stem Design Summary DEPARTMENT
General Requirements BLD2023-0532
Room Temperature: -10 °F Ambient Temperature: 105 °F Design Run-time: 18 Hrs Required Capacity: 9,800 BTUH
Selected Equipment
Line Item Quantity Type Tag
1.0 1 System SYS-1
1.1 1 Condensing Unit CDU-1
1.2 1 Unit Cooler UC-1
System Balance
Description
R-448A - Refrigeration Equipment Match 1
RF03501_4SEA
RL6E090DDA
Balanced Capacity: 10,454.1 BTUH Evap. T.D.: 9.9 °F Line Loss: 2 °F Suction Temp: -21.9 °F Calc. Run -Time: 16.9 Hrs
Quotes are valid for 30 Days. Due to ongoing product development. RaoidSoec and its export documentation is subject to change without notice. In no event shall HTPG
be liable for special or consequential damages in connection with the use or output of RapidSpec.
REV.1_Q178513 - Molly Moon's
SYS-1 - CDU-1 - Product Information
General Data
Model Line: NEXT-GEN MINI -CON
Model Number: RF0350L4SEA
Flooded: Yes
Refrigerant: R-448A
Voltage: 208-230/3/60
Compressor Type: SCROLL
Performance Data
Ambient Temp: 105 °F
Suction Temp: -22 °F
Capacity: 9,924 BTUH
Electrical Data
Compressor RLA: 10.9
Compressor LRA: 88
Total Condenser Fan FLA: 1
MCA: 25.6
MOPD: 35
Physical Data
Number of Compressors: 1
Compressor Model: ZF11K4E
Compressor HP: 3.5
Number of Condenser Fans: 2
Approx. Ship Weight: 255 Ibs
Sound Data: 73 dBA
Liquid Line: 3/8 in.
Suction Line: 7/8 in.
Pump Down Capacity (%): 90
Pump Down Capacity: 14.3 Ibs
Option Data
Mounted Option NO STANDARD DEFROST KIT
Mounted Option LIQUID LINE WITH COMPONENTS: SEALED FILTER & SIGHT GLASS
Mounted Option STANDARD RECEIVER
Mounted Option FIXED HIGH/ADJUSTABLE LOW PRESSURE CONTROL
Compliance Data
AWEF: 3.15
Notes
Quotes are valid for 30 Days. Due to ongoing product development. RapidSpec and its export documentation is subject to change without notice. In no event shall HTPG
be liable for special or consequential damages in connection with the use or output of RapidSpec. MCA/MOPD and Defrost Kit selection will be confirmed at time of
purchase. Submittal data shown represents design conditions.
Dimensional Drawing
LIQUII
OUT
MON
AIR
21-1/4
-- 24-3/16
Standard Features
• All-weather Galvanized steel painted housing
• Generously sized high efficiency condenser,
enhanced copper tubes/aluminum fins
• Integral Liquid Subcooling Circuit provides subcooled
liquid to the expansion device
• Crankcase heater
• Large electrical panel with hinged/removable door
• Color coded point-to-point wiring
Certifications
CONTROL
PANEL
7/8" KO (2)
FOR
LECTRICAL
)NNECTIONS
• Quick access to shut off valves from exterior
• UL/cUL certified for use with multiple refrigerants
• UL/cUL listed for outdoor use
• Flooded models include flooded head pressure
control
• Non flooded models include mild ambient fan cycle
control
REV.1_Q178513 - Molly Moon's
SYS-1 - UC-1 - Product Information
General Data
Model Line: NEXT-GEN ALL -TEMP Model Number: RL6E090DDA Motors: DUAL SPEED EC MOTOR
Unit Voltage: 208-230/1/60 Defrost Type: ELECTRIC DEFROST Refrigerant: R-448A
Fins Per Inch: 6 Number of Fans: 2
Performance Data
Suction Temp: -20 °F T.D: 9.9 °F Capacity: 10,454.1 BTUH CFM: 1550
Electrical Data
Motor Voltage: 208-230/1/60 Total Unit Fan Motor Amps: 1
Heater Voltage: 208-230/1/60 Heater Amps: 9.8 Heater Watts: 2250
MCA: 15 MOPD: 20
Physical Data
Liquid Line: 3/8 in. Suction Line: 7/8 in. Approx. Ship Weight: 58 Ibs
Option Data
Mounted Option EcoNet Control Package
Manual Option White Epoxy Cabinet Coating
Compliance Data
AWEF: 4.15
Notes
Quotes are valid for 30 Days. Due to ongoing product development. RapidSpec and its export documentation is subject to change without notice. In no event shall HTPG
be liable for special or consequential damages in connection with the use or output of RapidSpec. Submittal data shown represents design conditions. This quote contains
000tions that were manually added. All manually added options will require review by HTPG prior to orders being accepted.
Dimensional Drawing
16
(BACKSIDE)
Standard Features
• Embossed aluminum housing
• Enhanced copper tube and aluminum fin coil
construction
• Sweat connections
• Thermal overload protection
• High efficiency fan guard design and deep draw
venturi
• Heavy-duty fans are balanced for vibration -free
operation
Certifications
��pSSIFjFo
C UL uS
7/8 ELECTRICAL
KNOCKOUTS
(BACKSIDE)
-AIR
• Fan sections are baffled to prevent short cycling of air
• Slide out end panels
• Removable drain pan
• Mounts flush to the ceiling
• Top pan includes 1/2" wide slotted mounting points
• UL/cUL certified for use with multiple refrigerants
• NSF approved for use in food preparation areas