SMCE Reroute SI testing report/Medical Gas Services 918 S Horton St Suite 917 Seattle, WA 98134 medgasservices.io (425) 894 5918 Medical Gas Line Verification Report Date: January 27, 2023 Job Number: 4178 Contractor: MacDonald -Miller Facilities Service Date(s) / Time(s) of Testing: January 24, 2023 — 0800hrs Facility: Swedish Medical Center— Edmonds Campus 21601 76th AVE W Edmonds, WA 98026 Scope of Work: Re -rout of medical oxygen and medical vacuum distribution. Our firm certifies that the verifier named in the report is properly trained and certified to perform the activities required. All test and measurement equipment is properly calibrated and maintained. As a representative of Medical Gas Services LLC the verifier named in this report has conducted testing and verification of medical gas piping systems and related equipment to certify the following on the above date. I. General Findings: A. Medical oxygen and vacuum are in compliance with NFPA 99 (2012ed): Category 1 B. No crossed lines were found in medical oxygen or vacuum systems in the tested areas on the day of testing. C. Medical oxygen meets minimum concentration. D. Medical oxygen meets minimum flow and is at normal pressure. E. Medical vacuum meets minimum flow and is at normal vacuum pressure. F. Medical gas system components in the area tested are in compliance with NFPA 99 (2012ed). G. Medical Gas Line Purity Test: PASS H. Purge Gas: Lot # T1027201 (Central) I. Attachments: Worksheet Note: Existing Equipment and Systems NFPA 99(2012ed) #5.1.1.4 — An existing system that is not in strict compliance with the provisions of this standard shall be permitted to be continued in use as long as the authority having jurisdiction has determined that such use does not constitute a distinct hazard to life. VR-Medical Gas Line Pg 1 of 2 /Medical Gas Services 918 S Horton St, Suite 917 Seattle, WA 98134 medgasservices.io (425) 894 5918 II. Medical Gases: A. Oxygen: 1. Static Line Pressure: 52.9 psi 2. Dynamic Outlet Free Flow: >8 scfm 3. Oxygen Concentration: 99.65 4. Delta Flow: PASS III. Vacuum: A. Medical —Surgical Vacuum 1. Static Line Vacuum: 4.5" HgV 2. Dynamic Inlet Free Flow: >3.0 scfm 3. Delta Flow: PASS IV. Particulate Test: PASS V. Odor: None VI. Outlets / Inlets: A. Brand: BeaconMedaes B. Quick Connect Style: Chemetron VII. Brazier: Micah Synsteby A. Brazier Number: SYNSTM*913ML B. Contractor: MacDonald Miller Facilities Solution Vill. Comments: A. None Tested By: David Pomeranz — ASSE 6030 Verifier VR-Medical Gas Line Pg 2 of 2 Medical Gas Services 918 S Horton St, Suite 917 Seattle, WA 98134 medsasservices.io (425) 894 5918 Medical Gas Outlet / Inlets Evaluation Worksheet Facility: Swedish Edmonds Job #: 4178 Date: 1.24.23 Area Tested: Imaging Verifier: DP Zone valve - n None n Not Required n New M Existing Labeled As: X-Ray 1,2,3 & Ultrasound 1 & 2 ZV Brand: BeaconMedaes Gas 3 Part Valve DL Gauge Ga. PSI Act PSI Comments: OX ® Yes ❑ No ® Yes ❑ No 54 52.9 VAC ® Yes ❑ No ® Yes ❑ No 21 20.43 Area Alarm - n None n Not Required n New M Existing Labeled As: X-Ray 1,2,3 & Ultrasound 1 & 2 Brand: BeaconMedaes Gas PSI Set HI Set LO Sensor Comments: OX 52 60 40 DL VAC 20 -- 12 DL Outlets & Inlets - n New nX Existing Outlet / Inlets Brand: BeaconMedaes Location: Wall Quick Connect: Chemetron Area / Room / Door Gas Flow SCFM Delta Flow Conc. Part. Comments: X-RAY 3 01104.013A 02 >8 <5 99.65 .000 Dip — 41.08 // HHC VAC 4.5 >12 -- -- 4179/1.24.23 Page 1 of 1