Loading...
BLD2023-0771_Manufacturer_Specifications_and_Installation_Instructions_6.19.2023_2.37.43_PM_3617366ELECTRICAL DATA U SERIES (VOLTAGE) V/PH OPER VOLTS* COMPR FAN MCA MAX FUSE** or CKT BRK AMPS MAX MIN LRA RLA FLA 018-A N 208/230/1 253 197 56.3 9.0 0.50 11.8 20 024-A (N) 62.9 10.9 0.50 14.1 25 030-A N 73.0 14.1 0.70 18.3 30 036-A (N) 77.0 14.1 1.20 18.8 30 048-A N) 124.0 18.5 1.20 24.3 40 D60-A N 152.5 23.7 1.45 31.1 50 036-A P) 208/230/3 253 197 71.0 9.0 1.20 12.5 20 048-A (P) 83.1 13.7 1.20 18.3 30 I 060-A P 110.0 15.9 1.45 21.4 35 036-A E) 460/3 506 I 414 38.0 5.6 0.60 7.6 15 048-A E 41.0 6.2 0.60 8.4 15 060-A (E) 52.0 7.1 0.80 9.7 15 LEGEND: FLA - Full Load Amps HACR - Heating, Air Conditioning, Refrigeration LRA - Locked Rotor Amps NEC - National Electrical Code RLA - Rated Load Amps (compressor) * Permissible limits of the voltage range at which the unit will operate satisfactorily ** Time -Delay fuse. Complies with 2007 requirements of ASHRAE Standards 90.1 A -WEIGHTED SOUND POWER (dBA) Unit Size Standard Rating (dBA) Typical Octave Band Spectrum (dBA, without tone adjustment) 125 250 500 1000 2000 40DO 8000 18 69 50.5 57.0 59.5 64.5 60.5 53.5 43.0 24 66 50.5 58.5 60.5 59.5 56.5 51.0 41.5 30 68 55.5 59.5 61.5 63.5 60.0 58.0 49.5 36 71 59.5 59.5 62.0 65.5 63.5 62.0 55.0 48 170 57.5 59.5 64.0 66.0 63.0 60.5 54.5 60 73 60.0 61.5 64.5 67.0 66.0 65.5 58.0 NOTE: Tested in accordance with AHRI Standard 270-08 (not listed in AHRI. A -WEIGHTED SOUND POWER (dBA) WITH ACCESSORY SOUND SHIELD Unit Size Standard Typical Octave Band Spectrum (dBA, without tone adjustment) Rating (dBA) 125 250 500 1000 2000 4000 8000 18 68 52.5 58.0 58.5 64.5 59.5 52.5 42.5 24 65 54.5 57.5 59.5 59.0 56.0 50.5 40.5 30 68 55.0 60.0 61.5 62.5 60.0 58.0 49.5 36 71 59.5 59.5 62.5 65.0 63.0 61.5 55.0 48 70 57.5 59.5 63.0 65.0 62.5 60.0 54.0 60 73 61.0 62.0 64.0 67.0 65.5 65.51 57.5 NOTES: Tested in accordance with AHRI Standard 270-08 (not listed in AHRI). Accessory sound shield will not accommodate unit sizes 18 and 24. CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE) 1-1 DIMENSIONS - ENGLISH V 00 r I d m z YE5 m y (b•1 O NO C N W N N MINIMUM UNIT SIZE MOUNTING PAD _DIMENSIONS Z3" H 42' _ 18,24 30.36.48.60 24" % 50" m 1 CLEARANCE REQUIREMENTS SINGLE UNIT APPLICATIONS' WITH LCIL LAC Ell WALL• ALLOW 6 IN MINIMUM CLEARANCE ON COIL SIDE AND COIL END AND 20 IN MINIMUM CLEARANCE OA FAN 51BE WITH FAN FACING WALL ALLOW' B IN MINIMUM CLEARANCE ON FAN SIDE AND 6 1N. ON COIL END AND 20 IN MINIMUM CLEARANCE ON COIL SIDE MULTI - UNIT APPLICATIONS• ALLOW 24 IN MINIMUM CLEARANCE EETWEEN FAN AND COIL SIDES OF MULTIPLE UNITS ARRANGE UNITS SO DISCHARGE OF ONE DOES NOT ENIER INLLT OF ANOTHER WHEN TWO UNIT, ARE INSIALLED ENU TO END WIIH THE COIL ENDS FACING EACH OTHER ALLOW 12 IN MINIMUN CLEARANCE BETWEEN UNIIS COMPRESSOR END SERVICE CLEARANCE: ALLOW 24 IN MINIMUM CLEARANCE ON COMPRESSOR ENU WHEN UNITS ARE STACKED OF I HE HE IS LESS THAN 40 IN OF CLEARANCE ABOVE IHE TOP GF TFE UNIT. IF THERE IS 40 IN CLEARANCE ABOVE UNIT AND IHE IOP PANEL IS ACCESSIBLE FOR REMOVAL ALLOW G IN. MINI UM CLEARANCE ON COMPRESSOR END FOR SERVICE IMPORTANT: WHEN INSTALLING SINGLE OR MULTIPLE UNIIS IN AN ALCOVE. ROOF WELL. OR PARIIALLY ENCLOSED AREA, ENSURE THERE I5 ADEOUATE VENTILATION TO PRE VLNI NECIAC UL AIION OF 'DOE AIR. 2 MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING ill' MUD E IS 55SF, MAX. 125'F. 3. SERIES DESIGNATION IS THE 13TH POSITION OF [HE UNIT MODEL NUMBER. 4. CENIER OF GRAVITY 4 3/16S ALL DIMENSIONS ARE IN 'INCHES" UNLESS NOTED. FIELD CONTROL SUPPL WRE ENTRY 7/8" HOLE W/GROMMET --oM VAPOR LINE CONN FEMALE SWEAT CONN. 0 318" LIQUID LINE FEMALE SWEAT CONN- IELD POWER SUPPLY CONN. HOLE SIZES PROVIDED: R 0 7/6" NOLE WIIH D 0 11I6 NNOCNOUI AND IONS 0 13B" NNOC80U1 MINIMA,�lo