APPROVED FIR2023-0046+Fire_Alarm_Battery_Calculations+5.4.2023_4.14.08_PM+3526235Auxilary Power Supply Battery, Voltage Drop Calculations
Standby
Project: Edmonds Med Plaza Ste 202 Current Alarm Current
Model: Potter 1 0.06 0.06
Voltage drop calculations based on 14 gauge
wire, starting voltage 20.4
Length of circuit Voltage at
Device Description Current Draw one way end of line %Voltage drop
NAC 1-ntv 91 PI I-Iallwav
0
0
0
0
0
0
0
0
0
0
0
Total NAC 1
NAC 9-Qtv Suitp 9n1
0
1.21 250 18.486
0
0
0
0
0
0
0
0
0
0
0
0
0
Total NAC 2
NAc a-i it litp 9n9
H
1.3 250 18.3265
7
System Sensor SL-15 ca
0.043
0.301
2
System Sensor P2L-15 ca
0.054
0.108
1
System Sensor SCL-15
0.041
0.041
1
System Sensor PC2L-15
0.071
0.071
0
0
01
0
Total NAC 3
NAC 4-1 RI Ip 9n3
0.5211 19.40281
0
0
0
0
0
0
0
0
0
0
0
0
Total NAC 4
Auxiliary Power Draw
Total Power Draw
24 or 60 hrs.
Standby Power AH Required 24
5or10min
Alarm PowerAH Required 10
Total AH Required
Total Required +20%
Battery Required
Battery Supplied
1.11 300 18.2946
0.06 4.181
1.44
0.70
2.14
2.56
3
7
9.38
10.16
4.89
10.32
This Project is the complete remodel of this second floor space. The Building is not Sprinkled. There is an existing Addressable Fire Alarm System. We are adding
devices to meet the new configuration. There is an existing Auxiliary Power Supply that comes to the space. We will utilize that for our notification devices. We are
relocating existing smoke and heat detectors.
Device Schedule
Symbol
Description
Mounting
Quantity
FRCP
Fire Alarm Control Panel
Aux Pow sup
Auxiliary Power Supply
ANN
Annunciator
ounts to l or 2 gang box or l or
gang ring on 4" sq box
❑F
Manual Pull Station
Mgangrits ndeepe p4"sogang obor,
gang ring on deep 4" sq box
sD
Photoelectric Smoke Detector
Mounts to 1 gang box or 1 gang
ring on 4" sq box
HD
Heat Detector
Mounts to 1 gang box or 1 gang
ring on 4" sq box
DD
Duct Detector
eam Detector
wF
Sprinkler Waterflow Switch
Ts
Sprinkler Tamper Valve Switch
Es
Sprinkler Air Pressure Switch
MM
Addressable Monitor Module
Mounts to deep 4'cut box
DM
Addressable Dual Monitor Module
Mounts to deep 4' eq box
cM
Addressable Control Module
Mounts to deep 4• cut box
RM
Addressable Relay Module
Mounts to deep 4• sq box
QM
Quad combo Monitor/Relay Module
Mounts to deep 411n6°sq bex
zM
Conventional Zone Module
Mounts to deep 4 sq box w/ ext
and two gang ring or box w/l 1/2"
nng
IM
Isolator Module
Mounts to deep 4• sq box
Ceiling Strobe, Candela as Marked
Mounts to 1 gaanggboox or mudrng
Wall Strobe, Candela as Marked
Mountsmlgangbox ormudring
o 4" sq box
Ceiling Horn
Mounts to l gonggbox or mudring
on box
Wall Horn
Mounts to l gang box or mudring
on 4" sq box
I{ryl r,l
LJ V
Mini Horn
Mounts to l gang box or mudring
on 4" sq box
IS71/I
LSN
Ceiling Horn Strobe, Candela As Marked
Mounts to ogang box or mudring
4" sq box
Wall Horn Strobe, Candela As Marked
Mounts to o gang box or mudring
4" eq box
SP
Ceiling Speaker
Mounts to deep 4• eg box w/
extension
Wall Speaker
Mounts to deep 4' eq box w/
extensnon
ILSNsP
e
Ceiling Speaker Strobe, Candela As Marked
Mounts to deep 4• sq boxes/
extension
Wall Speaker Strobe, Candela As Marked
Mounts to deep 4• eq box w/
extension
OElectric
Bell
Mounts to Factory Box
°H
Magnetic Door Holder
Mounts to 1 gang box or ring
mountedto 4" so box, Must be
firmly fastened
FE
Firemen's Phone Jack
Mounts to 1 gang box or ring on 4"
sq box
EVAC
Voice Evacuation Panel
EALow
LF
Frequency Sounder
Mounts todeep 4"Sq
2nd Floor
1 st Floor
15 15 15 15 15 15 15 15 15 15 15
Existing SLC
B SD B SD B SD B SD B SD B SD B SD
FACP Auxiliary
,.at
Supply
Wire Table
Designation
Description
A
14/2 FPL
B
16/2 FPL
C
18/2 FPL
D
14/2 FPL Shielded
E
16/2 FPL Shielded
F
18/2 FPL Shielded
AR
14/2 FPLR
BR
16/2 FPLR
CR
18/2 FPLR
DR
14/2 FPLR Shielded
ER
16/2 FPLR Shielded
FR
18/2 FPLR Shielded
AP
14/2 FPLP
BP
16/2 FPLP
CP
18/2 FPLP
DP
14/2 FPLP Shielded
EP
16/2 FPLP Shielded
FP
18/2 FPLP Shielded
G
2-#14 THHN
H
2-# 16 TFFN
J
2-# 18 TFFN
05-18-2023 1W
PLAN REVIEW
NOTES: APPROVED WITH
CONDITIONS.
1. ENSURE A PULL STATION, SMOKE
DETECTOR AND DOCUMENT
CABINET ARE LOCATED AT THE
FACP AND POWER SUPPLY.
DFM BURT
II II I r�' I II II I
I I BREAK
From Existi , P I I EXAM I L — ROOM
SLC 7 208210 A [ ExistingExisting Device
Device EXAM 7 A Existing Device
El 5 Relocated F209 1 Relocated 15 Relocated
0 00SD
EXAM I / A
2
B
B
EXAM
205
15
WATER
HEATER
AT
HALLVVAY
os
B B
;TAIRK5
;i ing DeHi 15
=.I cated HD
sD
T LIT 04 A
B
J(IPRDERCE
s
15— Existing Device
sD Relocated
Existing Device B sD
Relocated B
A WAITING
REC ;ION 20oAn
5
sD Existiircuit
from existi g Power
Supply
N
a IMOM 111lI1L'[:1
RECEIVED
May 05 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
o i
O T
II�Cso
C\1
O
C\1
U
C/)
CZ
c�
N
N
o
CO
CIO
Ittn
r o
co
r E
N
0
W
Revisions
Revision
#
Date
Designed by: Harold Befus
Fire Alarm Systems NICET Level IV
Cert.
#110615, Exp. 3/1 /2025
Drawn By:
Scale: 1 /8" = V
Page No. FA-1
Date:5/4/23