ENG2023-0222 Water Availability CertificateFrom: McConnell, Jeanie
To: Edmonds Enaineerina Permits
Subject: FW: Behar - 7212 220th St SW - Water Availability
Date: Wednesday, July 12, 2023 10:12:53 AM
Attachments: Water Availability Cert 7212 220th Sianed.pdf
Jeanie McConnell I Engineering Program Manager
City of Edmonds
425-771-0220, ext 1338
425-754-5327 cell
Jeanie.mcconnell(@edmondswa.gov
From: Lambert, Jennifer<Jennifer.Lambert@edmondswa.gov>
Sent: Friday, June 30, 2023 4:49 PM
To: KGONZALEZ@CLARKBARNES.COM
Cc: DeLilla, Mike <Mike.DeLilla@edmondswa.gov>; McConnell, Jeanie
<Jeanie.McConnell@edmondswa.gov>; Barson, Christina <Christina.Barson@edmondswa.gov>;
Johns, Kristin <Kristin.Johns@edmondswa.gov>; Bjorback, Leif <Leif.Bjorback@edmondswa.gov>;
Burt, Chris (Fire District Address) <cburt@southsnofire.org>
Subject: Behar - 7212 220th St SW - Water Availability
Karla,
The water availability shows that there will not be enough fireflow to supply water for the nearby
fire hydrants since we only have a little over 1500 gpm at the street and it is a dead end. Domestic
demand is unknown since we don't have enough information at this point. For fire protection, there
will need to be 3 to 5 private fire hydrants onsite, per the fire marshal. This means by the time
extensions are done to the site that the flow numbers will drop significantly and will not be able to
provide the flow levels needed for fire protection for the project. A private looped system
connecting the pipe on 220th to the pipe on highway 99 will likely be a possible remedy for this issue
to meet flow requirements. This may require an easement through the properties east of the
development to allow for the installation of fire hydrants and any watermain that will be needed for
the project.
We are happy to entertain/discuss options. Please note, that based on previous projects in the area
of similar size and scope that the domestic water service and meter will likely need to be at least 6
inches in diameter, which will require a large vault with bypass pipe. This vault and bypass pipe
cannot be placed in the right of way. The City will require an easement for the meter located on
private property. The meter and easement shall be located adjacent to the right of way.
Feel free to contact Mike DeLilla (cc'd on this email) or myself if you have any questions or need
further clarifications.
Jewn�{ev Lainbe'lt
FYI Lf V� r
CXy of E"i&ncUk
425-771-0220 eyt 1321
jennifer.lambert(medmondswa.gov
RECEIVED
pf EVA104,T
4NC. 1 S90
SECTION A
WATER AVAILABILITY APPLICATION
Apr 24 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
Complete and submit this form through www.MyBuildingPermit.com. Submit as a
new application using the following prompts: Application Type — Utilities, Activity
Type — Utility Availability, Scope of Work — Water Main.
Information
Contact/Applicant Name Helene Behar and Elyse Behar
Phone Number 206-233-1999
Email helene beharcom any.com, elyse@beharcompany.com
Address 1000 2nd avenue suite 3230
City Seattle
I State WA
Zip 98104
Project Name Edmonds Green Apartments
Address 7212 220tht SW
city Edmonds
StateWA
Zip 98026
Parcel No. 27042900301800
Does the property currently have water service? Q! Yes (City of Edmonds water) ❑ No
Describe project (number of buildings, number of units, number of stories per building):
This project consists of 3 buildings. There are two apartment podiums, approximately 200 units each, equating
to around 400 units total. The third building is mini warehouse which is approximately 60,000Sgft.
In what phase is the project?
❑ Design Review
❑ Preliminary Plat
❑ Building Permit
❑ Rezone or Other
Associated permit application number(s), if applicable:
SECTION B
Exemptions from Utility Availability Study: 1) Single-family residence; 2) Multi -family project of four
units or less with combo water/fire lines; 3) Short plat subdivision (four single-family lots or less). Please
check one of the following:
❑ A utility availability study IS NOT requested/required. The applicant certifies that this project
is exempt from needing a study as described above and is not requesting a full utility availability
study at this time. Please sign below and submit this form through www.MyBuildingPermit.com.
® A utility availability study IS requested/required for the project, and associated fees will be
due. Please submit the complete application through www.MyBuildingPermit.com.
LAPPLICANT SIGNATURE: ADATE: Z-
APPLICANT PRINTED NAME:
Form Updated 3/28/2023
SECTION C
1. ✓❑ a. Water will be provided by service only to an existing s° cast iron (size) water
main that is 150 (feet) from the site.
OR
❑ b. Water service will require an improvement to the water system of:
❑ (1). feet of water main to reach the site; and/or
❑ (2). The construction of a distribution system on the site; and/or
❑ (3). Other (describe)
2. ✓❑ a. The water system is in conformance with a City approved water comprehensive plan.
OR
❑ b. The water system improvement will require a water comprehensive plan amendment.
(This will cause a delay in permit issuance and approval.)
3. ❑✓ a. The proposed project is within the corporate limits of the City, or has been granted
Boundary Review board approval for extension of service outside the City, or is within
the City approved service area of a private water purveyor.
OR
❑ b. Annexation or Boundary Review Board approval will be necessary to provide service.
4. ❑✓ a. Water is/or will be available at the rate of flow and duration indicated below at no less than
20 psi - Measured at the nearest fire hydrant 242 feet from the building/property
(or as marked on attached map)
Rate of Flow Duration
❑ Less than 500 gpm. (approximately gpm) ❑ Less than one (1) hour
❑ 500 to 999 gpm
❑ 1500 gpm or more
❑ Flow test of
❑ One (1) to two (2) hours
❑ Two (2) hours or more
❑ Other
❑ Calculation of 1563 gpm (Commercial building permits require flow test or
calculation)
OR
❑✓ b. Water system is not capable of providing fire flow.
Water Agency Certificatinii
Comments/Conditions:
Per model, static pressure is 106 psi
Hydrant available flow is 1563 gpm
Residual pressure at available flow is 91 psi
I hereby certify that the above information is true. This certification shall be valid for one year from the date of signature.
City of Edmonds - Engineering
Russell Lynch
(Agency Name)
(Signatory Printed Name)
Capital Projects Manager
� 6/30/2023
(Title)
Si nature Date)