APPROVED BLD RESUB1 BLD2022-1714+ARCH PLANS+1.23.2023_10.11.39_AM+3327610STRUCTURAL NOTES
O C
(THESE NOTES ARE TYPICAL UNLESS NOTED OR DETAILED OTHERWISE ON DRAWINGS)
CODE
ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE DRAWINGS,
SPECIFICATIONS, AND THE INTERNATIONAL BUILDING CODE (IBC), 2018 EDITION. SPECIFICATIONS AND STANDARDS
WHERE REFERENCED ON THE DRAWINGS ARE TO BE THE LATEST EDITION.
DESIGN LOADS
DEAD LOADS:
DECK 15 PSF
LIVE LOADS:
ROOF (SNOW LOAD) 25 PSF
DECK 60 PSF
STATEMENT OF SPECIAL INSPECTIONS
SPECIAL INSPECTIONS ARE NOT REQUIRED
DEFERRED APPROVAL ITEMS
SUBMITTAL DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE ARCHITECT OR
ENGINEER OF RECORD WHO SHALL REVIEW THEM AND INDICATE THAT THE DEFERRED SUBMITTAL DOCUMENTS
HAVE BEEN REVIEWED AND THAT THEY HAVE BEEN FOUND TO BE IN GENERAL CONFORMANCE WITH THE DESIGN
OF THE BUILDING. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THEIR DESIGN AND
SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING OFFICIAL. DEFERRED SUBMITTALS SHALL BE
STAMPED AND SIGNED BY A PROFESSIONAL ENGINEER REGISTERED IN THE SAME STATE AS THE PROJECT.
1. HANDRAILS AND GUARDRAILS
FOUNDATIONS: SPREAD FOOTINGS
SOILS REPORT: REPORT NO:
PREPARED BY:
DATED:
ALLOWABLE SOIL PRESSURE: 2000 PSF (ASSUMED; TO BE FIELD VERIFIED DURING CONSTRUCTION)
LATERAL EARTH PRESSURE:
UNRESTRAINED:
RESTRAINED:
PASSIVE:
COEFFICIENT OF FRICTION
35 PCF + ANY APPLICABLE SURCHARGE
50 PCF + ANY APPLICABLE SURCHARGE
300 PCF
0.35
FOOTINGS SHALL BEAR ON FIRM UNDISTURBED EARTH OR 12" OF COMPACTED STRUCTURAL FILL AS REQUIRED AND
AT LEAST 18" BELOW ADJACENT EXTERIOR GRADE. ANY FOOTING ELEVATIONS SHOWN IN THE DRAWINGS
REPRESENT MINIMUM DEPTHS AND ARE FOR BIDDING ONLY. ACTUAL FOOTING ELEVATIONS ARE SUBJECT TO SITE
CONDITIONS AND MUST THEREFORE BE ESTABLISHED BY THE CONTRACTOR. FOOTINGS SHALL BE CENTERED BELOW
COLUMNS OR WALLS ABOVE, UNLESS NOTED OTHERWISE.
IMPORTED STRUCTURAL FILL AND BACKFILL MATERIAL SHOULD CONSIST OF CLEAN, WELL GRADED GRANULAR
MATERIAL FREE OF DEBRIS OR ORGANICS WITH A MAXIMUM PARTICLE DIAMETER OF THREE INCHES AND NO MORE
THAN 10% FINES (PASSING THE #200 SIEVE).
FILL AND BACKFILL MATERIAL SHOULD BE PLACED IN LEVEL LIFTS NOT EXCEEDING TWELVE (12") INCHES IN LOOSE
THICKNESS AND COMPACTED TO A MINIMUM OF 95% OF ITS MAXIMUM DRY DENSITY AS DETERMINED BY ASTM
TEST METHOD D1557.
BACKFILL BEHIND ALL RETAINING WALLS WITH WELL -DRAINING, GRANULAR FILL AND PROVIDE FOR SUBSURFACE
DRAINAGE. PROVIDE DAMPPROOFING AT EXTERIOR FACE OF ALL FOUNDATION WALLS EXPOSED TO EARTH PER
ARCHITECTURAL SPECIFICATIONS.
EXCAVATIONS AND DRAINAGE INSTALLATION SHALL BE OBSERVED BY A SOILS ENGINEER RETAINED BY THE OWNER.
IF EXCAVATION SHOWS SOIL CONDITIONS TO BE OTHER THAN THOSE ASSUMED ABOVE NOTIFY THE STRUCTURAL
ENGINEER FOR POSSIBLE FOUNDATION REDESIGN.
CONCRETE
ALL CONCRETE SHALL BE MIXED, PROPORTIONED, CONVEYED, AND PLACED IN ACCORDANCE WITH CHAPTER 26 OF
ACI 318 AND THE AMERICAN CONCRETE INSTITUTE'S SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS
(ACI 301).
ALL CONCRETE SHALL BE STONE -AGGREGATE CONCRETE HAVING A UNIT WEIGHT OF APPROXIMATELY 150 POUNDS
PER CUBIC FOOT.
CONCRETE STRENGTHS AT 28 DAYS (fc) AND MIX CRITERIA SHALL BE AS FOLLOWS:
MAXIMUM
MIN CEMENT
TYPE OF CONSTRUCTION
f'c*
WATER/CEMENT
CONTENT PER CUBIC
MAXIMUM
SHRINKAGE STRAIN
RATIO
YARD
SLABS ON GRADE
3000 PSI
0.55
5 1/2 SACK
N/A
FOOTINGS
3000 PSI
0.55
5 1/2 SACK
N/A
THE MINIMUM AMOUNT OF CEMENT LISTED ABOVE MAY BE CHANGED IF A CONCRETE PERFORMANCE MIX IS
SUBMITTED TO THE ENGINEER AND THE BUILDING DEPARTMENT FOR APPROVAL TWO WEEKS PRIOR TO PLACING
ANY CONCRETE. THE PERFORMANCE MIX SHALL INCLUDE THE AMOUNTS OF CEMENT, FINE AND COARSE
AGGREGATE, WATER, AND ADMIXTURES AS WELL AS THE WATER -CEMENT RATIO, SLUMP, CONCRETE YIELD, AND
SUBSTANTIATING STRENGTH DATA IN ACCORDANCE WITH CHAPTER 26 OF ACI 318.
ALL CONCRETE EXPOSED TO WEATHER OR TO FREEZING TEMPERATURES SHALL BE AIR -ENTRAINED IN ACCORDANCE
WITH ACI 318 TABLE 19.3.3.1 FOR MODERATE EXPOSURE CLASS F1.
*PROVIDE Pc SPECIFIED IN TABLE FOR DURABILITY REQUIREMENTS. 2500 PSI CONCRETE MEETS STRENGTH
REQUIREMENTS, THEREFORE SPECIAL INSPECTION IS NOT REQUIRED.
REINFORCING STEEL
REINFORCING STEEL SHALL BE DEFORMED BILLET STEEL CONFORMING TO ASTM A615, AND SHALL BE GRADE 60 (Fy
= 60,000 PSI), UNLESS NOTED OTHERWISE. GRADE 60 REINFORCING BARS INDICATED ON DRAWINGS TO BE WELDED
SHALL CONFORM TO ASTM A706. REINFORCING COMPLYING WITH ASTM A615 MAY BE WELDED IF MATERIAL
PROPERTY REPORTS INDICATING CONFORMANCE WITH WELDING PROCEDURES SPECIFIED IN AWS D1.4 ARE
SUBMITTED.
WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185. PROVIDE WELDED WIRE FABRIC IN SHEETS NOT ROLLS. LAP
WELDED WIRE FABRIC 12" AT SIDES AND ENDS.
REINFORCING STEEL SHALL BE DETAILED INCLUDING HOOKS AND BENDS IN ACCORDANCE WITH ACI SP-66 AND ACI
318, LATEST EDITIONS. UNLESS OTHERWISE NOTED, REINFORCING SPLICE LENGTHS AND DEVELOPMENT LENGTHS
SHALL BE PER SCHEDULE.
MECHANICAL SPLICING OF REINFORCING BARS, WHERE INDICATED ON THE DRAWINGS, SHALL BE BY AN ICBO
APPROVED SYSTEM, SHALL DEVELOP 125% OF THE SPECIFIED YIELD STRENGTH OF THE BAR, AND SHALL BE
INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.
REINFORCING SHALL BE PLACED AND ADEQUATELY SUPPORTED PRIOR TO PLACING CONCRETE. WET -SETTING
EMBEDDED ITEMS IS NOT ALLOWED WITHOUT PRIOR ENGINEER APPROVAL. BARS PARTIALLY EMBEDDED IN
HARDENED CONCRETE SHALL NOT BE FIELD BENT UNLESS SO DETAILED OR APPROVED BY THE STRUCTURAL
ENGINEER. REFER TO CHAPTER 25 OF ACI 318 FOR OTHER REINFORCING STEEL REQUIREMENTS.
MINIMUM LAPS AND EMBEDMENT
UNLESS OTHERWISE NOTED, REINFORCING SPLICE LENGTHS AND DEVELOPMENT LENGTHS SHALL BE AS TABULATED
BELOW:
f c = 3000 PSI
DEVELOPMENT LENGTH
LAP SPLICE
BAR
TENSION
COMPRESSION
TENSION
COMPRESSION
SIZE
TOP BARS
OTHER BARS
ALL BARS
TOP BARS
OTHER BARS
ALL BARS
#3
22
17
9
28
22
12
#4
29
22
11
37
29
15
#5
36
28
14
47
36
19
#6
43
33
17
56
43
23
#7
63
48
20
81
63
27
#8
72
55
22
93
72
30
NOTE:
1. ALL LENGTHS ARE IN INCHES.
2. ALL LAP SPLICES ARE CLASS B.
3. "TOP BARS" ARE HORIZONTAL REINFORCEMENT PLACED SUCH THAT MORE THAN 12 INCHES OF
CONCRETE IS CAST IN THE MEMBER BELOW THE BAR.
CONCRETE COVER ON REINFORCING
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH
CONCRETE EXPOSED TO EARTH AND WEATHER:
#6 BARS AND LARGER
#5 BARS AND SMALLER
CONCRETE NOT EXPOSED TO EARTH OR WEATHER:
SLABS, WALLS AND JOISTS
COLUMN TIES OR SPIRALS AND BEAM STIRRUPS
CONCRETE GENERAL NOTES
3"
2"
1 1/2"
3/4"
1 1/2"
VERTICAL BARS SHALL START FROM TOP OF FOOTING. HORIZONTAL BARS SHALL START A DISTANCE OF 1/2 THE
NORMAL BAR SPACING FROM TOP OF FOOTING AND TOP OF FRAMED SLABS. IN ADDITION, THERE SHALL BE A
HORIZONTAL BAR AT A MAXIMUM OF 3" FROM TOP OF WALL AND BOTTOM OF FRAMED SLABS.
PROVIDE CORNER BARS TO MATCH THE HORIZONTAL REINFORCING WITH TENSION LAP SPLICE AT EACH SIDE PER
TABLE, OR BEND ONE SIDE OVER TO PROVIDE TENSION LAP.
PROVIDE CONTROL OR CONSTRUCTION JOINTS IN SLABS ON GRADE TO BREAK UP SLAB INTO RECTANGULAR AREAS
OF NOT MORE THAN 400 SQUARE FEET EACH. AREAS TO BE AS SQUARE AS PRACTICAL AND HAVE NO ACUTE
ANGLES. JOINT LOCATIONS TO BE APPROVED BY THE ARCHITECT.
ALL CONSTRUCTION JOINTS SHALL BE THOROUGHLY CLEANED AND PROPERLY PREPARED IMMEDIATELY PRIOR TO
POURING OF CONCRETE. DOWEL STEEL SHALL BE THE SAME SIZE AND SPACING AS MAIN REINFORCING DETAILED
BEYOND JOINT.
SEE ARCHITECTURAL DRAWINGS AND MECHANICAL DRAWINGS FOR EXACT LOCATIONS AND DIMENSIONS OF
OPENINGS IN CONCRETE WALLS, FLOORS AND ROOF. UNLESS INDICATED OTHERWISE, REINFORCE AROUND
OPENINGS GREATER THAN 12" IN EITHER DIRECTION WITH (2) #5 EACH SIDE AND (1) #5 x 4'-0" DIAGONAL AT EACH
CORNER. EXTEND BARS 2'-0" BEYOND EDGE OF OPENING. IF 2'-0" IS UNAVAILABLE, EXTEND AS FAR AS POSSIBLE
AND HOOK. HOOK ALL REINFORCING INTERRUPTED BY OPENINGS.
BARS PARTIALLY EMBEDDED IN HARDENED CONCRETE SHALL NOT BE FIELD BENT UNLESS SO DETAILED OR
APPROVED BY THE STRUCTURAL ENGINEER.
SEE ARCHITECTURAL DRAWINGS FOR ALL GROOVES, NOTCHES, CHAMFERS, FEATURE STRIPS, COLOR, TEXTURE AND
OTHER FINISH DETAILS AT ALL EXPOSED CONCRETE SURFACES. PROVIDE 3/4" CHAMFER AT ALL CORNERS EXCEPT AS
NOTED.
LUMBER
ALL GRADES SPECIFIED ARE MINIMUM GRADES REQUIRED. ALL LUMBER SHALL BE IN ACCORDANCE WITH WWPA
GRADING RULES, KILN -DRIED TO MC 19 AND OF THE FOLLOWING MINIMUM STANDARDS:
SIZE CLASSIFICATION
SPECIES
GRADE
Fb (PSI)
Fc (PSI)
SLEEPERS
DOUG-FIR
STUD
700
-
LIGHT FRAMING (STUDS)
HEM -FIR
STUD
675
800
2x JOISTS AND PLANKS
HEM -FIR
#2
850
-
PLATES AND BLOCKING
HEM -FIR
#2
850
-
6x AND LARGER BEAMS AND
STRINGERS
DOUG-FIR
#2
875
-
4x AND SMALLER BEAMS AND
STRINGERS
HEM -FIR
#2
850
-
ALL POSTS AND TIMBERS
DOUG-FIR
#1
1200
1000
REFER TO PLAN NOTES, SCHEDULES, AND DETAILS FOR MORE SPECIFIC LUMBER SIZE AND GRADE REQUIREMENTS.
UNLESS NOTED OTHERWISE IN THE PLANS, ALL WOOD AND WOOD -BASED MEMBERS EXPOSED TO WEATHER OR IN
CONTACT WITH CONCRETE, MASONRY, OR WITHIN 8" OF SOIL SHALL BE PRESERVATIVE -TREATED BY
VACUUM -PRESSURE IMPREGNATION IN ACCORDANCE WITH AWPA STANDARD U1.
NAILS, BOLTS, AND METAL CONNECTORS FOR WOOD
ALL NAILS SHALL CONFORM TO THE STANDARDS SET FORTH BY THE NATIONAL DESIGN STANDARDS (NDS) FOR
WOOD CONSTRUCTION, LATEST EDITION. NAILING NOT SPECIFIED SHALL BE PER IBC TABLE 2304.10.1 NAILING
SCHEDULE. ALL NAILS CALLED OUT ON PLANS SHALL BE COMMON NAILS UNLESS NOTED OTHERWISE AND SHALL
MEET OR EXCEED THE FOLLOWING MINIMUM GUIDELINES:
NAIL
SHANK 0
MIN LENGTH
8d COMMON
0.1310
2 1/2" SHANK
10d COMMON
0.1480
3" SHANK
12d COMMON
0.1480
3 1/4" SHANK
16d COMMON
0.1620
3 1/2" SHANK
10d BOX NAILS MAY BE SUBSTITUTED FOR 8d COMMON NAILS WITH NO CHANGE IN NAIL SPACING. FRAMING
MEMBERS MAY BE NAILED WITH 16d SINKERS (0.148"0 x 3 1/4"), BUT ONLY 16d COMMON NAILS SHALL BE USED
WHERE 16d NAILS ARE INDICATED IN THIS DRAWING SET. ENGINEER MAY APPROVE OTHER NAILS IF NAIL LABELS
ARE SUBMITTED TO ENGINEER PRIOR TO START OF CONSTRUCTION.
ALL BOLTS IN WOOD MEMBERS SHALL CONFORM TO ASTM A307. PROVIDE WASHERS UNDER THE HEADS AND NUTS
OF ALL BOLTS AND LAG SCREWS BEARING ON WOOD. LEAD HOLES FOR LAG BOLTS SHALL BE BORED FOR THE
SHANK AND THREADED PORTIONS PER NDS 12.1.4.2.
CONNECTORS CALLED OUT BY LETTERS AND NUMBERS SHALL BE "STRONG -TIE" BY SIMPSON COMPANY, CATALOG
TO BE THE LATEST EDITION, OR ENGINEER APPROVED EQUAL. CONNECTORS SHALL BE INSTALLED IN ACCORDANCE
WITH THE MANUFACTURER'S RECOMMENDATIONS AND WITH THE NUMBER AND SIZE OF FASTENERS AS SPECIFIED
BY THE MANUFACTURER. WHERE CONNECTOR STRAPS CONNECT TWO MEMBERS, PLACE ONE-HALF OF THE NAILS,
SCREWS, OR BOLTS IN EACH MEMBER.
INSTALL SOLID BLOCKING AT ALL BEARING POINTS. ALL SHIMS SHALL BE SEASONED, DRIED, AND THE SAME GRADE
(MINIMUM) AS MEMBERS CONNECTED.
GALVANIZATION
UNLESS NOTED OTHERWISE, STEEL CONNECTORS IN CONTACT WITH TREATED WOOD SHALL BE GALVANIZED
ACCORDING TO THE FOLLOWING TABLE:
GALVANIZATION
UNTREATED
WOOD
CCA-C
SBX
ACQ-C
ACQ-D
CBA-A
CA-B
OTHER
BORATE
ACZA
OTHER PT
WOOD
G90
X
X
X
G185
X
X
X
X
X
X
HDG
X
X
X
X
X
X
STT300
X
X
X
X
X
X
X
X
G90 = 0.90 OZ. OF ZINC PER SQUARE FOOT OF AREA
G185 = 1.85 OZ. OF ZINC PER SQUARE FOOT OF AREA
HDG = HOT DIP GALVANIZED
SST300 = TYPE 316L STAINLESS STEEL
GLUE -LAMINATED TIMBER
GLUE -LAMINATED TIMBER SHALL BE DOUGLAS FIR, FABRICATED IN CONFORMANCE WITH ANSI/AITC STANDARD
A190.1, LATEST EDITION. EACH MEMBER SHALL BEAR AN AITC IDENTIFICATION MARK AND SHALL BE ACCOMPANIED
BY AN AITC CERTIFICATE OF CONFORMANCE. FABRICATOR SHALL BE CERTIFIED. MEMBERS SHALL BE OF THE
FOLLOWING MINIMUM STANDARDS:
SPAN
COMBINATION
Fb
SIMPLE SPAN BEAMS
24F-V4
2400 PSI
CANTILEVER OR MULTI -SPAN BEAMS
24F-V8
2400 PSI
EXISTING BUILDING
CONTRACTOR SHALL VERIFY ALL DIMENSIONS, MEMBER SIZES AND CONDITIONS OF THE EXISTING BUILDING
DEPICTED IN THE DRAWINGS, AND NOTIFY THE STRUCTURAL ENGINEER OF ANY DISCREPANCIES FOR POSSIBLE
REDESIGN.
CONTRACTOR RESPONSIBLE FOR COMPLETELY SEALING ALL AREAS WHERE EXISTING ROOF MATERIAL IS
PENETRATED OR REMOVED. PROVIDE WATER PROOFING AS REQUIRED BY THE ARCH.
GENERAL
CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS FOR COMPATIBILITY BEFORE PROCEEDING. ANY
DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT BEFORE PROCEEDING.
CONTRACTOR SHALL BE RESPONSIBLE FOR ERECTION STABILITY AND TEMPORARY SHORING AS NECESSARY UNTIL
PERMANENT SUPPORT AND STIFFENING ARE INSTALLED.
CONTRACTOR -INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT AND STRUCTURAL
ENGINEER FOR APPROVAL PRIOR TO FABRICATION OR CONSTRUCTION. CHANGES SHOWN ON SHOP DRAWINGS
ONLY WILL NOT SATISFY THIS REQUIREMENT.
DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE NOT
SPECIFICALLY INDICATED BUT ARE OF A SIMILAR CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS OF
CONSTRUCTION SHALL BE USED, SUBJECT TO REVIEW AND APPROVAL BY THE ARCHITECT AND THE STRUCTURAL
ENGINEER.
LEGEND
DEFINITION
SYMBOL
DEFINITION
NATIVE SOIL
SYMBOL
DIRECTION OF
FRAMING
— — — — —
EXTENT OF
FRAMING
GRANULAR FILL
COLUMNS
STRUCTURAL STEEL
COLUMN BEARING
ON BEAM
P
RATED SHEATHING
BEAM CONTINUOUS
OVER SUPPORT
�
SHEAR WALL
(SEE SCHEDULE)
SWX
CONCRETE WALL
COLUMN MARK
(SEE SCHEDULE)
BEARING STUD
WALL
FOOTING MARK
(SEE SCHEDULE)
O
`'
1
NON -BEARING
STUD WALL
HOLDOWN MARK
(SEE SCHEDULE)
BEARING STUD
SHEAR WALL
HANGER MARK
(SEE SCHEDULE)
O
NON -BEARING
STUD SHEAR WALL
FLAG NOTE
(SEE PLAN NOTES)
CMU WALL
STEEL MOMENT
FRAME CONN.
�V
ABBREVIATIONS
(A)
ABOVE
ANCHOR BOLT
HORIZ
HORIZONTAL
AB
KIP
KING POST
ALT
ALTERNATE
KSI
KIPS PER SQUARE INCH
MECHANICAL
ARCH
ARCHITECT
MECH
(B)
BELOW
MF
MOMENT FRAME
BLKG
BLOCKING
INS
NEAR SIDE
ON CENTER
BM
BEAM
OC
BOT
BOTTOM
BETWEEN
OPP
OPPOSITE
PLATE
BTWN
PL
CJP
COMPLETE JOINT PENETRATION
PLCS
PLACES
CLR
CLEAR
PSI
POUNDS PER SQUARE INCH
CMU
CONCRETE MASONRY UNIT
PSF
POUNDS PER SQUARE FOOT
COL
COLUMN
P/T
POST TENSIONED
CONIC
CONCRETE
PT
PRESSURE TREATED
CONN
CONNECTION
REINF
REINFORCING
CONT
CONTINUOUS
REQ'D
REQUIRED
DBL
DOUBLE
SCHED
SCHEDULE
SIMILAR
DET
DETAIL
SIM
DIM
DIMENSION
SOG
SLAB ON GRADE
STANDARD
EA
EACH
STD
ELEV
ELEVATION
EXISTING
SW
SHEAR WALL
TOP OF CONCRETE
EXIST
TOC
EXP
EXPANSION
TOS
TOP OF STEEL
FLR
FLOOR
TOW
TOP OF WALL
FDN
FOUNDATION
FOOTING
TYP
TYPICAL
FTG
LINO
UNLESS NOTED OTHERWISE
FS
FAR SIDE
FULL HEIGHT
VFY
VERIFY
VERIFY IN FIELD
FH
VIF
GLIB
GLUE -LAMINATED BEAM
VERT
VERTICAL
ALL WORK SUBJECT
TO FIELD
INSPECTION FOR
CODE COMPLIANCE
City Of Edmonds
Building Department
ENGINEERING
250 4TH AVE. S., SUITE 200
EDMONDS, WASHINGTON 98020
PHONE (425) 778-8500
FAX (425) 778-5536
01/ 2�/ 23
31
J F
Q F—
H 2
Z 2 CID
O m Ln
=) w
cn =
H F—
U 2 2
M I= =
LJ w w
a- a
DESIGN: AAL
DRAWN: ATD
CHECK: DMT
JOB NO: 22349.10
DATE: 1 2/ 1 6/22
Q
0—
W
U
W
0
RESUB
Jan 23 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
W 0
U N
0
I?Z00
0 O)
Lj
W > Q
� Q
APPROVED
Haaress 800 12TH AVE N
M: (n
PLANS MUST BE
Owner HAMBURG
W N 0
ON JOB SITE
m 0
Approved Date 1/26/2023
M o M
Building Official GWo 0� W. W OfAALIL
Q o 0
--------------
= 00 W
Permit Number BLD2022-1714
REVISIONS
DATE - PAGES - CHANGES
REV1
REV2
REV3
REV4
REV5
SHEET:
S1.1
Q
D
I—
U
D
I—
V)
Tom;
0
DECK FRAMING PLAN
SCALE: 1/4" = V-0"
BrARA nrn nl AM
7" L3x3x:
THRU
6"
DETAIL
SCALE: 1" = V-0"
DN ABU
IASE
CONCRETE
I W/ #3
1 3" OC
ED GRADE
NCRETE
ER PLAN
-A WAY
1 SI., Z^l
53.1 151.2
FULL DEPTH
BLOCKING
BEAM PER PLAN
DETAIL
SCALE: 1" = V-0"
Z W/ (2) 1/4" x 4"
TREWS @ 16" OC
SIMPSON DTT2Z
=CK TIE PER PLAN
SIMPSON LU
HANGER
JOIST PER PLAN
EXIST EXTERIOR
HOUSE WALL
OTE:
DR NOTES & INFO NOT
:IECIFICALLY CALLED OUT
EFER TO DETAIL 2.
SIMPSON LU
HANGER, TYP
BEAM PI
FRAMING DETAIL
SCALE: 1" = V-0"
SISTER W/ (2) 1/4"0 SIMPSON
SIDS SCREWS @ 12" OC
Z&
EXIST JOIST
NEW JOIST PER PLAN
ENGINEERING
250 4TH AVE. S., SUITE 200
EDMONDS, WASHINGTON 98020
PHONE (425) 778-8500
FAX (425) 778-5536
01123123
J
Q
z CID
O m Ln
Lu
� N �
U � �
LLJ Lu Lu
Q a- a
N
m
Ld
rq
lZ
Q
N
O
Y
Q
DESIGN:
AAL
DRAWN:
ATD
CHECK:
DMT
JOB NO: 22349.10
DATE:
1 2/ 1 6/22
Q: RESUB
Q
Jan 23 2023
0-
W
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
Y
Z
W
0
�
Ld
O
U
N
C)
Z
w
Z
00
Z
0
00
LLI
>
Q
W
<
LL
�
N
�
m
Q
U
Q
o
o
o
W
W
=
00
w
p
SHEET:
S2ml
4= - 4m�lhl
ENGINEERING
250 4TH AVE. S., SUITE 200
EDMONDS, WASHINGTON 98020
PHONE (425) 778-8500
FAX (425) 778-5536
Ig M. ?,
EXIST PICKET RAILING TO BE REPLACED EXIST PICKET RAILING TO BE REPLACED aF WA&45901
0
Hill
ANAL
01 / 23123
+I
pj�
m
El El El El El El El�
� EQ
ElEl
Q �cc
k-G
z2i�
O m cn
�=)W
�Ln=
COLUMN TO BE REMOVED F- F-
U 2 2
W w w
a a
c� m
EXISTING WEST ELEVATION N N
1 SCALE: 1/4" = V-0"
C) N \
r-I O
Y
Q
DESIGN: AAL
DRAWN: ATD
CHECK: DMT
JOB NO: 22349.10
DATE: 1 2/ 1 6/22
RESUB
Q Jan 23 2023
EXIST PICKET RAILING TO BE REPLACED CITY OFEDMONDS
w DEVELOPMENT SERVICES
DEPARTMENT
lEw ITHFUTHI PHROM APB Y
c� Z
o O
Ll w ~
U ON Q
O
w Z 00 w
0 � J
+I W j Q W
m Q
a
Z
m 0 (�
Q o o X W
2 00 w w
SHEET:
EXISTING SOUTH ELEVATION
2 SCALE: 1/4" = V-0" S3 ■
4= - llm�lhl
ENGINEERING
250 4TH AVE. S., SUITE 200
EDMONDS, WASHINGTON 98020
PHONE (425) 778-8500
FAX (425) 778-5536
NEW CABLE RAILING NEW CABLE RAILING Z5 M. ?,
of waste
0
ul R LL
ANAL
01123123
w
z
+I =
NEW COLUMNS `J
O
�IF IElEl Li
O
z
J
Q
Q �cc
k-G
z�12
O m cn
��W
REPLACE COLUMN REPLACE COLUMN cn =
H F-
U 2 2
W w w
a a
c14 m
PROPOSED WEST ELEVATION N N
1 SCALE: 1/4" = V-0"
N \
O
!GUARDRAILS SHALL BE MIN. 36" IN HEIGHT( (GUARDRAILS SHALL BE DESIGNED TO RESIST ■ Y
CONCENTRATED LOAD OF 200 POUNDS IN ANY I Q
WHERE THE ADJACENT SURFACE OR �
(GRADE IS 30" OR MORE BELOW. RAILINGS I (DIRECTION AT THE TOP OF THE GUARDRAIL.
!SHALL BE SPACED TO NOT ALLOW THE ■ .INFILL COMPONENTS SHALL BE DESIGNED TO ! DESIGN: AAL
(PASSAGE OF A 4" SPHERE. (RESIST A HORIZONTAL LOAD OF 50 POUNDS I DRAWN: ATD
■�■�■�■�■�■�■�■�■�■�■ ■OVER AONE SQUARE FOOT AREA.
�■�■�■�■�■�■�■�■�■�■�■i CHECK: DMT
JOB NO: 22349.10
DATE: 1 2/ 1 6/22
RESUB
QJan 23 2023
NEW CABLE RAILING 0- CITY OFEDMONDS
W DEVELOPMENT SERVICES
DEPARTMENT
N 11 �.j
U O
Ld
0 �
O Q
LiN >
U W
wp
Z 00 J
Lu 0 0� W
+I Q " • Q
�? U
� 0 LJ 0
F W
z 0 F- N N
w N 0 O
m T-- o � �O: O
Q O 0 W
= co w
SHEET:
PROPOSED SOUTH ELEVATION
2 SCALE: 1/4" = V-0"
S302