APPROVED FIR2023-0015+Fire_Alarm_Battery_Calculations+2.23.2023_1.18.18_PM+3385313PROJECT INFORMATION
NAME: PSM CONSULTING - TI
ADDRESS: 7614 195TH STREET SW.
EDMONDS, WA 98026
SCOPE OF WORK
PRO COMM TO INSTALL A NEW ADDRESSABLE FIRE ALARM SYSTEM IN AN EXISTING
BUILDING. BUILDING IS NOT SPRINKLED AND IS DESIGNED WITH TOTAL COVERAGE. THE
FACP IS TO BE MONITORED BY AN APPROVED CENTRAL STATION. THE ANNUNCIATOR WILL
BE MOUNTED ON THE EXTERIOR OF THE BUILDING IN A HEATED NEMA ENCLOSURE
FIRE ALARM SYSTEM CONTRACTOR
NAME: PROCOMM PROTECTION & COMMUNICATIONS INC.
ADDRESS: 19630 40TH AVE WEST
LYNNWOOD, WA 98036
PHONE: (425) 774 - 9099
APPLICABLE CODES AND STANDARDS
NFPA 72 NATIONAL FIRE ALARM CODE 2019 EDITION
INTERNATIONAL BUILDING CODE 2015 EDITION
INTERNATIONAL FIRE CODE 2015 EDITION
NFPA 70 NATIONAL ELECTRICAL CODE 2020 EDITION
CIRCUIT LABELING LEGEND
DEVICE IDENTIFIER
SLC1 •###
CIRCUIT IDENTIFIER
ABBREVIATIONS
SLC = SIGNALING LINE CIRCUIT
NAC = NOTIFICATION APPLIANCE CIRCUIT
A
AMPERE
J-BOX
JUNCTION BOX
AFF
ABOVE FINISHED FLOOR
kV
KILOVOLT
AHU
AIR HANDLING UNIT
kVA
KILOVOLT AMPERE
AL
ALUMINIUM
kW
KILOWATT
AMP
AMPERE
kWh
KILOWATT HOUR
AWG
AMERICAN WIRE GAUGE
MFR
MANUFACTURER
BLDG
BUILDING
MECH
MECHANICAL
C
CONDUIT
MIN
MINIMUM
CB
CIRCUIT BREAKER
(A)
NEW
CCTV
CLOSED CIRCUIT TELEVISION
NAC
NOTIFICATION APPLIANCE CIRCUIT
CKT
CIRCUIT
NEC
NATIONAL ELECTRIC CODE
CLG
CEILING
NEUT
NEUTRAL
CO
CONDUIT ONLY
NFPA
NATIONAL FIRE PROTECTION ASSOCIATION
COMM COMMUNICATION
NC
NORMALLY CLOSED
CU
COPPER
NIC
NOT IN CONTRACT
DCV
DOUBLE CHECK VALVE
NO
NUMBER; NORMALLY OPEN
DIA
DIAMETER
NTS
NOT TO SCALE
DISC
DISCONNECT
OD
OVERHEAD DOOR; OVERALL DIAMETER
DN
DOWN
PIV
POST INDICATOR VALVE
DO
DOOR OPERATOR
PNL
PANEL
(E)
EXISTING
PVC
POLYVINYL CHLORIDE (PLASTIC)
EA
EACH
PWR
POWER
EF
EXHAUSTFAN
QTY
QUANTITY
ELEC
ELECTRIC
REQD
REQUIRED
ELEV
ELEVATOR
RH
RANGE HOOD
EMT
ELECTRICAL METALLIC TUBING
RMC
RIGID METALLIC CONDUIT
EOL
END OF LINE RESISTOR
SF
SUPPLY FAN; SQUARE FEET
EOLR
END OF LINE RESISTOR
SLC
SIGNALING LINE CIRCUIT
EXIST
EXISTING
SPEC
SPECIFICATION
F
FIXED
ST
SHUNT TRIP
FA
FIRE ALARM
STD
STANDARD
FAA
FIRE ALARM ANNUNCIATOR
TEL
TELEPHONE
FACP
FIRE ALARM CONTROL PANEL
TELCO TELEPHONE COMPANY
FAPS
FIRE ALARM POWER SUPPLY
TEMP
TEMPORARY
FARA
FIRE ALARM REMOTE ANNUNCIATOR
TS
TAMPER SWITCH
FBO
FURNISHED BY OTHERS
TYP
TYPICAL
FDC
FIRE DEPARTMENT CONNECTION
UGND
UNDERGROUND
FEC
FIRE EXTINGUISHER CABINET
UL
UNDERWRITERS LABORATORIES
FH
FIRE HYDRANT
UON
UNLESS OTHERWISE NOTED
FPL
FIRE POWER LIMITED
V
VOLT
FPLR
FIRE POWER LIMITED RISER
VA
VOLT AMPERE
FPLP
FIRE POWER LIMITED PLENUM
VAC
VOLTAGE, ALTERNATING CURRENT
FS
WATER FLOW SWITCH
VDC
VOLTAGE, DIRECT CURRENT
FSD
FIRE/SMOKE DAMPER
VR
VANDAL RESISTANT
G
GROUND
W
WATT
GEC
GROUNDING ELECTRODE CONDUCTOR
W/
WITH
GEN
GENERATOR
W/0
WITHOUT
HT
HEAT TRACE
WP
WEATHERPROOF
IDC
INITIATING DEVICE CIRCUIT
Z
IMPEDANCE
GENERAL NOTES
0
(DI71S
FIRE ALARM SYSTEM
DEVICE LEGEND
SYMBOL
MANUFACTURER
PART NO
DESCRIPTION
QTY
FACP
POTTER
IPA-100
FIRE ALARM CONTROL PANEL
1
NAC
POTTER
PSN-1000(E)
INTELLIGENT NOTIFICATION POWER EXPANDER
1
DACT
AES
7707P-88-ULP-M
INTELLINET 2.0 FIRE SUBSCRIBER, 8 ZONE WITH 7794A AES-INTELLIPRO, AND INTEGRATED ONBOARD LOCAL
1
ANNUNCIATOR PLUS MCT, RED ENCLOSURE
FAA
POTTER
RA-650OR
LCD RELEASING ANNUNCIATOR
1
POTTER
PAD100-PSSA
ADDRESSABLE PULL STATION SINGLE ACTION
1
IM
POTTER
PAD100-IM
ISOLATOR MODULE
1
O
POTTER
PAD200-HD W/PAD200-6DB
HEAT DETECTOR WITH 6" STANDARD BASE
9
O
POTTER
PAD200-PD W/PAD200-6DB
PHOTOELECTRIC SMOKE DETECTOR WITH 6" STANDARD BASE
53
o WP
POTTER
HS-24WR-WP
OUTDOOR HORN STROBE, FIXED 75 CANDELA, STANDARD ENCLOSURE, RED
1
POTTER
HS-24WW
HORN STROBE, 24 VDC, WHITE
5
a5C
POTTER
CHS-24W
HORN STROBE, CEILING, WHITE
10
\0/
/ \
C
POTTER
CS-24W
STROBE, CEILING, WHITE
23
POTTER
S-24WW
STROBE, 24 VDC, WHITE
5
• ALL FIRE ALARM SYSTEM WORK COMPLETED UNDER THE SCOPE OF THIS FIRE ALARM PLAN REVIEW SHALL BE FIELD
VERIFIED BY FIRE INSPECTION PERSONNEL AND THE FIRE CODE OFFICIAL.
• VISIBLE NOTIFICATION APPLIANCES SHALL REMAIN ACTIVE (FLASHING) WHEN THE AUTOMATIC AND MANUAL FIRE ALARM
SYSTEM IS SILENCED.
• FIRE ALARM SYSTEM SHALL TRANSMIT TROUBLE, SUPERVISORY AND FIRE SIGNALS DIRECTLY TO THE COMMUNICATIONS
CENTER REMOTE SUPERVISING STATION.
• MOUNT PULL STATIONS AT 42" AT ACTIVATOR WITHIN 5' OF LATCH SIDE OF EXIT DOORS
• MOUNT AUDIO VISUAL DEVICES AT 80" ABOVE FLOOR LEVEL
• A DEDICATED 120VAC, 20A BRANCH CIRCUIT BREAKER SHALL BE PROVIDED, MARKED IN RED, LOCK -ON PROVISION AND
IDENTIFIED AS "FIRE ALARM CIRCUIT CONTROL". THE LOCATION OF THE CIRCUIT BREAKER WILL BE PERMANENTLY
IDENTIFIED AT THE FIRE ALARM CONTROL UNIT.
• NEW FIRE ALARM SYSTEM WILL BE CONNECTING TO THE EXISTING AES RADIO COMMUNICATOR.
FIRE ALARM CABLE AND WIRE LEGEND
LABEL
WIRE TYPE
MFR.
PART NO.
AWG
RESISTANCE
(4/Mft)
DESCRIPTION
A
COMTRAN
38697
18
6.7000
2 COND. SOLID COPPER FPLP ANALOG UNSHIELDED
B
-------------------
COMTRAN
38700
14
3.07
2 COND. SOLID COPPER FPLP ANALOG UNSHIELDED
C
COMTRAN
38697
18
6.7000
4 COND. SOLID COPPER FPLP ANALOG UNSHIELDED
TYPICAL DEVICE MOUNTING DETAIL
ROOF DECK
MOUNT TO
STRUCTURE
BASE HEAD
J-BOX ABOVE CEILING
J-BOX
DEVICE
SUPPORT
SUPPORT
BRACKET
N/A VIA
BRACKET
I
PLASTER RING CEILING
BASE HEAD
CEILING MOUNT
SMOKE OR HEAT DETECTOR
NOTIFICATION APPLIANCE
WALL MOUNT
NOTIFICATION APPLIANCE
FIRE ALARM
CONTROLPANEL
FIRE ALARM
ANNUNCIATOR
0
MANUAL
MIXIM 9
Sl
mmtn
OOeoo
®
PULL
STATION
FIRE
ALARM
O
72" 60" 80"
48"
if
Approved
DFM c lhy s gurt
South County Fire
Date: 03/03/2023
Mill Creek Adutt ft
Famfly Homes. Inc
b
194th sc Sw f 1946 St Sw
a
Pro Piano Move, inc
9 El
3
a
194lh PI SW
qt00 N
N0)co ai
� N , 0 I �}
�41
0 0
D 00 `-
Q
��00
W V
\ }
1(I o
V
O
iYHG
I .
LL �N }
y0
v r\
m"I^°
014
�
o 000
0Z„3
.0L3
LOW VOLTAGE SYSTEMS BY�f
/001
prollar""i
PROTECTION 6 COMMA N IC AT I QN INC.
19630 40-FH AVE WEST
LVNNWOOD, WA 98036
C4z5:)-7-7-4-9099
I Weddings
& Events
tsstsw
srti
lJJ
H
It
Learning Fun
Q
For Everyone
0
e A Dllnd America
Strictly Lashes
98n4=shoo `�'
Deal $eal
Royal India Fine
o�Igmnuy si so if'�
❑ruing &Catering
,
p
�
�
GTOw with Us Preschool
and Child Care
9Love ri Care Daycare
d
0
p
4
A round the Ta hie
Boarcigame Pub
B Thai Cuisine
9Olivia BIF
erne a.�e
rn.1
EdmGrids iS ndeTCare
0
w
Betty Brite Cleaners
ww
Sea-Mounta[n InsuranceL
8
r
Olympic West Apa�ment�
T
El
-
Rite Aid
Drug s ere
Edmonds Ridge
Apartments
-4
N
VICINITY MAP
SHEET INDEX
SHEET NO.
SHEET DESCRIPTION
FA0.1
TITLE SHEET
FA1.1
FLOOR PLAN - FIRE ALARM SYSTEM
FA2.1
FIRE ALARM RISER DIAGRAM & CIRCUIT CALCULATION
F2.2
FIRE ALARM RISER CIRCUIT CALCULATIONS
03-03-2023
PLAN REVIEW
APPROVED WITH CONDITIONS:
1. KNOX BOX REQUIRED AT
NEAR ANNUNCIATOR PANEL.
2. INSTALL DOCUMENT BOX
NEAR FACP.
DFM BURT
FIRE ALARM SYSTEM OUTPUTS
FACP & C.S. NOTIFICATION
ANNUNCIATORS MONITORING & CONTROL EQUIPMENT
9
O�S,oFij,O SF,L OTlL9
O T
L % /
OHO` F/G SGq
S q G,o 'Qy �9 9A
s�X%
FIRE ALARM SYSTEM INPUTS
SYSTEM SMOKE/HEAT DETECTORS
MANUAL PULL STATION
SYSTEM TROUBLE
BATTERY FAULT
101
OPEN CIRCUIT/SHORT
GROUND FAULT
LOSS OF PRIMARY POWER
GENERAL NOTES:
• REFERENCE NUMBERS ARE SHOWN IN PARENTHESES (1) FOR "NOTES / NOTATIONS" INDICATED BELOW AND IN
HEADINGS TO THE RIGHT
J
O
ADRIAN M. STEIK
Senior Engineering Technician, Level 4
NICET Certifcation Number: 093706
Authorizing Signature: C� K—� 0'. 1,
0
Z
I I
�0
�Z
"0
f's W
DRAWN BY: CNG
W
j
CHECKED BY: Adrian M. Steik
PLOT DATE: 2 / 14 / 2 3
PROJECT NUMBER: 2 3 —011
RECEIVED
FIR2023� 0015 Feb 24 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT I FA011
DRAWING ONLY TO SCALE IF PLOTTED AT 24" X 36"
SHEET NUMBER:
SLC•061
OPEN EXAM AR
r-- ---------------------
SLC•062
PS1•NAC2.09 EOL
4AB 75cd
I C
I S
I J
I
I
0 i SLC• 0
o
Q
z 70/ \
U
�LC-)Uj
I
I
i S
I
N \ / SLC•059
T
SLC•058
d
I
:LOUNGE
TOIL /PS1•NAC2.06 r
/ \15cd
SLC•056
�� C S PS1 •NAC2.05
SLC•057 30cd
C
S
OFFICE
4SLC*038
'
I �
PS1•NAC2.0' a oM
15cd i--- O
C
SLC•0S7TORAGE
SLC• 36
S
P-LINK•2 TORAGE i I
PS1 I ��s
NAC 71
- ------ ----- O --I
PS1 •NAC1.01
60cd
I
I H
V SLC•035
HR TO FAA
WAITING
SLC•053
S C
I
I
I
I
PS1•NAC2.04
30cd
C
I
I
I
I
I
ECEPTIiON
-(��-4BOOKE&ING
SLC•054
\�✓
------------
PS1 •NAC2.03
30cd
C
HALL
S SLC•040 S
SLC•048
PS1-NAC1-03
• 15cd
15cd 1 d
C / __ C /
-- - /�\
H H H
MECH/ELEC/EQUIPMENT
SLC•034
LEVEL 1 - FIRE ALARM SYSTEM
SCALE = 3/16" - 1'0" 0 4' 8' 12' 16'
CONDTION:
KNOX BOX REQUIRED NEAR
ANNUNCIATOR.
P-LINI. .
T - >HR TO FACP
OFFICE
S
SLC•052
C PTION
S
SLC•C
FLAG NOTES
WALL MOUNT DETECTOR WITHIN 36" HORIZONTALLY OF CEILING
PEAK AND 4" DOWN.
P� ANNUNCIATOR TO BE MOUNTED IN HEATED NEMA ENCLOSURE
HR TO FACP<
SLC•027
iS I
--------
-----------i
\ 1
1 15
WAITING
71c7d
\ /
COUNSELING RM
/ \
SLC•050
I
z O
/PS1
o
•NAC1.13
15cd
S '
PS1•NAC1.16
EOL
o
30cd
U
S
C
`n 1 '
I
SLC•028
S
I
I
I
i
COUNSELING RM
PS1 •NAC1.06
75cd SLC•046
CO ______^S r----------I
I SLC•047
I I I
I I o
I
i
i
PS1•NAC1.12
1
_
^l
I
I\&
\ / PS1•NA
--
•07 ---�I
I
\ /
15cd -- _�
LC 029
S
I
15cd
/ \
C
I SLC•045
-
i
PS1•NAC1.10
SLC 044
i
I
15cd
I
I
LAB
COUN'ISE RM
I
O
/ \ C
U�SELING RM
I
a
z
I
C\
"J y PS1•NAC1.05
15cd /
15cd -----�
a
�
I
/C\ 15cd
C / \
I
0- co
C
I
1
SLC•030
I
SLC•032 i
SLC•033
I
S
SLC•031
/ I \ ----r
J PS1•NAC1.09
LOUNGE
COUNSELING RM
15ccCOUNSELING RM
PLAN NORTH
S
OFFICE
S
SLC•022
r-------------
UI
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
NjAC2�•p7 EOL 5.1k
1 �' \ /
C /Q\
H
NAC2.06
75cd
C
RS&ME
s
SLC•01
Printer) PLOTTER
I u SLC•016
S STORAGE NAC1.01
N'5cd
C2.05jSLC•023
I
C I
I
I
I
I
I
I------------
FE
SLC•007
NAC1.11 S
15cd
/ I \
I
MASSAGE
I
I
I
I
I
I
I
S �SLC
I
NAC1.1 V/
15cd ROOM A
® fc STORA E AREA WP
• w r SLC•015 r^--- -- O
SLC•026 15cd cn S r^
S /��---;>HR TO FACP CONDITION:
I I INSTALL A DOCUMENT
]CABINET.
S BREAK KITCHEN SL 4 F FACP IFDAC7T
10o N
N (n 00 o,
LLok-
N�
C=
r j� /i \0 0
lJ 1 O
_
U
00 O
t�
Q
nnV),
00 V
J
O
W L
/Q I O
cm0
V rcm
V
Q
\0 N
oCHrn3.
0�00 .'
LL N +
Y 0
U � �
m I^U
O
000
ti
00Z�
03
LOW VOLTAGE SYSTEMS 8Y 4
LMPraromm
axoi[ciod a coHNUNlc aria HS Nc.
19630 40TH AVE WEST
L'%/N"WOOD, WA 98036
(:4 z 5 Do--7- -7-4-9099
w
0
z
O
w
C
0
m
ADRIAN M. STEIK
Senior Engineering Technician, Level 4
NICET Certifcation Number: 093706
Authorizing Signature: 6- ol• I'D
NAC1. 2 i
*TC'I
NAC1.03 15cdI W---1
C•025 15cd I
NA�2.04 \ / - � SLC•011 C
I 15cd •02---------------- \ /
C 5cd / i\ t
I S
SI
SLC•001 ' w N
I v1 rn
0
r---------------
SLC•013o EXAM ROOM W
p NAC2.03 S " W
zoo W 0
LOBBY � cd SLC 010 WAITI 4G
7 UM=
W
I
�Q
I Q
I _ ____��\ S J J RECEPTION / M I SLC•002
WAITING •012 I 1 NAC1.06
15cd i W
SLC•009 A C i T
S NAC1.05 :EXAM I ZOOM
-------- 15cd LL
1 C I 0 I I I ^
NAC1•' EOL 5.1k NAC1.07
0 75cd S SLC•063 30cd
2
C r------------ 0O O Z
F-- <
V
S � J
SLC•003 O
S SLC•005
\ /
-----------------
NAC1.09
15cd ROOM B
LEVEL 2 - FIRE ALARM SYSTEM
SCALE = 3/16" -1'0" 0 4' 8' 12' 16'
S SLC•004 i
\ / j
-------------- ----
NAC1.08 &X M
- ROOM C
L.L
�W w W
J
H
RECEPTION I-
w �JJ
2
RECEIVED
Feb 24 2023 DRAWN BY: CN6
CITY OF EDMONDS
DEVELOPMENT SERVICES Adrian M. Ste i k
DEPARTMENT CHECKED BY:
PLAN NORTH PLOT DATE: 2/14/23
PROJECT NUMBER: 2 3 -O 11
FA1 1
DRAWING ONLY TO SCALE IF PLOTTED AT 24" X 36"' SHEET NUMBER:
NAC2.07 EOL 5.1 k
NAC2.06
NAC2.05
NAC2.04
NAC2.03
NAC2.02
NAC2.01
15cd
75cd
15cd
15cd
75cd
15cd
15cd
C----- - - - -
-C-------
C--------
C--------C
--------
C------
C
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
FIRE ALARM
CONTROL PANEL
NACl-12 EOL 5.1k NAC1.11 NAC1.10 NAC1.09 NAC1.08 NAC1.07
NAC1.06
NAC1.05
NAC1.04
NAC1.03
NAC1.01
75cd 15cd 15cd 15cd 15cd 30cd
15cd
15cd
30cd
15cd
NAC1.02
75cd
C C C C C C
- - - - - - - - ------------------
C
C
C
\ C
15cd
p
WP
�• DeDICATED i2av
�� 20 AMP CIRCUIT
LEVEL 2
I
LEVEL
I
I
I
I
I
I
I
I
P-LINK•1
ANNUNCIATOR
PS1•NAC1.16 EOL ® •
PS1•NAC1.13 PS1•NAC1.14 PS1•NAC1.15 30cd
15cd 30cd 15cd C
I I
I I
I
I P-LINK4
PS1
PS1•NAC1.08 PS1•NAC1.07 PS1•NAC1.06 PS1•NAC1.05 PS1•NAC1.04 PS1•NAC1.03 PS1•NAC1.02
j PS1•NAC1.12 PS1•NAC1.11 PS1•NAC1.10 PS1•NAC1.09 15cd 15cd 75cd 15cd 15cd 15cd 15cd PS1•NAC1.01 NAC EXPANDER
1,15cd 30cd 15cd 15cd C C C C C C C 60cd POWER SUPPLY
-------- - - - - - - - - - - -
-------------------- - - - - - - - - ----------------------------- - - - - - - - - ----------�-------------------
- - - - - - - - I
I
x�DEDICATED 120V
G 20 AMP CIRCUIT
PS1•NAC2.09 EOL PS1•NAC2.08 PS1•NAC2.07
PS1•NAC2.06 PS1•NAC2.05
PS1•NAC2.04
I
I
PS1•NAC2.03 PS1•NAC2.01
75cd 15cd 15cd
15cd 30cd
30cd
30cd PS1•NAC2.02 115cd
C C C
- - - - - - - - - - - - - - - - - - - -----------
C C
--------- - - - - - - -
C
- * - - - - - - - -
C 30cd I C
-�7------------------0�
FIRE ALARM RISER DIAGRAM
SCALE = NOT TO SCALE
SLC•001 SLC•002 SLC•003 SLC•004 SLC•005 SLC•006 SLC•007 SLC•008 SLC•009 SLC•010
SLC•014
SLC•013
SLC•011 _ SLC•012
SLC•015 SLC•016 SLC•017 SLC•018 SLC•019 SLC•020 SLC•021 SLC•022 SLC•023 SLC•024 SLC•025
S S S S H S S S S H
SLC•026
SLC•027 SLC•028 SLC•029 SLC•030 SLC•031 SLC•032 SLC•033 SLC•034 SLC•035 SLC•036 SLC•037 SLC•038
SLC•048 ,-• SLC•047 - SLC•046 SLC•045 SLC•044 - SLC•043 SLC•042 - SLC•041 - SLC•040 ,-• SLC•039
SLC•049 /� SLC•050 /� SLC•051 /� SLC•052 /� SLC•053 /� SLC•054 /� SLC•055 /� SLC•056 /� SLC•057 SLC•058 SLC•059
SLC•062 _ SLC•061
SLC•060
LEVEL 2
LEVEL 1
RECEIVED
Feb 24 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
L
c
LLMI
LLM LLJ
CJ]
t�
J
Cn C-.1)
z
cm
1po
N (� 000 0,
N
H
�rh\
o
D o
VV1
V1 � Q)
of LL. O
QIo 0
U
o�\0.N
OLHrn�
o��o
LL N
Y o V)
U � �
m"I
0
o00 ho ti
0z
00
LOW VOLTAGE SYSTEMS BY
�Proromm
Pxoi[-- ...... .
19630 40TH AVE WEST
L'%/N"WOOD, WA 98036
Lu
Q
0
Z
O
w
C
ADRIAN M. STEIK
Senior Engineering Technician, Level 4
NICET Certifcation Number: 093706
Authorizing Signature:
IMM
in
an
LU
-
U)
Q
LU
LL
z
0
Q
U
J
U
LU
-
Q
F-
orf
W Q
J N
I- LLJ
LU �
W
W of
2
61
DRAWN BY: CNG
CHECKED BY: Adrian M. Steik
PLOT DATE: 2 / 14/ 2 3
PROJECT NUMBER: 2 3 -O 11
1
DRAWING ONLY TO SCALE IF PLOTTED AT 24" X 36" SHEET NUMBER:
1po L1
LLMIN (� 000 0,
N�
��
W ��\
0
_ U
D W d
Q V)
00 Q)
J O
�_ j LL
CJ'K$x Q I O o
0
c� � N
oCHrn�
o���
LL N +
Y o
U V)
H T e-, U
00 O "
OOO 0
O Z � 3
��a
SOW VOLTAGE SYSTEMS BY��
�placomm /001
P•orE „o� . �...... a„..s I-
19630 40TH AVE WEST
LVN"WOOD, WA 98036
w
0 7
z
O
w
c
0
m
ADRIAN M. STEIK
Senior Engineering Technician, Level 4
NICET Certlfcatlon Number: 093706
Authorizing Signature: ��C. = 0%.
W
co
0 ''ww N
vl J
O W
W�
W
Z
�Q O
J �
vl �
J
Q
vi U
0
Ln W
Q
l� 0 O m
V
�O U
�W
LLi Q
J N
H LL
� W
W Cf
w
w �
2
DRAWN BY: CNG
RECEIVED CHECKED BY: Adrian M. Steik
Feb 24 2023 2/14/23
PLOT DATE:
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT 2 3 -011
PROJECT NUMBER:
FIRE ALARM BATTERY & CIRCUIT CALCULATION
BSCALE = NOT TO SCALE
1
DRAWING ONLY TO SCALE IF PLOTTED AT 24" X 36" SHEET NUMBER:
BATTERY CALCULATION
(SECONDARY POWER SOURCE REQUIREMENTS)
PANEL POWER SUPPLY MAX CURRENT = 5A
TOTAL USED CAPACITY (IN ALARM) = 3.0228A (60.46 %)
STANDBY CURRENT (AMPS)
SECONDARY ALARM CURRENT (AMPS)
QTY
PART N0.
DESCRIPTION
CURRENT DRAW (A)
TOTAL (A)
CURRENT DRAW (A)
TOTAL
PANEL COMPONENTS
Main Board for IPA-100 Fire
1
IPA-100 MAIN BOARD
Alarm Control Panel
0.13
0.13
0.22
0.22
CIRCUIT
SYMBOL
QTY
PART NO
DESCRIPTION
CURRENT DRAW (A)
TOTAL (A)
CURRENT DRAW (A)
TOTAL (A)
�o
2
CHS-24W
Horn Strobe,
C
NAC1 LUMP SUM REPORT
CIRCUIT
SETTINGS
TOTALS
Starting Calculation Voltage:
20.4
Max. Voltage Drop:
1.85
Min. Operational Voltage:
16
End Of Line Voltage:
18.55
Max. Circuit Current (A):
3
Voltage Drop Percent:
9.06
Wire Resistance (4/kFt):
3.07
Total Circuit Current (A):
1.673
Circuit Wiring Properties: 'V' 14/2 FPLP/R (NAC) 14 AWG, 2 Cond. Solid Copper FPLP/R Analog Unshielded
Total Circuit Length (Ft):
180
Spare Current (A):
1.327
Distance measured using drawn segment lengths with 10.00 %additional length calculated
Total Circuit Resistance (4):
1.105282
Spare Current (A) Percent:
44.23
Symbol
Part No.
Description
Qty.
Device Current (A)
Total Current (A)
�o
HS-24WW
Horn Strobe, 24 VDC, White
15cd
1
0.098
0.098
/o\ C
CS-24W
Strobe, Ceiling, White 15cd
7
0.12
0.84
DEVICE TOTALS
�o C
CHS-24W
Horn Strobe, 30cdiling, White
2
0.143
0.286
�o C
CHS-24W
Horn Strobe,
5 defiling, White
1
0.223
0.223
�o WP
HS-24WR-WP
Outdoor Horn Strobe, Fixed
75 Candela, Standard
Enclosure, Red 75cd
1
0.226
0.226
Calculation Methods:
Total Resistance (f�) =Wire Resistance (4/Ft) x 2 x Total Circuit Length (Ft)
Total Voltage Drop =Total Resistance (4) x Total Circuit Current (A)
NAC2 LUMP SUM REPORT
CIRCUIT SETTINGS
TOTALS
Starting Calculation Voltage:
20.4
Max. Voltage Drop:
0.89
Min. Operational Voltage:
16
End Of Line Voltage:
19.51
Max. Circuit Current (A):
3
Voltage Drop Percent:
4.35
Wire Resistance (4/kFt):
3.07
Total Circuit Current (A):
1.046
Circuit Wiring Properties: 'V' 14/2 FPLP/R (NAC) 14 AWG, 2 Cond. Solid Copper FPLP/R Analog Unshielded
Total Circuit Length (Ft):
138
Spare Current (A):
1.954
Distance measured using drawn segment lengths with 10.00 %additional length calculated
Total Circuit Resistance (4):
0.848785
Spare Current (A) Percent:
65.13
Symbol
Part No.
Description
Qty.
Device Current (A)
Total Current (A)
DEVICE TOTALS
C
CS-24W
Strobe, Ceiling, White 15cd
5
0.12
0.6
o' C
CHS-24W
Horn Strobe, Ceiling, White
75cd
2
0.223
0.446
Calculation Methods:
Total Resistance (4) =Wire Resistance (4/Ft) x 2 x Total Circuit Length (Ft)
Total Voltage Drop =Total Resistance (f2) x Total Circuit Current (A)
P-LINK LUMP SUM REPORT
CIRCUIT
SETTINGS
TOTALS
Starting Calculation Voltage:
24
Max. Voltage Drop:
0.22
Min. Operational Voltage:
18
End Of Line Voltage:
23.78
Max. Circuit Current (A):
1
Voltage Drop Percent:
0.90
Wire Resistance (4/kFt):
7.77
Total Circuit Current (A):
0.065
Circuit Wiring Properties: 'PLINK+' 18/4 FPLP/R (P-LINK/PWR) 18 AWG, 4 Cond. Solid Copper FPLP/R Analog
Unshielded
Total Circuit Length (Ft):
214
Spare Current (A):
0.935
Distance measured using drawn segment lengths with 10.00 % additional length calculated
Total Circuit Resistance (4):
3.331499
Spare Current (A) Percent:
93.50
Symbol
Part No.
Description
Qty.
Device Current (A)
Total Current (A)
DEVICE TOTALS
NAc
PSN-1000(E)
Intelligent Notification Power
Expander
1
0.015
0.015
Faa
RA-6500R
LCD Releasing Annunciator
1
0.05
0.05
Calculation Methods:
Total Resistance (f�) =Wire Resistance (4/Ft) x 2 x Total Circuit Length (Ft)
Total Voltage Drop =Total Resistance (4) x Total Circuit Current (A)
PANEL PS1 (PSN-1000(E)) BATTERY CALCULATION
(SECONDARY POWER SOURCE REQUIREMENTS)
PANEL POWER SUPPLY MAX CURRENT = 10A
TOTAL USED CAPACITY (IN ALARM) = 3.1A (31.00 %)
STANDBY CURRENT (AMPS)
SECONDARY ALARM CURRENT (AMPS)
QTY
PART N0.
DESCRIPTION
CURRENT DRAW (A)
TOTAL (A)
CURRENT DRAW (A)
TOTAL
Main Board for PSN-1000(E)
PANEL COMPONENTS
1
PSN-1000(E) MAIN BOARD
Intelligent Notification Power
0.06
0.06
0.2
0.2
Expander
CIRCUIT
SYMBOL
QTY
PART NO
DESCRIPTION
CURRENT DRAW (A)
TOTAL (A)
CURRENT DRAW (A)
TOTAL (A)
`o
1
CHS-24W
Horn Strobe, White
o
0
0
0.143
0.143
C
defiling,
Horn Strobe, Ceiling, White
o' C
1
CHS-24W
75cd
0
0
0.223
0.223
/�\ C
6
CS-24W
Strobe, Ceiling, White 15cd
0
0
0.12
0.72
PS1•NAC1
�0
2
HS-24WW
Horn Strobe, 24 VDC, White
0
0
0.114
0.228
30cd
�0
1
HS-24WW
Horn Strobe, 24 VDC, White
0
0
0.153
0.153
60cd
�\
5
S-24WW
Strobe, 24 VDC, White 15cd
0
0
0.042
0.21
Horn Strobe, Ceiling, White
�o C
2
CHS-24W
0
0
0.143
0.286
Horn Strobe, White
o
1
CHS-24W
cdeiling,
0
0
0.223
0.223
PS1-NAC2
C
/0\
5
CS-24W
Strobe, Ceiling, White 15cd
0
0
0.12
0.6
C
Horn Strobe, 24 VDC, White
�0
1
HS-24WW
30cd
0
0
0.114
0.114
TOTAL STANDBY (A)
0.06
TOTAL ALARM (A)
3.1
REQUIRED STANDBY TIME = 24 HOURS
REQUIRED ALARM TIME = 5 MINUTES
SECONDARY STANDBY LOAD (A)
0.06
24
1.44
SECONDARY ALARM LOAD (A)
3.1
0.08
0.26
STANDBY AND ALARM SUBTOTAL (AMP HOURS)
1.7
DERATING FACTOR
1.2
SECONDARY LOAD REQUIREMENTS (AMP HOURS)
2.04
PROVIDE (2) 12V 7AH BATTERIES
*BATTERY BOX SIZE CAPACITY NOT SPECIFIED. REFER TO MANUFACTURER DOCUMENTATION.
PS1 NAC1 LUMP SUM REPORT
CIRCUIT
SETTINGS
TOTALS
Starting Calculation Voltage:
20.4
Max. Voltage Drop:
1.92
Min. Operational Voltage:
16
End Of Line Voltage:
18.48
Max. Circuit Current (A):
3
Voltage Drop Percent:
9.39
Wire Resistance (t2/kFt):
3.07
Total Circuit Current (A):
1.677
Circuit Wiring Properties: 'B' 38700 14 AWG, 14 AWG 2 COND. SOLID COPPER FPLR UNSHIELDED
Total Circuit Length (Ft):
186
Spare Current (A):
1.323
Distance measured using drawn segment lengths with 10.00 %additional length calculated
Total Circuit Resistance (4):
1.142843
Spare Current (A) Percent:
44.10
Symbol
Part No.
Description
Qty.
Device Current (A)
Total Current (A)
S-24WW
Strobe, 24 VDC, White 15cd
5
0.042
0.21
�o
HS-24WW
Horn Strobe, 24 VDC, White
30cd
2
0.114
0.228
DEVICE TOTALS
/�\ C
CS-24W
Strobe, Ceiling, White 15cd
6
0.12
0.72
o' C
CHS-24W
Horn Strobe,
0 defiling, White
1
0.143
0.143
�o
HS-24WW
Horn Strobe, 24 VDC, White
60cd
1
0.153
0.153
o C
CHS-24W
Horn Strobe, Ceiling, White
1
0.223
0.223
Calculation Methods:
Total Resistance (f�) =Wire Resistance (S2/Ft) x 2 x Total Circuit Length (Ft)
Total Voltage Drop =Total Resistance (4) x Total Circuit Current (A)
PS1 NAC2 LUMP SUM REPORT
CIRCUIT SETTINGS
TOTALS
Starting Calculation Voltage:
20.4
Max. Voltage Drop:
1.05
Min. Operational Voltage:
16
End Of Line Voltage:
19.35
Max. Circuit Current (A):
3
Voltage Drop Percent:
5.16 %
Wire Resistance (4/kFt):
3.07
Total Circuit Current (A):
1.223
Circuit Wiring Properties: 'B' 38700 14 AWG, 14 AWG 2 COND. SOLID COPPER FPLR UNSHIELDED
Total Circuit Length (Ft):
140
Spare Current (A):
1.777
Distance measured using drawn segment lengths with 10.00 %additional length calculated
Total Circuit Resistance (4):
0.860892
Spare Current (A) Percent:
59.23
Symbol
Part No.
Description
Qty.
Device Current (A)
Total Current (A)
HS-24WW
Horn Strobe, 24 VDC, White
30cd
1
0.114
0.114
��\ C
CS-24W
Strobe, Ceiling, White 15cd
4
0.12
0.48
DEVICE TOTALS
\ /
/�\ C
CS-24W
Strobe, Ceiling, White 30cd
1
0.12
0.12
o' C
CHS-24W
,o defiling, White
Horn Strobe30cd
2
0.143
0.286
d C
CHS-24W
Horn Strobe, Ceiling, White
75cd
1
0.223
0.223
Calculation Methods:
Total Resistance (4) =Wire Resistance (4/Ft) x 2 x Total Circuit Length (Ft)
Total Voltage Drop Total Resistance (t2) x Total Circuit Current (A)