590333a rated wall assembly ENG judgementENGINEERING JUDGMENT FIRESTOP DETAIL NEERING THIWOULIDBEEXPECT DNTOPASSTHESTATEDRATINGSIFTES EDHAT PROJECT: SMC EDM MRI ADDRESS: 21601 76TH AVE W, EDMONDS, WA 98026 ISSUED TO: -B N BUILDERS Ratings F-RATING = 1-HR. OR 2-HR. TOP VIEW T NOM. 0" 2 1 3 1. GYPSUM SHAFT WALL ASSEMBLY (ULIcUL CLASSIFIED) (MIN. 2-1/2" STEEL STUDS) (1-HR. OR 2-HR. FIRE -RATING) (2-HR. SHOWN). 2. GYPSUM WALL ASSEMBLY (ULIcUL CLASSIFIED) (1-HR. OR 2-HR. FIRE -RATING) (2-HR. SHOWN). 3. GYPSUM CAP CONSISTING OF TWO ADDITIONAL LAYERS (MIN. 5/8" THICK) TYPE "X" GYPSUM BOARD, INSTALLED AND ATTACHED PER THE ONSITE ENGINEERS SPECIFICATIONS. 4. MINIMUM 1/2" BEAD HILTI CP 606 FLEXIBLE FIRESTOP SEALANT APPLIED AT POINT OF CONTACT. NOTES: 1. WIDTH OF JOINT = NOMINAL 0". 2. T-RATING MAY NOT EQUAL F-RATING IN ACCORDANCE WITH UL 2079. 3. FIRE -RATING OF ASSEMBLY IS DEPENDENT UPON THE PERFORMANCE OF GYPSUM CAP UNDER FIRE CONDITIONS. 4. THIS SYSTEM IS DESIGNED AS A STATIC SYSTEM ONLY. 5. THE F-RATING OF THIS ENGINEERING JUDGMENT IS DEPENDENT UPON THE LOWEST F-RATING OF THE CONSTRUCTION ASSEMBLIES. 6. THIS SYSTEM IS NOT DESIGNED TO REPLACE MUD AND TAPE WHERE REQUIRED. Referenced Tested Systems Project Application Details (REFERENCE : UL/cUL SYSTEM NO. WW-S-0059, WW-S-0048, & HW-S-0054) CS0159316 Applicable Test Method UL 2079 HILTI, Inc. Sheet 1 of 1 Drawing No. 3Designed Plano, Texas USA (800) 879-8000 590333a Scale 114" =1" by Hilti FPE Austin Griffith Drafter TT Hilti Firestop Systems Date Apr. 10, 2023 Saving Lives through /nnov tion and Education