICROINVERTERS EXISTING 200A MAIN SERVICE PANEL 120/240V, 1 P, 3W 0 0 0 0 CONTRACTOR Northwest Electric and Solar Address: 18001 73rd Ave NE Kenmore WA 98028 Phone number: 206-356-0601 Appointments: nwsolar.com Northwest Solar ELECTRICAL 1-LINE DIAGRAM CNGINCC�INC Drawn by: New@engineerinc.io DATE: 02/28/2023 Project Name: 7215 -Drown Property Adress: 1046 3rd Ave S, Edmonds, WA 98020 Project: Scale: PV SYSTEM AS INDICATED FP-V 2.0 LABEL 1 LABEL 2 LABEL 3 LABEL 4 LABEL 5 LABEL 6 LABEL 7 (STICKER TO BE LOCATED ON CONDUIT WITH DC CURRENT EVERY 4' HORIZONTALLY OR 1 UVERTICALLY AND V FROM EACH SIDE OF A BEND) LABEL 8 LABEL 9 (STICKER LOCATED (STICKER LOCATED INSIDE PANEL INSIDE PANEL NEXT TO SOLAR BREAKER) BELOW PV BREAKER) DIRECTORY LABEL 10 (STICKER LOCATED ON THE PV SUB PANEL) (TO BE LOCATED ON SUB -PANEL ONLY WHEN SUB -PANEL IS DEDICATED FOR PV ONLY) LABEL 11 (STICKER LOCATED ON THE MAIN SERVICE PANEL) Permanent directory or plaque providing location of service disconnecting means and photovoltaic system disconnecting means, if not located at the same location. (Plaques shall be metal or plastic, with engraved or machine printed letters, or electro-photo plating, in a contrasting color to the plaque. Plaques shall be permanently attached to the equipmenq or in the required location using an approved method that is suitable to withstand the environment to which it is exposed. Plaques and signage shall meet legibility, defacemet, exposure and adhesion requirements of Underwriters Laboratories marking and labeling system 969(UL969). Plaques will have red background & white lettering. INVERTER *if applicable METER ffOX CO)© SUB -PANEL MAIN SERVICE * if applicable AC PANEL INTEGRATED PV SUB -PANEL DISCONNECT 6 7 * if applicable © O * if a licable O O PV ARRAY DC DISCONNECT ©1 O pp 11 ® MoM ® O 1 © ® O MARKINGS, LABELS AND WIRING SIGNS A. Purpose: Provide emergency responders with appropriate warning and guidance with respect to isolating solar electric system. This can facilitate identifying energized electrical lines that connect solar panels to the inverter, as these should not be cut when venting for smoke removal B. Main Service Disconnect. 1. Residential buildings - The marking main be placed within the main service disconnect. The marking shall be placed outside cover if the main service disconnect is operable with the service panel closed. 2. Commercial buildings - Tha marking shall be placed adjacent to the main service disconnect clearly visible from the location where the level is operated 3. Markings: Verbiage, Format and Type of Material. a. Verbiage: CAUTION: SOLAR ELECTRIC SYSTEM CONNECTED b. Format: White lettering on a red background. Minimum 3/8 inches letter height. All letters shall be capitalized. Arial or similar font, non bold. c. Material: Reflective, weather resistant material suitable for the environment (use UL - 969 as standard for weather rating). Durable adhesive materials meet this requirement. C.Marking Requirements on DC conduit, raceways, enclosures, cable assemblies, DC combiners and junction boxes: 1. Markings: Verbiage, Format and Type of Material. a. Placement : Markings shall be placed every 10 feet on all interior and exterior DC conduits, raceways, enclosures, and cable assemblies, at turns, above and for below penetrations, all DC combiners and junction boxes b. Verbiage: CAUTION: SOLAR CIRCUIT Note: The format and type of material shall adhere to "V. V-3b, c" of this requirement. c. Inverters are not required to have caution markings 1.Marking is required on all interior and exterior DC conduit raceways,enclosures,cable assemblies,and junction boxes,combiner boxes and disconnects. 2.The materials used for marking shall be reflective,weather resistant material suitable for the environment. Minimum 3/8 "letter height; all upper case letters Arial or similar font; Red background with white lettering. 3.Marcking shall contain the words: WARNING: PHOTOVOLTAIC POWER SOURCE. 4.Marking shall be placed adjacent to the main service disconnect in a location clearly visible from the location where the disconnect is operated LABEL12 SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO Z41 AL.C.� SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY CONTRACTOR Northwest Electric and Solar Address: 18001 73rd Ave NE Kenmore WA 98028 Phone number: 206-356-0601 Appointments: nwsolar.com Northwest & Solar SYSTEM LABELING DETAIL CNGINCCZINC Drawn by: New@engineerinc.io DATE: 0212812023 Project Name: 7215 - Drown Property Adress: 1046 3rd Ave S, Edmonds, WA 98020 Project: Scale: PV SYSTEM AS INDICATED PV 3.0 0 Q LEGEND D MS S ......................... Main Meter MSP................ Main Service Panel AC ........................ AC Disconnect W O �� E ECB........... Enphase IQ Combiner 270 D� as so aD d� 10° SCALE: 3/32" = 1'-0" PROPERTY LINE , „ 142 —6 °g°Q�,°$pg� _ ° ^ °gE° °°g D°° 00 Oaa D°DO 0° d°D 0°9qqO,° e°ocQ OoD°Bn ° — — — — — — °n° ° °° D 0 °°° d00� ° ° D d0� a a °0a0 0° 0°" °OOCc ° c ° 6 p°e °°°d pqy, O°d d ODAc�q, a D�1n$°q,4 0 o n 0 n Dao°6�°$0 0 ° ° 46 °°°D ado 9'-8" ° at ° °ap° ° ° dp0 D0 ° ° n°0°D �d0 °0o°D 0 ° °0 aDOD°�q,q o0D D no D d 0 d 0 e yS, 'a ° 0 ° DdO � ° 0 ° d ° d °�'h0'�6 oqa a °d d 00° ° 0 d nn 0 °d to ° ❑ dd0 c d n°Ong d d °d�e°D��a�°ego a�a I ao Dom Qa d �0B 0 ° D Od0 0 a �a dd 0 d D°� DOm °0°p d °n" d °a0° 8 a c°°aAaaa °°°°D a D a OO Deo 0 d °0� gq7 ddd oSn d Da�a �Om D00 ° Da a aaD o d °� aaa0 ° ❑ D �o 00 a° Qa od ° d°0�D °d° ad a a D as 0, 0� Q°d° °Q06 0 d 0Dp 8°pROO Da X S' n �a Oa a aoo o°ap�pad a� aaa0 a0 Oo adds ad 00Oan d a 0 ga a aaAa�a ❑ I 14 60'-1 " ❑ o ® cn 67'-3" FD 67'-3" a' ❑ ® ® ® ® co I I D a, o90°o p , ag aP 00 as o°po Doc°g age o a ❑ 0 0°a dD D° dao ! a QAa 0° Qa0'fa a a a a ° ° ° ° 0 ° ° 410 0 0 ° °°0%ad00 a a d0 $°q,p Dq°, a60, Dnd Oq °Ded d aa'S'o0",h d °h0"�a ❑ oe0 �°a e'D°'° d a aD a a D a DRIVEWAY 0 d00 a 00 I d ddo C d dd d o°)0 p° a E°°0° O ° 06 a a o 0a 0aaa n�°��,t a a� d'n a 0 , „ 000°0 0 d pp°D n° a�0 on c°°a �p°a 5'6 MSP ° O�a.G' g ° d aD Wig° — — — — — — — — — SS00 ,�,�pa 6D0 ° 0o d°da as X0 dada ad — ��B MM 142'-6" D o o ° aga I �D I 000 a a aoD a as 101 101 CONTRACTOR 101 CONTRACTOR CONTRACTOR Northwest Electric and Solar Address: 18001 73rd Ave NE Kenmore WA 98028 Phone number: 206-356-0601 Appointments: nwsolar.com Northwest Solar PROPERTY PLAN CNGINCCZINC Drawn by: New@engineerinc.io DATE: 02/28/2023 Project Name: 7215 -Drown Property Adress: 1046 3rd Ave S, Edmonds, WA 98020 Project: Scale: PV SYSTEM AS INDICATED FP-V 4.0 ROOF SECTION DETAIL Solar Modul Attachment Truss 2 x 6 @ 24" O.C. if Plywood & Building Felt locking 1 Layer of COMP. SHINGLE DX#$ 2 ATTACHMENT RAIL — — — — — — — — — — — Truss 2x6 @24"O.C. IRONRIDGE ATTACHMENT AND RACKING DETAILS 3. 6 1.02 F 3. 7 —IRONRIDGE STOPPER SLEEVE IRONRIDGE UNIVERSAL FASTENING OBJECT (E) RAFTERS PV MODULE IRONRIDGE RAIL 1 .0 d 30 o- TIRONRIDGE UNIVERSAL FASTENING OBJECT IRONRIDGE FLASHFOOT2 IRONRIDGE RAIL ---_ IRONRIDGE FLASHFOOT2 PV MODULE, BY OTHERS IRONRIDGE RAIL (E)ROOF ��FLASHFOOT2 � 5/16" STAINLESS STEEL LAG SCREW I INTO FRAMING MEMBER (E) BUILDING FLASHFOOT2 G (E) BUILDINLDIN G STRUCTURE STRUCTURE A DETAIL FLASHF00T2 SIDE D DETAIL FLASHFOOT2 FRONT IRONRIDGE UNIVERSAL IRONRIDGE RAIL IRONRIDGE STOPPER SLEEVE PV MODULE FRAME FASTENING OBJECT IRONRIDGE UNIVERSAL IRONRIDGE UNIVERSAL PV MODULE FRAME FASTENING OBJECT FASTENING OBJECT PV MODULE FRAME IRONRIDGE UNIVERSAL PV MODULE FRAME IRONRIDL RAIL FASTENING OBJECT IRONRIDGE STOPPE IRONRIDGE RAIL SLEEVE \MP PLAN C DETAIL MID CLAMP FRONT B DETAIL END CLAMP PLAN B DETAIL END CLAMP FRONT DESIGN CRITERIA POINT LOAD CALCULATION PER ARRAY Prior to the commencement of work, the contractor shall verify the existing roof and framing Modules: 32 Module Weight (Ibs) 45 conditions. Notify New@engineerinc.io of any Discrepancies prior to starting construction. Max Distributed Load: 3 PSF # Of Modules 32 Prior to the commencement of work, the contractor shall inspect framing for any damage such as Total Module Weight (Ibs) 1288 water damage, cracked framing, etc. and notify New@engineerinc.io if any issues are found. Rack Weight (Ibs) 286 These Plans are stamped for structural code compliance of the roof framing supporting the rs Weight (Ibs) 76.16 proposed PV installation reference only. These plans are not stamped for water leakage. PV Total System Total System Weight (Ibs) 1804.16 modules, racking, and attachment components must follow manufacturer guidelines and # Of Standoffs 86 requirements. Attachments to be installed in a staggered orientation to properly distribute loads. Max Span Between Standoffs (in) 72 Loading Per Standoff (Ibs) 20.97 Total Area (sq.ft.) 704 Loading (PSF) 2.56 171-411 -13'-411- — — — — — — — — — — — — \ I I 1 NVA NVA IV, A 74114514 CONTRACTOR Northwest Electric and Solar Address: 18001 73rd Ave NE Kenmore WA 98028 Phone number: 206-356-0601 Appointments: nwsolar.com & Solar ATTACHMENT LAYOUT CNGINCCZINC Drawn by: New@engineerinc.io DATE: 0212812023 Project Name: 7215 - Drown Property Adress: 1046 3rd Ave S, Edmonds, WA 98020 Project: Scale: PV SYSTEM AS INDICATED FP-V 5.0 n ENPHASE. IQ8 Series Microinverters Our newest IQ8 Microinverters are the industry's first microgrid-forming, software - defined microinverters with split -phase power conversion capability to convert DC power to AC power efficiently. The brain of the semiconductor -based microinverter is our proprietary application -specific integrated circuit (ASIC) which enables the microinverter to operate in grid -tied or off -grid modes. This chip is built in advanced 55nm technology with high speed digital logic and has super -fast response times to changing loads and grid events, alleviating constraints on battery sizing for home energy systems. Part of the Enphase Energy System, IQ8 Series Microinverters integrate with the Enphase IQ Battery, Enphase IQ Gateway, and the Enphase App monitoring and analysis software. 0=c Connect PV modules quickly and easily to I08 Series Microinverters using the Included Q-DCC-2 adapter cable with plug-n-play MC4 connectors. IQ8 Series Microinverters redefine reliability standards with more than one million cumulative hours of power -on testing. enabling an industry -leading limited warranty of up to 25 years. I08 Series Microinverters are UL Listed as PV Rapid Shut Down Equipment and conform with various regulations, when installed according to manufacturer's instructions. © 2022 Enphase Energy. All rights reserved. Enphase, the Enphase logo, IQ8 microinverters, and other names are trademarks of Enphase Energy, Inc. Data subject to change. I08SE-DS-0001-01-EN-US-2022-03-01 Easy to install Lightweight and compact with plug-n-play connectors Power Line Communication (PLC) between components Faster installation with simple two -wire cabling High productivity and reliability Produce power even when the grid is down More than one million cumulative hours of testing Class II double -insulated enclosure Optimized for the latest high- powered PV modules Microgrid-forming Complies with the latest advanced grid support Remote automatic updates for the latest grid requirements Configurable to support a wide range of grid profiles Meets CA Rule 21(ILL 1741-SA) requirements 1,08 Series Microinverters Commonly used module pairings' w 235 - 350 235 - 440 I 260 - 460 I 295 - 500 320 - 540+ 295 - 500+ Module compatibility 60-cell/120 half -cell 60-cell/120 half -cell. 66-cell/132 half -cell and 72-cell/144 half -cell MPPT voltage range V 27-37 29-45 33-45 36-45 38-45 38-45 Operating range v 25 - 48 25 - 58 Min/max start voltage V 30 / 48 30 / 58 Max input DC voltage V 50 60 Max DC current' [module Isc] A 15 Overvoltage class DC port II DC port backfeed current mA 0 PV array configuration OUTPUT DATA [ACI lxl Ungrounded array: No additional DC side protection required: AC side protection requires max 20A per branch circuit r r r• Peak output power VA 245 300 330 366 384 366 Max continuous output power VA 240 290 325 349 380 360 Nominal (L-L) votage/range' V 240 / 211- 264 208 / 183 - 250 Max continuous output current A 1.0 1.21 1.35 1.45 1.58 1.73 Nominal frequency Hz 60 Extended frequency range Hz 50 - 68 Max units per 20 A (L-L) branch circult° 16 13 11 11 10 9 Total harmonic distortion <5% Overvoltage class AC port III AC port backfeed current mA 30 Power factor setting 1.0 Grid -tied power factor (adjustable) 0.85leading - 0.85lagging Peak efficiency % 97.5 97.6 97.6 97.6 97.6 97.4 CEC weighted efficiency % 97 97 97 97.5 97 97 Night-time power consumption mw 60 MECHANICAL DATA Ambient temperature range -400C to+60°C (-40°F to+140°F) Relative humidity range 4%to 100%(condensing) DC Connector type MC4 Dimensions (HxWxD) 212 mm (8.3") x 175 mm (6.9") x 30.2 mm (1.2") Weight 1.08 kg (2.38lbs) Cooling Natural convection - no fans Approved for wet locations Yes Acoustic noise at 1 In <60 dBA Pollution degree PD3 Enclosure Class II double -insulated. corrosion resistant polymeric enclosure Environ. category / UV exposure rating NEMA Type 6 / outdoor CA Rule 21 ILL 1741-SA). UL 62109-1. UL1741/IEEE1547. FCC Part 15 Class B. ICES-0003 Class B. CAN/CSA-C22.2 NO.107.1-01 Certifications This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC 2014. NEC 2017, and NEC 2020 section 690.12 and C22.1-2018 Rule 64-218 Rapid Shutdown of PV Systems. for AC and DC conductors, when installed according to manufacturer's instructions. (1) The IQ8H-208 variant will be operating in grid -tied mode only at 208V AC. (2) No enforced DC/AC ratio. See the compatibility calculator at https://Iink.enphase.com/module-compatibility (3) Maximum continuous input DC current is 10.6A (4) Nominal voltage range can be extended beyond nominal if required by the utility. (5) Limits may vary. Refer to local requirements to define the number of microinverters per branch in your area. I08SE-DS-0001-01-EN-US-2022-03-01 CONTRACTOR Northwest Electric and Solar Address: 18001 73rd Ave NE Kenmore WA 98028 Phone number: 206-356-0601 Appointments: nwsolar.com I Northwest Solar INVERTER DATA SHEET CNGINCCZINC Drawn by. New@engineerinc.io DATE. 0212812023 Project Name: 7215 - Drown Property Adress: 1046 3rd Ave S, Edmonds, WA 98020 Project: Scale: PV SYSTEM AS INDICATED F_D6_- 0 Enphase•Energy // Rapid Shutdown Rapid shutdown is built-in The 2014 edition of the National Electrical Code (NEC 2014) added What's new in NEC 20114? new rapid shutdown requirements for PV systems installed on buildings. NEC 2014. Cocton 690.12 app Enphase Microinverters fully meet rapid shutdown requirements in the to P1/ conduc*,= m'or 10 feet from new code without the need to install any additional electrical equipment. Vas PV array and requires that the conductor power down to 30 volt; and 240 %M-arrpam vothin 10 seconds of rapid shutdown initiatim String inverters require work arounds for rapid shutdown Work around. Cpecializea riapjd Shutclaa electr teal box in�,aNed on t1 roof Yhtf Un 10 foot of array. Work around. shutoff rw tch that :: Ga 4y aocor,_,>ate to f mt responder on the grouna Work around. Extra conaua in Irmallanon Residential String Inverter Work around. D7r�g :f1 zar �r ;i Ga on roof, a t=. Ve or onmom inat =rng un9rw—. are not WA to live in Commercial String Inverter Enphase comes standard with rapid shutdown capability All Eophass mrcroet- :erter,, even those thin wore previously installed, inrierently noel rapid chutdovm roqurremerttc, no additional equiprris -- or worknroun&. neeJea Residential Miuoinvartet To leam more, visit enphase.com Enphase rracroinver-Lors can safety ;hut down auwmatl agy.leaving only low -voltage DC etectra y ix xed m the PV module Commercial Microinvrrtgr [ei enphase- n ENPHASE Install the Enphase IQ8 Series Microinverter To install Enphase IQ8 Series Microinverters, read and follow all warnings and instructions in this guide and in the Enphase IQ8 Series Microinverter Installation and Operation Manual at enohase_com/support Safety warnings are listed on the back page of this guide. The Enphase Microinverter models listed in this guide do not require grounding electrode conductors (GEC), equipment grounding conductors (EGC), or grounded conductor (neutral). The microinverter has a Class II double -insulated rating, which includes ground fault protection (GFP). To support GFP, use only PV modules equipped with DC cables labeled PV Wire or PV Cable IMPORTANT: Enphase IQ8 Series Microinverters require the IQ Cable. An IQ Gateway is required to monitor performance of the IQ Microinverters. The Q Accessories work only with Enphase IQ8 Series Microinverters. Note: After you log in to your Enphase Installer Platform account from Enphase Installer app, Scan the microinverter OR code and connect to the Enphase IQ Gateway to track the system installation progress. PREPARATION A ) Download the Enphase Installer App and open it to log in to your Enphase Installer Platform account. With this app, scan the microinverter QR code and connect to the Enphase IQ Gateway to track system installation progress. To download, go to enphase.com/toolklt or scan the OR code at right D) Check that you have these other items. FE1.11f+�i0 ACjunction box. `t r— r Tools: screwdrivers, wire cutter, voltmeter, torque wrench, sockets, +' and wrenches for mounting hardware B) Refer to the following table and check PV module electrical compati- bility at: enpha oe Innort/module-comoatihility Model DC connector Typical PV module* cell count IQ8-60-2-US MC4locking type Pair with 60 cell /120-half-cell modules IQBPLUS-72-2-US MC-4 locking type Pair with 60 cell / 120-halfcell, 66 cell, or 72 cell / 144-half-cell 18M-72-2-US IQBA-72-2-US IQ8H-240-72-2-US I081-1-208-72-2-US MCA locking type Pair with 60 cell /12D-half-cell, 66 cell, or 72 cell / 144-half-cell Enphase IQ8 Series Microinverters are compatible with bi-facial PV modules if thetemperature adjusted electrical parameters (maximum power, voltage and current) ofthe modules, considering the front side electrical parameters (i.e., 0 0 back side gain), are within the allowable rnjcroinverter input parameters range. C) In addition to the Enphase Microinverters, PV modules and racking, you will need these Enphase IQ8 Series Microinverters: Enphase IQ Gateway (model ENV-IQ-AM1-240) communications gateway or Enphase IQ Combiner (check enohase.com for models): is required to monitor solar production. Tie wraps or cable clips (Q-CLIP-100) Enphase Sealing Caps (Q-SEAL-10): for any unused connectors on the Enphase IQ Cable Enphase Terminator (Q-TERM-10): one needed at the end of each AC cable segment Enphase Disconnect Tool (Q-DISC-10) Enphase IQ Cable: Cable model ConnectorPv module spacing* orientation Connectors per box Q-12-10-240 1.3m Portrait (all) 240 Q-12-17-240 2.Om Landscape (60- and 66-celp 240 Q-12-20-200 2.3m Landscape (72-cell) 200 *Allows for 30cm of cable slack E ) Protect your system with lightning and/or surge suppression devices. It is also important to have insurance that protects against lightning and electrical surges. F) Plan your AC branch circuits to meet the following limits for maximum number of microinverters per branch when protected with a 20-amp over -current protection device (OCPD) Maximum* I08 Series Microinverters per AC branch circuit (sin- gle-phase) Q8(240V) IQ8+ (240V) IQBM (240V) 16 13 11 IQBA (240V) 108H (240V) IQBH (208V) 11 10 9 • Limits may vary. Refer to local requirements to define the number of microinverters per branch in your area. G ) Size the AC wire gauge to account for voltage rise. Select the correct wire size based on the distance from the beginning of the Enphase IQ Cable to the breaker in the load center. Design for a voltage rise total of less than 2% for these sections. Refer to the Voltage Rise Technical Brief at enphase com/support for more information. Best practice: Center -feed the branch circuit to minimize voltage rise in a fully -populated branch. DC connector \Tie wraps or cable clips 0 Enphase IQ8 Series Microinverter (horizontal installation shown, vertical installation also allowed). AC junction box Terminator Enphase I�Calle �AC connector 0 2021 Enphase Energy. All rights reserved. Enphase,the Enphase logo, Enphase IQ8 Series microinverters (IQ8, IQ8+, IQBA, IQBH and IQSM ), Enphase Installer Platform Enphase IQ Gateway, and other trademarks or service names are thetrademarks of Enphase Energy, Inc. Data subject to change. Re%02-10-23-2021 III IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII III III 140-00195-02 CONTRACTOR Northwest Electric and Solar Address: 18001 73rd Ave NE Kenmore WA 98028 Phone number: 206-356-0601 Appointments: nwsolar.com Northwest Solar ENPHASE RAPID SHUTDOWN, COMPATIBILITY WITH PV ENGINEEr-4INC Drawn by: New@engineerinc.io DATE: 0212812023 Project Name: 7215 - Drown Property Adres 1046 3rd Ave S, Edmonds, WA 98020 Project: Scale: PV SYSTEM AS INDICATED D 7.0 rW REC ALPHOC e PU BLACK SERIES PRODUCT SPECIFICATIONS �nr�r�l 400WPREC 251 YEAR NoTRLb7 �J WARRANTY ZO.3 �T` LEAD-FREE CI Ir IDI C cnLJC rnNADI IDNIT =_=nDf REC 50LAR5 MOST TRUSTED 3011.21 Measurements in mm (NI T GENERALDATA 132hatFtutRECheterqunctionrells St5ubiMC4PV-KBT4/KST4.12AWG(4mm') Cell type: with lead-free,gaplesstechnology Connectors: inaccordancewith IEC 62852 6 stringsof22cells inseries IP68onlywhenconnected ..................................................................................................................-............................................. ................. ..................................... _....... Glass: 0.13 in(3.2 mm) solar glass with Cable 12AWG(4mm2)PVwire,43+47in(L1+12r4 anti -reflection surface treatment a-dancewlth EN50518 Backsheet: Highly resistant polymer (black) Dimensions: 71.7x40x1.2in(1821x1016x30mm) ............................ _............................................ _..................................'...........8...... Frame: Anodized aluminum black ...... Weight: _........ _....._..................................... ...........................g' _ 45lbs 20.5k ........................... _............................................................ -.......... _........... Junction box: 3-part, 3 bypass diodes. IP67 rated .................. ................... Origin; ............ ................ ..................... _........................ _ Madein5ingapore Inaccardancewith IEC62790 ELECTRICAL DATA Product Code': RECxxxAA Pure Black PowerOutPut-P (W) _....... _......... atx._..Q.._.._......_._..._...._....._._..._._. 385 390 .................._.__..._.I.._._. 395 400 ........ . 405 Watt Class Sorting-(W) 0/+5 0/+5 0/+5 0/+5 ...__._........_._... 0/+5 _................_................._.........._.I._......._. _....._.....-.._-__ Nominal Power Voltage-V.(V) ........................_.... 412 41.5 __ 41.8 421 _ . 42.4 ................._.._........._.__............_...._._.._...._............... u Nominal Power Current. I..(A) ..._....._..._.. 935 ............. 9.40 ............. .... ............... 9.45 I ........ .... 9.51 ................ 9.56 ...._._..._...__...._._ ..... N Open Circuit Voltage- V. ........_........................... 48.5 48.6 _... _...... .......... 48.7 ..... _._................ 48.8 ................ _ 48.9 _............................_..............._........._........._._____._......_..._._...__....._....._......._........................................_..........._.........._ Short Circuit Current- Iu (A) 9 99 10.03 10.07 1030 10.14 ...............................................................__._....:...... Power Der ity(W/sgft) .......__............................................_.........._._.................._...... 19.3 19.6 19.8 20.1 20.3 _...................................................... __......... __..._............._........ Panel Efficiency(%) ...... _.......... _.......................................................... 20.8 21.1 21.3 _..._.........._. 21.6 _......_....._ 21.9 Power Output-P.x(Wp) ..........._ 293 297 301 305 309 ..........................................................._....._......,............................_.................................._....,....................._........._..,............._.._.. F Nominal Power Voltage-V.....V) 38.8 39.1 39.4 39.7 40.0 NomIna IPower Current-I_(A) 7.55 7.59 7.63 7.68 7.72 Z_............. ..................................... ........ _.............. __.._...... ....... .._....__._......_.._..._._..............._._._.__...._.._................_......._..............._ Open Circuit Voltage -Vo,(V) ..........................................................._....................._... Shot tCircuitCurrent -1,(A) .45:_...............45:8................45.9.................46.0................46.1.. 8.07 8.10 8.13 8.16 8.19 Values at standard test a witio s(STC airman AM15. inadlarxe 10.75 W/sgft 0000 Wlej ternperature7TF(25°CI based on aproduKtbn spread with a tolwarxeof P,v,,,, Va&kci3ea within orue wan class Nornnual mudulewera ftterTeratue(NMOT: air mass AM15, inadianre 8WWftn ,terrperature6TF(20'Clwhdspeed 33ft/s0m/sl'Where= indicates thenominal power dass(Pr,j at STCabove. 4L CERTIFICATIONS IEC 6121S:2016. IEC 61730:2016, UL 61730 (Pend ing) 150140012004, ISO9001:2015, OHSAS 18001:2007. IEC 62941 4=8\�-CEa I� rj- WARRANTY _ Stardardi RECProTrust InstalledbyanRECCertified Solar Professional No € Yes Yes System5ize All i _ 125kW 25-SOOkW Product Warranty (yrs) 20 25 25 Power Warranty(yrs) 25 �25 25 _ Labor Warranty (yrs) 0 25 10 PowerinYear l 98% 98% 98% Annua I Degradation 0.25% € 0.25% 0.25% Power in Year25 92% ) 92% 92% Seewarranty documents for detalls.Conditions apply MAXIMUM RATINGS Operation l temperature -40...+185'F(-40...+85'C) ............. ..................... ........................... _... _......... Maximum system voltage: 1000V ................................................. _.......... _..... ........... _.._................... __._.......... Maximum test load (front): -7000Pa046Ibs/,sgft)* ...................................................._._................__............................................. Maximum test load (rear): -4000Pa(83.5lbs/sgft)' ....................................................................................................... .............- Maxseries fuse rating: 25 A .......................................................................................... . .............................. Maxreversecurrent: 25A - 'Seelnstallatlon manual for mountinginstructions. Designload•Test load/ 1.5(safety factor) lo 3 ao TEMPERATURE RAT INGS- Nominal Module Operating Temperature: 44'C(t2'C) a .... ..................................................................... __........._._............_......_..... Temperature coefficient of Pm_: -0.26%/'C ._........................................................._..._...._..._...._..._ _ ............... _... Temperature -0.24% C P i oc Temperature coefficient of Ise 0.04%/'C wu The temperaturecoefficlents stated are linear values LOW LIGHT BEHAVIOUR Typical low irradiance performance ofmodule at STC: - re F Inadance (w/mr) Founded in 1996. REC Group is an international pioneering solar energy company dedicated to empowering consumers with clean, affordable solar power. As Solar's Most Trusted, REC is committed to high quality, Innovation, and a low carbon footprint in the solar materials and solar panels it manufactures. Headquartered in Norway with operational headquarters in Singapore. REC also has regional hubs in NorthAmerica, Europe, and Asia -Pacific. CONTRACTOR Northwest Electric and Solar Address: 18001 73rd Ave NE Kenmore WA 98028 Phone number: 206-356-0601 Appointments: nwsolar.com MODULE DATA SHEET CNGINCCZINC Drawn by: New@engineerinc.io DATE: 02/28/2023 REC Project Name 7215 - Drown wwwrecigroupcnu`. O O property Adress: 1046 3rd Ave S, Or Edmonds, WA 98020 Project: Scale: PV SYSTEM AS INDICATED IRONRIDGE Built for solar's toughest roofs Datasheet Flush Mount System IronRidge builds the strongest mounting system for pitched roofs in solar. Every component has been tested to the limit and proven in extreme environments. Our rigorous approach has led to unique structural features, such as curved rails and reinforced flashings, and is also why our products are fully certified, code compliant and backed by a 25-year warranty. Strength Tested All components evaluated for superior structural performance. Class A Fire Rating Certified to maintain the fire resistance rating of the existing roof. PE Certified Pre -stamped engineering letters available in most states. Design Assistant Online software makes it simple to create, share, and price projects. - XR Rails 8 XR10 Rail i A low -profile mounting rail for regions with light snow. • 6'spanning capability • Moderate load capability • Clear and black finish XR100 Rail The ultimate residential solar mounting rail. • 8' spanning capability • Heavy load capability • Clear and black finish Clamps & Grounding e - UFOs Stopper Sleeves .IL --a. Universal Fastening Objects bond modules to rails. • Fully assembled & lubed • Single, universal size • Clear and black finish Attachments S FlashFoot2 Snap onto the UFO to turn into a bonded end clamp. • Bonds modules to rails • Sized to match modules • Clear and black finish Conduit Mount XR1000 Rail A heavyweight mounting rail for commercial projects. • 12' spanning capability • Extreme load capability • Clear anodized finish CAMO Bond modules to rails while staying completely hidden. • Universal end -cam clamp • Tookless installation • Fully assembled Slotted L-Feet 8 -1, V_ I -- Flash and mount XR Rails with superior waterproofing. • Twist -on Cap eases install • Wind -driven rain tested • Mill and black finish — Resources - Flash and mount conduit, strut, or junction boxes. • Twist -on Cap eases install • Wind -driven rain tested • Secures 3/a" or 1"conduit Drop -in design for rapid rail attachment. • Secure rail connections • Slot for vertical adjusting • Clear and black finish Datasheet Bonded Splices All rails use internal splices for seamless connections. • Self -drilling screws • Varying versions for rails • Forms secure bonding Grounding Lugs Connect arrays to equipment ground. • Low profile • Single tool installation • Mounts in any direction Bonding Hardware Bond and attach XR Rails to roof attachments. • T & Square Bolt options • Nut uses 7/16" socket • Assembled and lubricated Design Assistant •�4 NABCEP Certified Training UL 2703 Listed System 25-Year Warranty Go from rough layout to fully INAP Earn free continuing education credits, Entire system and components meet Products guaranteed to be free engineered system. For free. while learning more about our systems. 1. newest effective UL 2703 standard. of impairing defects. Go to IronRidge.com/design Go to Iron Ridge.com/training i -a O 2019 Iron Ridge. Inc. AN rights reserved. U.B. Patents: #8,895.290: #9.819,303: #9,885,93& others Penring. version 1.70 r� CONTRACTOR Northwest Electric and Solar Address: 18001 73rd Ave NE Kenmore WA 98028 Phone number: 206-356-0601 Appointments: nwsolar.com SolarNorthwest Electric RACKING DATA SHEET CNGINCCZINC Drawn by: New@engineerinc.io DATE: 0212812023 Project Name: 7215 - Drown Property Actress: 1046 3rd Ave S, Edmonds, WA 98020 Project: Scale: PV SYSTEM I AS INDICATED D 9.0 Data Sheet Enphase Networking Enphase IQ Combiner 4/4C X-IQ-AM1-240-4 X-IQ-AM1-240-4C f_ X-I( U�, X•IQ-AM7-240.4 s — LISTED To learn more about Enphase offerings, visit enohase.com -'ENPHASE The Enphase IQ Combiner 4/4C with Enphase IQ Gateway and integrated LTE-M1 cell modem (included only with IQ Combiner 4C) consolidates interconnection equipment into a single enclosure and streamlines IQ microinverters and storage installations by providing a consistent, pre -wired solution for residential applications. It offers up to four 2-pole input circuits and Eaton BR series busbar assembly. Smart Includes IQ Gateway for communication and control • Includes Enphase Mobile Connect cellular modem (CELLMODEM-M1-06-SP-05), included only with IQ Combiner4C • Includes solar shield to match Enphase IQ Battery aesthetics and deflect heat • Flexible networking supports WI-Fi, Ethernet, or cellular • Optional AC receptacle available for PLC bridge Provides production metering and consumption monitoring Simple • Centered mounting brackets support single stud mounting • Supports bottom, back and side conduit entry Up to four 2-pole branch circuits for 240 VAC plug-in breakers (not included) • BOA total PV or storage branch circuits Reliable • Durable NRTL-certified NEMA type 3R enclosure Five-year limited warranty Two years labor reimbursement program coverage included for both the IQ Combiner SKU's • UL listed ENPHASE Enphase IQ Combiner 4/4C MODEL NUMBER IQCombiner 4 (X-IQ-AM1-240-4) IQ Combiner 4 with Enphase IQ Gateway printed circuit board for integrated revenue grade PV production metering (ANSI C1220+/- 0.5%) and consumption monitoring (+/- 25%). Includes a silver solar shield to matchthe IQ Battery system and IQ System Controller 2 and to deflect heat. IQ Combiner 4C (X-IQ-AMI-240-4C) IQ Combiner 4C with Enphase IQ Gateway printed circuit board for integrated revenue grade PV production metering (ANSI C12.20+/- 0.5%) and consumption monitoring (+1- 2.5%). Includes Enphase Mobile Connect cellular modem (CELLMODEM-Ml-06-SP-05), a plug -and -play industrial -grade cell modem for systems upto 60 microlnverters. (Available In the US, Canada, Mexico, Puerto Rico, and the US Virgin Islands, where there is adequate cellular service in the installation area.) Includes a silver solar shield to match the IQ Battery and IQ System Controller and to deflect heat. ACCESSORIES AND REPLACEMENT PARTS (not included, order separately) Ensemble Communications Kit Includes COMMS-KIT-01 and CELLMODEM-M7-06-SP-05 with 5-year Sprint data plan for COMMS-CELLMODEM-Ml-06 Ensemble sites CELLMODEM-M1-06-SP-05 4G based LTE-Ml cellular modem with 5-year Sprint data plan CELLMODEM-MI-06-AT-05 4G based LTE-Ml cellular modem with 5-year AT&T data plan Circuit Breakers Supports Eaton BR210, BR215, BR220, BR230, BR240, BR250, and BR260 circuit breakers. BRK-10A-2-240V Circuit breaker, 2 pole,10A, Eaton BR210 BRK-15A-2-240V Circuit breaker, 2 pole,l5A, Eaton BR215 BRK-20A-2P-240V Circuit breaker, 2 pole, 20A, Eaton BR220 BRK-15A-2P-240V-B Circuit breaker, 2 pole, l SA, Eaton BR2158 with hold down kit support BRK-20A-2P-24OV-B Circuit breaker, 2 pole, 20A, Eaton BR220B with hold down kit support EPLC-01 Power line carrier (communication bridge pair), quantity- one pair XA-SOLARSHIELD-ES Replacement solar shield for IQ Combiner 4/4C XA-PLUG-120-3 Accessory receptacle for Power Line Carrier in IQ Combiner 4/4C (required for EPLC-01) XA-ENV-PCBA-3 Replacement IQ Gateway printed circuit board (PCB) for Combiner 4/4C X-I Q-NA-HD-125A Hold down kit for Eaton circuit breaker with screws ELECTRICAL SPECIFICATIONS System voltage Eaton BR series busbar rating Max. continuous current rating Max. continuous current rating prput from PV/storage) Max. fuse/circuit rating (output) Branch circuits (solar and/or storage) Max, total branch circuit breaker rating (input) Production metering CT Continuous duty 120/240 VAC, 60 Hz 125A 65 A 64 A 90 A Up to four 2-pole Eaton BR series Distributed Generation (DG) breakers only (not included) 80A of distributed generation / 95A with IQ Gateway breaker included 200 A solid core pre -installed and wired to IQ Gateway Consumption monitoring CT (CT-200-SPLIT) A pair of 200 A split core current transformers MECHANICAL DATA Dimensions (WxHxD) 37.5 x 49.5 x 16.8 cm (14.75' x 19.5' x 6.63•). Height is 21.06• (53.5 cm) with mounting brackets. Weight 7.5 kg (16.5 Ibs) Ambient temperature range -400 C to+46° C (400 to 115' F) Cooling Natural convection, plus heat shield Enclosure environmental rating Outdoor, NRTL-certified NEMA type 3R, polycarbonate construction Wire sizes 20 A to 50 A breaker inputs:14 to 4 AWG copper conductors 60 A breaker branch input: 4 to 110 AWG copper conductors • Main lug combined output: 10 to 2/OAWG copper conductors Neutral and ground: 14 to 1/0 copper conductors Always follow local code requirements for conductor sizing. Altitude To 20DO meters (6,560 feet) INTERNET CONNECTION OPTIONS Integrated Wf FI 802.11b/g/n Cellular CELLMODEM-MI-06-SP-05, CELLMODEM-M1-06-AT-05 (4G based LTE-Ml cellular modem). Note that an Enphase Mobile Connect cellular modem is required for all Ensemble installations. Ethernet Optional, 802.3. Cat5E (or Cat 6) UTP Ethernet cable (not Included) COMPLIANCE Compliance, IQ Combiner UL 1741, CAN/CSA C22.2 No.107.1, 47 CFR, Part 15, Class B, ICES 003 Production metering: ANSI C12.20 accuracy class 0.5 (PV production) Consumption metering: accuracy class 2.5 Compliance, IQ Gateway UL 60601-1/CANCSA 22.2 No. 61010-1 To learn more about Enphase offerings, visit enohase.com u ENPHASE. Q 2021 Enphase Energy All rights reserved. Enphase, the Enphase logo, 10 Combiner 4/4C, and other names are trademarks of Enphase Energy, Inc. Data subject to change. 10-21-2021 CONTRACTOR Northwest Electric and Solar Address: 18001 73rd Ave NE Kenmore WA 98028 Phone number: 206-356-0601 Appointments: nwsolar.com Northwest Solar ENPHASE IQ COMBINER DATASHEET CNGINCCZINC Drawn by: New@engineerinc.io DATE: 0212812023 Project Name: 7215 - Drown Property Adress: 1046 3rd Ave S, Edmonds, WA 98020 Project: scale: PV SYSTEM AS INDICATED FD_1 1.0