TAB reportCOMMISSIONING, START-UP & 1ST MacDonald -Miller FACILITY SOLILTIONS INSPECTION REPORT page 1 0l 1 JOB NAME: SMC EDMONDS JOB# 7722-1356 DATE: 4125123 CONTACT: JOB SITE ADDRESS: 21601 76TH AVE W EDMONDS WA 98026 PHONE NUMBER: NEW INSTALL/REPLACE/EXISTING? PROJECT MGR: Jake Burstein TECHNICIAN: Phil Roach UNIT REMOVAL INFO REFRIGERANT TYPE: AMOUNT OF REFRIGERANT: METHOD OF DISPOSAL & PO#: OLD INDOOR MODEL# OLD MAKE: OLD SIN: OLD OUTDOOR MODEL# OLD MAKE: OLD S/N: OLD INDOOR UNIT DESIGNATI OLD OR CODE 1l: -D OUTDOOR UNIT DESIGNATIO OLD OR CODE UNIT TYPE: Indoor & Package) Exhaust fan u blast- serves MRI UNIT TYPE: Outdoor CU HP SPLfT SYSTEM ONLY: NIT NUMBER/ MAKE EF.X.0241 COOK NEW OR CODE: AA000797 UNIT NUMBER: NEW OR CODE: MODEL M 165 ACRUX 165RX17D MAKE SERIAL M 033SK0441 0010000701 MODEL M NAMEPLATE VOLTAGE/PHASE: 1201208 1 1 SERIAL #t ACTUAL VOLTAGE/PHASE: 207yac 1 1 NAMEPLATE VOLTAGE/PHASE. I TONNAGE: TOTAL UNIT UNIT RATED AMPS: 4.0-3.8 TXV OR ORIFICE: ACTUAL VOLTAGE/PHASE (A,B,C): I HEAT TYPE: LOCATION: MRI rooftop LINE SIZES: SUCTION: REFER TYPE: R- LIQUID: Refer bottle S/N: QUANTITY: CKT A CKT B: TRANSFORMER SECONDARY VOLTAGE MEASURED: FILTERS: NA SIZE NOTES: NC failed closed 24VAC backdraft damper. Slight vibration at 100%. Adlusted to 1460 rip mWAX BELTS: NA OTY SIZE OTY SIZE UNIT LABELED YES MMFS STICKER INSTALLED YES HVAC UNIT DEMO & RECOVERY FORM NA YES YES YES WIRING CONNECTIONS TIGHT CONDENSATE TRAP INSTALLED SHIPPING BLOCKSIBOLTS REMOVED NA YES NA ECONOMIZER OPERATION CHECKED ADEQUATE FUSED DISCONNECT PROPER FUSES INSTALLED YES NA NA START-UP LABEL WITH JOB If IN UNIT DEFROST ON HEAT PUMP CHECK VERIFY BELT TENSIONIALIGNMENT NA NA CONDENSATE PUMP INSTALLED CONDENSATE PUMP OPERATIONS FAN ROTATION VERIFIED CONTROLS: DOC CONTROL SYSTEM: NA MMFS PROGRAMMED: MAKE: MODEL: PC LOCATION: PASSWORD ACCESS: PERSON TRAINED: SMOKE DETECTOR: DESIGN MINIMUM & MAX PRESS: MEASURED AIR PRIES.: STAND ALONE: BUILDING SYSTEM: SMOKE DETECTOR WORKS CORRECTLY: SMOKE DETECTOR model#: E)dsbng or New: FAN SHAFT FAN: NAMEPLATE AMPERAGE: 3.8A MEASURED AMPS (A,B,C): 3.6A at 00 MOTOR FN # SIZE: NA FAN PULLEY HP. 112 SPEED/RPM: 1590 max CL BETWEEN SHAFTS NA MOTOR PULLEY SIZE•. NA SIZE: NA OUTDOOR FAN: NA NAMEPLATE AMPERAGE MEASURED AMPS (A,B,C): HP. COMPRESSOR A NA MEASURED VOLTS (A,B,C). NAMEPLATE AMPS: MEASURED AMPS (A,B,C): LIO PRESS: Hot Gas Bypass: SUCT PRESS: CLG: HTG: CLG: HTG: Comp. Disc. Line Temp: C: H: EVACUATED: SUPh: C' H: SUBc: C: H: RAT: C: H: SAT: C: H: AT:C: H: ENTHALPY AIRIWATER INLET TEMP. C: If. AIR/WATER OUTLET TEMP: C: H: OUTDOOR TEMP. SETTING: COMPRESSOR B: NA MEASURED VOLTS (A,B,C): NAMEPLATE AMPS: MEASURED AMPS (A,B,C): LIQ PRESS: Hot Gas Bypass: SUCT PRESS: CLG: HTG: CLG: HTG: Comp. Disc. Line Temp: C: H: EVACUATED: SUPh: C: H: SUBc: C: H: RAT: C: H: SAT: C; H: AT: C: H: GAS HEAT: NA NAMEPLATE MANIFOLD PRESSURE: MANIFOLD PRESSURE AT FIRE: BOILER (yes or no): INDUCER MOTOR RATED AMPS: INDUCER MOTOR MEASURED AMPS RETURN TEMP: SUPPLY TEMP: AT IGH LIMIT SETTING: TEST HIGH LIMIT?: FLAME ROLL OUT?: PRESSURE SWITCHES?: NAMEPLATE ELECTRIC HEAT: NA MFG: Model- M SERIAL P. KW AT MEASURED VOLTS (A,B,C): NAMEPLATE AMPS: MEASURED AMPS (A,B,C): TEST HIGH LIMIT? BALANCING: DESIGN CFM: MEASURED CFM: Design GPM: MEASURED GPM: Single 2/2 grille in MRI room. Toggle switch outside the room turns onloff the fan. REMARKS: 116/23 rev CAOM MacDonald-Miller FACILITY SOLUTIONS Preliminary TAB REPORT SUMMARY SMCE 3T MRI JOB # 7722-1356 1) General Notes a) HVAC balancing was completed 5/8/23. b) Design information was taken from engineered drawings. c) TAB work was in accordance with NEBB procedural standards. d) Outlet volumetric flow rates were measured by use of a calibrated Flow Hood. 2) Scope of work a) Balance 3 new VAVH and VAVR to design values. b) Balance new EF-x.024 to design values. 3) Summary a) VAV boxes serving rooms E104.024 and E104.024C are short on air at maximum flow. Need to know what fan system serves these boxes and increase duct static on the supply and return systems. b) Existing VAVH.104.013 is not controlling. The damper is being told by the controls to beat 0% open. Need Siemens to investigate. Damper was manually commanded open to verify operation. Project Manager: Jake Burstein Field Technician: Rick Stambaugh (TAB / Building Commissioning) #rTrVA MacDonald-Miller FACILITY SOLUTIONS Project SMCE 3T MRI Job Number 77221356 Area Served VAVH104.024B E.104.024A 1 CD Totals Address 194 Inlet Size 0.325 Multiplier 0.69 ETS Offset 0 Remarks: Name in the ddc=104.024A. VAVR104.024B Air Outlet Test Report System OutletI Design Preliminary Fin"FIlow Percent of No. Type Size Ak Vel. Flow Vel. Flow Vel. Design 350 1 1 155 1 1 355 1 101 % Design Actual Max Flow 350 355 Min Flow 350 355 Test Date: 5/8/2023 Readings By: RS/ CKY E.104.024A I 1 1 EG 350 1 130 1 1 360 1 103% 1 Totals Address 194 Design Actual Inlet Size 0.325 Max Flow 350 360 Multiplier 0.72 Min Flow 350 360 Remarks: Test Date: 5/8/2023 Readings By: RS/ CKY �E.104.024 1 1 1 CD 780 475 665 1 85% J Totals Address 193 Design Actual Inlet Size 0.325 Max Flow 780 655 Multiplier 0.68 Min Flow 400 415 ETS Offset 0 Remarks: Supply and exhaut dampers at 100% at max flow.. Test Date: 5/8/2023 Readings By: RS/ CKY -Miller MacDonald FACILITY SOLUTIONS Project SMCE 3T MRI Job Number 77221356 Area Served Air Outlet Test Report System Outlet Design PreliminaryFinal Percent of No. T e Size Ak Vel. Flow Vel. Flow Vel. Flow Design �E.104.024 1 1 1 EG 780 595 660 J Totals Address 193 Design Actual Inlet Size 0.55 Max Flow 780 660 Multiplier 0.63 Min Flow 400 405 Remarks: Supply and exhaut dampers at 100% at max flow. Test Date: 5/8/2023 Readings By: RS/ CKY VAVH104.024C �E.104.024C I 1 1 1 CD 580 425 450 1/ "- J Totals Address 195 Max SP Design Actual Inlet Size 0.35 Min SP Max Flow 580 450 Multiplier Min Flow 190 200 Filter Size Remarks: Name in the ddc=104.024B. Test Date: 5/8/2023 Supply and exhaut dampers at 100% at max flow.. Readings By: RS/ CKY VAVR104.024C E.104.024C I 1 1 1 EG 580 285 455 1 78% J Totals Address 195 Max SP Design Actual Inlet Size 0.325 Min SP Max Flow 580 455 Multiplier Min Flow 190 185 Filter Size Remarks: Test Date: 5/8/2023 Readings By: RS/ CKY 4=!OMacDonald -Miller FACILITY SOLUTIONS Project SMCE 3T MRI Job Number 77221356 System Area Served Outlet Design PreliminaryFinal Percent of No. I Type I Size I Ak Vel. I Flow Vel. I Flow Vel. I Flow I Design Totals Address Max SP Inlet Size Min SP Multiplier Filter Size Remarks: Existing VAV control damper is controling to 0% EF-X.024 0 Design Actual Max Flow Min Flow Test Date: 5/8/2023 Readings By: RS/CKY E.104.024 1 1 1 1 EG 1000 755 995 1 100% J Totals Remarks: Speed controller is at MAX. Test Date: 5/8/2023 Readings By: RS/CKY Test Date Readings By Page: A CR 2 31 41 5 a ' LEVEL 1 PARTIAL MECHANICAL PLAN SCALE LB'- Ya C I D r U) KEY NOTES J�JJ 1. EAaUST VAV_.SARE ONIENTED YT CONTROL BOX A ESS AT THE BOTTOM. E PT FOR VaVW11M.2a 2. TE EASING -USER. USER TANS FLOW RERDNG BEFORE AAND SINBNANCE U) OEL OSFUSER TO EASING A W AFT ER I Q 3. .— THROUGH RFF IRELD SHALL BE MADE TNROUG IAWAVEG E PRO— BY THE SMELGNG -ER PROVIDE F CONNEC ON TO THE WAVE GU E. Q O AND pFNSERB.PROWEACF CONNEONNSNEOFTHE wAVE S_ a, 1 14 DUCT UP. SEE NOTE S ABOVE. DUCT PENETRATES CEl1NG OFTHERFSHB'RGTHRWGHA WAVE GLIDE af J B. i E PEAa .ANNo HN�NBORs .—RN DUOTYORN HERE TO SERVE MPo E%aM ROOM. B. SEEM 1FOR CRIED TER DNGPAM. NGdaUED�GdAS� AR�AFMUL/FBnSE S. SEE 1A 1 FOR SHALLOW GRD OONNEMpNOWGRPM. GENERAL NOTES G° 1. -RE ARE NO TRANSFER DUCTS YT THE SPACE. 2, IS NO NreRNaL IN ED I—N THE A;�'�sn. OICT — THERE 6CLOSEO CELL FOAM SOUND IINNG ­S SUP TERN U -, j:.._- 5`r 3. ANCHANG SOFNEMRENRaftND EETSSFGl GES OF O In =t LA �A PERMR SET KEY PLAN LEVEL 1 PARTNL MECHANICAL PUN M2.1