FIR2022-0077+Fire_Alarm_Voltage_Calculations+8.9.2022_9.18.19_AM+30397603RD FLOOR
EX
FACP•N3.05 EOL 4.7k
30cd
EX EX
v
FACP•N3.04 FACP•N3.03
30cd
EX �EX
v
FACP•N3.02 FACP•N3.01
30cd
EX EX EX EX "FACP-N2-02
EX
o F o FACP-N2.06 EOL 4.7k FACP•N2.05 FACP-N2.04 FACP•N2.03FACP•N2.01
30cd 30cd30cd
2ND FLOOR ---------------------------I-----
EX, EX EX
FACP •Z7.1 FACP •Z7.2 FACP •Z7.3 EOL 4.7k
EX
FACP •Z12.1 FACP •Z12.2 EOL
EX EX EX
FACP •Z6.1 FACP •Z6.2 FACP •Z6.3 EOL 4.7k
EX F11-k EX
FACP •Z11.1 FACP •Z11.2 EOL
EXISTING '
FIRE ALARM
EX EX EX EX EX CONTROL PANEL EX EX U EX
F v F v0- S S ,� -1 -
FACP •N 1 •05 EOL 4.7k FACP •N 1 •04 FACP •N 1 •03 FACP •N1 •02 FACP -N 1.01 FACP •Z5.1 FACP •Z5.2 FACP •Z5.3 EOL 4.7k
30cd 30cd 30cd q�-a;;,
� U
:X
-ACP •Z1 •l EOL 4.7k
NEW
FACP •Z13.1 EOL
NEW
FACP•Z14.1 EOL
NEW
r
FACP•Z15.1 EOL
EX
FACP •Z2.1 EOL 4.7k
EX
FACP •Z3.1 EOL 4.7k
EX
FACP•Z4.1 EOL 4.7k
FACP •Z8.1 EOL 4.7k
EX
FACP •Z9.1 EOL 4.7k
EX EX
FACP•Z1O.1 FACP•Z10.2 EOL 4.7k
1 s-L FLO QR - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -j s-L FLO QR -
SINGLE LINE RISER DIAGRAM - nts
PANEL FACP (SK-5207) BATTERY CALCULATION
(SECONDARY POWER SOURCE REQUIREMENTS)
STANDBY CURRENT (AMPS)
SECONDARY ALARM CURRENT (AMPS)
PANEL COMPONENTS
QTY
PART NO.
DESCRIPTION
CURRENT DRAW (A)
TOTAL (A)
CURRENT DRAW (A)
TOTAL
1
SK-5207 MAIN BOARD
FIRE ALARM CONTROL PANEL MAIN BOARD
0.14
0.14
0.46
0.46
1
Sk-5210
PANEL COMPONENT, ZONE EXPANDER FOR 5207
0
0
0
0
CIRCUIT
SYMBOL
QTY
PART NO
DESCRIPTION
CURRENT DRAW (A)
TOTAL (A)
CURRENT DRAW (A)
TOTAL (A)
2
HR
Horn, red
0
0
0.069
0.138
FACP•N 1
0
3
P2R
2-Wire Horn/Strobe red 30cd
0
0
0.116
0.348
3
HR
Horn, red
0
0
0.069
0.207
FACP•N2
0
3
P2R
2-Wire Horn/Strobe red 30cd
0
0
0.116
0.348
FACP•N3
2
HR
Horn, red
0
0
0.069
0.138
0
3
P2R
2-Wire Horn/Strobe red 30cd
0
0
0.116
0.348
FACP•Z1
g
1
WATERFLOW SWITCH
CONTACT DEVICE
0
0
0
0
FACP•Z10
❑F
2
PS -SA
CONVENTIONAL SINGLE ACTION MANUAL PULL STATION
0
0
0
0
FACP•Z11
❑F
2
PS -SA
CONVENTIONAL SINGLE ACTION MANUAL PULL STATION
0
0
0
0
FACP•Z12
❑F
2
PS -SA
CONVENTIONAL SINGLE ACTION MANUAL PULL STATION
0
0
0
0
FACP•Z13
0
1
5603
135 °F (57' C) fixed temperature
0
0
0
0
FACP•Z14
O
1
5623
135 °F (57' C) fixed temperature, dual circuit.
0
0
0
0
FACP•Z15
1
GENERIC CONTACT DEVICE
CONTACT DEVICE
0
0
0
0
FACP•Z2
1
TAMPER SWITCH
TAMPER SWITCH
0
0
0
0
FACP•Z3
1
2W-B
2-wire Standard i3 Detector
0.0001
0.0001
0.13
0.13
FACP•Z4
0
1
2W-B
2-wire Standard i3 Detector
0.0001
0.0001
0.13
0.13
FACP•Z5
0
3
2W-B
2-wire Standard D Detector
0.0001
0.0003
0.13
0.39
FACP•Z6
3
2W-B
2-wire Standard i3 Detector
0.0001
0.0003
0.13
0.39
FACP•Z7
0
3
2W-B
2-wire Standard i3 Detector
0.0001
0.0003
0.13
0.39
FACP•Z8
1
TAMPER SWITCH
TAMPER SWITCH
0
0
0
0
FACP•Z9
❑F
1
PS -SA
CONVENTIONAL SINGLE ACTION MANUAL PULL STATION
0
0
0
0
TOTAL STANDBY (A)
1 0.1411
TOTAL ALARM (A)
3.417
REQUIRED STANDBY TIME = 24 HOURS
REQUIRED ALARM TIME = 5 MINUTES
SECONDARY STANDBY LOAD (A)
0.1411
24
3.39
SECONDARY ALARM LOAD (A)
3.417
0.08
0.28
STANDBY AND ALARM SUBTOTAL (AMP HOURS)
3.67
DERATING FACTOR
1.2
SECONDARY LOAD REQUIREMENTS (AMP HOURS)
4.41
PROVIDE (2)12V 7AH BATTERIES
*BATTERY BOX SIZE CAPACITY NOT SPECIFIED. REFER TO MANUFACTURER DOCUMENTATION.
FACP BATTERY CALCULATIONS
FACP N1 POINT-TO-POINT REPORT
CIRCUIT SETTINGS
TOTALS
Starting Calculation Voltage:
20.4
Max. Voltage Drop:
0.42
Min. Operational Voltage:
16
End Of Line Voltage:
19.98
Max. Circuit Current (A):
3
Voltage Drop Percent:
2.08 %
Wire Resistance (0/kFt):
3.07
Total Circuit Current (A):
0.486
Circuit Wiring Properties: 'BP' 14/2 FPLP 14 AWG, 2 Cond. Solid Copper FPLP Analog Unshielded
Total Circuit Length (Ft):
166
Spare Current (A):
2.514
Distance measured using drawn segment lengths with 10.00 % additional length calculated
Total Circuit Resistance (0):
1.017409
Spare Current (A) Percent:
83.80 %
Device Label
Part No.
Description
Device Current (A)
Remaining Current (A)
Dist. From Previous (Ft)
Resistance From Previous (Q)
Voltage Drop From Previous
Voltage At Device
Total Voltage Drop
Voltage Drop Percent
FACP•N1.01
P2R
2-Wire Horn/Strobe red 30cd
0.116
0.486
113
0.69135
0.34
20.06
0.34
1.65
FACP•Nl-02
HR
Horn, red
0.069
0.37
23
0.143916
0.05
20.01
0.39
1.91 %
FACP•N1.03
P2R
2-Wire Horn/Strobe red 30cd
0.116
0.301
9
0.054641
0.02
19.99
0.41
1.99 %
FACP•Nl-04
HR
Horn, red
0.069
0.185
9
0.058285
0.01
19.98
0.42
2.04 %
FACP•N1.05 EOL 4.7k
P2R
2-Wire Horn/Strobe red 30cd
0.116
0.116
11
0.069217
0.01
19.98
0.42
2.08 %
Calculation Methods:
Resistance From Previous (0) = Wire Resistance (Q/Ft) x 2 x Dist. From Previous (Ft)
Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A)
FACP N2 POINT-TO-POINT REPORT
CIRCUIT SETTINGS
TOTALS
Starting Calculation Voltage:
20.4
Max. Voltage Drop:
0.85
Min. Operational Voltage:
16
End Of Line Voltage:
19.55
Max. Circuit Current (A):
3
Voltage Drop Percent:
4.14 %
Wire Resistance (t2/kFt):
3.07
Total Circuit Current (A):
0.555
Circuit Wiring Properties: 'BP' 14/2 FPLP 14 AWG, 2 Cond. Solid Copper FPLP Analog Unshielded
Total Circuit Length (Ft):
374
Spare Current (A):
2.445
Distance measured using drawn segment lengths with 10.00 % additional length calculated
Total Circuit Resistance (0):
2.296383
Spare Current (A) Percent:
81.50 %
Device Label
Part No.
Description
Device Current (A)
Remaining Current (A)
Dist. From Previous (Ft)
Resistance From Previous (0)
Voltage Drop From Previous
Voltage At Device
Total Voltage Drop
Voltage Drop Percent
FACP•N2.01
P2R
2-Wire Horn/Strobe red 30cd
0.116
0.555
139
0.851679
0.47
19.93
0.47
2.32 %
FACP•N2.02
HR
Horn, red
0.069
0.439
41
0.249588
0.11
19.82
0.58
2.85 %
FACP•N2.03
P2R
2-Wire Horn/Strobe red 30cd
0.116
0.37
50
0.306066
0.11
19.7
0.7
3.41 %
FACP•N2.04
HR
Horn, red
0.069
0.254
45
0.275094
0.07
19.63
0.77
3.75 %
FACP•N2.05
P2R
2-Wire Horn/Strobe red 30cd
0.116
0.185
53
0.322464
0.06
19.57
0.83
4.04 %
FACP•N2.06 EOL 4.7k
HR
Horn, red
0.069
0.069
47
0.291492
0.02
19.55
0.85
4.14 %
Calculation Methods:
Resistance From Previous (0) = Wire Resistance (Q/Ft) x 2 x Dist. From Previous (Ft)
Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A)
FACP N3 POINT-TO-POINT REPORT
CIRCUIT SETTINGS
TOTALS
Starting Calculation Voltage:
20.4
Max. Voltage Drop:
0.42
Min. Operational Voltage:
16
End Of Line Voltage:
19.98
Max. Circuit Current (A):
3
Voltage Drop Percent:
2.08
Wire Resistance (0/kFt):
3.07
Total Circuit Current (A):
0.486
Circuit Wiring Properties: 'BP' 14/2 FPLP 14 AWG, 2 Cond. Solid Copper FPLP Analog Unshielded
Total Circuit Length (Ft):
168
Spare Current (A):
2.514
Distance measured using drawn segment lengths with 10.00 % additional length calculated
Total Circuit Resistance (0):
1.030161
Spare Current (A) Percent:
83.80 %
Device Label
Part No.
Description
Device Current (A)
Remaining Current (A)
Dist. From Previous (Ft)
Resistance From Previous (0)
Voltage Drop From Previous
Voltage At Device
Total Voltage Drop
Voltage Drop Percent
FACP•N3.01
P2R
2-Wire Horn/Strobe red 30cd
0.116
0.486
118
0.725969
0.35
20.05
0.35
1.73 %
FACP•N3.02
HR
Horn, red
0.069
0.37
9
0.056461
0.02
20.03
0.37
1.83 %
FACP•N3.03
P2R
2-Wire Horn/Strobe red 30cd
0.116
0.301
15
0.092901
0.03
20
0.4
1.97 %
FACP•N3.04
HR
Horn, red
0.069
0.185
9
0.058285
0.01
1 19.99
0.41
2.02 %
FACP•N3.05 EOL 4.7k
P2R
2-Wire Horn/Strobe red 30cd
0.116
0.116
16
0.096545
0.01
1 19.98
0.42
2.08 %
Calculation Methods:
Resistance From Previous (0) = Wire Resistance (Q/Ft) x 2 x Dist. From Previous (Ft)
Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A)
FIRE PROTECTION INC.
17410 Ash Way, Ste 8
Lynnwood, WA 98037
425-290-9600
FPISEATTLE.COM
#14T3
Cq
v rn
o
*k N
=� a
' LL:
w>_ 0
U H LU
Z U >
W
W
CO U
W�a
0 U =
U � d V J
N J
a
U p 0 o
z�W��
>QU-Ujo>
m W J Q W
�W�Wa
aau -ja
o
REVISION RECORD
DATE / DESCRIPTION
FIR2022-0077
RECEIVED
Aug 10 2022
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
DATE: 08/03/2022
PROJECT NAME
Z ID N
WC
QU)CO
W �
a >
iL
Cn
W � � Z
QN2
>
G
W 13
H W W
SHEET TITLE I
FIRE ALARM
SINGLE LINE RISER
DIAGRAM / BATTERY
CALCULATIONS / POINT TO
POINT VOLTAGE DROP
POINT TO POINT VOLTAGE DROP REPORT
SHEET NUMBER I
FA 1m0