Loading...
FIR2022-0033+bracing+3.31.2022_9.23.27_AM+2772904TOLBraceTM Seismic Bracing Calculations V8.8.118 Contractor: northwest fire Project Address: MAIN ST COMMON EAST Address: 22645 83rd ave s f kent, 98032 * wa 0 MAIN ST 558 (east bldg) Phone: 2067727502 Powtisnrrg6 s41e56lM1w+dwrde Licence: RECEIVED EDMONDS, WA Mar 31 2022 Job # 05043C Calculations based on 2016 NFPA Pamphlet#13 CITY OF EDMONDS Brace Information TOLCOTM Brace Components TOLCOTM Component Listed Load Adjusted Load Maximum Brace Length TO" (2.134 m) Diameter of Brace 1 Fig. 1001 Clamp 1600 Ibs (726 kg) 1131 Ibs (513 kg) Fig.980 - 1/2" Universal SWIVE 2100 Ibs (953 kg) 1485 Ibs (674 kg) Type of Brace Sch.40 See Fastener Information Angle of Brace 45° Min. *Calculation Based on CONCENTRIC Loading *Please Note: These calculations are for TOLCOTM components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42" (11 mm) Seismic Brace Assembly Detail L/R Value 200 Max Horizontal Load 1310 Ibs (594 kg) ll wl vE RS,� SWAV B RALE ar+ace alas Fastener Information Orientation to Connecting Surface NFPA Type E Fastener Type 1/2in. x 3 1/2in. Lag Screw / Bolt Diameter 1/2in. Length 3 1/2in. Maximum Load 220 Ibs (100 kg) SWAY �??.IO Brace Identification on Plans SB-1 Prying Factor N/A Brace Type Lateral [X] Longitudinal [ ] 4-Way [ ] Sprinkler System Load Calculation (Fpw = CpWp) CP = 0.598 Diameter Type Length Total Length Weight Per Unit Length Total Weight 2.5" (65 mm) I Eddy -Flow 121 ft (6.4 m) 121 ft (6.4 m) 15.3 lb/ft (7.89 kg/m) 1111 Ibs (50 kg) 1.25" (32 mm) Eddy -Flow 76.5 ft (23.3 m) 176.5 ft (23.3 m) 2.02 lb/ft (3.01 kg/m) 155 Ibs (70 kg) Subtotal Weight 266 Ibs (121 kg) Wp (incl. 15%) 306 Ibs (139 kg) Main Size 2.5" Type/Sch. Eddy -Flow Spacing (ft) 21 Total (Fpw) Maximum Fpw per 9.3.5.5.2 (if applicable) 183 Ibs (83 kg) 440 Ib (199 kg) 1TOLBraceT'" Version 81 Use of TOLBraceTM is subject to terms and conditions per the end user license agreement TOLBraceT"" Seismic Calculations MAIN ST COMMON EAST 550 MAIN ST Brace Identification Brace Type (Per NFPA#13) Braced Pipe (ft) Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # 05043C SB-1 NFPA Type E 2.5" EddyFlow Pipe 21' 0" (6.4 m) Lateral 1" Sch.40 7' 0" (2.13 m) 200 45' 1/2in. x 3 1/2in. Lag Screw or Lag Bolt 3 1 /2in. Summary of Pipe within Zone of Influence 2.5" EddyFlow Pipe (63.5 mm) 21 ft (6.4 m) 1.25" EddyFlow Pipe (31.75 mm) 176.5 ft (23.3 m) G-Factor Used 0.598 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 183 Ibs (83 kg) Material Capacity 1310 Ibs (594 kg) Fastener Capacity 485 Ibs (220 kg) Fig. 1001 Clamp 1131 Ibs (513 kg) Fig.980 - 1/2" Universal Swivel 1485 Ibs (674 kg) Structural Member GLB Calculations prepared by BRYAN FARMER *The description of the Structural Member is for informational purposes only. TOLBrace— software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBrace- 8 Visit us at www.tolco.com E:�T*N Ponrerirrg 9aa AMC womww ----------------------------+ WASHINGTON STATE ■ CERTIFICATE OF COMPETENCY ■ FIRE PROTECTION SPRINKLER SYSTEMS Byron Richard Moye N 9419-0815-C Level 0 ■ Northwest Fire Systems, LLC N ,� NO HFS928CR o o� ■ Expliea ; Ygna 72/37/22 ---------------------------- TOLBraceTM Seismic Bracing Calculations V8.8.118 Contractor: northwest fire Project Address: MAIN ST COMMON EAST Address: 22645 83rd ave s f * kent, wa 98032 550 MAIN ST Phone: 2067727502 Powermg&Wu IasewordMe EDMONDS, WA Licence: Job # 05043C Calculations based on 2016 NFPA Pamphlet#13 Brace Information TOLCOTM Brace Components TOLCOTM Component Listed Load Adjusted Load Maximum Brace Length TO" (2.134 m) Diameter of Brace 1 Fig. 4L Clamp 2000 Ibs (907 kg) 1414 Ibs (641 kg) Fig.980 - 1/2" Universal SWIVE 2100 Ibs (953 kg) 1485 Ibs (674 kg) Type of Brace Sch.40 See Fastener Information Angle of Brace 45° Min. *Calculation Based on CONCENTRIC Loading *Please Note: These calculations are for TOLCOTM components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42" (11 mm) Seismic Brace Assembly Detail L/R Value 200 Max Horizontal Load 1310 Ibs (594 kg) TOLCO FIG 9800 ERACE PIPE Fastener Information Orientation to Connecting Surface NFPA Type E Fastener Type 1/2in. x 3 1/2in. Thru Bolt O TOLCO PIG 4L Diameter 1/2in. Length 31/2in. Maximum Load 350 Ibs (159 kg) Brace Identification on Plans SB-2 Prying Factor N/A Brace Type Lateral[ ] Longitudinal [X] 4-Way [ ] Sprinkler System Load Calculation (Fpw = CpWp) CP = 0.598 Diameter Type Length Total Length Weight Per Unit Length Total Weight 2.5" (65 mm) Eddy -Flow 17.375 ft (5.3 m) 17.375 ft (5.3 m) 5.3 Ib/ft (7.89 kg/m) 92 Ibs (42 kg) 1.5" (40 mm) Eddy -Flow 69.79 ft (21.3 m) 69.79 ft (21.3 m) 2.86 lb/ft (4.26 kg/m) 200 Ibs (91 kg) 1.25" (32 mm) Eddy -Flow 5.375 ft (1.6 m) 5.375 ft (1.6 m) 2.02 lb/ft (3.01 kg/m) 11 Ibs (5 kg) 1.25" (32 mm) Sch. 40 5.25 ft (1.6 m) 5.25 ft (1.6 m) 2.93 lb/ft (4.36 kg/m) 15 Ibs (7 kg) 1" (25 mm) Sch. 40 64.375 ft (19.6 m) 64.375 ft (19.6 m) 2.05 lb/ft (3.05 kg/m) 132 Ibs (60 kg) Subtotal Weight 450 Ibs (204 kg) Wp (incl. 15%) 518 Ibs (235 kg) Main Size 2.5" Type/Sch. Eddy -Flow Spacing (ft) 17.375 Total (Fpw) Maximum Fpw per 9.3.5.5.2 (if applicable) 309 Ibs (140 kg) N/A 1TOLBraceT'" Version 81 Use of TOLBraceTM is subject to terms and conditions per the end user license agreement TOLBraceT"" Seismic Calculations MAIN ST COMMON EAST 550 MAIN ST Job # 05043C E:�T*N Ponrerirrg 9aa AMC womww Brace Identification Brace Type (Per NFPA#13) Braced Pipe (ft) Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener SB-2 NFPA Type E 2.5" EddyFlow Pipe 17' 4.8" (5.3 m) Longitudinal 1" Sch.40 7' 0" (2.13 m) 200 45' 1/2in. x 3 1/2in. Thru Bolt 3 1 /2in. Summary of Pipe within Zone of Influence 2.5" EddyFlow Pipe (63.5 mm) 17.375 ft (5.3 m) 1.5" EddyFlow Pipe (38.1 mm) 69.79 ft (21.3 m) 1.25" EddyFlow Pipe (31.75 mm) 5.375 ft (1.6 m) 1.25" Sch.40 Steel Pipe (31.75 mm) 5.25 ft (1.6 m) 1" Sch.40 Steel Pipe (25.4 mm) 64.375 ft (19.6 m) G-Factor Used 0.598 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 309 Ibs (140 kg) wASNIN[iTOX STATE ■ CERTIFICATE OF COMPETENCY Material Capacity 1310 Ibs (594 kg) FIRE PROTECTION SPRINKLER SYSTEMS Fastener Capacity 350 Ibs (159 kg) ■ Byron Richard Moe ■ y y N 9419-0815-C Level 3 Fig. 4L Clamp 1414 Ibs (641 kg) ■ Northwest Fire Systems, LLC Co ■ N THFS928CR o o; Fig.980 - 1/2" Universal Swivel 1485 Ibs (674 kg) r ■ ■ Expires ■ Structural Member GLB r............. ingnaiuir4,zis,nz m.............. r Calculations prepared by BRYAN FARMER *The description of the Structural Member is for informational purposes only. TOLBrace— software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBrace- 8 Visit us at www.tolco.com