FIR2023-0041+Fire_Alarm_Battery_Calculations+4.28.2023_10.38.50_AM+3511753i N w U N co il�I, 7 N (9 O N — W Z C O _ d O tA C W C O > O p co V L Q<CD EDISH EDMONDS HOSPITALO � w�CD v CD�0 o ,2L ACC 1ST FLOOR MR1 SUITE T. I Eric , CET DRAWINGS REVIEWED BY. NICEBTeck#1 8077 Fire Alarm Svstems. Level III SITE GENERAL CONTRACTOR SWEDISH EDMONDS 21601 76TH AVE W EDMONDS,WA 98026-7506 OWNER SWEDISH EDMONDS 21601 76TH AVE W EDMONDS,WA 98026-7506 Johnson ,(I Controls SALES REPRESENTATIVE KEVIN JONES (206) 777-4838 kevin.3.jones@jci.com PROJECT COORD/NA TOR RICHARD KIM 206-777-4823 richard.kim@jci.com MORTENSON CONSTRUCTION 14719 NE 29TH PL BELLEVUE, WA 98009 INSTALLER COCHRAN INC 12500 AURORA AVE NORTH SEATTLE, WA 98133 12781 GATEWAY DRIVE TU KWI LA, WA 98168 Sheet List Table Sheet Number Include Sheet Title FA-001 X COVER SHEET FA-002 X GENERAL INFORMATION FA-101 DEVICE PLACEMENT PLAN - FIRST FLOOR PLAN - SECTOR 1 FA-102 DEVICE PLACEMENT PLAN - FIRST FLOOR PLAN - SECTOR 2 FA-103 X DEVICE PLACEMENT PLAN - FIRST FLOOR PLAN - SECTOR 3 FA-104 DEVICE PLACEMENT PLAN - FIRST FLOOR PLAN - SECTOR 4 FA-105 DEVICE PLACEMENT PLAN - FIRST FLOOR PLAN - SECTOR 5 FA-106 DEVICE PLACEMENT PLAN - FIRST FLOOR PLAN - SECTOR 6 FA-107 DEVICE PLACEMENT PLAN - FIRST FLOOR PLAN - SECTOR 7 FA-108 DEVICE PLACEMENT PLAN - INTERSTITIAL SPACE PLAN FA-109 DEVICE PLACEMENT PLAN - SECOND FLOOR PLAN - SECTOR A FA-110 DEVICE PLACEMENT PLAN - SECOND FLOOR PLAN - SECTOR D FA-111 DEVICE PLACEMENT PLAN - ROOF PLAN FA-201 RISER DIAGRAM FA-202 RISER DIAGRAM FA-501 PANEL DETAIL FA-601 FACP CALCULATIONS AND SCHEDULES FA-602 X FACP CALCULATIONS AND SCHEDULES FA-603 NAC1 CALCULATIONS AND SCHEDULES FA-701 X WIRING TYPICALS FA-702 WIRING TYPICALS FA-703 X WIRING TYPICALS REVIEW NOTES: 1. PROVIDE RECORD OF A COMPLETION IN ACCORDANCE WITH NFPA 72 PRIOR TO TESTING/ACCEPTANCE IFC 907.7.2 2. COMBINATION SMOKE/CO DETECTORS TEST INDEPENTLY BY FUCTION. 3. SYSTEM ACCEPTANCE INCLUDES BUILDING FUNCTIONS 1.E, DOOR HOLD SERVICE, DUCT INNITIATION HVAC CONTROL, ELEVATOR CONTROL, ETC. 0 0 0 N ry 0- U) O 0 0 � W o z�00 N = Ow rn U� o Q M w =� o L-H r_ z � CD v) co N �w M J � a7 C) — m U Q W cf) oe Z Cn Z W O (f) � m z Z :2 Q o O J Q � 2: O U = W Wp O p p ZO C L Q U LLJ J O CD CD0 Q Lo V O O W V �_ I� N (� M M M CD Cn M M CCD 14 � � U O — O — m O — O LL1 CD p c0 c.0 6) M Q Q Q Cn Q Q U W Q Q Q Q QCO O m W W W W U:5 Cn Q Q:E O O O O W M O Co Cp c0 LfJ LfJ lf') V cV N — — 7 QN N I O J W Y co < W CO Lf) V M N co Q Ln :�E PHONE: 206-291-1400 SERVICE: 206-291-1400 DRAWN BY: SHASHIKALA CHECKED BY: RAKESH ISSUE DATE: 8/8/14 JOB #: PROJECT #: 458:979327746 JCI © 2023 SYSTEM: FIRE ALARM SYSTEM SHEET: DESIGNER TECHNICIAN SCHEDULER I COVER SHEET ERIC BECK 206-777-4841 eric.q.beck@jci.com NICET Level IV, 102032 YVONNE THOMPSON 206-777-4860 yvonne.thompson@jci.com a mo J_ U m M 00 �n co N O N 0 N 0 w z a U) Q J GENERAL NOTES SYSTEM DESCRIPTION /SCOPE OF WORK SYMBOL KEY 1. THESE DRAWINGS DEPICT GENERAL LOCATIONS OF LIFE SAFETY EQUIPMENT & FIELD DEVICES. EXACT ROUTING OF CONDUITS TO BE DETERMINED IN THE FIELD BY THE INSTALLING CONTRACTOR TO SUIT CONDITIONS. ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS. 2. SHOULD ANY CONDITIONS EXIST THAT DIFFER FROM WHAT IS INDICATED ON THESE DRAWINGS WHICH CAUSE MAJOR DEVIATIONS IN THE WORK SHOWN, THE CONTRACTOR SHALL CONTACT JOHNSON CONTROLS IN A TIMELY MANNER SO AS NOT TO IMPAIR THE CONSTRUCTION SCHEDULE. 3. CONTRACTOR IS RESPONSIBLE FOR MAKING AND OBTAINING APPROVAL FOR ALL NECESSARY ADJUSTMENTS IN CIRCUITING AS REQUIRED TO ACCOMMODATE THE RELOCATION OF EQUIPMENT AND/OR DEVICES WHICH ARE AFFECTED BY ANY AUTHORIZED CHANGE. ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS. 4. A STAMPED SET OF APPROVED FIRE ALARM DRAWINGS SHALL BE AT THE JOB SITE AND SHALL BE USED FOR INSTALLATION. 5. THE POWER CIRCUIT TO THE FACP AND TO THE FIRE ALARM POWER SUPPLIES SHALL BE ON A DEDICATED 120V, 20A BRANCH CIRCUIT BREAKER, AND SHALL HAVE A RED MARKING, LOCK -ON PROVISION AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT CONTROL." THE LOCATION OF THE CIRCUIT DISCONNECT MEANS (CIRCUIT BREAKER) SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT. 6. UPDATE THE AS -BUILT DRAWING SET DAILY WITH JOB PROGRESS. RETURN THE AS -BUILT DRAWING SET TO JOHNSON CONTROLS NO LATER THAN 7 DAYS AFTER FINAL TEST. 7. THE CONTRACTOR WILL MAINTAIN ALL AREAS OF THE BUILDING IN A NEAT AND WORKMAN LIKE MANNER. 8. DO NOT APPLY POWER EXCEPT IN THE PRESENCE OF A FACTORY TRAINED JOHNSON CONTROLS TECHNICAL REPRESENTATIVE. 9. ANY SMOKE DETECTOR HEAD INSTALLED BEFORE THE BUILDING IS CLEANED AND ACCEPTED SHALL BE COVERED TO PROTECT FROM DUST. ANY FALSE ALARMS DUE TO DIRT CONTAMINATED HEADS SHALL BE THE RESPONSIBILITY OF THE FIRE ALARM INSTALLER. 10. THE FIRE ALARM INSTALLER WILL MAINTAIN THE FIRE RESISTANCE INTEGRITY OF ALL WALL, CEILING, AND ROOF ASSEMBLIES ANY TIME THAT WORK IS NOT ACTIVELY BEING PERFORMED. 11. INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. POWER LIMITED AND NON -POWER LIMITED FIELD WIRING MUST BE INSTALLED WITHIN THE FACP ENCLOSURE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND NEC. 12. ALL WIRING SHALL BE INSTALLED ACCORDING TO NFPA 70 (NEC). 13. FIRE ALARM CIRCUITS SHALL BE IDENTIFIED IN ACCORDANCE WITH APPROPRIATE SECTION OF NEC 760. MARK ALL FIRE ALARM WIRES IN ACCORDANCE WITH NEC 760 SECTIONS FOR POWER LIMITED AND NON -POWER LIMITED WIRE. 14 FIRE ALARM CABLE INSTALLED IN DUCTS, PLENUM, AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP. 15. FIRE ALARM CABLE INSTALLED IN THE VERTICAL RUNS AND PENETRATE MORE THAN ONE FLOOR OR CABLES INSTALLED IN VERTICAL RUNS IN SHAFTS SHALL BE TYPE FPLR. 16. FIRE ALARM CABLE INSTALLED IN UNDERGROUND CONDUIT OR OTHER WET LOCATIONS SHALL BE UL LISTED FOR WET LOCATIONS. 17. FIRE ALARM CIRCUITS EXTENDING BEYOND ONE BUILDING AND RUN OUTDOOR SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 70 ARTICLES 760, 770, 725 AND 800 WHERE APPLICABLE. 18. ALL WIRING, INCLUDING SHIELDS MUST BE DRY AND FREE OF SHORTS AND GROUNDS. 19. ALL SHIELDED WIRE MUST HAVE SHIELD CONTINUITY AT FULL LENGTH OF THE WIRE. 20. ONLY SYSTEM WIRING CAN BE RUN IN THE SAME CONDUIT. 21. 120VAC IS NOT PERMITTED IN THE SAME CONDUIT WITH LOW VOLTAGE WIRING. 22. MAINTAIN 40 PERCENT CONDUIT FILL RATIO AS PER NEC REQUIREMENTS. 23. EXISTING CONDUITS MAY BE USED BY THE INSTALLATION CONTRACTOR AS DEEMED NECESSARY, HOWEVER, ANY EXISTING CONDUIT WILL BE USED ONLY IF CONDUITS MEET CURRENT STANDARDS AND CODES. JOHNSON CONTROLS MAKES NO STATEMENTS WRITTEN OR VERBAL AS TO THE CONDITION OF EXISTING CONDUITS. W RE SCHEDULE FIRE ALARM WIRE LIST CIRCUIT DESCRIPTION RISER RATED: FPLR ISINGLE CONDUCTOR(THHN,TFFN) PLENUM RATED: FPLP B RUI/N2 COMMUNICATION SG ANIX./PAIGE 740215 SG ANIX./PAIGE 740214L 1 PAIR 18 AWG TWISTED AREA=0.0196 SQ. INCH AREA=0.0196 SQ. INCH OVERALL SHIELD ANIXTER PART NUMBER ANIXTER PART NUMBER T740215 FAMC-1802C-1-2S-03B5 D DOOR HOLDER CIRCUIT SG ANIX./PAIGE 454718ARE SG ANIX./PAIGE 454719ARE 2 CONDUCTOR TWISTED AREA=0.0380 SQ. INCH AREA=0.0333 SQ. INCH PAIR 14 AWG SOLID ANIXTER PART NUMBER (2) #14 AWG ANIXTER PART NUMBER FA-1402C-1-IN-03-BX AREA=0.0097 SQ. INCH (EACH) FA- 1 402C- 1 -2N-03 K REMOTE TEST SWITCH/ SG ANIX./PAIGE 454703ARE SG ANIX./PAIGE 740132R LED CIRCUIT - (2) 2 AREA=0.0204 SQ. INCH AREA=0.0141 SQ. INCH CONDUCTOR 18 AWG ANIXTER PART NUMBER (4) #18 AWG ANIXTER PART NUMBER SOLID FA-1802C-1-1N-03-BX AREA=0.0055 SQ. INCH (EACH) FA- 1 802C- 1 -2N-03 M MAPNET/IDNET CIRCUIT SG ANIX./PAIGE 740215 SG ANIX./PAIGE 740214L 1 PAIR 18 AWG TWISTED AREA=0.0196 SQ. INCH AREA=0.0196 SQ. INCH OVERALL SHIELD ANIXTER PART NUMBER ANIXTER PART NUMBER T740215 FAMC-1802C-1-2S-03B5 N RS-485 COMMUNICATION SG ANIX./PAIGE 740215 SG ANIX./PAIGE 740214L TRUNK - 1 PAIR 18 AWG AREA=0.0196 SQ. INCH AREA=0.0196 SQ. INCH TWISTED OVERALL SHIELD ANIXTER PART NUMBER ANIXTER PART NUMBER T740215 FAMC-1802C-1-2S-03B5 P POWER CIRCUIT SG ANIX./PAIGE 454718ARE SG ANIX./PAIGE 454719ARE 2 CONDUCTOR AREA=0.0380 SQ. INCH AREA=0.0333 SQ. INCH 14 AWG SOLID (SUBSCRIPT ANIXTER PART NUMBER (2) #14 AWG ANIXTER PART NUMBER "r" IF RESETTABLE) FA-1402C-1-IN-03-BX AREA=0.0097 SQ. INCH (EACH) FA- 1 402C- 1 -2N-03 R RELAY CIRCUIT SG ANIX./PAIGE 454718ARE SG ANIX./PAIGE 454719ARE 2 CONDUCTOR AREA=0.0380 SQ. INCH AREA=0.0333 SQ. INCH 14 AWG SOLID ANIXTER PART NUMBER (2) #14 AWG ANIXTER PART NUMBER FA-1402C-1-IN-03-BX AREA=0.0097 SQ. INCH (EACH) FA- 1 402C- 1 -2N-03 S AUDIO CIRCUIT SG ANIX./PAIGE 454703ARE SG ANIX. PAIGE 740132R 1 PAIR 18 AWG TWISTED AREA=0.0204 SQ. INCH AREA=O. 141 SQ. INCH UNSHIELDED ANIXTER PART NUMBER ANIXTER PART NUMBER FA-1802C-1-1N-03-BX FA- 1 802C- 1 -2N-03 V VISUAL/SIGNAL CIRCUIT SG ANIX./PAIGE 454718ARE SG ANIX./PAIGE 454719ARE 2 CONDUCTOR 14 AWG AREA=0.0380 SQ. INCH AREA=0.0333 SQ. INCH SOLID ANIXTER PART NUMBER (2) #14 AWG ANIXTER PART NUMBER FA-1402C-1-IN-03-BX AREA=0.0097 SQ. INCH (EACH) FA- 1 402C- 1 -2N-03 Z ZONE CIRCUIT SG ANIX./PAIGE 454703ARE SG ANIX./PAIGE 740132R 2 CONDUCTOR 18 AWG AREA=0.0204 SQ. INCH AREA=0.0141 SQ. INCH SOLID ANIXTER PART NUMBER (2) #18 AWG ANIXTER PART NUMBER FA-1802C-1-1N-03-BX AREA=0.0055 SQ. INCH (EACH) FA- 1 802C- 1 -2N-03 CONDUIT SIZE CONDUCTOR AREA CONDUIT SIZE CONDUCTOR AREA 1/2" 0.12 SQ INCH * 1-1 /4" 0.60 SQ INCH * 3/4" 0.21 SQ INCH 1-1 /2" 082 INCH * 1 0.34 SQ INCH * 2 SSQ .Q INCH * * 40% FILL PER N.E.C. THE CABLES SPECIFIED HERE ARE FOR REFERENCE OF REQUIRED ELECTRICAL CHARACTERISTICS AS WELL AS CODE REQUIREMENTS. ALTERNATE SUPPLIERS MAY BE SUBSTITUTED PROVIDING EQUIVALENT CHARACTERISTICS ARE MAINTAINED. ITEMS SUCH AS CAPACITANCE BETWEEN CONDUCTORS AND WIRE GAUGE CAN BE CRUCIAL TO THE CIRCUIT DESIGN OF THIS SYSTEM INSTALLATION. REFERENCE https://www.anixter.com/customer/tycofs FOR SG ANIXTER CABLE DATA OCCUPANCY TYPE: SPRINKLER PROTECTION 1-2 INSTITUTIONAL GROUP BUILDING IS FULLY SPRINKLED LEVEL 1 MRI SUITE TENANT IMPROVEMENT. PROVIDE AND INSTALL TWO NEW DEVICES AS INDICATED ON DRAWINGS. ALL WIRING TO BE CLASS B. WIRING IS STYLE Y FOR NOTIFICATION APPLIANCE CIRCUITS, STYLE B FOR INITIATING DEVICE CIRCUITS, AND STYLE 4 FOR SIGNALING LINE CIRCUITS. AUTOMATIC FIRE ALARM SYSTEM SHALL TRANSMIT THE ALARM, SUPERVISORY AND TROUBLE SIGNALS TO AN APPROVED SUPERVISING STATION. THE SUPERVISING STATION SHALL BE LISTED AS EITHER UUFX OR UUJS UNDERWRITERS LABORATORY OR SHALL MEET THE REQUIREMENTS OF FACTORY MUTUAL RESEARCH APPROVAL STANDARD 3011. SUPERVISION OF SYSTEM AND LEASED TELEPHONE LINES SHALL BE ARRANGED BY THE OWNER. RE ALARM APPLICABLE CODES & STANDARDS Original Build WASHINGTON ADMINISTRATIVE CODE CHAPTERS 51-54, 2012 (AMENDED INTERNATIONAL FIRE CODE (IFC), 2012 EDITION) NATIONAL FIRE ALARM CODE (NFPA 72), 2010 EDITION NATIONAL ELECTRIC CODE (NFPA 70), 2008 EDITION ELEVATOR CODE - ASME A17.1-2004, ASME A17.1A-2005 JURISDICTIONS WITHIN THE STATE MAY HAVE AMENDMENTS TO THE STATE ADOPTED CODE. CHECK WITH THE LOCAL JURISDICTION AUTHORITY FOR MORE DETAILS. Tenant Improvement National Fire Alarm and Signaling Code (NFPA 72), 2016 Edition National Electrical Code (NFPA 70), 2020 Edition International Building Code (IBC), 2018 Edition w/ Washington Amendments - WAC 51-50 International Fire Code (IFC), 2018 Edition wl Washington Amendments - WAC 51-54A International Mechanical Code (IMC), 2018 Edition wl Washington Amendments - WAC 51-52 ICC/ANSI Al 17.1-2009 Accessibility w/ WAC 51-50-1101.2 ABBREVIATIONS LEGEND AC = ABOVE CEILING C = CEILING MOUNTED E = EXISTING TO REMAIN RC = EXISTING TO REMOVE AND COVER RD = EXISTING DEVICE TO BE RELOCATED RL = RELOCATED DEVICE RR = REMOVE EXISTING AND REPLACE W/NEW WP = WEATHERPROOF XP = EXPLOSION PROOF H = HIGH HUMIDITY AFF = ABOVE FINISHED FLOOR AHJ = AUTHORITY HAVING JURISDICTION ALM = ALARM ANN = ANNUNCIATOR BMS = BUILDING MANAGEMENT SYSTEM CBC = CALIFORNIA BUILDING CODE CD = (eg. 15CD) CANDELA CSFM = CALIFORNIA STATE FIRE MARSHALL DET = DETECTOR DGP = DATA GATHERING PANEL EOL = END OF LINE EPO = EMERGENCY POWER OFF FACP = FIRE ALARM CONTROL PANEL FATC = FIRE ALARM TERMINAL CABINET FBO = FURNISHED BY OTHERS FCC = FIRE COMMAND CENTER FAA = FIRE ALARM ANNUNCIATOR FTR = FIRE ALARM TRANSPONDER FSD = FIRE SMOKE DAMPER HT = HEIGHT HVAC = HEATING, VENTILATION, & AIR CONDITIONING IMS = INFORMATION MANAGEMENT SYSTEM MAX = MAXIMUM MIN = MINIMUM N/A = NOT APPLICABLE NAC = NOTIFICATION APPLIANCE CIRCUIT EXTENDER NDU = NETWORK DISPLAY UNIT NEC = NATIONAL ELECTRICAL CODE NFPA = NATIONAL FIRE PROTECTION ASSOCIATION NIC = NOT IN CONTRACT NPU = NETWORK PROCESSING UNIT NTS = NOT TO SCALE PAP = PRE -ACTION PANEL SCC = STATUS COMMAND CENTER SLC = SIGNALING LINE CIRCUIT SMK = SMOKE SUPV = SUPERVISORY TAC = TRUEALERT ADDRESSABLE CONTROLLER TRBL = TROUBLE TS = TAMPER SWITCH TYP = TYPICAL UON = UNLESS OTHERWISE NOTED VCC = VOICE COMMAND CENTER VT = VALVE TAMPER WF = WATER FLOW W = (eg. 1 /2W) WATT W/ = WITH W/O = WITH OUT DEVICE ADDRESSING LEGEND ADDRESSABLE CARD (IDNET OR MAPNET) NODE DESIGNATOR ----] r DEVICE ADDRESS N1:M2-11 ADDRESSABLE DEVICES NUMBERING SPEAKER CIRCUIT NODE DESIGNATOR -] r DEVICE DESIGNATOR N 1:S2-1 SPEAKER DEVICE 4009 NAC PANEL I [CIRCUIT DESIGNATOR (WHEN APPLICABLE) V=VISUAL OR A/V, H=AUDIBLE ONLY) NODE DESIGNATOR ----i r- DEVICE DESIGNATOR N 1: NAC 1:V2-1 VISUAL, AUDIBLE OR A/V DEVICE SYMBOL DESCRIPTION MODEL# BACKBOX SUPPLIED BY JOHNSON CONTROLS FACP FIRE ALARM CONTROL PANEL SIMPLEX 4100-9114 (REFER TO MOUNTING DETAIL FOR SPECIFIC DIMENSIONS) W / 50AH BATTERY SET SIMPLEX 2081-9296 FAA SERIAL LCD ANNUNCIATOR SIMPLEX 4603-9101 6 GANG BOX 3 1/2" DEEP NAC EXTENDER PANEL FN-AC-fl # DESIGNATES THE NAC PANEL NUMBER SIMPLEX 4009-9201 SUPPLIED BY JOHNSON CONTROLS W / 6.2AH BATTERY SET SIMPLEX 2081-9272 ❑F MANUAL PULL STATION SIMPLEX 4099-9001 SINGLE GANG BOX 2 1/2" DEEP SMOKE SENSOR / BASE SIMPLEX 4098-9714 Q SIMPLEX 4098-9792 BASE 4" OCTAGONAL BOX 1 1/2" DEEP SMOKE SENSOR, WITH CO SENSOR BASE SIMPLEX 4098-9714 9CO SIMPLEX 4098-9770 BASE 4" OCTAGONAL BOX 1 1/2" DEEP HEAT SENSOR / BASE SIMPLEX 4098-9733 O SIMPLEX 4098-9792 BASE 4" OCTAGONAL BOX 1 1/2" DEEP DUCT SMOKE SENSOR SIMPLEX 4098-9756 MOUNT TO DUCTWORK QR TRACK MOUNTED SINGLE RELAY SPDT W/ ENCLOSURE SIMPLEX 2088-9008 SUPPLIED W/ ENCLOSURE C (APOLLO AMERICA INC MR-101/C) Op ENCAPSULATED RELAY AIR PRODUCTS PAM-SD SINGLE GANG BOX 2 1/8" DEEP W/COVER 0 REMOTE TEST STATION W/ LED AND KEY SWITCH SIMPLEX 2098-9806 SINGLE GANG BOX 2 1/2" DEEP aM INDIVIDUAL ADDRESSABLE MODULE SIMPLEX 4090-9001 SINGLE GANG BOX 2 1/2" DEEP WITH COVER ® RELAY IAM SIMPLEX 4090-9002 4" SQUARE BOX 2 1/8" DEEP W/TWO GANG COVER WALL MOUNT MULTI -CANDELA STROBE ONLY WHITE SIMPLEX 4906-9103 4" SQUARE BOX 1 1/2" DEEP # =CANDELA RATING W/4905-9940 ADAPTER SKIRT WHEN SURFACE MOUNTED CEILING MOUNT MULTI -CANDELA STROBE ONLY WHITE SIMPLEX 4906-9104 HANDY BOX 1 1/2" DEEP # =CANDELA RATING # # WALL MOUNT MULTI -CANDELA SPEAKER/STROBE WHITE SIMPLEX 4906-9153 4" SQUARE BOX 1 1/2" DEEP W/ 1 1/2" EXTENSION RING # =CANDELA RATING, #W = SPEAKER TAP **USE 70 VOLT TAP** W/4905-9947 ADAPTER SKIRT WHEN SURFACE MOUNTED # # CEILING MOUNT MULTI -CANDELA SPEAKER/STROBE WHITE SIMPLEX 4906-9154 4" SQUARE BOX 1 1/2" DEEP W/ 1 1/2" EXTENSION RING c # =CANDELA RATING, #W = SPEAKER TAP **USE 70 VOLT TAP** # C ADDRESSABLE CEILING MOUNT MULTI -CANDELA HORN/STROBE WHITE SIMPLEX 4906-9230 4" SQUARE BOX 1 1/2" DEEP # =CANDELA RATING Q DOOR HOLDER RSG DH1224FPC SINGLE GANG BOX 2 1/2" DEEP ® TAMPER SWITCH SUPPLIED BY OTHERS INSTALLED BY MECHANICAL CONTRACTOR W POST INDICATOR VALVE SUPPLIED BY OTHERS INSTALLED BY MECHANICAL CONTRACTOR © WATERFLOW SWITCH SUPPLIED BY OTHERS INSTALLED BY MECHANICAL CONTRACTOR O� SMOKE/FIRE DAMPER SUPPLIED BY OTHERS SUPPLIED BY OTHERS DC SMOKE DOOR RELEASE MECHANISM, WALL MOUNTED MAGNETIC TYPE SUPPLIED BY OTHERS SUPPLIED BY OTHERS END -OF -LINE RESISTOR 3.3K (EOL) SIMPLEX 4081-9002 # END -OF -LINE RESISTOR 4.7K (EOL) SIMPLEX 4081-9003 END -OF -LINE RESISTOR 6.8K (EOL) SIMPLEX 4081-9004 SUPPLIED BY OTHERS END -OF -LINE RESISTOR 10K (EOL) SIMPLEX 4081-9008 SEQUENCE OF OPERATION SYSTEM INPUTS REMARKS SMOKE/• 1 /•MANUAL PULL STATION ©HEAT SENSOR/DETECTOR DUCT SENSOR/DETECTOR © MAIN FLR. SMOKE DETECTOR LOBBY 00----000-00---000--0-----------00-0© Q. � • � :: � 1 � • 00����000�00���000�0������������00�00 ELEVATOR MECH. ROOM / 1 / • ELEVATOR SHAFT HEAT DETECTOR m1ELEVATOR SHAFT SMOKEDETECTOR m ELEVATOR •, • MONITOR --��--�---�-�----------------------�m ®WATERFLOW SWITCHTAMPER SWITCH m POST INDICATOR VALVE SWITCH INFIRIEALARM AC POWER FAILURE FIRE ALARM SYSTEM LOW BATTERY m OPEN OR GROUND ----��----�--�---------------------Om m oil IN m 92 Im I:1�Jl/l�J■�■�<JW■■�1■:�■�■u■Wv■,L>•■:�17■I.111VWl:�VL� '�' ': I:i/11:1JI:l�fli/:i�lCl:lld>•I:I�J 0 (V O O C � O w z a O C w C > o O 00 Q00 CY) V �Q04 04 O d' .<< i; N C �Yof -F-W DRAWINGS REVIEWED BY: Eric Beck, CET �,�. NICET #148077 Fire Alarm Svstems, Level III 0- V J 0 V J 0 Z 0 Co O 0 r- ti W o Z N W O Q W 00 rn 0 W = Q -- LU c~O r__ = �0 0 0 v ! C/5 CO cV F LU 0 0 0 o= M J � rn U - m U F_: Q LU u H z 0 N m z ZD N Q o 0000= < LU LU o 0 0 0 z0 C L Q C) F- r, r, O Q z 0 0 0 L(i W I� V t= r- (V U V Cl) M M CD CD O O (=) O U) Cl) CV Lo L0 U m O o0 N N (D GO 6) 6) Q Q Q w Q Q C) LU a Q a U) Q Q m 0 0 0 0 N Q N N O j� M 4 1­ co OUj Y co < O coO l2') V M N DRAWN BY: SHASHIKALA CHECKED BY: RAKESH ISSUE DATE: 8/8/14 JOB #: PROJECT #: 458:979327746 JCI © 2023 SYSTEM: FIRE ALARM SYSTEM SHEET: GENERAL INFORMATION 0 0 0 0 E ►= i J_ U r Co N Co N O N O N p LL H z n, 0- Co J PLAN NORTH DEVICE PLACEMENT PLAN SCALE: 1 /8" = V-0" - FIRST FLOOR PLAN -SECTOR 3 0 4 8 16 (IN FEET) 0 REVISION 9 GENERAL NOTES: 1. EXISTING WIRING AND DEVICE LOCATION INFORMATION IS BASED ON RECORD DRAWINGS PROVIDED BY OTHERS. FIELD VERIFY ALL EXISTING DEVICE LOCATIONS AND WIRING NEEDED. CONTRACTOR TO REDLINE AND NOTE ANY AND ALL CHANGES ON RECORD DRAWING. 2. TAP SPEAKERS AT 1/2W UNLESS OTHERWISE NOTED. REVISION 9 FLAG NOTES: Q TIE-IN TO EXISTING FLOOR SPEAKER AND STROBE CIRCUITS AT THIS LOCATION. o 0 (V O 0 C 0 w z C W CtA > o O p Q�� V LuQ� O �_ d' Qa04 N C Lu - F-tn DRAWINGS REVIEWED BY: Eric Beck, CET NICET #148077 Fire Alarm Svstems, Level III n C ) O Co O L0 Ill W o z�00 N = Ow rn C/) — o Q w w _� cn ll o z c)'- O C w�� Lw ! C/) c,4 3 0 0 0 ry F o= M _ O J � rn U — m U Q LU u p Z Co `n Z 0 N m Z = N QLu p p U ) = OfW Lu p O p p ZO Q U F- M M O Q Z o 0 o U Q ao 0 0_ Lu­: v o 0 U V Cl) Cl)Cc'.)O O O CDU CI) N )Lu _ O o0 N N in Co GO 6) 6) Q Q Q Cn Q Q 0 Lu a Q a a U Co Q Q m 0 0 O O W Cl)N O � v v N Q N N O M O J W `Y 7D Of O 1-1-1- li') V M N Co DRAWN BY: SHASHIKALA CHECKED BY: RAKESH ISSUE DATE: 8/8/14 JOB #: PROJECT #: 1 458:979327746 JCI © 2023 SYSTEM: FIRE ALARM SYSTEM SHEET: DEVICE PLACEMENT PLAN - FIRST FLOOR PLAN - SECTOR 3 FA-103 0 0 0 m o O O N 3 � m — h � m .o J_ U 73 co c� co N 0 N 0 N 0 w z a U) Q J U)N w U Q N X 0 M SMC EDMONDS ACC FACP 4100es FACP Standby Total Alarm Total Module Qty Description Current Standby Current Alarm Panel Equipment 4100-9114 1 4100 MASTER CONTROLLER, INFO -ALARM DISPLAY * 0.4450 0.4450 0.5400 0.5400 4100-0634 1 POWER DISTRIBUTION MODULE 120V 0.0000 0.0000 0.0000 0.0000 4100-1240 1 AUXILIARY AUDIO INPUT BOARD 0.0100 0.0100 0.0100 0.0100 4100-1241 1 IMESSAGE EXPANSION BOARD - 8 MINUTES 0.0020 0.0020 0.0170 0.0170 4100-1245 1 FLEX 50 EXPANSION NAC BOARD 0.0084 0.0084 0.0600 0.0600 4100-1253 1 1.5 CHANNEL AUDIO OPERATOR INTERFACE 0.0000 0.0000 0.0240 0.0240 4100-1280 2 8 SWITCH, 8 RED LED MODULE 0.0000 0.0000 0.0240 0.0480 4100-1288 1 64/64 LED/SWITCH CONTROLLER 0.0200 0.0200 0.0200 0.0200 4100-1312 2 ANALOG FLEX 50W AMP W/3 CLASS B NACS 25V 0.0850 0.1700 2.2700 4.5400 4100-2320 1 AUDIO EXPANSION BAY KIT 0.0000 0.0000 0.0000 0.0000 4100-3101 1 IDNET MODULE, UP TO 250 POINTS * 0.0750 0.0750 0.1150 0.1150 4100-3202 1 4 RELAYS, 10 AMP CONTACTS 0.0150 0.0150 0.1750 0.1750 4100-5101 3 EXPANSION PWR SUPPLY (XPS) - 120VAC 60HZ 0.0500 0.1500 0.0500 0.1500 4100-6052 1 EVENT REPORTING DACT 0.0300 0.0300 0.0400 0.0400 4100-6078 1 NETWORK IF CARD, MODULAR 0.0460 0.0460 0.0460 0.0460 4100-6056 2 NETWORK MEDIA CARD WIRED 0.0550 0.1100 0.0550 0.1100 4100-9620 1 BASIC AUDIO WITH MICROPHONE - ANALOG 0.2250 0.2250 0.2250 0.2250 4100-5115 1 EXPANSION NAC MODULE - 3 NACS 1 0.0250 1 0.0250 1 0.0250 1 0.0250 Panel Totals 1.3314 6.1450 IDNet Addressable Devices (SLC) 4099-9001 11 IDNET SINGLE ACTION PULL STATION * 0.0000 0.0000 0.0000 0.0000 4090-9001 13 IDNET SUPERVISED IAM * 0.0000 0.0000 0.0000 0.0000 4090-9002 7 IDNET RELAY IAM * 0.0000 0.0000 0.0000 0.0000 4098-9714 143 TRUEALARM PHOTO SMOKE SENSOR 0.0000 0.0000 0.0000 0.0000 4098-9733 4 TRUEALARM HEAT SENSOR 0.0000 0.0000 0.0000 0.0000 4098-9756 76 TRUEALARM DUCT SMOKE SENSOR W/ RELAY OUTPUT * 0.0000 0.0000 0.0000 0.0000 4009-9201 1 4009 IDNET NAC EXTENDER, 120 VAC * 0.0000 0.0000 0.0000 0.0000 4098-9792 130 TRUEALARM SENSOR BASE * 0.0000 0.0000 0.0000 0.0000 4098-9780 2 TRUEALARM 2 WIRE RELAY SENSOR BASE * 0.0000 0.0000 0.0000 0.0000 4098-9770 15 TRUEALARM SENSOR BASE WITH CO MODULE * 0.0000 0.0000 0.0000 0.0000 Miscellaneous Peripheral Devices That May Require System Power 4098-9843 76 ENCAPSULATED RELAY PAM-SD 0.0000 0.0000 0.0150 1.1400 4098-9756 76 TRUEALARM DUCT SMOKE SENSOR W/ RELAY OUTPUT 0.0030 0.2280 0.0150 1.1400 4098-9860 2 2-WIRE RELAY FOR USE WITH 4098-9780 SENSOR BASE 0.0000 0.0000 0.0000 0.0000 Notification Appliances 4906-9103 63 V/0 MC NON -ADDRESS, WHT, WALL 15 0.0000 0.0000 0.0600 3.7800 4906-9103 12 V/0 MC NON -ADDRESS, WHT, WALL 30 0.0000 0.0000 0.0940 1.1280 4906-9103 4 V/0 MC NON -ADDRESS, WHT, WALL 75 0.0000 0.0000 0.1860 0.7440 4906-9153 1 S/V M-C NON -ADDRESS, WHT, WALL 110 0.0000 0.0000 0.2520 0.2520 4906-9153 30 S/V M-C NON -ADDRESS, WHT, WALL 15 0.0000 0.0000 0.0600 1.8000 4906-9153 2 S/V M-C NON -ADDRESS, WHT, WALL 30 0.0000 0.0000 0.0940 0.1880 4906-9153 9 S/V M-C NON -ADDRESS, WHT, WALL 75 0.0000 0.0000 0.1860 1.6740 4906-9154 1 S/V M-C NON -ADDRESS, WHT, CEILING 15 0.0000 0.0000 0.0750 0.0750 4906-9154 1 S/V M-C NON -ADDRESS, WHT, CEILING 30 0.0000 0.0000 0.1250 0.1250 49 - 5 - N- 5 .0 0 0. 3 .3 0 Peripheral Totals 0.2280 14.6920 Added Current for EPS Conversion of 24 to 29 Volt IDNac Devices 0.0000 0.0000 RUI Totals 0 0.0000 0.0000 Address Totals 255 Addresses 0.2039 0.2547 * Device Address current draw included below (See Additional Current Draws): 2. Backup Amplifier assumes Main Amplifier alarm current on failure. C Battery Set #1 (Cabinet/Charger #1) Select ALL Power Supplies on this battery set: SPS-1 XPS-2 X Additional Current Draws: p-2 Total Standbyl 1.7633 j Total Alarml 21.0917 Standby Standby Alarm Alarm Current Total Current Total 1.0314 6.1740 0.1500 6.1170 0.2 00 4.5900 0.1580 3.9560 9 Q 0.0850 2.2700 Q ub otal 1.7294 2 .37 0 9 MAPNET/IDNet Device Address Communication Current 255 x 0.000800 = 0.20S9 x 0.000999 = 0.2547 Sub Total 1.9333 25.6317 Spare addressable point capacity 0% 0 x 0.0008 = 0.0000 x 0.000999 = 0.0000 Total 1.9333 25.6317 Standby Time = 24 Hrs x 1.9333 Standby Ah Alarm Time = 5 Min 0.08333 x 25.6317�46.3992 2.1360 Alarm Ah 48.5352 Additional Spare Battery Capacity = 0% + 0.0000 48.5352 Battery Discharge Factor = 20% + 9.7070 Minimum Battery Required PW-PS12750U 75AH (2x) 58.2422 Battery Supplied PW-PS12750U 75AH (2x) SMC EDMONDS ACC FACP - SPS-1 CIRCUIT SUMMARY & VOLTAGE DROP Plan Circuit Description Load % Drop N4:V3 FIRST FLOOR VISUAL CIRCUIT SIG3 0.792A 4.98% N4:V4 FIRST FLOOR VISUAL CIRCUIT SIG4 1.488A 10.32% N4:V5 IFIRST FLOOR VISUAL CIRCUIT SIG5 1.379A 1 12.58% 3.659A Total Ili]I►�C.�.y7[�Pi�l�■I�■�L1�Ni��.��:����:iC�7�'1��11�[el�la�l[yX.� N4:V3 Distributed Load Voltage Drop Allowable % Drop: Wire Gauge: Starting Voltage: Circuit Capacity 17.9% Wire Res. Per Ft. 0.0031 @ 75° Celsius Min. Device Voltage: 16.vdc % Voltage Drop 4.98% Normal Operation 14ga 19.5vdc 3.A Device # PID Candela Distance (Feet) Device Current Voltage Drop Voltage At Device N4:V3-1 4906-9103 15cd 68 0.060 0.331 19.17 N4:V3-2 4906-9103 15cd 30 0.060 0.466 19.03 N4:V3-3 4906-9103 15cd 24 0.060 0.565 18.94 N4:V3-4 4906-9153 75cd 27 0.186 0.666 18.83 N4:V3-5 4906-9103 15cd 53 0.060 0.805 18.70 N4:V3-6 4906-9153 75cd 26 0.186 0.863 18.64 N4:V3-7 4906-9103 15cd 38 0.060 0.905 18.59 N4:V3-8 4906-9103 15cd 70 0.060 0.957 18.54 N4:V3-9 4906-9103 15cd 39 0.060 0.971 18.53 Totals:1 375 Ft. 10.792A N4:V4 Distributed Load Voltage Drop Allowable % Drop: Wire Gauge: Starting Voltage: Ckt Capacity 17.9% Wire Res. Per Ft. 0.0031 @ 75° Celsius Min. Device Voltage: 16.vdc % Voltage Drop 10.32% 14ga 19.5vdc 3.A Normal Operation Device # PID Candela Distance (Feet) Device Current Voltage Drop Voltage At Device N4:V4-1 4906-9103 15cd 70 0.060 0.640 18.86 N4:V4-2 4906-9103 15cd 20 0.060 0.815 18.69 N4:V4-3 4906-9154 110cd 20 0.316 0.983 18.52 N4:V4-4 4906-9154 75cd 60 0.233 1.370 18.13 N4:V4-5 4906-9103 15cd 20 0.060 1.471 18.03 N4:V4-6 4906-9103 15cd 15 0.060 1.541 17.96 N4:V4-7 4906-9154 75cd 80 0.233 1.884 17.62 N4:V4-8 4906-9154 75cd 35 0.233 1.984 17.52 N4:V4-9 4906-9154 75cd 20 0.233 2.013 17.49 Totals:1 340 Ft. 1 1.488A N4:V5 Distributed Load Voltage Drop Allowable % Drop: Wire Gauge: Starting Voltage: Ckt Capacity 17.9% 14go Wire Res. Per Ft. 0.0031 @ 75° Celsius Min. Device Voltage: 16.vdc % Voltage Drop 12.58% Normal Operation 19.5vdc 3.A Device # PID 4906-9154 Candela Distance (Feet) Device Current Voltage Drop Voltage At Device N4:V5-1 75cd 190 0.233 1.609 17.89 N4:V5-2 4906-9154 75cd 25 0.233 1.785 17.72 N4:V5-3 4906-9154 75cd 50 0.233 2.065 17.44 N4:V5-4 4906-9103 30cd 35 0.094 2.211 17.29 N4:V5-5 4906-9103 15cd 15 0.060 2.265 17.23 N4:V5-6 4906-9154 75cd 40 0.233 2.394 17.11 N4:V5-7 4906-9154 75cd 20 0.233 2.430 17.07 N4:V5-8 4906-9153 15cd 60 0.060 2.452 17.05 Totals:1 435 Ft. 1 1.379A SMC EDMONDS ACC FACP 4100es FACP Speaker Db Loss Calculations *Circuit Voltage = 25vrms Et MAXIMUM -3 d6 DROP SPEAKER CIRCUIT DESCRIPTION Amp # Plan Circuit Number Speaker Tap Speaker Tap Speaker Tap Total Spkrs per Circuit Total Watts [P] Wire Gauge Est. Ckt. Length [D] in Feet Wire Res. Per Foot [Rw] Circuit Resistance [RI=2D*Rw] Speaker Current [I=P/Et] Speaker Resistance [Rs=Et/1] Voltage At End [Es=(Et*Rs) Rs+RI Watts At End [Pe=(Es) *2 Rs Actual dB Loss [dB=Log10 Pe P *10 Max Allowable Ckt. Length [ML=(0.414*Rs) 2*Rw .25 Watt .5 Watt 1. Watt FIRST FLOOR SPEAKER CIRCUIT 1C Amp-1 N3:S1 15 15 7.5 Watts 90 1500 0.0078 23.310 0.300 83.333 19.536 4.580 -2.14 db 2220 Ft. FIRST FLOOR SPEAKER CIRCUIT Amp-1 N3:S2 7 3 10 6.5 Watts 90 1400 0.0078 21.756 0.260 96.154 20.387 4.323 -1.77 db 2562 Ft. 1 a 0 7 1 4 -1 7 FIRST FLOOR SPEAKER CIRCUIT Amp-2 N3:S4 1 18 2 21 11.25 Watts 1 90 1200 0.0078 18.648 0.450 55.556 18.717 6.306 -2.51 db 1480 Ft. a - ROOF SPEAKER CIRCUIT Amp-2 N3:S6 4 1 5 3. Watts 1 90 500 0.0078 7.770 0.120 208.333 24.101 2.788 -.32 db 5550 Ft. SECOND FLOOR SPEAKER CIRCUIT Amp-2 N3:S7 9 11 20 7.75 Watts 9a 1030 0.0078 16.006 0.310 80.645 20.860 5.396 -1.57 db 2148 Ft. SPARE Amp-2 N3:S8 Watts 1 9a 0.0078 0.000 0.000 0.000 0.000 0.000 db 0 Ft. SPARE Amp-2 N3:S9 Watts 189a 0.0078 0.000 0.000 0.000 0.000 0.000 db 0 Ft. SMC EDMONDS ACC FACP - XPS-2 CIRCUIT SUMMARY & VOLTAGE DROP Plan Circuit Description Load % Drop N3:V9 FIRST FLOOR VISUAL CIRCUIT SIG9 1.007A 10.88% N3:V10 FIRST FLOOR VISUAL CIRCUIT SIG10 0.334A 5.21% N3:V11 FIRST FLOOR VISUAL CIRCUIT SIG11 1.532A 17.62% N3:V12 FIRST FLOOR VISUAL CIRCUIT SIG12 1.894A 17.65% N3:V13 FIRST FLOOR VISUAL CIRCUIT SIG13 0.586A 2.51% N3:V14 FIRST FLOOR VISUAL CIRCUIT SIG14 0.574A 5.99% 15.927A ]Total POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES. N3:V9 Distributed Load Voltage Drop Allowable % Drop: 17.9% Wire Gauge: 14ga Starting Voltage: 19.5vdc Circuit Capacity 3.A Wire Res. Per Ft. 0.0031 @ 75° Celsius Min. Device Voltage: 16.vdc %Voltage Drop 10.88% Normal Operation Device # PID Candela Distance (Feet) Device Current Voltage Drop Voltage At Device N3:V9-1 4906-9154 75cd 220 0.233 1.360 18.14 N3:V9-2 4906-9154 30cd 60 0.125 1.645 17.85 N3:V9-3 4906-9153 15cd 40 0.060 1.805 17.70 N3:V9-4 4906-9103 15cd 15 0.060 1.859 17.64 N3:V9-5 4906-9103 15cd 10 0.060 1.892 17.61 N3:V9-6 4906-9103 15cd 5 0.060 1.906 17.59 N3:V9-7 4906-9103 30cd 15 0.094 1.944 17.56 N3:V9-8 4906-9103 15cd 10 0.060 1.963 17.54 N3:V9-9 4906-9103 15cd 50 0.060 2.041 17.46 N3:V9-10 4906-9103 15cd 25 0.060 2.071 17.43 N3:V9-11 4906-9103 15cd 40 0.060 2.104 17.40 N3:V9-12 4906-9154 15cd 38 0.075 2.122 17.38 Totals:l 528 Ft. 11.007A N3:V10 Distributed Load Voltage Drop Allowable % Drop: Wire Gauge: Starting Voltage: Ckt Capacity 17.9% 14go 19.5vdc 3.A Wire Res. Per Ft. Min. Device Voltage: % Voltage Drop 0.0031 @ 16.vdc 5.21 % 75° Celsius Normal Operation Device # PID Candela Distance (Feet) Device Current Voltage Drop Voltage At Device N3:V10-1 4906-9153 15cd 460 0.060 0.943 18.56 N3:V10-2 4906-9103 30cd 15 0.094 0.969 18.53 N3:V10-3 4906-9103 15cd 30 0.060 1.002 18.50 N3:V10-4 4906-9103 15cd 10 0.060 1.009 18.49 N3:V10-5 4906-9103 15cd 20 0.060 1.016 18.48 Totals:1 535 Ft. 1 0.334A N3:V11 Distributed Load Voltage Drop Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75° Celsius Wire Gauge: 14ga Min. Device Voltage: 16.vdc Starting Voltage: 19.5vdc % Voltage Drop 17.62% Ckt Capacity. 3.A Normal Operation Device # PID Candela Distance (Feet) Device Current Voltage Drop o age Device N3:V11-1 0.000 0.000 19.50 N3:V11-2 4906-9153 75cd 150 0.186 1.411 18.09 N3:V11-3 4906-9103 15cd 5 0.060 1.452 18.05 N3:V11-4 4906-9153 75cd 50 0.186 1.847 17.65 N3:V11-5 4906-9103 15cd 30 0.060 2.050 17.45 N3:V11-6 4906-9103 30cd 60 0.094 2.433 17.07 N3:V11-7 4906-9153 15cd 30 0.060 2.607 16.89 N3:V11-8 4906-9103 15cd 10 0.060 2.662 16.84 N3:V11-9 4906-9103 30cd 60 0.094 2.966 16.53 N3:V11-10 4906-9103 75cd 20 0.186 3.056 16.44 N3:V11-11 4906-9103 15cd 25 0.060 3.140 16.36 N3:V11-12 4906-9153 15cd 25 0.060 3.214 16.29 N3:V11-13 4906-9103 15cd 5 0.060 3.227 16.27 N3:V11-14 4906-9153 15cd 50 0.060 3.340 16.16 N3:V11-15 4906-9153 75cd 40 0.186 3.415 16.09 N3:V11-16 4906-9153 15cd 20 0.060 3.429 16.07 N3:V11-17 4906-9103 15cd 15 0.060 3.435 16.07 Totals:) 595 Ft. 11.532A N3:V12 Distributed Load Voltage Drop Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75° Celsius Wire Gauge: 14go Min. Device Voltage: 16.vdc Starting Voltage: 19.5vdc % Voltage Drop 17.65% Ckt Capacity 3.A Normal peration Device # PID 4906-9153 Candela Distance (Feet) Device Current Voltage Drop Voltage At Device N3:V12-1 15cd 60 0.060 0.698 18.80 N3:V12-2 4906-9103 75cd 15 0.186 0.867 18.63 N3:V12-3 4906-9103 15cd 35 0.060 1.221 18.28 N3:V12-4 4906-9103 30cd 25 0.094 1.465 18.04 N3:V12-5 4906-9103 15cd 30 0.060 1.740 17.76 N3:V12-6 4906-9103 15cd 12 0.060 1.845 17.65 N3:V12-7 4906-9103 15cd 12 0.060 1.947 17.55 N3:V12-8 4906-9103 15cd 5 0.060 1.987 17.51 N3:V12-9 4906-9153 15cd 30 0.060 2.218 17.28 N3:V12-10 4906-9153 30cd 30 0.094 2.438 17.06 N3:V12-11 4906-9153 75cd 30 0.186 2.641 16.86 N3:V12-12 4906-9153 30cd 30 0.094 2.809 16.69 N3:V12-13 4906-9153 15cd 30 0.060 2.960 16.54 N3:V12-14 4906-9103 15cd 15 0.060 3.030 16.47 N3:V12-15 4906-9103 15cd 15 0.060 3.094 16.41 N3:V12-16 4906-9103 75cd 25 0.186 3.193 16.31 N3:V12-17 4906-9103 30cd 25 0.094 3.262 16.24 N3:V12-18 4906-9103 15cd 10 0.060 3.284 16.22 N3:V12-19 4906-9103 15cd 10 0.060 3.303 16.20 N3:V12-20 4906-9153 15cd 65 0.060 3.399 16.10 N3:V12-21 4906-9103 15cd 15 0.060 3.415 16.08 N3:V12-22 4906-9103 15cd 25 0.060 3.434 16.07 N3:V12-23 4906-9103 15cd 20 0.060 3.441 16.06 N3:V12-24 0.000 3.441 16.06 TotaIs: 1569 Ft.11.894A N3:V13 Distributed Load Voltage Drop Allowable % Drop: Wire Gauge: Starting Voltage: Ckt Capacity 17.9% 14go 19.5vdc 3.A Wire Res. Per Ft. Min. Device Voltage: % Voltage Drop Normal 0.0031 @ 16.vdc 2.51 % Operation 75° Celsius Device # PID 4906-9153 Candela Distance (Feet) Device Current o age Drop Voltage Device N3:V13-1 11Ocd 80 0.252 0.288 19.21 N3:V13-2 4906-9103 15cd 60 0.060 0.411 19.09 N3:V13-3 4906-9153 15cd 10 0.060 0.428 19.07 N3:V13-4 4906-9153 15cd 30 0.060 0.467 19.03 N3:V13-5 4906-9103 15cd 12 0.060 0.478 19.02 N3:V13-6 4906-9103 30cd 20 0.094 0.490 19.01 Une reNfWAF ♦ 11Il•'13,'1•_1 N3:V14 Distributed Load Voltage Drop Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75° Celsius Wire Gauge: 14ga Min. Device Voltage: 16.vdc Starting Voltage: 19.5vdc % Voltage Drop 5.99% Ckt Capacity 3.A Normal Operation Device # PID Candela Distance (Feet) Device Current Voltage Drop Voltage At Device N3:V14-1 4906-9103 30cd 200 0.094 0.705 18.80 N3:V14-2 4906-9153 15cd 25 0.060 0.779 18.72 N3:V14-3 4906-9153 15cd 20 0.060 0.830 18.67 N3:V14-4 4906-9153 15cd 35 0.060 0.907 18.59 N3:V14-5 4906-9103 15cd 55 0.060 1.009 18.49 N3:V14-6 4906-9153 15cd 55 0.060 1.090 18.41 N3:V14-7 4906-9103 15cd 25 0.060 1.117 18.38 N3:V14-8 4906-9153 15cd 45 0.060 1.151 18.35 N3:V14-9 4906-9153 15cd 45 0.060 1.167 18.33 C I� SMC EDMONDS ACC FACP - XPS-4 CIRCUIT SUMMARY & VOLTAGE DROP Plan N :V2 FI ST FLOG V SUA CIRCUIONON IG2 1.3 4A ON 15 96% 3: 2 RS FL OR IS AL IR IT SI 2 7977T.3 0 N3:V23 FIRST FLOOR VISUAL CIRCUIT SIG23 0.700A 11.41 % 1 3.026A I Total POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES. N3:V21 Distributed Load Voltage Drop Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75° Celsius Wire Gauge: 14go Min. Device Voltage: 16.vdc Starting Voltage: 19.5vdc % Voltage Drop 15.96% Circuit Capacity 3.A Normal Operation Device # PID Candela Distance (Feet) Device Current Voltage Drop Voltage Device N3:V21-1 4906-9103 30cd 225 0.094 1.871 17.63 N3:V21-2 4906-9153 75cd 5 0.186 1.909 17.59 N3:V21-3 4906-9153 15cd 10 0.060 1.975 17.52 N3:V21-4 4906-9103 30cd 40 0.094 2.224 17.28 N3:V21-5 4906-9103 15cd 20 0.060 2.337 17.16 N3:V21-6 4906-9103 15cd 10 0.060 2.390 17.11 N3:V21-7 4906-9153 15cd 20 0.060 2.488 17.01 N3:V21-8 4906-9103 15cd 20 0.060 2.579 16.92 N3:V21-9 4906-9103 15cd 12 0.060 2.629 16.87 N3:V21-10 4906-9103 15cd 12 0.060 2.675 16.83 N3:V21-11 4906-9103 15cd 30 0.060 2.778 16.72 N3:V21-12 4906-9153 15cd 10 0.060 2.809 16.69 N3:V21-13 4906-9103 15cd 20 0.060 2.863 16.64 N3:V21-14 4906-9153 15cd 40 0.060 2.956 16.54 N3:V21-15 4906-9153 15cd 25 0.060 3.005 16.49 6 0 1 6 N3:V21-17 4906-9154 15cd 40 %oof0.075 3.686 16.41 N3:V21-18 4906-9154 30cd 35 0.125 3.113 16.39 N3:V22 Distributed Load Voltage Drop Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75° Celsius Wire Gauge: 14go Min. Device Voltage: 16.vdc Starting Voltage: 19.5vdc % Voltage Drop 16.37% Ckt Capacity 3.A Normal peration Device # PID Candela Distance (Feet) Device Current Voltage Drop Voltage At Device N3:V22-1 4906-9103 15cd 400 0.060 2.387 17.11 N3:V22-2 4906-9103 15cd 25 0.060 2.527 16.97 N3:V22-3 4906-9103 15cd 25 0.060 2.658 16.84 N3:V22-4 4906-9103 15cd 35 0.060 2.828 16.67 N3:V22-5 4906-9153 75cd 10 0.186 2.873 16.63 N3:V22-6 4906-9153 75cd 45 0.186 3.024 16.48 N3:V22-7 4906-9103 15cd 25 1 0.060 3.079 16.42 N3:V22-8 4906-9103 15cd 15 0.060 3.107 16.39 N3:V22-9 4906-9103 15cd 15 0.060 3.129 16.37 N3:V22-10 4906-9103 15cd 15 0.060 3.146 16.35 N3:V22-11 4906-9103 15cd 45 0.060 3.179 16.32 N3:V22-12 4906-9103 1 15cd 1 35 1 0.060 1 3.192 1 16.31 iffi Me 4010 N3:V23 Distributed Load Voltage Drop Allowable %Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75° Celsius Wire Gauge: 14ga Min. Device Voltage: 16.vdc Starting Voltage: 19.5vdc % Voltage Drop 11.41 % Ckt Capacity 3.A Normal Operation Device # PID Candela Distance (Feet) Device Current Voltage Drop Voltage At Device N3:V23-1 4906-9153 15cd 375 0.060 1.612 17.89 N3:V23-2 4906-9153 15cd 15 0.060 1.671 17.83 N3:V23-3 4906-9153 15cd 35 0.060 1.795 17.70 N3:V23-4 4906-9153 15cd 70 0.060 2.019 17.48 N3:V23-5 4906-9103 15cd 25 0.060 2.089 17.41 N3:V23-6 4906-9103 30cd 30 0.094 2.163 17.34 N3:V23-7 4906-9153 15cd 10 0.060 2.182 17.32 N3:V23-8 1 4906-9103 1 15cd 10 1 0.060 1 2.197 1 17.30 N3:V23-9 1 4906-9103 1 75cd 1 25 1 0.186 1 2.226 1 17.27 Totals:1 595 Ft. 10.700A SMC EDMONDS ACC FACP - XPS-3 CIRCUIT SUMMARY & VOLTAGE DROP Plan Circuit Description Load % Drop N4:V15 DO NOT USE - AMP POWER SIG15 0.000A 0.00% N4:V16 DO NOT USE - AMP POWER SIG16 0.000A 0.00% N4:V17 DO NOT USE - AMP POWER SIG17 0.000A 0.00% O.00I OA ITotal POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES. N4:V15 Distributed Load Voltage Drop Allowable %Drop: Wire Gauge: Starting Voltage: Circuit Capacity 17.9% Wire Res. Per Ft. 0.0031 @ 75° Celsius Min. Device Voltage: 16.vdc % Voltage Drop 0.00% 14ga 19.5vdc 3.A Normal Operation Device # PID Candela Distance (Feet) Device Current Voltage Drop Voltage At Device N4:V15-1 0.000 0.000 19.50 Totals: � 0 Ft. � O.000A � N4:V16 Distributed Load Voltage Drop Allowable % Drop: Wire Gauge: Starting Voltage: Ckt Capacity Wire Res. Per Ft. 0.0031 @ 75° Celsius Min. Device Voltage: 16.vdc % Voltage Drop 0.00% Normal Operation 17.9% 14ga 19.5vdc 3.A Device # PID Candela Distance (Feet) Device Current Voltage Drop Voltage At Device N4:V16-1 0.000 0.000 19.50 Inil�ti>♦�#[�>�il�I�l� N4:V17 Distributed Load Voltage Drop Allowable % Drop: 17.9% Wire Res. Per Ft. 0.0031 @ 75° Celsius Wire Gauge: 14go Min. Device Voltage: 16.vdc Starting Voltage: 19.5vdc % Voltage Drop 0.00% Ckt Capacity 3.A Normal Operation Distance Device Voltage o age At Device # PID Candela (Feet) Current Drop Device N4:V17-1 0.000 0.000 19.50 Totals: 0 Ft. 0.000A CD_ w z _ a O N C w C > o O Q<� V WQ� O U aQii; 0Ju N C �Yof "�cwi) DRAWINGS REVIEWED BY. Eric Beck, CET NICET #148077 Fire Alarm Svstems, Level III 0- V ) O Z V ) Z O C� O LO W o Z N ��^^ O Q W 00 rn VJ 0 W = Q = - Uj C2 C~O r-- Z C) W - O coo a= M J � U - m U w � o z cn 0 N m z ZD 2i N Q o "'off_ w o 0 0 0 z0 C L Q U � 0 r, r, o Q z o 0 o U 1--Q UU-) coo O Wr� t o 0 V M M M O O OFCCN Lo L6 U mO o2 N Nin O O O O Q Q Q cn Q 3�: i�: m U W Q Q Q oMcn3: 3: mU_U_LLU_ 0�U)QQ0000 W CD Q N N O M W Y Of N U DRAWN BY: SHASHIKALA CHECKED BY: RAKESH ISSUE DATE: 8/8/14 JOB #: PROJECT #: 458:979327746 JCI @ 2023 SYSTEM: FIRE ALARM SYSTEM SHEET FACP CALCULATIONS AND SCHEDULES LIi1■l�l'LJ Totals:1 505 Ft. 10.574A� J_ U rn N (Tl co CV 0 N 0 CV 0 w z a I— U) < J DEVICE MOUNTING HEIGHT REFERENCE (PER NFPA 72) VISUAL APPLIANCE MOUNTING HEIGHT CONSIDERATIONS IN SLEEPING ROOMS A/C SUPPLY 1. MIN DISTANCE IN SLEEPING ROOMS IS 24" 610mm FROM CEILING TO OR RETURN „ ( ) DIFFUSER THE 4 REQUIREMENT FOR SMOKE DETECTORS HAS TOP OF LENS FOR 11OCD STROBES WITHIN 16' OF THE PILLOW BEEN REMOVED FROM THE 2010 EDITION OF NFPA 72 2. 177CD STROBES, USED IN SLEEPING ROOMS, CAN BE WITHIN THE 24" 4" NOTE: MEASUREMENTS (610mm) MINIMUM DISTANCE FROM THE CEILING. THE HIGHER 3' (MIN) (102mm) SHOWN ARE TO THE INTENSITY IS TO COMPENSATE FOR A POSSIBLE SMOKE LAYER. (914mm MIN) CEILING CLOSEST EDGE OF THE DETECTOR. CEILING MOUNTED FOR CEILING HEIGHTS LESS THAN 86" (2180mm), NFPA 72 AUDIBLE APPLIANCE SMOKE/HEAT 4 THE VISUAL LENS MOUNTING HEIGHT SHALL BE 6" MIN (152.4mm MIN) DETECTOR (102mm) 12" (MAX) WITHIN 6" (150mm) OF THE CEILING. AUDIBLE ONLY BELOW FINISHED CEILING (305mm MAX) 0 90" MIN (2286mm MIN) ACCEPTED HERE NEVER HEREORS _ ABOVE FINISHED FLOOR FM (OTHER MOUNTING HEIGHTS SHALL BE PERMITTED BY THE AHJ PROVIDING IT AUDIBLE/VISUAL MEETS THE SOUND LEVEL OUTPUT REQUIRED.) & VISUAL ONLY APPLIANCES TO EXIT DOOR No 5' (MAX.) SYNCHRONIZE MORE THAN (1524mm) DOOR TWO APPLIANCES IN ANY WIDTH FIELD OF VIEW. LESS 3 REF. 80" MIN (IBC) (2032mm MIN) REF. 96" MAX (IBC) (2440mm MAX) ABOVE FINISHED FLOOR (76mm) 96" MAX NFPA ADA) ) 5„ (2440mm MAX) (127mm) ABOVE FINISHED FLOOR MANUAL TO TOP OF LENS PULL STATION 80" MIN (ADA) (2032mm MIN) FIRE 80" MIN (NFPA) (2032mm MIN) PHONE MAGNETIC TO BOTTOM OF LENS JACK F ® DOOR • HOLDER NOTE: REFER TO THE PROPER DEVICE INSTALLATION INSTRUCTIONS FOR BACKBOX MOUNTING HEIGHT. FINISHED FLOOR O t Wig 48" MAX (ADA) (1 219m m ) 48" MAX (NFPA, ADA) (1219mm MAX) 42" MIN (NFPA) (1067mm MIN) MEASUREMENTS SHOWN ARE TO TOP OF PULL HANDLE 4100ES BACKBOX INSTALLATION INSTRUCTIONS 1. REMOVE ELECTRONIC CARD CAGE (IF PRESENT) AND STORE IT IN A SAFE DRY AREA. 2. NO KNOCKOUTS PROVIDED. CUT CONDUIT/SERVICE ENTRANCE OPENINGS. REFER TO FIG.1 FOR PROPER LOCATIONS. CONDUIT PROTRUSION INTO BOX 1/2" MAX. 3. MOUNT BOX TO WALL: BOX MUST BE LEVEL AND PLUMB. FOR SURFACE MOUNT USE TEAR DROP AND CLEARANCE HOLES ON BACK SURFACE. FOR SEMI —FLUSH MOUNT: USE WALL STUD GUIDES FOR MAXIMUM ALLOWABLE BOX DEPTH TO PROVIDE OPEN DOOR CLEARANCE. USE KNOCKOUTS ON SIDE WALL, SCREW OR NAIL BOX TO WALL STUDS. KNOCKOUT — 4. MINIMUM DISTANCE BETWEEN ANY TWO BOXES IS 3 1/4" (6" MAXIMUM). SCREW/NAIL 5. IF PRESENT, USE WIRE MANAGEMENT BRACKETS ON BOX SIDES HOLES FOR TO SECURE WIRE RUNS. SEMI —FLUSH 6. NEMA RATING: NEMA 1 — GENERAL PURPOSE. MOUNT 7. DO NOT LOCATE POWER —LIMITED WIRING IN THE SHADED AREAS (SEE NOTE 3.) OF THE BACKBOX, THIS AREA IS RESERVED FOR NON —POWER WALL STUD GUIDES — LIMITED CIRCUITRY SUCH AS AC POWER, BATTERIES AND CITY (SEE NOTE 3.) CONNECTION. 8. REFER TO SIMPLEX BACKBOX INSTALLATION DOCUMENT 579-117 FOR DETAILED INSTRUCTIONS. NOTE: ADA REQUIREMENTS LIMIT THE ALLOWABLE PROTRUSION OF OBJECTS MOUNTED IN PUBLIC ACCESSIBLE WALKS, HALLS, CORRIDORS, PASSAGEWAYS OR AISLES. THE 4 INCH (100mm) RESTRICTION APPLIES TO ANY ITEM IN WHICH THE MEASUREMENT FROM THE FLOOR TO THE BOTTOM OF THE UNIT IS MORE THAN 27 INCHES. PKG. SIZE PID NUMBER BOX HEIGHT 1 BAY 2975-9407 22" 2 BAY 2975-9408 40" 3 BAY 2975-9409 56" 1 BAY 2975-9410 22" 2 BAY 2975-9411 40" 3 BAY 2975-9412 56" 1 BAY 2975-9438 22" 2 BAY 2975-9439 40" 3 BAY 2975-9440 56" TYPICAL CONDUIT LOCATION FOR PWR. LIMITED FIELD WIRING FIG. 1 11 11/16"- 6 29/32" 1 7/16" 4 3/4 66" (TYPICAL, FOR 5 FOOT HEIGHT TO LCD DISPLAY CENTERLINE) CHART 5 17/32" 3 17/32" WALL FLOOR WALL MOUNTED / SMOKE/HEAT DETECTOR REFER TO FIGA FOR TYP. CONDUIT PENETRATION LOCATIONS 24„ 3 1/4" MIN. 10" MAX. r 16" r�1 FOR SURFACE MOUNT USE 4 HOLES TO SECURE BACKBOX TO WALL I FINISHED WALL EXAMPLE OF ADDITIONAL CABINET MOUNTING LOCATION L CONDUIT FOR INTERNAL PANEL HARNESSES OR BATTERY AREA NPL WIRING. (IF APPLICABLE) NO CONDUIT ENTRY OR WIRING IN THIS AREA SIDE WALL PID NUMBER BOX HEIGHT BOX LENGTH BOX DEPTH 2081-9280 12" 26 1/2" 12" 4081-9306 13 1/2" 27 7/8" 14 5/8" 4081-9308 13 1/2" 27 7/8" 14 5/8" 4009 NAC PANEL, TYPICAL WIRING DETAIL IF OPTIONAL SHIELDS ARE USED FOR IDNet WIRING. FOLLOW THESE PRECAUTIONS. M FROM PREVIOUS IDNet DEVICES 1. IF IDNet WIRING CONTINUES ON TO ANOTHER DEVICE, OR HOST IDNet CONTROL PANEL TAPE SHIELDS TOGETHER. DO NOT TERMINATE SHIELD AT 4009 IDNet. TO ADDITIONAL IDNet DEVICES 2. IF IDNet WIRING TERMINATES AT THE 4009, TAPE SHIELD. OR RETURN TO HOST IDNet CONTROL PANEL DO NOT TERMINATE SHIELD AT 4009 IDNet. IDNet CONTROLLER ADDRESS: TO NAC#:V4 DEVICES V TO NAC#:V3 DEVICES V V TO NAC#:V2 DEVICES TO NAC#:V1 DEVICES ')V e00 00 NNQmQm m m IDNET MAC 1 MAC 2 NAC 3 NAC 4 m , m sxz Q7 p�mw _ �® (�O�g AUX POWER O4 Iszol�� 0 00�� BPos Ef IPOS IN N INPUT 1 � O BEf IN VISIBLEPOS o o pO �c �IPM UT AUIMBEKAME (Do lour INPUT BATTERY 4009-9201 IDNet NAC EXTENDER O AODFEiSA6lf raAc SYM AM 0565-771 A B C B BATTERY II BATTERY (OPTIONAL) 4009-9807 FOUR POINT NAC MODULE CONNECT A 12 AWG COPPER GROUND WIRE FROM SAFETY GROUND IN THE ELECTRICAL DISTRIBUTION PANEL TO THE 4009 SAFETY GROUND STUD. TERMINAL o STRIP < PART OF 733-991 TO NAC#:V5 DEVICES TO NAC#:V6 DEVICES TO NAC#:V7 DEVICES TO NAC#:V8 DEVICES CONNECT TO 120VAC 60HZ INPUT 3A MAX. END —OF —LINE RESISTOR CODES NOTE: REFER TO PANEL/MODULE AND DEVICE INSTALLATION INSTRUCTIONS FOR PROPER TERMINATIONS. * USE WITH RETROFIT OR HIGH CURRENT MODULE MODEL REFERENCE NUMBER OHMS 1ST BAND 2ND BAND 3RD BAND 4TH BAND 5TH BAND WATTS CIRCUIT TYPE / FIRE ALARM PANEL MODULE 4081-9001 733-892 2.2K RED RED RED GOLD N/A 1 /2 ANNUNCIATOR (4300) 4004, 4010 (TROUBLE) 4081-9002 733-893 3.3K ORANGE ORANGE RED GOLD N/A 1 N.O. INITIATING PULL, SMOKE, HEAT, WATERFLOW, TAMPER, ETC. 4004*, 4004R, 4005*, 4006, 4100, 4120, 41000, ZAM'S 24 PT. 1/0 SWITCH SUPV. 4605-7401, 4100 SERIES 4081-9003 733-896 4.7K YELLOW VIOLET RED GOLD N/A 1/2 CURRENT LIMITED N.O. INITIATING 4090-9001 IDNET IAM (EOLR) NOTIFICATION (DACT) 2080-9024 4081-9004 733-886 6.8K BLUE GREY RED GOLD N/A 1/2 N.O. INITIATING PULL, SMOKE, HEAT, WATERFLOW, TAMPER, ETC. 4004, 4005, 4090-9001 IDNET IAM 2190-9173 MAPNETII 2 PT 1/0 4-20MA ZAM TROUBLE 4081-9005 733-984 1.8K BROWN GREY RED GOLD N/A 1/2 CURRENT LIMITED N.O. INITIATING (IN LINE) 4090-9001 IDNET IAM 4081-9006 733-890 560 n GREEN BLUE BROWN GOLD N/A 1 N.C. INITIATING (EOLR) 4005*, 4090-9001 IDNET IAM 4100, 41000 4081-9007 733-891 1.2K BROWN RED RED GOLD N/A 1 N.C. INITIATING (EOLR) 4005 4081-9008 733-894 10K BROWN BLACK ORANGE GOLD N/A 1/2 NOTIFICATION 4004, 4005, 4006, 4008, 4009, 4010, 4100, 41000 4081-9009 733-912 20n RED BLACK BLACK GOLD N/A 1 TO MR-101 RELAY COIL 4005 8 POINT 1/0 4081-9010 733-973 1 K BROWN BLACK RED GOLD N/A 1 N.C. INITIATING (ACROSS CONTACTS) 4005*, 4090-9001 IDNET IAM 24 PT. 1/0 (ACROSS CONTACTS) 4605-7401, 4100 SERIES CURRENT LIMITED N.O. INITIATING (IN SERIES WITH CONTACT) 4090-9001 IDNET IAM 4081-9011 733-974 100n BROWN BLACK BROWN GOLD N/A 1/2 ANNUNCIATOR (N2) 4006, 4008, 4010 4081-9012 733-985 22K RED RED ORANGE GOLD N/A 1/2 SPEAKER CIRCUIT 4003 4081-9013 734-086 4.99K YELLOW WHITE WHITE BROWN BROWN 1/2 4081-9014 734-092 2.4K RED YELLOW RED GOLD N/A 1/2 N.C. INITIATING (SECURITY MONITORING EOLR) 4090-9001 IDNET IAM 4081-9015 734-093 1.5K BROWN GREEN RED GOLD N/A / 1/2 / CURRENT LIMITED N.O. INITIATING (SECURITY MONITORING EOLR) 4090-9001 IDNET IAM 4081-9016 734-149 150K BROWN GREEN YELLOW GOLD N/A 1/2 4081-9017 734-171 3.9K ORANGE WHITE RED GOLD N/A 1 4081-9018 734-168 10K BROWN BLACK ORANGE GOLD N/A 1 70VRMS CONSTANT SUPV. NACS 4100-1260 378-090 8.2K GRAY RED RED GOLD N/A 1/2 SECURITY MONITORING (EOLR) 4100, 41000 378-046 5.6K GREEN BLUE RED GOLD N/A 1/2 N.O. SECURITY MON. (SERIES) 4100, 41000 378-069 12K BROWN RED ORANGE GOLD N/A 1/2 N.C. SECURITY MON. (SHUNT) 4100, 41000 PRODUCT INFORMATION FEATURES: • UL LISTED • FM APPROVED • FLUSH MOUNT ON STANDARD ELECTRICAL BOXES SPECIFICATIONS: . VOLTAGE: 24VDC NOMINAL • CURRENT: ALARM 140mA SUPERVISORY 65mA • OPERATING TEMPERATURE: 32' F TO 120' F . HUMIDITY RANGE: 10% TO 90% RH FROM 32' F TO 104' F . STANDARD TRIM: BEIGE (SUPPLIED WITH BOTH SLOTTED AND TAMPERPROOF SCREWS) OPTIONS • BRUSHED ALUMINUM TRIM: 4603-9111 • SURFACE BOX: 2975-9206 • DIMENSIONS 11 31/32"L X 4 5/8" W X 2 3/4"D • FINISH: LIGHT BROWN ENAMEL NOTES: 1. ALL WIRING TO BE No. 18 AWG OR TO LOCAL CODE. 2. ALL WIRING SUPERVISED 3. WIRE TO BE 18 AWG TWISTED SHIELDED PAIR RECOMMENDED CONSULT SALES ENGINEERING FOR EXCEPTIONS. 2500 FT ONE WAY MAX COMMUNICATION LINE POWER 32 VDC MAX 130 mA MAX 1200 OR 9600 BAUD 4. WHEN WIRING LEAVES THE BUILDING, OVER VOLTAGE PROTECTORS ARE REQUIRED; USE 2081-9044 ONE IS INSTALLED WHERE IT LEAVE THE BUILDING AND ONE WHERE IT ENTERS THE NEXT BUILDING. TWO 2081-9044 (MAX) ����►_. .FIN TO FLUSH —MOUNT IN MASONRY WALLS, USE A A RAYCO 965 (3-1/2" DEEP) MASONRY BOX OR ITS EQUIVALENT. TO FLUSH —MOUNT IN PLASTERBOARD WALLS, USE A STEEL CITY GW-635—G OR A RAYCO EQUIVALENT. TO SURFACE —MOUNT, USE A SIMPLEX 2975-9206 BACK BOX FLUSH MOUNTING r TO ADDITIONAL 24VDC POWERED DEVICES IF USED r— — — — — — I FROM 24VDC POWER SOURCE IIII I II O O ®I ®®®I TB2 p p _ o — - TB1 - - + + g g O :ABBAAABA� FOR RUI ADDRESSABLE SETUP SEE INSTALLATION INSTRUCTIONS 579- r �i TO NEXT RUI DEVICE OR RETURN TO FIRE ALARM CONTROL PANEL IN STYLE 6 SYSTEM IL _ L — FROEMALA MIOCON CONTROL PANUS RUI EL AEVICE OR PRODUCT INFORMATION 4099-9001 SINGLE ACTION IDNet SLC ADDRESSABLE MANUAL STATION FEATURES: SINGLE GANG EXTENSION RING 3/4 • UL LISTED MOUNTING INSTRUCTIONS: KNOCKOUTS FOR 3/4" CONDUIT (RACO NO. 773) 1. COVER & BACKPLATE COME ASSEMBLED. TOP AND BOTTOM OF BOX SUPPLIED BY CONTRACTOR • SINGLE ACTION, IDNet SLC ADDRESSABLE 2. UNLOCK STATION DROP COVER FORWARD MOUNTING INSTRUCTIONS: • PULL LEVEL PROTRUDES WHEN ALARMED TO EXPOSE MOUNTING SCREWS. 1. COVER & BACKPLATE COME ASSEMBLED. 2. UNLOCK STATION, DROP COVER FORWARD • TAMPER RESISTANT RESET KEY LOCK 0• MOUNTING: SEMI —FLUSH, SURFACE TO EXPOSE MOUNTING SCREWS. 0 • OPERATING TEMPERATURE RANGE: 32 — 120' F 2099_9828 p 2099_9828 ° • OPERATING HUMIDITY RANGE: 0 — 93% RH INSTITUTIONAL INSTITUTIONAL • ADAPTER PLATES 2099-9813 OR 2099-9814 CAN BE COVER KIT COVER KIT USE FOR RETROFIT APPLICATIONS. (IF REQ D) 0 (IF REQ'D) , o • 5" HIGH X 3 3/4" WIDE X 1' DEEP \ • SCREW TERMINALS FOR 18 TO 14 AWG WIRE \ • ADDRESSED BY MEANS OF AN 8 POSITION DIP SWITCH • COMPATIBLE WITH IDNet SLC/MAPNETow ° OPERATION: ACTIVATION: 4099-9001 SINGLE ACTION STATION REQUIRES A FIRM DOWNWARD PULL TO ACTIVATE THE ALARM SWITCH. COMPLETING THIS ACTION BREAKS AN INTERNAL PLASTIC BREAK -ROD THAT IS VISIBLE BELOW THE PULL LEVER (USE OF PLASTIC ROD IS OPTIONAL). THE PULL LEVEL LATCHES INTO THE ALARM POSITION AND REMAINS EXTENDED OUT OF THE HOUSING TO PROVIDE A VISIBLE INDICATION. RESETTING 4099-9001 SINGLE ACTION STATION REQUIRES A KEY TO RESET THE ACTIVATION LEVER AND DEACTIVATE THE ALARM SWITCH. (IF OPTIONAL PLASTIC BREAK ROD WAS USED IT MUST BE REPLACED) CONSTRUCTION: STATION HOUSING AND PULL LEVER ARE CONSTRUCTED OF CHIP RESISTANT AND DIRT RESISTANT, HIGH IMPACT LEXAN. HOUSING IS RED WITH RAISED WHITE LETTERING AND PULL LEVER IS WHITE WITH RED RAISED LETTERING. * LEXAN IS A REGISTERED TRADEMARK OF THE GENERAL ELECTRIC CO. APPLICATION: PULL STATIONS SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72 AND ADA GUIDE LINES. INTRODUCTION: THE 4099-9001 ADDRESSABLE PULL STATION PROVIDES TWO —STATE STATUS INFORMATION (NORMAL AND SHORT) TO THE IDNet SLC COMPATIBLE FIRE ALARM CONTROL PANEL (FACP) VIA THE IDNet SLC CHANNEL. THE IDNet SLC CHANNEL PROVIDES THE COMMUNICATION LINK BETWEEN PULL STATION AND THE FACP AND POWERS THE ENTIRE CIRCUITRY. WIRING: 1. ALL WIRING TO COMPLY WITH LOCAL CODE. 2. CONDUCTORS MUST TEST FREE OF ALL GROUNDS. 3. MAINTAIN CORRECT POLARITY 4. IDNet SLC LINES ARE TO BE 18 AWG TWISTED SHIELDED PAIR 5. MAXIMUM LINE RUN FROM PANEL TO FARTHEST DEVICE NOT TO EXCEED 2500 FEET. 6. MAXIMUM TOTAL WIRE (INCLUDING ALL T—TAPS) FROM PANEL NOT TO EXCEED 10,000 FEET. 7. MAXIMUM QUANTITY OF DEVICES PER CIRCUIT: 250 8. TERMINALS 1 AND 2 FOR FIELD WIRING. TERMINALS 3 AND 4 ARE FACTORY WIRING. 9. WIRE NUT, SPLICE, OR SOLDER THE SHIELD WIRES. 10. IF SHIELD IS PRESENT, IT SHOULD BE CONNECTED TO THE OUTGOING IDNet SLC SHIELD TO PROVIDE A CONTINUOUS SHIELD OVER THE LENGTH OF THE IDNet SLC CHANNEL. SHIELD SHOULD BE INSULATED FROM THE ELECTRICAL BOX. 11. SEE INSTALLATION INSTRUCTIONS 574-332 4" SQUARE x 2 1 8" DEEP BOX (RACO NO.OR OR (RACO NO.1500) 232) SINGLE GANG SWITCH BOX 2 1/2" DEEP SUPPLIED BY CONTRACTOR o� o(9 �� 2975-9178 OR 0 v BOXES �4 FROM SIMPLEX It FROM SIMPLEX OR WIREMOLD BOX NO. 5747 SUPPLIED ADDRESS DIP SWITCHES UNDER RE -SEALABLE LABEL BY CONTRACTOR SEE INSTALLATION INSTRUCTIONS (574-332 FOR SETTINGS SURFACE MOUNTING 2099-9819 (BLACK) OR 4 11/16" SQUARE x 2 1/8" DEEP BOX 2099-9820 BEIGE) SUPPLIED BY CONTRACTOR SEMI -FLUSH MOUNTING FLUSH ADAPTOR AVAILABLE FROM SIMPLEX MOUNTING INSTRUCTIONS: 1. COVER & BACKPLATE COME ASSEMBLED. �® 2. UNLOCK STATION, DROP COVER FORWARD o TO EXPOSE MOUNTING SCREWS. WO 2099-9828 ° o� INSTITUTIONAL IT (IF REQKD) 0 _ ° q FLUSH MOUNTING IDNet SLC 11112 3 ® 9❑ LLD �� SHIELD SHIES FROM FIRE ALARM CONTROL PANEL OR + + TO ADDITIONAL IDNet SLC DEVICES OR RETURN OTHER IDNet SLC DEVICES ON CIRCUIT FIRE ALARM CONTROL PANEL FOR STYLE 6 AP ❑7 � � � � APPLICATION. II II FEE] NOTE: BOX MUST BE RECESSED INTO WALL 1' TO 1 1 /8". CUTOUT MUST BE A MINIMUM 6" HIGH BY 5" WIDE O© o 0 (V 0 C � O w z a_ _ C W C > o O �, Qco M MN V wa� O U < <w U�U > C "�cWi� DRAWINGS REVIEWED BY. - Eric Beck, CET NICET #148077 Fire Alarm Systems, Level III V ) O V J M z O O LO ti W o Z � N �/^ O W 00 M VJ 0 Q W Q ^ Q '=^ v J Ill Z Lu Lu CD v ! C/5 co c,4 LL LJ 3 0 0 N Ir v M J � U — m Qu U � < W cf) O0 0 z co 0 N m z ZD N < CZ)w 0 _ w o 0 0 0 zO C LJ < U 1 Q r, r, O < z 0 0 0 d L(i CO O O_ W I- V � CV U V M M M O O CD CD O O Cn M CV LCJ U m Lu O M CV " CD CO O 'M < < < Cn < < C) w < < < a U)< Q m 0 0 0 0 w N o f f�-- v v < N N O M (� 'ITv � co w `Y CT O H O L. V CM CV DRAWN BY: SHASHIKALA CHECKED BY: RAKESH ISSUE DATE: 8/8/14 JOB #: PROJECT #: 458:979327746 JCI © 2023 SYSTEM: FIRE ALARM SYSTEM SHEET WIRING TYPICALS FA-701 TrueAlertTMNON -ADDRESSABLE MULTI -CANDELA VISIBLE NOTIFICATION APPLIANCE TrueAlertTMNON-ADDRESSABLE MULTI -CANDELA SPEAKER/VISIBLE NOTIFICATION APPLIANCE PRODUCT INFORMATION PRODUCT INFORMATION ���� 4" SQUARE x 1-1/2" DEEP BOX FEATURES: (WALL MOUNT) WHEN SURFACE MOUNTING USE o ( WALL MOUNT) RED SKIRT NO.4905-9937 OR FEATURES: WHITE SKIRT NO. 4905-9940 • UL LISTED TO STANDARD 1971 & 1480 N • UL LISTED TO STANDARD 1971 4905-9931 ADAPTER PLATE • ADA COMPATIBLE STANDARD ELECTRICAL BOX MOUNTING 0 2975-9145 BOX STANDARD ELECTRICAL BOX MOUNTING 4" SQUARE BOX, 1-1/2" DEEP, o • ADA COMPATIBLE • OPTIONS FOR WALL MOUNT SPEAKER VISUALS: 4" SQUARE BOX, 1-1/2" DEEP, WITH A 4" SQUARE BOX EXTENSION, 7 SYNCHRONIZATION FLASH RATE MODE FOR USE WITH: O - SKIRTS FOR SURFACE MOUNT ELECTRICAL BOXES WITH A 4" SQUARE BOX EXTENSION, 1-1/2" DEEP, SUPPLIED BY OTHERS • SEPARATE STROBE SYNCHRONIZATION MODULES THAT ARE AVAILABLE ° RED 4905-9946, WHITE 4905-9947 1-1/2" DEEP, SUPPLIED BY OTHERS �O O o FOR CLASS B OR CLASS A OPERATION 4905-9961 OPTIONAL WIRE - 4905-9998 WIRE GUARD TRANSPARENT HOUSING p�0 SURFACE MOUNT ADAPTER SKIRT ° O 0 C O a GUARD (SHOWN HERE FOR O 3 3 16" 81mm) DEEP. ° AND LENS ASSEMBLY O 0 0 Q Otoilim • SEPARATE SMARTSYNC CONTROL MODULES (SCMs) THAT PROVIDE O REFERENCE ONLY, CAN BE °� � SYNCHRONIZATION FLASH RATE MODE FOR USE WITH: ° CONDUIT CUTOUTS ARE PROVIDED ° CLASS B OR CLASS A OUTPUT FROM CONVENTIONAL NAC INPUTS USED ON OTHER MOUNTING ° • SEPARATE STROBE SYNCHRONIZATION MODULES THAT ARE AVAILABLE 0 0 ON ALL FOUR SIDES. • °0 °D SPECIFICATIONS: _ _ OPTIONS) 0 FOR CLASS B OR CLASS A OPERATION • 0 °Q ° • HOUSING DIMENSIONS: 5-1/8" H X 5" W X 2-3/4" D (130mm X 127mm X 70mm) ° REMOVABLE COVER C. O o.0 WIRING INPUT TERMINALS AND *TEMPERATURE RANGE: 32'F TO 122'F (0 TO 50'C) (TOOL REQUIRED) ° SPEAKER TAP SELECTION ARE ° O° M • HUMIDITY RANGE: 10% TO 93% NON -CONDENSING AT 100'F (38'C) SPECIFICATIONS: ACCESSIBLE FROM REAR 1111MV 00 �Q� • TERMINAL BLOCKS FOR 18AWG TO 12AWG; TWO WIRES PER • HOUSING DIMENSIONS: 7-1 /4" H X 5" W X 2-5/8" D (184mm X 127mm X 67mm) SPEAKER ASSEMBLY ° O v � �' o TERMINAL FOR IN/OUT WIRING. O O ALTERNATE BACK BOXES •TEMPERATURE RANGE: 32'F TO 122'F (0 TO 50'C) STROBE ASSEMBLY v (D ¢J 0 WIRING: 1. 2 GANG 1-1/2" DEEP BOX • HUMIDITY RANGE: 10% TO 93% NON -CONDENSING AT 100'F (38'C) ~ O°Yof 2. SINGLE GANG 1-1/2" DEEP BOX INTENSITY SELECTION N �w 1. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL. STANDARD ELECTRICAL BOX MOUNTING • TERMINAL BLOCKS FOR 18AWG TO 12AWG; TWO WIRES PER INTENSITY SELECTION PLUG, ACCESSIBLE ONLY F- W 2. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP 4" SQUARE BOX, 1-1/2" DEEP TERMINAL FOR IN/OUT WIRING. STROBE INTENSITY 75 ` PLUG, ACCESSIBLE ONLY FROM REAR OF HOUSING; 5 FROM REAR OF WIRES UNDER TERMINALS. VIEWING SLOT FACTORY SETTING HOUSING; S 15cd 130 FACTORY SETTING IS 15cd 3. ALL NAC WIRING CONNECTIONS ARE SUPERVISED AND POWER -LIMITED. WIRING NOTES: STROBE INTENVIEWING IT 5 DRAWINGS REVIEWED BY.- 4. SEE INSTALLATION INSTRUCTIONS (579-548) FOR ADDITIONAL INFORMATION. 1. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL.. �� SEMI -FLUSH MOUNTING Eric Beck, CET STROBE: SURFACE MOUNTING EF 1 2. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP SEMI -FLUSH MOUNT NICET#148077 • RATED VOLTAGE RANGE: UL LISTED: 16 VDC TO 33 VDC PER UL 1971 WIRES UNDER TERMINALS. IMPORTANT! SURFACE MOUNT OPTION Fire Alarm Systems, Level III ULC LISTED: 20 VDC TO 30 VDC PER ULC S526-M878 3. ALL NAC WIRING CONNECTIONS ARE SUPERVISED AND POWER -LIMITED. WALL MOUNT INSTALLATION • FLASH RATE: 1Hz SURFACE MOUNT ADAPTER SKIRT 4. SEE INSTALLATION INSTRUCTIONS (579-548) FOR ADDITIONAL INFORMATION. HEIGHT REFERENCE • SYNCHRONIZED MODE NAC LOADING: MAXIMUM OF 35 SYNCHRONIZED STROBES PER NAC CIRCUIT. 1 5/8" (41 mm) DEEP. 2975-9145 4" SQUARE BOX OUTLINE CONNDUIT CUTOUTS ARE PROVIDED BOX OUTLINE 4" *CURRENT DRAWS REFLECT STROBE FLASHING ON ALL FOUR SIDES. TO ADDITIONAL NOTIFICATION STROBE: APPLIANCE DEVICE OR RETURN • RATED VOLTAGE RANGE: UL LISTED: 16 VDC TO 33 VDC PER UL 1971 MODEL NUMBER COLOR COLOR RATING 16 VDC 18 VDC 24 VDC � HOUSING LETTERING STROBE TO FACP FOR STYLE Z APPLICATION ULC LISTED: 20 VDC TO 30 VDC PER ULC S526-M878 TLT 4906-9101 RED IF LAST DEVICE ON CIRCUIT IN A WHITE 15cd 60 mA 53 mA 40 mA • FLASH RATE: 1 Hz 30cd 94 mA 84 mA 63 mA --+-4 STYLE Y APPLICATION PLACE A • SYNCHRONIZED MODE NAC LOADING: MAXIMUM OF 35 SYNCHRONIZED STROBES PER NAC CIRCUIT. 1-1/2" 75cd 186 mA 165 mA 124 mA TERMINALS 3 & 4 ARE NOT USED 10K 1/2W END -OF LINE RESISTOR TrueAlert SPEAKER 110cd 252 mA 224 mA 168 mA I I *CURRENT DRAWS REFLECT STROBE FLASHING JUMPER SETTINGS 78-1/2" NFPA 72 REQUIRES THAT 4906-9103 1 WHITE RED 15cd 60 mA 53 mA 40 mA HOUSING LETTERING STROBE RMS CURRENT @ IN. THE ENTIRE LENS BE NOT JUMPER WATTAGE LESS THAN 80" AND NOT 30cd 94 mA 84 mA 63 mA I I MODEL NUMBER COLOR COLOR RATING 16 VDC 18 VDC 24 VDC g2" 75cd 186 mA 165 mA 124 mA 110cd 252 mA 224 mA 168 mA I ® ® I 4 ® JI PTTOI TAP A V L A S 1: 4 G GREATER HEFINISHED9FLOOR.VE 4906-9151 RED WHITE 15cd 60 mA 53 mA 40 mA MIN. 30cd 94 mA 84 mA 63 mA O LO O 75cd 186 mA 165 mA 124 mA J1 TO TA 70.7VRMS 112 IMPORTANT! FROM A COMPATIBLE SIMPLEX + sL 110cd 252 mA 224 mA 168 mA SMARTSYNC NAC OR FROM E) O ® 0 O 4906-9153 WHITE RED 15cd 60 mA 53 mA 40 mA 2 WALL MOUNT INSTALLATION SMARTSYNC CONTROL L L 30cd 94 mA 84 mA 63 mA A A 1 2 HEIGHT REFERENCE MODULE (SCM) 4905-9938 ®90 ®90 75cd 186 mA 165 mA 124 mA A TO TAP F 25VRMS 1 ELECTRICAL BOTTOM OF LENS OR SIMPLEX 4905-9914 110cd 252 mA 224 mA 168 mA ATO TAP G SPKR - - OR 9922 SYNC CUBE SPKR + SPKR + BOX OUTLINE IS EITHER EVEN WITH SPEAKER: END -OF -LINE OR SLIGHTLY ABOVE 4906 s 4906 S 4906 S (VALUE FROM AUDIO NAC CHANNEL BOTTOM OF FREQUENCY RESPONSE: FIRE ALARM: 400 TO 4000Hz DEPENDANT RESISTOR (VALALFACP) COMPATIBLE BOXES GENERAL SIGNALING: 125 TO 12kHz SPKR + SPKR + ¢ SPKR + ¢ SPKRON s SPEAKER OUTPUT RATINGS @ 10 FT. (3m) (4100/4003) (SEE WIRING NOTES) 1 SPKR - SPKR - ¢ SPKR - ¢ SPKR - O O CD O0 1 /4W 1 /2W 1 W 2W FROM STANDARD NAC OR ll NAC + 0 STROBE + STROBE + 4 STROBE + NFPA 72 REQUIRES THAT 75 REVERBERATE CHAMBER COMPATIBLE SIMPLEX SMARTSYNC NAC _ THE ENTIRE LENS BE NOT UL 464 TEST 76 dBA 79 dBA 82 dBA 85 dBA NAC OR FROM SMARTSYNC CONTROL STROBE - STROBE - STROBE - 80" LESS THAN 80" AND NOT INTENSITY SELECTION 15 MODULE (SEE WIRING NOTES) MIN. GREATER THAN 96" ABOVE PLUG, ACCESSIBLE ONLY ANECHOIC CHAMBER 87 dBA 90 dBA 93 dBA 96 dBA NAC NAC - HE FINISHED FLOOR. FROM REAR OF HOUSING; FACTORY SETTING IS 15cd q NAC + NAC + STROBE INTENSITY VIEWING SLOT PRODUCT INFORMATION TrueAlertTM (STYLE 4) AUDIO/VISIBLE NOTIFICATION APPLIANCES 4906 SERIES TrueAlertTM NON -ADDRESSABLE MULTI -CANDELA SPEAKER/VISIBLE NOTIFICATION APPLIANCE FEATURES: INDIVIDUALLY ADDRESSED AUDIBLE/VISIBLE MOUNTING ADAPTERS AND BOXES PRODUCT INFORMATION (CEILING MOUNT) O NOTIFICATION APPLIANCES WITH EFFICIENT ELECTRONIC MODEL DESCRIPTION DIMENSIONS HORN AND HIGH INTENSITY XENON STROBE PROVIDES: NUMBER FEATURES: *CURRENT DRAWS REFLECT STROBE FLASHING • SUPERVISION OF EACH INDIVIDUAL APPLIANCE'S WIRING AND SURFACE MOUNT WHITE ADAPTER SKIRT, USE TO COVER 1 1/2" DEEP 5 3/8" H x 5 1/4" W x 1 5/8"D MODEL HOUSING LETTERING STROBE RMS CURRENT @ O 4" (102mm) SQUARE, 1 1/2" (38mm) DEEP 4905-9915 • UL LISTED TO STANDARD 1971 & 1480 NUMBER COLOR RATING 16 VRMS 18 VRMS 24 VRMS CONNECTIONS SURFACE MOUNTED BOXES (136 mm X 133 mm X 41 mm) O BOX WITH 1 1/2" EXTENSION (BY OTHERS) • ABILITY TO CONNECT USING "T" TAPPING FOR CLASS B/STYLE 4 DEPTH WITH HORN =3 1/8" (79mm) • ADA COMPATIBLE 4906-91541 WHITE I RED 15cd 75mA 67mA 50mA O �� CIRCUITS TO SIMPLIFY WIRING 30cd 125mA 111mA 83mA O • HORNS CONTROLLED SEPARATELY FROM STROBES ON THE SAME SYNCHRONIZATION FLASH RATE MODE FOR USE WITH: 75cd 233mA 207mA 155mA 2-WIRE CIRCUIT ALLOWING "ON -UNTIL -SILENCED" AND TrueAlert A/V UNITS- DIP SWITCH ADDRESS CHART ®_� 4" SQ. x 1 1/2" DEEP • SYNCHRONIZATION MODULES FOR CLASS B (STYLE Y) OR 110cd 316mA 281 mA 211 mA "ON -UNTIL RESET" USING A SINGLE ADDRESS (101.6 mm x 38.1 mm) CLASS A (STYLE Z) OPERATION D • XENON STROBE OUTPUT IS MANUALLY SELECTABLE FOR 15, 30, RESERVED FOR -DIP SWITCHES 5 & 6� (RACO NO. 191 OR EQUAL) SPEAKER dBA AT 10' (RATED WATTS) WIRING INPUT TERMINALS AND 75, 110 CANDELA OR "FACP". THE "FACP" SETTING ALLOWS THE FUTURE USE II SPEAKER TAP SELECTION ARE 4100 TO PROGRAM THE CANDELA SETTING. 0000 1000 0100 1100 SPECIFICATIONS: 1/4 1/2 1 2 ACCESSIBLE FROM REAR OF • MAGNETIC TEST DIAGNOSTICS TO ASSIST CHECKOUT AND TESTING 0000 0 16 32 48 DIP SWITCH SW1 • SPEAKER HOUSING DIMENSIONS: 7 1/2" DIA X 1/2"D (191MM X 13MM) REVERBERATE CHAMBER SPEAKER HOUSING OF APPLIANCES AND WIRING 1000 1 17 33 49 (SEE MOUNTING NOTE4) • STROBE LENS PROTRUSION DIMENSION: 2 5/8" (67MM) ABOVE SPEAKER HOUSING UL 464 TEST 76 dBA 79 dBA 82 dBA 85 dBA LED INDICATOR AND MAGNETIC TEST FEATURE: 0100 2 18 34 50 • DEPTH INTO BOX 2 3/4" (70MM) ANECHOIC CHAMBER 87 dBA 90 dBA 93 dBA 96 dBA • LED INDICTOR CAN BE SELECTED TO DISPLAY EACH POLLING CYCLE 1100 3 19 35 51 TEMPERATURE RANGE: 32'F TO 122'F 0 TO 50'C TO INDICATE APPLIANCE SUPERVISION 0010 4 20 36 52 E ( ) • WHEN THE TrueAlert CONTROLLER IS IN DIAGNOSTIC MODE, THE 1010 5 21 37 53 I R • HUMIDITY RANGE: 10% TO 93% NON -CONDENSING AT 1007 (38'C) MAGNETIC TEST PULSES THE LED TO INDICATE APPLIANCE ADDRESS DIP SWITCHES 0110 6 22 38 54 • TERMINAL BLOCKS FOR 18AWG TO 12AWG; TWO WIRES PER AND IS SELECTABLE TO ALSO BRIEFLY FLASH THE STROBE TO CONFIRM OPERATION 1 THRU 4 1110 7 23 39 55 O TERMINAL FOR IN/OUT WIRING. TrueAlert 2-WIRE ADDRESSABLE CONTROL OF VISIBLE 0001 8 24 40 56 O AND AUDIBLE NOTIFICATION ACTIVATES APPLIANCES WITH: 1001 9 25 41 57 WIRING: • HORNS SOUNDED AS TEMPORAL OR MARCH TIME PATTERN, OR ON 0101 10 26 42 58 INTENSITY SELECTION 1101 11 27 43 59 1. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL. CONTINUOUSLY, CONTROLLED SEPARATELY FROM VISIBLE APPLIANCES PLUG, ACCESSIBLE � ) ON THE SAME TWO -WIRE CIRCUIT 0011 12 28 44 60 ONLY FROM REAR OF 2. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP STROBE INTENSITY �J J Cl) 1011 13 29 45 61 I+° HOUSING, FACTORY WIRES UNDER TERMINALS. VIEWING SLOT O o • UL LISTED TO STANDARD 1971 0111 14 30 46 62 5 Q TrueAlert NOTIFICATION APPLIANCE DESIGN PROVIDES 1111 15 31 47 63 MAGNETIC TEST "° ' SETTING IS FACP 3. ALL NAC WIRING CONNECTIONS ARE SUPERVISED AND POWER -LIMITED. �_ AREA FACP 4. SEE INSTALLATION INSTRUCTIONS (579-548) FOR ADDITIONAL INFORMATION. AUDIBLE NOTIFICATION APPLIANCE (HORN) °' • CONTROLLER CAN BE SELECTED FOR "HIGH" OUTPUT OR A "LOW" co OUTPUT SOUND LEVEL -5 dBA DIFFERENCE STROBE: r- M INTENSITY SELECTION PLUG, ( ) LSB MSB STROBE INTENSITY SETTING ACCESSIBLE ONLY FROM /1 • UL LISTED TO STANDARD 464 VIEWABLE THROUGH THE LENS • RATED VOLTAGE RANGE: UL LISTED: 16 VDC TO 33 VDC �./ J SPECIFICATIONS: SEMI -FLUSH MOUNTING REAR SETTING MOUNTING NOTES: ULC LISTED: 20 VDC TO 30 VDC PER ULC S526-M878 Q STROBE: •FLASH RATE: 1 Hz U) 1 2 3 4 5 6 7 8 1. THE TrueAlert CEILING -MOUNT A/V ATTACHES DIRECTLY TO A STANDARD 4-INCH SQUARE ELECTRICAL CM SUPERVISORY VOLTAGE RANGE: 17 VRMS TO 31 VRMS BOX (NOT SUPPLIED), SEMI -FLUSH OR SURFACE MOUNTED. ENSURE CORRECT ORIENTATION OF THE BOX SYNCHRONIZED MODE NAC LOADING: MAXIMUM OF 35 SYNCHRONIZED STROBES PER NAC CIRCUIT. TO ADDITIONAL NOTIFICATION APPLIANCE - SUPERVISORY REQUIREMENTS: 1 UNIT LOAD Q 0 0 0 0 DEVICES (STROBE) OR RETURN TO FACP E2 STROBE FLASH RATE: 1 Hz IN RELATION TO THE LOCATION OF THE MOUNTING SCREWS AND THE A/V's POSITION. + + OR SYNC MODULE FOR STYLE Z APPLICATION O FROM FACP 16-33VDC NON -CODED NOTIFICATION � � o OPERATING VOLTAGE RANGE: UP TO 43 TRUEAlert ADDRESSABLE SYNCHRONIZED STROBES MAXIMUM PER SLC. 2. FOR INSTALLATION IN A CONCRETE OR PLASTER CEILING. FLUSH -MOUNT THE BOX (WITH A 1/4" RECESS, APPLIANCE CIRCUIT OR PRECEDING DEVICE i� - IF LAST DEVICE ON CIRCUIT IN A STYLE Y * NOT MAXIMUM). APPLICATION PLACE A 10K 1 /2W END -OF- p NOMINAL AVERAGE CURRENT (� VOLTAGE &HORN SETTING USED LINE RESISTOR p o HOUSING LETTERING 15cd 30cd 75cd 110cd 1=0N O=OFF 3. FOR INSTALLATION IN A SUSPENDED CEILING, USE A SUITABLE TILE BRIDGE THAT REST ON TILE TO MODEL NUMBER VOLTAGE FROM FIRE ALARM CONTROL PANEL OR TO ADDITIONAL 25 OR 70VRMS SPEAKERS ORLO COLOR COLOR HIGH LOW HIGH LOW HIGH LOW HIGH SUPPORT THE BOX. Q ti OTHER 25 OR 70VRMS SPEAKER CIRCUIT � - � RETURN TO FACP FOR STYLE Z APPLICATION � 0 23 VRMS 0.075 0.070 0.110 0.105 0.198 0.193 0.250 0.245 4. ADDRESS SWITCH SW1 IS ACCESSIBLE WITH THE CEILING -MOUNT A/V REMOVED. + + IF LAST DEVICE ON CIRCUIT IN A STYLE Y 4906-9228 RED WHITE U) G6 17 VRMS 0.082 0.077 0.135 0.130 0.249 0.244 0.335 0.330 SPEAKER TAP APPLICATION PLACE A 10K 1 /2W END -OF- w CV 0 23 VRMS 0.075 0.110 0.105 0.198 0.193 0.250 0.245 LINE RESISTOR z 4906-9230 WHITE RED 17 VRMS 0.082 0.135 0.130 0.249 0.244 0.335 0.330 JUMPERS c * PERFORMANCE REFERENCE, NOMINAL AVERAGE CURRENTS WITH STROBES FLASHING AND HORN ON 4906 A/V 4906 A/V 4906 A/V 4906 A/V = 0 LLW p o HORN: > Q SOUND OUTPUT CHARACTERISTICS: 2400 TO 3700 Hz SWEEP, MODULATED AT 120 Hz O O O o a, 1 2 1 2 1 2 1 2 Jumper Watt O Q 0 HORN SOUND OUTPUT (dBA) ® 10 FT. (3m): - ¢ CKT + - CKT ¢ + - ¢ CKT + - CKT ¢ + Position Voltage Top W = c VOLTAGE 17 VRMS 22 VRMS 24 VRMS Q J1 to Ta A 1 4 a Q Q = C~O FROM TrueAlert COMPATIBLE SLC - SLC - SLC - _ J1 to Ta B 70.7 VRMS 1 2 ST n3 SOUND TYPE STEADY CODED STEADY CODED STEADY CODED SLC - 1 1 - w f� Z � SLC CONTROLLER (SEE WIRING NOTES) f ___ + SETTING HIGH LOW HIGH LOW HIGH LOW HIGH LOW HIGH LOW HIGH LOW SLC + SLC + SLC + ® J1 to Ta D 1 4 ® C 0 REVERBERANT s - ' s + A to Ta E 25 VRMS 1 2 s - ' s + yj O CHAMBER, UL 84.6 79.1 80.6 75.5 86.3 81.5 82.4 77.2 WIRING NOTES: J1 to T F 1 CO 464 TEST J1 to Ta G 2 ^ � N � °�' ANECHOIC 1. REFER TO FIELD WIRING DIAGRAMS SUPPLIED WITH THE 4009 TrueAlert ADDRESSABLE CONTROLLER FOR ADDITIONAL SLC WIRING INFORMATION. V , CHAMBER 91 84 86 79 93 87 88 82 2. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL. 0 3. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP WIRES UNDER TERMINALS. O o o O 4. ALL TrueAlert SLC WIRING CONNECTIONS ARE SUPERVISED AND POWER -LIMITED. GENERAL SPECIFICATIONS: r` a HOUSING DIMENSIONS (INCLUDING LENS): 4 3/4" H x 6 7/8" W x 2 5/8" D (121 mm x 175 mm x 67 mm) 5. POWERING THE A/V FROM AN APPLIANCE POWER SOURCE LESS THAN 17 VDC OR GREATER THAN 32 VDC MAY CAUSE PERMANENT DAMAGE TO THE�jilll�C�i A/V UNIT. DEPTH INTO BOX 11/16" (17 mm) "•'"�"'Y "�� J 6. THE TrueAlert A/V CAN ONLY BE OPERATED THROUGH A 4009 TrueAlert ADDRESSABLE CONTROLLER OR TrueAlert COMPATIBLE FACP. TEMPERATURE RANGE: 32' TO 122' F (0' TO 50' C) 3 LL_HUMIDITY RANGE: 10% TO 93% NON -CONDENSING AT 100' F (38' C) 7. WHEN CONTROLLED FROM A 4009 TrueAlert ADDRESSABLE CONTROLLER, THE FACP SETTINGS ARE NOT SUPPORTED. o CONNECTIONS: TERMINAL BLOCKS FOR 18 TO 12 AWG 8. MAXIMUM LENGTH OF TAP IS 100 FEET. TrueAlert' NON -ADDRESSABLE MULTI -CANDELA VISIBLE NOTIFICATION APPLIANCE N PRODUCT INFORMATION (CEILING MOUNT) FEATURES: ° • UL LISTED TO STANDARD 1971 (ERICO NO. 512) T-BAR WITH CLIPS AND SCREWS • ADA COMPATIBLE SUPPLIED BY CONTRACTOR - SYNCHRONIZATION FLASH RATE MODE FOR USE WITH: • SEPARATE STROBE SYNCHRONIZATION MODULES THAT ARE AVAILABLE HANDY BOX, 1-1/2" DEEP OR FOR CLASS B OR CLASS A OPERATION 6, SINGLE GANG BOX, 2-1/2" DEEP _ • SEPARATE SMARTSYNC CONTROL MODULES (SCMs) THAT PROVIDE SUPPLIED BY OTHERS Q F mo CLASS B OR CLASS A OUTPUT FROM CONVENTIONAL NAC INPUTS cn LU � SINGLE GANG BOX z 5 Z `n o SPECIFICATIONS: °0 (WIREMOLD V5744S) 0 N m z ZD w 2-1/4" (57mm) o� p � z • HOUSING DIMENSIONS: 4-3/4" L X 2-5/16" W X 2-5/8" D (121 mm X 75mm X 67mm) ° SUPPLIED BY OTHERS LU o= o • TEMPERATURE RANGE: 32'F TO 122'F (0 TO 50'C) zo C o ¢ Q Q • HUMIDITY RANGE: 10% TO 93% NON -CONDENSING AT 100'F (38'C) ; o 0 o Ov < Q J 4905-9910 ADAPTER PLATE, a L o o w ,, F ,� N -TERMINAL BLOCKS FOR 18AWG TO 12AWG; TWO WIRES PER REQUIRED FOR SURFACE MOUNT v M Cl) co o o o 0 TERMINAL FOR IN/OUT WIRING. F I WITH HANDY BOX UNLESS USING U) o C-4 N N THE 4905-9926 WIRE GUARD o � Q0 rn M ¢ ¢ ¢ U) m WIRING NOTES: co w a Q a 1. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL. IF 0Lo � U)3: 3:o m 0000 U_ U_ U_ U_2. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP C) � n ¢ Q WIRES UNDER TERMINALS. "---------- -obe intensity -------- i M 3. ALL NAC WIRING CONNECTIONS ARE SUPERVISED AND POWER -LIMITED. 4 viewing slot w Cr) CD � � co 4. SEE INSTALLATION INSTRUCTIONS (579-548) FOR ADDITIONAL INFORMATION. i' �o Intensity selection plug, i ¢ N N a M o _ LP accessible only from rear of lensi (� v v co 6' housing; factory setting is 15 cd i OJ co STROBE: L-------------------------- LU Of Q C14OD r__ o • RATED VOLTAGE RANGE: UL LISTED: 16 VDC TO 33 VDC PER UL 1971 OPTIONAL 4905-9926 WIRE GUARD :50 ULC LISTED: 20 VDC TO 30 VDC PER ULC S526-M878 CEILING MOUNT WITH MOUNTING PLATE N • FLASH RATE: 1 Hz • SYNCHRONIZED MODE NAC LOADING: MAXIMUM OF 35 SYNCHRONIZED STROBES PER NAC CIRCUIT. o FROM FACP 24VDC NON -CODED TO ADDITIONAL NOTIFICATION R RETURN NOTIFICATION APPLIANCE CIRCUIT - TOPFACP FOR STYLELIANCE DEVICE D Z APPLICATION z *CURRENT DRAWS REFLECT STROBE FLASHING OR PRECEDING DEVICE, OR IF LAST DEVICE ON CIRCUIT IN A DRAWN BY: SHASHIKALA SIMPLEX 4905-9914, 9922, OR + a HOUSING LETTERING STROBE RMS CURRENT STYLE Y APPLICATION PLACE AN CHECKED BY: RAKESH 9938 SYNC MODULE. END -OF LINE RESISTOR. RESISTOR MODEL NUMBER COLOR COLOR RATING 16 VDC 18 VDC 24 VDC ( Q - c m m m VALUE IS FACP DEPENDENT.) ISSUE DATE: 8/8/14 J c m m m JOB #: c m m m c m m m 0 0 0 PROJECT #: 458:979327746 - 1 WHITE cd mA 67 mA 50 mA - + - + JCI © 2023 30cd 125 mA 1 111 mA 1 83 mA c mA 1 207 mA 1 155 mA O (0 SYSTEM: 11 cd 316 mA 281 mA 211 mA FIRE ALARM SYSTEM SHEET: WIRING TYPICALS N o 0 U) w L U FA-703 x 0 M