APPROVED PLN BLD2023-0934+Mechanical_Plan+7.26.2023_7.08.33_AM+3688841GENERAL NOTES - MECHANICAL 1. REFERENCE TO RELATED WORK: "REF" INDICATIONS DENOTE WORK COVERED ELSEWHERE (ARCHITECTURAL, STRUCTURAL, CIVIL, ELECTRICAL, LANDSCAPE, OR KITCHEN), OR ITEM BASED ON A SPECIFIC MANUFACTURER'S DIMENSIONS (VERIFY). 2. ELECTRICAL CHARACTERISTICS: REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS (VOLTAGES, ETC). OF MECHANICAL EQUIPMENT, UNLESS OTHERWISE INDICATED. 3. CODES: COMPLETE INSTALLATION OF THE MECHANICAL SYSTEM SHALL BE PER THE APPLICABLE BUILDING, MECHANICAL, ENERGY, PLUMBING, FIRE, AND HEALTH CODES AND REGULATIONS AS ADOPTED BY THE LOCAL AHJ. 4. PREPARE AND SUBMIT FOR REVIEW A SHOP DRAWING BASED ON FINAL STRUCTURAL SHOP DRAWINGS FOR LOCATING AND ROUTING ALL DUCTWORK, DAMPERS, EQUIPMENT, PIPING, ETC. A. COORDINATE FLOOR AND BEAM PENETRATIONS WITH STRUCTURAL. B. COORDINATE FINAL LOCATION AND ROUTING WITH CEILING, LIGHTS, WALLS, FIRE SPRINKLER PIPING, AND OTHER TRADES WORK. C. INCLUDE ADDITIONAL OFFSETS, ELBOWS, ROUTING, EQUIVALENT DUCT SIZING EXCHANGE, RELOCATING, ETC. AS REQUIRED FOR A COMPLETE OPERATING MECHANICAL SYSTEM. D. PROVIDE SHOP DRAWINGS AT NO ADDITIONAL COST TO THE OWNER. 5. MECHANICAL CONTRACTOR SHALL LOCATE AND COORDINATE EXACT LOCATION OF ALL MECHANICAL EQUIPMENT WITHIN THE STRUCTURE. 6. ACCESS DOORS: COORDINATE WITH ARCHITECT AND LOCATE ALL ACCESS DOORS ON SHOP DRAWINGS PRIOR TO BEGINNING OF CONSTRUCTION. ACCESS DOORS IN FIRE RATED STRUCTURE SHALL BE FIRE RATED. VERIFY ACCESS DOOR LOCATIONS WITH GENERAL CONTRACTOR PRIOR TO BIDDING. 7. RATED PENETRATION: DUCT PENETRATIONS THROUGH RATED ENCLOSURES SHALL BE FIRE/SMOKE DAMPERED PER THE LATEST EDITION OF THE UNDERWRITERS LABORATORIES (UL) FIRE RESISTANCE WITH HOURLY RATINGS FOR THROUGH -PENETRATION FIRE STOPS SYSTEM VOLUME #2, OR SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S UL LISTINGS (3M OR EQUIVALENT). DETERMINE REQUIREMENTS WITH GENERAL CONTRACTOR PRIOR TO BID. 8. EXHAUST OUTLETS: SOURCE -SPECIFIC FANS SHALL BE VENTED TO OUTDOORS WITH A MINIMUM 3' CLEARANCE BETWEEN VENT OUTLETS AND BUILDING OPENINGS, AND 10' MINIMUM BETWEEN VENT OUTLETS AND MECHANICAL AIR INTAKES. 9. ROOF PENETRATIONS: SEE ARCHITECTURAL DRAWINGS FOR ROOF CAP, ROOF CURB, ROOF DRAIN, AND VTR DETAILS. 10. EXPOSED PIPING: PROVIDE CHROME PLATING FOR EXPOSED PIPING IN FINISHED ROOMS. 11. PENETRATIONS: PROVIDE ESCUTCHEON PLATES FOR EXPOSED PIPING PENETRATIONS AND SHEET METAL FLASHING FOR EXPOSED DUCTWORK PENETRATIONS. 12. SHAFT AND PLENUM CONNECTIONS: SEAL CONNECTIONS TO AIR SHAFTS AIRTIGHT. PROVIDE AIRTIGHT SEAL AROUND PENETRATIONS IN AIR PLENUMS. 13. LIGHT FIXTURE CLEARANCE: COORDINATE LOCATIONS OF MECHANICAL WORK TO PROVIDE CLEARANCES OVER LIGHTING FIXTURES FOR REMOVAL AND REPLACEMENT. 14. CABLE TRAYS: DUCTWORK AND PIPING INSTALLED ADJACENT TO ELECTRICAL CABLE TRAYS SHALL ALLOW MINIMUM ACCESS OF 6" ABOVE AND TO THE SIDE OF CABLE TRAYS. 15. MOTORS: COMPLY WITH ENERGY CODE ENFORCED BY AHJ FOR MINIMUM EFFICIENCIES UNDER FULL LOAD. 16. ACCESS CLEARANCES FOR MAINTENANCE AND REPLACEMENT: VERIFY PHYSICAL DIMENSIONS OF EQUIPMENT TO ENSURE THAT ACCESS CLEARANCES CAN BE MET. COORDINATE LOCATIONS OF MECHANICAL WORK AND WORK OF OTHER TRADES TO PROVIDE ACCESS CLEARANCES FOR SERVICE AND MAINTENANCE. COORDINATION REQUIREMENTS 1. PIPING: COORDINATE WITH STRUCTURAL FOR EXACT LOCATION OF ALL STRUCTURAL FRAMING AND FOOTINGS AND FINALIZE THE EXACT ROUTING OF ALL PIPES WITH STRUCTURAL AND AT THE SITE PRIOR AND DURING THE CONSTRUCTION. 2. DUCTWORK: LOCATE AND COORDINATE THE EXACT LOCATION OF DUCTWORK WITH STRUCTURAL PLANS AND WITH THE GENERAL CONTRACTOR PRIOR TO INSTALLATION OF ANY STRUCTURE OR EQUIPMENT. COORDINATE WITH FRAMING CONTRACTOR TO ASSURE JOIST SPACES LINE UP WHEN DUCTWORK MUST PASS THROUGH DIFFERENT JOIST SPACES. 3. ADJUSTMENTS: ALL EQUIPMENT, MOTORS, FANS GAS BURNERS, IGNITION DEVICES, DRIVES, ETC. SHALL BE ADJUSTED AND BALANCED TO OPERATE AT SPECIFIED RATINGS AS REQUIRED FOR THIS PROJECT SITE AND ACCOUNTING FOR ELEVATION ABOVE SEA LEVEL. 4. APPROVALS: MECHANICAL AND PLUMBING EQUIPMENT SHALL BE APPROVED FOR INSTALLATION IN THE PROJECT LOCATION AND SHALL HAVE ALL CERTIFICATIONS AND RATINGS TO MEET ALL ENERGY, POLLUTION, ENVIRONMENTAL, SEISMIC, ETC. CODES AND REGULATIONS. THE CONTRACTOR SHALL COORDINATE WITH HIS MANUFACTURE SUPPLIERS AND SHALL INCLUDE ALL COSTS REQUIRED TO MEET THESE REQUIREMENTS IN HIS BID. GENERAL NOTES 8. TAKEOFFS TO OPENINGS: CONICAL TYPE WITH VOLUME DAMPER FOR ROUND DUCT BRANCHES PER SMACNA HVACDCS FIG 2-6, MINIMUM INLET DIAMETER 2 INCHES LARGER THAN DUCT SIZE. 45 DEGREE ENTRY FITTING FOR RECTANGULAR DUCT BRANCHES PER SMACNA HVACDCS FIG 2-6. 9. FLEXIBLE CONNECTIONS: PROVIDE AT EACH DUCT CONNECTION TO FANS, PACKAGED HVAC EQUIPMENT, EXTERNALLY ISOLATED AIR HANDLING UNITS, FAN COIL UNITS, AND SIMILAR EQUIPMENT. EXCEPTION: EQUIPMENT IN CORRIDOR CEILING SPACES WHERE FIRE RATING IS REQUIRED. 1. ATTACHMENTS: AIR DISTRIBUTION OUTLETS AND LOUVERS SHALL HAVE ALL REQUIRED ACCESSORIES AND ATTACHMENTS FOR A COMPLETE CONNECTION TO THE SPECIFIC TYPE OF STRUCTURE THAT THEY ARE BEING ATTACHED TO. THIS INCLUDES, BUT IS NOT LIMITED TO, EXTERIOR BRICKS, GWB WALLS, GWB CEILING, ETC. 2. DUCTWORK: DUCTWORK SHALL BE SMOOTH SHEET METAL (CLASS-1). DUCTWORK THROUGH FIRE RATED STRUCTURE AND FLOOR SHALL BE MIN. 26 GA. STEEL. MAXIMUM LENGTH OF FLEXIBLE DUCTS SHALL BE 5-0", UNLESS OTHERWISE NOTED ON DRAWINGS. DUCTWORK SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS. 3. SEISMIC: PROVIDE SEISMIC RESTRAINTS FOR MECHANICAL EQUIPMENT, PIPING, AND DUCTWORK PER SMACNA AND LOCAL REGULATIONS. 4. FILTER CLEARANCE: PROVIDE ADEQUATE CLEARANCE FOR CHANGING AIR FILTERS. 5. FIRE RATINGS: RATED FLOOR/CEILING JOINT SPACES HAVING DUCTWORK INSIDE THEM SHALL BE FIRE/SMOKE PROTECTED TO MAINTAIN THE 1-HOUR FLOOR/CEILING RATING PER LOCAL JURISDICTIONS. EXHAUST DUCTWORK PENETRATING THE 1-HOUR ROOF/CEILING OR FLOOR/CEILING ASSEMBLY SHALL HAVE ACCESSIBLE CEILING FIRE DAMPERS. ALTERNATIVELY, THE EXHAUST DUCTWORK SHALL BE ROUTED INSIDE A RATED SHAFT TO PROTECT THE CEILING/ROOF RATING PER THE LOCAL JURISDICTIONS. 6. FIRESTOP: PIPE, DUCT AND CONDUIT PENETRATIONS THROUGH RATED ASSEMBLIES SHALL BE FIRE AND SMOKE STOPPED PER CODE. 7. VOLUME DAMPERS: PROVIDE AN ACCESSIBLE MANUAL VOLUME DAMPER FOR EACH SUPPLY, RETURN, OSA AND EXHAUST OPENING, LOCATED AS FAR UPSTREAM AS POSSIBLE FROM THE OPENING. PROVIDE A MANUAL VOLUME DAMPER FOR BRANCH MAINS SERVING MORE THAN ONE OPENING. VOLUME DAMPERS IN NON -ACCESSIBLE CEILING SHALL HAVE A CONTROL ARM EXTENDED TO AN ACCESSIBLE LOCATION. PROVIDE "YOUNG" REGULATOR OR EQUAL. EXACT LOCATION OF CONTROL DEVICES VISIBLE IN FINISHED SPACES SHALL BE COORDINATED WITH THE ARCHITECT. NOTE: DUCTWORK/DIFFUSERS WITHIN THE UNITS SHALL BE PROVIDED WITH OBD'S IN LIEU OF BALANCING DAMPERS OUTLINED ABOVE. 8. TEST AND BALANCE WORK SHALL BE PERFORMED BY AN INDEPENDENT TEST AND BALANCE AGENCY. PROVIDE (3) COPIES OF TEST AND BALANCE REPORT TO OWNER. 9. PROVIDE SEISMIC RESTRIANTS FOR ALL MECHANICAL EQUIPMENT PER CODE AND SMACNA STANDARDS. 1. DISASSEMBLY PROVISIONS: PROVIDE UNIONS OR FLANGES AT PIPING CONNECTIONS TO EQUIPMENT, COILS, TRAPS, CONTROL VALVES, AND OTHER COMPONENTS TO ALLOW DISASSEMBLY FOR MAINTENANCE. 2. REDUCERS: PROVIDE AS REQUIRED FROM LINE PIPE SIZE TO EQUIPMENT, TRAP, COIL, AND CONTROL VALVE CONNECTION SIZES. 3. OFFSETS: PROVIDE FOR BRANCH LINES TO EQUIPMENT. 4. DIELECTRIC UNIONS: PROVIDE AT CONNECTIONS OF DISSIMILAR PIPE. 5. REFRIGERANT PIPING: PROVIDE SIZING & INSTALLATION IN STRICT ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. INSTALL REFRIGERANT PIPING BETWEEN INDOOR AND OUTDOOR UNITS AS AS REQUIRED AND RECOMMENDED BY MANUFACTURER. REFRIGERANT PIPING RUNS OVER 50' SHALL BE INSTALLED PER MANUFACTURER'S LONG RUN SIZING AND INSTALLATION STANDARDS. NOTE: ROUTING NOT SHOWN ON PLANS. REVISIONS DATE - PAGES - CHANGES REV1 REV2 REV3 REV4 REV5 INSULATION/LINING NOTES 1. ENERGY CODE: AS A MINIMUM, COMPLY WITH THICKNESSES AND TYPES LISTED IN ENERGY CODE ENFORCED BY AHJ. SHEET METAL NOTES 1. REFERENCE: SMACNA HVAC DUCT CONSTRUCTION STANDARDS, METAL AND FLEXIBLE, CURRENT EDITION. 2. CLEARANCE: COORDINATE DUCTWORK WITH MISCELLANEOUS OBSTRUCTIONS IN CEILING SPACE. 3. ROUND ELBOWS AND OFFSETS: FULL RADIUS (R/D = 1.5), 5-PIECE SEGMENTED OR STAMPED. REFER TO SMACNA HVACDCS FIG 2-7, 3-3. DO NOT USE ANGLED OFFSET (TYPE 1). MITERED OFFSET (TYPE 2) MAY BE USED UP TO 30 DEGREE OFFSET ANGLE. 4. ROUND TEES AND LATERALS: CONICAL TEE PER SMACNA HVACDCS FIG 3-5; DO NOT USE STRAIGHT TEE; DO NOT USE CONICAL SADDLE TAP FOR EXPOSED DUCTWORK IN FINISHED SPACES. 90-DEGREE TEE WITH OVAL TO ROUND TAP, LATERAL, AND 45-DEGREE RECTANGULAR LEAD-IN PER SMACNA HVACDCS FIG 3-4. 5. RECTANGULAR ELBOWS AND OFFSETS: FULL RADIUS WHERE SPACE PERMITS, R/W = 1.5; OTHERWISE USE SQUARE CORNER ELBOW WITH TURNING VANES. 6. RECTANGULAR DIVIDED FLOW FITTINGS: USE GENERALLY, EXCEPT BRANCHES TO TERMINALS; SMACNA HVACDCS FIG 2-5. 7. TURNING VANES: H.E.P. MANUFACTURER OR APPROVED HIGH EFFICIENCY PROFILE AIRFOIL TYPE FOR RECTANGULAR SQUARE THROAT ELBOWS. ACOUSTICAL TYPE FOR RETURN AIR MITERED ELBOWS. HVAC SCOPE REQUIREMENTS 1. MECHANICAL PERMIT: CONTRACTOR TO OBTAIN AND PAY FOR MECHANICAL PERMITS. 2. AIR BALANCE: CONTRACTOR IS RESPONSIBLE FOR PROVIDING DISTRIBUTION SYSTEM WITH AIR FLOWS AT DIFFUSERS THAT MEASURE WITHIN ±10% OF SPECIFIED VALUES. AIR BALANCE TO BE PERFORMED BY QUALIFIED TECHNICIAN. AIR BALANCE TO BE SUBMITTED TO OWNER AND ENGINEER. DRAWINGS ARE DIAGRAMMATIC, SHOWING THE GENERAL LOCATION, TYPE, LAYOUT, AND EQUIPMENT REQUIRED. THE DRAWINGS SHALL NOT BE SCALED FOR EXACT MEASUREMENT. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS. REFER TO MANUFACTURER'S STANDARD INSTALLATION DRAWINGS FOR EQUIPMENT CONNECTIONS AND INSTALLATION REQUIREMENTS. PROVIDE DUCTWORK, CONNECTIONS, ACCESSORIES, OFFSETS, AND MATERIALS NECESSARY FOR A COMPLETE SYSTEM. APPROVED BY PLANNING Aug 04 2023 RTU's that exceed 400 pounds shall have attachments designed by a Washington State Engineer to prevent wind and seismic displacement in accordance with ASCE. Designs shall be onsite at the time of final. City Of Edmonds Building Department Work MECHANICAL- (4) RTU Address 7609 212TH ST SW Owner BURGER KING Approved Date 08/01 /2023 Building Official Elrl l (iG�'f ZIr Permit Number BLD2023-0934 LEGEND TYPICAL EQUIPMENT DESIGNATION (EXHAUST FAN SHOWN) DUCT SMOKE DETECTOR ROOM THERMOSTAT OR TEMPERATURE TRANSMITTER CARBON MONOXIDE SENSOR ARCHITECTURAL BACKGROUND (THIN LINE) NEW MECHANICAL WORK (HEAVY LINE) MATCHLINE OR PROPERTY LINE ALL WORK SUBJECT TO FIELD INSPECTION FOR CODE COMPLIANCE DUCT (1ST FIGURE = SIDE SHOWN, 2ND 18xl2 FIGURE = SIDE NOT SHOWN) APPROVED UP DOWN ®j \ DUCT SECTION, POSITIVE PRESSURE UP DOWN PLANS MUST BE DUCT SECTION, NEGATIVE PRESSURE i UP DOWN 16 ROUND DUCT SECTION ON JOB SITE UP UP UP DUCT PENETRATION THRU FLOOR OR 0 m ROOF FSD FIRE/SMOKE DAMPER (--< I = HORIZ FSD DUCT, --<> = VERT DWT), 2-HR RATED, LION VOLUME DAMPER FD FIRE DAMPER FtRIZ DUCT, \A VERT DUCT)HR RATED, LION 0 ROUND DUCT INDICATOR AFF ABOVE FINISHED FLOOR AHJ AUTHORITY HAVING JURISDICTION BTUH BRITISH THERMAL UNIT PER HOUR C COMMON CAP CAPACITY CFM CUBIC FEET PER MINUTE CLG CEILING, COOLING COMB COMBUSTION CONT CONTINUE, CONTROL CONTR CONTRACTOR COP COEFFICIENT OF PERFORMANCE D DIAMETER DB DRY BULB, DECIBEL DEG DEGREE DIM DIMENSION DN DOWN DSD DUCT SMOKE DETECTOR EA EXHAUST AIR EAT ENTERING AIR TEMPERATURE EER ENERGY EFFICIENCY RATIO EF EXHAUST FAN EFF EFFICIENCY ELEC ELECTRIC EQUIV EQUIVALENT ESP EXTERNAL STATIC PRESSURE EXH EXHAUST EXT EXTERIOR, EXTERNAL F FAHRENHEIT FD FIRE DAMPER FLR FLOOR FPM FEET PER MINUTE FPS FEET PER SECOND FSD FIRE/SMOKE DAMPER G GAS HORIZ HORIZONTAL HP HORSEPOWER, HEAT PUMP HVAC HEATING, VENTILATING, AND AIR CONDITIONING HX HEAT EXCHANGER ID INDIRECT DRAIN, INSIDE DIAMETER IN INCH KW KILOWATT L LONG, LENGTH LB POUND MBH THOUSAND BTU PER HOUR MECH MECHANICAL MCA MINIMUM CIRCUIT AMPACITY MOCP MAXIMUM OVER CURRENT PROTECTION MTD MOUNTED OSA OUTDOOR AIR OBD OPPOSED BLADE DAMPER OD OUTSIDE DIMENSION OR DIAMETER OPNG OPENING POC POINT OF CONNECTION RA RETURN AIR REF REFERENCE RF RELIEF FAN RG RETURN GRILLE RPM REVOLUTIONS PER MINUTE SA SUPPLY AIR SCH SCHEDULE SF SUPPLY FAN, SQUARE FOOT SENS SENSIBLE SG SUPPLY GRILLE SMACNA SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION SO SCREENED OPENING SP STATIC PRESSURE SQ SQUARE TYP TYPICAL UON UNLESS OTHERWISE NOTED V VENT VENT VENTILATION, VENTILATOR VTR VENT THRU ROOF WB WET BULB (TEMPERATURE) SCOPE OF WORK SCOPE OF WORK COVERED BY THESE PLANS ARE LIMITED TO REPLACING 4 EXISTING ROOF TOP UNITS WITH LIKE FOR LIKE. NEW RTU ECONOMIZER SETUP SHALL MATCH WHAT WAS INTENDED TO SERVE THE BUILDING ON THE EXISTING DESIGN. APPLICABLE CODES THE FOLLOWING PROJECT DESIGN IS BASED ON THE FOLLOWING CODES: -2018 INTERNATIONAL BUILDING CODE (IBC) & WA AMENDMENTS -2018 INTERNATIONAL MECHANICAL CODE (IMC) & WA AMENDMENTS -2018 UNIFORM PLUMBING CODE (UPC) & WA AMENDMENTS -2018 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) & WA AMENDMENTS -2018 INTERNATIONAL FUEL GAS CODE (IFGC) & WA AMENDMENTS DRAWING INDEX DWG DESCRIPTION M000 COVERSHEET X moo SCHEDULE X M100 SITE PLAN X M200 MECH FLOOR & ROOF PLAN X z O O Un w 0 w 0 0 z 00000kJ A C 0000 Op F,O ........... s 00 ............ ��F Wasy;�co� poo OOp 13 00 '• 4'F ISTERF'� O ASS/ ...... .. 000 1` 0 0 ¢LLJ ¢ 0 z z O O 0 ¢ Ff) w 0 o O ¢ m C4 O 00 W a 0 O 0 w �R V 3 Z (j) �e ♦W N_ V N W O m m O w 0 DATE: 07/25/2023 SHEET TITLE: O O I �o m F-- Iw � O W m :5 :5 Cn D Q z U O � Q Oz Qe� O a_ U 0 m Uj �I-Vcr)m co 0 � 0 c m ¢gyLu<lq 7-0-(_0 O O O cv i�: LU ozz O rn 1 0- z O 0 � Vl z WMEM X Im W 0z V z W COVERSHEET RECEIVED Jul 26 2023 SHEET NO. M000 SCHEDULE EXISTING ROOF TOP UNITS TO REPLACE ic MWE' YCD060SQ215.04 Tag: All dimensions are inches Standard Efficiency 5 Ton Packaged EVAPORATOR SECT TOP PANEL Gas/Electric ACCESS PANEL _ CONDENSER FAN Downflow YCD060C 00 33 1/2' 0 1/2" NPT GAS CONN. 38 7/8" CONDENSER COIL �* o 02" HOLE (UNIT POWER WIRES) CONTROL & COMPRESSOR 8 5/16" ACCESS PANEL 83 1/16" \ 07/8" HOLE 46 9/16" (UNIT CONTROL WIRES) CLEARANCE 36" as" \ 83 1/16" "'IL'EARANCE 48" 6 3/32" CLEARANCE 18" HORIZONTAL 36' DOWNFLOW `\ TYPICAL ROOF OPENING 39"' 77 5/8' 2" 2„ 43 3/8' 46 9/16" CLEARANCE 36" Table 1 Unit Wiring Unit Minimum Circuit Maximum Fuse Size or Unit Operating Ampacity Maximum Circuit Breaker' Model No. Voltage Range (Standard/Oversize) (Standard/Oversize) YCD060CI 187-253 46.5/47.8 60/60 YCD060C3 187-253 31.3/32.6 45/50 YCD060C4 414-506 16.3/16.9 25/25 YCD060CW 517-633 12.0/NA 15/NA Note: 1. HACR type circuit breakers per NEC. Table 2 Accessory Net Weights (Ibs) Oversized Hard All LPG Economizer Outside Air Damper Roof Motor Start Zone Conversion Net Manual Motorized Curb Adder Kit Sensors Kit 40 32 - 80 5 5 1 5 Notes: 1. Net weight should be added to unit weight when ordering factory installed accessories Quick Reference Guide Precedent"' - Standard Efficiency Cooling, Gas/Electric 3 to 10 Tons Packaged Rooftop Model Number: Used With: SC tandard Efficiency Cooling Only (Electric Heat Optional) SC ptandard Efficiency Gas Heat Unit March 2020 RT-PRC037AG-EN © 2020 Table 2. Standard efficiency, 3 to 10 ton packaged rooftop performance data (cooling or gas) Table 1. List of factory installed options(a) Table 3 General Data 5 Ton Downflow Units YCD060C1 YCD060C3,C4,CW Cooling Performance' Gross Cooling Capacity 64,000 62,500 SEER2 9.85 10.00 Nominal CFM/ARI Rated CFM 2,000/2,000 2,000/2,000 ARI Net Cooling Capacity 61,500 60,000 System Power (KW) 6.95 6.71 Heating Performance Heating Models Low High Low High Heating Input (Btuh) 90,000 135,000 90,000 135,000 Heating Output (Btuh) 70,000 105,000 73,000 109,000 AFUE%4 78 78 81 81 Steady State Efficiency (%) 80 80 81 81 No. Burners 1 1 No. Stages 1 1 Gas Connection Pipe Size (in.) 1/2 1/2 Compressor No./Type 1/Climatuff® 1/Climatuff Sound Rating (BELS)5 8.6 8.6 Outdoor Coil - Type Hi -Performance Hi -Performance Tube Size (in.) O.D. .375 .375 Face Area (sq ft) 11.32 9.76 Rows/FPI 2/16 2/16 Indoor Coil - Type Hi -Performance Hi -Performance Tube Size (in.) .375 .375 Face Area (sq ft) 6.33 6.33 Rows/FPI 2/15 2/15 Refrigerant Control Short Orifice Short Orifice Drain Connection No./Size (in.) 1 / 314" PVC 1 / W, PVC Outdoor Fan - Type Propeller Propeller No. Used/Diameter (in.) 1/24 1/24 Drive Type/No. Speeds Direct/1 Direct/1 CFM 4,900 4,270 No. Motors/HP 1/.50 1/.40 Motor RPM 975 1,075 Indoor Fan - Type FC Centrifugal FC Centrifugal No. Used 1 1 Diameter x Width (in.) 1/12 x 9 1/12 x 9 Drive Type/No. Speeds DirecU2 Direct/2 No. Motors 1 1 Motor HP (Standard/Oversized) .60/.75 .60/.75 Motor RPM (Standard/Oversized) 850/1,040 850/1040 Motor Frame Size (Standard/Oversized) 48/48 48/48 Filters - Type/Furnished? Throwaway/Yes Throwaway/Yes (No.) Size Recommended (in.) (2) 20 x 25 x 1 (2) 20 x 25 x 1 Refrigerant Charge (Lbs of R-22)6 8.4 7.9 NOTES: 1. Coaling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to + 20 % of nominal cfm. Rated in accordance with ARI Standard 210. 2. SEER is rated at ARI conditions and in accordance with DOE test procedures. 3. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2,000 feet. For elevations above 2,000 feet, ratings should be reduced at the rate of 4 % for each 1,000 feet above sea level. 4. AFUE and Steady State Efficiency are rated in accordance with DOE test procedures. 5. Sound is rated in accordance with ARI Standard 270. 6. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 2 NEW ROOF TOP UNITS SPECS 0-50% Motorized outside air damper Manual outside air damper Air-Fip Wireless Communication Interface MERV 8 filters BACnet@ Communication Interface (BCI-R) MERV 13 filters Barometric relief Multiple zone VAV (variable air volume) Belt drive motor Multi -speed indoor fan system Clogged filter switch NOVAR 2024 controls CompleteCoatTM (microchannel condenser coil) NOVAR 3051 controls without zone sensor Condensate overflow switch NOVAR 3051 zone sensor Demand control ventilation wiring NOVAR return air sensor Discharge air temperature sensing kit Powered convenience outlet Economizer - comparative enthalpy ReliaTelT" controls Economizer - dry bulb Single zone variable air volume (SZVAV) Economizer - low leak, dry bulb Stainless steel drain pan Economizer - reference enthalpy Stainless steel heat exchanger Fan failure switch Supply, return, and plenum air smoke detectors Fault detection & diagnostics (FDD); Meets CA Title 24 requirements Through -the -base electric provision FrostatT" Through -the -base gas provision Hail guard Unit mounted circuit breaker Hinged access panels Unit mounted non -fused disconnect Human interface - 5-in. color touchscreen Unpowered convenience outlet LonTalk@ Communication Interface (LCI) (a) Verify option availability in product catalog. Nomura Size Tons 3 4 5 6 7.5 Singe Compressor 7.5 Dual Compressors 8.5 10 Cooling Performance Supply Air (cfm)(,') 1,200 1,600 2,000 2,400 3,000 3,000 3,400 4,000 Tot/ Sens Cap (M13h)(b)(C) 37.1/29.9 49.0/38.6 60.1/49.4 75.0/53.2 91.2/67.4 94.8/73.8 107.2/84.2 116.3/96.8 SEER/EER 14.0 14.0 14.0 11.2 11.2 11.2 11.2 11.2 IEER (T/Y) N/A N/A N/A 12.9/12.7 12.9/12.7 12.9/12.7 12.9/12.7 12.9/12.7 Gas Heating Performance Low Heat (Input/output) - (MBh) 80/64.8 80/64.8 80/64.8 80.0/64.0 120/96 120.0/96.0 120.0/96.0 150.0/120.0 Medium Heat (Input/output)-(MBh) 100/81 100/81 100/81 120.0/96.0 150/120 150.0/120.0 150.0/120.0 200.0/160.0 High Heat (Input/output)-(MBh) 120/97.2 130/105.3 150/121.5 150.0/120.0 200/160 200.0/160.0 200.0/160.0 235.0/164.5 Other Information Net Weight (Lbs) - Gas Heat 472 492 522 710 832 847 927 1058 Net Weight (Lbs) - Electric Heat 431 452 498 667 751 797 879 960 Roof Curb BAYCURB042A BAYCURB043A Unit Cabinet Size F C C D D D Filters(d) - Type Furnished Throwaway Throwaway Throwaway I Throwaway I Throwaway Throwaway I Throwaway I Throwaway Number Size Recommended (2) 20x3Ox2 (2) 20x3Ox2 (2) 20x3Ox2 1 (4) 16x25x2 1 (4) 16x25x2 (4) 20x25x2 1 (4) 20x25x2 1 (4) 20x25x2 (a) Nominal cfm (b) Cooling performance is rated at 80/67/95 (c) All units listed utilize 3-phase voltage (d) Optional 2-inch MERV 8 and MERV 13 filters also available O u� SPA Table 3. Unit MCA and MOP electrical data (standard indoor fan motor) (cooling or gas)(a) T YSC Volts MCA MOP 036 208-230/3 20 30 036 460/3 10 15 036 575/3 8 15 048 208-230/3 26 35 048 460/3 11 15 048 575/3 10 15 060 208-230/3 29 40 060 460/3 13 15 060 575/3 10 15 072 208-230/3 35 50 072 460/3 17 25 072 575/3 13 20 090 208-230/3 39 60 090 460/3 19 30 090 575/3 15 20 092 208-230/3 39 50 092 460/3 18 20 092 575/3 15 20 102 208-230/3 46 60 102 460/3 23 25 102 575/3 17 20 120 208-230/3 49 60 120 460/3 22 25 Table 4. Unit indoor fan data (cooling or gas) (continued) T YSC Volts Standard HP - RPM Oversize HP - RPM 102 208-230/3 2/1750 c 3/1750 102 460/3 2/1750(c) 3/1750 102 575/3 2/1750(c) 3/1750 120 208-230/3 2.75 - MULT - 120 460/3 2.75 - MULT - 120 575 ,' 2.75 - MULT - (a) Direct drive motor (b) Powered through 575/230V transformer (c) Multi -speed and single zone VAV fan option uses 2.75 - MULT motor (d) Powered through 575/480V transformer Table 5. Unit dimensional data C D F Unit Length UL 88 5/8 88 5/8 69 7/8 Unit Width UW 53 1/4 53 1/4 44 1/4 Unit Height UH 40 7/8 46 7/8 40 7/8 Clearance C1 48 48 48 Clearance C2 36 36 36 Clearance C3 36 36 36 Clearance C4 36 36 36 Clearance CS 72 72 72 Curb Length CL 84 1/2 84 1/2 65 13/16 Curb Width CW 50 3/8 50 3/8 41 7/16 Supply Length SL(a) 18 1/2 18 1/2 16 3/4 EXISTING EXISTING EXISTING EXISTING NEW NEW NEW NEW ROOFTOP AIR HANDLER UNIT EQUIP NO. DISCHARGE SUPPLY FAN COOLING HEATING ELECTRICAL WEIGHT,LBS BASIS OF DESIGN AIRFLOW, (CFM) OSA (CFM) ESP, IN WG MOTOR HP/BHP TOTAL CAPACITY (TON) EFF. GAS VOLTAGE RLA LRA INPUT (MBH) OUTPUT (MBH) (E)RTU-1 VERTICAL 2,000 - 0.5 0.75 5.0 SEER: 9.85 170 135 208/60/3 28.8 142 831 TRANE YCD060SQ215.04 (E)RTU-2 VERTICAL 2,000 - 0.5 0.75 5.0 SEER: 9.85 170 135 208/60/3 28.8 142 831 TRANE YCD060SQ215.04 (E)RTU-3 VERTICAL 2,000 - 0.5 0.75 5.0 SEER: 9.85 170 135 208/60/3 28.8 142 831 TRANE YCD060SQ215.04 (E)RTU-4 VERTICAL 2,000 - 0.5 0.75 5.0 SEER: 9.85 170 135 208/60/3 28.8 142 831 TRANE YCD060SQ215.04 (N)RTU-1 VERTICAL 2,000 - 0.5 0.75 5.0 SEER: 14 150 120 208/60/3 28.8 142 522 TRANE YSC060G3RHB0000 (N)RTU-2 VERTICAL 2,000 - 0.5 0.75 5.0 SEER: 14 150 120 208/60/3 28.8 142 522 TRANE YSC060G3RHB0000 (N)RTU-3 VERTICAL 2,000 - 0.5 0.75 5.0 SEER: 14 150 120 208/60/3 28.8 142 522 TRANE YSC060G3RHB0000 (N)RTU-4 VERTICAL 2,000 - 0.5 0.75 5.0 SEER: 14 150 120 208/60/3 28.8 142 522 TRANE YSC060G3RHB0000 Table 3. Unit MCA and MOP electrical data (standard indoor fan motor) (cooling or gas)(a) T YSC Volts MCA MOP 120 575/3 22 25 (a) For MCA/MOP of units with electric heat, refer to product catalog. Table 4. Unit indoor fan data (cooling or gas) T YSC Volts Standard HP - RPM Oversize HP - RPM 036 208-230/3 a 3/4 - MULT 1 - MULT 036 460/3(a) 3/4 - MULT 1 MULT 036 575/3 a 3/4 - MULT 1 MULT 048 208-230/3 a 1 - MULT 1 MULT 048 460/3(a) 1 - MULT 1 - MULT 048 575/3 a 1 - MULT 1 - MULT 060 208-230/3(aT 1 MULT 1 MULT 060 460/60/3 a 1 MULT 1 MULT 060 575/3 a 1 MULT 1 MULT 072 208-230/3 1/1750 2/1750 072 460/3 1/1750 2/1750 072 575/3 1/1750 2/1750 090 208-230/3 1/1750 3/1750 090 460/3 1/1750 3/1750 090 575/3 1/1750 3/1750 092 208-230/3(c) 1/1750 3/1750 092 460/3 c 1/1750 3/1750 092 575/3 c 1/1750 3/1750 5. Unit dimensional data (continued) C D F Supply Width SW(a) 34 3/8 34 3/8 17 7/8 Return Length RL(a) 18 1/4 18 1/4 14 19/16 Return Width RW a 34 3/8 34 3/8 25 3/16 T (a) Dimensions are for curb openings and not duct inserts. o �--_7Z� Reference the product catalog for duct insert dimensions. Trane - by Trane Technologies (NYSE: TT), a global climate innovator - creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices. RT-PRC037AG-EN 30 Mar 2020 Supersedes RT-PRC037AF-EN (Jan 2020) ©2020 z 0 U U/ LLJ t� W Q 0 z 00000J A C �000 Wasy;�co� 000 ': ❑ ❑ Z13 0 00.�• �F I1ERF'�•••��00� O�o000 0 0 Q Q LLJ z Z:0 U U Q f) LLJ W = C U Q m N O 00 W a 0 O G W a � Z ♦♦W N_ ♦0 N LL W M� O W CD U W 0 DATE: 07/25/2023 SHEET TITLE: O O I QO m � W W m in D Q z U U wQ D Oz rr,o n u 0 m Lv CO ct o m � DOLd m >Q Iq Q > co I- n O 0 6 N LJ z z -1 0- Zz 0V (j) Z Mw W O rZ V Z W SCHEDULE RECEIVED Jul 26 2023 SHEET NO. M001 0 W Q SCOPE OF WORK SCOPE OF WORK COVERED BY THESE PLANS ARE LIMITED TO REPLACING 4 EXISTING ROOF TOP UNITS WITH LIKE FOR LIKE. NEW RTU ECONOMIZER SETUP SHALL MATCH WHAT WAS INTENDED TO SERVE THE BUILDING ON THE EXISTING DESIGN. z O a_ U un w 0 w Q 0 O z 00000J A C 0000 Op F,O ,.......... ks 00 ���'pF Wasy;�co� 000 OOp . ❑ ❑ ; z13 00 .• �F ISTERF'� p�0000 0 0 a Q 0 � > w Y O U � Q W W = C) U Q m N O 00 0 O 0 Lu a � Z ♦W N V N w O m (D U w D O a_ DATE: 07/25/2023 O O I Q0m 11-w �o w m� un �Q z U U D Q oz Q:�O a_ U IN O M Ld V M co:' 0 C� uj Q Q � M [— r) O O 0 6 N cj Z Z O � J rL z ou cn Z ommo Ix ED w w OZ 0 jol Z SHEET TITLE: SITE PLAN RECEIVED Jul 26 2023 DEVELOPMENT SERVICES SHEETNO. mloo 3 N J N RTU-1 J 5.0 TON -CIT- 171 t]T-] 2 1 1 2 CD 11 ElN El I< I o N RTU-2 5.0 TON 3 ) - [I D I D 1E] El ZI 3 3 1 2 2 1 i r 7 IN N RTU-4 J N RTU-3 5.0 TON 5.0 TON �Dii 111 tl L I U- Ll 11 UVE71IFTUF 11 H��Jji ii[Liji ]Ff - N N SCALE SCALE MECH FLOOR PLAN 0„ MECH ROOF PLAN 13 GENERAL NOTES FLAG NOTES 1. ALL RTUs SHALL BE REPLACED LIKE FOR LIKE. l . INSTALLER SHALL NOT CUT ANY STRUCTURAL MEMBERS WITHOUT VERIFYING WITH A STRUCTURAL ENGINEER. 2. ECONOMIZER SETTING SHALL BE REMAINED AS EXISTING. 3. ALL DUCTWORK ASSOCIATED WITH EXISTING RTUs ARE EXISTING TO REMAIN. % z 0 w 0 cn w 0 w Q 0 0 z 00000� A C 0000 Op F,O ,.......... ks OOp ��� OF Wasy;�co� poo ❑ 00 '• �F ISTERF''Q) p�O000QQ��� l� Z`JLLJ FLLJ n 0 0 a Q 0 z z Y o � U U � Q w � 0 o U Q00 m N O W a 0 0 W Z � ♦W N V N W � O m 0 w 0 ) Z O Z z w ATE: 07/25/2023 D SHEET TITLE: VDEVELOPMENT SERVICES 4 MECH FLOOR & ROOF REC�IA( D Jul 26 2023 SHEET NO. M200 z 0 w 0 cn w 0 w Q 0 0 z 00000� A C 0000 Op F,O ,.......... ks OOp ��� OF Wasy;�co� poo ❑ 00 '• �F ISTERF''Q) p�O000QQ��� l� Z`JLLJ FLLJ n 0 0 a Q 0 z z Y o � U U � Q w � 0 o U Q00 m N O W a 0 0 W Z � ♦W N V N W � O m 0 w 0 ) Z O Z z w ATE: 07/25/2023 D SHEET TITLE: VDEVELOPMENT SERVICES 4 MECH FLOOR & ROOF REC�IA( D Jul 26 2023 SHEET NO. M200 0 0 a Q 0 z z Y o � U U � Q w � 0 o U Q00 m N O W a 0 0 W Z � ♦W N V N W � O m 0 w 0 ) Z O Z z w ATE: 07/25/2023 D SHEET TITLE: VDEVELOPMENT SERVICES 4 MECH FLOOR & ROOF REC�IA( D Jul 26 2023 SHEET NO. M200 m N O W a 0 0 W Z � ♦W N V N W � O m 0 w 0 ) Z O Z z w ATE: 07/25/2023 D SHEET TITLE: VDEVELOPMENT SERVICES 4 MECH FLOOR & ROOF REC�IA( D Jul 26 2023 SHEET NO. M200