FIR2022-0077+Fire_Alarm_Plan+8.9.2022_9.18.33_AM+3039763FIRE ALARM DEVICE INSTALLATION REQUIREMENTS NOT PERMITTED HFRF d" CABLE AND WIRE LEGEND LINE TYPE LABEL CABLE TYPE AWG RESIST. ( Q/Mft) DESCRIPTION U 18/2 FPLR 18 7.77 IDC ANALOG INITIATING CIRCUIT Z 18/2 FPLR 18 7.77 IDC ANALOG RELAY CIRCUIT — — T 12/2 THHN 12 2.44 HIGH VOLTAGE CONNECTION All CONDUCTORS SHALL BE INSTALLED IN RACEWAYS SUITABLE FOR THE INSTALLATION CONDITIONS, PER THE REQUIREMENTS OF IBC, IFC, NPFA-72 & NFPA-70 (NEC) OPERATIONAL MATRIX SYSTEM OUTPUTS Required Fire Safety Control Central Supervising Station Control Unit Annunciation m o co .40 w ti u .� .0 CZ w co O <° .5 Co wo 0 ;;e QQ o o�LIC?o c o p C .S) ' J� m � F� `� cow Q y� V° <� a` aj a` QQQF�F w� w� 4?R SYSTEM INPUTS A B C D E F G H 1 Manual Fire Alarm Pull -Station X X X X 1 2 Smoke/Heat Detectors X X X X 2 J 3 Q Wet / Dry Flow X X X X 3 4 Unused 4 d 5 Sprinkler Tamper X X 5 Cl) i 6 Low Air X X 6 7 Fire Alarm AC Power Failure X X 7 J m i 8 Fire Alarm System Low Battery X X 8 H 9 Open Circuit X X 9 10 Ground Fault X X 10 DODO©�0© VICINITY MAP L n nwoc 9 4th Ave' f Edmonds, WA 9802.0 I Wooduuay Esperance i� Shoreline i =C5 4TH AVENUE APARTMENTS ELEVATOR FRE ALARM NSTALLATON EDMONDS, WA AES INSTALLATION DETAIL O O O ELEV HAT DR HOLDS ELEV ALT ELEV PRI EXISTING CONVENTIONAL FACP (SILENT KNIGHT SK-5207 FIRE PANEL) SITE PLAN 4TH AVE SOUTH OUTDOOR BELL AND STROBE 0 0 Cn m m FACP & RISER RM ALLEY BETWEEN 4TH AND 5TH AVE SOUTH N Not to Scale 1 2 3 11 5 on IDP IN SUPPORT BRACKET ACT J-BOX GRID FA DEVICE CEILIEG 1 DETECTOR I s MAX HEIGHT 92" A.F.F MIN HEIGHT 82" A.F.F o FAA A 66" A.F.F 60" A.F.F - i 48" A.F.F DIFFUSER AIL_ MINIMUM 3' AWAY FROM HVAC DIFFUSERS SHEET INDEX SHEET # SHEET DESCRIPTION FA 0.0 FIRE ALARM : FIRE ALARM INSTALLATION FA 1.0 SINGLE LINE RISER DIAGRAM, BATTERY CALCULATIONS & POINT TO POINT VOLTAGE DROP PROJECT DETAIL 1. THE EXISTING 3—STORY BUILDING IS FULLY —SPRINKLED AND HAS AN EXISTING CONVENTIONAL FIRE ALARM CONTROL PANEL (SILENT KNIGHT SK-5207) LOCATED IN THE BACK OF THE BUILDING. 2. SITE IS MODERNIZING THEIR ELEVATOR WHICH HAS TWO EXISTING RECALL RELAYS. WE WILL BE ADDING (1) ELEVATOR FLASHING HAT RELAY, (1) ELEVATOR PIT HEAT, (1) SHUNT TRIP HEAT, AND (1) SHUNT TRIP AC SUPERVISION. 3. THE ELEVATOR SUPPORT COMPANY WILL PROVIDE AND INSTALL THE WIRING, THE EQUIPMENT, AND TERMINATION OF EQUIPMENT SHOWN IN THE DESIGN. FIRE PROTECTION, INC. WILL BE PROVIDING FULL SYSTEM DRAWINGS, TERMINATION OF WIRING ON FACP, SYSTEM PROGRAMMING, SYSTEM PRETEST AND FINAL ACCEPTANCE TEST. 4. NO OTHER CHANGES TO THE EXISTING SYSTEM WILL BE MADE, NO ADDITIONAL WORK IS INCLUDED IN THIS SCOPE. CONTACT INFO JOB OWNER FIRE ALARM CONTRACTOR ELEVATOR SUPPORT COMPANY, LLC FIRE PROTECTION INC 18402 66TH AVE W 17410 ASH WAY, SUITE 8 EDMONDS, WA 98037 LYNNWOOD, WA 98037 CONTACT : MICHAEL HARRIS CONTACT : DAVID MOW PHONE : 425.821.7189 PHONE 425.290.9600 CODE INFORMATION AUTHORITY HAVING JURISDICTION CITY OF EDMONDS FIRE CODE INTERNATIONAL FIRE CODE, 2018 EDITION BUILDING USE AND OCCUPANCY : R2 — FULLY SPRINKLED STANDARDS: 2017 NFPA 70, 2016 NFPA 72, AND CITY OF EDMONDS STANDARDS CLASSIFICATION OF SUPERVISING STATION : CENTRAL SUPERVISING STATION REMOTE SUPERVISING STATION : STANLEY SECURITY, INC. PRIME FIRE ALARM CONTRACTOR : FIRE PROTECTION, INC. PARCEL NUMBERS : 00912500010100, 00912500010200, 00912500020100, 00912500020200, 00912500030100, 00912500030200 INSTALLATION NOTES ALL WORK SHALL BE IN ACCORDANCE WITH NFPA STANDARDS AND ALL LOCAL ADOPTED CODES. ALL CIRCUITS MUST BE TESTED FOR OPENS, CONTINUITY, SHORTS, AND GROUNDS. INSTRUCTIONS FOR THE OPERATING, TESTING AND MAINTENANCE OF THE SYSTEM, ALONG WITH RECORD DRAWINGS OTHERWISE REFERRED TO AS ("AS —BUILT") AND EQUIPMENT SPECIFICATIONS SHALL BE PROVIDED TO THE OWNER ONCE THE FIRE ALARM SYSTEM HAS BEEN ACCEPTED BY THE AHJ. ALL SYSTEMS AND DEVICES SHALL BE INSTALLED AND TESTED PER THE MANUFACTURES LISTING AND THE AUTHORITY HAVING JURISDICTION (NFPA72 10.14.2.1). THE SYSTEM WILL BE 100% PRE —TESTED, AN NFPA 72 COMPLETION FORM WILL BE FILLED OUT AND PROVIDED TO THE AHJ AND THE ELECTRICAL PERMITS MUST BE SIGNED OFF PRIOR TO THE FIRE FINAL INSPECTION. THE AES RADIO REQUIRES A DEDICATED 120VAC 20AMP CIRCUIT. A NOTICE PLACED IN THE FACP SHALL DIRECT PERSONNEL TO THE LOCATION OF THE ELECTRICAL PANEL THAT IS SUPPLYING DEDICATED POWER TO THE SYSTEM (NFPA72, SECTION 10.5.5.1). THE DEDICATED CIRCUIT BREAKER THAT SERVES THE FIRE ALARM SYSTEM SHALL BE LABELED AND SECURED AGAINST TAMPERING WITH A RED BREAKER LOCKOUT (NFPA72, SECTION 10.5.5.2). UT INSTALLATION WIRING DIAGRAMS TERMINATION OF WIRE AT DEVICE YES NO CONVENTIONAL DETECTORS BASE ILLUSTRATION (2W-B / 5603 / 5623) WIRES TERMINATED ONTO ELEV. CONTROLLER BY THE ELEVATOR CONTRACTOR PHASE 1 RECALL PHASE 2 RECALL FIRE HAT UGHT ELEVATOR PHASE 1 & 2 RECALL INTERFACE w/FIRE HAT FACP FIRE ALARM CONTROL PANEL NOT TO SCALE FIRE PROTECTION INC. 17410 Ash Way, Ste 8 Lynnwood, WA 98037 425-290-9600 FPISEATTLE.COM �p4pTFC��'~ 4 � LU s + ] cs r NFPA' •�' CFPS #1473 vQ �# N W>_ o Z U IX W W M U �3 r.a Q2* 2 2 2 J > d J N Q- cY,0 z >-w�W m! O >- o m�" W W Q J �W� a. 2 www°dw Q 0IXcnJli 0 REVISION RECORD DATE / DESCRIPTION FIR2022-0077 RECEIVED Aug 10 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT DATE: 08/03/2022 PROJECT NAME H LU L0 CV U CD M w� DC a > Q a _ C/) H w0"Tz a>N° W 13 H I j W SHEET TITLE I FIRE ALARM PROJECT DETAILS SHEET NUMBER I FA OmO 3RD FLOOR EX FACP•N3.05 EOL 4.7k 30cd EX EX v FACP•N3.04 FACP•N3.03 30cd EX �EX v FACP•N3.02 FACP•N3.01 30cd EX EX EX EX "FACP-N2-02 EX o F o FACP-N2.06 EOL 4.7k FACP•N2.05 FACP-N2.04 FACP•N2.03FACP•N2.01 30cd 30cd30cd 2ND FLOOR ---------------------------I----- EX, EX EX FACP •Z7.1 FACP •Z7.2 FACP •Z7.3 EOL 4.7k EX FACP •Z12.1 FACP •Z12.2 EOL EX EX EX FACP •Z6.1 FACP •Z6.2 FACP •Z6.3 EOL 4.7k EX F11-k EX FACP •Z11.1 FACP •Z11.2 EOL EXISTING ' FIRE ALARM EX EX EX EX EX CONTROL PANEL EX EX U EX F v F v0- S S ,� -1 - FACP •N 1 •05 EOL 4.7k FACP •N 1 •04 FACP •N 1 •03 FACP •N1 •02 FACP -N 1.01 FACP •Z5.1 FACP •Z5.2 FACP •Z5.3 EOL 4.7k 30cd 30cd 30cd q�-a;;, � U :X -ACP •Z1 •l EOL 4.7k NEW FACP •Z13.1 EOL NEW FACP•Z14.1 EOL NEW r FACP•Z15.1 EOL EX FACP •Z2.1 EOL 4.7k EX FACP •Z3.1 EOL 4.7k EX FACP•Z4.1 EOL 4.7k FACP •Z8.1 EOL 4.7k EX FACP •Z9.1 EOL 4.7k EX EX FACP•Z1O.1 FACP•Z10.2 EOL 4.7k 1 s-L FLO QR - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -j s-L FLO QR - SINGLE LINE RISER DIAGRAM - nts PANEL FACP (SK-5207) BATTERY CALCULATION (SECONDARY POWER SOURCE REQUIREMENTS) STANDBY CURRENT (AMPS) SECONDARY ALARM CURRENT (AMPS) PANEL COMPONENTS QTY PART NO. DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL 1 SK-5207 MAIN BOARD FIRE ALARM CONTROL PANEL MAIN BOARD 0.14 0.14 0.46 0.46 1 Sk-5210 PANEL COMPONENT, ZONE EXPANDER FOR 5207 0 0 0 0 CIRCUIT SYMBOL QTY PART NO DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL (A) 2 HR Horn, red 0 0 0.069 0.138 FACP•N 1 0 3 P2R 2-Wire Horn/Strobe red 30cd 0 0 0.116 0.348 3 HR Horn, red 0 0 0.069 0.207 FACP•N2 0 3 P2R 2-Wire Horn/Strobe red 30cd 0 0 0.116 0.348 FACP•N3 2 HR Horn, red 0 0 0.069 0.138 0 3 P2R 2-Wire Horn/Strobe red 30cd 0 0 0.116 0.348 FACP•Z1 g 1 WATERFLOW SWITCH CONTACT DEVICE 0 0 0 0 FACP•Z10 ❑F 2 PS -SA CONVENTIONAL SINGLE ACTION MANUAL PULL STATION 0 0 0 0 FACP•Z11 ❑F 2 PS -SA CONVENTIONAL SINGLE ACTION MANUAL PULL STATION 0 0 0 0 FACP•Z12 ❑F 2 PS -SA CONVENTIONAL SINGLE ACTION MANUAL PULL STATION 0 0 0 0 FACP•Z13 0 1 5603 135 °F (57' C) fixed temperature 0 0 0 0 FACP•Z14 O 1 5623 135 °F (57' C) fixed temperature, dual circuit. 0 0 0 0 FACP•Z15 1 GENERIC CONTACT DEVICE CONTACT DEVICE 0 0 0 0 FACP•Z2 1 TAMPER SWITCH TAMPER SWITCH 0 0 0 0 FACP•Z3 1 2W-B 2-wire Standard i3 Detector 0.0001 0.0001 0.13 0.13 FACP•Z4 0 1 2W-B 2-wire Standard i3 Detector 0.0001 0.0001 0.13 0.13 FACP•Z5 0 3 2W-B 2-wire Standard D Detector 0.0001 0.0003 0.13 0.39 FACP•Z6 3 2W-B 2-wire Standard i3 Detector 0.0001 0.0003 0.13 0.39 FACP•Z7 0 3 2W-B 2-wire Standard i3 Detector 0.0001 0.0003 0.13 0.39 FACP•Z8 1 TAMPER SWITCH TAMPER SWITCH 0 0 0 0 FACP•Z9 ❑F 1 PS -SA CONVENTIONAL SINGLE ACTION MANUAL PULL STATION 0 0 0 0 TOTAL STANDBY (A) 1 0.1411 TOTAL ALARM (A) 3.417 REQUIRED STANDBY TIME = 24 HOURS REQUIRED ALARM TIME = 5 MINUTES SECONDARY STANDBY LOAD (A) 0.1411 24 3.39 SECONDARY ALARM LOAD (A) 3.417 0.08 0.28 STANDBY AND ALARM SUBTOTAL (AMP HOURS) 3.67 DERATING FACTOR 1.2 SECONDARY LOAD REQUIREMENTS (AMP HOURS) 4.41 PROVIDE (2)12V 7AH BATTERIES *BATTERY BOX SIZE CAPACITY NOT SPECIFIED. REFER TO MANUFACTURER DOCUMENTATION. FACP BATTERY CALCULATIONS FACP N1 POINT-TO-POINT REPORT CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20.4 Max. Voltage Drop: 0.42 Min. Operational Voltage: 16 End Of Line Voltage: 19.98 Max. Circuit Current (A): 3 Voltage Drop Percent: 2.08 % Wire Resistance (0/kFt): 3.07 Total Circuit Current (A): 0.486 Circuit Wiring Properties: 'BP' 14/2 FPLP 14 AWG, 2 Cond. Solid Copper FPLP Analog Unshielded Total Circuit Length (Ft): 166 Spare Current (A): 2.514 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0): 1.017409 Spare Current (A) Percent: 83.80 % Device Label Part No. Description Device Current (A) Remaining Current (A) Dist. From Previous (Ft) Resistance From Previous (Q) Voltage Drop From Previous Voltage At Device Total Voltage Drop Voltage Drop Percent FACP•N1.01 P2R 2-Wire Horn/Strobe red 30cd 0.116 0.486 113 0.69135 0.34 20.06 0.34 1.65 % FACP•Nl-02 HR Horn, red 0.069 0.37 23 0.143916 0.05 20.01 0.39 1.91 % FACP•N1.03 P2R 2-Wire Horn/Strobe red 30cd 0.116 0.301 9 0.054641 0.02 19.99 0.41 1.99 % FACP•Nl-04 HR Horn, red 0.069 0.185 9 0.058285 0.01 19.98 0.42 2.04 % FACP•N1.05 EOL 4.7k P2R 2-Wire Horn/Strobe red 30cd 0.116 0.116 11 0.069217 0.01 19.98 0.42 2.08 % Calculation Methods: Resistance From Previous (0) = Wire Resistance (Q/Ft) x 2 x Dist. From Previous (Ft) Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A) FACP N2 POINT-TO-POINT REPORT CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20.4 Max. Voltage Drop: 0.85 Min. Operational Voltage: 16 End Of Line Voltage: 19.55 Max. Circuit Current (A): 3 Voltage Drop Percent: 4.14 % Wire Resistance (t2/kFt): 3.07 Total Circuit Current (A): 0.555 Circuit Wiring Properties: 'BP' 14/2 FPLP 14 AWG, 2 Cond. Solid Copper FPLP Analog Unshielded Total Circuit Length (Ft): 374 Spare Current (A): 2.445 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0): 2.296383 Spare Current (A) Percent: 81.50 % Device Label Part No. Description Device Current (A) Remaining Current (A) Dist. From Previous (Ft) Resistance From Previous (0) Voltage Drop From Previous Voltage At Device Total Voltage Drop Voltage Drop Percent FACP•N2.01 P2R 2-Wire Horn/Strobe red 30cd 0.116 0.555 139 0.851679 0.47 19.93 0.47 2.32 % FACP•N2.02 HR Horn, red 0.069 0.439 41 0.249588 0.11 19.82 0.58 2.85 % FACP•N2.03 P2R 2-Wire Horn/Strobe red 30cd 0.116 0.37 50 0.306066 0.11 19.7 0.7 3.41 % FACP•N2.04 HR Horn, red 0.069 0.254 45 0.275094 0.07 19.63 0.77 3.75 % FACP•N2.05 P2R 2-Wire Horn/Strobe red 30cd 0.116 0.185 53 0.322464 0.06 19.57 0.83 4.04 % FACP•N2.06 EOL 4.7k HR Horn, red 0.069 0.069 47 0.291492 0.02 19.55 0.85 4.14 % Calculation Methods: Resistance From Previous (0) = Wire Resistance (Q/Ft) x 2 x Dist. From Previous (Ft) Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A) FACP N3 POINT-TO-POINT REPORT CIRCUIT SETTINGS TOTALS Starting Calculation Voltage: 20.4 Max. Voltage Drop: 0.42 Min. Operational Voltage: 16 End Of Line Voltage: 19.98 Max. Circuit Current (A): 3 Voltage Drop Percent: 2.08 Wire Resistance (0/kFt): 3.07 Total Circuit Current (A): 0.486 Circuit Wiring Properties: 'BP' 14/2 FPLP 14 AWG, 2 Cond. Solid Copper FPLP Analog Unshielded Total Circuit Length (Ft): 168 Spare Current (A): 2.514 Distance measured using drawn segment lengths with 10.00 % additional length calculated Total Circuit Resistance (0): 1.030161 Spare Current (A) Percent: 83.80 % Device Label Part No. Description Device Current (A) Remaining Current (A) Dist. From Previous (Ft) Resistance From Previous (0) Voltage Drop From Previous Voltage At Device Total Voltage Drop Voltage Drop Percent FACP•N3.01 P2R 2-Wire Horn/Strobe red 30cd 0.116 0.486 118 0.725969 0.35 20.05 0.35 1.73 % FACP•N3.02 HR Horn, red 0.069 0.37 9 0.056461 0.02 20.03 0.37 1.83 % FACP•N3.03 P2R 2-Wire Horn/Strobe red 30cd 0.116 0.301 15 0.092901 0.03 20 0.4 1.97 % FACP•N3.04 HR Horn, red 0.069 0.185 9 0.058285 0.01 1 19.99 0.41 2.02 % FACP•N3.05 EOL 4.7k P2R 2-Wire Horn/Strobe red 30cd 0.116 0.116 16 0.096545 0.01 1 19.98 0.42 2.08 % Calculation Methods: Resistance From Previous (0) = Wire Resistance (Q/Ft) x 2 x Dist. From Previous (Ft) Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A) FIRE PROTECTION INC. 17410 Ash Way, Ste 8 Lynnwood, WA 98037 425-290-9600 FPISEATTLE.COM #14T3 Cq v rn o *k N =� a ' LL: w>_ 0 U H LU Z U > W W CO U W�a 0 U = U � d V J N J a U p 0 o z�W�� >QU-Ujo> m W J Q W �W�Wa aau -ja o REVISION RECORD DATE / DESCRIPTION RECEIVED Aug 10 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT DATE: 08/03/2022 PROJECT NAME Z ID N WC QU)CO W � a > iL Cn W � � Z QN2 > G W 13 H W W SHEET TITLE I FIRE ALARM SINGLE LINE RISER DIAGRAM / BATTERY CALCULATIONS / POINT TO POINT VOLTAGE DROP POINT TO POINT VOLTAGE DROP REPORT SHEET NUMBER I FA 1m0