TAB reportCOMMISSIONING, START-UP & 1ST
MacDonald -Miller
FACILITY SOLILTIONS
INSPECTION REPORT
page 1 0l 1
JOB NAME: SMC EDMONDS JOB# 7722-1356 DATE:
4125123 CONTACT:
JOB SITE ADDRESS: 21601 76TH AVE W EDMONDS WA 98026
PHONE NUMBER:
NEW INSTALL/REPLACE/EXISTING? PROJECT MGR: Jake Burstein
TECHNICIAN: Phil Roach
UNIT REMOVAL INFO REFRIGERANT TYPE: AMOUNT OF REFRIGERANT:
METHOD OF DISPOSAL & PO#:
OLD INDOOR MODEL# OLD MAKE: OLD SIN:
OLD OUTDOOR MODEL# OLD MAKE: OLD S/N:
OLD INDOOR UNIT DESIGNATI OLD OR CODE 1l: -D OUTDOOR UNIT DESIGNATIO
OLD OR CODE
UNIT TYPE: Indoor & Package) Exhaust fan u blast- serves MRI
UNIT TYPE: Outdoor CU HP SPLfT SYSTEM ONLY:
NIT NUMBER/ MAKE EF.X.0241 COOK NEW OR CODE: AA000797
UNIT NUMBER:
NEW OR CODE:
MODEL M 165 ACRUX 165RX17D
MAKE
SERIAL M 033SK0441 0010000701
MODEL M
NAMEPLATE VOLTAGE/PHASE: 1201208 1 1
SERIAL #t
ACTUAL VOLTAGE/PHASE: 207yac 1 1
NAMEPLATE VOLTAGE/PHASE.
I
TONNAGE: TOTAL UNIT UNIT RATED AMPS: 4.0-3.8 TXV OR ORIFICE:
ACTUAL VOLTAGE/PHASE (A,B,C):
I
HEAT TYPE: LOCATION: MRI rooftop
LINE SIZES: SUCTION:
REFER TYPE: R-
LIQUID: Refer bottle S/N:
QUANTITY: CKT A CKT B:
TRANSFORMER SECONDARY VOLTAGE MEASURED:
FILTERS: NA
SIZE
NOTES:
NC failed closed 24VAC backdraft damper. Slight vibration at 100%. Adlusted to 1460 rip mWAX
BELTS: NA
OTY
SIZE
OTY
SIZE
UNIT LABELED
YES
MMFS STICKER INSTALLED
YES
HVAC UNIT DEMO & RECOVERY FORM
NA
YES
YES
YES
WIRING CONNECTIONS TIGHT
CONDENSATE TRAP INSTALLED
SHIPPING BLOCKSIBOLTS REMOVED
NA
YES
NA
ECONOMIZER OPERATION CHECKED
ADEQUATE FUSED DISCONNECT
PROPER FUSES INSTALLED
YES
NA
NA
START-UP LABEL WITH JOB If IN UNIT
DEFROST ON HEAT PUMP CHECK
VERIFY BELT TENSIONIALIGNMENT
NA
NA
CONDENSATE PUMP INSTALLED
CONDENSATE PUMP OPERATIONS
FAN ROTATION VERIFIED
CONTROLS: DOC CONTROL SYSTEM: NA MMFS PROGRAMMED: MAKE:
MODEL:
PC LOCATION: PASSWORD ACCESS:
PERSON TRAINED:
SMOKE DETECTOR: DESIGN MINIMUM & MAX PRESS: MEASURED AIR PRIES.:
STAND ALONE: BUILDING SYSTEM:
SMOKE DETECTOR WORKS CORRECTLY: SMOKE DETECTOR model#:
E)dsbng or New:
FAN SHAFT
FAN: NAMEPLATE AMPERAGE: 3.8A MEASURED AMPS (A,B,C): 3.6A at 00
MOTOR FN # SIZE: NA
FAN PULLEY
HP. 112 SPEED/RPM: 1590 max CL BETWEEN SHAFTS NA MOTOR PULLEY SIZE•.
NA SIZE: NA
OUTDOOR FAN: NA
NAMEPLATE AMPERAGE MEASURED AMPS (A,B,C):
HP.
COMPRESSOR A NA MEASURED VOLTS (A,B,C). NAMEPLATE AMPS:
MEASURED AMPS (A,B,C):
LIO PRESS:
Hot Gas Bypass: SUCT PRESS: CLG: HTG: CLG: HTG:
Comp. Disc. Line Temp: C:
H:
EVACUATED: SUPh: C' H: SUBc: C: H: RAT: C: H: SAT: C: H: AT:C:
H:
ENTHALPY
AIRIWATER INLET TEMP. C: If. AIR/WATER OUTLET TEMP: C: H: OUTDOOR TEMP. SETTING:
COMPRESSOR B: NA MEASURED VOLTS (A,B,C): NAMEPLATE AMPS:
MEASURED AMPS (A,B,C):
LIQ PRESS:
Hot Gas Bypass: SUCT PRESS: CLG: HTG: CLG: HTG:
Comp. Disc. Line Temp: C:
H:
EVACUATED: SUPh: C: H: SUBc: C: H: RAT: C: H: SAT:
C; H: AT: C:
H:
GAS HEAT: NA NAMEPLATE MANIFOLD PRESSURE: MANIFOLD PRESSURE AT FIRE:
BOILER (yes or no):
INDUCER MOTOR RATED AMPS: INDUCER MOTOR MEASURED AMPS RETURN TEMP:
SUPPLY TEMP:
AT
IGH LIMIT SETTING: TEST HIGH LIMIT?: FLAME ROLL OUT?: PRESSURE SWITCHES?:
NAMEPLATE
ELECTRIC HEAT: NA MFG: Model- M SERIAL P.
KW
AT
MEASURED VOLTS (A,B,C): NAMEPLATE AMPS: MEASURED AMPS (A,B,C):
TEST HIGH LIMIT?
BALANCING:
DESIGN CFM: MEASURED CFM: Design GPM:
MEASURED GPM:
Single 2/2 grille in MRI room. Toggle switch outside the room turns onloff the fan.
REMARKS:
116/23 rev
CAOM
MacDonald-Miller
FACILITY SOLUTIONS
Preliminary TAB REPORT SUMMARY
SMCE 3T MRI
JOB # 7722-1356
1) General Notes
a) HVAC balancing was completed 5/8/23.
b) Design information was taken from engineered drawings.
c) TAB work was in accordance with NEBB procedural standards.
d) Outlet volumetric flow rates were measured by use of a calibrated Flow Hood.
2) Scope of work
a) Balance 3 new VAVH and VAVR to design values.
b) Balance new EF-x.024 to design values.
3) Summary
a) VAV boxes serving rooms E104.024 and E104.024C are short on air at maximum flow. Need to know what fan
system serves these boxes and increase duct static on the supply and return systems.
b) Existing VAVH.104.013 is not controlling. The damper is being told by the controls to beat 0% open. Need
Siemens to investigate. Damper was manually commanded open to verify operation.
Project Manager: Jake Burstein
Field Technician: Rick Stambaugh (TAB / Building Commissioning)
#rTrVA
MacDonald-Miller
FACILITY SOLUTIONS
Project
SMCE 3T MRI
Job Number
77221356
Area Served
VAVH104.024B
E.104.024A
1
CD
Totals
Address
194
Inlet Size
0.325
Multiplier
0.69
ETS Offset
0
Remarks:
Name in the ddc=104.024A.
VAVR104.024B
Air Outlet
Test Report
System
OutletI
Design
Preliminary
Fin"FIlow
Percent of
No.
Type
Size
Ak
Vel.
Flow
Vel. Flow
Vel.
Design
350 1 1 155 1 1 355 1 101 %
Design
Actual
Max Flow
350
355
Min Flow
350
355
Test Date:
5/8/2023
Readings By:
RS/ CKY
E.104.024A
I 1 1 EG
350 1 130 1 1
360 1 103% 1
Totals
Address
194
Design
Actual
Inlet Size
0.325
Max Flow
350
360
Multiplier
0.72
Min Flow
350
360
Remarks:
Test Date:
5/8/2023
Readings By:
RS/ CKY
�E.104.024
1 1 1 CD 780
475
665 1 85% J
Totals
Address
193
Design
Actual
Inlet Size
0.325 Max Flow
780
655
Multiplier
0.68 Min Flow
400
415
ETS Offset
0
Remarks:
Supply and exhaut dampers at 100% at max flow..
Test Date:
5/8/2023
Readings By:
RS/ CKY
-Miller MacDonald
FACILITY SOLUTIONS
Project SMCE 3T MRI
Job Number 77221356
Area Served
Air Outlet
Test Report
System
Outlet
Design
PreliminaryFinal
Percent of
No.
T
e Size
Ak
Vel.
Flow
Vel. Flow
Vel. Flow
Design
�E.104.024
1 1 1 EG 780
595
660 J
Totals
Address
193
Design
Actual
Inlet Size
0.55 Max Flow
780
660
Multiplier
0.63 Min Flow
400
405
Remarks:
Supply and exhaut dampers at 100% at max flow.
Test Date:
5/8/2023
Readings By:
RS/ CKY
VAVH104.024C
�E.104.024C
I 1 1 1 CD 580
425
450 1/ "- J
Totals
Address
195 Max SP
Design
Actual
Inlet Size
0.35 Min SP Max Flow
580
450
Multiplier
Min Flow
190
200
Filter Size
Remarks:
Name in the ddc=104.024B.
Test Date:
5/8/2023
Supply and exhaut dampers at 100% at max flow..
Readings By:
RS/ CKY
VAVR104.024C
E.104.024C I 1 1 1 EG
580 285
455 1 78% J
Totals
Address 195 Max SP
Design
Actual
Inlet Size 0.325 Min SP
Max Flow
580
455
Multiplier
Min Flow
190
185
Filter Size
Remarks:
Test Date:
5/8/2023
Readings By:
RS/ CKY
4=!OMacDonald -Miller
FACILITY SOLUTIONS
Project SMCE 3T MRI
Job Number 77221356 System
Area Served Outlet Design PreliminaryFinal Percent of
No. I Type I Size I Ak Vel. I Flow Vel. I Flow Vel. I Flow I Design
Totals
Address Max SP
Inlet Size Min SP
Multiplier
Filter Size
Remarks: Existing VAV control damper is controling to 0%
EF-X.024
0
Design Actual
Max Flow
Min Flow
Test Date: 5/8/2023
Readings By: RS/CKY
E.104.024 1 1 1 1 EG 1000 755 995 1 100% J
Totals
Remarks: Speed controller is at MAX. Test Date: 5/8/2023
Readings By: RS/CKY
Test Date Readings By Page:
A
CR
2
31
41
5
a
' LEVEL 1 PARTIAL MECHANICAL PLAN
SCALE LB'- Ya
C I D
r
U)
KEY NOTES
J�JJ
1. EAaUST VAV_.SARE ONIENTED YT CONTROL BOX
A ESS AT THE BOTTOM. E PT FOR VaVW11M.2a
2. TE EASING -USER. USER TANS FLOW RERDNG BEFORE
AAND SINBNANCE
U)
OEL OSFUSER TO EASING A W
AFT ER
I
Q
3. .— THROUGH RFF IRELD SHALL BE MADE
TNROUG IAWAVEG E PRO— BY THE SMELGNG
-ER PROVIDE F CONNEC ON TO THE WAVE GU E.
Q
O AND pFNSERB.PROWEACF CONNEONNSNEOFTHE
wAVE S_
a, 1 14 DUCT UP. SEE NOTE S ABOVE. DUCT PENETRATES
CEl1NG OFTHERFSHB'RGTHRWGHA WAVE GLIDE
af
J
B. i E PEAa .ANNo HN�NBORs .—RN
DUOTYORN HERE TO SERVE MPo E%aM ROOM.
B. SEEM 1FOR CRIED TER DNGPAM.
NGdaUED�GdAS� AR�AFMUL/FBnSE
S. SEE 1A 1 FOR SHALLOW GRD OONNEMpNOWGRPM.
GENERAL NOTES G°
1. -RE ARE NO TRANSFER DUCTS YT THE SPACE.
2, IS NO NreRNaL IN ED I—N THE
A;�'�sn.
OICT — THERE 6CLOSEO CELL FOAM SOUND IINNG
S SUP TERN U
-, j:.._- 5`r
3. ANCHANG SOFNEMRENRaftND EETSSFGl GES OF
O
In
=t
LA
�A
PERMR SET
KEY PLAN
LEVEL 1 PARTNL
MECHANICAL
PUN
M2.1