APPROVED BLD PLN BLD2023-0767+Mechanical_Plan+7.20.2023_11.57.07_AM+3679135MECHANICAL BASIS OF DESIGN MECHANICAL GENERAL NOTES 0 N c a� U a w N 0 N a� .� N c� U m 0 E w _o N N_ H N 0 N N .� N ca m U m 0 E w 0 N N 0 M Q � M m ti o� ti� M� N N o� NW �o '•� OW �� A. PROJECT CLIMATE ZONE: KING COUNTY, ZONE 4C 1. INDOOR DESIGN CONDITIONS: 72°F FOR HEATING, 75°F FOR COOLING. 2. EXTERIOR DESIGN CONDITIONS: 24°F FOR HEATING, 83°F FOR COOLING. B. BUILDING ENVELOPE: 1. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR ENVELOPE REQUIREMENTS 2. ALL ENVELOPE COMPONENTS SHALL MEET THE PRESCRIPTIVE REQUIREMENTS OF THE 2018 WSEC, C402 AS FOLLOWS. 3. BUILDING ENVELOPE MEETS THE FOLLOWING PRESCRIPTIVE REQUIREMENTS PER THE 2018 WSEC, C402 AS FOLLOWS: a. OPAQUE ROOF: INSULATION ENTIRELY ABOVE DECK, R-38CI b. OPAQUE WALLS: MASS WALLS, R-9.5 CI; WOOD FRAMED WALLS, R-21 INT c. FLOORS: MASS FLOORS, R-30 CI; JOISTS/FRAMING FLOORS, R-30 d. SLAB ON GRADE FLOORS: R-10 FOR 24" BELOW e. OPAQUE DOORS: SWINGING DOORS, U-0.37; NON -SWINGING DOORS, U-0.34 4. FENESTRATION: NONMETAL FRAMING, U-0.30 C. DUCTWORK DESIGN CRITERIA (MAXIMUM ALLOWABLE AIR PRESSURE DROPS AND AIR VELOCITIES) TO MEET HIGH EFFICIENCY OPERATION WITH MINIMAL ACOUSTICAL NOISE. DUCT STATIC PRESSURE FRICTION LOSS SHALL NOT EXCEED 0.2" PER 100 FEET IN MECHANICAL ROOMS AND SHAFTS. LOW PRESSURE SUPPLY AND EXHAUST DUCT STATIC PRESSURE FRICTION LOSS BASED ON A MAXIMUM OF 0.08" PER 100 FEET. LOW PRESSURE RETURN DUCT STATIC PRESSURE FRICTION LOSS BASED ON A MAXIMUM OF 0.05" PER 100 FEET. MEDIUM PRESSURE DUCTWORK SHALL NOT EXCEED MAXIMUM VELOCITY AS LISTED BELOW. A. COMMON SPACES MECHANICAL EQUIPMENT: 1. EXISTING AHU IS TO BE REUSED. B. ACOUSTICAL 1. THE FOLLOWING NOISE NC/RC CRITERIA LEVELS WILL BE DESIGNED AS DEFINED IN THE ASHRAE HVAC APPLICATIONS HANDBOOK. THESE LEVELS ADDRESS THE MECHANICAL SYSTEMS ONLY. ACTUAL SOUND PERFORMANCE REQUIREMENTS FOR EACH SPACE MUST BE VERIFIED WITH ACOUSTICAL CONSULTANT. a. CORRIDORS AND LOBBIES: 40 b. OFFICES: 30 City Of Edmonds Building Department Work MECHANICAL FOR T/I Address 21616 76TH AVE W SUITE 202 Owner EDMONDS MEDICALPLAZA Approved Date 7/31/2023 Building Official � c>�isuc Permit Number BLD2023-0767 APPROVED PLANS MUST BE ON JOB SITE ALL WORK SUBJECT TO FIELD INSPECTION FOR CODE COMPLIANCE OBTAIN ELECTRICAL PERMIT FROM STATE LABOR & INDUSTRIES REVISIONS DATE CHANGES REV1 REV2 REV3 REV4 REV5 APPROVED BY PLANNING Jul 21 2023 �/ 1. THE TOTAL INSTALLATION SHALL COMPLY WITH ANY AND REQUIREMENTS OF THE LEGALLY CONSTITUTED AUTHORITIES HAVING JURISDICTION INCLUDING 2019 CBC (CALIFORNIA BUILDING CODE), 2019 CMC/CPC (CALIFORNIA MECHANICAL AND PLUMBING CODE), 2019 CAL GREEN REQUIREMENTS AND THE 2019 TITLE 24 ENERGY CODE. 2. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID AND SHALL THOROUGHLY FAMILIARIZE THEMSELVES WITH THE EXISTING CONDITIONS UNDER WHICH HE WILL BE REQUIRED TO WORK. 3. ALL INDICATED DIMENSIONS ARE APPROXIMATE AND ARE GIVEN FOR ESTIMATE PURPOSES ONLY. BEFORE PROCEEDING WITH THE WORK THIS CONTRACTOR SHALL CAREFULLY CHECK AND VERIFY DIMENSIONS, SIZES, REQUIRED CLEARANCES AND SHALL ASSUME FULL RESPONSIBILITY FOR THE FITTING OF EQUIPMENT AND MATERIALS HEREIN REQUIRED TO OTHER PARTS OF THE WORK OF OTHER TRADES. DUCT DIMENSIONS SHOWN ON PLANS ARE NET INSIDE CLEAR. 4. THE DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC TO THE EXTENT THAT OFFSETS, BENDS, SPECIAL FITTINGS AND LOCATIONS ARE NOT EXACTLY LOCATED. DUCTWORK DIMENSIONS SHOWN ON THE DRAWINGS ARE NET INSIDE DIMENSIONS. DO NOT FABRICATE DUCTWORK FROM THESE DRAWINGS. THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR SUPPLYING SHOP DRAWINGS WHICH REFLECT THE PROPOSED INSTALLATION. THE SHOP DRAWINGS MUST BE APPROVED BY THE ENGINEER PRIOR TO ANY SHEET METAL FABRICATION. THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ACCURATE AS -BUILT DRAWINGS AT THE COMPLETION OF THE PROJECT AND SUBMITTING THEM TO THE ENGINEER AND OWNER. 5. IN THE PREPARATION OF THESE DOCUMENTS, CERTAIN ASSUMPTIONS ARE MADE REGARDING EXISTING CONDITIONS. SOME OF THESE ASSUMPTIONS MAY NOT BE VERIFIABLE WITHOUT EXPENDING ADDITIONAL SUMS OF MONEY OR DESTROYING OTHERWISE ADEQUATE OR SERVICEABLE PORTIONS OF EXISTING BUILDINGS AND/OR EQUIPMENT. THEREFORE, THE ENGINEER SHALL NOT BE HELD RESPONSIBLE FOR ANY CHANGES OR ADDITIONAL COSTS INCURRED DUE TO EXISTING CONDITIONS. 6. THE CONTRACTOR SHALL COMPLY WITH CONTRACT DOCUMENTS IN LAYING OUT HIS WORK AND EQUIPMENT. HE SHALL COORDINATE THE WORK OF THIS SECTION WITH THE WORK OF OTHER TRADES AND JOB CONDITIONS. 7. THE INSTALLATION OF ACCESS PANELS OR OTHER INDICATING EQUIPMENT OR SPECIALTIES REQUIRING READING, ADJUSTMENT, INSPECTION, REPAIRS, REMOVAL OR REPLACEMENT SHALL BE CONVENIENTLY LOCATED WITH REFERENCE TO THE FINISHED BUILDING. 8. WHERE MATERIAL IS SHOWN ON THE DRAWINGS BUT NOT SPECIFIED, IT SHALL BE OF THE SAME TYPE AND QUALITY AS EXISTING MATERIAL. 9. PROVIDE MANUAL VOLUME DAMPERS AT UPSTREAM PORTION OF TERMINAL AIR BRANCHES. THESE SHALL BE OF THE LOCKING QUADRANT TYPE. WHERE LOCATED OVER SLOPED OR HARD CEILINGS, PROVIDE DURO-DYNE ANGLE GEAR DRIVE OR BOWDEN CABLE CONTROL SYSTEM OR PROVIDE UNITED ENERTECH POWER/BALANCE SYSTEM. REMOTE PLATE LOCATIONS TO BE LOCATED AS DETERMINED BY ARCHITECT. 10. PROVIDE MINIMUM 1"ACOUSTICAL LINING IN DUCTWORK WITHIN 10 FEET OF AIR MOVING EQUIPMENT. PROVIDE DURO-DYNE FLEXIBLE CONNECTION AT DUCT AT EQUIPMENT LOCATIONS. 11. DUCTS IN AN UNCONDITIONED SPACE OR EXTERIOR DUCT WORK SHALL HAVE A MIN. OF R-8 INSULATION. DUCTS WITHIN THE CONDITIONED ENVELOPE ABOVE A CEILING SHALL HAVE A MIN. OF R-4.2 INSULATION. EXTERIOR DUCTWORK SHALL NOT HAVE INSULATION EXPOSED TO THE ENVIRONMENT. 12. WHERE NOT SPECIFICALLY INDICATED OTHERWISE, DUCTWORK AND EQUIPMENT SHALL BE SUPPORTED PER THE SMACNA GUIDELINES FOR SEISMIC RESTRAINT AND CURRENT APPLICABLE UNIFORM MECHANICAL CODE. 13. WHEN A FIRE ALARM SYSTEM WITH FULL COVERAGE SMOKE DETECTORS ARE PROVIDED, DUCT SMOKE DETECTORS MAY BE ELIMINATED. FIRE ALARM CONTRACTOR SHALL WIRE SMOKE/FIRE DAMPER ACTIVATORS TO AREA SMOKE DETECTORS. 14. TESTING, ADJUSTING, AND BALANCING (TAB) OF THE AIR CONDITIONING SYSTEMS AND RELATED ANCILLARY EQUIPMENT WILL BE PERFORMED BY A CERTIFIED, INDEPENDENT THIRD PARTY, AABC AGENCY PROCURED BY THE MECHANICAL CONTRACTOR A COMPLETE AIR BALANCE REPORT TO BE SUBMITTED TO THE ADMINISTRATIVE AUTHORITY AND TO THE MECHANICAL ENGINEER AND APPROVED PRIOR TO FINAL PAYMENT. 15. AIR HANDLING DUCT SYSTEMS SHALL BE CONSTRUCTED, INSTALLED AND INSULATED AS PROVIDED IN CHAPTER 6 OF 2019 CMC. 16. MATERIALS EXPOSED WITHIN DUCTS OR PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL HAVE FLAME SPREAD INDEX NOT GREATER THAN 25 AND A SMOKE DEVELOPED INDEX NOT GREATER THAN 50 (2019 CMC SECTION 602.2). 17. ALL DUCTWORK SHALL BE HARD DUCT. FLEXIBLE AIR DUCTS AND CONNECTORS SHALL BE NOT MORE THAN 5' IN LENGTH AND SHALL NOT BE USED IN LIEU OF RIDGED ELBOWS OR FITTINGS. FLEXIBLE AIR DUCTS SHALL BE PERMITTED TO BE USED AS AN ELBOW AT A TERMINAL DEVICE (SEC 603.4.1 CMC). 18. ANY SUBSTITUTION MADE BY THE CONTRACTOR THAT IS DIFFERENT FROM WHAT IS SPECIFIED ON THE DRAWINGS SHALL BE CLEARLY INDICATED ON THE SUBMITTAL AS TO THAT IS BEING SUBSTITUTED. 19. THERMOSTATS SHALL COMPLY WITH THE 2019 ENERGY COMMISSION AND SHALL BE WIFI ENABLED. 20. AT THE TIME OF ROUGH INSTALLATION, OR DURING STORAGE ON THE CONSTRUCTION SITE AND UNTIL FINAL STARTUP OF THE HEATING AND COOLING EQUIPMENT, DUCT AND OTHER RELATED AIR DISTRIBUTION COMPONENT OPENINGS SHALL BE COVERED WITH TAPE, PLASTIC, SHEET METAL OR OTHER METHODS ACCEPTABLE TO THE ENFORCING AGENCY TO REDUCE THE AMOUNT OF DUCT OR DEBRIS WHICH MAY COLLECT IN THE SYSTEM. 21. WHERE MORE THAN ONE HEATING, COOLING, VENTILATING, OR REFRIGERATING SYSTEM IS INSTALLED ON THE ROOF OF A BUILDING OR WITHIN A BUILDING, IT SHALL BE PERMANENTLY IDENTIFIED AS TO THE AREA OR SPACE SERVED BY THE EQUIPMENT. (CMC 303.6) PROVIDE PERMANENT LABELING AND IDENTIFICATION FOR HVAC UNIT (SINGLE SYSTEM OR MULTIPLE) AND THERMOSTATS. IDENTIFICATION FOR THE THERMOSTATS SHALL CORRELATE TO THE HVAC UNIT THAT IT SERVES. 22. AIR CONDITIONING REFRIGERATION SERVICE PORTS LOCATED OUTDOORS SHALL BE FITTED WITH LOCKING TYPE TAMPER RESISTANT CAP OR SHALL BE PROTECTED FROM UNAUTHORIZED ACCESS BY A MEANS ACCEPTABLE TO THE BUILDING DEPARTMENT PER CMC SECTION 1106.14. 23. MECHANICAL CONTRACTOR SHALL REVIEW THE LEED REQUIREMENTS FOR THIS PROJECT PRIOR TO BID AND THROUGHOUT THE CONSTRUCTION TO ENSURE THAT THE REQUIRED LEED DOCUMENTATION'S AND CREDITS ARE ACHIEVED. SYMBOL CD-1 TG CE/CR AIR DISTRIBUTION SCHEDULE DESCRIPTION CEILING DIFFUSER TRANSFER SIDEWALL GRILLE CEILING REGISTER MANUFACTURER & I FINISH MODEL N0. "TITUS" I TO MATCH CEILING MODEL OMNI-AA "TITUS" I TO MATCH CEILING MODEL 25L "TITUS" I TO MATCH CEILING MODEL 50F ACCESSORIES 10 AT ALL HARD LID CEILINGS, CONTRACTOR SHALL PROVIDE FOR "MAT" CABLE DRIVEN DAMPERS. MODEL RT-150. CABLE SHALL BE ROUTED BEHIND GRILLE OPENING AND INSTALLED PER MANUFACTURER'S REQUIREMENTS. MECHANICAL SHEET INDEX SHEET # SHEET NAME M-0.1 MECHANICAL LEGENDS NOTES &SCHEDULES M-0.2 MECHANICAL SCHEDULES M-1.1 MECHANICAL FLOOR PLAN M-2.1 MECHANICAL DETAILS M-3.0 MECHANICAL SPECIFICATIONS SYMBOLS -�®� q r � -- DETAIL No. SHEET No. EQUIPMENT ID. No. �SyS;�'{i5555� HI BD TC MT HVAC LEGEND ABBREVIATIONS I DESCRIPTIONS SQ., RECT., OR ROUND DUCT SIZE AS NOTED DUCT WITH ACOUSTICAL LINER EXISTING DUCT OR EQUIPMENT TO REMAIN EXISTING DUCT OR EQUIPMENT TO BE REMOVED FLEXIBLE DUCT CD � CEILING DIFFUSER, SUPPLY CR / CE � CEILING REGISTER, RETURN /EXHAUST SECTION THROUGH DUCT DUCT DOWN RECTANGULAR TO ROUND TRANSITION DUCT ACCESS DOOR MITERED DUCT ELBOW WITH TURNING VANES SFD COMBINATION SMOKE /FIRE DAMPER WITH ACCESS DOOR MVD MANUAL VOLUME DAMPER, LOCKING QUADRANT TYPE FOR ROUND DUCT OR OPPOSED BLADE TYPE FOR RECT DUCT. SECTION REFERENCE DETAIL REFERENCE EQUIPMENT DESIGNATION AND NUMBER OBD OPPOSED BLADE DAMPER PARALLEL DAMPER T'STAT THERMOSTAT CO2SENSOR CO2SENSOR HUMIDISTAT HUMIDITY INDICATOR BY-PASS TIMER BACK DRAFT DAMPER SWITCH TIME CLOCK MASTER CONTROL STAT DUCT DETECTOR REMOTE SENSOR A.F.F. ABOVE FINISHED FLOOR CFM CUBIC FEET OF AIR PER MINUTE CFMS CFM SUPPLY CFMR CFM RETURN CFME CFM EXHAUST O.S.A. OUTSIDE AIR (E) or EXIST. EXISTING (N) NEW 30"x10" INDICATES RECTANGULAR DUCT SIZE: WIDTH x HEIGHT 12"(� INDICATES ROUND DUCT SIZE: DIAMETER POC POINT OF CONNECTION POD POINT OF DEMOLITION MOTORIZED DAMPER REFR. REFRIGERANT LINES ANCHORAGE AND BRACING NOTES 1. PIPES, DUCTS AND CONDUITS SHALL BE SUPPORTED AND BRACED PER THE 2006 SMACNA "GUIDELINES FOR SEISMIC RESTRAINTS OF MECHANICAL SYSTEMS AND PLUMBING SYSTEMS", THE "SUPERSTRUT SEISMIC RESTRAINT SYSTEM" FOR PIPES AND CONDUITS ONLY. APPLICABLE NOTES 1. BUILDING CODE: 2018 INTERNATIONAL BUILDING CODE WITH WASHINGTON STATE AMENDMENTS 2. PLUMBING CODE: 2018 UNIFORM PLUMBING CODE WITH WASHINGTON STATE AMENDMENTS 3. MECHANICAL CODE: 2018 INTERNATIONAL MECHANICAL CODE WITH WASHINGTON STATE AMENDMENTS 4. ELECTRICAL CODE: 2020 NATIONAL ELECTRICAL CODE (NFPA 70 - 2020) INC. ANNEX A, B, AND C 5. FIRE/LIFE SAFETY: 2018 INTERNATIONAL FIRE CODE WITH WASHINGTON STATE AMENDMENTS 6. ADA AND ACCESSIBILITY GUIDELINES (LATEST EDITION) 7. ASME A17.1 SAFETY CODE FOR ELEVATORS AND ESCALATORS. 8. ENERGY: 2018 WASHINGTON STATE ENERGY CODE t 425.778.1530 21911 76th Ave W. Suite 210 f 425.774.7803 Edmonds WA 98026 info@tg ba rch itects.com www.tg ba rc h itects.co m 110 James St., Suite 106 Edmonds, WA 98020 Phone: 425.458.9700 Fax: 909.890.3770 Email: cadd@designwesteng.com DESIGN WEST ENGINEERING MECHANICAL' ELECTRICAL' ENERGY CONSULTANTS EDMONDS MEDICAL PLAZA - SPEC SUITE 202 216116 76TH AVENUE WEST RESUB EDMONDS, WA 98026 Jul 20 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT MECHANICAL LEGENDS NOTES & SCHEDULES ISSUANCE PROJECT INFORMATION PROJECT NUMBER: 22011 PROJECT LEAD: Designer DRAWN BY: Author SHEET NO ��a ■ 22-101 EXHAUST FAN SCHEDULE FAN SYSTEM TAG MANUFACTURER & AREA TYPE dBA OPER. WT. W/ ANCHORAGE DETAIL REMARKS MODEL NO. SERVED CFM ESP RPM BHP WATTS AMPS V-PH-HZ ACCESSORIES (LBS) REFERENCE (SEE EQUIPMENT NOTES BELOW) EF 1 G SP B9 OCK RESTROOM CEILING MTD. 100 0.75" 1,050 0.07 128 1.8 115-1-60 4.8 20 M21 1 2 3 4 OOOO O COMPLETE WITH BACKDRAFT DAMPER. O EXHAUST FAN TO BE OPERATED BY OCCUPANCY SENSOR. O COMPLETE WITH FAN SPEED CONTROLLER. O EXHAUST FAN TO BE ENERGY STAR RATED. 0 N C N U w N O N N .� .� t6 N (6 d f6 U_ N C O E W 0 N N N O N N .-., ._ (6 N (>S U_ C O W O N N O M Q � Mm O v j MN O� Nw ti� ^o aw � cn ��a t 425.778.1530 21911 76th Ave W. Suite 210 f 425.774.7803 Edmonds WA 98026 info@tgbarchitects.com www.tg ba rc h i tects.co m 110 James St., Suite 106 Edmonds, WA 98020 Phone: 425.458.9700 Fax: 909.890.3770 Email: caddQdesignwesteng.com DESIGN WEST ENGINEERING MECHANICAL' ELECTRICAL' ENERGY CONSULTANTS EDMONDS MEDICAL PLAZA - SPEC SUITE 202 216116 76TH AVENUE WEST EDMONDS, WA 98026 MECHANICAL SCHEDULES ISSUANCE RESUB Jul 20 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT No. Description Date PROJECT INFORMATION PROJECT NUMBER: 22011 PROJECT LEAD: Designer DRAWN BY: Author SHEET NO M-0.2 22-101 c c F c c c i u c r 0 0 0 c z a L G Z Z u C c c c c � n Q M � ti o� ti� M� N IV o� NN �o '•� OW �rn ��a i � T—� � � I / � � I I I�� r r � � �1- I �I -- -- � � i I I I'�-- -I_� � I I DEMO (E) DIFFUSER `� I' I I i (TYP) 12x12 CD E I I I I ) 12"x1 ' I � II I DEMO (E) SUPPLY DISTRIBUTION � �� I I I I AND CONNECTIONS TO (E) DIFFUSERS L (TYP) (E) 12"x12" (E) 12"x12" r� �� " ' 20x20 CR I�I L — J , �.,. — — � — � I I ��( �H I � � �� � 1 1 ��I � I u I I _-1—_—J DEMO (E) SUPPLY DUCTWORK I I � � i �ii I — MIN 12" DOWNSTREAM OF � I � � i� 1 �i � i�i I (E) DUCT HEATER I I I I/ i T U� i �`� it ,� J � �� I I 0 - ,_ - i � Ji r (E) 24"x8' 8x EXAM � ILA' 8x8 CD 150 CFM (E) 16"x1 0 L- 207M 8"x 8x6 TG L��I � �_—J CD CFM 1 1 i � � _ I EXAM I 208 `� i 6x6 CD t L-- --J 70CFM 8x8 CR 8x8 CR � �� � -- I I �_ � � � 8x6 TG 8x6 TG � 10"x10" RETURN DUCT TERMINATION - ABOVE CEILING (8'-6"). PROVIDE SCREENING 14x14 CR EF 1 EXHAUST FAN DUCT TO ROOF. �' PROVIDE DUCT CAP & BACKDRAFT DAMPER. EXHAUST SHALL NOT TERMINATE WITHIN 10' OF ANY MECHANICAL OSA INTAKES. � __� � _r I \ � \ I �"� L - - I JI 1T IJ DW I�-��- 1 2x12CD i -- i � I I 12x12 CD E �� I I � II II II II II JL_ T — I I DEMO (E) RETURN DIFUSSER AND (E) FLECIBLE DUCTWORK AND ASSOCIATEDCONENCTION; RIGID DUCTWORK OPENING POST DEMO IS TO REMAIN UNCAPPED �� � i �\ 29M � � _ 6x6 CD � 70 CFM I � �� � � � . FICE 6"x6 HALLWAY TRANSFER GRILL TO 206 TERMINATE ABOVE CEILING AND BELOW BEAMS (TYP.) TSTAT � 6"x6" � 6"x6" � _ _ � J 6x6 CD 60 CFM 8x6 TG 8x8 CR e Z MECHANICAL DEMOLITION FLOOR PLAN I 1/4" = 1'-0" I 1 1 I`� IJ QVIV�-�=�__� BREAK ROOM 210 I i �� I L — — 6x6 CD � � 80 CFM III I �,� � �, �/� .�. :. 8x6 TG 8x8 CR I� �I � � �6 CD 50 CFM 6"x6" 8"x8" �� I I � � I I L- WAITING 6x6 CD 200 90 CFM MECHANICAL REMODEL FLOOR PLAN L NOT 1. ALL EQUIPMENT, PIPING, DUCTWORKM CONTROLSM AND OR WIRING SHOWN IS A REPRESENATION OF THE ACTUAL SYSTEMS AND IS NOT TO BE CONSIDERED AN AS -BUILT. ALL DIMENSIONS, LOCATIONS, AND QUANTITIES SHALL BE FIELD VERIFIED PRIOR TO COMMENCEMENT OF DEMOLITION OR NEW CONSTRUCTION. 2. UPON REMOVAL OF EXISTING EQUIPMENT, PIPING, DUCTWORK, ETC., THE CONTRACTOR SHALL PATCH ANY EXISTING ROOF, WALL, FLOOR, AND OR CEILING ASSEMBLIES. REFER TO ARCHITECTURAL DEMOLITION DRAWINGS FOR ADDITIONAL INFORMATION AND COORDINATION ITEMS. 3. ALL MATERIALS REMOVED UNDER DEMOLITION PHASE SHALL BE DISPOSED OF OFF SITE. CONSTRUCTION NOTES t 425.778.1530 21911 76th Ave W. Suite 210 f 425.774.7803 Edmonds WA 98026 info@tg ba rch itects.com www.tg ba rc h itects.co m 110 James St., Suite 106 Edmonds, WA 98020 Phone: 425.458.9700 Fax: 909.890.3770 Email: caddQdesignwesteng.com DESIGN WEST ENGINEERING MECHANICAL' ELECTRICAL' ENERGY CONSULTANTS EDMONDS MEDICAL PLAZA - SPEC SUITE 202 216116 76TH AVENUE WEST RESUB EDMONDS, WA 98026 Jul 20 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT MECHANICAL FLOOR PLAN ISSUANCE PROJECT INFORMATION PROJECT NUMBER: PROJECT LEAD: DRAWN BY: SHEET NO 22011 Designer Author 22-101 0 N N_ N O N d) .� N (0 CL (B U m O E W O N N O M Q � M m �i O v ti �� N N O � NW �o OW �� o; � 1/2" 0 HANGER ROD LENGTH AS REQUIRED. (LENGTHS OVER 12" REQUIRE 45 DEG. BRACING AT 2 OPPOSITE CORNERS) 22 GA. G.I. FLASHING. (TYP.) ROOFING UP ALL SIDES BY ROOF CONTR. e (4) EACH UNIT. MAX. 2 INCHES FROM CORNER; (E) STRUCTURE A ,1/11 IAITIAI/'. Arl�/".I/r-T EXHAUST FAN MOUNTING SUPPLY OR RETURN DUCT. SEE PLANS FOR SIZE AND LOCATION. #10 S.M.S. @ 6" O.C. MAX. CAULK &SEAL WATERTIGHT !9ldill�� ROOF CANT STRIP , BY ROOF CONTRACTOR GYP. BOARD CT THR�ROOF :�. System Na. F-C-TD43 0 c us �, ] 6! U-.__�__ � �. a u �+I�Ima rlxuuo-sr Is L � �� 3 3 3 16 `�+� 1G 3 L''J SECTION A -A 1. Flpgr�ilirg As�ern4y—The 1 hrre sled salrl pr truS5ed lurnberpietfl°ar�eiing assem4�'shall4eoarrstrucled �Ihe malerialsard in ire marner speafled n pre irdroidusl L511(I Series Floor•Geiirlg p�asignsn use lJL Fire Res�iance pirectary. Toe galwrala°nstruclion fealures oilhe floor�erllrg assalrply aresurnmarized headw, A. Fldorirr� System—Lulnhernrplyerodd s�fldcr tiim frllsh floor of lurroer, plyunod or Floor Topping MLrlure' as Crfled In the irYdlvldual Floor-Ceiing design. IAaxaraa olopanng af>all ba 143n.2 (923 un2] unlh a maK dmar�dncf 13 in. ]334n•m]. H_Nhod Joist'—Nom 1Un. {25d rnrnj deep{ordaeper] lumber, steel ormmhinalion Ilrnherand sl9eljoisls,1ru55es or St�uctural'Ncud Mernhers'v,;ih hridgng es requred and uilh endsfiesmpped. G. {3y�urn F3pard' —Min S18 n. { 1$ nYn] Ihidr ar«sp9cibed in the indrviduel Fla°r-Gelling Deggn. i3ypgum hpald 9ectrred fd wwd jsisl�or Porrng shenrrelg as spedLred in the irldi�iduEl Fbor�elirg Geaigl. kgix area olopen�9 shall krc id3n.2 i923 em71 uirh a max drrren�on9t 13 in. (aaamrj, 2 Stleel dda —Iklas 12 byr 101n, (505 by 254 mm] Ho-. 28 ga [a heavlerj gals steel dust ro benstalled a+lrercancenMcal�areoxn4ncaywAhin flra9resrop system. The space bM.�een the steel duet and perpfrery of openng shall benirr O In. I;polnt contact] lomax 1 In. (2� rnm]. 51ee1 tluct ld barigidly suppdrtatl dA both sieas dflha flda�eiing assembly. 3. Fieslop5pseem — Mi•r 3rd in. (19 r'nmj Ihickne55 of seelanl applied xulhn the amlilA Fi.l6hwilh Ihei°p aurface of ih911dor_ Min 5�d in. (16 mmj �ricknessaf sealantapplied xilhn the emdus M1rsh with the hot�m surlafle of gypsum hnardaeiling. HILTI GONSTRl1CT14N GI-I�.iIGAG$, pl1,i pF HILTI INS— GP $p$ Fle>aHe Fr�gtpp $ealenkorF$'One Se81ar>f 9r FSQFJE MA3C Inhlrr,e�nl Sealant `Indcaoes each proaacts shall krear8re UL or cUL C+i0fiG80on k�lrk iarjl+isdruliansemployingthe ULordklL Cauon{such as Canada]. resf�cha>?fy, Fdeproduced hryr HILTI, Inc. Ceurteey M Urdervni�r5 Lah°rgtpigg, h� Hilti Firestop System9 January21,2a15 ANSPULrd79 iasrt,, ES'If:l :snN�ULG Sr1S F katlr>Q-1 Hr F Ratng —1 Hr T Ra1ng —1 N Hr FT Ral�g —1 N Hr FH Rang-1 Hr FTH Rarli�g —1la Hr FLOOR/ROOF ASSEMBLY FIRE PENETRATION 7 TYPICAL SQUARE OR RECTANGULARDUCT 45° FOR CONNECTION TO STRUCTURE - REFER TO 2008 SMACNA -� GUIDELINES G.I. DUCT HANGER - SEE SCHEDULE BELOW FOR SIZE #10 SMS (TYP.) 2x2x16GA. G.I. DIAGONAL BRACE ALTERNATE SIDES EVERY HANGER 1"MIN. NOTE: PER 2008 SMACNA HVAC DUCT CONSTRUCTION STANDARDS AND 2019 CMC SECTION 602 & 603 HORIZONTAL HANGER STRAP SCHEDULE DUCT SIZE HANGER SIZE MAX. MATERIAL UP THRU 18" 1" x 18 GA. 10'-0" O/C G.I. STEEL 19" TO 30" 1" x 18 GA. 10'-0" O/C G.I. STEEL 31" TO 48" 1" x 1/8" 10'-0" O/C G.I. STEEL VERTICAL DUCT SIZE HANGER SIZE MAX. SPACING MATERIAL UP THRU 24" 1" x 1/8" STRAP 12'-0" O/C G.I. STEEL 25" TO 36" 1" x 1" x 1/8" ANGLE 12'-0" O/C G.I. STEEL 37" TO 48" 1-1/8" x 1-1/8" x 1/8" ANGLE 12'-0" 0/C G.I. STEEL RECTANGULAR DUCT SUPPORT STRUCTURE 1 1/2" LONG TEK SCREW I IruvvER STRAP (3) STRONGHOLD "J" NAILS MIN. AT EACH WIRE LOOP. 1"MIN. 12 GA. HANGLr\ uvmL LOOPED AND TURNED AS SHOWN AT CONN. TO STRUCTURE. U II"�V VIVl1L UI V"�VL SOD STRUCTURAL MBER 1 1/2"MIN. EQUIPMENT CONNECTION TO STRUCTURE UCT \MPER ROOF HOOD -EXHAUST FAN n 5 12 G.A. DIAGONAL - BRACING WIRE. PROVIDE (4) TIGHT TURNS WITHIN 1-1/2" FROM END 1"x3"L16GA. BENT CLIP SECURED TO CD/CR W/#10 SMS TYP. (2) EACH CD/CR DIAG. 12 GA. WIRE CEILING -REFER — TO ARCHITECTURAL REFLECTIVE CEILING PLAN FLIER PANEL � NOTE: SEAL ALL JOINTS & CONNECTIONS AIR TIGHT W/ APPROVED SEALANT. FOR CONNECTION TO STRUCTURE - REFER TO 2008 SMACNA 2" WIDE x 22 GUIDELINES GA. HANGER STRAP CONTRACTOR TO CONNECT FLEX TO DUCT COLLAR OF PLENUM. COLLAR W (3)#10 SMS W/APPROVED SEALANT t 425.778.1530 21911 76th Ave W. Suite 210 SIDE CONNECTION TO f 425.774.7803 Edmonds WA 98026 PLENUM WHERE CEILING info@tgbarchitects.com SPACE IS LIMITED www.tg ba rc h itects.co m � CEILING DIFFUSER OR REGISTER REFER TO SPECS. FOR MFR.# AND MODEL # GI. PLENUM WITH 1" A.C. LINING SECURE TO CD/CR WITH (4) #10 SMS TYP. CEILING DIFFUSER AIR DISTRIBUTION 1 1 /2" x 1 1 /2" x 16 GA. ANGLES FASTI COLLAR ONLY W/ I SMS AT 8" 0/C FOR WALL SEE ARCH'L. DRWGS. MOUNTING HEIGHT AR LOUVER WITH MIN. 50% FREE AREA SIDEWALL LOUVER � FRONT APPROACH � SIDE APPROACH OVER OBSTRUCTION THERMOSTAT MOUNTING 3 110 James St., Suite 106 Edmonds, WA 98020 Phone: 425.458.9700 Fax: 909.890.3770 Email: cadd@designwesteng.com DESIGN WEST ENGINEERING MECHANICAL' ELECTRICAL' ENERGY CONSULTANTS EDMONDS MEDICAL PLAZA - SPEC SUITE 202 216116 76TH AVENUE WEST EDMONDS, WA 98026 MECHANICAL DETAILS ISSUANCE PROJECT INFORMATION PROJECT NUMBER: PROJECT LEAD: DRAWN BY: SHEET NO M-2.1 RESUB Jul 20 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT 22011 Designer Author 22-101 PART1GENERAL 1.01 SCOPE A. WORK OF THIS SECTION INCLUDES EVERYTHING NECESSARYAND INCIDENTAL TO COMPLETING HEATING, VENTILATING, AND AIR CONDITIONING WORK; EXCEPT AS HEREIN SPECIFICALLY EXCLUDED. 1.02 GENERAL REQUIREMENTS A. ALL CORE DRILLING, CUTTING, AND PATCHING FOR THE INSTALLATION OF WORK UNDER THIS SECTION SHALL BE PERFORMED UNDER THIS SECTION OF THE SPECIFICATIONS. NO HOLES WILL BE ALLOWED IN ANY STRUCTURAL MEMBERS WITHOUT THE WRITTEN APPROVAL OF THE ARCHITECT AND/OR STRUCTURAL ENGINEER. 8. GUARANTEE.' FURNISH A WRITTEN GUARANTEE FORM AS STIPULATED IN SECTION "GENERAL CONDITIONS," FOR A PERIOD OF ONE (1) YEAR FROM DATE OF ACCEPTANCE OF WORK BY THE O WNER. C. MATERIALS: 1. ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND IN PERFECT CONDITION WHEN INSTALLED, OF THE BEST GRADE AND OF THE SAME MANUFACTURER THROUGHOUT FOR EACH CLASS OR GROUP OF EQUIPMENT. MATERIALS NOT IDENTIFIED BYNAME OR MANUFACTURER SHALL BE COMPARABLE TO THAT SPECIFIED AND AS APPROVED BY THE ARCHITECT. MAINTAIN ADEQUATE JOB PROTECTION FOR ALL MATERIALS, EQUIPMENT AND WORK OF OTHER TRADES. STORE ALL PIPE AT LEAST FOUR INCHES (4') ABOVE GRADE TO AVOID CONTACT WITH WATER AND DIRT. 2. UNLESS OTHERWISE DIRECTED BY THE MECHANICAL ENGINEER IN WRITING, OR SPECIFIED OR INDICATED, ALL MATERIALS, AND EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND INSTRUCTIONS. 3. MECHANICAL EQUIPMENT SHALL BEAR THE MANUFACTURER'S LABEL NAMEPLATE SHOWING ALL PERFORMANCE CHARACTERISTICS. ALL VALVES, PIPE FITTINGS, ETC., SHALL BEAR THE MANUFACTURER'S TRADEMARK OR IDENTIFYING MARKINGS. 4. ALL MATERIALS OF SIMILAR FUNCTION OR SERVICE SHALL BE OF ONE MANUFACTURER. D. APPROVAL OF MATERIALS: 1. WITHIN THIRTY (30) DAYS AFTER AWARD OF THE CONTRACT, SUBMIT TO THE ARCHITECT, SIX (6) COPIES OF A COMPLETE LIST OF MATERIAL AND EQUIPMENT PROPOSED FOR THE JOB INCLUDING RATING AND CAPACITY DATA, SIZES, GRADE, ELECTRICAL DATA, PART OR CATALOG NUMBER, MANUFACTURER'S NAME, PICTURES, CATALOG CUTS, ETC. 2. SUBMIT WITH THE ABOVE LIST, SIX (6) COPIES OF COMPLETE SHOP DRAWINGS FOR ALL FABRICATED EQUIPMENT AND SIX (6) COPIES OF COMPLETE CONTROL DIAGRAMS WITH DESCRIPTIONS AND DETAILS. 3. SAFETY COMPLIANCE: ALL MATERIALS, EQUIPMENT AND INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS OF "OCCUPATIONAL SAFETY AND HEALTH ACT" (OSHA) STANDARDS. 4. IF APPROVED BYARCHITECT, DIGITAL SUBMISSION OF SHOP DRAWINGS AND SUBMITTALS MAY BE PROVIDED IN PLACE OF HARD COPIES. E. VERIFICATION OF DIMENSIONS: 1. ALL INDICATED DIMENSIONS ARE APPROXIMATE AND ARE GIVEN FOR ESTIMATING PURPOSES ONLY. BEFORE PROCEEDING WITH THE WORK, THIS CONTRACTOR SHALL CAREFULLY CHECK AND VERIFY ALL DIMENSIONS, SIZES, REQUIRED CLEARANCES AND SHALL ASSUME FULL RESPONSIBILITY FOR THE FITTING OF ALL EQUIPMENT AND MATERIALS HEREIN REQUIRED TO OTHER PARTS OF THE WORK AND TO THE WORK OF OTHER TRADES. 2. THE DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC TO THE EXTENT THAT ALL OFFSETS, BENDS, SPECIAL FITTINGS AND LOCATIONS ARE NOT EXACTLY LOCATED. F. THIS CONTRACTOR SHALL COMPLY WITH ALL CONTRACT DOCUMENTS IN LAYING OUT HIS WORKAND EQUIPMENT. HE SHALL COORDINATE THE WORK OF THIS SECTION WITH THE WORK OF OTHER TRADES AND ALL JOB CONDITIONS. 1. THE INSTALLATION OF VALVES, THERMOMETERS, GAUGES, DAMPERS, DUCT ACCESS DOORS OR OTHER INDICATING EQUIPMENT OR SPECIALTIES REQUIRING READING, ADJUSTMENT, INSPECTION, REPAIRS, REMOVAL OR REPLACEMENT SHALL BE CONVENIENTLYANDRCCESSIBLY LOCATED WITH REFERENCE TO THE FINISHED BUILDING. 2. WHERE WALL AND CEILING ACCESS DOORS ARE REQUIRED FOR ACCESS TO MECHANICAL EQUIPMENT, DOORS SHALL BE FURNISHED AND INSTALLED UNDER OTHER SECTIONS. COORDINATE THIS REQUIREMENT WITH APPROPRIATE SECTION OF SPECIFICATIONS. G. ROUGH -IN.' ROUGH -IN AND FINAL CONNECTIONS SHALL BE PROVIDED FOR EQUIPMENT FURNISHED UNDER OTHER SECTIONS AND BY THE OWNER IN ACCORDANCE WITH ROUGH -IN DRAWINGS FURNISHED BY OTHERS. FUTURE EQUIPMENT, AS NOTED ON THE DRAWINGS, SHALL BE PROVIDED WITH ALL REQUIRED ROUGH -IN UTILITIES. H. MACHINERY GUARDS: ALL MOVING PARTS OF MACHINERY, SUCH AS SHAFT COUPLINGS, BELT DRIVES, ETC., SHALL BE ADEQUATELY COVERED WITH REMOVABLE METAL GUARDS TO PROTECT PERSONNEL FROM POSSIBLE INJURY. GUARDS SHALL BE FURNISHED BY THE EQUIPMENT MANUFACTURER AND SHALL COMPLY WITH APPLICABLE REQUIREMENTS OF APPLICABLE STATE AGENCIES AND OSHA. '_ 0 N U w w N O N N N (6 0_ f6 U_ C O E W 0 N N_ F-- N O N N .� (6 N (E (a U_ N C O E W 0 N N O � � Q � � - M m ti o� �� ti� N N o� tv N j O_ Q W � v MECHANICAL SPECIFICATIONS 8. WEATHERPROOFING 1. GENERAL: WHERE INSULATED PIPING IS EXPOSED OUTDOOR CONDITIONS, IT SHALL BE COVERED. THIS INCLUDES ALL COLD WATER PIPING EXPOSED TO OUTDOORS. 2. COVER OUTDOOR EXPOSED INSULATED PIPING WITH 0.016 INCH THICK CORRUGATED ALUMINUM JACKET. 3. ALUMINUM JACKET SHALL BE SECURED WITH ALUMINUM DRAW BANDS EIGHTEEN INCHES (18') ON CENTER, WITH LONGITUDINAL SEAM OVERLAPPED AND POSITIONED TO SHED WATER. AT CIRCUMFERENTIAL JOINT, PLACE SEALANT AROUND ONE END AND OVERLAP ADJACENT PIECE TWO INCHES (2') AND SECURE WITH ONE HALF INCH (1/2') ALUMINUM HAND. 4. ELBOWS, ALL VALVES, FLANGES, FITTINGS, ETC., SHALL BE COVERED WITH "OWENS CORNING" OR EQUAL COVERS WITH CIRCUMFERENTIAL JOINTS DESCRIBED ABOVE. 2.09 SHEET METAL A. LAYOUT. DRAWINGS ARE IN PART DIAGRAMMATIC AND ARE INTENDED TO CONVEY THE SCOPE OF WORKAND INDICATE THE GENERAL ARRANGEMENT OF EQUIPMENT, DUCTS AND PIPING. MECHANICAL TRADES SHALL FOLLOW THESE DRAWINGS IN LAYING OUT THEIR WORK, CONSULT GENERAL CONSTRUCTION DRAWINGS TO FAMILIARIZE THEMSELVES WITH ALL CONDITIONS AFFECTING THEIR WORK AND SHALL VERIFY SPACES IN WHICH THEIR WORK WILL BE INSTALLED. WHERE JOB CONDITIONS REQUIRE CHANGES IN INDICATED LOCATIONS AND ARRANGEMENT, MAKE SUCH CHANGES AT NO ADDITIONAL COST TO OWNER. 8. DESCRIPTION: INCLUDES SHEET METAL PLENUMS, DUCTWORK, MANUALLY OPERATED DAMPERS AND EQUIPMENT CONNECTIONS. C. MATERIAL: ALL SHEET METAL SHALL BE FABRICATED OF GALVANIZED STEEL. D. LOW PRESSURE DUCT CONSTRUCTION: GAUGES, TRANSVERSE JOINTS, SPACING OF JOINTS AND INTERMEDIATE BRACING SHALL BE AS TABULATED BELOW, IN WHICH TRANSVERSE JOINTS ARE SHOWN SS FOR S-STOP, DS FOR DRIVE SLIP, PS FOR POCKET SLIP, AND BS FOR BAR SLIP. PS AND BS LAPPED AND RIVETED A T CORNERS. INTERMEDIATE BRACING WHERE SHOWN MAY BE OMITTED IF DUCT SECTIONS OF FOUR FEET (4'0') OR LESS ARE USED. MAXIMUM SPACING OF BRACING - FOUR FEET (4'0'J 1. SCHEDULE.' SHAPE SIZE (IN.) GAUGE RECT. UP TO 12 26 RECT. 13 TO 16 24 RECT. 17 TO 18 22 RECT. 19 TO 30 18 RECT. 43 TO 54 22 ROUND 8 &UNDER 26 ROUND 9 TO 16 24 ROUND 16 TO 20 22 2. STIFFENING: PANELS TWENTY INCHES (20') AND LARGER SHALL BE CROSS BROKEN UNLESS STANDING SEAMS ARE USED AND ARE SPACED CLOSER THAN THIRTY SIX INCHES (36'). 3. CHANGES IN DIRECTION AND SIZE. DUCTURNS USED WHERE INDICATED. INDUCTS TWENTY INCHES (20'J WIDE OR LESS, USE BARBER-COLEMAN DUCTURNS OR AS APPROVED. TRANSITIONS WITH LENGTHS NOT SHORTER THAN THOSE SHOWN; MINIMUM LENGTH OF THREE FEET (3'0'J WHERE NOT INDICATED. ROUND ELBOWS SHALL BE OF 4-PIECE CONSTRUCTION. SAME GAUGE AS ADJACENT DUCT. ROUND "WYE" FITTINGS TO HAVE 45 DEGREE SIDE TAKE -OFF TAPPED INTO REDUCING TRANSITION. SEAL ALL JOINTS AS SPECIFIED BELOW 4. JOINTS: AIRTIGHT FOR THE PURPOSE INTENDED. SEAL ALL JOINTS WITH HIGH PRESSURE, FLEXIBLE DUCT SEALANT WITH PRESSURE TESTS TO 10" OF WATER COLUMN. SEALANT SHALL BE AS MANUFACTURED BY "GLENKOTE" OR APPROVED EQUAL. ALTERNATELY, DUCTWORK MAYBE SEALED WITH 6 OZ CANVAS STRIPS AND ARABOL. PITTSBURGH LOCK OR DOUBLE SEAMS EXCEPTED. ARABOL SHALL BE USED FULL STRENGTH WITH NO DILUTION. DUCT TAPE SHALL NOT BE USED. 5. SUPPORTS: DUCTS SECURED AGAINST DISPLACEMENT AND VIBRATION. ANCHOR TO STRUCTURAL PARTS OF BUILDING E. MOTORS AT INTERVALS NOT GREATER THAN TEN FEET (10'0') AND SUSPEND WITH HANGER STRAPS. ALL SUPPORTS SHALL BE PER SMACNA STANDARDS. SUBMIT SHOP DRAWINGS FOR APPROVAL. 1. MOTORS SHALL BE HEAVY DUTY, 1750 RPM, OPEN DRIP -PROOF, HORSEPOWER AND VOLTAGE AS INDICATED ON 6. MANUAL DAMPERS: INSTALL WHERE SHOWN; MANUALLY OPERATED, OPPOSED BLADE DAMPERS WITH INTERLOCKING EQUIPMENT SCHEDULE. EDGES, FABRICATED OF 18 GAUGE STEEL AND EQUIPPED WITH LOCKING QUADRANTS AND END BEARINGS. DURO DYNE 2. MOTORS SHALL BE EQUIPPED WITH PERMANENTLY LUBRICATED, SEALED BALL BEARINGS. SRH-228 DAMPER REGULATORS SHALL BE INSTALLED ON DAMPERS IN LINED DUCT; SRST-L ON WRAPPED DUCT, WITH PROPER OFFSET FOR DUCT INSULATION. EACH DAMPER REGULATOR ROD, DURO DYNE MODEL "SB." SUBMIT SHOP F. FACTORYACCESSORIES DRAWINGS FOR APPROVAL. 7. ALL ROUND "WYE" FITTINGS SHALL INCLUDE A MANUAL VOLUME DAMPER WITH LOCKING QUADRANT. DAMPERS SHALL 1. FANS SHALL BE COMPLETE WITH THE FOLLOWING FACTORYACCESSORIES: BE "DURO DYNE" JDS SERIES OR EQUAL. SUBMIT SHOP DRAWINGS FOR APPROVAL. 8. TURNING VANES IN DUCTS TWENTY INCHES (20') WIDE AND LARGER SHALL BE DOUBLE WALL WITH PERFORATE INNER a. GRAVITY BACKDRAFT DAMPER FACE AND PACKED WITH FIBERGLASS. USE "SONOTURN" OR EQUAL. SUBMIT SHOP DRAWINGS FOR APPROVAL. b. BIRD SCREENS 9. REGISTER BOXES: SHEER METAL REGISTER BOXES SHALL BE PROVIDED FOR ALL CEILING DIFFUSERS AND REGISTERS WITH ROUND DUCT CONNECTIONS. REGISTER BOXES SHALL BE LINED WITH ONE INCH (1'J DUCT LINER AND BE 2.14 EXHAUST FANS (CEILING MOUNTED) (GREENHECK) COMPLETE WITH ROUND STARTER COLLAR, SIZE AS INDICATED ON DRAWINGS. SUBMIT SHOP DRAWING FOR APPROVAL. A. GENERAL 10. FLEXIBLE DUCTWORK SHALL BE "GLASSFLEX" AVC-180 OR EQUAL, UL-181 CLASS 1 AIR DUCT, MATERIAL TESTED AND LABELED WITH A FLAME AND SMOKE RARING OF 25/50 OR LOWER. THE DUCT SHALL HAVE A R-4.5 FIBERGLASS 1. FAN SHALL BE DIRECT DRIVEN, CEILING MOUNTED, WITH CENTRIFUGAL BLOWER. INSULATION AND A 0.17 PERM VAPOR BARRIER. MAXIMUM LENGTH SHALL NOT EXCEED FIVE FEET (5'0'J. SUBMIT SHOP 2. SEE EQUIPMENT SCHEDULE FOR CAPACITIES AND DUTY OF EACH EXHAUST FAN TO BE PROVIDED AND PLANS FOR DRAWINGS FOR APPROVAL LAYOUT DETAILS. 11. THE CONTRACTOR SHALL VERIFY ALL CLEARANCES ON JOB PRIOR TO FABRICATING DUCTWORK. PROVIDE 3. FANS SHALL BE U.L. LISTED AND ALL ELECTRICAL COMPONENTS SHALL CARRY THE LISTING AND COMPLY WITH THE TRANSITIONS AND OFFSETS AS REQUIRED TO INSTALL THE WORKAND COORDINATE ALL CLEARANCES WITH OTHER STATE OF CALIFORNIA ELECTRICAL CODE. TRADES. 4. FANS SHALL BE AS MANUFACTURED BY "LOREN COOK COMPANY," OR APPROVED EQUAL IN "GREENHECK" OR "PENN." 12. PROVIDE "DURO DYNE" MODEL TH-1 INSTRUMENT PORT IN EACH SUPPLYAND RETURN TRUNK FOR EACH SPECIFIED SYSTEM. SUBMIT SHOP DRAWINGS FOR APPROVAL. 8. QUALITYASSURANCE 2.10 DUCT INSULATION A. LINE ALL DUCTWORK WHERE SPECIFIED BELOW WITH ONE INCH (1') 1.5 PCF DENSITY MOISTURE -RESISTANT, FIRE- RESISTANT, GLASS, SOUND ABSORBING DUCT LINER. LINER SHALL BE CEMENTED TO DUCT WITH "3M" #EC-104 ADHESIVE. WHERE WIDTHS OF DUCTS OR CASINGS EXCEED TWENTY INCHES (20'J, BOTH MECHANICAL FASTENERS EIGHTEEN INCHES (18'J ON CENTERS AND ADHESIVE SHALL BE USED. EXPOSED EDGES SECURELY CEMENTED TO PREVENT FRAYING. DIMENSIONS OF DUCTS ARE NET INSIDE LINERS. MANUFACTURER SHALL BE "MANVILLE" LINACOUSTIC R OR APPROVED EQUAL. FLAME SPREAD NOT OVER 25. SMOKE DEVELOPED NOT OVER 50. LINER SHALL MEET ALL OF THE REQUIREMENTS OF NFPA 90A & 908. SUBMIT SHOP DRAWINGS FOR APPROVAL ON METHOD OF FASTENING AND MATERIAL. 1. ALL SUPPLY, RETURN, AND EXHAUST PLENUMS. 2. LINE ALL DUCTWORK FROM INLET OF EXHAUST FANS UPSTREAM FOR A DEVELOPED LENGTH OF TWENTY FEET (20'0') FROM THE FAN. 3. LINE ALL REGISTER BOXES WITH ONE INCH (1') DUCT LINER. 4. IN ADDITIONAL LOCATIONS WHERE SHOWN ON DRAWINGS. 8. WRAP ALL UNLINED DUCTWORK IN UN -INSULATED OR UNCONDITIONED AREAS WITH 1 %", .75 PCF FIRE-RESISTANT MOISTURE RESISTANT FIBERGLASS INSULATION DUCT WRAP. INSULATION PACKAGE SHALL HAVE A FLAME SPREAD RATING OF 25, AND A SMOKE DEVELOPED FACTOR OF 50 AND SHALL MEET ALL OF THE REQUIREMENTS OF NFPA 90A & 90B. DUCT WRAP INSULATION SHALL CONSIST OF A BLANKET OF GLASS FIBERS FACTORY LAMINATED TO A REINFORCED FOIL VAPOR RETARDANT FACING WITH A 2"MIN. STAPLING AND TAPING FLANGE ON ONE EDGE. 1. DUCT WRAP SHALL NOT EXCEED 25% COMPRESSION DURING INSTALLATION AND SHALL CARRY AN R-VALUE OF 4.2 INSTALLED FOR DUCTS WITHIN CONDITIONED ENVELOPE ATTIC SPACE AND AN R-VALUE OF 8.0 FOR DUCTS INSTALLED WITHIN AN UNCONDITIONED SPACE OR AS REGULATED BY THE ENERGY STANDARDS OF TITLE 24. 2. DUCT WRAP SECTIONS SHALL BE TIGHTLY BUTTED TO ADJACENT SECTIONS WITH THE 2"FLAP OVERLAPPING THE ADJACENT SECTION. ALL JOINTS TO BE STAPLED AND TAPED WITH PRESSURE SENSITIVE TAPE MATCHING THE INSULATION FACING, FRK BACKING STOCK OR GLASS FABRIC AND MASTIC. SEAL ALL TEARS, PUNCTURES AND OTHER PENETRATIONS OF THE DUCT WRAP FACING WITH TAPE OR MASTIC TO PROVIDE AVAPOR-TIGHT SYSTEM. 3. INSULATION SHALL BE AS MANUFACTURED BY "OWENS-CORNING, OR EQUAL IN "MANVILLE" OR `ARMSTRONG". 4. DUCT WRAP SHALL BE SECURED WITH #16 SOFT GALVANIZED WIRE, SPACED AT TWELVE INCH CENTERS.. NO RA W EDGES EXPOSED WILL BE ACCEPTABLE 2.11 CEILING DIFFUSERS AND REGISTERS A. PERFORMANCE: 1. DEVICES SHALL PROVIDE THE REQUIRED AIR THROW AND SPREAD WITH NO APPARENT DRAFTS OR EXCESSIVE AIR MOVEMENT WITHIN THE VENTILATED OR AIR CONDITIONED AREA. 2. ALL AIR DISTRIBUTION ACCESSORIES REQUIRED TO AFFECT THESE CONDITIONS SHALL BE PROVIDED AND INSTALLED BY THIS CONTRACTOR. 3. DIFFUSERS, GRILLES AND REGISTERS CAUSING EXCESSIVE AIR MOVEMENT, DRAFTS OR OBJECTIONABLE NOISE SHALL BE REPLACED AT NO COST TO THE OWNER. 8. CEILING DIFFUSERS: 1. DIFFUSERS SHALL BE MODULAR, REMOVABLE CORE TYPE, WITH ADJUSTABLE VOLUME CONTROL DAMPERS. 2. FURNISH DIFFUSERS IN A FACTORYAPPLIED, BAKED ENAMEL FINISH. COLOR AS SELECTED BY THE ARCHITECT. 3. DIFFUSERS SHALL BE AS MANUFACTURED BY "KRUEGER" SERIES 51240 MODULAR ADJUSTABLE AIR DIFFUSERS, ALUMINUM CONSTRUCTION, OR EQUAL IN "NAILOR." OR METAL-AIRE 4. VERIFY FRAME TYPES PRIOR TO ORDERING. SUBMIT SHOP DRAWINGS, INCLUDING COLOR SAMPLES, FOR APPROVAL. 5. PROVIDE IN THE NECK A T EACH DIFFUSER AT DUCT TAKEOFF FROM MAIN DUCT, AN ADJUSTABLE TYPE AIR EXTRACTOR AND VOLUME CONTROLLER. SUBMIT SHOP DRAWINGS FOR APPROVAL. 6. WHERE AIR DISTRIBUTION DEVICES ARE INSTALLED INLAY -IN CEILINGS, TWENTY FOUR BY TWENTY FOUR (24" X 24'J FILLER PANEL SHALL BE PROVIDED. FOR CEILING DIFFUSERS LARGER THAN 24"X 24" (I.E. 30" X 22'), PROVIDE PROPERLY SIZED FILLER PANEL. C. SIDEWALL DIFFUSERS: 1. DIFFUSERS SHALL BE EXTRUDED ALUMINUM LINEAR BAR GRILLES WITH SIZES AS SHOWN ON PLANS. 2. DEFLECTION BARS SHALL BE 15 IN A PERMANENTLY FIXED POSITION. 3. BORDERS SHALL BE 1 "WIDE. 4. GRILLE AND REGISTER SECTIONS SHALL BE FURNISHED IN ONE PIECE UP TO 6 FEET IN LENGTH. 5. BAR GRILLE BORDERS SHALL BE MECHANICALLY FASTENED TO PROVIDE A NEAT HAIRLINE CORNERS. 6. FURNISH ALL GRILLES WITH OPPOSED BLADE DAMPERS. 7. GRILLES SHALL HAVER NATURAL ANODIZED FINISH, AND SHALL BEAS MANUFACTURED BYKRUEGER OR APPROVED EQUAL IN "NAILOR" OR "METAL-AIRE". 8. FURNISH ALL REGISTERS WITH A FACTORYAPPLIED, BAKED ENAMEL FINISH. COLOR AS SELECTED BY THE ARCHITECT. D. RETURN/EXHAUST REGISTERS: 1. REGISTERS SHALL BE ALUMINUM CONSTRUCTION WITH KEY OPERATED, OPPOSED BLADE, VOLUME DAMPERS. 2. FURNISH ALL REGISTERS WITHA FACTORYAPPLIED, BAKED ENAMEL FINISH. COLORAS SELECTED BY THE ARCHITECT. 3. REGISTERS SHALL BE AS MANUFACTURED BY "KRUEGER" MODEL S585, OR EQUAL IN "METAL AIRE" OR "NAILOR" 4. VERIFY FRAME TYPES PRIOR TO ORDERING. SUBMIT SHOP DRAWINGS, INCLUDING COLOR SAMPLES, FOR APPROVAL. 5. WHERE REGISTERS ARE INSTALLED INLAY -IN CEILINGS, TWENTY FOUR BY TWENTY FOUR (24"X 24') FILLER PANEL SHALL BE PROVIDED. FOR RETURN/EXHAUST REGISTERS LARGER THAN 24"X 24" (I.E. 30"X 22'), PROVIDE PROPERLY SIZED FILLER PANEL. 1. EXHAUST FANS SHALL BE DESIGN CERTIFIED BYAMCA. 2. ALL FANS SHALL BE STATICALLYAND DYNAMICALLY BALANCED. C. CONSTRUCTION 1. THE DRIVE FRAME, BEARING, AND MOTOR PLATES SHALL BE CONSTRUCTED OF MILD GAUGE STEEL. D. MOTORS 1. MOTORS SHALL BE HEAVY DUTY, 1750 RPM, OPEN DRIP -PROOF, HORSEPOWER AND VOLTAGE AS INDICATED ON EQUIPMENT SCHEDULE. 2. MOTORS SHALL BE EQUIPPED WITH PERMANENTLY LUBRICATED, SEALED BALL BEARINGS. t 425.778.1530 21911 76th Ave W. Suite 210 f 425.774.7803 Edmonds WA 98026 info@tgbarchitects.com www.tg ba rc h i tects.co m 110 James St., Suite 106 Edmonds, WA 98020 Phone: 425.458.9700 Fax: 909.890.3770 Email: cadd@designwesteng.com DESIGN WEST ENGINEERING MECHANICAL' ELECTRICAL' ENERGY CONSULTANTS EDMONDS MEDICAL PLAZA - SPEC SUITE 202 216116 76TH AVENUE WEST RESUB EDMONDS, WA 98026 Jul 20 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT MECHANICAL SPECIFICATIONS ISSUANCE PROJECT INFORMATION PROJECT NUMBER: PROJECT LEAD: DRAWN BY: SHEET NO M-3.0 22011 Designer Author 22-101