Loading...
APPROVED BLD BLD2022-1587+Plumbing_Plan+11.17.2022_8.13.07_AM+3224969O N 0' c a) U a w N O N a� .5 U) M N n3 0- U 0 m c 0 E w O N N_ N O N U) M N M a m U_ a> 0 0 E w 0 N N O z co Q 2 1-1 o m M tiz N) N N NN N N o" O 2E K PLUMBING FIXTURE SCHEDULE CONNECTION SIZE: TAG SPECIFICATION WASTE I TRAP I VENT I CW WATERCLOSET: KOHLER "HIGHLINE" K-3519 PRESSURE ASSISTED, ADA, 17-1/8" HIGH WC RIM, (1.0 GPF), FLOOR MOUNTED, ELONGATED BOWL, TANK TYPE, WHITE 1 VITREOUS CHINA. KOHLER PLASTIC SEAT MODEL K-4650, ELONGATED, OPEN FRONT, STAINLESS STEEL MOUNTING BOLTS. LAVATORY: KOHLER "CHESAPEAKE" K-1728, WHITE VITREOUS CHINA, WALL HUNG LAVATORY W/ FAUCET HOLES ON CENTERS. CHICAGO FAUCET EQ-Al2C-13ABCP DECK MOUNTED SINGLE HOLE E-TRONIC TRADITIONAL SINK FAUCET WITH BATTERY OPERATED DUAL BEAM INFRARED SENSOR, L CHICAGO FAUCET 131-ABNF-ECAST 1 THERMOSTATIC MIXING VALVE, W/ 0.5 GPM AERATOR, PROVIDE ASSE 1070 APPROVED TMV SET TO 110°, GRID STRAINER DRAIN W/ 1-1/2" CAST BRASS P-TRAP WITH CHROME FINISH, W/ QUARTER TURN ANGLE STOPS. PROVIDE JOSAM 17000 SERIES WALL CARRIER. ON ADA COMPLIANT PROVIDE TRUEBRO LAV GUARD PER ADA CODE 4.19.4 EXAM RM.: KOHLER "STERLING 1411-0", TOP MOUNT OR UNDERMOUNT, 13-5/8" DIA. SINGLE BOWL GAUGE 20 STAINLESS STEEL BOWL, CENTER DRAIN, NO OVERFLOW, MIRROR FINISH. FAUCET: AMERICAN STANDARD 7500-160, TWO -HANDLE CENTER SET LAVATORY FAUCET WITH 6" WRIST BLADE HANDLES, 0.35 GPM WITH V035 S AERATOR. THERMOSTATIC MIXING VALVE 1 605XTMV1070 D. RECOMMENDED ACCESSORIES: KOHLER K-8998 P-TRAP AND KOHLER STERLING 7400 STRAINER. STOP & SUPPLIES: 1/4" TURN ANGLE STOPS WITH RIGID RISER. FURNISH AND INSTALL LAV GUARD #102 TRAP WARP BY TRUEBRO. BREAK RM SINK: ELKAY "LUSTERTONE" LRADQ191865, ADA COMPLIANT, DROP -IN, 191 X 18"W X 6-1/2"D, SINGLE BOWL, GAUGE 18, 304 STAINLESS STEEL, LUSTROUS SATIN FINISH, REAR CENTER 3-1/2" DRAIN. RECOMMENDED ACCESSORIES: KOHLER K-8998 P-TRAP, S LK-99 ELKAY DELUXE 3-1/2" DRAIN TYPE 304 STAINLESS STEEL BODY STRAINER 2 RUBBER SEAL AND TAILPIECE. FAUCET: CHICAGO FAUCETS 1100-G2E3-317AB, 8" FIXED CENTER, 6-1/4" RIGID/SWING GOOSENECK SPOUT, VANDAL PROOF 4" WRISTBLADE HANDLES, CAST BRASS CONSTRUCTION. STOP & SUPPLIES: 1/4" TURN ANGLE STOPS WITH RIGID RISER. FURNISH AND INSTALL LAV GUARD #102 TRAP WARP BY TRUEBRO. THERMOSTATIC MIXING VALVE WATTS MN #LFMMV. SB SERVICE BOX (ICE MAKER): OATEY 39157. 1 1/4" TURN VALVE, CONTRACTOR PACK. FLOOR DRAIN: JOSAM 30002-5A FLOOR DRAIN FD WEJLOC CAST IRON BODY W/CLAMP RING, 1 FLANGE, ADJUSTABLE NIKALOY STRAINER, POLISHED BRONZE GRATE. PROVIDE WITH TRAP PRIMER CONNECTION FOR TP-1. TRAP PRIMER: MIFAB MODEL "MI-300-BP" BATTERY OPERATED TRAP PRIMER, 1/2" TP OUTLET WITH OPTIONAL DISTRIBUTION UNIT, PROVIDE ENCLOSURE AND ACCESS DOOR, 1 MAYBE LOCATED AS INDICATED IN THE DRAWING OR AS REQUIRED BY CODE. UPC LISTED, PROVIDE SHUT-OFF VALVE (CONTRACTOR TO VERIFY). HW I ELEC. 3" 1 INT. 1 2" 1 112" 1 1 - 2" 1 1-1/2" 1 1-1/2" 1 1/2" 1 1/2" 1 - 2" 1 1-1/2" 1 1-1/2" 1 1/2" 1 1/2" 1 2" 1-1/2" 1-1/2" 1 1/2" 1 1/2" 1 1/2" - 2" 2" 1-1/2" I 1 1 1/2" 1 I BATTERY APPROVED PLANS MUST BE ON JOB SITE ALL WORK SUBJECT TO FIELD INSPECTION FOR CODE COMPLIANCE PIPE MATERIAL SCHEDULE PRESSURE SHUT-OFF PIPE MATERIAL TYPE OF SERVICE FITTINGS RATINGS VALVE &WEIGHT JOINTS MATERIAL PSI-SWP COLD WATER CAST BRONZE/ BALL ABV GROUND COPPER L TUBE SOLDERED WROUGHT COPPER 125 GATE CHECK COLD WATER CAST BRONZE/ BALL BELOW GROUND TO COPPER K TUBE BRAZED WROUGHT COPPER 125 GATE 5' OUTSIDE BUILDING COLD WATER BELOW GROUND SCHEDULE 80 PVC SOLVENT- PVC 125 GATE BEYOND 5-0" WELD HOT WATER COPPER L TUBE SOLDERED CAST BRONZE/ 125 BALL ABV GROUND WROUGHT CHECK VENT NO -HUB CAST IRON NO -HUB N/A N/A N/A WASTE, SOIL & SCHEDULE 40 ABS SOLVENT- ABS N/A N/A ROOF DRAINS WELD BELOW GRADE NO -HUB CAST IRON NO -HUB NIA NIA N/A COPPER L TUBE SOLDERED BRONZE 125 N/A WASTE, SOIL & ROOF DRAINS NO -HUB CAST IRON NO -HUB N/A N/A N/A BELOW GRADE CONDENSATE COPPER L TUBE SOLDERED BRONZE 125 N/A PIPE INSULATION SCHEDULE FLUID TEMPERATURE RANGE (7) CONDUCTIVIT Y RANGE (IN BTU-IN/HR PER SQFT/°F) INSULATION MEAN RATING TEMPERATUR E (7) PIPE SIZE (IN. DIA>) < 1 1 to < 1.5 1.5 to < 4 to < 8 8 AND LARGER REQUIRED INSULATION THICKNESS (IN.) HOT WATER SYSTEMS ABOVE 350° 0.32 - 0.34 250° INCHES 4.5 5.0 5.0 5.0 5.0 R-VALUE R-37 R-41 R-37 R-27 R-23 251 ° - 350° 0.29 - 0.32 200° INCHES 3.0 4.0 4.5 4.5 4.5 R-VALUE R-24 R-34 R-35 R-26 R-22 201 ° - 250° 0.27 - 0.30 150° INCHES 2.5 2.5 2.5 3.0 3.0 R-VALUE R-21 R-20 R-17.5 R-17 R-14.5 141 ° - 200° 0.25 - 0.29 125° INCHES 1.5 1.5 2.0 2.0 2.0 R-VALUE R-11.5 R-11 R-14 R-11 R-10 105° -140° 0.22 - 0.28 100° INCHES 1.0 1.5 1.5 1.5 1.5 R-VALUE R-7.7 R-12.5 R-11 R-9 R-8 SIZE 1/2" 3/4" 1" 1-1/4' 1-1/2" 2" 2-1/2" 4" 6" HOT WATER BRANCH LENGTH SCHEDULE PIPE VOLUME AND MAXIMUM LENGTH IS BASED ON 2018 WASHINGTON STATE ENERGY CODE TABLE C404.3.1 NOMINAL PIPE SIZE VOLUME (LIQUID OUNCES PER FT.) MAXIMUM PIPING LENGTH (FT.) PUBLIC LABATORY FAUCETS OTHER FIXTURES AND APPLIANCES 1/2" 1.5 2 43 3/4" 3 0.5 21 1" 5 0.5 13 1-1/4" 8 1 0.5 8 1-1/2" 11 0.5 6 2" & LARGER 18 0.5 4 PLUMBING SIZING FORM PIPE SIZE IS BASED ON 2018 UPC CHART APIPE SIZE IS BASED ON 2018 UPC CHART A 105.1�(a. 3.0 P.S.I. / 100 FT. P.S.I. / 100 FT. FIXTURE UNITS ARE BASED ON 2018 UPC TABLE A 103.1(2) FROM APPENDIX A PIPE SIZE SCHEDULE FIXTURE UNITS FIXTURE UNITS F. TANK F. VALVE GPM VELOCITY 1 0 1.5 2.5 5 0 5 3.2 13 0 10 4.0 24 0 17 4.5 47 10 27 5.0 158 64 56 6.0 380 245 100 7.5 691 630 160 8.0 1,171 1,171 230 8.0 2,000 2,000 321 8.0 NUMBER FIXTURE UNIT TOTAL 1 WATER CLOSET TANK TYPE 2.5 2.5 1 LAVATORY 1 1 4 EXAM RM. SINK 1 4 1 1 BREAK RM. SINK 1.5 1.5 1 SERVICE BOX 0.5 0.5 TOTAL FIXTURE UNITS TOTAL G.P.M. 9•5 14 VELOCITY FOR COLD WATER PIPING LESS THAN 8 FT. PER SECOND VELOCITY FOR HOT WATER PIPING LESS THAN 5 FT. PER SECOND MAXIMUM SIZE FOR HOT WATER PIPING SHALL BE 3" City Of Edmonds Building Department Work PLUMBING FOR T/I Address 76TH AVE W #202 Owner EDMONDS MEDICAL PLAZA Approved Date 11 /29/2022 C&rter Building Official ffr( Permit Number BLD2022-1587 GENERAL NOTES 1. THE TOTAL INSTALLATION SHALL COMPLY WITH ANY AND ALL REQUIREMENTS OF THE LEGALLY CONSTITUTED AUTHORITIES HAVING JURISDICTION INCLUDING 2018 INTERNATIONAL BUILDING CODE (IBC), 2018 INTERNATIONAL MECHANICAL CODE (IMC), 2018 UNIFORM PLUMBING CODE (UPC) WITH WASHINGTON STATE AMENDMENTS AND THE 2018 WASHINGTON STATE ENERGY CODE. 2. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID AND SHALL THOROUGHLY FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONS UNDER WHICH HE WILL BE REQUIRED TO WORK. ALL INDICATED DIMENSIONS ARE APPROXIMATE AND ARE GIVEN FOR ESTIMATE PURPOSES ONLY. 3. BEFORE PROCEEDING WITH THE WORK THIS CONTRACTOR SHALL CAREFULLY CHECK AND VERIFY ALL DIMENSIONS, SIZES, REQUIRED CLEARANCES AND SHALL ASSUME FULL RESPONSIBILITY FOR THE FITTING OF ALL EQUIPMENT AND MATERIALS HEREIN REQUIRED TO OTHER PARTS OF THE WORK OF OTHER TRADES. 4. THE DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC TO THE EXTENT THAT ALL OFFSETS, BENDS, SPECIAL FITTINGS AND LOCATIONS ARE NOT EXACTLY LOCATED. IN THE PREPARATION OF THESE DOCUMENTS, CERTAIN ASSUMPTIONS ARE MADE REGARDING EXISTING CONDITIONS. SOME OF THESE ASSUMPTIONS MAY NOT BE VERIFIABLE WITHOUT EXPENDING ADDITIONAL SUMS OF MONEY OR DESTROYING OTHERWISE ADEQUATE OR SERVICEABLE PORTIONS OF EXISTING BUILDINGS AND/OR EQUIPMENT. THEREFORE, THE ENGINEER SHALL NOT BE HELD RESPONSIBLE FOR ANY CHANGES OR ADDITIONAL COSTS INCURRED DUE TO EXISTING CONDITIONS. 5. ITEMS RELATED TO PLUMBING UTILITIES AND/OR OTHER SERVICE(S); MATERIALS, LABOR, PERMITS, FEES, ETC., SHALL BE VERIFIED WITH THE RESPECTIVE SERVING UTILITY COMPANY PRIOR TO SUBMISSION OF A BID. THE ACT OF SUBMITTING A BID SHALL CONSTITUTE FULL RESPONSIBILITY OF THE CONTRACTOR TO INSTALL SERVICE(S) IN COMPLIANCE WITH THE REQUIREMENTS OF THE SERVING UTILITY COMPANY AND THE MECHANICAL ENGINEER. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CHARGES LEVIED BY THE SERVING UTILITY COMPANY EXCEPTING THE FIRST BILLING DEPOSIT. 6. THE CONTRACTOR SHALL COMPLY WITH ALL CONTRACT DOCUMENTS IN LAYING OUT THEIR WORK AND EQUIPMENT. THEY SHALL COORDINATE THE WORK OF THIS SECTION WITH THE WORK OF OTHER TRADES AND ALL JOB CONDITIONS. 7. THE INSTALLATION OF ACCESS PANELS OR OTHER INDICATING EQUIPMENT OR SPECIALTIES REQUIRING READING, ADJUSTMENT, INSPECTION, REPAIRS, REMOVAL OR REPLACEMENT SHALL BE CONVENIENTLY LOCATED WITH REFERENCE TO THE FINISHED BUILDING. 8. EQUIPMENT AND FIXTURES INSTALLED UNDER THIS CONTRACT SHALL BE HUNG OR ANCHORED IN ACCORDANCE WITH 2018 (IBC) AND 2018 UPC. 9. THE INTENT OF THE DRAWINGS AND SPECIFICATIONS IS TO CONSTRUCT THE PROJECT IN ACCORDANCE WITH 2O18 WASHINGTON STATE ENERGY CODE. 10. WHERE MATERIAL IS SHOWN ON THE DRAWINGS BUT NOT SPECIFIED, IT SHALL BE OF THE SAME TYPE AND QUALITY AS EXISTING MATERIAL. 11. TEST SYSTEM(S) IN ACCORDANCE WITH REQUIREMENTS OF THE GOVERNING AUTHORITIES. 12. CLEANOUTS SHALL BE INSTALLED WHERE READILY ACCESSIBLE AND LOCATED AS PER CODE REQUIREMENTS THE CONTRACTOR SHALL COORDINATE ALL CLEANOUT LOCATIONS WITH EQUIPMENT CABINETS, ETC. AND THE ARCHITECT PRIOR TO ANY INSTALLATION. 13. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND REPAIRING ALL PAVED AREAS WHICH ARE EXCAVATED AND/OR DAMAGED BY THEIR OPERATIONS. IN ADDITION, THE CONTRACTOR SHALL RESTORE TO ORIGINAL CONDITION ALL PLANTED AREAS DAMAGED BY THEIR OPERATIONS. 14. CONNECTIONS TO EXISTING SERVICES SHALL BE MADE SUCH THAT INTERRUPTION TIME WILL BE AS SHORT AS POSSIBLE. THE CONTRACTOR SHALL GIVE THE OWNERS REPRESENTATIVE A MINIMUM OF 72 HOURS NOTICE OF SUCH INTERRUPTIONS AND THE ACTUAL SHUT -DOWN TIME SHALL BE AT A TIME DESIGNATED BY THE OWNERS REPRESENTATIVE. 15. POTABLE WATER SYSTEMS SHALL BE DISINFECTED AND FLUSHED PRIOR TO USE BY WATER -CHLORINATION SOLUTION AND HAVE BACTERIOLOGICAL EXAMINATION MADE BY AN APPROVED AGENCY PER 2018 UPC 609.9 AND AS PRESCRIBED IN AWWA C651. METHODS OF CLEANING/ DISINFECTING FOR NEW OR REPAIR PIPING AS DESCRIBED IN C651 OR NFPA 24. 16. PLUMBING PIPE, FITTINGS AND FIXTURES USED TO CONVEY OR DISPENSE WATER FOR HUMAN CONSUMPTION SHALL BE LEAD-FREE PER 2018 UPC 604.2. 17. ANY SUBSTITUTION MADE BY THE CONTRACTOR THAT IS DIFFERENT FROM WHAT IS SPECIFIED ON THE DRAWINGS NEEDS TO BE APPROVED BY ENGINEER OF RECORD AND OWNER PRIOR TO BID AND SHALL BE CLEARLY INDICATED ON THE SUBMITTAL AS TO ALL THAT IS BEING SUBSTITUTED. 18. SHUT-OFF VALVES SHALL BE PROVIDED IN MAIN BRANCHES, RUNS TO RISERS AND WHERE INDICATED ON DRAWINGS. 19. NEW NON-RESIDENTIAL WATER CLOSETS SHALL COMPLY WITH 2O18 UPC 411.2 AND SHALL NOT EXCEED 1.6 GALLONS PER FLUSH. 20. NEW NON-RESIDENTIAL WALL MOUNTED URINALS SHALL COMPLY WITH 2O18 UPC 412.1 AND SHALL NOT EXCEED 1.0 GALLON PER FLUSH. 21. NEW NON-RESIDENTIAL LAVATORY FAUCETS SHALL COMPLY WITH 2O18 UPC 407.2.1 AND SHALL NOT EXCEED 0.5 GALLONS PER MINUTE FOR PUBLIC LAVATORY AT 60 PSI. 22. FIXTURES, EQUIPMENT, PIPING, FITTINGS, AND MATERIALS SHALL BE LISTED. 23. PLUMBING FIXTURES SHALL MEET THE FLOW REQUIREMENTS SPECIFIED IN THE 2018 UPC. 24. PUBLIC LAVATORIES SHALL HAVE CONTROLS TO LIMIT THE WATER TEMPERATURE TO 120°F. APPLICABLE CODES 1. BUILDING CODE: 2018 INTERNATIONAL BUILDING CODE WITH WASHINGTON STATE AMENDMENTS 2. PLUMBING CODE: 2018 UNIFORM PLUMBING CODE WITH WASHINGTON STATE AMENDMENTS 3. MECHANICAL CODE: 2018 INTERNATIONAL MECHANICAL CODE WITH WASHINGTON STATE AMENDMENTS 4. ELECTRICAL CODE: 2020 NATIONAL ELECTRICAL CODE (NFPA 70 - 2020) INC. ANNEX A, B, AND C 5. FIRE/LIFE SAFETY: 2018 INTERNATIONAL FIRE CODE WITH WASHINGTON STATE AMENDMENTS 6. ADA AND ACCESSIBILITY GUIDELINES (LATEST EDITION) 7. ASME A17.1 SAFETY CODE FOR ELEVATORS AND ESCALATORS. 8. ENERGY: 2018 WASHINGTON STATE ENERGY CODE ANCHORAGE AND BRACING NOTES 1. PIPES, DUCTS AND CONDUITS SHALL BE SUPPORTED AND BRACED PER THE SMACNA "GUIDELINES FOR SEISMIC RESTRAINTS OF MECHANICAL SYSTEMS AND PLUMBING SYSTEMS", THE "SUPERSTRUT SEISMIC RESTRAINT SYSTEM" FOR PIPES AND CONDUITS ONLY. PLUMBING SHEET INDEX SHEET # SHEET NAME P-0.1 PLUMBING LEGEND NOTES & SCHEDULES P-0.2 PUMBING SCHEDULES (CONT) P-1.1 PLUMBING DEMOLITION FLOOR PLAN P-2.2 PLUMBING REMODEL FLOOR PLAN P-3.1 PLUMBING DOMESTIC WATER AND WASTE & VENT RISER DIAGRAMS P-4.1 PLUMBING DETAILS P-4.2 PLUMBING DETAILS (CONT) P-5.1 PLUMBING SPECIFICATIONS P-5.2 PLUMBING SPECFICATIONS (CONT) DATE REV1 REV2 REV3 REV4 REV5 REVISIONS PAGES - CHANi PLUMBING LEGEND SYMBOLS SYMBOL ABBREVIATIONS DESCRIPTION KDETAIL No. SHEET No. KSTACK RISER ID. No. EQUIPMENT ID. No. -GW -CWV RD/OD COND SEC CONS G MPG LPG AS RW CA CA nY VAIJ N2 �3 O �O 0- C- I ICCO DETAIL REFERENCE SECTION REFERENCE PLUMBING STACK OR RISER REFERENCE EQUIPMENT REFERENCE FW FILTERED WATER SCW SOFTENED / CONDITIONED COLD WATER CW COLD WATER HW HOT WATER HWR HOT WATER RETURN POP -OFF DRAIN LINE OR HIDDEN WATER LINE S or W SOIL or WASTE BELOW GRADE (or FLOOR) GW GREASE WASTE BELOW GRADE (or FLOOR) CWV COMBINATION WASTE AND VENT RD/OD ROOF& OVERFLOW DRAIN ABOVE & BELOW GRADE (or SD HE DRAIN S or W SOIL or WASTE ABOVE GRADE (or FLOOR) V PLUMBING VENT COND CONDENSATE DRAIN SEC COND SECONDARY CONDENSATE DRAIN G GAS LOW PRESSURE MPG GAS MEDIUM PRESSURE LPG LIQUID PROPANE GAS AS AUTOMATIC FIRE SPRINKLER RW RECLAIM WATER CA COMPRESSED AIR CAO COMPRESSED AIR OUTLET OX OXYGEN N20 NITROUS OXIDE MA MEDICAL AIR VAC VACUUM N2 NITROGEN BV BALL VALVE SOV SHUT OFF VALVE SOV or GC SHUT OFF VALVE OR GAS COCK ON RISER CV SWING CHECK VALVE PRV PRESSURE REDUCING VALVE PTR PRESSURE -TEMPERATURE RELIEF VALVE RPBFP REDUCED PRESSURE BACKFLOW PREVENTER DN PIPE DOWN UP PIPE UP DN TEE DOWN UP TEE UP PIPE RISER & PIPE DROP (UP AND DOWN) FCO FLOOR CLEANOUT WCO WALL CLEANOUT CO CLEANOUT PLUG COTG YARD CLEANOUT or CLEANOUT TO GRADE CAP ON END OF PIPE HB HOSE BIBB WITH VACUUM BREAKER WHA & TP WATER HAMMER ARRESTOR & TRAP PRIMER CS CIRCUIT SETTER GR GAS REGULATOR GC GAS COCK (or GAS STOP) GS GAS SOLENOID EXISTING PIPING TO BE DEMOLISHED P.O.C. POINT OF CONNECTION P.O.D. POINT OF DEMOLITION AP ACCESS PANEL (WALL AND CEILING) ABV ABOVE BEL BELOW AGA AMERICAN GAS ASSOCIATION CONN CONNECTION CONT CONTINUATION (E) EXISTING (N) NEW DN DOWN ADA AMERICAN DISABILITY ACT IE INVERT ELEVATION (TYP) TYPICAL U.O.N. UNLESS OTHER NOTED VTR VENT THROUGH ROOF W/ WITH FU PLUMBING FIXTURE UNIT SEC COND SECONDARY CONDENSATE B.F.F. BELOW FINISH FLOOR R.I.C. ROUGH IN CONNECT CCO CONDENSATE CLEAN OUT t 425.778.1530 21911 76th Ave W. Suite 210 f 425.774.7803 Edmonds WA 98026 info@tgbarchitects.com www.tgbarchitects.com PRELIMINARY: NOT FOR CONSTRUCTION U Ai* '. f h210077.17` S``,IviV 11, 1,�1s 110 James St., Suite 106 Edmonds, WA 98020 Phone: 425.458.9700 Fax: 909.890.3770 Email: cadd@designwesteng.com DESIGN WEST ENGINEERING MECHANICAL' ELECTRICAL' ENERGY CONSULTANTS EDMONDS MEDICAL PLAZA - SPEC SUITE 202 216116 76TH AVENUE WEST EDMONDS, WA 98026 PLUMBING LEGEND NOTES & SCHEDULES ISSUANCE No. Description Date PROJECT INFORMATION PROJECT NUMBER: 22011 PROJECT LEAD: Designer DRAWN BY: Author SHEET NO RECEIVED Nov 17 2022 CITY OF EDMONDS - EVELOPMENT SERVICES ■ DEPARTMENT 01 22-101 ELECTRIC WATER HEATER SCHEDULE TAG MANUFACTURER & MODEL NO. LOCATION CAPACITY (GAL.) RECOVERY UEF ELECTRICAL DRY WT. (LBS) WET WT. (LBS) DETAIL REMARKS WATTAGE AMPS V-P-HZ WH A.O. SMITH DEL-30 STORAGE RM. 30 69 GAL./HR. @ 72 DEG. TEMP. RISE 0.92 12,200 59 208V-10-60Hz 118 368 P 4 2 O NOTES: O WET WT. INCLUDES UNIT AND TANK CAPACITY EXPANSION TANK SCHEDULE CAPACITY ACCEPTANCE MAX MAX. TEMP SYSTEM DIMENSIONS (IN.) DRY WET TAG SYSTEM MANUFACTURER & LOCATION (GAL.) VOLUME PRESSURE (OF) CONNECTION WT. WT. DETAIL REMARKS DIA. HT. MODEL N0. GAL. (GAL.) PSI (PSI) IN. ( ) LBS. (LBS.) LBS. (LBS.) 1T DOMESTIC WATER WATTS MODEL #DETA 5 STORAGE RM. 3.5 2.3 150 200 3/4 10 14 21 51 P 4 2 9 NOTES: U WET WT. INCLUDES UNIT AND TANK CAPACITY CIRCULATOR PUMP SCHEDULE TAG SYSTEM MANUFACTURER & MODEL NO. LOCATION CAPACITY CONSTRUCTION MOTOR (HP) ELECTRICAL WEIGHT (LBS) DETAIL REMARKS AMPS V-P-HZ CP WH-1 TACO 007-SF5 STORAGE RM. 1.5 GPM @ 5' TDH STAINLESS STEEL 1/25 0.76 120V-10-60Hz 7 P 42 O N ry O C N U 0- w N O N N U) M N 0- f6 U_ 7-5 U 70 C O E 70 w O N N_ F-- N O N N U) M N 0- (a U_ 0 N U) C O E w 0 N N O c) Q � o — ti m M tiM N N oC5 � N j o" O t 425.778.1530 21911 76th Ave W. Suite 210 f 425.774.7803 Edmonds WA 98026 info@tgbarchitects.com www.tgbarchitects.com PRELIMINARY: NOT FOR CONSTRUCTION �O°%��,L r � 21007747 `1111Eg�� �S<4IONA1, 110 James St., Suite 106 Edmonds, WA 98020 Phone: 425.458.9700 Fax: 909.890.3770 Email: cadd Ebdesignwesteng.com DESIGN WEST ENGINEERING MECHANICAL' ELECTRICAL' ENERGY CONSULTANTS EDMONDS MEDICAL PLAZA - SPEC SUITE 202 216116 76TH AVENUE WEST EDMONDS, WA 98026 PUMBING SCHEDULES (CONY) ISSUANCE PROJECT INFORMATION PROJECT NUMBER: PROJECT LEAD: DRAWN BY: 22011 Designer Author SHEET NO RECEIVED Nov 17 2022 CITY OF EDMONDS - VELOPMENT SERVICES DEPARTMENT 22-101 J CD N ry O C N U w w N O N N a --I U) (6 N f6 d f6 7-5 U_ N fn 70 C O E 70 w O N N F-- N O N N U) (6 N 0_ (a U_ N U) C O E w 0 N N O co Q � o — ti m M N N oNj tv N j j o" O II Y II I II I II I 0 II j ----- L__ <. I II IA - -- fir -- —� Imo r= I I I II I/ I I IIQ IT I I I I Ir I� II II II I� �I II II II II PLUMBING DEMOLITION FLOOR PLAN GENERAL NOTES 1. FOR LINE TYPES, SYMBOLS & ABBREVIATIONS SEE LEGEND ON SHEET P-0.1. 2. CONTRACTOR SHALL PATCH FLOORS, WALLS & CEILINGS TO MATCH NEW CONSTRUCTION PER ARCHITECTS SPECIFICATIONS. 3. PRIOR TO CONSTRUCTION CONTRACTOR SHALL FIELD VERIFY FOR EXACT SIZES, LOCATIONS & INVERT ELEVATIONS OF EXISTING WASTE LINES & COORDINATE WITH PLUMBING ENGINEER FOR ANY CHANGES NEEDED. 4. REMOVE ALL EXPOSED PLUMBING PIPES, VALVES AND EQUIPMENT. CAP AT POINT OF TERMINATION. CONSTRUCTION NOTES 1O REMOVE (E) SINK, (E) CW & HW ABOVE CEILING AND (E) WASTE & VENT CAP WASTE ABOVE FLOOR SLAB AND VENT ABOVE CEILING. 2O REMOVE (E) RESTROOM WATER CLOSET AND LAVATORY, (E) CW & HW ABOVE CEILING AND (E) WASTE & VENT. CAP WASTE ABOVE FLOOR SLAB AND VENT ABOVE CEILING. < (E) CW, HW & HWR MAINS AND (E) W & V MAINS TO REMAIN. t 425.778.1530 21911 76th Ave W. Suite 210 f 425.774.7803 Edmonds WA 98026 info@tgbarchitects.com www.tgbarchitects.com PRELIMINARY: NOT FOR CONSTRUCTION �77'4� ��A ��SIONA1,� 1 10 James St., Suite 106 Edmonds, WA 98020 Phone:425.458.9700 Fax: 909.890.3770 Email: cadd@designwesteng.com DESIGN WEST ENGINEERING MECHANICAL' ELECTRICAL' ENERGY CONSULTANTS EDMONDS MEDICAL PLAZA - SPEC SUITE 202 216116 76TH AVENUE WEST EDMONDS, WA 98026 PLUMBING DEMOLITION FLOOR PLAN ISSUANCE PROJECT INFORMATION PROJECT NUMBER: 22011 PROJECT LEAD: DRAWN BY: SHEET NO p=1 Designer Author RECEIVED Nov 17 2022 CITY OF EDMONDS EVELOPMENT SERVICES DEPARTMENT 22-101 O N O C N U a w N O N N co (6 N f6 0- 0 E w O N N_ 1— N O N N U) (6 N (0 0- (>S U_ O 75 U) C O E w O N N O c Q � M - ti m M ;~ rn N� N CD N �V N o" W 2E K PLUMBING REMODEL DOMESTIC WATER FLOOR PLAN PLUMBING REMODEL WASTE & VENT FLOOR PLAN GENERAL NOTES 1. FOR LINE TYPES, SYMBOLS & ABBREVIATIONS SEE LEGEND ON P-0.1. 2. FOR CONNECTION TO STRUCTURE & PIPE SUPPORT, SEE DETAILS 1, 2, 3 & 4 ON SHEET P-4.1. 3. UNLESS NOTED ALL CW & HW RISERS FROM FIXTURE TO CEILING ARE 1/2", SEE FIXTURE SCHEDULE ON P-0.1. 4. ROUTE HOT WATER LOOP AS CLOSE AS POSSIBLE TO ALL FIXTURES. 5. SEE FIXTURE SCHEDULE ON P0.01 FOR ADA & STANDARD RIM HEIGHTS FOR WATER CLOSETS. 6. NEW OR REPAIRED POTABLE WATER SYSTEMS SHALL BE DISINFECTED PRIOR TO USE, ACCORDING TO THE METHOD SET IN SECTION 609.9 OF THE 2018 UPC. 7. CONTRACTOR SHALL PATCH FLOORS, WALLS & CEILINGS TO MATCH NEW CONSTRUCTION PER ARCHITECTS SPECIFICATIONS. 8. SHUT-OFF VALVES SHALL BE PROVIDED ON ALL MAIN BRANCHES, RUNS TOO RISERS AND WHERE SHOWN ON DRAWING. LOCATE SHUT-OFF VALVES OVER T-BAR CEILING WHEN POSSIBLE. PROVIDE ACCESS PANELS WHEN SHUT-OFF VALVES ARE LOCATED OVER HARD LID CEILINGS. 9. CONTRACTOR SHALL PATCH FLOORS, WALLS & CEILINGS TO MATCH NEW CONSTRUCTION PER ARCHITECTS SPECIFICATIONS. 10. PRIOR TO CONSTRUCTION CONTRACTOR SHALL FIELD VERIFY FOR EXACT SIZE, LOCATION & INVERT ELEVATION OF EXISTING WASTE LINE & COORDINATE WITH PLUMBING ENGINEER FOR ANY CHANGES NEEDED. 11. FOR CEANOUTS, SEE DETAIL 5 P-4.1 12. FOR PIPES THRU RATED WALL, SEE DETAIL 6 P-4.1 13. FOR WATER HEATER, SEE DETAIL 1 P-4.2 14. FOR CIRCULATOR PUMP, SEE DETAIL 2 P-4.2 15. FOR TRAP PRIMER, SEE DETAIL 3 P-4.2 ®= CONSTRUCTION NOTES Z 1O SET CIRCUIT SETTER AT 0.5 GPM. O2 2" W DN TO BELOW. 1 /T" = 11-011 1 O3 3" W DN TO BELOW. 4O ISOLATION AND CHECK VALVE INSTALLED IN VERTICAL. O5 1/2" HW TO DISWASHER. O6 WASTE FROM DISHWASHER. 4 " 0 0 4p 1 IV t 425.778.1530 21911 76th Ave W. Suite 210 f 425.774.7803 Edmonds WA 98026 info@tgbarchitects.com www.tgbarchitects.com PRELIMINARY: NOT FOR CONSTRUCTION ()LE oil WAs 21007747 w ��GISTEg�� � LSIONAL ���dw 1 10 James St., Suite 106 Edmonds, WA 98020 Phone:425.458.9700 Fax: 909.890.3770 Email: cadd@designwesteng.com DESIGN WEST ENGINEERING MECHANICAL' ELECTRICAL' ENERGY CONSULTANTS EDMONDS MEDICAL PLAZA - SPEC SUITE 202 216116 76TH AVENUE WEST EDMONDS, WA 98026 PLUMBING REMODEL FLOOR PLAN ISSUANCE PROJECT INFORMATION PROJECT NUMBER: PROJECT LEAD: DRAWN BY: SHEET NO 22011 Designer Author RECEIVED Nov 17 2022 CITY OF EDMONDS - VELOPMENT SERVICES ■ DEPARTMENT 22-101 0 N U a w N 0 N U) (6 N f6 d U 0 E Lu N N E- N O N 0 U) co (0 0- a) 7- 0 0 E w 0 N N O c Q � �n — ti m M ;~ rn N N cV N j o" 2E K 314" HWR- (1.5 GPM) 112" CW--,, (0 F.U.) 314" CW- (1 F.U.) 314" HW (0.75 F.U.) II WH 1 S 1 TP 112" CW 1 (2.5 F.U.) 314" CW (1 F.U.) 314" HW 314" HWR (1.5 F.U.) (0.75 F.U.) o 314" CW ,o� �314" CW (I F.U.) >0000"\� (2 F.U.) �314" HW(0.75 F.U.) S 1 —1" HW CW 314" HWR \ \ S 314" CW \ (0.5 GPM) \ 1 314" HW (1.875 F.U.) 112" CW CP (1 F.U.) 1 314" HWR II 314" (E) HWR (0.75 F.U.) II 314 (E) HW II 1 114" (E) CW� \ we L 1 1 314" HW (3.25 F.U.) 314" CW- (3.5 F.U.) i h 0 2„V i II (2 D.F.U.) i 11/2"V �� II (1 D.F.U.) II 2 V S II (2.5D.F.U.)�I 2" W (1 D.F.U.) i II II CI 2"V--,� II (3 D.F.U.) �I WCO I I I I 3 W II \ II (3.5 D.F.U.) \ �I L II 3" W- (2.5 D.F.U.) we 1 WCO FLOOR PENETRATION, - (TYP.) WCO 3„ (E) V W (2 D.F.U.) 4" (E) W 1 D.F.U. e2' W( ) W (1 D.F.U.) 314" CW- (0.75 F.U.) 314" HW--,,, (1 F.U.) S 1 _S 2 HW(2.25 F.U.) CW (3 F.U.) DISHWASHER (1.5 F.U. CW) (1.125 F.U. HW) 2" V (3 D.F.U. � II 11/2"V II II / 1112"V(2D.F.U.) (1 D.F.U.)�I I✓ S II II 1 II jj SS II II / \ 2 / DISHWASHER (2 D.F.U.) WCO —2" W (4 D.F.U.) (1 D.F.U.) 2" W"2'"W (5 D.F.U.) e� WASTE &VENT RISER DIAGRAM 112" CW (0.5 F.U.) e DOMESTIC WATER RISER DIAGRAM 2 - t 425.778.1530 21911 76th Ave W. Suite 210 f 425.774.7803 Edmonds WA 98026 info@tgbarchitects.com www.tgbarchitects.com PRELIMINARY: NOT FOR CONSTRUCTION COLE oil 21007747 w GISTEg�� � �SSIONAL E��S 1 10 James St., Suite 106 Edmonds, WA 98020 Phone:425.458.9700 Fax: 909.890.3770 Email: cadd@designwesteng.com DESIGN WEST ENGINEERING MECHANICAL' ELECTRICAL' ENERGY CONSULTANTS EDMONDS MEDICAL PLAZA - SPEC SUITE 202 216116 76TH AVENUE WEST EDMONDS, WA 98026 PLUMBING DOMESTIC WATER AND WASTE & VENT RISER DIAGRAMS ISSUANCE No. Description Date PROJECT INFORMATION PROJECT NUMBER: PROJECT LEAD: DRAWN BY: SHEET NO 22011 Designer Author RECEIVED Nov 17 2022 - ■ CITY OF EDMONDS EVELOPMENT SERVICES DEPARTMENT 22-101 0 N ry c a) U a w N 0 N 2 .5 U) co N n3 U a) 15 0 c 0 E w _o N CV 1- N 0 N 2 U) co N ca a U m 75 0 0 E w 0 N N O M Q 10 1-1 m M �z C-171 N CD R, j o" O 2E K COVER INSTALL PER 2018 UPC (SEC. 707.0 & 719.0) FINISH FLOOR COVER PLATE FINISH FLU FCO OR COTG WASTE 2% SLOPE �- PIPE CLAMP (TYP.) 3/4" THICK ACRYLONITRILE BUTADIENE POLYVINYL CHLORIDE (AB/PVC) FLEXIBLE FOAM INSULATION PIPE 1/2" MIN BEAD OF CID 25WB+ CAULK CLEANOUT FIRE RATED FRAMED WALL CID 25WB+ CAULK ON BOTH SIDES OF WALL PIPE PENETRATION THRU RATED WALL 5 THREADED HANGER STRUCTURE ROD. FOR SIZE AND FOR CONNECTION SPACING SEE 2 TO STRUCTURE /BE 1 1/2" LONG S"TEK" SCREW SADD VERTICAL ANGLE S STIFFENER IF LENGTH GREATER THAN MAX LENGTH SHOW ON PIPE SUPPORT SCHEDULE NUT & WASHER - TOP & BOTTOM "B-LINE" - B3690 ADJUSTABLE "J" HANGER PIPING. SEE PLANS FOR SIZE AND LOCATION INSULATION WHERE - APPLIES SEE SPECIFICATIONS NOTE: "B-LINE" B3162 PIPE SADDLE TRANSVERSE ANGLE BRACE. ALTERNATE SIDES EVERY BRACE. 1. DETAIL APPLIES TO PIPES 2" I.D. AND SMALLER 2. REFER TO PIPE SUPPORT SCHEDULE FOR ADDITIONAL INFORMATION FOR CONNECTION TO STRUCTURE SEE LONGITUDINAL DIAGONAL ANGLE (SLOPE 1 TO 1). FOR SIZE AND SPACING 0 SEE SCHEDULE. ALT. SIDES EACH BRACE. ATTACH BOLT - SEE SCHEDULE FOR SIZE "B-LINE" B327 SHORT ANGLE INSULATION - SEE SPECIFICATIONS TYPICAL PIPE - SEE PLAN FOR SIZE AND LOCATION PIPE SUPPORT (SMALL PIPES) ADD VERTICAL ANGLE STIFFNER IF LENGTH IS GREATER THAN MAX. LENGTH SHOWN ON PIPE SUPPORT SCHEDULE HANGAR ROD - SEE 2 SCHEDULE FOR SIZE TRANSVERSE ANGLE BRACE. ALTERNATIVE SIDES EVERY BRACE. PIPE SLEEVE WITH I.D. 1/4" LARGER THAN O.D. OF BOLT "B-LINE" B3100 CLEVIS HANGAR - SEE SCHEDULE FOR SPACING 2 "B-LINE" B3162 PIPE SADDLE NOTE: 1. DETAIL APPLIES TO PIPES 2-1/2" I.D. AND LARGER. PIPE SUPPORT (LARGE PIPES) 3 1/2"0 HANGER ROD (TYP) STRUCTURE 1 1/2" LONG "TEK SCREW" 2 1 /2"x2 1 /2"A 6 GA. ANGLE BRACE (TYP) CONNECTION TO WOOD STRUCTURE CONNECTION TO STUCTURE MAXIMUM SPAN O O 0 PIPE BETWEEN HANGER MAX. VERTICAL TRANSVERS SIZE SUPPORT ROD LENGTH LONGITUDINAL HANGER E BOLT IN HANGERS O.C. DIAMETER FOR RODS ANGLE BRACE ANGLE ANGLE SIZE INCHES HORIZ. VERT SIZE (STIFFENER) BRACE COPPER TUBE &PIPE 1/2 & 3/4 6-0" 10'-0" 3/8" 37" 1-1/2 x 1-1/2 x 18 1 x 1 x 18GA 1-1/2 x 1-1/2 x 18 3/8" GA 80'-0" O.C. GA 40'-0" O.C. THRU 1-1/ 6-0" 10'-0" 3/8" 37" 1-1/2 x 1-1/2 x 18 1 x 1x 18GA 1-1/2 x 1-1/2 x 18 3/8" GA 80'-0" O.C. GA 40'-0" O.C. 2 10'-0" 10'-0" 3/8" 37" 1-1/2 x 1-1/2 x 18 1 x 1 x 18GA 2-1/2 x 2-1/2 x 16 3/8" GA 40'-0" O.C. STEEL PIPE FOR GAS 1/2 & 3/4 6' 0" 6' 0" 3/8" 37" 1-1/2 x 1-1/2 x 18 1 x 1 x 18GA 1-1/20-1/2 1-1/2 x 18 3l8" GA 80'-0" O.C. GA 40'-0" O.C. 1 8'-0" 8'-0" 3/8" 37" 1-1/2 x 1 1/2 x 18 1 x 1 x 18GA 1-1/2" x 1-1/2 x 18 3/8" GA ' " 80-0O.C. GA ' 40-0" O.C. 1-1/4 THRU 10'-0" 10'-0" 3/8" 37" 2 1/2 x 2 1/2 x 16 1 x 1 x 18GA 2-1/2 x 2-1/2 x 16 3/8" GA a�80'-0" O.C. GA 40'-0" O.C. SCHEDULE 40 PVC& ABS DWV & 3/4 4' 0" 10' 0" 3/8" 37" 1-1/2 x 1-1/2 x 18 1 x 1x 18GA 1 1/2 x 1 1/2 x 18 3/8" 71/2 GA @ 40'-0" O.C. THRU 2 4' 0" 10' 0" 3/8" 37" 1-1/2 x 1-1/2 x 18 1 x 1 x 18GA 1-1/2 x 1-1/2 x 18 3/8" GA 80'-0" O.C. GA 40'-0" O.C. CAST IRON HUBLESS NO HUB 1 1/2 & 2 AO 160" 3/8" 37" 1-1/2 x 1-1/2 x 18 1 x 1 x 18GA 1-1/2 x 1-1/2 x 18 3/8" GA 80'-0" O.C. GA 40'-0° 3 THRU 6 O REFER TO SMACNA GUIDELINES IN SCHEDULE BELOW OSUPPORT EVERY JOINT. SUPPORT SHALL BE WITHIN 18 INCHES OF JOINT ON BOTH SIDES. (SUPPORT ALSO REQUIRED AT EACH HORIZONTAL JOINT CONNECTION) ALL PIPING 2-1/2" AND LARGER PER THE FOLLOWING SMACNA GUIDELINES 2-1/2 10'-0" x 16 3/8" 10'-0" 1/2" 25" 2-1/2 x 2-1/2 x 16 2 x 2 x 16GA 2-1/2740'-0" GA @ 80' 0" O.C. GA O.C. 3 10' 0" 10' 0" 1/2" 25" 2-1/2 x 2-1/2 x 16 2 x 2 x 16GA 2-1/2 x 2-1/2 x 16 3/8" GA 80'-0" GA @ 40'-0" O.C. 4 10'-0" 10'-0" 5/8" 31" 2-1/2 x 2-1/2 x 16 2 x 2 x 16GA 2-1/2 x 2-1/2 x 16 1/2" GA @ 80'-0" O.C. GA 40'-0" O.C. 2-1/2 x 2-1/2 x 16 2-1/2 x 2-1/2 x 16 5 10'-0" 10'-0" 5/8" 31" GA 80'-0" O.C. 2 x 2 x 16GA GA 40'-0" O.C. 1/2" 2-1/2 x 2-1/2 x 16 2-1/2 x 2-1/2 x 16 6 10'-0" 10'-0" 5/8" 37" GA 40'-0" O.C. 2 x 2 x 16GA GA 40'-0" O.C. 1/2" NOTES 0) VERTICAL ANGLE ONLY REQUIRED WHEN ROD MAXIMUM LENGTH IS EXCEEDED. O BRACING MAY BE OMITTED WHERE TOP OF PIPE IS 12" OR LESS FROM BOTTOM OF HANGER SUPPORT CONNECTED TO STRUCTURE O ALLOW FOR EXPANSION EVERY 30'-0" PIPE SUPPORT SCHEDULE 2 t 425.778.1530 21911 76th Ave W. Suite 210 f 425.774.7803 Edmonds WA 98026 info@tgbarchitects.com www.tgbarchitects.com PRELIMINARY: NOT FOR CONSTRUCTION 21007747 w IST 0 � %tIL_&IONAL E��S 1 10 James St., Suite 106 Edmonds, WA 98020 Phone:425.458.9700 Fax: 909.890.3770 Email: cadd@designwesteng.com DESIGN WEST ENGINEERING MECHANICAL' ELECTRICAL' ENERGY CONSULTANTS EDMONDS MEDICAL PLAZA - SPEC SUITE 202 216116 76TH AVENUE WEST EDMONDS, WA 98026 PLUMBING DETAILS ISSUANCE PROJECT INFORMATION PROJECT NUMBER: PROJECT LEAD: DRAWN BY: SHEET NO P=4m 22011 Designer Author RECEIVED Nov 17 2022 CITY OF EDMONDS EVELOPMENT SERVICES DEPARTMENT 22-101 O N Ir C m U a LL 75 F N O N a� .j U) M N f0 0- a) U C O E w 0 N N N O N a) U) co N (0 0- m U_ am O E Lu 0 N N 2E K R CHECK VALVE 12 GA. SPLAY WIRE, ATTACH TO METAL DECK W/ #10 SMS FOR CONNECTION TO CW 1/2" CW INLET STRUCTURE CW TO SUPPLY ATER HEATER "B" F ELECTRONIC CONTROLLER C.W. SUPPLY � H.W. SUPPLY ET BALL VALVE (TYP.) 1 UNION (TYP.) ADJUSTMENT DIALS I C.W. CONNECTION H.W. CONNECTION VACUUM RELIEF VALVE H.W. RETURN INSTALL PER LOCAL CODES S.S. SOLENOID 1" AIR GAP T&P RELIEF SECURE W/H TO WALL WITH 1" WIDE - MIN. 20 VALVE DISCHARGE TO GA. SHEET METAL STRAP & ATTACH TO METAL LOW LEAD COPPER I JANITORS SINK STUD BACKING PER 1/AD-1.0 W/ #10 SMS EA. MANIFOLD BRASS MI -GAP 3/4" OVERFLOW END. PER UPC SEC. 508.0 - 508.2 TO FLOOR DRAIN WATER HEATER WH FS FD OR SET AT 120E 1 F L ------------- 1 1 k66P DRAIN VALVE TRAP PRIMER LINE FLOOR CONNECTIONS WATER HEATER SHELF AS MANUFACTURED 1/2" CW BY HOLDRITE MFG MODEL 50-SWHP-W SECURE TO METAL STUD BACKING PER 1/AD-1.0 W/ #12 SMS EA. HOLE IN BRACKET PIPE ANCHOR 0 PROVIDE 6" WASTE AIR GAP FLOOR DRAIN TRAP PRIMER CONNECTION 3 WATER HEATER 1 LOCATION OF ANCHORS - PLAN VIEW SEE DETAIL BELOW CID PUMP MOUNTING 3" MIN. � BRACKET EMBEDMENT BY PUMP MFR. 4" CONCRETE PAD 0 SECURE PUMP TO CONC. W/ FRONT VIEW (4) "HILTI" - KWIK BOLTS 1/2"0 x 3" MIN. EMB. (TYP 2 EA. BRACKET) CIRCULATOR PUMP SUPPORT 2 t 425.778.1530 21911 76th Ave W. Suite 210 f 425.774.7803 Edmonds WA 98026 info@tgbarchitects.com www.tgbarchitects.com PRELIMINARY: NOT FOR CONSTRUCTION �2tOO77�47�&IONAL 110 James St., Suite 106 Edmonds, WA 98020 Phone: 425.458.9700 Fax: 909.890.3770 Email: cadd@designwesteng.com DESIGN WEST ENGINEERING MECHANICAL' ELECTRICAL' ENERGY CONSULTANTS EDMONDS MEDICAL PLAZA - SPEC SUITE 202 216116 76TH AVENUE WEST EDMONDS, WA 98026 PLUMBING DETAILS (CONY) ISSUANCE No. Description Date PROJECT INFORMATION PROJECT NUMBER: 22011 PROJECT LEAD: Designer DRAWN BY: Author SHEET NO RECEIVED Nov 17 2022 CITY OF EDMONDS - VELOPMENT SERVICES ■ DEPARTMENT 22-101 0 N ry c a) U a Lu 7. N 0 N a� U) N N f6 0- U a) 5 c 0 E w _o N N_ N 0 N a� U) M N M 0- a) 5 0 E Lu 0 N N O Z M Q N - ti m M ;~ rn NN) N N 00 N N o" v PART 1 GENERAL 1.01 SCOPE A. Work of this section includes everything necessary and incidental to completing plumbing work, except as herein specifically excluded. 1.02 GENERAL REQUIREMENTS A. All core drilling, cutting, and patching for the installation of work under this section shall be performed under this section of the specifications. No holes will be allowed in any structural members without the written approval of the Architect. B. Guarantee: Furnish a written guarantee form as stipulated in section "General Conditions," for a period of one (1) year from date of acceptance of work by the owner. 1. Materials: a. All material and equipment shall be new and in perfect condition when installed, of the best grade and of the same manufacturer throughout for each class or group of equipment. Materials not identified by name or manufacturer shall be comparable to that specified and as approved by the Architect. Maintain adequate job protection for all materials, equipment and work of other trades. Store all pipe at least four inches (4") above grade to avoid contact with water and dirt. b. Unless otherwise directed by the Mechanical Engineer In writing, or specified or indicated, all materials, fixtures and equipment shall be installed in accordance with manufacturers recommendations and instructions. c. Plumbing equipment shall bear the manufacturer's label nameplate showing all performance characteristics. All valves, pipe fittings, etc., shall bear the manufacturer's trademark or identifying markings. d. All materials of similar function or service shall be of one manufacturer. 2. Approval of Materials: a. Within thirty (30) days after award of the contract, submit to the Architect, six (6) copies of a complete list of material and equipment Proposed for the job including rating and capacity data, sizes, grade, electrical data, part or catalog number, manufacturer's name, pictures, catalog cuts, etc. b. Submit with the above list, six (6) copies of complete shop drawings for all fabricated equipment and six (6) copies of complete wiring diagrams with descriptions and details. c. Safety Compliance: All materials, equipment and installation shall comply with the requirements of "Occupational Safety and Health Act" (OSHA) Standards. C. Verification of Dimensions: 1. All indicated dimensions are approximate and are given for estimating purposes only. Before proceeding with the work, this contractor shall carefully check and verify all dimensions, sizes, required clearances and shall assume full responsibility for the fitting of all equipment and materials herein required to other parts of the work and to the work of other trades. 2. The drawings are essentially diagrammatic to the extent that all offsets, bends, special fittings and locations are not exactly located. 3. This contractor shall comply with all contract documents in laying out his work and equipment. He shall coordinate the work of this section with the work of other trades and all job conditions. 4. The installation of valves, thermometers, gauges, cleanouts, water hammer arrestor access doors or other indicating equipment or specialties requiring reading, adjustment, inspection, repairs, removal or replacement shall be conveniently and accessibly located with reference to the finished building. 5. Where wall and ceiling access doors are required for access to plumbing equipment, doors shall be furnished and installed under other sections. Coordinate this requirement with appropriate section of specifications. D. Rough -In: Rough -in and final connections shall be provided for equipment furnished under other sections and by the owner in accordance with rough -in drawings furnished by others. Future equipment, as noted on the drawings, shall be provided with all required rough -in utilities. E. Before submitting his bid for the work under this division the contractor shall carefully study all drawings and shall make a careful examination of the premises. He shall determine in advance, the methods of installing and connecting the equipment, the means to be provided for getting the equipment into place and shall make himself thoroughly familiar with all the requirements of the contract. After award of the contract, no subsequent allowances will be made to the contractor due to the failure to comply with the above requirements or any other conditions affecting the installation and completion of the work. F. Any minor changes in work, which have not been installed, shall be made by this contractor without additional compensation except changes which increase or decrease the size of the materials specified or indicated on the drawings. This contractor shall submit an estimate of the cost, or credit for, such changes he does not consider of a minor nature and shall proceed only upon the written authorization of the Engineer. G. Machinery Guards: All moving parts of machinery, such as shaft couplings, belt drives, etc., shall be adequately covered with removable metal guards to protect personnel from possible injury. Guards shall be furnished by the equipment manufacturer and shall comply with applicable requirements of applicable state agencies and OSHA. PART 2 PRODUCTS 2.01 PIPING INSTALLATION A. Arranged as shown on the drawings and as required for a complete system. B. Run straight and true to line and as direct as possible. C. Risers shall be plumb. Form right angles on parallel lines with building wall. D. Keep pipes close to walls and partitions, off -set only where necessary to follow walls, or as directed. E. Locate groups of pipes parallel to each other. Pipe spacing shall permit application of full insulation and access for servicing valves. F. All piping shall be isolated from other piping, any part of the building, framing, conduit, etc., with one inch (1") strips of hair, felt, or pipe isolators. G. Risers shall not have couplings in runs from one floor outlet to next. H. All piping shall be concealed in walls or above ceilings unless otherwise noted. I. Street elbows, bushings, and long screw fittings will not be allowed for on -site buildings. J. Cleanouts 1. Floor cleanouts, as specified (see plans for size), shall be no -hub and installed into pipe where shown on plans. Floor cleanouts shall be accessible in all cases and shall be brought to surface on "WYE" branches. 2. Wall cleanouts, as specified (see plans for size), shall be taper thread plugs and installed into pipe where shown on plans. Wall cleanouts shall be accessible in all cases. 3. All cleanouts shall be provided with removable floor or wall plate as hereinbefore specified. 4. Cleanouts to grade shall be provided with either a traffic rated brass cap or concrete yard box. K. Install stops on all hot and cold water fixture supplies, unless integral stops are specified. Supply trim shall have all metal -to -metal connections. L. Protect open pipe ends. Keep piping free from scale and dirt; protect open ends whenever work is suspended during construction to prevent foreign bodies entering and lodging there; use temporary plugsl or other approved material for protection. M. Bending or mitering of pipe to constitute fittings shall not be permitted. 2.02 DOMESTIC HOT AND COLD WATER PIPING SYSTEM A. AMains, risers, branches, connections of sizes and arrangement as indicated on drawings. B. Shut-off valves shall be provided in main branches, runs to risers and where indicated on drawings. C. Piping below grade shall be dipped and wrapped with "Hunt's Process" No. HP#6-F. All field joints and fittings shall be double wrapped with "Scotch Wrap" No. 50. In lieu of wrapping, "X-Tru-Coat" steel pipe shall be considered an approved equal. D. Joints under concrete slabs, if allowed by local codes, shall be brazed. 2.03 SOIL, WASTE, AND VENT PIPING SYSTEMS (CAST IRON PIPING) A. Mains, risers, branches and connections of sizes and arrangement as indicated on drawings. B. All waste, vent sewer and storm lines shall be cast iron soil pipe and fittings and shall conform to ASTM A-888 or ASTM A-74 and the requirements of CISPI Standard 301 for all pipe and fittings. Pipe and fitting shall be marked with the collective trademark of the Cast Iron Soil Pipe Institute or receive prior approval of the engineer. Refer to section 3.01 for submittal requirements. C. Cast iron soil pipe and fittings below grade shall be service weight no -hub type. 1. Shall be no -hub service weight using no -hub coupling assembly, all stainless steel (#304) coupling. a. One and one half (1 1/2"), two inch (2"), three inch (3" ), four inch (4"), diameter coupling shall consist of a three inch (3") wide corrugated 304 stainless steel shield in conjunction with four (4) stainless steel clamps mounted in series, secured in place by means of a fixed and "floating" eyelet to allow clamp travel during tightening. b. For five inch (5"), six inch (6"), eight inch (6"'), and ten inch (10"), shall consist of a four inch (4.") wide corrugated 304 stainless steel shield in conjunction with six (6) stainless steel clamps mounted in series, secured in place by means of a fixed and "floating" eyelet to allow clamp travel during tightening. c. All HUSKY Series 4000 couplings, or approved equal, shall be installed using a factory preset torque wrench, set to 80 inch - pounds. D. Above grade piping and vent line shall be service weight cast iron with no -hub joints. E. Vent piping may be schedule 40 galvanized steel in lieu of item 2.03, C. F. Cleanouts shall be provided as previously specified and in the following locations: 1. Near bottom of each stack and riser. 2. At every 135 degree change of direction for horizontal line. 3. Every one hundred feet (100') horizontal run. G. Extend cleanouts to accessible surface. Do not place cleanouts in carpeted floors. In such locations, use wall -type cleanouts. H. Each fixture and appliance discharging water into sanitary sewer or building sewer lines shall have a seal trap in connection with a complete venting system so gasses pass freely to atmosphere with no pressure for siphon condition on water seal. I. Vent entire system to atmosphere. Discharge fourteen inches (14") above roof. Join lines together in fewest practical number before projecting above roof (see plans for locations) . Offset vent lines so they will not pierce roof near an edge or valley. J. Use torque wrench to obtain proper tension in cinch bands when using hubless cast iron pipe. Butt ends of pipe against centering flange or coupling. K. Grade all soil and waste lines at one quarter inch (1/4") fall per foot, indirection of flow; unless otherwise noted on plans (see plans for other locations) 2.04 SOIL, WASTE, AND VENT PIPING SYSTEMS (ABS) A. Mains, risers branches and connections of sizes and arrangement as indicated on drawings. B. ABS soil pipe and fittings shall comply with ASTM D2661 85a or ASTM F628 85. 1. Piping shall be black in color and have a pipe wall thickness the same as that of Schedule 40 (IPS) standard steel pipe. 2. Pipe shall be marked on two sides, 180 degrees apart or spirally, in letters not less than 3/16" high in a contrasting color, and shall contain the following information: a. Mfgr's name or trademark b. ASTM designation c. Nominal pipe size d. Symbol ABS-DWV or COEX ABS FOAMED CORE DWV e. Mfgr's code f. IAPMO certification C. Above grade piping and vent line shall also be ABS piping. D. Exposed vents thru roof shall be protected by water base synthetic latex paints. E. Cleanouts shall be provided as previously specified and in the following locations: 1. Near bottom of each stack and riser. 2. At every 135 degree change of direction for horizontal line. 3. Every one hundred feet (100') horizontal run. F. Extend cleanouts to accessible surface. Do not place cleanouts in carpeted floors. In such locations, use wall -type cleanouts. G. Each fixture and appliance discharging water into sanitary sewer or building sewer lines shall have a seal trap in connection with a complete venting system so gasses pass freely to atmosphere with no pressure for siphon condition on water seal. H. Vent entire system to atmosphere. Discharge fourteen inches (14") above roof. Join lines together in fewest practical number before projecting above roof (see plans for locations) . Offset vent lines so they will not pierce roof near an edge or valley. I. Use torque wrench to obtain proper tension in cinch bands when using hubless cast iron pipe. Butt ends of pipe against centering flange or coupling. J. Grade all soil and waste lines at one quarter inch (1/4") fall per foot, indirection of flow; unless otherwise noted on plans (see plans for other locations). 2.05 UNIONS A. Provide unions, screwed or flanged, where indicated and In the following locations: 1. In by-passes around equipment. 2. In connection to traps, heaters, tanks, pumps and other equipment requiring disconnection for repairs or replacement. Locate between shutoff and equipment. 3. Where access panels for unions and valves in walls, partitions and ceilings are required. Coordinate this requirement with the General Contractor. B. For two Inches (2") and smaller pipe, use screwed unions; for two and one half Inches (2 1/2") and larger use flanged. C. For steel pipe, use malleable iron unions, 150 PSI SWP for standard pipe and 250 PSI SWP for extra strong pipe, with bronze - to -iron ground joints by Grinnell Company, or approved equal; or cast iron flanged unions gasket type by Grinnell Company, Fig 487, or approved equal. D. For threaded brass pipe use flanged bronze unions with steel bolts and gasket for 150 PSI SWP, Walworth Company No. 3480, or approved equal; or bronze ground joint unions with octagon ends for 200 PSI SWP, Walworth Company No. 3477, or approved equal. 2.06 CONCEAL PIPING: A. Where indicated or specified, conceal piping in building construction. Install such piping in time so as not to delay work of other trades and to allow ample time for tests and approval; do not cover before test approval is obtained from the Engineer. B. Run up branches passing through floor or roof into partition; offset above floor close to equipment unit; expose only as much as necessary for final connection. C. Where furred spaces are indicated, keep pipes as close to structural members as possible so as to require minimum furring. In case of furred beams, obtain approval, from Architect, of resulting headroom clearance before installing pipes. D. Access panels: Install where shown and over all concealed valves, cleanouts, isolation unions and any concealed equipment which may require access for operation, maintenance and repair. Panel shall be sized for proper service and be not less than twelve Inches by twelve inches (12" x 12"), furnished and installed by this contractor. 2.07 PIPES PIERCING WATERPROOFING: A. For pipes passing through waterproofed floor or roof, provide sleeves and flashing to maintaining watertight condition. Submit details for approval. 2.08 CHECK FOR INTERFERENCES WITH OTHER TRADES A. Before installing piping, check architectural, structural, plumbing, electrical and fire protection drawings. Make accurate layout of all piping, including installed elevations. Submit copies of final layout to other trades for coordination with their work so that grouped pipes, conduit, and ducts will not interfere with each other, or with full swing doors and will leave minimum headroom as indicated. B. Coordination of the mechanical piping Is the responsibility of this section. C. Protect open pipe ends. Keep piping free from scale and dirt. Protect open ends whenever work is suspended during construction to prevent foreign bodies entering and lodging there; use temporary plugs, burlap, or other approved material for protection. 2.10 SUPPORTS, HANGERS, FLASHING, AND SEISMIC RESTRAINT A. Pipe Support 1. All piping shall be supported in such a manner that it is securely attached to the structure of the building. Attachment is to be capable of supporting the tributary weight of pipe and contents in any direction. Maximum spacing of support and braces shall be as detailed on drawings. 2. Support horizontal overhead piping with clevis hangers. Upper end of hanger rod shall be supported from a code approved attachment. See drawings for pipe support details. Submit shop drawings of all piping supports for approval. 3. Piping shall be attached to top chord members only of prefabricated roof or floor trusses. Where plywood web trusses occur, pipe support may be secured to additional web stiffeners as shown on plans. B. Flashing: Pipes through roof shall be flashed with "Semco" No. 1110-7 steel reinforced boot type, six (6) pound seamless lead flashing with suitable counter -flashing sleeve, or as approved by the Architect. Submit shop drawings for approval. C. Seismic Restraint: All piping and equipment shall be suitably restrained and anchored in both horizontal and vertical directions to withstand seismic forces as required by the State of Washington. See drawings for details. 2.11 PIPES OVER ELECTRICAL EQUIPMENT A. Where pipe joints or valves in cold and hot water lines occur within two feet (2'0") in horizontal direction from electrical panels, or equipment, provide a drip pan of size which will afford protection. Submit pan size and construction for approval. B. Pans shall be 18 GA. GI sheet, edges turned up two and one half inches (2 1/2") all sides, reinforced with galvanized angles or by rolling edge over one quarter of an inch (1/4") diameter galvanized wire. C. Provide drain with three quarters of an inch (3/4") galvanized flange and galvanized pipe drain to nearest floor sink. D. Support with galvanized bars or angles, brace to prevent sagging or swaying, as detailed for ductwork. 2.12 ASTM DESIGNATIONS FOR PIPE AND FITTING MATERIALS A. Pipe, as specified in schedule, shall conform to requirements covered by following ASTM designations: 1. Copper Tube "B": B-75. 2. Copper Tube "K" and "L-: B-88. 3. Cast Iron Waste: A-74 or A-888. 4. Schedule 80 PVC 5. ABS Waste: D2661-85a B. Fittings, as specified in schedule for various services, shall conform to requirements covered by the following ASTM designations: 1. Malleable Iron: A-197. 2. Bronze, Solder Joint: B-88. 3. Wrought Copper, Solder Joint: ANSI B16.22, B16.18. 4. ABS: D2661-85a & D3311-82 2.13 MANUFACTURERS OF PIPE AND FITTINGS A. All pipe and fittings shall be "U.S." manufactured. Pipe manufacturer shall be submitted for approval. The following manufacturers shall be acceptable for materials listed under each group: 1. Copper Tubing and Fittings a. Muller Brass b. Chase c. Revere d. Cerro 2. Cast Iron Pipe a. Alhambra b. Anaheim Foundry c. U.S. Pipe and Foundry d. Universal Cast Iron Manufacturing 2.14 PIPE JOINTS A. Unless otherwise specified, join pipe as follows: 1. All steel pipe two inches (2") and smaller shall have screwed joints. 2. All steel pipe two and one half inches (2 1/2") and larger shall have welded joints. 3. All copper pipe shall have soldered joints made with 95-5 tin/antimony solder. 4. Galvanized vent pipe shall be screwed "Durham" tarred drainage fittings. 5. All joints In underground and under -floor distribution piping shall be welded, regardless of size. 6. All ABS piping shall have solvent welded joints. B. Welding Exceptions: In locations such as risers in shafts or mains in crowded corridors, where welding may be difficult; permission may be given by job inspector or Mechanical Engineer to use screwed joints up to four inch (4") size. C. Welding Process, Procedure: 1. Where welding is required by work of this section, such work shall only be performed by welders qualified and certified by a recognized, approved agency. Such certification shall bear a date not more than six (6) months prior to date of starting work under this section and shall be submitted and approved by the job inspector and Mechanical Engineer prior to starting work. 2. Pipe welding shall comply with the latest revision of applicable code, ASA Code for Pressure Piping and State requirements. Before welding Is performed, contractor shall submit to the Mechanical Engineer evidence of compliance of welding and operator's qualification according to provisions of governing codes. Standard Procedure Specifications and operators qualified by National Certified Pipe Welding Bureau shall be considered as conforming to requirements of these specifications. 3. Use only welding type fittings and welding neck flanges. The following exceptions may be used, only as approved by the Mechanical Engineer: a. Join "small" branches into mains with intersection weld, instead of using welding type tee. "Small" shall mean that the branch is one size less than half the size of the main which it intersects as: 1 1/4" branch into 3" main; 1 1/2" branch Into 4" main; 2" branch into 6" main; 4" branch into 10" main. b. Use only "Weldolet" of "Threadolet" type of welding fittings for intersection welding of branches to mains. 4. Do not make direct welded connections to valves, expansion joints, strainers, apparatus, other equipment; which are intended to be removable. 5. Brass piping shall have screwed joints for sizes two inches (2"); flanged for two and one half inches (21/2") and larger. D. Brazing Option: Brazing of threadless brass pipe to bronze fittings with pre -inserted rings, will be acceptable in place of screwed joints. 1. For brazing joints on threadless brass pipe and copper "B" tube, copper tube type "K" and "L," use brazing alloy„ 80% copper, 15% silver, 5% phosphorous, which will flow freely at 1300 F; Handy and Harmon "Sil-Fos," or approved equal; use flux and brazing method recommended by manufacturer of brazing alloy. 2. Copper tube type "K" and "L" shall have soldered or sweated joints with solder -joint type or copper fittings. Flared joints with flare type bronze fittings may be used where approved for specific service. Solder shall be 95-5 or equal. 3. Do not make brazed or soldered connections to valves, expansion joints, strainers, apparatus, other units, which are intended to be removable. E. Screwed Joints: 1. For screwed joints use red or white lead and oil, or approved pipe joint compound; apply only on male threads. 2. Brass pipe shall have screwed joints, for sizes two inches (2") and under; flanged two and one half (2 1/2") and over. 3. Cut pipe, nipples evenly, cut threads clean, remove burrs, ream ends to full inside bore. Cut brass pipe with hack saw rather than with pipe cutter. 4. Do not use Stulson Wrench for making brass pipe joints tight; such pipe, bearing wrench marks, will not be acceptable and shall be replaced at Contractor's own expense. F. Joints of Dissimilar Metals: Provide with "EPCO" dielectric valves isolation couplings of same size as pipe. G. Pipe Preparation: 1. Pipe shall be carefully cleaned before installation. The ends of threaded pipe shall be reamed out full-size with a long taper reamer so as to be partially bell -mouthed and perfectly smooth. 2. All threads on black steel pipe shall be cut with new clean dies, full thickness of the die and so that no more than two (2) threads are left exposed on the pipe when the joint is made up in the fitting or valve. 3. Copper, brass pipe and chromed, polished or painted. connections from fixtures shall show no tool marks. Install with approved wrenches. 4. Thread lubricant shall be used for all threaded joint make-up and shall be applied to the make thread only. Lubrication shall include threaded cleanout plugs. 2.15 PIPE FLANGES A. Flanges of same weight as fittings in same service category; drilled for 150 PSI service. B. Screwed flanges shall be cast iron. C. Welded flanges shall be steel welding neck type. 2.16 GASKETS A. Gaskets for pipe flanges shall be ring type, one sixteenth inch (1/16") thick, of compressed fiber and special compound, suitable for service intended. B. Factory cut for 125 lb. flange size, "Durable Mfg. Co.," Durable Series. C. Garlock 122. "Garlock Packing Co.," for hot and cold water. D. Rubber gaskets for cast iron pipe shall meet the requirements of ASTM A 74-80. 2.17 PIPE SLEEVES, ESCUTCHEONS, COVERS A. Furnish and set sleeves to accommodate pipes passing through foundations, walls, floors, partitions, roof; provide escutcheons at exposed finished surfaces pierced by pipes. B. Any pipe passing through a wall of a vertical shaft or through a wall of an occupancy separating or floor shall pass through a 16 GA G.I. sleeve. After pipe has been installed through sleeve, remaining space shall be packed tightly with an inert packing and secured on each side of wall with a 16 GA escutcheon around pipe. Submit shop drawings for approval. 2.18 VALVE TYPES A. General: For valve location and installation, refer to "Valves" under "Piping Installation" herein and the drawings. B. Valve Requirements: Unless otherwise indicated or specified for particular system or individual equipment, following requirements shall apply-- 1 . Valves, General: Designed for packing under pressure with valve open or closed. 2. Valves used for throttling of controlling flow: Globe type as indicated; for shut off use butterfly or ball type as indicated. 3. Ball valves on all cold water and hot water piping unless otherwise noted. 4. Valves shall have rating of not less than 125 PSI SWP or as indicated in service schedule. 5. Valve Material: Bronze for sizes two inches (2") and smaller. 6. Valve ends: Screwed for all sizes two inches (2") and smaller, except copper tube. 7. Valve ends for copper tubes, Type K and L: Solder joint type. 8. Flange valves shall have flange drilling to suit joining pipe flanges. 9. Gate valves shall have solid tapered wedge, except where otherwise specified. t 425.778.1530 21911 76th Ave W. Suite 210 f 425.774.7803 Edmonds WA 98026 info@tgbarchitects.com www.tgbarchitects.com PRELIMINARY: NOT FOR CONSTRUCTION �!0, , U j� f 210077.17� n 0 .tin >> 110 James St., Suite 106 Edmonds, WA 98020 Phone: 425.458.9700 Fax: 909.890.3770 Email: cadd@designwesteng.com DESIGN WEST ENGINEERING MECHANICAL' ELECTRICAL' ENERGY CONSULTANTS EDMONDS MEDICAL PLAZA - SPEC SUITE 202 216116 76TH AVENUE WEST EDMONDS, WA 98026 PLUMBING SPECIFICATIONS ISSUANCE PROJECT INFORMATION PROJECT NUMBER: PROJECT LEAD: DRAWN BY: 22011 Designer Author SHEET NO RECEIVED Nov 17 2022 CITY OF EDMONDS P= 5ml EVELOPMENT SERVICES DEPARTMENT 2E K 22-101 O N ry c a� U a W N 0 N 2 73 U) M N M 0- U m c 0 E w _o N N_ N O N a� U) co N (0 0- 0 E Lu 0 N N O M Q � N 1-1 m M ;~ rn tiZ NC-Ti N N 0CD INJ N N o" v 10. Globe type valves shall have renewable composition discs recommended by manufacturer for intended service, or renewable bevel seat and metal disc where so specified. 11. Check valves shall be horizontal swing type with bronze seat and composition or bronze disc as approved; body of same material, pressure rating, screwed or flanged, finish as adjoining globe or gate valve. Check valves in pump discharge lines shall be of the spring loaded non -slam type as manufactured by "Mission" Duo Check Series 150-S-M-F. A. Submit complete shop drawings and catalog cuts of all valve types to be used, for review and approval by Mechanical Engineer, prior to installation. No Exceptions. 2.19 VALVE CATALOG NUMBER DESIGNATIONS A. Valve design, material of components, workmanship, other features: Equal to "Stockham Valve Company" catalog numbers (unless otherwise noted) for various types of valves listed. B. Gate Valves 1. Screwed, bronze, union bonnet, rising stem, 150 PSI SWP; NO. B-120. 2. Screwed, ibbm, non -rising stem, 125 PSI SWP; NO. G608. 3. Flanged, ibbm, non -rising stem, 125 PSI SWP; NO. G461. 4. Flanged, ibbm, OS & Y, 125 PSI SWP; NO. G-623. C. Ball Valves 1. Screwed two inches (2") and smaller, cast bronze body, 40 PSI WOG, "Apollo 3" Series 82. 2. Valves shall include reinforced Teflon packing ring, thrust seal, body seals and seats. 3. Balls shall be chromium plated bronze; with full size ports. 4. Quarter turn on -off, adjustable packing gland and internally inserted stem. 5. 21/2" and larger: "Powell" 150 PSI; flanged ball valve Fig. 4226T with 316 stainless steel (SS) body and 316 55 ball and stem with Teflon seat. D. Globe and Angle Valves 1. Screwed, bronze, composition, 150 PSI SWP; B-22 globe, No. 17 angle. 2. Screwed, bronze, bevel seat and metal disci 20OP51 SWP; B-37 globe, No. 701 angle. E. Check Valve, Horizontal Swing Type (not for pump discharge) 1. Screwed, bronze body, bronze disc, 125 PSI SWP; B-319. 2. Flanged, cast iron, bronze disc, 125 PSI SWP; G-931. F. Cocks 1. One inch (1") and larger, 175 lb. brass, square head, "Powell" Fig. 2201 lubricated type. 2.20 MANUFACTURER OF VALVES A. Valves: "Stockham," "Crane," "Nibco" or "Apollo." B. All valves shall be the product of manufacturer. C. All valves shall bear name or trademark of manufacturer, working pressure, and direction of flow cast or stamped on valve body. 2.21 PIPE ISOLATION A. Hangers shall be separated from pipe by means of steel encased hair felt padded isolation. B. Isolator shall be as manufactured by "Lemco-Trisolators" or "Potter Roemer RP Isolators." Submit shop drawings for approval. 2.22 PIPING IDENTIFICATION A. Each individual pipe line concealed or exposed shall be labeled for quick and easy identification as to direction of flow and content of materials carried in the pipes by method of stenciling. B. Labels shall be installed at each valve, special fittings and at all branch take -offs and twenty feet (20'-0") apart on long runs. C. Samples of all stenciling for flow and content shall be submitted for approval prior to installation. LETTERS Domestic Hot Water Supply HW Domestic Cold Water Supply CW Soil S Waste W Vent V Gravity Condensate COND D. Prior to stenciling, all fuel gas piping shall be provided with one coat of primer paint and one coat of yellow paint. Primer and paint types as selected by the Architect. 2.23 PLUMBING FIXTURES A. All plumbing fixtures shall be as specified on the drawings with connection sizes as indicated on the fixture schedule and/or in the specifications and must be furnished and installed in accordance with manufacturer's specifications by this contractor. B. Plumbing Fixtures: Accessible plumbing fixtures shall comply with all of the requirements of IBC Section 1101. Heights and location of all fixtures shall be according to IBC 1101. Fixture controls shall comply with IBC Section 1101. C. Accessible sinks and lavatories shall have Truebro "Lavguard" or "Layshield insulation system for water and waste piping under the sink. Foam wrap and tape will not be acceptable. D. Interior exposed pipe, valves, and fixture trim shall be chrome plated. E. The complete installation of each fixture shall include trap and accessories with accessible stop or control valve in each hot and cold water branch supply line. Fixture floor connections shall be made with approved brand of cast Iron floor flange, soldered or caulked securely to waste pipe. Make joint between fixture and floor flange tight with approved fixture setting compound or gaskets. F. Polish chrome finish at completion of project. G. Install fixtures and fittings as per local codes and manufacturer's instructions. H. Do not use flexible water piping. I. Caulking: Fixtures shall be bedded and caulked along joint at walls, counter tops and other intersecting surfaces with "Polysenseal" distributed by "Gladding-McBean" or approved equal. J. Backing for all fixtures indicated on wall shall be one quarter inch by six inches (1/4" x 6") steel) plate; recessed flush with stud face and extending to next stud beyond fixture on each side. Secure plate top and bottom at each stud and weld three eighths inch (3/8") steel stud bolts to each stud. See fixture schedule for type of support required. For wood stud installation, secure backing plate to each stud with three eighths inch by two inch (3/8" x 2") long lag bolts. Minimum two (2) per stud. 2.25 WATER HAMMER ARRESTORS A. Piston operated, type K copper barrel, with brass threaded adaptor 1. The piston shall provide a permanent mechanical barrier between fluid and pre -load air change. 2. The piston shall be equipped with two (2) 0-rings, "Parker Specifications" N741-75, temperature rated 40 OF to 450 OF. Seal lubricant shall be "Dow Corning" Silicone Compound #111 FDA listed as safe for use in potable water systems. B. Shall be designed to operate under domestic and commercial line pressures and equal to the pipe diameter at the point of installation. C. The installation shall be made in the vertical or horizontal positions from the source of lock. Shall be installed in the following locations: 1. All quick closing valves. 2. All valves that close with the flow of fluid. D. Normal arrestor operating pressure shall be 35 to 250 Psig; with a maximum surge or spike pressure not to exceed 1500 Psig. E. Arrestor shall be fully guaranteed in writing by manufacturer for the entire life of the system. F. Shall be as manufactured by "Precision Plumbing Products, Inc.," SC Series. Submit shop drawings for approval by the Mechanical Engineer. 2.26 CLEANOUTS A. Floor: "J.R.Smith" 4023 or 4043 or "Zurn" 1400-2 or 1440-3 or "Josam" 55000-1-CFC-22-Z or "Josam" 55000-1-SQ-22-Z; with polished nickel bronze non-skid adjustable round or square top. Use carpet clamping type top with carpet marker in carpeted areas. B. Dry Wall: "J.R.Smith" 4670 or approved equal by "Zurn" or "Josam;" prime coated steel, face or wall type. C. All other walls: "J.R.Smith" 4470 or approved equal by"Josam" 58540 or "Zurn" 1470 series with chrome plated cover and screws. Provide "J.R. Smith" 4710 or approved equal where wall thickness is inadequate to conceal cleanout. D. Submit shop drawings and/or catalog cuts for each type for Mechanical Engineer's approval, prior to installation. 2.27 THERMOMETERS A. Mercury -filled lens tube type with separable socket. Adjustable, six inch (6") scale shall be 40 deg. F to 240 deg. F range for hot water system with 2 deg. F increments. B. Case, polished, nickel plated or enameled, straight style or angle style case, as required for ease in reading. C. Installed where shown, and adjacent to each liquid immersion thermostat. Locate accessible and for ease in reading, position thermometers located more than 6 feet (6) above floor. D. Thermometers shall be manufactured by "Palmer" 6016, 6017, 1021; or approved equal in "Taylor," or "Scientific." E. Submit shop drawings and/or catalog cuts for each type for Mechanical Engineer's approval, prior to installation. 2.28 PIPE INSULATION A. General 1. Furnish and install thermal insulation on clean dry surfaces; after testing, inspection, and approval in strict accordance with these specifications, contract documents and manufacturer' 5 recommendations. 2. All insulation and accessory material shall meet the requirements of flame spread not to exceed 25 and smoke developed not to exceed 50, as tested by "Procedure ANSI/ASTM-E-84, NFPA 225 or UL 723. 3. Insulation shall be as manufacture by "Manville" or as approved by the Mechanical Engineer, prior to installation. 4. Installation: By skilled appliers directly in the employ of firms with a minimum of five (5) years successful installation experience, specializing in this type of work. 5. Pipe Hangers shall be installed outside the insulation. This contractor shall insert a section of cellular glass insulation at the support of a length not less than twice pipe diameter. B. Medium Temperature Pipe Insulation 1. All piping with hot surfaces shall be insulated. These shall include, but not be limited to the following: a. Domestic hot water supply piping. b. Domestic hot water return piping. 2. Insulation shall be one inch (1") thick for piping 1 1/2" and smaller, and one and one half (1 I/2").thick for piping 2" and larger; with a K factor of 0.23 at 75 -F, high density, white draft bonded to aluminum foil reinforced with fiberglass yarn, "Manville" Micro-Lok with AP jacket or approved equal in C.S.G., or P.P.G. 3. Insulation shall be applied over clean, dry pipe after piping has been tested. Insulation shall be butted together and longitudinal joint closed with white vapor barrier adhesive. Butt strips shall be applied over the circumferential joint and secured with three inch (Y) wide self-sealing butt joint strips. 4. Insulate all fittings, flanges, valves and appurtenances with pre -molded one-piece PVC molded fitting covers with factory matched precut insulation insert, "Manville Zeston" or approved equal. C. Weatherproofing 1. General: Where insulated piping is exposed outdoors, it shall be covered. This includes all cold water piping exposed to outdoors. 2. Cover outdoor exposed insulated piping with 0.016 inch thick corrugated aluminum jacket. 3. Aluminum jacket shall be secured with aluminum draw bands eighteen inches (18") on center, with longitudinal seam overlapped and positioned to shed water. At circumferential joint, place sealant around one end and overlap adjacent piece two inches (2") and secure with one half inch (1/2") aluminum hand. 4. Elbows, all valves, flanges, fittings, etc., shall be covered with "GASCO" or equal covers with circumferential joints described above. 2.29 EQUIPMENT IDENTIFICATION A. Valves 1. Numbered brass disc attached to each valve for identification. 2. Valve tag shall be stamped to identify type of service and sequence number (i.e.: HW-1). Submit sample valve tag for approval prior to installation. 3. Valve directory to be provided with operations and maintenance submittals. PART 3 - EXECUTION 3.01 SUBMITTALS AND TESTS A. Requirements and Submittals 1. Conformation to requirements of Uniform Plumbing Code 2018 Edition, local and/or State codes and/or Ordinances, including the Uniform City and County Building Codes, State County and City Health Department Ordinances, State of Washington Industrial Accident Commission Safety Orders. 2. Apply and pay for all permits, fees, inspections, examinations and tests required by any legally constituted authorities. 3. Contractor shall clearly note on submittals any changes or deviations from that which is specified so that the engineer may readily identify any proposed substitutions. 4. Submission of Electronic PDF containing certified manufacturer's drawings and cuts of all equipment and specialties within thirty (30) days after Contract is signed. Partial or incomplete submittals will be rejected and will be returned to Contractor for re -submittal. a. Submittals shall be in a single Electronic PDF and shall contain a complete list, in index form, of the manufacturer's names, cuts of equipment, performance data, catalog numbers and trade names; as required; to properly identify the materials and equipment to be furnished under these specifications. b. Data submitted for each item shall be properly identified by reference to item number of paragraphs in the specifications and mechanical drawings' equipment schedule designation. c. Any deviation from item as specified shall be clearly indicated on the submittal and noted as such. d. These specifications and accompanying drawings specify and illustrate equipment and materials deemed most suitable for the service anticipated. This is not to preclude other products equally as good and efficient. The contractor shall prepare his bid on the basis of the particular equipment and materials specified for the purpose of determining the low bid. e. The awarding of the contract shall constitute a contractual obligation to furnish the specified equipment and materials. f. After the execution of the contract, should the contractor desire to substitute equipment other than that specified in the contract documents, such substitution will be considered for one reason only: The equipment proposed for substitution is superior in construction and efficiency to that specified herein. g. In the event the contractor obtains the Engineer's approval of equipment other than that herein described; he shall, at his own expense, make any changes in the structures, buildings, or piping necessary to accommodate the equipment and shall furnish record drawings to the Engineer. h. It will be assumed that the cost to the contractor of the equipment proposed to be substituted is less than that of the equipment specified in the contract documents; and, if the substitution is approved, the contract price shall be reduced by an amount equal to the savings. B. Domestic Water Systems Testing 1. Test each section of the piping system and subject it to a test pressure of 150 psig of water for a duration of 4 hours. a. All tests shall be performed in the presence of the administrative authority for the project. 2. Potable water systems shall be disinfected and flushed prior to use by water -chlorination solution and have bacteriological examination made by an approved agency per 2018 upc sec. 609.9 and as prescribed in awwa c651. methods of cleaning/ disinfecting for new or repair piping as described in c651 or nfpa 24. C. Soil and Waste Systems Testing 1. Test each section of the piping system and subject it to a test pressure of 4 psig of compressed air (or 10 ft/hd) for a duration of 15 minutes. a. All tests shall be performed in the presence of the administrative authority for the project. 3.02 EQUIPMENT A. Regulation, Operation and Instruction 1. Lubricate all bearings in accordance with manufacturer's recommendations and instructions. 2. Check operation of all pumps, fixtures, motors, etc. 3. Furnish any additional operation, labor, and material that may be required during guarantee period. 4. The contractor shall, during the guarantee period, and as directed by the owner, make any additional tests, adjustments, etc., that may be required and correct any deficiencies arising from the operation of the system. 3.03 OPERATING AND MAINTENANCE DATA A. Data: Submit to the Architect for approval, prior to acceptance of the installation, complete and at one time. Partial or separate data will not be accepted. Data shall consist of the following- 1. Manufacturer's Literature: Electronic PDF of manufacturer's instructions for operation and maintenance of all equipment, valves, and controls; including replacement parts lists. 2. Written Instruction: Typewritten instruction for operation and maintenance of the system composed of Operation Instructions and Maintenance Instruction. Electronic PDF submitted to the Architect for approval. 3. Operating instructions shall contain a brief description of the system. Adjustments requiring the technical knowledge of the service agency personnel shall not be included in the operating instructions. 4. Maintenance instructions shall list each item (i.e. plumbing fixtures and equipment) requiring inspection, lubrication, or service and describe the performance of such maintenance. 5. Verbal Instructions: Operating personnel shall be instructed in the operation of the systems in accordance with typewritten instructions. No other verbal instructions shall be given. 6. Binders: Four (4) complete sets of the above data in loose leaf, ring type binders with permanent covers, with identification on inside cover. 3.04 SPECIAL REQUIREMENTS A. The manufacturer and/or supplier of all equipment shall certify in writing to the owner that this equipment complies with these specifications. B. All new equipment shall be anchored as required and/or as detailed on drawings. C. Written Certifications, in a form approved by the Mechanical Engineer, shall be provided by the equipment manufacturer or his authorized representative: 1. That the equipment and its installation was inspected on the job by the manufacturer and that the equipment is in first- class condition throughout, was installed in accordance with manufacturer's requirements and recommendations, and that the installation is approved by the manufacturer. 2. That the equipment is operating in a safe and satisfactory manner and is delivering capacities and performance hereinbefore specified and/or indicated on the drawings. 3. The following shall be certified as described above: All plumbing fixtures and domestic hot water heaters. D. Damage by Leaks: The contractor shall be responsible for all damage to equipment and premises caused by leaks or breaks in piping or equipment for a period of one (1) year after date of final acceptance. E. Unless otherwise directed, and/or specified, and/or indicated; all materials and equipment shall be installed in accordance with the manufacturer's recommendations and instructions. F. Plumbing equipment shall bear the manufacturer's label or nameplate showing performance characteristics. Identifying size or model number shall be given only when not practicable or customary to show otherwise. All valves, pipe, fixtures and fittings shall bear the manufacturer's trademark or identifying markings. G. All materials of similar class or service shall be of one manufacturer. I. Plumbing piping layouts as shown on the drawings are subject to modifications, by contractor, without extra cost as required to clear other items of construction. This contractor shall coordinate the work of this section with that of other sections as to avoid interferences by other crafts involved. H. Contractor shall visit site prior to bidding and fully acquaint himself with all conditions affecting installation of the proposed system. Failure to do so shall not relieve contractor of responsibility of providing complete, operational, and acceptable system. 3.05 COMPLETION A. When the installation is complete and adjustments specified herein are made, the system shall be operated for a period of one week, during which time it shall be demonstrated to the Mechanical Engineer as being completed and operating in conformance with these specifications. B. Record as -built drawings showing locations and size of all plumbing piping, fixtures, and equipment as installed shall be kept up-to-date and available for inspection at all times during construction. These shall be signed by the General Contractor and Plumbing Contractor to certify their accuracy and shall be submitted to the owner prior to final acceptance of the work. END OF SECTION t 425.778.1530 21911 76th Ave W. Suite 210 f 425.774.7803 Edmonds WA 98026 info@tgbarchitects.com www.tgbarchitects.com PRELIMINARY: NOT FOR CONSTRUCTION f 210077.17� 110 James St., Suite 106 Edmonds, WA 98020 Phone: 425.458.9700 Fax: 909.890.3770 Email: cadd@designwesteng.com DESIGN WEST ENGINEERING MECHANICAL' ELECTRICAL' ENERGY CONSULTANTS EDMONDS MEDICAL PLAZA - SPEC SUITE 202 216116 76TH AVENUE WEST EDMONDS, WA 98026 PLUMBING SPECFICATIONS (CONY) ISSUANCE No. Description Date PROJECT INFORMATION PROJECT NUMBER: PROJECT LEAD: DRAWN BY: 22011 Designer Author SHEET NO RECEIVED Nov 17 2022 CITY OF EDMONDS P=502 VELOPMENT SERVICES DEPARTMENT 22-101 2E K