REV 2 ARW - Hyundai Sales Addition Edmonds WA - 2020.03.18c� CD N 0 N co co STRUCTURAL NOTES: A. GENERAL 1. THE STRUCTURAL NOTES ARE INTENDED TO COMPLEMENT THE PROJECT SPECIFICATIONS WHICH ARE PART OF THE CONSTRUCTION DOCUMENTS. SPECIFIC NOTES AND DETAILS ON THE DRAWINGS SHALL GOVERN OVER THE STRUCTURAL NOTES AND TYPICAL DETAILS. 2. THESE DRAWINGS (AND, WHERE APPLICABLE, ACCOMPANYING WRITTEN SPECIFICATIONS)ARE THE ONLY CONTRACT DOCUMENTS PROVIDED BY ARW ENGINEERS FOR THE PROJECT REPRESENTED HEREIN. NOTHING IN ANY DIGITAL MODEL OR DIGITAL FILE RELATED TO THIS PROJECT SHALL BE TAKEN TO SUPERSEDE ANY INFORMATION SHOWN IN THESE DRAWINGS (INCLUDING, BUT NOT LIMITED TO, DIMENSIONS, SIZES, ETC). 3. THE ARCHITECTURAL DRAWINGS ARE THE PRIME CONTRACT DRAWINGS. THE STRUCTURAL DRAWINGS ARE SUPPLEMENTARY TO AND MUST BE USED IN CONJUNCTION WITH THE ARCHITECTURAL DRAWINGS AND OTHER CONSULTANTS DRAWINGS. ALL OMISSIONS OR CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF THE WORKING DRAWINGS AND/OR SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND STRUCTURAL ENGINEER BEFORE PROCEEDING WITH ANY WORK INVOLVED. IN CASE OF CONFLICT, FOLLOW THE MOST STRINGENT REQUIREMENT AS DIRECTED BY THE ARCHITECT AT NO ADDITIONAL COST TO THE OWNER. 4. SEE SPECIFICATIONS FOR REQUIRED SUBMITTALS. SUBMITTALS SHALL BE MADE IN A TIMELY MANNER AS INDICATED IN SPECIFICATIONS. REVIEW OF SUBMITTALS BY ARW ENGINEERS IS FOR GENERAL COMPLIANCE ONLY AND IS NOT INTENDED AS APPROVAL. CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL SIZES, DIMENSIONS, AND ELEVATIONS ON SUBMITTALS AS RELATED TO DESIGN DOCUMENTS. PREPARATION OF SHOP DRAWINGS FOR STRUCTURAL ELEMENTS WILL REQUIRE INFORMATION (I.E. DIMENSIONS, ETC.) FOUND IN THE ARCHITECTURAL, STRUCTURAL, AND OTHER CONSULTANTS DRAWINGS. 5. THE CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AT THE SITE. IF ACTUAL CONDITIONS DIFFER FROM THOSE SHOWN ON CONTRACT DOCUMENTS, CONTRACTOR SHALL NOTIFY ARCHITECT PRIOR TO FABRICATION OR CONSTRUCTION OF ANY AFFECTED ELEMENTS. 6. THE CONTRACTOR SHALL COORDINATE AND VERIFY ALL LOCATIONS AND SIZES OF MECHANICAL EQUIPMENT OR OTHER EQUIPMENT BEFORE FABRICATING AND ERECTING STRUCTURAL ELEMENTS. SIZES AND LOCATIONS THAT DIFFER FROM THOSE SHOWN ON THE CONTRACT DOCUMENTS SHALL BE REPORTED TO THE ARCHITECT. 7. THE CONTRACTOR SHALL SUBMIT A WRITTEN REQUEST TO THE ARCHITECT FOR ARCHITECT AND/OR ENGINEER APPROVAL BEFORE PROCEEDING WITH ANY CHANGES, MODIFICATIONS, OR SUBSTITUTIONS. 8. OBSERVATION VISITS TO THE SITE BY ARW ENGINEERS FIELD REPRESENTATIVES SHALL NEITHER BE CONSTRUED AS INSPECTION NOR APPROVAL OF CONSTRUCTION. 9. DURING AND AFTER CONSTRUCTION, BUILDER AND/OR OWNER SHALL KEEP LOADS ON STRUCTURE WITHIN THE LIMITS OF DESIGN LOADS AS NOTED IN THESE DOCUMENTS. 10. TYPICAL OR SIMILAR DETAILS AND SECTIONS SHALL APPLY WHERE SPECIFIC DETAILS ARE NOT SHOWN. TYPICAL OR SIMILAR DETAILS REFER TO THE CONDITION ADDRESSED AND ARE NOT NECESSARILY DETAILS LABELED "TYPICAL" OR "SIMILAR" IN THE PLANS AND DOCUMENTS. 11. DRAWINGS AND DETAILS HAVE BEEN PREPARED WITH THE INTENT TO VISUALLY REPRESENT INFORMATION PROVIDED IN SCALED FORM; HOWEVER CONTRACTOR/SUPPLIERS SHOULD NOT SCALE PLANS OR DETAILS FOR DIMENSIONAL INFORMATION. 12. THE CONTRACTOR SHALL PROVIDE ADEQUATE TEMPORARY SHORING AND BRACING FOR ALL STRUCTURAL ELEMENTS UNTIL THE ENTIRE STRUCTURAL SYSTEM IS COMPLETED. DESIGN OF ALL SHORING AND BRACING IS BY OTHERS AT NO ADDITIONAL COST TO THE OWNER. 13. ENGINEER SHALL NOT BE RESPONSIBLE FOR ACTIVITIES UNDER CONTROL OF THE CONTRACTOR SUCH AS CONSTRUCTION SITE SAFETY, MEANS, METHODS AND SEQUENCING OF CONSTRUCTION. ENGINEER SHALL NOT BE RESPONSIBLE FOR FABRICATION, ERECTION AND CONSTRUCTION REQUIREMENTS AS PRESCRIBED BY OSHA OR OTHER REGULATORY AGENCIES REGARDLESS OF INDICATIONS IN THESE DOCUMENTS. 14. NOTICE OF COPYRIGHT: THESE STRUCTURAL DRAWINGS ARE HEREBY COPYRIGHTED BY ARW ENGINEERS, ALL RIGHTS RESERVED. THESE DOCUMENTS DEFINE A STRUCTURE AND ARE INSTRUMENTS OF SERVICE, FOR ONE USE ONLY. REPRODUCTION AND DISTRIBUTION OF THESE DRAWINGS IS ONLY ALLOWED AS REQUIRED FOR REGULATORY AGENCIES AND FOR CONVEYANCE OF INFORMATION TO PARTIES INVOLVED IN THE CONSTRUCTION OF THIS PROJECT. THESE DOCUMENTS SHALL NOT BE REPRODUCED OR COPIED, IN PART OR WHOLE BY ANY PARTY FOR USE IN PREPARATION OF SHOP DRAWINGS OR OTHER SUBMITTALS. B. STATEMENT OF SPECIAL INSPECTIONS AND SPECIAL INSPECTIONS 1. THE DESIGNATED SEISMIC/WIND SYSTEMS AND SEISMIC/WIND-FORCE-RESISTING SYSTEMS THAT ARE SUBJECT TO SPECIAL INSPECTIONS IN ACCORDANCE WITH IBC SECTION 1705.11 AND 1705.12 ARE IDENTIFIED ON THESE DOCUMENTS WITH A CIRCLE "L". ALL OTHER ITEMS REQUIRING SPECIAL INSPECTION ARE IDENTIFIED IN THE SPECIAL INSPECTION SCHEDULE ON SHEET S006. 2. SPECIAL INSPECTIONS AND TESTING ARE TO BE PROVIDED AS REQUIRED BY IBC SECTIONS 1704 THROUGH 1705 AND OTHER APPLICABLE SECTIONS OF THE IBC. THE TYPE AND FREQUENCY OF TESTING AND SPECIAL INSPECTIONS SHALL BE AS NOTED IN THE SPECIAL INSPECTION SCHEDULE, JOB SPECIFICATIONS, AND ACCORDANCE WITH IBC SECTION 110 AND CHAPTER 17. CONTRACTOR SHALL COORDINATE AND COOPERATE WITH REQUIRED INSPECTIONS. 3. ALL TESTING AND SPECIAL INSPECTION SHALL BE PROVIDED BY A QUALIFIED INDEPENDENT SPECIAL INSPECTION AGENCY IN ACCORDANCE WITH IBC 1704 AND AS OUTLINED IN THE JOB SPECIFICATIONS. REPORTS OF FINDINGS OR DISCREPANCIES SHALL BE NOTED AND FORWARDED TO THE CONTRACTOR, ARCHITECT, ENGINEERS, AND BUILDING OFFICIAL IN A TIMELY MANNER. 4. STRUCTURAL OBSERVATION VISITS SHALL BE PERFORMED BY A REPRESENTATIVE FROM ARW ENGINEERS IN ACCORDANCE WITH THE CONTRACT AS NEEDED TO OBSERVE THE CONSTRUCTION OF CRITICAL BUILDING ELEMENTS (I.E. FOOTINGS, BRACED FRAMES, MOMENT FRAMES, DRAG STRUTS AND THEIR CONNECTIONS, COLLECTORS, AND ROOF AND FLOOR DIAPHRAGMS). STRUCTURAL OBSERVATION REPORTS FOR EACH VISIT SHALL BE SENT DIRECTLY TO THE ARCHITECT FOR DISTRIBUTION TO THE CONTRACTOR AND BUILDING OFFICIAL. STRUCTURAL OBSERVATION VISITS SHALL NEITHER BE CONSTRUED AS SPECIAL INSPECTION NOR APPROVAL OF COMPLETED CONSTRUCTION. 5. IN ACCORDANCE WITH IBC 1704.4, THE CONTRACTOR SHALL SUBMIT A WRITTEN CONTRACTOR'S STATEMENT OF RESPONSIBILITY TO THE BUILDING OFFICIAL AND OWNER. THE STATEMENT SHALL BE SUBMITTED PRIOR TO THE CONSTRUCTION OF ANY SEISMIC/WIND-FORCE-RESISTING SYSTEM, DESIGNATED SEISMIC/WIND SYSTEM, OR COMPONENT IDENTIFIED IN THESE DOCUMENTS WITH A CIRCLE °L". C. BASIS OF DESIGN 1. GOVERNING BUILDING CODE : INTERNATIONAL BUILDING CODE (IBC) 2015 RISK CATEGORY : II 2. ROOF LOADS a. FLAT -ROOF SNOW LOAD, Pf: 25 PSF 1. GROUND SNOW LOAD, Pg-. 25 PSF 2. SNOW EXPOSURE FACTOR, Ce: 1.0 3. SNOW LOAD IMPORTANCE FACTOR, Is: 1.0 4. THERMAL FACTOR, Cc: 1.0 b. LIVE LOAD = 20 PSF c. DEAD LOAD = 15 PSF 3. WIND DESIGN a. BASIC WIND SPEED (3 SECOND GUST)-. 11O MPH b. WIND EXPOSURE : C c. COMPONENT AND CLADDING DESIGN WIND PRESSURE SHALL BE AS REQUIRED PER ASCE 7-10. 4. SEISMIC DESIGN : a. SEISMIC IMPORTANCE FACTOR, IE: 1.0 b. SITE CLASS: D c. MAPPED SPECTRAL RESPONSE ACCELERATIONS : Ss = 1.266 , S1 = 0.494 d. SPECTRAL RESPONSE COEFFICIENTS : SDs = 0.844 , SD1 = 0.496 e. SEISMIC DESIGN CATEGORY : D f. BASIC SEISMIC -FORCE -RESISTING SYSTEM : STEEL ORDINARY MOMENT FRAME (N-S); SPECIAL REINFORCED CONCRETE SHEAR WALLS (E-W); COLD FORMED STEEL WALL WITH WOOD SHEATHING (CARPORT N-S) g. DESIGN BASE SHEAR : VN-s = Cs W , VE-W = Cs W h. SEISMIC RESPONSE COEFFICIENT, Cs: 0.24 (OMF); 0.17 (SRCSW); 0.12 (CARPORT N-S) i. RESPONSE MODIFICATION FACTOR, R : 3.5 (OMF); 5.0 (SRCSW); 7.0 (COLD FORM) j. ANALYSIS PROCEDURE : EQUIVALENT LATERAL FORCE D. FOUNDATION 1. DESIGN SOIL PRESSURE : 4000 PSF 2. SOILS REPORT BY : GOLDER ASSOCIATES REPORT # : 1533298 DATED : JUNE 23, 2017 3. SOIL PREPARATION UNDER FOOTINGS AND SLABS -ON -GRADE SHALL BE IN ACCORDANCE WITH THE SOILS REPORT. 4. TOP OF FOOTING ELEVATIONS SHOWN ON THE FOOTING AND FOUNDATION PLAN ARE BASED ON PRELIMINARY GRADING INFORMATION AND MUST BE VERIFIED PRIOR TO CONSTRUCTION. STEPS WHERE SHOWN ARE AT APPROXIMATE LOCATIONS. ALL EXTERIOR FOOTINGS MUST BEAR A MINIMUM OF 24 INCHES BELOW LOWEST ADJACENT FINAL GRADE. 5. ALL WALLS (EXCEPT CANTILEVERED RETAINING WALLS) SHALL BE ADEQUATELY BRACED AGAINST LATERAL MOVEMENT PRIOR TO BACKFILLING. DESIGN AND ERECTION OF BRACING/SHORING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. BRACING SHALL REMAIN IN PLACE UNTIL SUPPORTING STRUCTURAL ELEMENTS ARE IN PLACE AND HAVE ATTAINED FULL STRENGTH. 6. UNLESS NOTED OTHERWISE, ALL FOOTINGS AT COLUMNS TO BE CENTERED BELOW COLUMNS. 7. UNLESS NOTED OTHERWISE, ALL FOOTINGS SHALL HAVE VERTICAL FACES FORMED WITH STANDARD FORMING MATERIALS (WOOD, METAL, ETC.). WITH PRIOR APPROVAL OF ARCHITECT AND ENGINEER, CONCRETE FOR FOOTINGS CAN BE PLACED IN EXCAVATED "SOIL" FORMS PROVIDED THAT THE DIMENSIONS ARE INCREASED 3" ON EACH SIDE. E. CONCRETE 1. ALL CONCRETE MIX DESIGNS SHALL COMPLY WITH THE PROJECT SPECIFICATIONS AND THE REQUIREMENTS LISTED BELOW : a. FOOTINGS, GRADE BEAMS, FOUNDATION WALLS 1. WHERE THE TOP OF THE ELEMENT IS EXPOSED OR IS LOCATED WITHIN 30" OF THE LOWEST ADJACENT GRADE (EXPOSURE CATEGORY F1) : a. 28 DAY COMPRESSIVE STRENGTH : 4500 PSI b. MAXIMUM W/C RATIO: 0.45 c. MAXIMUM AGGREGATE SIZE : 1" d. AIR CONTENT: 4.5% +/- 1.5% 2. WHERE THE TOP OF THE ELEMENT IS NOT EXPOSED OR IS NOT LOCATED WITHIN 30" OF THE LOWEST ADJACENT GRADE (EXPOSURE CATEGORY FO) a. 28 DAY COMPRESSIVE STRENGTH : 3000 PSI b. RETAINING WALLS (EXPOSURE CATGEORY F1) : 1. 28 DAY COMPRESSIVE STRENGTH : 4500 PSI 2. MAXIMUM W/C RATIO : 0.45 3. MAXIMUM AGGREGATE SIZE : 1" 4. AIR CONTENT: 4.5% +/- 1.5% c. INTERIOR SLABS ON GRADE (EXPOSURE CATEGORY FO) 1. 28 DAY COMPRESSIVE STRENGTH : 3000 PSI d. EXTERIOR SLABS (DOCKS, ETC.) (EXPOSURE CATEGORY F1) : 1. 28 DAY COMPRESSIVE STRENGTH : 4500 PSI 2. MAXIMUM W/C RATIO : 0.45 3. MAXIMUM AGGREGATE SIZE : 1" 4. MINIMUM AIR CONTENT: 4.5% +/- 1.5% 2. WATER USED IN MIXING CONCRETE SHALL CONFORM TO ASTM C1602. 3. NO PIPES, DUCTS, SLEEVES, ETC. SHALL BE PLACED IN STRUCTURAL CONCRETE UNLESS SPECIFICALLY DETAILED OR APPROVED BY THE STRUCTURAL ENGINEER. NO ALUMINUM PRODUCTS SHALL BE EMBEDDED IN CONCRETE. PENETRATIONS THRU STRUCTURAL CONCRETE ELEMENTS MUST BE APPROVED BY THE ENGINEER AND SHALL BE BUILT INTO THE ELEMENT PRIOR TO CONCRETE PLACEMENT. 4. REFER TO ARCHITECTURAL DRAWINGS FOR MOLDS, GROOVES, ORNAMENTS, ETC. TO BE CAST IN TO CONCRETE, AND FOR EXTENT AND LOCATION OF DEPRESSIONS, CURBS, RAMPS, ETC. 5. UNLESS NOTED OTHERWISE, MINIMUM REINFORCING IN ALL CONCRETE FOUNDATION WALLS SHALL BE AS FOLLOWS: TOP & THICKNESS BOTTOM BARS VERTICAL HORIZONTAL 8" (2) #5 #4 AT 18"O.C. #4 AT 12"O.C. 6. UNLESS NOTED OTHERWISE, CONCRETE SLABS ON EARTH SHALL BE REINFORCED AS FOLLOWS: 6" THICK - #4 AT 18"O.C. EACH WAY REINFORCING SHALL BE CONTINUOUSLY SUPPORTED AT 36"O.C. MAXIMUM SPACING. 7. UNLESS NOTED OTHERWISE, FOR NON -DETAILED OPENINGS IN CONCRETE WALLS LARGER THAN 12" AND SMALLER THAN 24" IN ANY DIRECTION ADD (2) #5 BARS ON ALL SIDES IN ADDITION TO REGULAR WALL REINFORCING AND EXTEND 24" EACH WAY BEYOND OPENING. IF 24" IS NOT AVAILABLE ON EVERY SIDE, NOTIFY STRUCTURAL ENGINEER FOR FURTHER DIRECTION. OPENINGS SHALL HAVE A MINIMUM OF 12" OF CONCRET ABOVE THE OPENING, TYP. 8. CONSTRUCTION JOINTS NOT SHOWN ON THE PLANS SHALL BE MADE AND LOCATED SO AS TO NOT IMPAIR THE STRENGTH OF THE STRUCTURE AND AS APPROVED BY THE STRUCTURAL ENGINEER. PROVIDE 2 X 4 (SHAPED) KEYWAY IN ALL VERTICAL AND HORIZONTAL JOINTS UNLESS NOTED OR DETAILED OTHERWISE. ALL STEEL REINFORCING SHALL BE CONTINUOUS THROUGH COLD JOINTS UNLESS NOTED OTHERWISE. SEE TYPICAL DETAILS FOR COLD/CONSTRUCTION JOINTS FOR SLABS ON GRADE. 9. WHERE NEW CONCRETE IS PLACED AGAINST PREVIOUSLY HARDENED CONCRETE, THE JOINT SHALL BE CLEAN AND FREE OF LAITANCE. IMMEDIATELY BEFORE NEW CONCRETE IS PLACED, CONSTRUCTION JOINTS SHALL BE PREWETTED AND STANDING WATER REMOVED. WHERE NOTED IN SPECIFIC DETAILS, HARDENED CONCRETE SHALL BE ROUGHENED TO 1/4" AMPLITUDE AND A BONDING AGENT SHALL BE APPLIED TO THE JOINT PRIOR TO PLACING NEW CONCRETE. F. ANCHOR BOLTS/EMBEDDED BOLTS 1. ALL ANCHOR BOLTS SHALL HAVE ASTM A-563 HEAVY HEX NUT AND ASTM F-436 WASHERS AT STANDARD OR OVERSIZED HOLES PER AISC SPECIFICATION TABLE J3.3. WHERE HOLE SIZES DO NOT COMPLY WITH THE LIMITATIONS FOR OVERSIZED HOLES THE STRUCTURAL ENGINEER SHALL BE NOTIFIED TO DETERMINE STEEL PLATE WASHER REQUIREMENTS. ANCHOR BOLTS SHALL COMPLY WITH THE FOLLOWING : a. AT MOMENT RESISTING FRAMES - ASTM F1554 GRADE 105 HEADED BOLTS.(ASTM A449 THREADED ROD MAY BE USED WITH DOUBLE NUT AND WASHER.) b. AT ALL OTHER ANCHOR BOLTS (UNLESS NOTED OTHERWISE) - ASTM F1554 GRADE 36 HEADED BOLTS. (ASTM A36 THREADED ROD MAY BE USED WITH DOUBLE NUT AND WASHER.) 2. SEE TYPICAL ANCHOR BOLT DETAIL FOR DEFINITIONS OF EMBEDMENT LENGTH, ETC. 3. FURNISH TEMPLATES AND OTHER DEVICES AS NECESSARY FOR PRESETTING ALL BOLTS PRIOR TO PLACING CONCRETE AND/OR GROUT. 4. IF THREADED RODS ARE USED AS PERMITTED ABOVE, THEY SHALL BE CLEAR OF SOIL AND DIRT. 5. WHERE REQUIRED FOR ERECTION, HOLES LARGER THAN OVERSIZED MAY BE PERMITTED WITH THE USE OF STEEL PLATE WASHERS AT THE DISCRETION OF THE STRUCTURAL ENGINEER. G. ADHESIVE/MECHANICAL ANCHORS 1. ALL ADHESIVE/MECHANICAL ANCHORS SHALL BE INSTALLED, INCLUDING HOLE DRILLING AND PREPARATION, IN ACCORDANCE WITH AN APPROVED INDEPENDENT EVALUATION REPORT (ICC-ES, IAPMO, OR APPROVED EQUAL), AS INDICATED BELOW, AND IN ACCORDANCE WITH ALL MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS (MPII). 2. ADHESIVE ANCHORS SHALL BE INSTALLED IN CONCRETE HAVING A MINIMUM AGE OF 21 DAYS AT TIME OF ANCHOR INSTALLATION. ADHESIVE ANCHORS SHALL NOT BE FULLY LOADED UNTIL CONCRETE HAS REACHED DESIGN STRENGTH. 3. UNLESS APPROVED BY THE ENGINEER OF RECORD, CONCRETE AND DRILLED ANCHOR HOLES SHALL BE DRY AND FREE OF WATER FOR 24 HOURS PRIOR TO ADHESIVE INSTALLATION. CONTACT THE ENGINEER OF RECORD FOR GUIDANCE IF THE CONTRACTOR CHOOSES TO INSTALL IN WET OR DAMP HOLES. 4. CONCRETE TEMPERATURE AT THE TIME OF INSTALLATION SHALL BE MONITORED BY THE CONTRACTOR. CONTRACTOR SHALL COMPLY WITH ALL MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS (MPII) RELATIVE TO SUBSTRATE TEMPERATURE. 5. INSTALLATION OF ADHESIVE ANCHORS HORIZONTALLY OR UPWARDLY INCLINED TO SUPPORT SUSTAINED TENSION LOADS SHALL BE PERFORMED BY PERSONNEL CERTIFIED BY AN APPLICABLE CERTIFICATION PROGRAM. CERTIFICATION SHALL INCLUDE WRITTEN AND PERFORMANCE TESTS IN ACCORDANCE WITH THE ACl/CRSI ADHESIVE ANCHOR INSTALLER CERTIFICATION PROGRAM, OR EQUIVALENT IN ACCORDANCE WITH ACI 318-11 D.9.2.2. PROOF OF CURRENT CERTIFICATION SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO INSTALLATION. CONTINUOUS SPECIAL INSPECTION SHALL BE PROVIDED FOR THESE ANCHORS. 6. UNLESS NOTED OTHERWISE, ALL ADHESIVE ANCHORS INTO CONCRETE SHALL BE: a. HILTI HIT -RE 50OV3 (ESR-3814), OR HILTI HIT-HY 200 (ESR-3187). b. SIMPSON SET-3G (ESR-4057), OR AT-XP (ER-0263). c. DEWALT PURE 110+ (ESR-3298), OR AC200+ GOLD (ESR-4027-COLD WEATHER). 7. UNLESS NOTED OTHER WISE, ALL MECHANICAL ANCHORS INTO CONCRETE SHALL BE: a. HILTI KW IK BOLT TZ (ESR-1917). b. DEWALT POWER STUD+ SD2 (ESR-2502). c. SIMPSON STRONG -BOLT 2 (ESR-3037). 8. UNLESS NOTED OTHERWISE, ALL SCREW ANCHORS INTO CONCRETE SHALL BE: a. SIMPSON TITEN HD (ESR-2713). b. DEWALT SCREWBOLT+ (ESR-2526). c. HILTI KWIK HUS-EZ (ESR-3027). 9. THE TESTING LABORATORY WILL PERFORM VISUAL INSPECTION OF ANCHORS AND DOWELS AS SPECIFIED IN THE SPECIAL INSPECTION SCHEDULE AND THE APPROVED INDEPENDENT EVALUATION REPORT. TENSION TESTING CAN BE REQUIRED AT THE DIRECTION OF THE STRUCTURAL ENGINEER OF RECORD OR THE SPECIAL INSPECTOR. 10. IF REINFORCEMENT IS ENCOUNTERED DURING DRILLING, ABANDON THAT HOLE AND SHIFT THE ANCHOR LOCATION TO AVOID THE REINFORCEMENT. PROVIDE A MINIMUM SPACE OF (2) ANCHOR HOLE DIAMETERS OR 1 INCH, WHICH EVER IS LARGER, OF SOUND CONCRETE/MASONRY BETWEEN THE ANCHOR AND THE ABANDONED HOLE. FILL THE ABANDONED HOLE WITH NON -SHRINK GROUT. AT CONTRACTORS OPTION, LOCATE EXISTING REINFORCMENT PRIOR TO DRILLING/CORING. IF THE ANCHOR OR DOWEL CANNOT BE SHIFTED AS NOTED ABOVE, THE ENGINEER WILL DETERMINE A NEW LOCATION. 11. LOCATE REINFORCEMENT AND CONFIRM FINAL ANCHOR LOCATIONS PRIOR TO FABRICATING PLATES, MEMBERS, OR OTHER STEEL ASSEMBLIES ATTACHED WITH MECHANICAL ANCHORS. 12. SUBSTITUTION REQUESTS FOR ALTERNATE PRODUCTS SHALL BE APPROVED IN WRITING BY THE STRUCTURAL ENGINEER OF RECORD PRIOR TO USE. SUBSTITUTION REQUESTS SHALL INCLUDE AN ICC ESR OR IAPMO REPORTAND SUPPORTING CALCULATIONS INDICATING COMPLIANCE WITH DESIGN INTENT. H. REINFORCING STEEL 1. REINFORCING BAR STRENGTH REQUIREMENTS: a. ALL REINFORCING BARS SHALL CONFORM TO ASTM STANDARD A-615 GRADE 60 AND ALL WELDED WIRE FABRIC SHALL CONFORM TO ASTM STANDARD A-1064 AND SHALL BE SUPPLIED IN FLAT SHEETS. ADEQUATELY TIE AND SUPPORT ALL REINFORCING STEEL AS SPECIFIED BY ACI 117, TO MAINTAIN EXACT REQUIRED POSITION. 2. HEADED SHEAR STUD ASSEMBLIES SHALL CONFORM TO ASTM A1044. 3. STEEL DISCONTINUOUS FIBER REINFORCEMENT SHALL BE DEFORMED AND CONFORM TO ASTM A820 AND SHALL HAVE A LENGTH TO DIAMETER RATIO NOT SMALLER THAN 50 AND NOT GREATER THAN 100. 4. HEADED DEFORMED BARS SHALL CONFORM TO ASTM A970. OBSTRUCTIONS OR INTERRUPTIONS OF THE BAR DEFORMATIONS, IF ANY, SHALL NOT EXTEND MORE THAN 2 BAR DIAMETERS FROM THE BEARING FACE OF THE HEAD. 5. ALL FIELD BENT DOWELS SHALL BE GRADE 40 WITH SPACING INDICATED REDUCED BY 1/3. 6. UNLESS NOTED OTHERWISE, REINFORCEMENT SHALL HAVE THE FOLLOWING CONCRETE COVERAGE a. CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH ..... 3" b. EXPOSED TO EARTH OR WEATHER 1. #6 & LARGER ..... 2" 2. #5 & SMALLER .....1-1/2" c. NOT EXPOSED TO WEATHER OR EARTH 1. SLABS WALLS JOISTS #11 & SMALLER ..... 3/4" 2. BEAMS, COLUMNS: MAIN REINFORCING OR TIES ..... 1-1/2" d. SLAB ON GRADE : 1. PLACE REINFORCING AT CENTER OF SLAB UNLESS INDICATED OTHERWISE. 7. EXCEPT WHERE NOTED ON PLANS OR DETAILS CONTINUOUS REINFORCEMENT SHALL BE SPLICED AT POINTS OF MINIMUM STRESS BY LAPPING PER THE REBAR LAP SCHEDULE. 8. REINFORCING STEEL MAY BE SPLICED WITH MECHANICAL COUPLERS THAT HAVE A TENSION CAPACITY OF AT LEAST 125% OF THE STRENGTH OF THE BAR. MECHANICAL COUPLERS SHALL BE A POSITIVE CONNECTING TYPE COUPLER, AND SHALL BE INSTALLED IN ACCORDANCE WITH AN APPROVED ICC RESEARCH REPORT. WHERE THESE ARE USED, SPLICES ON ADJACENT BARS SHALL BE STAGGERED AT LEAST 24 INCHES ALONG THE LENGTH OF THE BARS. 9. ALL VERTICAL REINFORCING IN STRUCTURAL ELEMENTS ABOVE SHALL BE SPLICED WITH MATCHING DOWELS EMBEDDED WITHIN THE FOOTINGS OR STRUCTURE BELOW. SPLICE LENGTHS SHALL COMPLY WITH REBAR LAP SCHEDULE. DOWELS INTO FOOTINGS SHALL TERMINATE WITH A STANDARD HOOK, AND SHALL EXTEND TO WITHIN 4" OF THE BOTTOM OF THE FOOTING, BUT NEED NOT EXTEND MORE THAN 20" INTO FOOTING. 10. DO NOT WELD REINFORCING EXCEPT AS NOTED ON PLANS, WHERE REINFORCING IS WELDED, USE ASTM A-706 REINFORCING. 11. REINFORCING BARS, TIES, AND TENDONS SHALL BE SUPPORTED BY NYLON CONES, PLASTIC -COATED TIE -WIRES, OR PLASTIC -COATED CHAIRS. REINFORCING IN FOOTINGS IS PERMITTED TO BE SUPPORTED ON CONCRETE DOBIES. 12. UNLESS NOTED OTHERWISE, HOOKS, STIRRUPS, TIES, AND OTHER BENDS IN REINFORCING STEEL SHALL MEET THE STANDARDS SET FORTH IN ACI 318/318R-14. UNLESS OTHERWISE PERMITTED BY THE ENGINEER, ALL REINFORCEMENT SHALL BE BENT COLD. REINFORCEMENT PARTIALLY EMBEDDED IN CONCRETE SHALL NOT BE FIELD BENT, EXCEPT AS SHOWN ON THESE DRAWINGS OR OTHERWISE PERMITTED BY THE ENGINEER. 13. UNLESS SPECIFICALLY NOTED AND/OR DETAILED IN THE STRUCTURAL DRAWINGS CONDUIT SHALL NOT BE IN CONTACT WITH REINFORCING STEEL. STRUCTURAL NOTES CONTINUED ON S002 31 r Ik architecture I design Q. TIMBER 1. WOOD GRADES (UNLESS NOTED OTHERWISE) a. ALL FRAMING LUMBER SHALL BE DOUGLAS FIR/LARCH CLEARLY MARKED WITH A STAMP BY WWPA APPROVED AGENCY AND SHALL BE GRADED AS FOLLOWS: 1. HORIZONTAL MEMBERS: JOISTS & RAFTERS: NO. 2, BEAMS & STRINGERS: NO. 2. 2. VERTICAL MEMBERS: POST & TRIMMERS: NO. 1, STUDS: NO. 2. b. ALL FRAMING IN CONTACT WITH FOOTINGS, FOUNDATIONS OR SLABS ON GRADE SHALL BE PRESSURE TREATED OR TIMBERSTRAND LSL TREATED LUMBER WITH EQUIVALENT STRESS GRADES TO TYPICAL FRAMING MEMBERS. c. UNLESS NOTED OTHERWISE, ALL ENGINEERED LUMBER SHALL BE FURNISHED BY TRUS-JOIST CORPORATION OR APPROVED EQUAL AND SHALL HAVE THE FOLLOWING MINIMUM PROPERTIES : MODULUS OF ELASTICITY FLEXURAL STRESS RATING LVL : 2,000,000 PSI 2,600 PSI 2. SHEATHING SHALL BE APA RATED SHEATHING, EXPOSURE I, EXTERIOR GLUE AND PANEL INDEX RATING AS NOTED BELOW UNLESS NOTED OTHERWISE LOCATION THICKNESS PANEL INDEX WALLS : 15/32" 24/0 ROOFS: 19/32" 32/16 3. INDIVIDUAL PIECES OF SHEATHING AT ROOF, FLOOR, AND SHEAR WALLS SHALL NOT BE SMALLER THAN 24" IN EITHER DIRECTION AND SHALL SPAN A MINIMUM OF TWO FRAMING SPACES, UNO. 4. CONNECTIONS, FASTENERS, AND ADHESIVE a. ALL BOLTS THRU WOOD SHALL BE ASTM A307 AND SHALL HAVE HARDENED WASHERS UNDER ASTM A563 HEAVY HEX NUT AND BOLT HEADS. b. UNLESS NOTED OTHERWISE, 10d COMMON (0.148) NAILS SHALL BE USED TO FASTEN ALL PLYWOOD FLOOR AND ROOF SHEATHING TO SUPPORTING TRUSSES, JOISTS, LEDGERS OR BLOCKING AS FOLLOWS: 1. BOUNDARY NAILING "BN": 4"O.C. AT ALL BEARING WALLS, SHEAR WALLS, BLOCKING, AND WHERE OTHERWISE INDICATED IN THE STRUCTURAL DRAWINGS. 2. PANEL EDGE NAILING "EN": 6"O.C. AT ALL OTHER PLYWOOD PANEL EDGES. 3. PANEL FIELD NAILING "FN": 12"O.C. AT INTERIOR SUPPORTS IN FIELD OF PANEL. c. NAILS SHALL BE GALVANIZED OR STAINLESS STEEL AT EXPOSED LOCATIONS OR IN TREATED WOOD (SEE NOTE BELOW FOR FASTENERS CONNECTED TO OR IN CONTACT WITH TREATED WOOD). THE HEAD OF ALL NAILS SHALL BE DRIVEN FLUSH WITH THE SURFACE OF THE SHEATHING. d. UNLESS NOTED OTHERWISE, ALL NAILS SHALL HAVE THE FOLLOWING MINIMUM PROPERTIE COMMON SHANK HEAD LENGTH MIN. PENETRATION NAIL SIZE DIAMETER DIAMETER INTO SUPPORT MEMBER 6d 0.113" 0.266" 2" 1.25" 8d 0.131 " 0.281 " 2-1/2" 1.375" 10d 0.148" 0.312" 3" 1.50" 12d 0.148" 0.312" 3-1/4" 1.50" 16d 0.162" 0.344" 3-1/2" 1.62" e. A CONTINUOUS BEAD OF PERMANENT BOND TIMBER/WOOD ADHESIVE COMPOUND SHALL BE USED TO FASTEN ALL PLYWOOD FLOOR SHEATHING TO FLOOR JOISTS IN ACCORDANCE WITH MANUFACTURERS' SPECIFICATIONS. f. ALL FRAMING ANCHORS, POST CAPS, HOLD DOWNS, COLUMN BASES ETC. TO BE PROVIDED BY SIMPSON OR APPROVED EQUAL AND SHALL BE ATTACHED IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED DATA, UNLESS NOTED OTHERWISE. g. UNLESS NOTED OTHERWISE, ALL WALL BOTTOM PLATES TO BE ANCHORED TO FOUNDATIONS OR FOOTINGS WITH 3/4" DIAMETER ANCHOR BOLTS AT 32"O.C. WITH 8" MINIMUM EMBEDMENT. THERE SHALL BE A MINIMUM OF (2) ANCHOR BOLTS PER PLATE WITH ONE BOLT LOCATED NOT MORE THAN 12" AND NOT LESS THAN 4" FROM EACH END OF EACH PIECE. h. WALL BOTTOM PLATES AT SHEAR WALLS SHALL INCLUDE 1/4" x 3" x 3" STEEL PLATE WASHERS BETWEEN THE SILL PLATE AND NUT OF THE ANCHOR BOLT. THE HOLE IN THE PLATE WASHER IS PERMITTED TO BE DIAGONALLY SLOTTED WITH A WIDTH UP TO 3/16" LARGER THAN THE BOLT DIAMETER AND SLOT LENGTH NOT TO EXCEED 1-3/4", PROVIDED A STANDARD CUT WASHER IS PLACED BETWEEN THE PLATE WASHER AND THE NUT. THE PLATE WASHER SHALL EXTEND TO WITHIN'/2" OF THE EDGE OF THE BOTTOM PLATE ON THE SHEATHED SIDE. i. FASTENERS CONNECTED TO OR IN CONTACT WITH PRESERVATIVE - TREATED AND/OR FIRE -RETARDANT -TREATED WOOD (EXCEPT FOR TIMBERSTRAND LSL TREATED LUMBER AND BORATE BASED TREATMENTS) SHALL BE OF G-185 HOT -DIP GALVANIZED STEEL OR 304 OR 316 STAINLESS STEEL. STAINLESS STEEL AND GALVANIZED STEEL SHALL NEVER BE USED IN CONTACT WITH EACH OTHER. 5. UNLESS NOTED OTHERWISE, ALL BEARING WALLS SHALL BE 2X6 SPACED AT 16"O.C. BLOCK ALL NON -SHEATHED BEARING WALLS AT 4'-0"O.C. 6. VERIFY THE STUD SPACING WITH THE ANCHOR BOLT LAY -OUT. WHERE STUDS INTERFERE WITH ANCHOR BOLTS, PROVIDE AN ADDITIONAL FULL - HEIGHT STUD TO ENSURE THAT THE FULL CROSS -SECTIONAL AREA OF THE STUD IS IN CONTACT WITH THE SILL PLATE. 7. EXCEPT WHERE NOTED OTHERWISE, THE NUMBER AND SIZE OF NAILS CONNECTING WOOD MEMBERS SHALL NOT BE LESS THAN THAT SET FORTH IN IBC TABLE 2304.10.1. CONNECTIONS FOR MULTIPLE PIECES OF ENGINEERED LUMBER PIECES SHALL BE IN ACCORDANCE WITH THE MANUFACTURERS SPECIFICATIONS. 8. UNLESS NOTED OTHERWISE, ALL HORIZONTAL FRAMING MEMBERS SHALL BE INSTALLED WITH THE NATURAL CROWN UP. 265 Winslow Way East Suite 202D Bainbridge Island Washington 98110 telephone 206 842 1253 e-mail frank@3rkarchitecture.com l-3a-1D1 Y CONSULTANTS: ENGINEERS structurai consuiLants 1594 W. Park Cir. Ogden, Utah 84404 ph. 801.782.6008 fx. 801.782.4656 W o z� 0 0� Z Q � = N cD 00 � N = a' J w v � J `^ Q L.L V J cn V vi U a a M � z � z o 0 0 D rf) , 2i 0 � 2 N SCALE: ISSUE DATE:01/31/19 REVISIONS: 1 CITY REVIEW 04/05/19 2 OWNER REVISION 07/11/19 5 OWNER REVISION 03/18/20 REVIEW SET S001 n c� 0 N 0 N 00 co 1. STRUCTURAL STEEL 1. STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH THE LATEST EDITION OF THE FOLLOWING: a. ANSI/AISC 360-10 "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS", WITH "COMMENTARY" AND "SUPPLEMENTS" AS REQUIRED BY BUILDING CODE. b. AISC 303-10 "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES" EXCLUDING THE FOLLOWING SECTIONS: 4.4, 4.4.1, AND 4.4.2. c. AISI "SPECIFICATIONS FOR THE DESIGN OF COLD -FORMED STEEL STRUCTURAL MEMBERS". d. AISC "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS". e. AWS D1.1 AND 1.3, "STRUCTURAL WELDING CODE" (EXCEPT SPECIFIC ITEMS DO NOT APPLY IF THEY CONFLICT WITH AISC). f. ANSI/AISC 341-10 "SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS". 2. STRUCTURAL STEEL SHALL COMPLY WITH THE FOLLOWING: a. WIDE FLANGE SHAPES AND WT SHAPES - ASTM A992 b. OTHER SHAPES AND PLATES - ASTM A-36 (UNO) c. HOLLOW STRUCTURAL SECTIONS (HSS) - ASTM A-500, GRADE C FOR SQUARE, RECTANGULAR AND ROUND SHAPES (FY = 50 KSI FOR SQUARE AND RECTANGULAR SHAPES AND 46 KSI FOR ROUND SHAPES) d. STAINLESS STEEL SHAPES, PLATES, AND FASTENERS -ASTM 304 e. DEFORMED BAR ANCHORS (DBA) -ASTM A-496, WELDED IN ACCORDANCE WITH AWS D1.1 f. HEADED STUD ANCHORS (HSA) - ASTM A-108, GRADE 1015 STEEL AND WELDED IN ACCORDANCE WITH AWS D1.1 FOR TYPE "B". USE 3/4" DIAMETER STUDS, UNLESS NOTED OTHERWISE. g. THREADED ROD - ASTM A-449. h. NON -SHRINK GROUT - ASTM C110. NON -SHRINK GROUT SHALL BE PRE -PACKAGED, NON-METALLIC, WITH A 28-DAY COMPRESSIVE STRENGTH OF 6,000 PSI. 3. CONNECTIONS SHALL COMPLY WITH THE STRUCTURAL DRAWINGS UNLESS WRITTEN APPROVAL TO CHANGE IS GIVEN BY THE STRUCTURAL ENGINEER. 4. ALL SHOP FABRICATIONS SHALL BE PERFORMED BY AN APPROVED FABRICATOR IN ACCORDANCE WITH SECTIONS 1702 AND 1704 OF THE IBC OR WITH SHOP INSPECTION BY AN INDEPENDENT AGENCY IN ACCORDANCE WITH SECTION 1704.2.5 OF THE IBC. 5. WELDING a. ALL WELDING AND CUTTING SHALL BE PERFORMED BY AWS QUALIFIED WELDERS IN ACCORDANCE WITH ANSI/AWS D1.1 (LATEST EDITION). b. USE E-70XX ELECTRODES UNLESS NOTED OTHERWISE. E-60XX MAY BE USED FOR WELDING STEEL DECKS. c. ALL INTERSECTING STEEL SHAPES WHICH ARE NOT CONNECTED WITH BOLTS SHALL BE WELDED TOGETHER WITH A FILLET WELD ALL AROUND UNLESS NOTED OTHERWISE. WHERE WELD SIZES ARE NOT SHOWN USE THE FOLLOWING: 1. WHERE ALL CONNECTED PARTS ARE THICKER THAN 1/4", WELD IS 1/16" LESS THAN THE THICKNESS OF THE THINNEST PART. 2. WHERE ANY OF THE CONNECTED PARTS IS LESS THAN 1/4" THICK, WELD IS SAME AS THICKNESS OF THE THINNEST PART. d. WELDING OF HSA'S AND DBA'S SHALL CONFORM TO THE MANUFACTURER'S SPECIFICATIONS. e. WHEREVER POSSIBLE, WELDS SHALL BE SHOP WELDS. SPECIAL CONSIDERATIONS, SUCH AS ITEMS WHICH MAY NEED ADJUSTMENT AT THE SITE, REQUIRE THAT SOME WELDS BE FIELD WELDS. WHERE QUESTIONS OR DISCREPANCIES OCCUR THE CONTRACTOR SHALL COORDINATE THE WORK BETWEEN THE SHOP FABRICATOR AND THE STEEL ERECTOR. 6. BOLTING a. UNLESS NOTED OTHERWISE, ALL STRUCTURAL STEEL TO STEEL CONNECTIONS SHALL USE HIGH STRENGTH BOLTS CONFORMING TO ASTM A-325. b. UNLESS NOTED OTHERWISE, ALL BOLTING IS CLASSIFIED AS NON -SLIP CRITICAL BEARING TYPE CONNECTIONS WITH THREADS INCLUDED IN SHEAR PLANE. TIGHTEN BOLTS TO A SNUG TIGHT CONDITION, WITH ALL PLIES OF THE JOINT IN FIRM CONTACT. c. WHERE OVERSIZED OR SLOTTED HOLES OCCUR IN THE OUTER PLY, AN ASTM F436 WASHER OR 5/16" THICK COMMON PLATE WASHER SHALL BE USED AS REQUIRED TO COMPLETELY COVER THE HOLE. d. BOLTS SHALL BE CENTERED IN SLOTTED HOLES, UNLESS NOTED OTHERWISE. e. WHERE A STEEL BEAM TO BEAM CONNECTION IS NOT SHOWN, PROVIDE AN AISC STANDARD FRAMED CONNECTION SIZED FOR 1/2 OF THE TOTAL LOAD CAPACITY OF THE BEAM FOR THE SPAN AND STEEL SPECIFIED. 7. METAL DECKING a. UNLESS NOTED OTHERWISE, METAL ROOF DECK SHALL BE 22 GAUGE TYPE B GALVANIZED STEEL DECK. SEE ROOF DECK SCHEDULE FOR ATTACHMENTS. b. ALL DECK SHALL BE CONTINUOUS OVER 3-SPANS. WHERE NOT POSSIBLE, THE DECK SUPPLIER/CONTRACTOR SHALL PROVIDE HEAVIER GAUGE DECK AS NEEDED TO PROVIDE THE EQUIVALENT PERFORMANCE OF THE SPECIFIED DECK WITH 3-SPAN CONTINUITY. c. SEE TYPICAL DETAILS FOR SUPPORT OF DECK AT OPENINGS. d. PROVIDE 1_2"x2"x3/16" FOR DECK SUPPORT AT LOCATIONS WHERE COLUMNS EXTEND THROUGH DECK. e. PAINTED STEEL DECK SHALL CONFORM TO ASTM A1008 AND GALVANIZED STEEL DECK SHALL CONFORM TO A653 GRADE G60. f. BUILDING ELEMENTS MAY BE SUPPORTED BY HANGING DIRECTLY FROM METAL DECKING, PROVIDED THAT THE TOTAL WEIGHT PER CONNECTION IS LESS THAN 50 LBS AND THAT THE ATTACHMENT TO THE DECKING IS DISTRIBUTED ACROSS AT LEAST TWO RIBS AND SPACED AT LEAST 6 FEET APART IN ANY DIRECTION. 8. PROVIDE FULL DEPTH WEB STIFFENER PLATES AT EACH SIDE OF STEEL BEAMS AT ALL BEARING (EXCEPT SECONDARY FRAMING) POINTS. STIFFENER PLATES SHALL BE THICKNESS SHOWN UNLESS NOTED OTHERWISE AND SHALL BE WELDED BOTH SIDES WITH FILLET WELDS ALL AROUND. FLANGE WIDTH STIFFENER THICKNESS WELD THICKNESS < 8 1/4" 1/4" 3/16" 8 1/4" < BF < 12 1 /2" 3/8" 1/4" 12 1 /2" < BF < 18" 1 /2" 5/16" 9. FABRICATORS AND SUPPLIERS SHALL COORDINATE PAINT/FINISHES WITH REQUIREMENTS FOR DIRECT APPLIED INSULATION, FIREPROOFING, ETC. AS NOTED IN THE PROJECT SPECIFICATIONS. 10. WHEN DETERMINING THE FIRE RESISTANCE OF ASSEMBLIES, USE THE FOLLOWING: STEEL ROOF MEMBERS ARE CONSIDERED UN -RESTRAINED AND STEEL FLOOR FRAMING MEMBERS ARE CONSIDERED RESTRAINED. 11. UNLESS NOTED OTHERWISE, ALL HORIZONTAL FRAMING MEMBERS SHALL BE ERECTED WITH THE NATURAL CROWN UP. 12. UNLESS OTHERWISE SHOWN OR DETAILED IN THE PLANS, ALL STEEL COLUMNS, BEAMS, BRACES, STRUTS, ETC. SHALL BE CONTINUOUS BETWEEN CONNECTIONS OR SUPPORTS. SPLICES IN MEMBERS SHALL NOT BE PERMITTED WITHOUT WRITTEN APPROVAL BY THE ENGINEER OF RECORD. J. MOMENT FRAMES 1. STRUCTURAL STEEL IN MOMENT FRAMES SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH THE LATEST EDITION OF THE AISC SPECIFICATIONS NOTED IN THE STRUCTURAL STEEL NOTES ABOVE IN ADDITION TO THE FOLLOWING : a. AISC 341 - RECOMMENDED SPECIFICATIONS AND QUALITY ASSURANCE GUIDELINES FOR STEEL MOMENT -FRAME CONSTRUCTION FOR SEISMIC APPLICATIONS. 2. STRUCTURAL STEEL IN MOMENT FRAMES SHALL COMPLY WITH THE REQUIREMENTS NOTED IN THE STRUCTURAL STEEL NOTES ABOVE TO INCLUDE THE FOLLOWING: a. ALL SHAPES OF GROUP 3 (WITH FLANGES THICKER THAN 1-1/2"), GROUP 4 AND GROUP 5, AS WELL AS ALL PLATES 2" AND THICKER, THAT ARE PART OF THE SEISMIC FORCE RESISTING SYSTEM SHALL HAVE CHARPY V-NOTCH ABSORBED ENERGY OF AT LEAST 20 FT-LBS. AT 70 DEGREES F. 3. BOLTED CONNECTIONS IN MOMENT FRAMES SHALL CONFORM TO AISC 358 FASTENER AND TIGHTENING REQUIREMENTS. ALL BOLTS IN MOMENT FRAMES SHALL BE INSPECTED AND TESTED. 4. WELDED CONNECTIONS BETWEEN THE PRIMARY MEMBERS OF MOMENT FRAMES SHALL BE TESTED FOR COMPLIANCE ACCORDING TO IBC 1705.2.1 AND THE CONTRACT SPECIFICATIONS AND PLANS. INSPECTION SHALL BE DONE BY A QUALIFIED TESTING INSPECTOR. AS A MINIMUM, THE TESTING SHALL INCLUDE THE FOLLOWING: a. ALL COMPLETE -JOINT -PENETRATION GROOVE WELDS CONTAINED IN JOINTS AND SPLICES SHALL BE TESTED 100% EITHER BY ULTRASONIC TESTING OR BY RADIOGRAPHY. b. PARTIAL PENETRATION GROOVE WELDS WHEN USED IN COLUMN SPLICES SHALL BE TESTED EITHER BY ULTRASONIC TESTING OR BY RADIOGRAPHY. A MINIMUM OF 50% OF THESE WELDS SHALL BE TESTED. c. BASE METAL THICKER THAN 1-1/2", WHEN SUBJECTED TO THROUGH THICKNESS WELD SHRINKAGE STRAINS SHALL BE ULTRASONICALLY INSPECTED FOR DISCONTINUITIES DIRECTLY BEHIND SUCH WELDS AND THREE INCHES ABOVE AND BELOW THE WELD AFTER JOINT ASSEMBLY COMPLETION. d. ANY MATERIAL DISCONTINUITIES SHALL BE ACCEPTED OR REJECTED ON THE BASIS OF THE DEFECT RATING IN ACCORDANCE WITH THE IBC STANDARDS AS IT REFERS TO THE TESTING IN AWS D1.1 CHAPTER 6, EXCLUDING SECTIONS 6.1 THROUGH AND INCLUDING 6.6. ALL DEFICIENT WELDS SHALL BE CORRECTED AND TESTED AT NO ADDITIONAL COST TO THE OWNER. 5. ALL COMPLETE -JOINT -PENETRATION WELDS USED IN MOMENT FRAMES ARE CONSIDERED DEMAND CRITICAL AND THE FOLLOWING SPECIAL PROVISIONS APPLY: WELDING METHODS, PROCEDURES AND QUALITY CONTROL SHALL COMPLY WITH AWS D1.1 AND THE FOLLOWING: a. TACK WELD QUALITY SHALL COMPLY WITH SECTION 5.18. b. ARC STRIKES, GOUGES AND OTHER IMPERFECTIONS WITHIN OR ADJACENT TO THE JOINT, SHALL BE REPAIRED OR REMOVED. c. PREHEAT AND INTER -PASS REQUIREMENTS AS OUTLINES IN SECTION 3.5. d. USE WELD TABS AT BEAM FLANGE CONNECTION; AFTER WELDING, REMOVE THE WELD TABS AND FINISH TO A SMOOTH CONTOUR PER SECTION 5.31.3. e. BACKER BARS SHALL BE REMOVED FROM BEAM BOTTOM FLANGE CONNECTIONS TO COLUMNS. THE ROOT OF THE WELD SHALL BE BACK GOUGED TO SOUND METAL TO REMOVE ALL SLAG AND CRACKS. WELD THE BACK -GOUGED REGION AND FINISH WELDING USING A REINFORCING FILLET WELD, ACCORDING TO SECTION 5.10.4. f. BACKER BARS NEED NOT BE REMOVED FROM THE BEAM TOP FLANGE CONNECTIONS TO COLUMNS PROVIDED THAT THE BACKER BARS ARE WELDED TO THE COLUMN FLANGE WITH A CONTINUOUS FILLET WELD FOR THE ENTIRE LENGTH OF THE BACKER BAR. g. UNREPAIRED CRACKS, GOUGES, AND NOTCHES WILL NOT BE PERMITTED IN THE JOINT AREA. h. USE ELECTRODES WITH CHARPY V-NOTCH ABSORBED ENERGY EQUAL TO OR GREATER THAN 20 FT-LBS AT -20 DEGREES FAHRENHEIT UNDER AWS A5 CLASSIFICATION TEST METHODS, AND 40 FT- LBS AT 70 DEGREES FAHRENHEIT USING TEST PROCEDURES PRESCRIBED IN APPENDIX X OF AISC 358. ACCEPTABLE ELECTRODES INCLUDE E70TG-K2, E71T-8, AND E71T-1. 6. ALL NON -COMPLETE -JOINT -PENETRATION WELDS USED IN MOMENT FRAMES SHALL BE MADE WITH A FILLER METAL THAT CAN PRODUCE WELDS THAT HAVE A MINIMUM CHARPY V-NOTCH TOUGHNESS OF 20 FT -LB AT 0 DEGREES F, AS DETERMINED BY THE APPROPRIATE AWS A5 CLASSIFICATION TEST METHOD OR MANUFACTURER CERTIFICATION. K. COLD -FORMED STEEL 1. LIGHT GAUGE STEEL FRAMING a. STEEL FRAMING SIZE DESIGNATORS USED IN THE DRAWINGS FOLLOW THE CONVENTION ESTABLISHED BY THE STEEL STUD MANUFACTURERS' ASSOCIATION (SSMA) AND THE NORTH AMERICAN STEEL FRAMING ALLIANCE (NASFA). FRAMING MEMBERS PROVIDED SHALL MEET OR EXCEED ALL SSMA AND NASFA STANDARDS AND DESIGN PROPERTIES. b. ALL LOAD BEARING STUDS (AND/OR) JOIST FRAMING MEMBERS ALONG WITH ALL RUNNERS, BRIDGING, AND END -TRACKS SHALL BE OF THE DESIGNATION SHOWN ON THE PLANS. ALL OF THE ABOVE ELEMENTS SHALL BE FORMED FROM STEEL MEETING REQUIREMENTS OF ASTM A1011/A1011M-04. ALL COMPONENTS SHALL BE GALVANIZED. ALL COMPONENTS SHALL HAVE THE FOLLOWING YIELD STRESSES : COMPONENT BASE METAL THICKNESS YIELD STRESS STUDS, JOISTS & TRACKS 33 & 43 MILL 33,000 PSI 54, 68 & 97 MILL 50,000 PSI END CLOSURES & BRIDGING 33, 43, 54 & 68 MILL 33,000 PSI c. FOLLOW ALL MANUFACTURERS' RECOMMENDATIONS FOR THE USE OF THESE PRODUCTS. d. UNLESS NOTED OTHERWISE, ALL WELDED CONNECTIONS SHALL BE IN ACCORDANCE WITH AWS D1.3 AND THE STRUCTURAL DETAILS. ALL WELDS SHALL BE COMPLETED USING E60XX ELECTRODES. 2. SHEATHING SHALL BE APA RATED SHEATHING, EXPOSURE I, EXTERIOR GLUE AND PANEL INDEX RATING AS NOTED BELOW UNLESS NOTED OTHERWISE : LOCATION THICKNESS PANEL INDEX WALLS : 15/32" 24/0 ROOFS: 19/32" 32/16 a. INDIVIDUAL PIECES OF SHEATHING AT ROOF, FLOOR, AND SHEAR WALLS SHALL NOT BE SMALLER THAN 24" IN EITHER DIRECTION AND SHALL SPAN A MINIMUM OF TWO FRAMING SPACES, UNO. b. UNLESS NOTED OTHERWISE, ALL ROOF SHEATHING AND WALL SHEATHING AT SHEAR WALLS SHALL HAVE FLAT STUD BLOCKING AT ALL PANEL EDGES. 3. CONNECTIONS, FASTENERS, AND ADHESIVE a. UNLESS NOTED OTHERWISE, #8 TEK SCREWS SHALL BE USED TO FASTEN ALL SHEATHING TO SUPPORTING JOISTS, LEDGERS OR BLOCKING AS FOLLOWS : 1. BOUNDARY SCREWS "BS": 4"O.C. AT ALL ROOF SHEATHING INTO BEARING AND/OR SHEAR WALLS, TOP & BOTTOM OF WALLS. 2. EDGE SCREWS "ES": 6"O.C. AT ALL OTHER PLYWOOD PANEL EDGES. 3. PANEL FIELD SCREWS "FS": 12"O.C. AT INTERIOR SUPPORTS IN FIELD OF PANEL. SCREWS SHALL BE GALVANIZED OR STAINLESS STEEL AT EXPOSED LOCATIONS. THE HEAD OF ALL SCREWS SHALL BE SCREWED FLUSH WITH THE SURFACE OF THE SHEATHING. b. ALL SCREWS SHALL HAVE THE FOLLOWING MINIMUM PROPERTIES SCREW SIZE SHANK DIAMETER NO. 6 0.138" NO. 8 0.164" NO. 10 0.1901, NO. 12 0.216" c. UNLESS NOTED OTHERWISE, ALL FRAMING ANCHORS, SLIPS, HOLD DOWNS, STRAPS, ETC. TO BE PROVIDED BY THE STEEL NETWORK OR APPROVED EQUAL. d. UNLESS NOTED OTHERWISE, ALL EXTERIOR WALL BOTTOM TRACKS TO BE ANCHORED TO THE CONCRETE FOUNDATION WALL WITH HILTI KWIK HUS-EZ'/4"X2-1/2" EMBEDMENT ANCHOR BOLTS @ 16"O.C. 4. UNLESS NOTED OTHERWISE, ALL STEEL STUD WALLS SHALL BE CONTINUOUS BETWEEN TOP AND BOTTOM TRACKS WITH NO SPLICES. 4. UNLESS NOTED OTHERWISE, ALL STEEL STUD JOISTS AND BOX HEADER COMPONENTS SHALL BE CONTINUOUS WITH NO SPLICES BETWEEN BEARING SUPPORTS. 5. ALL TOP AND BOTTOM TRACKS OF STUD WALLS AND BOX HEADERS SHALL BE CONTINUOUS. WHERE LONG TRACKS ARE NOT AVAILABLE, TRACKS MAY BE WELDED TOGETHER PER NOTE 1D OF THESE NOTES, ON ALL SIDES OR TRACKS MAY BE SPLICED PER DETAIL 4/S205. 6. SEE TYPICAL DETAIL FOR REINFORCEMENT OF KNOCK OUT HOLES AT BEARING AND POINT LOAD LOCATIONS ON STEEL JOISTS AND BOX HEADERS. 7. AT ALL OVERBUILD LOCATIONS, ROOF SHEATHING SHALL BE COMPLETE BELOW OVERBUILDS PRIOR TO OVERBUILD CONSTRUCTION. 8. UNLESS NOTED OTHERWISE, ALL EXTERIOR WALLS SHALL BE 80OS162-54 STUDS SPACED AT 16"O.C. W/ 80OT150-54 TRACKS. ATTACH TRACK TO STUDS W/ (1) #8 TEK SCREW EACH SIDE OF STUD. 9. UNLESS NOTED OTHERWISE, ALL INTERIOR WALL STUDS SHALL BE 60OS162-54 STUDS SPACED AT 16"O.C. WITH 600T150-54 TRACKS. ATTACH TRACK TO STUDS WITH (1) #8 TEK SCREW EACH SIDE OF STUD. 10. PREFABRICATED SYSTEMS: SUBMIT COMPLETE SHOP DRAWINGS AND CALCULATIONS OF ALL ELEMENTS FOR REVIEW. SUBMITTALS SHALL BEAR THE STAMP OF A PROFESSIONAL ENGINEER LICENSED IN THE STATE IN WHICH THE PROJECT OCCURS. L. OPEN WEB JOISTS AND GIRDERS 1. ALL OPEN WEB STEEL JOISTS AND GIRDERS SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH THE LATEST EDITION OF "STANDARD SPECIFICATIONS AND CODE OF STANDARD PRACTICE" OF THE STEEL JOIST INSTITUTE. 2. (###/###) DENOTES APPLIED TOTAL AND LIVE UNIFORMLY DISTRIBUTED LOADS IN POUNDS PER LINEAR FOOT OF JOIST, RESPECTIVELY. 3. SEE JOIST LOAD PROFILES FOR SPECIALLY LOADED JOISTS. 4. CONCENTRATED POINT LOADS (NOT SPECIFICALLY SHOWN ON THE PLANS) OF LESS THAN 200 LBS FOR MECHANICAL UNITS. FIRE SPRINKLER MAINS, AND OTHER EQUIPMENT SUPPORTED FROM JOISTS SHALL BE SUPPORTED WITHIN 6" OF A CHORD PANEL POINT. SUPPORT BEYOND PANEL POINTS CAN BE PROVIDED BY ADDING (2) 1_2"x2"x1/4" DIAGONALS TO THE NEAREST OPPOSITE CHORD PANEL POINT. LOADS SHALL BE SPACED AT LEAST 6 FEET APART WITH NO MORE THAN 4 PER JOIST. SEE JOIST FABRICATOR FOR ADDITIONAL REQUIREMENTS. 5. ANY BRACING REQUIRED FOR MISCELLANEOUS ITEMS (I.E. DUCTWORK, PIPING, ETC.) MUST CONNECT TO THE TOP CHORD OF THE JOIST OR GIRDER. BRACING TO THE BOTTOM CHORD IS NOT ALLOWED UNLESS SPECIFICALLY DETAILED THAT WAY ON THE PLANS. 6. PROVIDE SPECIAL BEARING ENDS AS REQUIRED AT SLOPED BEARING CONDITIONS. CONTRACTOR SHALL COORDINATE WITH OTHER STRUCTURAL ELEMENTS. 7. ALL JOISTS SHALL BE CAMBERED PER SJI SPECIFICATIONS, UNLESS NOTED OTHERWISE. 8. FIELD MODIFICATIONS (INCLUDING HOLES IN THE CHORD OR WEB MEMBERS) SHALL NOT BE MADE TO ANY JOIST OR GIRDER WITHOUT PRIOR APPROVAL BY THE MANUFACTURER. 9. FABRICATORS AND SUPPLIERS SHALL COORDINATE PAINT/FINISHES WITH REQUIREMENTS FOR DIRECT APPLIED INSULATION, FIREPROOFING, ETC. AS NOTED IN THE PROJECT SPECIFICATIONS. 10. JOIST BRIDGING SHALL BE PROVIDED AS REQUIRED BY THE JOIST MANUFACTURER AND SJI STANDARDS. BRIDGING WHERE SHOWN ON THE STRUCTURAL DRAWINGS IS A SCHEMATIC REPRESENTATION ONLY. SEE JOIST MANUFACTURER FOR BRIDGING SIZE, CONNECTIONS, TYPE AND QUANTITY. 11. WHERE ADDED LOADS ARE SHOWN ON THE JOISTS BUT NOT SPECIFICALLY DIMENSIONED, THE JOIST DESIGNER SHALL PLACE THOSE LOADS ON THE JOIST AT A LOCATION THAT RESULTS IN THE HIGHEST STRESS IN THE MEMBERS. THE DESIGNER MAY ASSUME THAT THE LOAD OCCURS WITHIN 10 FEET OF A SCALED DIMENSION. 12. FABRICATOR MUST SUBMIT A CERTIFICATE OF COMPLIANCE TO THE BUILDING OFFICIAL PER IBC 2207.5 STATING THAT WORK WAS PERFORMED IN ACCORDANCE WITH APPROVED CONSTRUCTION DOCUMENTS AND WITH SJI SPECIFICATIONS. 13. UNLESS NOTED OTHERWISE, ROOF JOISTS AND GIRDERS SHALL BE DESIGNED FOR A NET WIND UPLIFT OF 10 PSF. 14. ALL ROOF JOISTS BEARING ON EXTERIOR WALLS SHALL BE DESIGNED TO TRANSFER 3.75 KIPS (ULTIMATE) TOP CHORD AXIAL FORCE THROUGH THE BEARING SHOE. 15. ALL JOISTS AT GRID LINES SHALL BE DESIGNED TO RESIST A 10 KIP TOP CHORD AXIAL FORCE (ULTIMATE). M. STRUCTURAL DELEGATED DESIGNS AND DEFERRED SUBMITTALS 1. STRUCTURAL DELEGATED DESIGNS AND SUBSEQUENT DEFERRED SUBMITTALS ARE FOR ELEMENTS, PARTS, OR PORTIONS OF THE OVERALL STRUCTURAL SYSTEM THAT ARE INDICATED OR REFERRED TO ON THESE DRAWINGS AND THAT ARE CRITICAL TO THE PERFORMANCE OF THE OVERALL STRUCTURAL SYSTEM. DESIGN CRITERIA HAS BEEN PROVIDED FOR THESE ITEMS IN THE STRUCTURAL NOTES, PLANS, AND DETAILS. 2. STRUCTURAL DEFERRED SUBMITTALS ARE COMPLETE PACKAGES TO BE SUBMITTED FOR REVIEW THAT INCLUDE DRAWINGS AND CALCULATIONS FOR ALL DELEGATED DESIGN ITEMS ANDTHEIR CONNECTIONS.DEFERRED SUBMITTALS SHALL BEAR THE STAMP AND SIGNATURE OF THE DESIGN PROFESSIONAL RESPONSIBLE FOR THEIR DESIGN. 3. ARW ENGINEERS WILL REVIEW STRUCTURAL DEFERRED SUBMITTALS TO VERIFY DESIGN CRITERIA IS COMPLIANT WITH THE APPROVED CONSTRUCTION DOCUMENTS. 4. STRUCTURAL DELEGATED DESIGN COMPONENTS SHALL NOT BE INSTALLED UNTIL APPROVED BY THE BUILDING OFFICIAL. 5. STRUCTURAL DELEGATED DESIGN ITEMS REQUIRING DEFERRED SUBMITTALS INCLUDE, BUT ARE NOT LIMITED TO: a. OPEN WEB JOISTS & GIRDERS, BRIDGING, BRACING, CONNECTIONS, AND RELATED COMPONENTS. N. NON-STRUCTURAL DELEGATED DESIGNS AND DEFERRED SUBMITTALS 1. NON-STRUCTURAL DELEGATED DESIGNS AND SUBSEQUENT DEFERRED SUBMITTALS ARE FOR ITEMS NOT INCLUDED IN THE STRUCTURAL DELEGATED DESIGN SECTION. THESE ARE ITEMS THAT ARE NOT CRITICAL TO THE OVERALL PERFORMANCE OF THE STRUCTURAL SYSTEM BUT THAT IMPART LOADS AND FORCES TO THE STRUCTURAL SYSTEM. 2. NON-STRUCTURAL DEFERRED SUBMITTALS SHALL BEAR THE STAMP AND SIGNATURE OF THE DESIGN PROFESSIONAL RESPONSIBLE FOR THE DESIGN. 3. ARW ENGINEERS WILL REVIEW NON-STRUCTURAL DEFERRED SUBMITTALS TO VERIFY DESIGN CRITERIA IS COMPLIANT WITH THE APPROVED CONSTRUCTION DOCUMENTS. 4. IF THE STRUCTURAL DRAWINGS INCLUDE LOADS TO ACCOMMODATE NON-STRUCTURAL ELEMENTS, THE CONTRACTOR SHALL SUBMIT DOCUMENTATION INDICATING THAT THE NON-STRUCTURAL ELEMENTS COMPLY WITH THE LOADING CRITERIA PROVIDED HEREIN. SUCH DOCUMENTATION SHALL BEAR THE STAMP AND SIGNATURE OF THE DESIGN PROFESSIONAL RESPONSIBLE FOR THE DESIGN. 5. IF THE NON-STRUCTURAL DEFERRED SUBMITTAL INDICATES THAT THE ELEMENT WILL IMPART FORCES IN EXCESS OF THOSE INDICATED ON THE STRUCTURAL DRAWINGS, THE CONTRACTOR SHALL SUBMIT A DETAILED GRAPHICAL REPRESENTATION OF THOSE DESIGN LOADS, INCLUDING MAGNITUDE, AND LOCATION. THE GRAPHIC SHALL BE ACCOMPANIED BY DOCUMENTATION INDICATING THAT THE NON- STRUCTURAL ELEMENT DESIGN COMPLIES WITH THE LOADING CRITERIA PROVIDED HEREIN. THE LETTER SHALL BEAR THE STAMP AND SIGNATURE OF THE DESIGN PROFESSIONAL RESPONSIBLE FOR THE DESIGN. 6. NON-STRUCTURAL DELEGATED DESIGN ITEMS REQUIRING DEFERRED SUBMITTALS SHALL INCLUDE, BUT ARE NOT LIMITED TO: a. COLD FORMED STEEL STUDS / JOISTS / HEADERS / JAMBS / TRUSSES. b. SEISMIC BRACING OF ALL ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL ITEMS WHERE REQUIRED BY ASCE 7-10 AND THE PROJECT CONTRACT DOCUMENTS. c. STRUCTURAL STEEL STAIRS. 0. EXISTING BUILDING NOTES 1. ARW ENGINEERS EXPRESSLY DISCLAIMS RESPONSIBILITY FOR ANY PORTION OF THE EXISTING BUILDING NOT SPECIFICALLY ADDRESSED IN THESE DRAWINGS. 2. DRAWINGS AND DETAILS HAVE BEEN PREPARED TO REFLECT THE EXISTING CONDITIONS AND CONFIGURATIONS OF STRUCTURAL ELEMENTS. HOWEVER, THE CONTRACTOR IS ULTIMATELY RESPONSIBLE FOR VERIFYING ALL EXISTING CONDITIONS AND ALERTING THE ENGINEER OF ANY DISCREPANCIES FOUND PRIOR TO FABRICATING OR INSTALLING STRUCTURAL ELEMENTS. 3. THE CONTRACTOR IS RESPONSIBLE FOR MAKING SURE THAT THE BUILDING AND ELEMENTS WITHIN THE BUILDING REMAIN STABLE UNTIL CONSTRUCTION IS COMPLETE. AT NO ADDITIONAL COST TO THE OWNER, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING SHORING OR OTHER TEMPORARY SUPPORT OF STRUCTURAL MEMBERS UNTIL THE FINAL CONFIGURATION HAS BEEN COMPLETED. 31 r Ik architecture I design 265 Winslow Way East Suite 202D Bainbridge Island Washington 98110 telephone 206 842 1253 e-mail frank@3rkarchitecture.com CONSULTANTS: ENGINEERS structurai consuiLants 1594 W. Park Cir. Ogden, Utah 84404 ph. 801.782.6008 fx. 801.782.4656 W o z� 0 0� � �Q Z Q = N Q cD 00 � = o' J N w v � J `^ Q L.L V J cn V vi (D a a M � in-z z c)0 0 D rf) , 0 2 N SCALE: ISSUE DATE:01/31/19 REVISIONS: 1 CITY REVIEW 04/05/19 2 OWNER REVISION 07/11/19 5 OWNER REVISION 03/18/20 REVIEW SET S002 73 n v c� 0 N O N 00 BEAM CONNECTION SCHEDULE SHEAR PLATE INFORMATION BOLTS W/ STANDARD WASHERS OVER WELDSLOTS BEAM PL. DIMENSIONS �A� COMMENTS DEPTH W/ SHORT- Lev Leh No. SIZE SLOTTED HOLES W8 x, W10 x PL. 1/4" x 4" 1 1/2" 2" 2 3/4" 0 3/16" W12 x PL. 5/16" x 4" 1 1/2" 211 3 3/4" 0 1/4" W14 x 90 & PL. 5/16" x 4" 1 1/2" 2" 3 3/4" 0 1/4" LIGHTER W16 x 77 & PL. 5/16" x 4" 1 1/2" 2" 4 3/4" 0 1/4" LIGHTER W 18 x 65 & PL. 5/16" x 4" 1 1/2" 2" 5 3/4" 0 1/4" LIGHTER FACE OF COLUMN / BEAM WEB 1/2' Leh / >� J O q SHEAR PL. - SEE SCHEDULE SHORT -SLOTTED HOLES IN ih SHEAR PLATE W/ WASHER PER THE STRUCTURAL NOTES x *0 J W BEAM - SEE PLAN SEE SCHED. A' WIND UPLIFT SCHEDULE (FOR JOIST AND JOIST GIRDER DESIGN) ZONE 1 = 9 psf 2 3 ZONE 2 = 20 psf ZONE 3 = 35 psf EXISTING BUILDING 1 2 2 3 2 1 2 3 2 3 KEY PLAN NOTE : LOADS SHOWN ARE NET UPLIFT LOADS. 60% OF DEAD LOAD HAS BEEN SUBTRACTED FROM GROSS WIND UPLIFT LOAD. ROOF DECK SCHEDULE AREA DECK ATTACHMENT MIN. ALLOWABLE SHEAR CAPACITY FLEXIBILITY FACTOR SUPPORTS DIA. WELD PATTERN SIDE SEAMS #12TEK TOP SEAM PUNCH SCREWS WELD LOCK" SUPPORTS PARALLEL TO FLUTES DEPTH TYPE GA. 0 WELD SPA. A 1 1/2 B 22 3/4" 36/5 18"o.c. - --- 3/4" 12"o.c. 342plf 43 FASTENING PATTERNS WELD PATTERN : 36/5 NOTES: 1. USE NESTABLE (OVERLAPPING) SIDE SEAMS AT SCREW ATTACHMENTS AND INTERLOCKING SIDE SEAMS AT WELDS. 2. ALL DECK WITH A PROFILE DEPTH OF 2" OR LESS SHALL HAVE NESTED OR TELESCOPED END LAPS. 3. SUBMIT CURRENT ICC APPROVAL FOR ALL DECKS. 4. ALTERNATE SYSTEMS SHALL MEET OR EXCEED THE MINIMUM SHEAR CAPACITY AND SHALL PROVIDE LESS THAN OR EQUAL TO THE MAXIMUM FLEXIBILITY FACTOR LISTED IN THE SCHEDULE. 5. ALL ALTERNATE SYSTEMS SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW AND APPROVAL. EXISTING BUILDING A A KEY PLAN STANDARD HOOK & BEND SCHEDULE DETAILING HOOK A DIMENSIONS Sol D (; I �) J 180' 4 db OR 2 1/2" MIN. db = BAR DIAMETER D = FINISHED INSIDE BEND DIAMETER DETAILING I DIMENSIONS J A D D = 6db FOR #3 THROUGH #8 D = 8db FOR #9 THROUGH #11 BAR SIZE DIMENSION OF STANDARD 180-DEG HOOKS, ALL GRADES DIMENSION OF STANDARD 90-DEG HOOKS, ALL GRADES A J D A D #3 5" 3" 2 1/4" 6" 2 1/4" #4 6" 4" 3" 8" 3" #5 7" 5" 3 3/4" 10" 3 3/4" #6 8" 6" 4 1/2" 1'-0" 4 1/2" #7 10" 7" 5 1/4" 1'-2" 5 1/4" #8 ill, 8" 6" 1'-4" 6" #9 1'-3" 11 3/4" 9 1/2" V-7" 9 1/2" #10 1'-5" 1'-1 1/4" 10 3/4" V-10" 10 3/4" #11 1'-7" 1'-2 3/4" 12" 2'-0" 12" 3 1 r 1k. architecture I design LEGEND OF SYMBOLS AND ABBREVIATIONS AB = ANCHOR BOLT FOOTING MARK ABV = ABOVE TOP OF FOOTING ELEV. ARCH = ARCHITECT BLW = BELOW SECTION MARK CJP = COMPLETE JOINT PENETRATION CL = CENTERLINE SHEET NUMBER COL = COLUMN CONC = CONCRETE TOP OF FOUNDATION WALL OR CID = CONCRETE PIER COLUMN PIER ELEV. DC = DEMAND CRITICAL DIA / 0 = DIAMETER S S FOOTING STEP DBA = DEFORMED BAR ANCHOR DBE = DECK BEARING ELEVATION CONCRETE BEAM ELEV = ELEVATION EOD = EDGE OF DECK FDN = FOUNDATION ELEVATION FTG = FOOTING FFE = FINISHED FLOOR ELEVATION L FRAMING ANGLE SEE TYPICAL DETAIL GB = CONCRETE GRADE BEAM HSA = HEADED STUD ANCHOR C FRAMING CHANNEL SEE TYPICAL JBE = JOIST BEARING ELEVATION DETAIL KB = KICKER BRACE MAX = MAXIMUM ITEMS, DETAILS, & SYSTEMS WHICH MECH = MECHANICAL L ARE PART OF THE LATERAL FORCE MEZZ = MEZZANINE RESISTING SYSTEM. MIN = MINIMUM NS, FS = NEAR SIDE, FAR SIDE MOMENT RESISTING CONNECTIONS - OAE = OR APPROVED EQUAL SEE DETAIL OPP = OPPOSITE PAF = POWDER ACTUATED FASTENER MOMENT RESISTING CANTILEVER PL = PLATE CONNECTIONS - SEE DETAIL REINF = REINFORCING REQ'D = REQUIRED KB KICKER BRACE SIM = SIMILAR SSH = STEEL STUD HEADER Q SSJ = STEEL STUD JAMB HD - SIMPSON HOLDOWN SIZE POST - SSS = STEEL STUD SILL p SIZE OF END POST CONNECTED TO SSW = STEEL STUD WALL g, HOLDOWN "A" - PLAN TOB = TOP OF BEAM ELEVATION Q� CONFIGURATION AT HOLDOWN AT TOC = TOP OF CONCRETE SLAB FOUNDATION TOF = TOP OF FOOTING TOG = TOP OF GIRDER ELEVATION TOS = TOP OF STEEL ELEVATION TYP = TYPICAL LINO = UNLESS NOTED OTHERWISE FOOTING SCHEDULE MARK WIDTH LENGTH THICK LENGTHWISE REINF. CROSSWISE REINF. REMARKS NO. SIZE NO. FSIZE SPA. FC2 2'-0" CONT. 12" (2) #5 - - - FT5 5'-0" CONT. 14" (5) #5 -- #5 12"o.c. TOP & BOTTOM REINF. F2 -0" 40" 5 ) -- F4 4'-0" 4'-0" 14" (4) #5 (4) #5 -- AT F4S, TOP & BOTTOM REINF. F 5'- 5'-0" 16" 5) #6 (5 6 - TOP TO I F. F6 6'-0" 6'-0" 20" (6) #6 (6) #6 -- 3" CLEAR TYP. EQ. EQ. EQ. 3" CLEAR 3" CLEAR EQ. EQLIP. EQ. 3" CLEAR n . LIP aa 2" CLEAR n an3 1p n- a - a a :z3" CLEAR n 3" CLEAR TYPICAL FOOTING REINFORCING FOOTING SECTION TYP. FOOTING SECTION W/ TOP & BOTTOM REINF. 265 Winslow Way East Suite 202D Bainbridge Island Washington 98110 telephone 206 842 1253 e-mail frank@3rkarchitecture.com 1-3a-1D1 Y CONSULTANTS: cl� ENGINEERS structural consultants 1594 W. Park Cir. Ogden, Utah 84404 ph. 801.782.6008 4. 801.782 . 4656 W o z� 0 0� a Z Q = N Q cD 00 � = o' J N w v � J `^ QMill, L.L V J cn V vi U a a M � z in-z o 0 0 D rf) , 2i 0 � 2 N SCALE: ISSUE DATE:01/31/19 REVISIONS: 1 CITY REVIEW 04/05/19 2 OWNER REVISION 07/11/19 5 OWNER REVISION 03/18/20 REVIEW SET S003 31 r Ik architecture I design 265 Winslow Way East Suite 202D Bainbridge Island Washington 98110 telephone 206 842 1253 e-mail frank@3rkarchitecture.com • • a r®G 39160 W IENN 0 vAL G r ! 3a m! Y • CONSULTANTS: Is ENGINEERS structurai consuiLants 1594 W. Park Cir. Ogden, Utah 84404 ph. 801.782.6008 fx. 801.782.4656 0 0 N O N 0 0 z � 0 O } Q = N Z o 0 V 00 w U Q J _ • - �_ U c./) N N 2 N _U O Q o z z o O Z 0 > N 0 0 2 N w a 0 E w 0 a m T SCALE: ISSUE DATE:01/31/19 N N Ch REVISIONS: Q) E 0 U N 1 CITY REVIEW 04/05/19 2 OWNER REVISION 07/11/19 5 OWNER REVISION 03/18/20 REVIEW SET U S004 STRUCTURAL STEEL SPECIAL INSPECTION SCHEDULE ESTABLISHED PER 2015 IBC SECTION 1705.2.1 FABRICATOR SPECIAL INSPECTOR INSPECTION TASKS PRIOR TO WELDING (TABLE N5.4-1) QUALITY CONTROL QUALITY ASSURANCE NOTES INSPECTION TASKS PRIOR TO BOLTING (TABLE N5.6-1) CONTINUOUS PERIODIC CONTINUOUS PERIODIC NOTES CONTINUOUS PERIODIC CONTINUOUS PERIODIC WELDING PROCEDURE SPECIFICATIONS (WPSs) AVAILABLE • • 1. PERIODIC -OBSERVE THESE ITEMS ON A RANDOM BASIS. MANUFACTURER'S CERTIFICATIONS AVAILABLE FOR FASTENER MATERIALS • • 1. PERIODIC -OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS NEED NOT BE DELAYED PENDING THESE MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMABLES AVAILABLE • • FASTENERS MARKED IN ACCORDANCE WITH ASTM REQUIREMENTS • • OPERATIONS NEED NOT BE DELAYED PENDING THESE INSPECTIONS. MATERIAL IDENTIFICATION (TYPE /GRADE) • • INSPECTIONS. 2. CONTINUOUS -PERFORM THESE TASKS FOR EACH WELDED JOINT PROPER FASTENERS SELECTED FOR THE JOINT DETAIL (GRADE, TYPE, BOLT LENGTH IF THREADS ARE TO BE EXCLUDED FROM SHEAR PLANE) • • 2. CONTINUOUS -PERFORM THESE TASKS FOR EACH BOLTED CONNECTION. WELDER IDENTIFICATION SYSTEMS • • OR MEMBER. 3. QUALITY CONTROL (QC) SHALL BE PROVIDED BY THE FABRICATOR AND ERECTOR. 3. QUALITY CONTROL (QC) SHALL BE PROVIDED BY THE FABRICATOR AND ERECTOR. 4. QUALITY ASSURANCE (QA) SHALL BE PROVIDED BY OTHERS WHEN FIT -UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY) PROPER BOLTING PROCEDURES SELECTED FOR JOINT DETAIL • • * JOINT PREPARATION • • 4. QUALITY ASSURANCE (QA) SHALL BE PROVIDED BY OTHERS WHEN REQUIRED BY THE AUTHORITY HAVING JURISDICTION (AHJ), APPLICABLE BUILDING CODE (ABC), PURCHASER, OWNER, OR CONNECTING ELEMENTS, INCLUDING THE APPROPRIATE PAYING SURFACE CONDITION AND HOLE PREPARATION, IF SPECIFIED, MEET APPLICABLE REQUIREMENTS • • REQUIRED BY THE AUTHORITY HAVING JURISDICTION (AHJ), APPLICABLE BUILDING CODE (ABC), PURCHASER, OWNER, OR ENGINEER OF RECORD (EOR). NONDESTRUCTIVE TESTING (NDT) * DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL) CLEANLINESS (CONDITION OF STEEL SURFACES) ENGINEER OF RECORD (EOR). NONDESTRUCTIVE TESTING (NDT) SHALL BE PERFORMED BY THE AGENCY OR FIRM RESPONSIBLE FOR QUALITY ASSURANCE, EXCEPT AS PERMITTED IN PRE -INSTALLATION VERIFICATION TESTING BY INSTALLATION PERSONNEL OBSERVED AND DOCUMENTED FOR FASTENER ASSEMBLIES AND METHODS USED • • SHALL BE PERFORMED BY THE AGENCY OR FIRM RESPONSIBLE FOR QUALITY ASSURANCE, EXCEPT AS PERMITTED IN ACCORDANCE WITH SECTION N7. TACKING (TACK WELD QUALITY AND LOCATION) * BACKING TYPE AND FIT (IF APPLICABLE) ACCORDANCE WITH SECTION N7. 5. QC AND QA INSPECTORS SHALL BE QUALIFIED IN ACCORDANCE PROPER STORAGE PROVIDED FOR BOLTS, NUTS, WASHERS AND OTHER FASTENER COMPONENTS • • 5. FOR SNUG -TIGHT JOINTS, PRE -INSTALLATION VERIFICATION TESTING AS SPECIFIED IN TABLE N5.6-1 AND MONITORING OF THE CONFIGURATION AND FINISH OF ACCESS HOLES • • WITH AISC 360-10 CHAPTER N4. INSTALLATION PROCEDURES AS SPECIFIED IN TABLE N5.6-2 ARE FIT -UP OF FILLET WELDS 6. NONDESTRUCTIVE TESTING PERSONNEL SHALL BE QUALIFIED IN ACCORDANCE WITH AISC 360-10 CHAPTER N4.3. INSPECTION TASKS DURING BOLTING (TABLE N5.6-2) CONTINUOUS PERIODIC CONTINUOUS PERIODIC NOT APPLICABLE. THE QCI AND QAI NEED NOT BE PRESENT DURING THE INSTALLATION OF FASTENERS IN SNUG -TIGHT JOINTS. DIMENSIONS (ALIGNMENT, GAPS AT ROOT) • • 7. NONDESTRUCTIVE TESTING OF WELDED JOINTS SHALL COMPLY FASTENER ASSEMBLIES, OF SUITABLE CONDITION, PLACED IN ALL HOLES AND 6. FOR PRETENSIONED JOINTS AND SLIP -CRITICAL JOINTS, WHEN THE * CLEANLINESS (CONDITION OF STEEL SURFACES) WITH AISC 360-10 CHAPTER N5a AND b. 8. OBSERVATION OF WELDING OPERATIONS AND VISUAL INSPECTION WASHERS (IF REQUIRED) ARE POSITIONED AS REQUIRED • • INSTALLER IS USING THE TURN -OF -NUT METHOD WITH MATCHMARKING TECHNIQUES, THE DIRECT -TENSION -INDICATOR * TACKING (TACK WELD QUALITY AND LOCATION) OF IN -PROCESS AND COMPLETED WELDS SHALL BE THE PRIMARY JOINT BROUGHT TO THE SNUG -TIGHT CONDITION PRIOR TO THE PRETENSIONING • METHOD, OR THE TWIST -OFF -TYPE TENSION CONTROL BOLT CHECK WELDING EQUIPMENT • METHOD TO CONFIRM THAT THE MATERIALS, PROCEDURES AND WORKMANSHIP ARE IN CONFORMANCE WITH THE CONSTRUCTION OPERATION • METHOD, MONITORING OF BOLT PRETENSIONING PROCEDURES SHALL BE AS SPECIFIED IN TABLE N5.6-2. THE QCI AND QAI NEED FASTENER COMPONENT NOT TURNED BY THE WRENCH PREVENTED FROM ROTATING • • 'THE FABRICATOR OR ERECTOR, AS APPLICABLE, SHALL MAINTAIN A SYSTEM BY WHICH A WELDER WHO HAS WELDED A DOCUMENTS. FOR STRUCTURAL STEEL, ALL PROVISIONS OF AWS NOT BE PRESENT DURING THE INSTALLATION OF FASTENERS JOINT OR MEMBER CAN BE IDENTIFIED. STAMPS, IF USED, SHALL BE THE LOW -STRESS TYPE. D1.1 / D1.1M STRUCTURAL WELDING CODE -STEEL FOR WHEN THESE METHODS ARE USED BY THE INSTALLER. STATICALLY LOADED STRUCTURES SHALL APPLY. FASTENERS ARE PRETENSIONED IN ACCORDANCE WITH THE RCSC SPECIFICATION, 7. FOR PRETENSIONED JOINTS AND SLIP -CRITICAL JOINTS, WHEN THE INSPECTION TASKS DURING WELDING (TABLE N5.4-2) CONTINUOUS PERIODIC CONTINUOUS PERIODIC 9. THERMALLY CUT SURFACES OF ACCESS HOLES SHALL BE TESTED BY QA USING MT OR PT, WHEN THE FLANGE THICKNESS EXCEEDS PROGRESSING SYSTEMATICALLY FROM THE MOST RIGID POINT TOWARD THE FREE EDGES • • INSTALLER IS USING THE CALIBRATED WRENCH METHOD OR THE TURN -OF -NUT METHOD WITHOUT MATCHMARKING, MONITORING USE OF QUALIFIED WELDERS • • 2 IN. (50mm) FOR ROLLED SHAPES, OR WHEN THE WEB THICKNESS EXCEEDS 2 IN. (50mm) FOR BUILT-UP SHAPES. ANY CRACK SHALL BE DEEMED UNACCEPTABLE REGARDLESS OF SIZE OR LOCATION. OF BOLT PRETENSIONING PROCEDURES SHALL BE AS SPECIFIED IN TABLE N5.6-2. THE QCI AND QAI SHALL BE ENGAGED IN THEIR ASSIGNED INSPECTION DUTIES DURING INSTALLATION OF CONTROL AND HANDLING OF WELDING CONSUMABLES INSPECTION TASKS AFTER BOLTING TABLE N5.6-3 ( ) CONTINUOUS PERIODIC CONTINUOUS PERIODIC * PACKAGING • • 10. WHEN REQUIRED BY APPENDIX 3, TABLE A-3.1, WELDED JOINTS REQUIRING WELD SOUNDNESS TO BE ESTABLISHED BY FASTENERS WHEN THESE METHODS ARE USED BY THE INSTALLER. 8. OBSERVATION OF BOLTING OPERATIONS SHALL BE THE PRIMARY DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED CONNECTIONS • • * EXPOSURE CONTROL RADIOGRAPHICS OR ULTRASONIC INSPECTION SHALL BE TESTED METHOD USED TO CONFIRM THAT THE MATERIALS, PROCEDURES NO WELDING OVER CRACKED TACK WELDS • • BY QA AS PRESCRIBED. REDUCTION IN THE RATE OF UT IS PROHIBITED. AND WORKMANSHIP INCORPORATED IN CONSTRUCTION ARE IN CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS AND THE ENVIRONMENTAL CONDITIONS 11. REDUCTION OF RATE OF ULTRASONIC TESTING -THE RATE OF UT PROVISIONS OF THE RCSC SPECIFICATION. *WIND SPEED WITHIN LIMITS • • IS ONLY PERMITTED TO BE REDUCED IF APPROVED BY THE FOR AND THE AHJ PER AISC 360-10 CHAPTER Nye. INSPECTION OF STEEL ELEMENTS OF COMPOSITE NOTES * PRECIPITATION AND TEMPERATURE 12. FOR STRUCTURES IN RISK CATEGORY II, WHERE THE INITIAL RATE CONSTRUCTION PRIOR TO CONCRETE PLACEMENT TABLE N6.11) ( CONTINUOUS PERIODIC CONTINUOUS PERIODIC WPS FOLLOWED FOR UT IS 10%, THE NDT RATE FOR AN INDIVIDUAL WELDER OR 1. 0 -OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS WELDING OPERATOR SHALL BE INCREASED TO 100% SHOULD THE REJECT RATE, THE NUMBER OF WELDS CONTAINING UNACCEPTABLE DEFECTS DIVIDED BY THE NUMBER OF WELDS NEED NOT BE DELAYED PENDING THESE INSPECTIONS. 2. P -PERFORM THESE TASKS FOR EACH BOLTED CONNECTION. 3. QUALITY CONTROL (QC) SHALL BE PROVIDED BY THE FABRICATOR * SETTINGS ON WELDING EQUIPMENT PLACEMENT AND INSTALLATION OF STEEL DECK • • * TRAVEL SPEED PLACEMENT AND INSTALLATION OF STEEL STUD ANCHORS • • • • COMPLETED, EXCEEDS 5% OF THE WELDS TESTED FOR THE WELDER OR WELDING OPERATOR. A SAMPLING OF AT LEAST 20 COMPLETED WELDS FOR A JOB SHALL BE MADE PRIOR TO AND ERECTOR. 4. QUALITY ASSURANCE (QA) SHALL BE PROVIDED BY OTHERS WHEN REQUIRED BY THE AUTHORITY HAVING JURISDICTION (AHJ), * SELECTED WELDING MATERIALS DOCUMENT ACCEPTANCE OR REJECTION OF STEEL ELEMENTS • • * SHIELDING GAS TYPE /FLOW RATE IMPLEMENTING SUCH AN INCREASE. WHEN THE REJECT RATE FOR APPLICABLE BUILDING CODE (ABC), PURCHASER, OWNER, OR * PREHEAT APPLIED THE WELDER OR WELDING OPERATOR, AFTER A SAMPLING OF AT LEAST 40 COMPLETED WELDS, HAS FALLEN TO 5% OR LESS, THE ENGINEER OF RECORD (EOR). NONDESTRUCTIVE TESTING (NDT) SHALL BE PERFORMED BY THE AGENCY OR FIRM RESPONSIBLE * INTERPASS TEMPERATURE MAINTAINED (MIN. MAX) RATE OF UT SHALL BE RETURNED TO 10%. FOR EVALUATING THE REJECT RATE OF CONTINUOUS WELDS OVER 3 FT (1M) IN LENGTH WHERE THE EFFECTIVE THROAT IS 1 IN. (25mm) OR LESS, EACH 12 FOR QUALITY ASSURANCE, EXCEPT AS PERMITTED IN ACCORDANCE WITH SECTION N7. 5. FOR THOSE ITEMS FOR QUALITY CONTROL (QC) THAT CONTAIN AN * PROPER POSITION (F, V, H, OH) WELDING TECHNIQUES IN. (300mm) INCREMENT OR FRACTION THEREOF SHALL BE CONSIDERED AS ONE WELD. FOR EVALUATING THE REJECT RATE OBSERVE DESIGNATION, THE QC INSPECTION SHALL BE PERFORMED BY THE ERECTOR'S QUALITY CONTROL INSPECTOR * INTERPASS AND FINAL CLEANING • • ON CONTINUOUS WELDS OVER 3 FT (1M) IN LENGTH WHERE THE (QCI). * EACH PASS WITHIN PROFILE LIMITATIONS EFFECTIVE THROAT IS GREATER THAN 1 IN. (25mm), EACH 6 IN. (150mm) OF LENGTH OR FRACTION THEREOF SHALL BE 6. FOR WELDING OF STEEL HEADED STUD ANCHORS, THE PROVISIONS OF AWS D1.1 / D1.1M, APPLY. * EACH PASS MEETS QUALITY REQUIREMENTS CONSIDERED ON WELD. 7. FOR WELDING OF STEEL DECK, OBSERVATION OF WELDING INSPECTION TASKS AFTER WELDING (TABLE N5.4-3) CONTINUOUS PERIODIC CONTINUOUS PERIODIC 13. ALL NDT PERFORMED SHALL BE DOCUMENTED. FOR SHOP OPERATIONS AND VISUAL INSPECTION OF IN -PROCESS AND FABRICATION, THE NDT REPORT SHALL IDENTIFY THE TESTED COMPLETED WELDS SHALL BE THE PRIMARY METHOD TO CONFIRM WELDS CLEANED • • WELD BY PIECE MARK AND LOCATION IN THE PIECE. FOR FIELD WORK, THE NDT REPORT SHALL IDENTIFY THE TESTED WELD BY THAT THE MATERIALS, PROCEDURES AND WORKMANSHIP ARE IN CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS. ALL SIZE, LENGTH AND LOCATION OF WELDS • • LOCATION IN THE STRUCTURE, PIECE MARK, AND LOCATION IN THE APPLICABLE PROVISIONS OF AWS D1.3 / D1.3M, STRUCTURAL WELDS MEET VISUAL ACCEPTANCE CRITERIA PIECE. WHEN A WELD IS REJECTED ON THE BASIS OF NDT, THE NDT RECORD SHALL INDICATE THE LOCATION OF THE DEFECT AND WELDING CODE -SHEET STEEL, SHALL APPLY. DECK WELDING INSPECTION SHALL INCLUDE VERIFICATION OF THE WELDING * CRACK PROHIBITION THE BASIS OF REJECTION 14. DEMAND CRITICAL WELDS SHALL MEET THE PROVISION FOUND IN CONSUMABLES, WELDING PROCEDURE SPECIFICATIONS AND QUALIFICATIONS OF WELDING PERSONNEL PRIOR TO THE START *WELD /BASE -METAL FUSION AISC 341-10 AND WELDING METHODS, PROCEDURES AND QUALITY OF THE WORK, OBSERVATIONS OF THE WORK IN PROGRESS, AND CRATER CROSS SECTION • • CONTROL SHALL COMPLY WITH AWS D1.1 AND THE FOLLOWING: a. ARC STRIKES, GOUGES AND OTHER IMPERFECTIONS WITHIN A VISUAL INSPECTION OF ALL COMPLETED WELDS. FOR STEEL DECK ATTACHED BY FASTENING SYSTEMS OTHER THAN WELDING, *WELD PROFILES OR ADJACENT TO THE JOINT, SHALL BE REPAIRED OR INSPECTION SHALL INCLUDE VERIFICATION OF THE FASTENERS TO *WELD SIZE REMOVED. b. PREHEAT AND INTER -PASS REQUIREMENTS AS OUTLINED IN BE USED PRIOR TO THE START OF THE WORK, OBSERVATIONS OF THE WORK IN PROGRESS TO CONFIRM INSTALLATION IN *UNDERCUT SECTION 3.5. CONFORMANCE WITH THE MANUFACTURER'S RECOMMENDATIONS, * POROSITY C. UNREPAIRED CRACKS, GOUGES, AND NOTCHES WILL NOT BE PERMITTED IN THE JOINT AREA. d. USE ELECTRODES WITH CHARPY V-NOTCH ABSORBED ENERGY EQUAL TO OR GREATER THAN 20 FT-LBS AT 20 DEGREES FAHRENHEIT UNDER AWS A5 CLASSIFICATION TEST AND A VISUAL INSPECTION OF THE COMPLETED INSTALLATION. ARC STRIKES • • K-AREA' • • BACKING REMOVED AND WELD TABS REMOVED (IF REQUIRED) • • METHODS, AND 40 FT-LBS AT 70 DEGREES FAHRENHEIT USING REPAIR ACTIVITIES • • TEST PROCEDURES PRESCRIBED IN APPENDIX X OF AISC 358. ACCEPTABLE ELECTRODES INCLUDE E70TG-K2, E71 T-1. DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT OR MEMBER • • WHEN WELDING OF DOUBLER PLATES, CONTINUITY PLATES OR STIFFENERS HAS BEEN PERFORMED IN THE K-AREA, VISUALLY INSPECT THE WEB K-AREA FOR CRACKS WITHIN 3 IN. (75mm) OF THE WELD) GENERAL STEEL SPECIAL INSPECTION NOTES 1. QUALITY ASSURANCE (QA) INSPECTION OF FABRICATED ITEMS SHALL BE MADE AT THE FABRICATOR'S PLANT. THE QUALITY ASSURANCE INSPECTOR (QAI) SHALL SCHEDULE THIS WORK TO MINIMIZE INTERRUPTION TO THE WORK OF THE FABRICATOR. 2. QA INSPECTION OF THE ERECTED STEEL SYSTEM SHALL BE MADE AT THE PROJECT SITE. THE QAI SHALL SCHEDULE THIS WORK TO MINIMIZE INTERRUPTION TO THE WORK OF THE ERECTOR. 3. WHERE A TASK IS NOTED TO BE PERFORMED BY BOTH QC AND QA, IT IS PERMITTED TO COORDINATE THE INSPECTION FUNCTION BETWEEN THE QCI AND QAI SO THAT THE INSPECTION FUNCTIONS ARE PERFORMED BY ONLY ONE PARTY. WHERE QA RELIES UPON INSPECTION FUNCTIONS PERFORMED BY QC, THE APPROVAL OF THE ENGINEER OF RECORD AND THE AUTHORITY HAVING JURISDICTION IS REQUIRED. 4. THE FABRICATOR'S QCI SHALL INSPECT THE FABRICATED STEEL TO VERIFY COMPLIANCE WITH THE DETAILS SHOWN ON THE SHOP DRAWINGS, SUCH AS PROPER APPLICATION OF JOINT DETAILS AT EACH CONNECTION. THE ERECTOR'S QCI SHALL INSPECT THE ERECTED STEEL FRAME TO VERIFY COMPLIANCE WITH THE DETAILS SHOWN ON THE ERECTION DRAWINGS, SUCH AS BRACES, STIFFENERS, MEMBER LOCATIONS AND PROPER APPLICATION OF JOINT DETAILS AT EACH CONNECTION. 5. THE QAI SHALL BE ON THE PREMISES FOR INSPECTION DURING THE PLACEMENT OF ANCHOR RODS AND OTHER EMBEDMENTS SUPPORTING STRUCTURAL STEEL FOR COMPLIANCE WITH THE CONSTRUCTION DOCUMENTS. AS A MINIMUM, THE DIAMETER, GRADE, TYPE AND LENGTH OF THE ANCHOR ROD OR EMBEDDED ITEM, AND THE EXTENT OR DEPTH OF EMBEDMENT INTO THE CONCRETE, SHALL BE VERIFIED PRIOR TO PLACEMENT OF THE CONCRETE. 6. THE QAI SHALL INSPECT THE FABRICATED STEEL OR ERECTED STEEL FRAME, AS APPROPRIATE, TO VERIFY COMPLIANCE WITH THE DETAILS SHOWN ON THE CONSTRUCTION DOCUMENTS, SUCH AS BRACES, STIFFENERS, MEMBER LOCATIONS AND PROPER APPLICATION OF JOINT DETAILS AT EACH CONNECTION. 7. QUALITY ASSURANCE (QA) INSPECTIONS, EXCEPT NONDESTRUCTIVE TESTING (NDT), MAY BE WAIVED WHEN THE WORK IS PERFORMED IN A FABRICATING SHOP OR BY AN ERECTOR APPROVED BY THE AUTHORITY HAVING JURISDICTION (AHJ) TO PERFORM THE WORK WITHOUT QA. NDT OF WELDS COMPLETED IN AN APPROVED FABRICATOR'S SHOP MAY BE PERFORMED BY THAT FABRICATOR WHEN APPROVED BY THE AHJ. WHEN THE FABRICATOR PERFORMS THE NDT, THE QA AGENCY SHALL REVIEW THE FABRICATOR'S NDT REPORTS. 8. AT COMPLETION OF FABRICATION, THE APPROVED FABRICATOR SHALL SUBMIT A CERTIFICATE OF COMPLIANCE TO THE AHJ STATING THAT THE MATERIALS SUPPLIED AND WORK PERFORMED BY THE FABRICATOR ARE IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS. AT COMPLETION OF ERECTION, THE APPROVED ERECTOR SHALL SUBMIT A CERTIFICATE OF COMPLIANCE TO THE AHJ STATING THAT THE MATERIALS SUPPLIED AND WORK PERFORMED BY THE ERECTOR ARE IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS. 9. IDENTIFICATION AND REJECTION OF MATERIAL OR WORKMANSHIP THAT IS NOT IN CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS, SHALL BE PERMITTED AT ANY TIME DURING THE PROGRESS OF THE WORK. HOWEVER, THIS PROVISION SHALL NOT RELIEVE THE OWNER OR THE INSPECTOR OF THE OBLIGATION FOR TIMELY, IN -SEQUENCE INSPECTIONS. NONCONFORMING MATERIAL AND WORKMANSHIP SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE FABRICATOR OR ERECTOR, AS APPLICABLE. 10. NONCONFORMING MATERIAL OR WORKMANSHIP SHALL BE BROUGHT INTO CONFORMANCE, OR MADE SUITABLE FOR ITS INTENDED PURPOSE AS DETERMINED BY THE ENGINEER OF RECORD. 11. CONCURRENT WITH THE SUBMITTAL OF SUCH REPORTS TO THE AHJ, FOR OR OWNER, THE QA AGENCY SHALL SUBMIT TO THE FABRICATOR AND ERECTOR: (1)NONCONFORMANCEREPORTS (2) REPORTS OF REPAIR, REPLACEMENT OR ACCEPTANCE OF NONCONFORMING ITEMS. 0 31 r Ik architecture I design 265 Winslow Way East Suite 202D Bainbridge Island Washington 98110 telephone01 206 842 1253 e-mail frank@3rkarchitecture.com ��' WAS J Q� 3s8a kNG C'�+1I�1 1-3a-m! Y CONSULTANTS: 7� ENGINEERS structural consultants 1594 W. Park Cir. Ogden, Utah 84404 ph. 801.782.6008 fx. 801.782.4656 0 a M O N Q O M O z O O Q � = O z 0 00 Q J Uj U J I_L - U Ln _� Q � z o O O N z 2 d S c co fV 0 N O 0 2 fV w C O E W c O Q rn N �6 co SCALE: ISSUE DATE:01/31/19 N LO N M Cb REVISIONS: 1 CITY REVIEW 04/05/19 E 0 2 OWNER REVISION 07/11/19 5 OWNER REVISION 03/18/20 U N REVIEW SET rn L a) rn U S005 COIL STRAP LAP SPLICE SCHEDULE LAP SPLICE ITEM # MIN. #FASTENER MIN. LAP SPLICE LENGTH COMMENTS PER SPLICE STACKED SIDE -BY -SIDE 16-10d -- 9" CS 18 18-8d -- 11 " 12-10d -- 6" CS 20 14-8d -- 9" 10-10d -- 7" CS 22 12-8d -- 6" NOTES: 1. NO STRAP MODIFICATION IS ALLOWED. 2. SPLICE MUST MEET BOTH THE MINIMUM NUMBER OF FASTENERS AND THE MINIMUM SPLICE LENGTH. 3. ALL NAIL SIZES LISTED ARE COMMON NAILS. 4. 10d COMMON MAY BE REPLACED BY 16d SINKERS. NO OTHER NAIL SUBSTITUTION IS ALLOWED FOR LAP SPLICES. 5. IF WOOD SPLITTING OCCURS, USE EVERY OTHER NAIL HOLE AND LENGTHEN SPLICE TO ACCOMMODATE THE REQUIRED NUMBER OF NAILS. 6. ALL STRAPS TO BE INSTALLED UNDER SHEATHING. 7. TWO OPTIONS EXIST FOR COIL STRAP LAPPING. a. LAP ONE STRAP STACKED ON TOP OF THE OTHER STRAP. b. INSTALL STRAPS SIDE BY SIDE - TO DO THIS A LARGER BLOCK MUST BE USED. THE BLOCK MUST BE ON SOLID PIECE. 8. STRAP TO BE INSTALLED TIGHT. BOUNDARY NAILING PLYWOOD SHEATHING - SEE STRUCT. NOTES 3x6 x REQ'D BLOCKING SIMPSON STRAP -SEE PLAN STACKED LAP 2015 IBC CONC. REBAR LAP SPLICE SCHEDULE FOR CONCRETE APPLICATIONS (ACI 318 - 14) FACE OF JOINT OR FACE OF JOINT OR COUPLER OR CRITICAL SECTION CRITICAL SECTION WELDED SPLICE a o fd Is kdh 2' - 0" DEVELOPMENT LENGTH LAP SPLICE LENGTH HOOK DEVELOPMENT CLEAR LENGTH CONCRETE REINFORCING &SPLICE LENGTHS (IN) CONCRETE BAR SIZE BAR LOCATION #3 #4 #5 #6 #7 #8 #9 #10 #11 COMMENTS TYPE STRENGTH £d �s kd h fd Is Pd h fd Ps Pd h $d Is kd h fd Is fd h fd Is fd h kd fd h fd Pd h Ed Pd h VERT. WALL BARS, NWC 3000 PSI 17 22 8 22 29 8 28 36 10 33 43 12 48 62 13 55 72 15 62 17 69 19 76 30 FILL ON METAL DECK HORIZ. WALL BARS, NWC 3000 PSI 17 22 8 22 29 8 28 36 10 33 43 12 48 62 13 55 72 15 62 17 69 19 76 30 FOOTING TOP BARS BEAM BOTTOM BARS, NWC 3000 PSI 17 22 8 22 29 11 28 36 14 33 43 16 48 62 19 55 72 22 62 25 69 27 76 30 COLUMN BARS FOOTING BOTTOM NWC 3000 PSI 12 16 8 14 18 8 17 22 10 20 26 12 29 38 13 33 43 15 37 17 42 19 46 30 BARS BEAM TOP BARS NWC 3000 PSI 22 29 8 29 38 11 36 47 14 43 56 16 63 82 19 72 94 22 81 25 90 27 98 30 SLAB ON GRADE NWC 3000 PSI 12 16 8 14 18 8 17 22 10 20 26 12 32 42 13 42 55 15 53 17 69 19 76 30 CONCRETE REINFORCING &SPLICE LENGTHS (IN) CONCRETE BAR SIZE BAR LOCATION #3 #4 #5 #6 #7 #8 #9 #10 #11 COMMENTS EPE ]STRENGTH Id Is Ydh Yd Is Ydh Id Is Ydh Id Is Ydh Yd Ys Ydh fd Is Ydh fd Ydh fd Ydh fd Ydh VERT. WALL BARS, NWC 4500 PSI 14 18 7 18 23 6 23 30 8 27 35 9 40 52 11 45 59 13 51 14 56 16 62 25 FILL ON METAL DECK HORIZ. WALL BARS, NWC 4500 PSI 14 18 7 18 23 6 23 30 8 27 35 9 40 52 11 45 59 13 51 14 56 16 62 25 FOOTING TOP BARS BEAM BOTTOM BARS, NWC 4500 PSI 14 18 7 18 23 9 23 30 11 27 35 13 40 52 16 45 59 18 51 20 56 22 62 25 COLUMN BARS FOOTING BOTTOM NWC 4500 PSI 12 16 7 12 16 6 14 18 8 17 22 9 24 31 11 27 35 13 31 14 34 16 37 25 BARS BEAM TOP BARS NWC 4500 PSI 18 23 7 24 31 9 30 39 11 35 46 13 51 66 16 59 77 18 66 20 73 22 80 25 SLAB ON GRADE NWC 4500 PSI 12 16 7 12 16 6 14 18 8 17 22 9 27 35 11 34 44 13 44 14 56 16 62 25 METAL STUD SHEAR WALL SCHEDULE A.B. @FOUND. (NOTE 8) EDGE WALL MARK PLYWOOD SCREWS STUD GA COMMENTS SHEATHING (SEE NOTES 2 (MIN.) DIA. SPA. (CDX U.N.O.) & 3) SW-1 15/32" 6"o.c. 16 3/4" DIA. 32"o.c. USE 7/8" SIMPSON SSTB28, OR APPROVED EQUAL, FOR ALL HOLD DOWNS U.N.O. SEE 8/S203 NOTES: 1. ALL SHEATHING PANEL EDGES TO BE BLOCKED. 2. ALL SCREWS SHALL BE #8 TEK SCREW MIN. 3. FIELD SCREW TO BE SAME SCREWS @ 12"o.c. 4. AT SHEAR WALLS W/SHEATHING ON BOTH SIDES, BOTH VERTICAL AND HORIZONTAL JOINTS ON OPPOSITE SIDES OF THE WALL SHALL BE STAGGERED. 5. SHEATHING SHALL BE STAMPED W/ APA STAMP. O.S.B. OF EQUIVALENT THICKNESS, GRADE, AND RATING MAY BE USED IN LIEU OF PLYWOOD. 6. ALL A.B.TO HAVE MIN. 8" EMBEDMENT INTO CONCRETE. 7. SEE 4/S206 FOR ANY LOCATIONS WHERE TRACK SPLICES OCCUR. 31 r Ik architecture I design Suite 202D Bainbridge Island Washington 98110 telephone 206 842 1253 e-mail frank@3rkarchitecture.com r was `,r 39160 ®�. k 1 is-m) 9 CONSULTANTS: structural consultants 1594 W. Park Cir. Ogden, Utah 84404 ph. 801.782.6008 fx. 801.782.4656 a rn �n M O N 0 O N 0 0 O� 1 � = z O c� 00 i J W U J C/) Q � — cn U c� (D Q Q o o z O O N 2 d z S c coN fV 0 O 0 2 fV w C O E W c O Q rn N �6 CO SCALE: ISSUE DATE:01/31/19 CA N M Cb REVISIONS: 1 CITY REVIEW 04/05/19 E 0 2 OWNER REVISION 07/11/19 5 OWNER REVISION 03/18/20 U N REVIEW SET rn L a) rn U S006 SPECIAL INSPECTION SCHEDULE 1, 2 ESTABLISHED PER 2015 IBC SECTION 110 AND CHAPTER 17 31 r Ik architecture I design 265 Winslow Way East Suite 202D Bainbridge Island Washington 98110 telephone 206 842 1253 e-mail frank@3rkarchitecture.com w�' J S Q� 3918a �h► 1-3a-m! Y CONSULTANTS: ENGINEERS Flj structural consultants 1594 W. Park Cir. Ogden, Utah 84404 ph. 801.782.6008 fx. 801.782.4656 (TYP.) < o 0 <N M 0 N 0 0 N 0 0 oQ � = O z (_� OO w Q J U J Q � C/) - c/) U c/) Q Q n o � z O 0 N N 2 z U co 0 N 0 2 N C O E W c O Q rn N �6 SCALE: ISSUE DATE:01/31/19 N LO N M Cb REVISIONS: 1 CITY REVIEW 04/05/19 E 0 2 OWNER REVISION 07/11/19 5 OWNER REVISION 03/18/20 U N REVIEW SET rn L a) rn U S007 WALL SCHEDULE BRIDGING OPTIONS MARK STUD SPACING TOP TRACK BOTTOM TRACK COMMENTS WHERE BRACING TERMINATES AT BUILT- UPJAMB OR POST, EXTEND CHANNEL INTO PUNCH -OUT. USE 2" x 2" x 16 GA. CLIP ANGLE 1-1/4" LESS THAN STUD WIDTH. ATTACH USING (4) #8 SCREWS. 1-1/2" x 16 GAUGE COLD ROLLED CHANNEL. TO BE SPACED AS REO'D PER EXTERIOR FRAMING NOTES 2" x 2" x 16 GAUGE CLIP ANGLE 1/4" LESS THAN STUD WIDTH. ATTACH USING (4) #8 SCREWS. CLIP ANGLE TO BE PLACED AT EACH STUD. OPTION 1 � TSN BRIDGEBAR OR COLD ROLLED CHANNEL OPTION 2 TSN BRIDGECLIP BC600 @ EA. STUD -SEE SCHED. ADDITIONAL SCREWS FOR LOAD BEARING APPLICATIONS SSW-1 800S162-54 16"o.c. 800T150-54 800T150-54 BRIDGING @ 4'-0"o.c. WHERE SHEATHING IS NOT ATTACHED ON BOTH FLANGES OF STUD NOTE: 1. USE SSW-1 UNLESS NOTED OTHERWISE. 2. ATTACH BOTTOM TRACK TO FOUNDATION WALL PER 11/S206 JAMB STUD SCHEDULE 5 EDA CONFIG. 1 CONFIG. 2 #8 SCREWS @ 24"o.c. (TYP.) MARK MAX. OPENING # OF JAMB STUDS CONFIGURATION CONCRETE CONNECTION ROOF CONNECTION COMMENTS CONNECTOR ANCHOR CONNECTOR ANCHORAGE S - 6 9 206 9 206 SE FOR CO ION SSJ-2 20'-0" (3) 2 7/S206 7/S206 9 & 10/S206 9 & 10/S206 SEE PLAN FOR ROOF CONNECTION SSJ-3 SEE PLAN (2) 1 7/S206 7/S206 -- -- HEADER SCHEDULE #8 SCREWS o.c. 5 Q HORIZONTAL SECTION (TYP.) VERTICAL SECTION (TYP.) CONFIG. 1 #8 SCREWS o.c. Q 51� CONFIG.2 IZONTAL SECTION (T P.) VERTICAL SECTION (TYP.) MARK MAX. OPENING VERT. SECTIONS HORIZ. SECTIONS CONFIGURATION HEADER CONNECTION COMMENTS 8 2-54 80 -54 6 SSH-2 20'-0" (2) 1200S162-54 (1) 800S350-68 & (2) 800T350-68 2 5/S206 SSH-3 SEE 7/S207 (2) 362S162-33 (2) 362T125-33 1 5/S206 SEE DETAIL 7/S207 SILL SCHEDULE SILL TRACK -SEE SCHED. CONFIG. 1 MARK MAX. OPENING SILL COMPONENTS CONFIGURATION SILL CONNECTION ANGLE COMMENTS SSS-1 10'-0" 800T150-54 1 5/S206 USE SAME CLIP AS SHOWN IN HEADER DETAIL 7 0 <V M 0 N 0 N 00 Cl) 0 0 A i EXISTING REINFORCED CONCRETE TILT -UP WALL i Lj o /i X', i rTrti r I Y Y - - - ar Q EXISTING REINFORCED CONCRETE TILT -UP WALL F \CO r-�CISTING REINFORCED DNCRETE TILT -UP WALL EXISTING REINFORCED CONCRETE TILT -UP WALL o 4 S 2 02 5�\\�00� S 2 C i L+ i - - -- F4S s' S203 TYP 5 353.03 \ / SW 1 S202 5' 9 C D E F G EXISTING REINFORCED 0 / CONCRETE TILT -UP WALL FC2 i 5 -�-�- - - - - - 1 - - - - - - - 353.03 - - TYP - - - - - S203 F5 i S202 , , 353.03 Cp 2X6S FC2 O+ 355.03 F6 ��I FC2 / � � I 353.03 353.03 I � TYP @ I 5 2x4 STUDS AT 16"o.c. - SEE INTERIOR TYP ARCH FOR FINISHES I S203 F6 (S263)7`VERIFY EXIST. COLUMN WALL`bTHICKNESS IN FIELD. IF WALL353.03O F5 THICKNESS IS LESS THAN 1/4", �55 353.03 CONSULT STRUCTURAL ENGINEER tis F+,ss� cp H 6X6 CO Cp3j8 �� � FC2 5 353.03 F5 S207 TYP / 353.03 F TY F. - .0 FC2 S203 \/"5 O 353.03 CONSULT STRUCTURAL ENGINEER 5G' Q IF LESS THAN 6'-0" SQUARE. VERIFY ySS O FOOTING SIZES UNDER THESE 6X6X3/ 1 L COLUMNS 8 5 g Cp,1 TYP �+ .�• ��� F5 S207 i 353.03 353.03 `r �� F5 - 3 . l� i F4 F4 354.53 354.53 F4 -1�+J �'SoN I FC2 / Cp X/2 354.53 & o+o 353.03 +�\S203 F4 TYP +� VERIFY EXIST. COLUMN WALL 354.53 LSD F4 ��� THICKNESS IN FIELD. IF WALL 5 +�� THICKNESS IS LESS THAN 5/16", TYP 354.53 LSD CONSULT STRUCTURAL ENGINEER S203 L- J F I / F6 I I N / SIM. L -1 F5 353.03 , +off , F4 5 1 \ o EXISTING REINFORCED F4 354.53 S202 S202 ��D 354.53 CONCRETE TILT -UP WALL _ _ tK 4 ,�.O�� C S202 - S202 - 5 TYP FC2 0 6 , + T L S S203 353.03 / S202 353.03 y SW-1 I / �O 5 9„ 5/ �s/BOG>> +�+h� / 8�iS�G,, OOP/& �5 sQ i TYP @ 1 I FC2 FC2 CARPORT S203 353.03 353.03 I ` ' 51 6 6 �s � S203 TYP �r� SSS-1 5CO 55� SSS-1 Cam, S203 CS' F4S 4�BooOG�� FC2 ��O �`'� +D+� 4`%oO�G>> 353.03 SW-1 �s353.03 /5\ 13'-0" SW 1 FOOTING & FOUNDATION PLAN A SCALE: 1/8" = V-0" S 101 31 r Ik architecture I design FOOTING & FOUNDATION NOTES : 1. SEE SHEET S001 FOR GENERAL STRUCTURAL NOTES. 2. ALL FOOTINGS SHALL BE PLACED ON SOIL WHICH HAS BEEN PREPARED FOR THE BEARING PRESSURE SHOWN IN THE STRUCTURAL NOTES. 3. VERIFY ALL DIMENSIONS WITH DRAWINGS AND NOTIFY ENGINEER OF ANY DISCREPANCIES FOUND. 4. SEE SHEET S002 FOR FOOTING SCHEDULE. 5. PROVIDE DOWELS IN FOOTINGS / FOUNDATIONS TO MATCH VERTICAL WALL REINFORCING U.N.O. 6. SEE SHEET S201 FOR TYPICAL FOOTING AND FOUNDATION DETAILS. 7. ALL EXTERIOR WALL FOOTINGS TO BEAR A MINIMUM DIMENSION BELOW EXTERIOR GRADE AS NOTED IN GENERAL STRUCTURAL NOTES. 8. FOUNDATION WALLS ARE DESIGNED AND DETAILED FOR THE COMPLETED CONDITION. CONTRACTOR IS RESPONSIBLE FOR MEANS AND METHODS OF CONSTRUCTION. BACKFILLED WALLS SHALL BE ADEQUATELY BRACED DURING CONSTRUCTION AND BACKFILLING TO PRODUCE PLUMB AND TRUE FINISHED WALLS. 9. ALL ANCHORS, HOLD-DOWNS, ANCHOR BOLTS, DOWELS, EMBEDDED ITEMS, ETC. SHALL BE HELD IN PLACE PRIOR TO AND DURING CONCRETE AND/OR GROUT PLACEMENT. 10. COORDINATE ALL FOOTING DEPTHS (INTERIOR AND EXTERIOR) WITH DRAINS, CONDUITS, ETC. THAT MAY INTERFERE WITH FOOTINGS. U 0 E L A L TO BE 8" THICK. SEE STRUCTURAL NOTES FOR REl FORCING. 12. SEE DETAIL 5/S207 FOR CP-1 SIZE AND REINFORCING. 1. SLAB ON GRADE SHALL BE 6" THICK REINFORCED CONCRETE U.N.O. SLAB SHALL BE UNDERLAIN BY FREE DRAINING MATERIAL AS PRESCRIBED IN THE SOILS REPORT. 2. SEE SHEET S201 FOR CONTROL AND CONSTRUCTION JOINT INFORMATION. 265 Winslow Way East Suite 202D Bainbridge Island Washington 98110 telephone 206 842 1253 e-mail frank@3rkarchitecture.com 1-3a-1D1 Y CONSULTANTS: BE ENGINEERS structural consultants 1594 W. Park Cir. Ogden, Utah 84404 ph. 801.782.6008 4. 801.782 . 4656 Q 0 z 0 Q z rn rn O p � Q H Z � = o Q c� 00 J J v < C/) Q LL. N V U a Q 0 � � o z 0 0 z 0 2 N SCALE: ISSUE DATE:01/31/19 REVISIONS: 1 CITY REVIEW 04/05/19 2 OWNER REVISION 07/11/19 5 OWNER REVISION 03/18/20 REVIEW SET S101 WE co 0 N 0 N O N co co O 0 0 ��y -------------------------------------- a - I C 31 r Ik architecture I design D E F G I � -�- - - -- - - - - - - - ---- - - I I / - - - -- - - - - - - - - -- - -- TEMPORARY SHORING TO BE / PROVIDED FOR NEW WALL, CONTRACTOR EAM AN D ST INSTALLATION / 10 S207 / / / I 3 I / OPP. / S207 Q / / 6 � NEW 2x12 SISTERED TO EACH S207 EXISTING 2x JOIST. SISTERED MEMBER TO BE CONT. BETWEEN J BEARING POINTS G LL J / 4 z of S207 7 O LL X S207 o U w Cf) / Z I c) I � I I ---- -----I-- ' S207 O 0 I � � 3 S207 � I I // I / I / TEMPORARY SHORING TO BE / PROVIDED BY CONTRACTOR / FOR NEW BEAM AND POST INSTALLATION / o / / / I / , WOOD FLOOR FRAMING NOTES: 1. FOR FLOOR SHEATHING AND NAILING REQUIREMENTS, SEE STRUCTURAL NOTES ON SHEET S001. 2. — — —INDICATES SIMPSON STRAPS. CENTER OVER TOP PLATE WITH JOISTS AND / OR 2x FLAT BLOCKING BELOW. SEE SCHEDULE. 3. SEE STRUCTURAL NOTES FOR REQUIRED DECK AND ATTACHMENTS. 4. CONTRACTOR SHALL ERECT AND MAINTAIN ADEQUATE TEMPORARY BRACING UNTIL ALL FLOOR FRAMING AND DECK ATTACHMENTS ARE COMPLETE. 265 Winslow Way East Suite 202D Bainbridge Island Washington 98110 telephone 206 842 1253 e-mail frank@3rkarchitecture.com CONSULTANTS: is IN, ENGINEERS structural consultants 1594 W. Park Cir. Ogden, Utah 84404 ph. 801.782.6008 4. 801.782.4656 Q 0 z 0 Q z rn O p � Q � Z Q = N Q cD 00 � = o' J N w v < J `^ V J cn V vi U a a M � z in—z o 0 0 D rf) , 0 2 N Lu SCALE: ISSUE DATE:01/31/19 REVISIONS: 1 CITY REVIEW 04/05/19 SECOND FLOOR & CANOPY FRAMING PLAN A 2 OWNER REVISION 07/11/19 SCALE : 1/8" = V-0° 1Sj J12 5 OWNER REVISION 03/18/20 REVIEW SET S102 WE 00 0 N M 0 N 0 N 00 co O A 6 C D E 6 1 S205 OPP TYP S204 3EAM (OMF) H 3EAM (OMF) 3EAM (OMF) H 5 -- - - - - - - - - - - - - - - - - 3 S205 2 w S204 Z N CO = N C0 U) 10 TYP S206 - - - - - - TYP S205 U 0 0 LO z_ J a W W N N co LD x W 13 9 8 S202 S202 48 psf ADD \ SNOW DRIFT o o in i N � I = J N Cl) W Z I 4 4 S204 - - - - W16X26 (NEW)- - - - S204 - SSH-1 SSH-1 XO6 YP -1- S205 w z Q M x w Q -> W W 00 z co F_: x S�) o W 1 ' - S205- - Q w m x w w z M x CD W16X26 (NEW) I 5 DRAG CONNECTION S204 W16X26 (NEW) 4 SIM _ S205 I w z 42 psf ADD SNOW DRIFT 10'-01, I F W12X26 (NEW) I� W14X22 (NEW) 4TYP x o ~ I RTU ADD LOAD 1500# I 0 I 4 TYP I S205 I W z LO co 00 I W18X35 (NEW) 7 S205 3 TYP S204 o x W N_ Y o W w 3 W z 7 z P o CD x W >< w ozRTU w po<� ~ ADD X z LOAD 1500# co 4 SIM S205 2 W 12X14 (NEW) 1OX12 (NEW)` TYP S205 DRAG CONNECTION 5 rn i 12X19 (NEW) S204 �^ 1 5 TYP OPP S204 S205 S2 5 10 TYP S206 ROOF FRAMING PLAN A SCALE: 1/8" = 1'-0" S 103 i ROOF FRAMING NOTES 42 psf ADD SNOW DRIFT 10'-01, G 8 � S204 TYP p0 P I �k P w U 'cam N d W I �n O 6 Q. TYP 204 �k P I R) P P 7 TYP S204 P 1 TYP @ MOMENT S206 FRAME �k Ali U) W U Q Q_ t7 0 W Z t7 W U Q 0- U) 0 In Z 31 r Ik architecture I design 1. SEE SHEET S001 FOR GENERAL STRUCTURAL NOTES. 2. GENERAL CONTRACTOR SHALL VERIFY MECHANICAL EQUIPMENT WEIGHTS, DIMENSIONS, AND LOCATIONS W/ MECHANICAL AND REFRIGERATION CONTRACTORS PRIOR TO ORDERING/FABRICATING JOISTS. 3. (### / ### ) DENOTES APPLIED TOTAL AND LIVE UNIFORMLY DISTRIBUTED LOADS IN POUNDS PER LINEAR FOOT OF JOIST, RESPECTIVELY. 4. JOISTS SUPPORTING MECHANICAL EQUIPMENT SHALL BE DESIGNED FOR ADDITIONAL LOADS INDICATED. 5. SNOW DRIFT LOADS INDICATED ON FRAMING PLANS SHALL BE APPLIED IN ADDITION TO UNIFORMLY DISTRIBUTED LOADS INDICATED PER NOTE 3. 6. PROVIDE ADDED HORIZONTAL AND VERTICAL JOISTS LOADS WHERE INDICATED ON PLAN OR DETAILS. 7. JOISTS AND GIRDERS SHALL BE DESIGNED FOR 15 PSF NET WIND UPLIFT, OR PER SCHEDULE ON SHEET S002 8. SEE ROOF DECK SCHEDULE FOR REQUIRED DECK AND ATTACHMENTS. 9. SEE SHEET S201 FOR OPENINGS IN ROOF DECK. SEE MECHANICAL AND ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS. 10. CONTRACTOR SHALL ERECT AND MAINTAIN ADEQUATE TEMPORARY BRACING UNTIL ALL ROOF FRAMING AND DECK ATTACHMENTS ARE COMPLETE. 11. CONCENTRATED LOADS FROM EQUIPMENT, PIPING, ETC., SHALL NOT BE HUNG FROM JOISTS EXCEPT AT PANEL POINTS AND AS APPROVED BY THE ENGINEER. 12. JOIST BRIDGING DESIGN AND LOCATION BY JOIST MANUFACTURER. 13. ANY CONCENTRATED LOAD ON JOIST CHORDS (INCLUDING FRAMING ANGLES) NOT LOCATED WITHIN 6" OF A PANEL POINT REQUIRE (2) L 2" X 2" X 1/4" FROM THE POINT LOAD TO THE NEAREST OPPOSITE CHORD PANEL POINT (CONTRACTOR SUPPLIED AND INSTALLED). 14. ANY ROOF SUPPORTED PIPING 6" OR LARGER RUNNING PARALLEL TO JOIST SHALL BE SUPPORTED BY TWO OR MORE JOISTS. 15. ALL JOISTS TO HAVE 2 1/2" JOIST SEAT. 265 Winslow Way East Suite 202D Bainbridge Island Washington 98110 telephone 206 842 1253 e-mail frank@3rkarchitecture.com CONSULTANTS: ENGINEERS structural consultants 1594 W. Park Cir. Ogden, Utah 84404 ph. 801.782.6008 fx. 801.782 . 4656 Q 0 z >_ Q z rn O p � Q � Z Q = N Q cD 00 J w v < J `^ Q L.L V J cn V vi U a a M � z � z o 0 0 � 2 N SCALE: ISSUE DATE:01/31/19 REVISIONS: 1 CITY REVIEW 04/05/19 2 OWNER REVISION 07/11/19 5 OWNER REVISION 03/18/20 REVIEW SET S103 POUR #1 DIAMOND BLOCKOU COLUMN POUR #2 POUR #3 NOTES: 1. JOINTS SHALL OCCUR AT MAIN COLUMN/GRID LINES W/ 10'-0" MAX. SPACING BETWEEN JOINTS @ 4" SLABS; 12'-0" MAX. @ 5" SLABS, & 15'-0" MAX. @ 6" SLABS. 2. SEE PLAN FOR SLAB THICKNESS'T' AND REINFORCING SIZE AND SPACING. TYPICAL CONCRETE SLAB JOINTS SCALE : NONE PLATE DOWELS @ 24"o.c. OR 1/2"0 x 18" UNBONDED DOWELS @ 18"o.c. SLAB REINFORCEMENT (WHERE OCCURS) TERMINATE 3" FROM CONC. FLOOR SLAB EA. SIDE OF CONSTRUCTION JOINTS a ° ° a Z SAWN OR FORMED JOINT °14 , CONC. FLOOR SLAB 18" 8... 18" - = - a 9 ,a ' III _III II III —III III III III —III III ' NOTE: THICKENING OF SLAB T -SLAB THICKNESS NOT REQUIRED FOR SLABS SLAB REINFORCEMENT WITH T = 6" OR GREATER T = SLAB THICKNESS (WHERE OCCURS) CONSTRUCTION JOINT CONTROL JOINT B SCALE: NONE A SCALE: NONE (2) #6 DOWELS (@ / CONCRETE FOUND. �Q WALLS ONLY) 30" TYP. FOUNDATION 24" REINFORCEMENT T = FOOTING THICKNESS H = FOOTING STEP HEIGHT ° a 4a O a a NTYP. FOUNDATION ° � REINFORCEMENT a4 III -III a a °e IIII 4 o FOOTING REINF. (TOP - 1 a CV - c> STEEL WHERE OCCURS) -III III°I III III III II III III II a 4 ° N 2 x ,H, °b\ e FOOTING OUTLINE 00 _ a° a I�IIII1° d =III NOTES: 1. FOUNDATION REINFORCING NOT SHOWN FOR CLARITY. 2. SEE FOOTING SCHEDULE FOR FOOTING WIDTH AND REINFORCING SIZE AND LOCATION. ALL FOOTING REINFORCING REFERENCED IN THE SCHEDULE OR SHOWN IN THE DETAILS MUST RUN CONTINUOUS THROUGH THE FOOTING STEP. TYPICAL STEPPED FOOTING SCALE : NONE NON-SHI VERIFY 1 TOP OF PIER / FC GRADE I HEADED ANCHOR BOLT THREADED ROD TYPICAL ANCHOR BOLT EMBEDMENT DETAIL SCALE : NONE PLAN VIEW (2) #4 x 4'-0" BARS SHALL BE PLACED IN THE SLAB WHERE CONTROL OR CONSTRUCTION JOINTS INTERSECT ONE ANOTHER BUT DO NOT CONTINUE PAST THE JOINT. C.J. (2) #4 x 4'-0" BARS SHALL BE PLACED IN THE SLAB WHERE CONTROL OR CONSTRUCTION JOINTS DO NOT EXTEND FROM THE CORNERS OF COLUMN BLOCK -OUTS IN SLABS. (2) #4 x 4'-0" BARS SHALL BE PLACED IN THE SLAB WHERE CONTROL OR CONSTRUCTION JOINT INTERSECTIONS DO NOT OCCUR AT DEPRESSED SLAB CORNERS. U DEPRESSED SLAB PLAN VIEW TYPICAL CONTROL JOINT DETAIL PLAN VIEW 52O1 SCALE : NONE NOTE: TYPICAL FOUNDATION WALL REINF. NOT SHOWN FOR CLARITY. CONCRETE OR CMU FOUNDATION WALL UTILITY TRENCHES Lu I I BACK FILL & COMPACT PER ° ° tl4 6a_I (1) #5 x24" ABOVE & BELOW GEOTECHNICAL REPORT_7A J — SLEEVE IN FOUNDATION WALLS a a s d -° Illllllllllilllllllllllllll ��i�i, .4 a TT PIPE TO CLEAR SLEEVE a da BY 1 ALL AROUND ° °� °° - -I a ' °_ 4� ° a NO PIPES ALLOWED TO ° 4 _a ° . ° �. 4 a uJ III > III 4 a . � a : II 1= PASS THROUGH FTGS. 1 1 a a d w III , a : "II _ OR GRADE BEAMS d a a ° °tr,, -l1 4 a a- w 11I III a 4 4 , . e1 °_ —I— cJnMIN. II 24" MAX.a ° a 2 IIIIIIII IIIF ° °III �I—ill BOTTOM OF FOOTING �� ��� 1 7 �°-I1YI MIII III III —III _III 7757— NOTE :THICKEN FOOTING WHERE FOR OPENINGS LARGER THAN 12" IN ANY PIPE IS LESS THAN 24" DIRECTION - SEE STRUCTURAL NOTE E-7. BELOW BOTTOM OF FOOTING NO DIGGING FOR PIPE TRENCH PARALLEL TO FOOTING WITHIN THIS BOUNDARY NOTE: 1. DETAIL IS SIMILAR AT MASONRY FOUNDATION WALLS. 2. SEE TYPICAL DETAIL FOR MULTIPLE WALL 2 S2O1 PENETRATIONS. PIPE PARALLEL TO FOOTING PIPE CROSSING FOOTING / FOUNDATION WALL 4 ALLOWABLE PIPING LOCATIONS @ FOOTING DETAIL r5 52O1 SCALE : NONE �21 1" MIN. NUT THICKNESS BASE PL. THICKNESS - SEE APPROPRIATE SCHED. OR DETAIL EMBEDMENT LENGTH - SEE DETAILS FOR MIN. EMBEDMENT LENGTH BOLT HEADS / NUT THICKNESS 1 THREAD MIN. 3" MIN. CLEAR 14 GA. STEEL SHEET 12" MIN. BEYOND OPFnlmlr: Fora \AioV ALL SIDES 'EK SCREWS AT 6"o.c. A WAY < PENETRATION NOTES: 1. USE DETAIL FOR FOLLOWING CONDITIONS NO ADDED LOAD NOTED ON PLANS. (1) TO (3) DECK FLUTES ARE PENETRATED. 2. FOR OPENINGS GREATER THAN THREE FLUTES (18") - SEE TYP. DETAIL TYPICAL FRAMING @ SMALL ROOF 7 OPENINGS S2O1 SCALE : NONE 3/4" 6" METAL DECK - SEE PLAN SEE ARCH. / MECH. PLAN L ANGLE (TYPICAL) ALL AROUND \ 3/16"I OPENING - SEE SCHEDULE V SUPPORT MEMBER - SEE PLAN SPAN LENGTH 'L'= JOIST SPACING OR LENGTH OF OPENING n PARALLEL WITH JOISTS, WHICHEVER IS GREATER SPAN ANGLE SIZE L<_6'-0" L4x4x1/4 L<_8'-0" L4x4x3/8 L <_ 10'-0" L 5 x 5 x 3/8 TYP. @ PERIMETER OF OPENING L TO FRAMING 1/4" 3" MIN. TYP. TYP. NOTES: 1. THIS DETAIL APPLIES TO ROOF OPENINGS LARGER THAN 18" IN EITHER DIRECTION. 2. MECHANICAL CURB ATTACHMENT TO STRUCTURE IS BY OTHERS. 3. THIS DETAIL OCCURS UNDER THE CURB AND AROUND THE OPENING. WHERE NO OPENING OCCURS, FRAME OCCURS BELOW CURB ONLY. TYP. FRAMING @ ROOF OPENINGS & 8 ROOFTOP EQUIPMENT DETAIL S2O1 SCALE : NONE 9 S2O1 SLEEVE DIAMETER PIPING/CONDUIT THRU SLAB OR WALL —0 --a 0 AC�-- C� � 3D MAX 'D' = T/3 OR 2", WHICHEVER IS SMALLER NOTE: WHERE CLEAR DISTANCE BETWEEN SLEEVES IS IMPOSSIBLE, THIS AREA SHALL BE TREATED AS AN OPENING PER REINFORCING AT STRUCTURAL CONCRETE SLAB OPENINGS, SEE TYPICAL DETAIL. PIPING/CONDUIT IN SLAB OR WALL TYP. PIPING/CONDUIT AT SLAB OR WALL SCALE : NONE fn NOTES: 1. fs = LAP SPLICE LENGTH - SEE REBAR LAP SCHEDULE 2. VERTICAL BARS NOT SHOWN 3. THIS DETAIL IS APPLICABLE AT ALL FOOTINGS AND FOUNDATION WALLS fs fs a pp °I 4 a a - 4 4 DOUBLE MAT a � INTERSECTION CORNER 4 ALTERNATE BENDS, TYP. ° fs Is a a° a SINGLE INTERSECTION CORNER TYP. REINF. @ INTERSECTIONS IN CONC. DETAIL SCALE : NONE C TYPE S13P-1 TYPE SBP-2 A = 1/2" MIN. B = 1 1/2" C=3"MIN. TYPICAL BASE PLATE SCALE : NONE a 31 r Ik architecture I design 3 S201 6 S2O1 J ■ B C B TYPE SBP-3 10 S2O1 265 Winslow Way East Suite 202D Bainbridge Island Washington 98110 telephone 206 842 1253 e-mail frank@3rkarchitecture.com 1-3a-m! Y CONSULTANTS: Is ENGINEERS structural consultants 1594 W. Park Cir. Ogden, Utah 84404 ph. 801.782.6008 fx. 801.782.4656 Q 0 z 0 Q z rn O p > Q � (10 Z Q = N Q cD 00 >_ J w v � J `^ Q L.L V J cn V vi U a a M � z in- z o 0 0 0 � 2 N SCALE: ISSUE DATE:01/31/19 REVISIONS: 1 CITY REVIEW 04/05/19 2 OWNER REVISION 07/11/19 5 OWNER REVISION 03/18/20 REVIEW SET S201 7 N 0 N 0 N 00 Cl) r a 4 .. =a EXISTING CONCRETE WALL d a - 4= 4 ° EXISTING SLAB ON GRADE d b d A.. d_ -I 4 d as d a a ° EXISTING FOUNDATION - WALL & FOOTING 'I 4 s .II -III ° d a d • 4 � s TYP. FOOTING & FOUNDATION INTO EXISTING FOOTING & FOUNDATION SCALE: NONE EXISTING CONCRETE WALL DRILL & EPDXY 6" INTO EXIST. FDN WALL FIELD VERIFY )IIIIIII FIELD -III VERIFY IIIIIII -�II,I�II1 EXISTING STRIP FOOTING DETAIL SCALE: NONE EXIST. TILT UP WALL - FIELD VERIFY FIELD VERIFY BEAM TO WALL CONNECTION HSS COLUMN - SEE PLAN ANGLE CLIP - SEE 5/S202 DETAIL SCALE: NONE d 3/16" FOUNDATION WALL REINF. - S E STRUCTURAL NOTES &SCHED LE. - DRILL & EPDXY ALL HORIZ. REIN TO EXISTING FDN W/ 6" MIN. EM D CONCRETE FTG - SEE PLAN \ & SCHEDULE FOR SIZE & REINF. L4 x 3 x 1/4 x 0'-4" (LLV) AT 2'-0"o.c TOP AND BOTTOM W/ 1/2" DIA. EPDXY ANCHORS W/ 5" EMBED 2x6 WOOD PLATE W/ 1/2" DIA. THREADED RODS AT 12"o.c. ATTACHED TO HSS FOR WOOD PLATE ATTACHMENT — FLOOR SHEATHING - SEE STRUCTURAL NOTES WOOD JOIST - SEE PLAN TOP FLANGE HANGER W/ 1500# MIN. CAPACITY NEW HSS BEAM - SEE ELEVATION 3 SIDES TYP EXISTING CONCRETE WALL B.N. -SEE STRUCTURAL NOTES SEE ELEVATION 5 NOTE: WOOD FRAMING NOT SHOWN FOR CLARITY 1 DETAIL 2 DETAIL 3 S202 SCALE : NONE S202 SCALE : NONE S202 NEW HSS COLUMN -SEE ELEVA L4x3x3/16 EA. SIDE OF COLUMN AT 4'-0" MAX SPACING W/ 1/2" DIA. THREADED ROD W/ HILTI HY200 EPDXY W/ MIN. 5" EMBED. - FIELD VERIFY 3" LOCATIONS 1/4" BASE PL. & A.B. - SEE 4/S202 1-1/2" NON -SHRINK CUT & REMOVE SLAB GROUT AS REQ'D. TO INSTALL NEW I FOOTING (IIIIIII III ° d a III II' N4. a - a d< -3.. C 4° U =1II III III III IIII- II��IIII, DRILL & EPDXY 6" INTO EXIST. FOOTING EXIST. ROOF - FIELD VERIFY EXIST. ZEE PURLIN - FIELD VERIFY 2 1 MAX 1/4 1/2" x 6" x 0'-8" PL. r L4x4x1/4 I I i 1/4 5 S202 EXISTING CONC. SLAB NEW FOOTING - SEE PLAN AND SCHED. EXIST. W BEAM - FIELD VERIFY 1/4 3 SIDES, TYP 3 SIDES, TYP 8 S202 DETAIL SCALE : NONE EXIST. ROOF d �.a< EXIST. CONCRETE WALLA (d. add .= 4 4 - _ - - - -• _ - .- 8 d - - - n 2 `` ed °y a= d .d a " d a 44..0 S202 a d ^ e - d P 4 _ bd - ed.' 4°HSS14x6x3/8 °. a_ :_- 001-," x x ° 00 -00' x - 00 a, d - - . 0D a cn cn ,- 2 2 ` NEW OPENING- - 4 .. ed TYP DETAIL SCALE : NONE EXIST. TILT UP WALL - FIELD VERIFY A I O o I L4 x 4 x 1/4 COPE AS REQ'D @ EACH END v 1/4 ANGLE CLIP - SEE 5/S202 HSS COLUMN -SEE PLAN N SECTION A 9 S20 'I-- 6 S202 (2) 1/2" DIA. THREADED ROD W/ HILTI HIT-HY 200 EPDXY W/ 6" MIN EMBED. FIELD VERIFY ANGLE ORIENTATION n�Tn ii — EXISTING CONCRETE WALL — NEW HSS JAMB COLUMN - SEE ELEVATION R" I � o M 6) I I 2" 3" 3„ 2„ I I I I NEW 5/8" x REQ'D .' BASE PL. W/ (4) 1/2"0 HEADED c A.B. W/ MIN. 8" EMBED. I I I I I I I I NEW CONCRETE i OUTING I I I L — — — — — — — — — — — — — — — J 31 r Ik architecture I design 4 S202 265 Winslow Way East Suite 202D Bainbridge Island Washington 98110 telephone 206 842 1253 e-mail frank@3rkarchitecture.com 1-3a-m! Y CONSULTANTS: 0 ENGINEERS structural consultants 1594 W. Park Cir. Ogden, Utah 84404 ph. 801.782.6008 fx. 801.782 . 4656 Q z 0 Q z rn O p � Q � Z � = o Q 00 J J v < � Q LL_ N V c/i U a Q � � z a-z o 0 0 2 N UJ SCALE: ISSUE DATE:01/31/19 REVISIONS: 1 CITY REVIEW 04/05/19 2 OWNER REVISION 07/11/19 5 OWNER REVISION 03/18/20 REVIEW SET S202 I N M O N 0 N 00 BASE PLATE SCHEDULE COLUMN SIZE BASE PLATE SIZE 8"SQ, 10"0 PL 3/4" x 14" x 1'-2" 6"SQ , 8" Q PL 3/4" x 12" x V-0" 4" SQ PL 3/4" x 10" x 0'-10" 5/16" REQ'D @ BASE PL'S STEEL PIPE OR HSS COLUMN THICKER 1/4" THAN 3/4" (4) 3/4"0 x REQ'D HEADED A.B. W/ NUT & WASHER W/ 8" MIN. SEE BASE PL SCHEDULE & EMBED - SEE DETAIL 7/S201 10/S201 FOR PLATE SIZE BLOCKOUT CONCRETE SLAB (WHERE OCCURS) - SEE PLAN FOR 1 1/2" NON -SHRINK GROUT THICKNESS AND REINF. I I a � 1 I I1 I I III III III III III ° � III III1 I I III III III IIIa' ° -III III III III III III III III III III=III III=III III' =III II II 4_ ° -"' IIIIII„ II III III III III III III, II' CONCRETE FOOTING - LEVELING NUT -TYPICAL III—IIL,,III,,,III,,,III—III SEE PLAN AND SCHEDULE FOR SIZE AND REINFORCING COLUMN TO SPOT FOOTING + 1 SCALE : NONE S2O3 WINDOW SYSTEM - BY OTHERS SEE ARCHITECT FOR CONCRETE SLAB REVEAL WHERE REQ'D. #4 DOWELS @ 24"o.c. EXTERIOR SLAB (BY OTHERS) 12„ 24" 4 '' —III III III III III III III III IIIa � ° _ d d —III „I I— I I "I I I I I I I I I„ I I I III III III III III III III —III -III I , III III I'- " IIIII IIIII ,III - =III III - CONCRETE FOUNDATION WALL - SEE PLAN AND STRUCTURAL II II NOTES FOR REINFORCING .I• ° " o- IIIIII. III ° III lii �II�'1III���III I �' ` I III III11r d IIIIII _" 4aa °°.n IIIIII 4 4 " ,IIIII °; •a-° ° °� ° a. a_ III III I I� I III ° °° " '1III'IIIIIIIIIIIIIIIIIIIIIIIIIIIIIII1111111111�, III I- SECTION @ EXTERIOR WALL WITH WINDOW SYSTEM SCALE : NONE SECTION 'A' CONCRETE FOOTING - SEE PLAN AND SCHEDULE FOR SIZE AND REINFORCING. HOLD DOWN SIZE ANCHOR SIZE MIN. EMBEDMENT DEPTH "le" S/HDU11 SSTB28 24 7/8" NOTE: INCREASE FOOTING THICKNESS OR STEP WALL AS REQUIRED FOR MIN. EMBEDMENT. PLACE SSTB ANCHOR DIAGONAL IN CORNER & END WALL APPLICATION LOCATE APPROX. 45 DEG. ° A IF in ° 4 ° �-1 3/4" SSTB CORNER / END WALL INSTALLATION TYPICAL HOLDOWN INFO. SCALE : NONE SSTB CONTINUOUS WALL INSTALLATION BASE PLATE SCHEDULE COLUMN SIZE BASE PL. SIZE �DIMENSION 'A' �DIMENSION 'B' A.B. SIZE W12x65 & 3/4"x14"x1'-2 1/4" 3" 4" 3/4" W 12x72 INTERIOR SLAB ON GRADE EXTERIOR CONCRETE #4 DOWELS @ 24"o.c. FLATWORK (WHERE OCCURS) � 12" 24" 5/16" REQ'D @ BASE PL'S W COLUMN 1/4" THICKER THAN 3/4" (4) HEADED A.B. W/ NUT & WASHER W/ 8" MIN. EMBED SEE BASE PL SCHEDULE FOR SEE DETAIL 7/S201 PLATE SIZE 1" MIN. BLOCKOUT CONCRETE SLAB - TYP., 'A' 'A' SEE PLAN FOR THICKNESS 1 1/2" NON -SHRINK GROUT A AND REINFORCING } III III III =III III —III III III III III III III III III= —III III —III III ° III III III III III III III III SECTION A IIIII " - . - ° - o-n a - " CONCRETE FOOTING - LEVELING NUT -TYPICAL SEE PLAN AND SCHEDULE FOR SIZE AND REINFORCING COLUMN TO SPOT FOOTING SCALE : NONE WALL SHEATHING - SEESTRUCT.NOTES BOTTOM TRACK - SEE 11/S206 & STRUCT. NOTES 2 S203 METAL WALL STUDS - SEESTRUCT.NOTES CONCRETE SLAB #4 DOWELS @ 24"o.c. 24" 12" IIIIIIIIIIIIII�„III. III III III Ili- " CONCRETE FOUNDATION WALL - SEE PLAN AND STRUCTURAL NOTES FOR REINFORCING III III 5 SECTION S203)SCALE : NONE IIIIII. 111 III III III II II ° a n 1 -III 4°" ° III IIIIII : - ° IIIIII III,��IIIIIIIIIIIIIIIIIIIIIIIIIII���III���II1— EXTERIOR WALL CONCRETE FOOTING - SEE PLAN AND SCHEDULE FOR SIZE AND REINFORCING. 6 S203 � ° Q I as IIIII ii H III —III III � 31 r Ik architecture I design � W COLUMN -SEE PLAN 2" ABOVE FINISH GRADE - VERIFY W/ARCH EXTERIOR SLAB ON GRADE STEP CONTINUOUS TOP BARS lii iia III III III„ IIIIIIIIIIIII" IIIIIIIII�III_ BELOW RECESS =III 8 III CONCRETE PIER - SEE —III III= DETAIL 5/S207 FOR SIZE AND CONCRETE FOUNDATION WALL - IIIII " J REINFORCING SEE PLAN AND STRUCTURAL III d" a II NOTES FOR REINFORCING SEE DETAIL 2/S203 FOR BASE PLATE &ANCHOR II II CONCRETE FOOTING - BOLT INFO. III ICI SEE PLAN AND SCHEDULE FOR SIZE AND REINFORCING SEE PLAN AND SCHEDULE :III a ". ° III FOR SIZE AND REINFORCING °- e d III IIII a ° IIIIIII III n 4 III— CONCRETE FOUNDATION @ OPENING SCALE : NONE HSS COLUMN - SEE PLAN ARCHITECTURAL SLANTED COLUMNS - SEE ARCH CONCRETE SLAB ON GRADE - SEE PLAN FOR 3 S203 CONCRETE PIER SCALE : NONE TYP 1/4 V CONCRETE BLOCKOUT 3/4" BASE PL. AS REQ'D THICKNESS & REINF. I / 11 1/2" NON -SHRINK GROUT DETAIL SCALE : NONE STUD BLOCKING TYP. @ ALL PANEL EDGES r r r r r r AND 48"o.c. MAX. - SEESTRUCT.NOTES STIFFENER PLATE EACH SIDE - APA RATED SEE STRUCTURAL NOTES SHEATHING @ ALL SHEAR WALLS - SEE WOOD JOIST - SEE PLAN. STUDS - SEE SHEAR STRUCT. NOTES FOR SEE DETAIL 10/S203 FOR WALL SCHEDULE & PANEL NAILING HANGER INFO. FRAMING NOTES ` \ BOUNDARY POST PER PLAN SIMPSON HOLDOWN ANCHOR W/ ANCHOR BOLT PER PLAN BOTTOM TRACK CONC. FOOTING OR FOUNDATION WALL SEE PLAN FOR SIZE 1/4" CAP PLATE x 8" x 0'-1100 HSS COLUMN - SEE PLAN a SEE SHEAR WALL SCHED. FOR BOLTED ATTACHMENT TO 4 FOUNDATION. PROVIDE 1/4" x 3" x 0'-3" PL. WASHERS TYPICAL @ EACH ANCHOR BOLT FLOOR SHEATHING - SEE STRUCTURAL NOTES DOUBLE 2x OR SINGLE 3x WOOD NAILER PLATE W/ 1/2" DIA. THREADED ROD AT 24"o.c. ATTACHED TO BEAM FOR WOOD ATTACHMENT �I­ �M -SEE PLAN 1/2" TYP. 4'- 0" MAX. EXISTING FLOOR SHE EXISTING 2x JOISTS - FIELD VERIFY W BEAM - SEE PLAN 7 S203 4 � S203 SEE STRUCTURAL ES )D PLATE - SEE DETAIL 33 FOR MORE INFO. DR SHEATHING - SEE JCTURAL NOTES )D JOIST - SEE PLAN HOOD STIFFENER PLATE H SIDE OF WEB, TYP. FLANGE HANGER W/ 1500#MIN. CAPACITY 8 L BEAM TO BEAM 9 DETAIL 10 S20' SCALE : NONE S2O3 SCALE : NONE S203 265 Winslow Way East Suite 202D Bainbridge Island Washington 98110 telephone 206 842 1253 e-mail frank@3rkarchitecture.com 1-3a-m! Y CONSULTANTS: a ENGINEERS structural consultants 1594 W. Park Cir. Ogden, Utah 84404 ph. 801.782.6008 fx. 801.782 . 4656 SCALE: ISSUE DATE:01/31/19 REVISIONS: 1 CITY REVIEW 04/05/19 2 OWNER REVISION 07/11/19 5 OWNER REVISION 03/18/20 REVIEW SET S203 V BENT PLATE TO BEAM 3/16" 2"-12" SEE ROOF DECK SCHEDULE r%r'T A 11 SCALE : NONE IMMMMENWIMEM SCALE: NONE CONNECTION PLATE SEE SCHEDULE FOR PLATE THICKNESS AND BOLT REQUIREMENT — ROOFDECK- SEE SCHEDULE W BEAM - SEE PLAN —" FULL DEPTH STIFFENER PLATE MOMENT FRAME CONTINUITY PLATES (WHERE OCCURS) _ W COLUMN - SEE PLAN DETAIL SCALE: NONE SEE ARCH OL STEEL STUD - SEE 7/S204 SEE ARCH. 12" MAX. BENT PLATE 1/4" x CONT. 5" REQ'D. (4" MIN) RACTAI MnnE' ME!f11! VV 11- 1 IV IY 1 Lr-, I L - SEE SCHEDULE SEE ARCH STEEL STUD - SEE 7/S204 BENT PL. - SEE DETAIL 1/S204 FOR INFO. SEE ROOF DECK SCHED. )CKING - SEE 6/S204 - SEE PLAN 1 � S204 ROOF DECK - SEE SCHED. FOR SIZE & ATTACHMENT W BEAM - SEE PLAN 3/8" STIFFENER PL. EACH SIDE OF BEAM WEB 3/4" x 16" x 1'-4" CAP PL. W/ (4) 3/4" DIA. BOLTS HSS COLUMN - SEE PLAN 1/4" x 2" @ LH 1 /8" x 2" @ K ALL JS>40'-0" DETAIL 2 DETAIL 3 SCALE : NONE S2O4 SCALE : NONE S20 BENT PLATE TO JOIST (BEYOND) r% r- T A 1 1 SCALE : NONE SEE ROOF SEE ARCH DECK SCHED. BENT PLATE A TO JOIST W 1/4" x 2" @ LH 1 /8" x 2" @ K ROOF DECK - SEE SCHED. — 14ga x 4" x 8" x 1'-6" BENT PL. W/ (3) #12 SCREWS IN EACH FLUTE (4) #12 SCREWS TYP ROOF JOIST - SEE PLAN 362S162-43 BRACE @ 48"o.c. MAX DETAIL SCALE: NONE (4) #12 SCREWS TYP @ EACH INTERSECTION - ROOF DECK - SEE SCHED. FOR SIZE & ATTACHMENT HSS COLUMN - SEE PLAN DETAIL SCALE: NONE TOP TRACK - SEE STRUCT. NOTES BENT PLATE - SEE 1/S204 CLIP TO BENT PL. @ BEND IN CLIP SIMPSON FCB45.5 W/ MIN (4) #12 TEK SCREWS. WELD TO BENT PL. AS SHOWN 1 1 /2" MAX. SEE ARCH. 1/4" x 6" x 0'-6" PL. @ EACH STUD LOCATION. SEE NOTE 362S162-43 BRACE @ 48"o.c. MAX, SEE NOTE W BEAM - SEE PLAN WALL SHEATHING - SEE ARCH STEEL STUD -SEE STRUCT. NOTES BOTTOM TRACK - SEE STRUCT. NOTES 31 r Ik architecture I design 265 Winslow Way East BEARING PLATE Suite 202D PER TYP. DETAIL Bainbridge Island TYP. Washington 98110 AN FOR BEAM telephone 206 842 1253 e-mail frank@3rkarchitecture.com CONSULTANTS: 0 Ij ENGINEERS structural consultants 1594 W. Park Cir. Ogden, Utah 84404 ph. 801.782.6008 4. 801.782 . 4656 Q z 0 Q z rn rn O p � Q H Z � = o Q c� 00 J J v < C/) Q LL. N V U a Q 0 � z � o z 0 0 rf) 0 2 N Lu SCALE: ISSUE DATE:01/31/19 REVISIONS: 1 CITY REVIEW 04/05/19 2 OWNER REVISION 07/11/19 5 OWNER REVISION 03/18/20 REVIEW SET S204 a N O N O N 00 Cl) SEE ROOF ,> .... DECK SCHED. BENT PL. - SEE 1/S204 EXIST. Z PURLIN EXIST. W BEAM EXIST. HSS COLUMN & CAP PL. DETAIL SCALE: NONE ROOF DECK - SEE SCHED. FOR SIZE & ATTACHMENT ROOF JOIST - SEE PLAN SEE TYP SCHED. FOR BEAM CONNECTION NEW W BEAM - SEE PLAN I NEW HSS 6 x 6 x 1/2" x REQ'D W/ CAP AND BOTTOM PLATE 1 /+I 6" BENT PL. - SEE 1/S204 ROOF DECK - SEE SCHED. FOR SIZE & ATTACHMENT � I I Z —r-A OI I I OI I I I I SEE SCHED. FOR BEAM CONNECTION W BEAM SEE PLAN A DETAIL SCALE: NONE ROOF DECK - SEE SCHED. FOR SIZE & ATTACHMENT 1 S205 STEEL STUDS - SEE 7/S204 5 S205 (2) ROWS OF #12 SCREWS @ 6"o.c. STAGGERED TOP TRACK - SEE STRUCT.NOTES I I •i BENT PL. - SEE 7/S204 / STEEL STUD - SEE BENT PL. -SEE 7/S204 STRUCT.NOTES WALL SHEATHING - SEE 362S162-43 BRACE @ 48"o.c. / / STRUCT.NOTES f MAX. ALTERNATE BRACE / DIRECTION EACH BRACE 1 MAX / / (4) #12 TEK SCREWS @ 1 EACH STUD INTERSECT N • BOTTOM TRACK - SEE STRUCT.NOTES NOTE: COORDINATE DEFLECTION CONNECTION @ TOP OF WINDOW WINDOW SYSTEM -SEE CH W/ WINDOW SYSTEM MANUF. 5/8" DIA. THREADED ROD @ 12"o.c. INSTALL W/ HILTI HIT-HY 200 W/ MIN 5" EMBED. Z IT 0 EXIST. CONCRETE WALL 3/8" STIFFENER PL.s @ 24"o.c. O NOTE: EDGE OF BEAM FLANGE TO BE 1/4" MAX. FROM EXISTING CONCRETE WALL. BEAM CENTERLINES NEAR GRID C SHALL BE IN LINE. SCALE : NONE SEE ROOF DECK SCHED. BENT PL. - SEE 1/S204 HSS BLOCKING - SEE DETAIL 6/S204 ROOF DECK - SEE SCHED. FOR SIZE & ATTACHMENT W BEAM - SEE PLAN SEE SCHED. FOR BEAM CONNECTION 1 /4 I / 2"-12" L8 x 6 x 3/8 x CONT. (LLV) W/ (2) ROWS OF 5/8" THREADED RODS @ 12"o.c. INSTALL W/ HILTI HIT-HY 200 W/ MIN 5" EMBED. ("2� S205 L y a 3/4" STIFFENER PL. 1 MAX 7/8" x 16" x REQ'D BENT PL. 2 00 A B > a4 71 a4 A. a a a 4" 8" 3'- 0" MIN In EXIST. TILT UP WALL FIELD FIELD VERIFY dVERIFY z 4 o (4) 3/4" DIA. THREADED ROD W/ HILTI HIT-HY 200 EPDXY W/ 6" MIN EMBED. 04 00 IO O STIFFENER PL. (4) 3/4 DIA. THRU BOLTS SECTION A SECTION B DETAIL SCALE : NONE W BEAM SEE PLAN DETAIL SCALE : NONE 5/8" DIA. THREADED ROD @ 24"o.c. W/ HILTI HIT-HY 200 W/ 5" MIN EMBED. ROOF DECK - SEE SCHED. FOR SIZE & ATTACHMENT STIFFENER PLATE EA. SIDE - _ �SEE ROOF DECK SEE STRUCTURAL NOTES SCHED. ROOF DECK - SEE SCHED. 41 FOR SIZE & ATTACHMENT SEE 2/S204 FOR BOLT INFO 12" MAX °a 1 1/2" ROOF JOIST - SEE PLAN a a JL \ —n, EXIST. CONCRETE WALL ROOF DECK - SEE SCHED. FOR SIZE & ATTACHMENT W BEAM SEE PLAN 1/4 I / \ \\ 1 1/2" � V SEE 2/S204 FOR BOLT INFO TYP 3 SIDES \ 1 1/2 1/4 ROOF JOIST -SEE P7E\ \ ROOF JOIST TO BEA ON GIRDER 3/4" CAP PL AS REQ'D� HSS COLUMN - SEE PLAN W BEAM - SEE PLAN SEE TYP. SCHED. FOR BEAM CONNECTION 7/8" x 12" x V-0" END PL. 6 BEAM TO BEAM (BOLTED 3205 SCALE : NONE NEW 2x BLOCKING BETWEEN EXISTING JOISTS ALONG W BEAM — 1/4" CAP PLATE x REQ'D 1 1/2" EXISTING FLOOR SHEATHING EXISTING 2x JOIST - FIELD VERIFY 3/4" CAP PLATE AS REQ'D HSS COLUMN - SEE PLAN 1'- 0" OR DEPTH OF BEAM (MIN.) U.N.O. SEE PLAN 1/2" I'I 1 1/2" OO OO 1112140110 31 r Ik architecture I design PL. x 7" WIDE (BOTH SIDES OF BEAM WEB) SHIM AS REQ'D FOR FLUSH SURFACE 265 Winslow Way East CONTACT 1/2" GAP (MAX.) Suite 202D W BEAM - SEE PLAN Bainbridge Island Washington 98110 telephone 206 842 1253 e-mail frank@3rkarchitecture.com 3/4"0 BOLTS - / SEE SCHEDULE FOR QUANTITY PER SIDE I I � 1/4 TYP 3 BEAM TO BEAM (BOLTED S205 SCALE: NONE 11 SEE TYP SCHED. FOR BEAM CONNECTION W GIRDER - SEE PLAN SIMPSON A34 AT EACH JOIST WOOD PLATE - SEE DETAIL 9/S203 W BEAM - SEE PLAN BEAM CONNECTION - SEE TYP. SCHEDULE HSS COLUMN - SEE PLAN DETAIL 8 DETAIL 10 SCALE : NONE S205 SCALE : NONE S205 TYP 1/4 ARCHITECTURAL SLA C - S ARCH 7 S205 ARCHITECTURAL SLANTED COLUMNS - SEE ARCH DOUBLE 2x WALL TOP PLATE - SEE ROOF FRAMING NOTES CRIPPLE STUDS (WHERE OCCURS) SIMPSON LCE4 POST CAP - TYP. EACH SIDE HEADER BEAM -SEE TRIMMER STUDS - SEE SCHEDULE KING STUDS - SEE SCHEDULE v OPENING SIZE KING STUDS TRIMMER STUDS UP TO 5'-0" (2) 2x4 (2) 2x4 107:19 SCALE : NONE M 'LAN 1-3a-m! Y CONSULTANTS: 4 �O5 0 ENGINEERS structural consultants 1594 W. Park Ci, Ogden, Utah 84404 ph. 801.782.6008 fx. 801.782 . 4656 O C z 0 0� � = O z C� 00 J Uj Q J U U Q Q o a- z � z o O O ��� 0 = N o SCALE: ISSUE DATE:01/31/19 EVISIONS: 1 CITY REVIEW 04/05/19 2 OWNER REVISION 07/11/19 OWNER REVISION 03/18/20 11 REVIEW SET S205 S205 31 r Ik architecture I design o 0 NOTE: DO NOT WELD COLUMN 265 Winslow Way East TO CAP PL AT FILLET AREAS WHERE BRACING TERMINATES AT ROOF DECK - SEE SCHED. 33 BUILT-UP JAMB OR POST, EXTEND Suite 202D FOR SIZE & ATTACHMENT COLUMN CAP PL 2X BEAM FLANGE 6 Nv CHANNEL INTO PUNCH -OUT. USE 2" x 2" THICKNESS X DIMENSIONS OF x 16 GA. CLIP ANGLE 1-1/4" LESS THAN WALL TRACK -SEE HSS BLOCKING - SEE 6/S204 COLUMN Fy = 50 ksi 4 STUD WIDTH. ATTACH USING (4) #8 EXTERIOR FRAMING NOTES Bainbridge Island O SCREWS. 6 Washington 98110 TOLERANCES SHALL NOT ACCUMULATE TO THE EXTENT 1-1/2" x 16 GAUGE COLD t 6 O O THAT THE ANGLE OF THE x telephone � ROLLED CHANNEL. TO BE ACCESS HOLE CUT TO THE / 00 FLANGE SURFACE EXCEEDS 25' O z STRUCSPACEDT. NOAS RES PER SIDE EA. 206 842 1253 OF TRACK / x x O— / 4 `� ` ------ 14 e-mail CJP TYP. SEE SCHEDULE FOR BEAM O O frank@3rkarchitecture.com TO COLUMN CONNECTION 2" x 2" x 16 GAUGE CLIP ANGLE W BEAM - SEE PLAN 1/4" LESS THAN STUD WIDTH. KEY NOTES: O ATTACH USING (4) #8 SCREWS. 5/8" STIFFENER PL. ` CLIP ANGLE TO BE PLACED AT �Q� F'WAS CAP PLATE TO OR 1. BEVEL AS REQUIRED BY AWS D1.1 FOR SELECTED GROOVE WELD PROCEDURE. ` EACH STUD. COLUMN>— W COLUMN - SEE PLAN 2. LARGER OF tbf OR 1/2 INCH. (PLUS 1/2 W, OR MINUS 1/4 tbf). x N3. 3/4 tbf TO tbf, 3/4" MINIMUM (+ 1/4 INCH). STUD BLOCK TO MATCH 4. 3/8" MINIMUM RADIUS (PLUS NOT LIMITED, OR MINUS 0). GA. OF TRACK 5. 3 tbf. (+ 1/2 INCH). p Gc3sgp 6. SEE FEMA-353, RECOMMENDED SPECIFICATIONS AND QUALITY ASSURANCE GUIDELINES FOR STEEL MOMENT -FRAME CONSTRUCTION FOR SEISMIC APPLICATIONS, �0 FOR FABRICATION DETAILS INCLUDING CUTTING METHODS AND SMOOTHNESS REQUIREMENTS. CONSULTANTS: MOMENT FRAME CONNECTION DETAIL 1 DETAIL 2 TYP. LATERAL BRACING / BRIDGING 3 TYP. TRACK SPLICE DETAIL 4 SCALE: NONE S2O6 L SCALE : NONE S206 L SCALE : NONE S O6 SCALE: NONE S O6 (4) SCREWS AT 1 1/2" (2) JAMB STUDS / SECTION OF 16 GA. MIN. LAPPED TRACK _ 1r NOTE: IF ATTACHING TO BACK TO BACK 1 /8 \ 2-16 ENGINEERS TRACK LENGTH 1-1/4" LESS NOTE: IF ATTACHED TO ROOF DECK USE (4) #12 JAMB STUDS \ structural consultants THAN HEADER DEPTH. SCREW STRUCT. JAMB REPLACE EA. SCREW IN PLACE OF EACH ph.801W. ..7e�6008f�.xdebii82.4656 ATTACHED TO JAMB W/ (6) #10 SCREW W/ (1) HILTI X-U15 TITEN HD SCREWS. AND TO HEADER W/ P.A.F. (3) #10 SCREWS EA. FLANGE. ��� 00 • � p CAP JAMB TRACK FOR � Q . WINDOW/DOOR ATTACHMENT. CRIPPLE STUDS 6 u_ U) FULL HEIGHT JAMB STUDS • ? p . SEE STEEL STUD FRAMING EXTEND 10" ABOVE HEADER + • • , • o TOP VIEW NOTES FOR SIZES AND 8" BELOW SILL CONNECTIONS Q ch w O o ` (1) #8 SCREW TYP. N �N�tiG ATTACH TRACK TO SLAB EA. FLANGE STUD SECTION INSIDE USING (1) 3/8" DIA. x 4" TRACK SIMPSON TITEN HD ANCHORS #8 SCREWS @ 16"o.c. 18 GA. MIN. CLOSURE TRACK (2) #8 SCREWS A AS REQ'D ATTACH W/ 3 1/4" MIN. EMBED. HEADER CONNECTION . ' 4 SCREWS ON EA. SCREWS 24"o.c. LOCATED AS SHOWN ABOVE. @ 16"o.c. () @ W/ #8 SCREWS @ 16 o.c. - TYPICAL BOTTOM/TOP SIDE OF SPLICE CONNECTING CORNER COORDINATE W/ HEADER 0 \ STUD DETAILS BOTTOM TRACK a ATTACH STUDS USING JAMB STUDS -SEE \ TRACK SPLICE °' JAMB SCHEDULE % (2) #10 SCREWS @ N CONCRETE FOUNDATION WALL 16"o.c. M •• + o 16 GA. TRACK @ OPEN FACE (1) #8 SCREW @ `t N Q No OF JAMB AS REQ'D -ATTACH EACH FLANGE + N W/ #8 SCREWS @ 16"o.c. ATTACH JAMB MEMBERS USING O 2" x 2" x 16GA. CLIP ANGLE 1/2" I L 6" SECTION OF RUNNER TRACK, z LESS THAN STUD WIDTH. USE (3) 18 GA. MIN. USE (8) #10 SCREWS 0 #10 SCREWS IN EACH LEG AS AS SHOWN SHOWN HEADER STUDS AND • \ti TRACK - SEE JAMB AND HEADER SCHEDULE SECTION A SCREW OPTION A SCREW OPTION B WELD OPTION 0 = N O �4 TYPICAL WALL CONCRETE SLAB - SEE PLAN z 00 CORNER TYPICAL BUILT-UP STUDS STITCHING Q = TYP. BOX HEADER CONNECTION 5 DETAIL 6 DOOR JAMB ANCHORAGE 7 DETAIL 8 J w Q SCALE: NONE 5206 SCALE : NONE 5206 SCALE : NONE 5206 SCALE : NONE 5206 (j) J U _ U cry U Q Q o 2 o o- z N STEEL STUD -SEE z o 0 STRUCT. NOTES O o_ cCLIP TO EDGE co >- N Q nail ANGLE @ BEND IN CLIP TO EDGE (� W rn 1/8" 4" CLIP SIMPSON MSCB45.5 @ EACH STUD ANGLE @ BEND IN SIMPSON MSCB45.5 @ EACH STUD W/ (3) #12 SCREWS CENTERED A 1/8" 4" CLIP Q W/ (3) #12 SCREWS CENTERED A IN VERTICAL SLOT @ EACH STUD - IN VERTICAL SLOT @ EACH STUD - WELD TO EDGE ANGLE AS SHOWN STEEL STUD WELD TO EDGE ANGLE AS SHOWN STEEL STUD 0 BENT PL. - SEE 1/S204 w BBBI 99fl1 • c .2 CLIP CLIP . z Q Z EDGE ANGLE a W BEAM - SEE PLAN EDGE ANGLE N • f6 N � W BENT PL. - SEE 1/S204 PLAN SECTION - A BOTTOM WALL TRACK - SCALE: = PLAN SECTION - A SEE STRUCT. NOTES ISSUE DATE:01/31/19 STEEL STUDS - SEE STRUCT. LO STEEL STUDS - SEE W BEAM - SEE PLAN NOTES � STRUCT.NOTES WALL SHEATHING - SEE SCHED. 3/8" DIA. x 4" SIMPSON TITEN HD Cb REVISIONS: WALL SHEATHING -SEE SCHED. W/ 3 1/4" EMBEDMENT @ 32"o.c. 2 3/4" MIN. TO EDGE OF CONCRETE 1 CITY REVIEW 04/05/19 0 2 OWNER REVISION 07/11/19 5 OWNER REVISION 03/18/20 N DETAIL 9 DETAIL 10 DETAIL 11 REVIEW SET P SCALE: NONE S206 L SCALE : NONE S2O6 L SCALE : NONE S2O6 U S206 7 0 N N M 0 N 0 N 0 co STAGGER AT 4'-0"o.c. B.N. TYP. B.N. = BOUNDARY NAILING E.N. = EDGE NAILING F.N. = FIELD NAILING TYP. SHEATHING LAYOUT SCALE: NONE WOOD NAILER - FLOOR SHEATH STRUCTURALN WOOD JOIST - S SEE DETAIL 10/, HANGER INFO. W BEAM - SEE P—_ NOTE: SEE 2/S207 FOR ATTACHMENT OF NEW JOISTS TO EXISTING JOISTS, WHERE OCCURS. DETAIL SCALE: NONE B.N. - SEE STRUCTURAL NOTES ROOF SHEATHING - SEE STRUCTURAL NOTES — 2x REQ'D FLAT BLOCKING AT SIMPSON STRAPS W/ B.N. — WOOD JOIST - SEE PLAN 3 1/2" x 11 7/8" LEDGER - ATTACH TO EACH STUD (16"o.c. MAX) W/ (3) SIMPSON SDWH SCREWS W/ 3" MIN. PENETRATION INTO STUD, ATTACH TO BLOCKING W/ (2) ROWS OF 20d NAILS AT 4"o.c. PRE -DRILL AS REQ'D. TO PREVENT SPLITTING — SIMPSON ST2215 AT LEDGER SPLICES - CENTERED ON SPLICE — E.N. TYP. 2 x 4 FLAT BLOCKING AT ALL UNSUPPORTED EDGES 4'-0" x 8'-0" TYP SHEATHING 1/8" PANEL GAP (TYP.) EDGE SHEATHING JOINTS TO BE CENTERED ON JOISTS EDGE OF FLOOR B.N. - SEE STRUCTURAL NOTES STA( AT 4' 1 /8" F (TYP BLO( CONCRETE SLAB - SEE PLAN / NOTES FOR THICKNESS AND REINFORCING SEE ARCH B.N. = BOUNDARY NAILING E.N. = EDGE NAILING F.N. = FIELD NAILING o a: N �Q a_ 2'-0" E.N. TYP. 2 x 4 FLAT BLOCKING AT ALL UNSUPPORTED EDGES 4'-0" x 8'-0" TYP. SHEATHING EDGE SHEATHING JOINTS TO BE CENTERED ON JOISTS EDGE OF ROOF B.N. TYP. 1 �01 (3) 5/8" DIA x 3" HEADED STUDS AT 6"o.c., STAGGERED. TYP. (4) SIDES HSS COLUMN - SEE PLAN CONCRETE PIER W/ (8) # 6 VERTICAL AND #3 TIES AT 8"o.c. W/ (3) IN TOP 5" HSS COLUMN - SEE PLAN CONCRETE SLAB - SEE ARCH AND CIVIL 4 lit Sig SIG._ CONCRETE FOOTING - SEE SCHEDULE FOR SIZE AND REINFORCING BASE PLATE 1" x 15" x V-3" W/ (4) 1" DIA. A449 ANCHOR BOLTS W/ DOUBLE NUTS AND 12" MIN. EMBED EXISTING 2x JOIST (2) PIECES NOTE: PRE -DRILL HOLES IN EXISTING FRAMING AS REQ'D TO PREVENT SPLITTING. HEADER AND BEAM MEMBER CONNECTIONS SCALE : NONE TYP. AT CAP PLATE TYP. SEE ARCH HSS BEAM - SE SEE ARCH STEEL HEADEI ATTACH TO HE PER DETAIL 5/: NOTE: METAL STUDS NOT SHOWN FOR CLARITY EXISTING FLOOR SHEATHING (2) ROWS 12d NAILS AT 12"o.c. EACH SIDE OF BEAM NEW 2x JOIST - SEE PLAN 2 S207 1/4" CAP PLATE x REQ'D HSS COLUMN - SEE PLAN DETAIL SCALE: NONE WOOD NAILER - S FLOOR SHEATHIN STRUCTURAL NO W BEAM - SEE PL, BEAM CONNECTI( SEE TYP. SCHEDI HSS COLUMN - FIL,_ . uoo nrnnn orr ni nni ATTACH TO HSS COLUMN PER DETAIL 5/S206 31 r Ik architecture I design 3 S207 STEEL HEADER SSH-3 - ATTACH TO JAMB SSJ-3 PER DETAIL 5/S206 362S162-33 AT 16"o.c. TYP. AT (4) LOCATIONS 362T125-33 W/ (2) ROWS OF #8 SCREWS AT 16"o.c. STAGGERED. TYP. AT (8) LOCATIONS STEEL HEADER SSH-3 - ATTACH TO JAMB SSJ-3 PER DETAIL 5/S206 4 TYP. CANOPY FTG. DETAIL 5 DETAIL 6 DETAIL 7 5207 SCALE : NONE S207 SCALE : NONE S207 SCALE: NONE S207 SIMPSON LSTA18 AT 24"o.c. E.N. - SEE STRUCTURAL NOTES 2x OR LVL BLOCKING W/ SIMPSON A35 AT EACH END EXISTING WOOD STUD WALL B.N. - SEE STRUCTURAL NOTES FLOOR SHEATHING - SEE STRUCTURAL NOTES WOOD JOIST SEE PLAN WOOD BEAM - SEE PLAN. SEE DETAIL 2/S207 FOR ATTACHMENT TO EXISTING MEMBER NOTE: USE TOP FLANGE HANGER W/ 2000# MIN. CAPACITY AT LVL BEAM. EXISTING FLOOR SHEATHING EXISTING 2x JOIST - FIELD VERIFY EXISTING END BLOCKING - FIELD VERIFY 2x BLOCKING BETWEEN EACH EXISTING JOIST EXISTING FLOOR JOIST - FIELD VERIFY SIMPSON H2.5A AT EACH JOIST 3'- 6" MAX. WOOD BEAM - SEE PLAN DOUBLE TOP PLATE WOOD JAMB - SEE PLAN DETAIL 8 DETAIL 9 DETAIL 10 SCALE : NONE ��l SCALE : NONE �S2l7 SCALE : NONE �2O 265 Winslow Way East Suite 202D Bainbridge Island Washington 98110 telephone 206 842 1253 e-mail frank@3rkarchitecture.com 1-3a-m! Y CONSULTANTS: 0 ENGINEERS structural consultants 1594 W. Park Cir. Ogden, Utah 84404 ph. 801.782.6008 fx. 801.782. 4656 Q 0 z 0 Q z rn rn O p � Q H Z � = o Q c� 00 >- J J v � � Q � N V c/i U a Q 0 � z a- z o 0 0 ro 0 2 N uj SCALE: ISSUE DATE:01/31/19 REVISIONS: 1 CITY REVIEW 04/05/19 2 OWNER REVISION 07/11/19 5 OWNER REVISION 03/18/20 REVIEW SET A S207