REVIEWED RESUB 1-BLD2023-0796+Manufacturer_Specifications_and_Installation_Instructions+7.17.2023_3.04.17_PM+3669884BLDG 2023-0796:
IL VIALE WALK IN COOLER MECHANICAL INFORMATION
RC! !nnn,gAAP CZA0000 -
BONN
REVIEWED
BY
CITYJ EDMONDS
❑ For Record For Approval
BLD2023-0796 ;SUBMITTAL
Project Name:
Project Location:
Quote ID:
Item A.
1000
Submitted For.,
Submitted On:
o
Submitted By:
Submitted From:
Identity A,
Tag:
By:.
Product Family.,
HTS
Application:
Outdoor
Temperature Range:
Medium Temp
Voltage: (Volts/Ph/Hz)
208-23011160
Refrigerant Type:
R404A
Piping:
Standard
Compressor Brand.,
Copeland
Compressor Type:
Scroll
Compressor Hp:
0.8
Compressor Model.,
ZB07KAE-PFV
Number of Compressor(s):
1
Coil Type:
Microchannel
Note : This equipment meets the regulatory requirements for hydrofluorocarbons as of the manufacturing date. Only those refrigerants approved in the state for specific end uses may be used.
=SUB
172023
OFEDMONDS
IPMENTSEREVICES_T_T
7 Ambient
Temperature (°F)
Saturated Suction
Temperature (°F)
Application Capacity*
(BTU/H)
Altitude
(k)
AWEF Value
95
25.0
8,980
0
7.6
Electrical Data
Compressor(s)Ik Fan Motors)
Electric Ratings
RLA LRA Quantity Hp FLA Defrost
High or
Number of MCA
MOPD Evap.Fan
Defrost
Type
Low Amps?
Contactors
Amps
Heater
Amps
5.6
48
1
1115
0.5
AIR DEFROST
15
15 5
15
I
IN&
-2
0
Connections (in.) Receiver 90% Full (Ibs)
Fan Blade(s)
Approx. Net
Sound Data
Diameter
Weight
7L,iqouid Line Suction Standard Over Sized
(in)
(de)
(Ibs)
.375 01.625 9
14
61
168
Dimensional •
AGENCY LISTINGS
0 @us
28 I/2
LIQUID
AIR FLOW
UCTION
9�
5 3/8
6 5/16
5L3/16,
— 24 3/8 CL —
3/4
— 25 1/8
23 Il2 CL
2 3/16
UOM: inches
Page 1 of 4
BCH0008MBACZA0000 -
ONN
SUBMITTAL
Project Name:
Project Location:
Quote ID:
Item A.
1000
Submitted For.,
Submitted On:
Submitted By:
Submitted From:
Identity A,
Tag:
CABINET AND CONSTRUCTION
MICROCHANNEL COIL TECHNOLOGY STANDARD ON ALL UNITS
SERVICEABILITY
SUCTION SERVICE VALVES FOR HERMETIC AND SCROLL COMPRESSORS
LOCATED OUTSIDE THE CABINET FOR QUICK INSTALLATIONS.
RECEIVER WITH FUSIBLE PLUG, LIQUID SHUTOFF VALVE AND CHARGING PORT IS
STANDARD
LARGE ELECTRICAL PANEL FOR EASE OF ACCESS
PREFABRICATED WIRING HARNESSES FOR TIGHT CRIMP CONNECTIONS AND
CONSISTENT LABELING
UNIT STAYS ON IF THE HOOD IS REMOVED FOR SERVICING
SIGHT GLASS IS EASILY VIEWABLE
Preferred Package Code - AOZ
Motor - FIXED SPEED EC
Receiver Options - STANDARD
Liquid Line Options - FILTER DRIER AND SIGHT GLASS
Discharge Line Options - HEAD PRESSURE VALVE 150#
Fused Disconnect - NO FUSED DISCONNECT
Crankcase Heater -CRANKCASE HEATER
Pre Charged - NONE
Hail Guard Factory Installed - NONE
Walls or Obstructions for
Horizontal Air Flow
AIR W*
FLOW MIN.
QUALITY
ALL UNITS ARE COMPLETELY LEAK TESTED IN A HELIUM ENVIRONMENT, BUMP
TESTED AND ALLOWED TO CYCLE OFF ON THE HIGH AND LOW PRESSURE
CONTROL. EACH UNIT HAS A COPY OF THE RUN DATA SHIPPED INSIDE THE
ELECTRICAL PANEL
ELECTRICAL CIRCUITS ARE COMPLETELY CHECKED FOR CONTINUITY
PIPING IS LAID OUT TO MINIMIZE STRESS AND VIBRATION AND IS PRE -BENT TO
ELIMINATE LEAKS
ENCAPSULATED, AUTO -RESET, HIGH AND LOW PRESSURE CONTROLS TO
ELIMINATE LEAKS (ADJUSTABLE LOW PRESSURE CONTROL STANDARD)
PAINTED STEEL CABINETS FOR SUPERIOR STRENGTH AND CORROSION
PROTECTION
HEAVY DUTY, STEEL, 1-1/2" TALL BASE
• Brand Label - BOHN
Coil Selection - MICROCHANNEL COIL
• Defrost Timer Options - NO TIMER
Suction Line Options - SUCTION TUBE ONLY
• Cabinet Selection - Painted
Pressure Options - ADJUSTABLE LOW - FIXED HIGH
Phase Loss Monitor - NONE
Snow Legs - NONE
Multiple Units with Horizontal Air Flow
AIR FLOW AIR FLOW
*W = W*
unit width MIN.
W* MIN. W* MIN.
4 �
' Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the Net Capacity
is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
Page 2 of 4
BEL0095AS6AMABO402 -
ELECTRICALLY COMMUTATED MOTOR, PER 410.2
SUBMITTAL
OHN
❑ For Record ❑ For Approval
Project Name:
Project Location:
Quote ID:
Item A,2000
Submitted For:
Submitted On:
By:.
Product Family.,
BEL
Motor type
Defrost Type:
Air
Number of Fans:
2
Voltage: (Volts/Ph/Hz)
115/1 /60
Fan HorsePower
1 /20
Refrigerant Type:
R448A
Fins per Inch
6
Performance Data
acity
Air Flow
Altitude
it
( )
AWEF Value
TO
(°F) 7CF)
Application Capacity`
(BTU/H)
CFM
Fan Diameter
(in.)
Air Throw (ft)
Standard
w/Collar
Cooler > 32
Freezer <= 32
10 1 25
10000
1305
12
20
0
9
N/A
Fan Motor(s)
Defrost Heater(s)
Drain Pan Heater(s)
Watts
Amps
Watts
Amps
Watts
Amps
110
1 1.8
Connections (in.) Approx. Net
Weight
Coil Inlet Suction External Equalizer Drain Side Port Hot Gas Drain Pan (lbs)
112 518 114 314 51
Dimensional Drawing(s)
7/8" ELECTRICAL
KNOCKOUTS
I II/16 c U� us NSF,
3 I/8
13/8
3 1/16 4 5/16
REFRIGERANT ELECTRICAL 131/4
CONNECTION END CONNECTION END
6 1/8 —I I� 33 1/47 6 1/8
16 7/16 AIR FLOWYj15
1�/16
3/4" MPT 114NPSI UOM4 inches 45 1/2 DRAIN CONNECTION 8
Page 3 of 4
BEL 0095AS6AMAB0402 -
ONN
SUBMITTAL
Project Name:
Project Location:
Quote ID:
Item A.
2000
Submitted For.,
Submitted On:
Submitted By:
Submitted From:
Identity A,
Tag:
EASE OF INSTALLATION SERVICE
ALL ELECTRICAL COMPONENTS FACTORY WIRED TO TERMINAL BOARD AND
IDENTIFIED, MAKING IT EASY TO FIELD WIRE THE UNIT
RELIABLE DURABLE
HEAVY GAUGE GRAINED ALUMINUM CABINET CLEANS EASILY AND LOOKS
ATTRACTIVE
MOLDED FAN GUARD AND ACCESS PANELS ARE MADE OF STRONG, DURABLE,
AND NSF AND UL SANITATION RATED PLASTIC MATERIAL
SWEAT CONNECTIONS TO REDUCE POTENTIAL FOR LEAKS
ELECTRICALLY COMMUTATED MOTOR, PER 410.21
Cabinet Type - Stucco
• Controller Option - Mechanical Thermostat
Drain Pan Type - Stucco
Fan Blade- Standard
Coil Fin Material - Aluminium
• UC Solenoid Voltage - 115
Nozzle PartNumber - L-3/4
f PLAN VIEW
11/2 H
2 y
PLAN VIEW AIR FLOW
1 N
One Evaporator
NOTE:
H =Total Height
evaporator
coil surface.
PERFORMANCE
• EC MOTORS STANDARD ON ALL MODELS FOR IMPROVED UNIT EFFICIENCY
VERSATILE
LARGE DIAMETER DRAIN HOLE (314 " ID) IS LOCATED TOWARDS THE BACK OF THE
UNIT
MINIMAL HEIGHT OF THE LOW PROFILE SERIES MAKES IT IDEAL FOR LOW CEILING
COOLERS
CABINET DESIGN FEATURES HINGED, REMOVABLE FRONT ACCESS PANELS ON
EACH SIDE FOR EASY ACCESS TO ELECTRICAL AND REFRIGERATION
COMPONENTS
LIQUID LINE SOLENOID WIRE HARNESS IS FACTORY -INSTALLED FOR QUICK
INSTALLATION
MOTORS PLUG INTO WIRING HARNESS FOR EASIER SERVICING
• HINGED, REMOVABLE DRAIN PAN FOR EASY AND SAFE ACCESS
PRE -DRILLED HOLES ON THE BACK OF THE UNIT FOR ROOM THERMOSTAT
• QUICK REMOVAL FAN GUARD/MOTOR ASSEMBLY FOR EASY SERVICE OR
REPLACEMENT OF AIR MOVER PARTS
• INTERNAL PANELS ARE ISOLATED FOR QUIET OPERATION
INTERNALLY ENHANCED TUBING AND FIN DESIGN FOR HIGHER EFFICIENCY
Coil Mechanical Option - Mounted Sporlan TXV / Std Sol
• Drain Pan Defrost Type - None
DTFD Option - None
Fan Guard - Molded
Hot Gas External Piping - None
• Valve Part Number- BBIDE-1-1/2-C
t t
1 V2 H 1 V2 H
y i
11/2H 3H 11/2H
Two Evaporators
" Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the Net Capacity
is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
Page 4 of 4