Loading...
1400 9th AVE N AERO BARRIERAERDBARRIER. Air Sewing Technology from Aeroseal EDMONDS , LEIF HELLEREN CONSTRUCTION CO I 1400 9TH AVE N EDMONDS , WA 98020 DATE: 319I2023 BUILDING TYPE: Single Family Detached BEFORE SERVICE 3055.6 CFM of Leakage, equivalent to a 357.9 Square inch Hole, or 5.53 Air Changes per Hour [for your 3683 square -foot structure enclosing a volume of 33147 cubic feet] AFTER SERVICE 739.2 CFM of Leakage, equivalent to a 89.0 Square Inch Hole, or 1.34 Air Changes per Hour This corresponds to a 75.8% Reduction in Envelope Leakage NOTE: Envelope leakage and air -change results are calculated at a standard pressure of 50 Pa. ENVELOPE SEALING REPORT AEROBARRIER CASE ID: 8224 HARDWARE: AeroBarrier Connect TECHNICIAN: ENRIQUE ESTRADA L•i C 2C AW 60 03C 100 12I1D 14C Sealir; Time it lylirl:tes Pacific Partners Insulation North 6405 172nd st ne Arlington. Washington 98223 Phone: 360-435-9945 SmartSeal 6.0.2.11 (8224-141.141-141) 1 of 2 NOTES: a) A certified .HVAC..eontraotor.or rates should be used toassess the. need for enhanoeftalanced mechanical equipment as the desired leakage is reduced. b] This certificate provides results based on. an enclosure test. using positive pressure: Minal blower door test may sail be required.. STATE OF STRUCTURE AT TIME OF SEALING: Construction phase: Post Drywall Number of stories: 2 with basement Insulation type: Blown -in Attic construction: Vented Window count:. 30 • Door count: 8 Bathroom vent count: 4 • Range hood count: 1 Fireplace count: 1 • Supply & return register count: 2. SmadSeal 5.12.1:1 . (8224-141-1.41-141 ) 2 of 2 D INSTALLFD Building Products Residential Building Air Leakage Teat (1310wer 000r Tbsf) Results Permit #: House address or lot number. lea City; ❑ Zip: Cored. Floor Area 0): Ca ` Age of house: source (circle one): (1'�D Estimated Measured Results spell be reported as Air Changas per Hour at :fit Pascals (ACHO and 9s all be calculated as follows: ACHso c (CFM50 x 60Y Vaiume Where: CFM60 = Slower door fan flow at 50 Pascal pressure di#€erence Volume = Condlfioned Floor Area of the housing unit x ceiling height ,glower Door Test Result: I i 15 ACH40 CFMQ50Pa 7jCvS3 Ring (circle one if appllcable): Clean (!7D Slower Door Fan Loc�atiOn: t� dCO 9--weather Conditions: i certify that these blower door rosults are wGurate and determined easing Standard induatryr protocol. Company Nose. r Ta chnicISM Technician Sigrfaiure� - _ _ Date: a 7 z phone Number (& 4:6 2015 ipashtn&n gii6 FAsray Code refin"r-s: R4=4.€.Z Testing The buildia�g Or dwelling unit shalt be tested and verified as i>aving an air page rate of not exceediug 5 air cbang'ss par hour. Tom$ sisals be coaduated wills a blower door at a pressure of D.2 inches W.S. [5ti Pascals). Where (wired by the code aficia'1, testing sltaii be aantitECted by sn cpprayed tts#xd riE# TesEW—t the o £ h b e ar oo a'And shalt be pet�rmed at tittle a#'car ting area= of all pett=ttcns of the buildieg thermal cawhvpe. Luca visual inspection hss eaafrrnW sealing (see Table R482.4.1.13, operable windows and doors manufactured by small Bresinass shall be po rmitted to bs sealad off at tits+ frame prior sa tits mt- pACIple pi4RMCpM INSULA-TION SCt1T14, A am COMIA rMY, I.I.C. i07187TH Sim E ILLDING A, TACOMA, WA 98446 e P (253) 2-92--2315 e F (283) 341-4394 1R ww.PACIFiCPARTNERSiNSUiAilONSOUTH.COM