APPROVED BLD DEF SUB 12 BLD2018-1622_FIRE STOPPING_02-14-2022_16_53_37_GRE_Edmonds_99_-_Sub078413_Firestopping_SMS
REVIEWED MyJ CITY OF EDMONDS BLD2018-1622 DEF. SUB. #12 FIRESTOPPING RECEIVED 2/14/22 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SUBMITTAL REVIEW ARCHITECT'S REVIEW NO EXCEPTIONS NOTED EXCEPTIONS NOTED- RESUBMIT - NO RESUBMITTAL REQUIRED SEE COMMENTS ® ❑ ❑ Architect's review is for general conformance with the design concept and contract documents. Markings or comments shall not be construed as relieving the Contractor from compliance with the project plans and specifications, nor departures there from. The Contractor remains responsible for details and accuracy, for confirming and correlating all quantities and dimensions, for selecting fabrications, processes, for techniques of assembly, and for performing his work in a safe manner. Contractor to verify all dimensions at job site before ordering materials and equipment. STUDIO MENG STRAZZARA UL SYSTEM NO. F-C-2030 PLASTIC PIPE THROUGH WOOD FLOOR/CEILING ASSEMBLY F-RATING = 1-HR. OR 2-HR. T-RATING = 0-HR., 3/4-HR., 1-HR., 1-112-HR., OR 2-HR. 0 BOTTOM VIEW 0 N U 0 8 0 0 A A SECTION A -A 4 5 2 10000 3 6 7 Sheet 1 of 2 Drawing No. I �-E E1d3 HILTI, Inc. Scale 1/8" =1" FC Plano, Texas USA (800) 879-8000 Hilti Firestop Systems Date July 19,2018 2030r r-- Saving Lives through Innovation and Education UL SYSTEM NO. F-C-2030 PLASTIC PIPE THROUGH WOOD FLOOR/CEILING ASSEMBLY F-RATING = 1-HR. OR 2-HR. T-RATING = 0-HR., 3/4-HR., 1-HR., 1-112-HR., OR 2-HR. 1. WOOD FLOOR/CEILING ASSEMBLY (UL CLASSIFIED L500 SERIES) (1-HR. OR 2-HR. FIRE -RATING) (2-HR. SHOWN). 2. LUMBER OR PLYWOOD SUBFLOOR WITH FINISH FLOOR OF LUMBER, PLYWOOD, OR FLOOR TOPPING MIXTURE. 3. [OPTIONAL] FIRE -RATED OR NON -RATED SINGLE, DOUBLE, OR STAGGERED WOOD STUD/GYPSUM CHASE WALL ASSEMBLY CONSISTING OF NOMINAL 2" x 6" OR PARALLEL 2" x 4" LUMBER PLATES AND STUDS. 4. PENETRATING ITEM TO BE ONE OF THE FOLLOWING (ALSO SEE NOTE NO.2 BELOW) : A. MAXIMUM 4" NOMINAL DIAMETER PVC PLASTIC PIPE (CELLULAR AND SOLID CORE). B. MAXIMUM 4" NOMINAL DIAMETER ABS PLASTIC PIPE (CELLULAR AND SOLID CORE). C. MAXIMUM 4" NOMINAL DIAMETER FRPP PLASTIC PIPE. D. MAXIMUM 4" NOMINAL DIAMETER CPVC PLASTIC PIPE. 5. MINIMUM 314" DEPTH HILTI FS-ONE MAX INTUMESCENT FIRESTOP SEALANT FLUSH WITH TOP SURFACE OF FLOOR OR SOLE PLATE OF CHASE WALL. 6. MINIMUM 518" DEPTH HILTI FS-ONE MAX INTUMESCENT FIRESTOP SEALANT FLUSH WITH BOTTOM SURFACE OF CEILING OR LOWER TOP PLATE. 7. HILTI CP 643N FIRESTOP COLLAR WITH FASTENING HOOKS (SEE TABLE BELOW). 8. EACH FASTENING HOOK SECURED TO CEILING WITH MINIMUM 3116" DIAMETER STEEL TOGGLER BOLTS OR TO THE BOTTOM SURFACE OF LOWER TOP PLATE WITH MINIMUM NO. 12 BY MINIMUM 1" LONG STEEL WOOD SCREWS WITH STEEL WASHERS. W NOMINAL PIPE DIAMETER PRODUCT DESCRIPTION NO. OF FASTENING HOOKS MAXIMUM HOLE SIZE 1-112" CP 643 5011.5" N 2 2-112" 2" CP 643 6312" N 2 2-518" 3" CP 643 9013" N 3 4" 4" CP 643110/4" N 3 5" NOTES: 1. ANNULAR SPACE = MINIMUM 0", MAXIMUM 112". 2. CLOSED OR VENTED PIPING SYSTEM (PVC, ABS, FRPP = SCHEDULE 40; CPVC = SDR 17). Sheet 2 of 2 Drawing No. HILTI, Inc. Scale�_E E1d3 Plano, Texas USA (800) 879-8000 C Hilti Firestop Systems Date F July 19,2018 2030r Saving Lives through Innovation and Education UL SYSTEM NO. F-C-2389 PLASTIC PIPE THROUGH WOOD FLOOR/CEILING ASSEMBLY F-RATING = 1-HR. T-RATING = 3/4-HR. OR 1-HR. BOTTOM VIEW SECTION A -A 1. WOOD FLOOR/CEILING ASSEMBLY (UL CLASSIFIED L500 SERIES) (1-HR. FIRE -RATING). 2. GYPSUM WALL ASSEMBLY TO INCLUDE THE FOLLOWING CONSTRUCTION FEATURES: A. WOOD PLATES AND STUDS TO CONSIST OF NOMINAL 2" x 4" OR 2" x 6" LUMBER (SPACED MAXIMUM 16" OC). B. MINIMUM 1/2" THICK RATED OR NON -RATED GYPSUM WALLBOARD. 3. PENETRATING ITEM TO BE ONE OF THE FOLLOWING: A. MAXIMUM 3" NOMINAL DIAMETER PVC PLASTIC PIPE (CELLULAR OR SOLID CORE). B. MAXIMUM 3" NOMINAL DIAMETER CPVC PLASTIC PIPE (CLOSED PIPING SYSTEM ONLY). C. MAXIMUM 3" NOMINAL DIAMETER ABS PLASTIC PIPE (CELLULAR OR SOLID CORE). D. MAXIMUM 2" NOMINAL DIAMETER ENT. 4. MINIMUM 3/4" DEPTH HILTI FS-ONE MAX INTUMESCENT FIRESTOP SEALANT FLUSH WITH TOP SURFACE OF FLOOR OR TOP SURFACE OF SOLE PLATE. 5. MINIMUM 3/4" DEPTH HILTI FS-ONE MAX INTUMESCENT FIRESTOP SEALANT FLUSH WITH BOTTOM SURFACE OF LOWER TOP PLATE. 6. MINIMUM 1/2" BEAD HILTI FS-ONE MAX INTUMESCENT FIRESTOP SEALANT APPLIED AT POINT OF CONTACT OR OUT TO MAXIMUM 118" ANNULAR SPACE. NOTES: 1. MAXIMUM DIAMETER OF OPENING = 4". 2. ANNULAR SPACE = MINIMUM 0", MAXIMUM 5/8". 3. CLOSED OR VENTED PIPING SYSTEM (PVC, ABS = SCHEDULE 40; CPVC = SDR 13.5). 4. WHEN LUMBER PLATES ARE DISCONTINUOUS, ATTACH MINIMUM 1-112" WIDE STEEL STRAP (MIN. 20 GA.) AT SOLE PLATE AND MINIMUM 3" WIDE STEEL STRAP AT TOP PLATES TO BRIDGE OPENING. STRAPS TO OVERLAP PLATES MINIMUM 2" ON EACH SIDE OF OPENING AND SECURED WITH MINIMUM OF 2 NAILS OR SCREWS ON EACH SIDE. 5. T-RATING IS 3/4-HR. WHEN PVC OR CPVC PIPE IS USED AND 1-HR. WHEN ABS PIPE OR ENT IS USED. co 0 co M GV U Sheet 1 of 1 Drawing No. W3 HILTI, Inc. Scale 3/32" =1" FC Plano, Texas USA (800) 879-8000 Hilti Firestop Systems Date Aug.15,2019 2389e Saving Lives through Innovation and Education Mineral Wool Sound Attenuation Fire Batts (SAFB) COMPANY Johns Manville, a Berkshire Hathaway company, was founded in 1858. Our ownership by Berkshire Hathaway, one of the most admired companies in the world and one of the most financially secure, allows JM to invest for the future. This enables JM to continue delivering the broadest range of insulation products in the industry and offering innovative solutions that meet your needs. DESCRIPTION JM Mineral Wool Sound Attenuation Fire Batt (SAFB) Insulation is made of inorganic fibers derived from basalt, a volcanic rock. Advanced manufacturing technology ensures consistent product quality, with high -fiber density and low shot content for excellent performance. Mineral wool SAFB is inorganic, noncombustible, moisture resistant, non -deteriorating, and will not mildew or support corrosion. Mineral wool SAFB is available as an unfaced batt. USE Mineral wool SAFB is designed to deliver noise control in metal stud wall cavities of interior partitions, exterior walls or above suspended ceiling systems. INSTALLATION Mineral wool SAFB is easily cut with a knife for quick installation and snug fit, even around obstructions and structural members. Butt ends and edges closely together and fill all voids with additional insulation. Install friction -fit mineral wool SAFB between metal wall studs, filling the entire cavity to the full height of the wall. Leave no voids. PACKAGING Mineral wool SAFB is compression -packaged for savings in storage and freight costs. DESIGN CONSIDERATIONS Acoustical performance of interior drywall partitions can be substantially improved by including a number of important design and construction details. Important details include sealing the perimeter of walls, wall intersection construction considerations, and the location and proper installation of electrical outlets, ducts, doors and mechan- ical equipment. LIMITATIONS OF USE Check applicable building codes. SOUND & FIRE INSULATION PERFORMANCE ADVANTAGES Excellent Acoustical Performance: Lightweight, flexible insulation batts are excellent sound absorbers, efficiently reducing sound transmission. Mineral wool SAFB improves the Sound Transmission Class (STC) ratings of interior partition walls and suspended ceilings. Batts can improve wall assembly STC ratings by up to 10dB. Fire Safety: Mineral wool SAFB has a melting point in excess of 2000°F (I093°C). See Applicable Standards for details. Noncombustible: See Applicable Standards for details. Durable & Inorganic: Mineral wool SAFB does not support growth of fungi, nor does it sustain vermin. ENERGY AND ENVIRONMENT *GREENGUARD certification is not intended for residential environments. Instead, the certification is intended only for buildings meeting ASHRAE 62.1-2007 commercial building ventilation rates. This certification is proof that the product meets the GREENGUARD Environmental Institute' indoor air quality standards and product emission standards for VOCs. Mineral Wool Sound Attenuation Fire Batts (SAFB) SOUND & FIRE INSULATION APPLICABLE STANDARDS & BUILDING APPLICATION* MINERAL WOOL SAFB ASTM C665 Corrosivity to Steel, Passes ASTM C665 Material Specification, Type 1 ASTM C1104 Water Vapor Sorption, <1 % by Weight; <.02% by Volume at 120°F (49T), 95% PH ASTM C1338 Fungi Resistant, Passes ASTM E84 Flame Spread/Smoke Developed, 0/0 ASTM E136 Noncombustible, Passes UL 723, CAN/ULC-S102-M, 0/0 CAN4-S114-M, Passes City of New York, MEA-346-90 ICC (International Building Code), All Building Classification Types Nominal Density, 2.5 pcf (40kg/m3) ASTM C518 R-Value at 75°F, 3.7 per inch of thickness *DISCLAIMER: JMproducts are designed, manufactured and tested to strict quality standards in our own facilities. This, along with third -party auditing, is your assurance that this product delivers consistent high quality. STANDARD SIZES* THICKNESS WIDTH LENGTH in (mm) in (mm) in (mm) 1.5 - 6 (38 -1521 16 & 24 (406 & 6101 48 (1219) 'Thicknesses are available in 112"increments. Minimum order quantity may apply. Custom sizes are also available on a made -to -order basis ACOUSTICAL PERFORMANCE ASTM C423Test Method (TypeA Mounting) SOUND ABSORPTION COEFFICIENTS THICKNESS 1/3 Octave Band Center Frequencies, Hz in (mm) 125 250 500 1000 2000 4000 NRC 1 Y2 (38) 0.23 0.42 0.89 1.03 1.03 1.03 0.85 2 (51) 0.27 0.55 1.07 1.10 1.10 1.10 0.95 2Y2 (64) 0.25 0.77 1.10 1.04 0.98 0.98 1.00 3 (76) 0.34 0.92 1.16 1.04 0.98 0.98 1.05 3Y2 (89) 0.41 1.01 1.20 1.06 1.06 1.05 1.10 4 (102) 0.97 1.28 1.25 1.10 1.10 1.09 1.20 5 (127) 0.66 1.30 1.27 1.11 1.07 1.02 1.20 6 (152) 1.05 1.45 1.29 1.15 1.09 1.04 1.25 I/M"7 Johns Manville Visit our website at www.JM.com or call 800-654-3103 1 Building Insulation Division P.O. Box 5108 1 Denver, CO 80217-5108 Technical specifications as shown in this literature are intended to be used as general guidelines only. Please refer to the Safety Data Sheet and product label pri- or to using this product. The physical and chemical properties of mineral wool insulation listed herein represent typical, average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. They are supplied as a technical service and are subject to change without notice. Any references to numerical flame spread or smoke developed ratings are not intended to reflect hazards presented by these or any other materials under actual fire conditions. Check with the sales office nearest you for current information. All Johns Manville products are sold subject to Johns Manville's stan- dard Terms and Conditions, which includes a Limited Warranty and Limitation of Remedy. For a copy of the Johns Manville standard Terms and Conditions or for information on other Johns Manville insulation and systems, visit www2.jm.com/terms-conditions or call 800-654-3103. BID-0163 12/18 © 2018 Johns Manville. All Rights Reserved. Ben Lek From: Bejar, Marcos <mbejar@bdiinsulation.com> Sent: Tuesday, February 8, 2022 11:30 AM To: Ben Lek; Paul Mandish Cc: Bejar, Guillermo Subject: RE: Fire Stop Submittal Attachments: MinWooI-SAFB- Data -Sheet.pdf The Hilti CF-AS OP is being used on horizontal penetrations for air seal and not in the fire assemblies. The SAFB Mineral wool is being used for draft stopping to seal the gap between the double framed unit party walls every 10' vertically and every 10' horizontally. Marcos Bejar I Branch Manager Pacific Partners Insulation North, LLC 6405172nd Street NE, Suite C, Arlington, WA 98223 O: (360) 435-99451 C: (360) 333-38591 E: mbejar(a)bdiinsulation.com How are we doing? Please leave us a Google or Yelp review. For your convenience, to pay an invoice now please click here and then click on the "Pay Now" badge in the bottom right corner. From: Ben Lek <slek@goodmanre.com> Sent: Tuesday, February 8, 2022 10:46 AM To: Bejar, Marcos <mbejar@bdiinsulation.com> Cc: Bejar, Guillermo <gbejar@bdiinsulation.com> Subject: [EXTERNAL] RE: Fire Stop Submittal This email is being sent from: slek(aD-goodman re.com WARNING: This email originated from outside of the organization, from: slek(cDgoodman re. com. Please refrain from clicking any links or opening/saving any attachments if you doubt the validity of the email. For assistance, contact the IT helpdesk. Hi Marcos, How does the attached fire stop submittal address the architects (Lucas) comments: see below. pmvaaa For Rword 0 Jy QWVVN n H1p FirwWCV411"Pxb. Hm HIS*w1w *mw WDLrTm +Fra Nr pPN1"MONCAOM apprrr to oodarrn la spmdhcation DKWmCMIS Hsu CF,4S ,E h-w u Cja &W A" FEW - RNA & AKfW WInM1r*-r1W4= NIA&LCondrinl OM%KviwiH4tW9kx.tlut NM fa W19 MMOK&DCM AMVJwryna HID% Thanks Ben From: Bejar, Marcos <mbeiar@bdiinsulation.com> Sent: Tuesday, February 8, 2022 10:32 AM To: Ben Lek <slek@goodmanre.com> Cc: Bejar, Guillermo <gbeiar@bdiinsulation.com> Subject: Fire Stop Submittal Hi Ben Please see the attached additional information for the Fire stop detail Let me know if you have any questions Thanks Marcos Bejar I Branch Manager Pacific Partners Insulation North, LLC 6405 172nd Street NE, Suite C, Arlington, WA 98223 O: (360) 435-99451 C: (360) 333-38591 E: mbejar(a)bdiinsulation.com How are we doing? Please leave us a Goocile or YeIpreview- illi For your convenience, to pay an invoice now please click here and then click on the "Pay Now" badge in the bottom right corner. Please consider the environment before printing this e-mail! Table Of Contents UL Listings CLIV(CFS-P PA or CP 617)........................................................ 1 CLIV (Firestop Box Insert).......................................................... 8 F-C-1009....................................................................... 15 F-C-1059....................................................................... 17 F-C-2029(US Only)............................................................... 19 F-C-2071(US Only)............................................................... 20 F-C-2160(US Only)............................................................... 22 F-C-2189(US Only)............................................................... 24 F-C-2205(US Only)............................................................... 26 F-C-2230(US Only)............................................................... 28 F-C-2231(US Only)............................................................... 30 F-C-2232(US Only)............................................................... 32 F-C-2401(US Only)............................................................... 34 F-C-2516....................................................................... 36 F-C-3012....................................................................... 39 F-C-5004....................................................................... 41 F-C-5037....................................................................... 43 F-C-5088....................................................................... 45 CFS-BL Firestop Block Product Data Sheet for CFS-BL Firestop Block .......................................... 47 UL Certificate of Compliance for CFS-BL Firestop Block .................................. 48 Material Information Statement for Firestop Products ..................................... 49 LEED Information for CFS-BL Firestop Block ........................................... 50 CFS-S SIL GG Firestop silicone sealant Product Data Sheet for CFS-S SIL GG Firestop Silicone Sealant ............................ 51 UL Certificate of Compliance for CFS-S SIL SL and CFS-S SIL GG Firestop Silicone Sealant ..... 52 Safety Data Sheet (SDS) for CFS-S SIL SL and CFS-S SIL GG Firestop Silicone Sealant ........ 53 VOC EPA24 CFS-S SIL GG EN .................................................... 62 CP 606 Firestop acrylic sealant Product Data Sheet for CP 606 Flexible Firestop Sealant .................................. 63 UL Certificate of Compliance for CP 606 Flexible Firestop Sealant .......................... 64 Safety Data Sheet (SDS) for CP 606 Flexible Firestop Sealant ............................. 65 LEED Information for CP 606 Flexible Firestop Sealant ................................... 72 CP 617 Firestop Putty Pad Product Data Sheet for CP 617 Firestop Putty Pad ....................................... 73 UL Certificate of Compliance for CP 617 Firestop Putty Pad and CP 619 T Putty Roll ............ 74 Safety Data Sheet (SDS) for CP 617 Firestop Putty Pad, CP 618 Putty Stick, and CP 619T Putty Roll, CFS-D 1 ", CFS-D 25..................................................... 76 LEED V4 Certificate - CDPH Emission Test for CP 617................................... 84 CP 643 N firestop collars Product Data Sheet for CP 643N Firestop Collar ........................................ 85 UL Certificate of Compliance for CP 643N Firestop Collar ................................. 86 Material Information Statement for Firestop Products ..................................... 87 CP 648-E firestop endless wrap strips Product Data Sheet for CP 648-E Firestop Wrap Strip .................................... 88 UL Certificate of Compliance for CP 648-E and CP 648-S Firestop Wrap Strip ................. 89 Material Information Statement for Firestop Products ..................................... 90 VOC_SCAQMD and EPA24_CP648_EN.............................................. 91 CP 648-S firestop single wrap strips Product Data Sheet for CP 648-S Firestop Wrap Strip .................................... 92 UL Certificate of Compliance for CP 648-E and CP 648-S Firestop Wrap Strip ................. 93 Material Information Statement for Firestop Products ..................................... 94 VOC_SCAQMD and EPA24_CP648_EN.............................................. 95 FS-ONE MAX Firestop intumescent sealant Product Data Sheet for FS-ONE MAX Intumescent Firestop Sealant ......................... 96 UL Certificate of Compliance for FS-ONE MAX Intumescent Firestop Sealant .................. 97 Safety Data Sheet (SDS) for FS-ONE MAX Intumescent Firestop Sealant .................... 98 LEED Information for FS-ONE MAX Intumescent Firestop Sealant .......................... 105 Firestop box insert Product Data Sheet for Firestop Box Insert ............................................. 106 UL Certificate of Compliance for Firestop Box Insert......................................107 Material Information Statement for Firestop Products ..................................... 108 LEED Information for Firestop Box Insert .............................................. 109 v1SS c us Classified by Underwriters Laboratories, Inc. to UL 263 and CAN/ULC-S115 1 or 2 Hr Gypsur Assembly (2 Hr SI Wall Opening Protective Materials (CLIV, CLIV7) I I I nLj�j Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. January 30, 2019 ower Cable 118" thick CP617 or CFS-P PA Firestop Putty Pad Wood Stud or Steel Stud (Not Shown) UL Listed Non -Metallic Outlet Box (Refer to UL listing) Or UL Listed Metallic Outlet Box (Refer to UL listing) W C0 z X O m a O H Cl) w a a a Cl) U_ U ti a c.� e: 1 of 7 Wall Opening Protective Materials (CLIV, CLIV7) 1 or 2-Hr. Gypsum Wall Assembly (2-Hr. Shown) APPLICATION: HNI MMIDP OU IEW Ia aaw lt adatain to walalttra memo of Imm "1 hmaaell110 wles tal ham, k 1192m, atreal els 00 hma an appals Was a1 the milt k Im are ie' paM1a0 W tIM heat are mqt Nilllla had b hack. (leltr to UL !Ire lalltaaa lkabry) MPo, Ins., MS. 122ME.An. Tula, OK 7046, US, Tal.:1-BlN?57880 W, ww.ue.hNtl.can Nttl (Cana) Corporatlsn, LkslaaauWy Oncatlo. CA. Tel.: -W 034M,wuw.at.hltd.cm I I I n&j.] Hilti Firestop Systems Steel Stud or Wood Stud (Not Shown) Power Cable Firestop Box Insert UL Listed Non -Metallic Outlet 0Y(RBox (Refer to UL Listing) or UL Listed Metallic Outlet Box 0 efer to UL Listing) Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. January 30, 2019 LJJ Cn z X 0 m a 0 Cn w a a a vh LL U ti a c.� e: 2 of 7 I Wall Opening Protective Materials (CLIV, CLIV7) CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with flush device UL Listed Metallic Outlet Boxes installed with steel mud rings or UL Listed Nonmetallic Outlet Boxes in framed wall assemblies as specified below. When protective material is used on outlet boxes on both sides of the wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back (unless otherwise indicated). Installation shall comply with the National Electrical Code (NFPA 70). Min 1/8 in. thick (CP 617) or min 0.2 in. (CFS-P PA) thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the side of the outlet box against the stud) and conduit fittings/connectors and to completely seal against the stud and gypsum board in the wall cavity unless otherwise noted below. When CFS-P PA is used, the putty pads may be installed with the release liner intact on the outside of the pad with the exception of any overlaps, in which case the liner is to be removed from the bottom layer at the overlap location. The box composition, max device dimensions, hourly rating, type of stud and type of faceplate are specified below. CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with max 4 by 4 by max 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel cover plates in 1 and 2 hr. fire rated gypsum wallboard wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed as specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with max 4-11/16 by 4-11/16 by max 2-1/8 in., or max 4-3/8 by 4-7/8 by max 2-1/8 in., flush device UL Listed Metallic Outlet Boxes installed with steel cover plates for use in 1 hr fire rated V446 gypsum board/steel stud or U341 gypsum board/wood stud Wall and Partition Design No. in the Fire Resistance Directory. When U341 wall design is used, wall shall be sheathed with 5/8 in. gypsum board, and glass or mineral fiber batt insulation shall be installed in stud cavities in accordance with U341 design. Boxes may be installed back-to-back. CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with max 4-11/16 by 4-11/16 by max 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel cover plates for use in 1 and 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Min 0.8 pcf density fiberglass batt insulation is to be installed within the wall cavity required for 1 hr fire rated gypsum board wall assemblies and optional in 2 hr fire rated gypsum wallboard assemblies. CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with max 4 by 3-3/4 by 3 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Carlon Electrical Products, made from polyvinyl chloride, and bearing a 2 hr rating under the "Outlet Boxes and Fittings Classification for Fire Resistance" category in the Fire Resistance Directory. Putty pads and boxes for use in 1 and 2 hr fire rated gypsum wallboard assemblies, framed with min 3-1/2 in. deep wood studs and constructed as specified in the individual U300 Series Wall and Partition Designs in the Fire Resistance Directory. Outlet box secured to wood stud by means of two nailing tabs supplied with the outlet box. Putty pads shall lap min 1/2 in. onto the stud and gypsum board within the stud cavity. Outlet boxes installed with steel or plastic cover plates. CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with max 4 by 4 by 2-7/8 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Carlon Electrical Products, made from polyvinyl chloride, and bearing a 2 hr rating under the "Outlet Boxes and Fittings Classification for Fire Resistance" category in the Fire Resistance Directory. Putty pads and boxes for use in the 1 hr fire rated V446 gypsum board/steel stud or U341 gypsum board/wood stud Wall and Partition Design in the Fire Resistance Directory. When U341 wall design is used, wall shall be sheathed with 5/8 in. gypsum board, and glass or mineral fiber batt insulation shall be installed in stud cavities in accordance with U341 design. Outlet box secured to steel stud by means of fastening tab supplied with the outlet box. Putty pads shall lap min 1/2 in. onto the stud and gypsum board within the stud cavity. Outlet boxes installed with steel or plastic cover plates. Boxes may be installed back to back. CP 617(-L, -XL) Firestop Putty Pads, for use with max 2-1/4 by 3-3/4 by 2-3/4 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Pass and Seymore, Inc., and bearing a 2 hr rating under the "Outlet Boxes and Fittings Classification for Fire Resistance" category in the Fire Resistance Directory. Putty pads and boxes for use in 1 and 2 hr fire rated gypsum wallboard assemblies, framed with min 3-1/2 in. deep wood studs and constructed as specified in the individual U300 Series Wall and Partition Designs in the Fire Resistance Directory. Outlet box secured to wood stud by means of two nailing tabs supplied with the outlet box.Putty pads shall lap min 1/2 in. onto the stud and gypsum board within the stud cavity. Outlet boxes installed with steel or plastic cover plates. CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with max 4 by 3-3/4 by 3 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Allied Molded Products, Inc., made from fiber reinforced thermoplastic and bearing a 2 hr rating under the "Outlet Boxes and Fittings Classification for Fire Resistance" category in the Fire Resistance Directory. Putty pads and boxes for use in 1 hr fire rated gypsum wallboard assemblies, framed with min 3-1/2 in. deep wood studs and constructed as specified in the individual U300 Series Wall and Partition Designs in the Fire Resistance Directory. Outlet box secured to wood stud by means of two nailing tabs supplied with the outlet box. Putty pads shall lap min 1/2 in. onto the stud and gypsum board within the stud cavity. Outlet boxes installed with plastic cover plates. W co z X 0 m 0- 0 N w W a a a cis U_ U ti a t� Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. Hllti FirestopSystems January 30, 2019 Y Page: 3 of 7 Wall Opening Protective Materials (CLIV, CLIV7) CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with max 4 by 4 in. by 1-1/2 in. deep flush device UL Listed Metallic Outlet Boxes installed with steel cover plates in 1 hr. fire rated gypsum wallboard wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed as specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. The boxes are installed back to back with 5 in. by 4 in. UL Classified fire block, CP 657 or CFS-BL Firestop Block installed in the cavity between the two boxes. CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with max 14 by 4 by max 2-1/2 in. flush device UL Listed Metallic Outlet Boxes installed with steel cover plates in 1 and 2 hr. fire rated gypsum board wall assemblies framed with min 5-1/2 in. deep wood or steel studs for 2 hr fire rated walls and min 3-1/2 in. deep wood or steel studs for 1 hr fire rated walls. Walls constructed as specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Stud cavity insulation is required and shall consist of min 5-1/2 in. (2 hr rated walls) or min 3-1/2 in. (1 hr rated walls) thick fiberglass (min 0.8 pcf) or mineral fiber (min 4 pcf). Putty pads shall lap min 1/2 in. onto the stud and gypsum board within the stud cavity. When boxes are interconnected by means of electrical metallic tube (EMT) or conduit, a ball of putty pad material shall be used to completely plug the open end of each EMT or conduit within the box. CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with max 4-11/16 by 4-11/16 by max 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel or plastic cover plates for use in 1 and 2 hr fire rated gypsum board wall assemblies framed with min 5-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Putty pads shall lap min 1/2 in. onto the stud and gypsum board within the stud cavity. When boxes are interconnected by means of electrical metallic tube (EMT) or conduit, a ball of putty pad material shall be used to completely plug the open end of each EMT or conduit within the outlet boxes. Metallic outlet boxes may be provided with steel attachment brackets which offset box min 1/4 in. from stud. When steel attachment brackets are used, putty pad to be affixed to the back and all four sides of the box. CFS-P PA Moldable Putty Pads, for use with max 4-11/16 by 4-11/16 in. by max 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel cover plates in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 and V400 Series Wall and Partition Designs in the Fire Resistance Directory. An additional 3/4 in. ball of putty pad material shall be used to plug the end of each electrical metallic tube or conduit at its connection to the box. CFS-P PA Moldable Putty Pads, for use with max 4 by 4 by 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel or plastic cover plates in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 and V400 Series Wall and Partition Designs in the Fire Resistance Directory. An additional 3/4 in. ball of putty pad material shall be used to plug the end of each electrical metallic tube or conduit at its connection to the box. CFS-P PA Moldable Putty Pads, for use with max 14-1/4 by 4-1/2 by 2-1/2 in. flush device UL Listed Metallic Outlet Boxes installed with steel cover plates in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 and V400 Series Wall and Partition Designs in the Fire Resistance Directory. An additional 3/4 in. ball of putty pad material shall be used to plug the end of each electrical metallic tube or conduit at its connection to the box. HILTI Firestop Box Insert, for use with flush device UL Listed Metallic Outlet Boxes installed with steel mud rings or UL Listed Nonmetallic Outlet Boxes in framed wall assemblies as specified below. When protective material is used on outlet boxes on both sides of the wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back (unless otherwise indicated). Installation shall comply with the National Electrical Code (NFPA 70). The box composition, max device dimensions, hourly rating, type of stud and type of faceplate are specified below. HILTI Firestop Box Insert, for use with max 4-11/16 by 4-11/16 by 2-1/8 in. deep UL Listed Metallic Outlet Boxes without internal clamps in 1 or 2 hr fire rated gypsum wallboard wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed of materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Outlet boxes in 1 hr fire rated walls may be installed with plastic or steel cover plates. Outlet boxes in 2 hr fire rated walls shall be installed with steel cover plates. One 4-3/8 by 4-3/8 in. insert adhered to the interior back wall of the outlet box in accordance with the instructions supplied with the product. Smaller sized inserts may be cut and combined to achieve the 4-3/8 x 4-3/8 in coverage. HILTI Firestop Box Insert, for use with max 4 by 4 by 1-1/2 in. deep and 2-1/8 in. deep UL Listed Metallic Outlet Boxes without internal clamps in 1 or 2 hr fire rated gypsum wallboard wall assemblies framed with min 3 1/2 in. deep steel or wood studs and constructed of materials and in the manner specified in the individual U400, V400 or U300 Series Wall and Partition Designs in the Fire Resistance Directory, as summarized in the Table below. One 3-11/16 by 3-3/4 in. insert adhered to the interior back wall of the outlet box in accordance with the instructions supplied with the product. Smaller sized inserts may be cut and combined to achieve the 3-11/16 x 3-3/4 in coverage. W co z X 0 m 0- 0 W w a a a cis U_ U ti a t� Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. Hllti FirestopSystems January 30, 2019 Y Page: 4 of 7 Wall Opening Protective Materials (CLIV, CLIV7) W Cn Z X 0 m a 0 Cn w a a a Box Size Type of Box and Cover Plate Hourly Rating Wall Type 4 x 4 x 2-118 in deep Metallic w/ steel cover plates 2-hour U300, U400 or V400 -wood or steel studs Box Size Inserts Used Fire Rating Wall Type 4-1/2 x 8-1/2 x 1-5/8 in deep Two 3-11/16 x 3-3/4 in. inserts 2 hour U300, U400 or V400 -wood or steel studs ** 3-314 x 5-1/2 x 2-112 in deep One 3-11116 x 3-314 in. insert and one 1-718 1 hour U300, U400, or V400 -wood or steel studs x 2-13116 in. insert ** -Min 314 in. deep plaster rings installed over outlet box. After installation of gypsum board, nom 114 in. thickness of Hilti FS-ONE Sealant or FS-ONE MAX Intumescent Sealant, bearing the UL Classification Marking for Fill, Void or Cavity Materials, applied between the base layer of wallboard and the plaster ring. Wall Opening Protective Materials (CLIV, CLIV7) Firestop Box Inserts, for use with max 4 by 4 by 2-1/8 in deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 94 mm wide by 95 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with steel cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Firestop Box Inserts, for use with max 4 by 4 by 1-1/2 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep wood studs and with max 4 by 4 by 2-1/8 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 94 mm wide by 95 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with plastic cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Firestop Box Inserts, for use with 4-11/16 by 4-11/16 by 2-1/8 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 111 mm wide by 111 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Smaller sized inserts may be cut and combined to achieve the 111 mm by 111 mm coverage and adhered to the interior back wall of the outlet box. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with plastic or steel cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Firestop Box Inserts, for use with 4-11/16 by 4-11/16 by 2-1/8 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 111 mm wide by 111 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Smaller sized inserts may be cut and combined to achieve the 111 mm by 111 mm coverage and adhered to the interior back wall of the outlet box. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with steel cover plates. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Firestop Box Inserts, for use with max 3-3/4 by 5-1/2 by 2-1/2 in deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel or wood studs and constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 94 mm wide by 95 mm high and one 47 mm wide by 71 mm high inserts adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with steel cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Firestop Box Inserts, for use with 4-3/8 by 4-7/8 by 2-1/4 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 111 mm wide by 111 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Smaller sized inserts may be cut and combined to achieve the 111 mm by 111 mm coverage and adhered to the interior back wall of the outlet box. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with plastic or steel cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. W co z x O m 0- 0 H Cn w W a a a cis U ti a U Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. Hllti FirestopSystems January 30, 2019 Y Page: 6 of 7 Wall Opening Protective Materials (CLIV, CLIV7) W Cn Z X 0 m a 0 Cn w a a a Cn U_ U ti d U Firestop Box Inserts, for use with max 4 by 4 by 2-1/8 in deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 94 mm wide by 95 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with steel cover plates. A max 3/8 in. diam opening at one edge may be provided Firestop Box Inserts, for use with 4-3/8 by 4-7/8 by 2-1/4 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 111 mm wide by 111 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Smaller sized inserts may be cut and combined to achieve the 111 mm by 111 mm coverage and adhered to the interior back wall of the outlet box. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with steel cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Firestop Box Inserts, for use with max 4-11/16 by 4-11/16 by 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel mud rings and plastic or steel cover plates in 1 h or 2 h fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Min 3-1/2 in. thick fiberglass (min 0.5 pcf) or mineral wool (min 4.0 pcf) batt insulation is to be installed within the wall cavity. One 4-3/8 by 4-3/8 in. insert adhered to the interior back wall of the outlet box in accordance with the instructions supplied with the product. Installation to comply with the National Electrical Code (NFPA 70). A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of the wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. Hllti FirestopSystems January 30, 2019 Y Page: 7 of 7 v1SS c us Classified by Underwriters Laboratories, Inc. to UL 263 and CAN/ULC-S115 1 or 2 Hr Gypsur Assembly (2 Hr SI Wall Opening Protective Materials (CLIV, CLIV7) I I I nLj�j Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. January 30, 2019 ower Cable 118" thick CP617 or CFS-P PA Firestop Putty Pad Wood Stud or Steel Stud (Not Shown) UL Listed Non -Metallic Outlet Box (Refer to UL listing) Or UL Listed Metallic Outlet Box (Refer to UL listing) W C0 z X O m a O H Cl) w a a a Cl) U_ U ti a c.� e: 1 of 7 Wall Opening Protective Materials (CLIV, CLIV7) 1 or 2-Hr. Gypsum Wall Assembly (2-Hr. Shown) APPLICATION: HNI MMIDP OU IEW Ia aaw lt adatain to walalttra memo of Imm "1 hmaaell110 wles tal ham, k 1192m, atreal els 00 hma an appals Was a1 the milt k Im are ie' paM1a0 W tIM heat are mqt Nilllla had b hack. (leltr to UL !Ire lalltaaa lkabry) MPo, Ins., MS. 122ME.An. Tula, OK 7046, US, Tal.:1-BlN?57880 W, ww.ue.hNtl.can Nttl (Cana) Corporatlsn, LkslaaauWy Oncatlo. CA. Tel.: -W 034M,wuw.at.hltd.cm I I I n&j.] Hilti Firestop Systems Steel Stud or Wood Stud (Not Shown) Power Cable Firestop Box Insert UL Listed Non -Metallic Outlet 0Y(RBox (Refer to UL Listing) or UL Listed Metallic Outlet Box 0 efer to UL Listing) Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. January 30, 2019 LJJ Cn z X 0 m a 0 Cn w a a a vh LL U ti a c.� e: 2 of 7 Wall Opening Protective Materials (CLIV, CLIV7) CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with flush device UL Listed Metallic Outlet Boxes installed with steel mud rings or UL Listed Nonmetallic Outlet Boxes in framed wall assemblies as specified below. When protective material is used on outlet boxes on both sides of the wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back (unless otherwise indicated). Installation shall comply with the National Electrical Code (NFPA 70). Min 1/8 in. thick (CP 617) or min 0.2 in. (CFS-P PA) thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the side of the outlet box against the stud) and conduit fittings/connectors and to completely seal against the stud and gypsum board in the wall cavity unless otherwise noted below. When CFS-P PA is used, the putty pads may be installed with the release liner intact on the outside of the pad with the exception of any overlaps, in which case the liner is to be removed from the bottom layer at the overlap location. The box composition, max device dimensions, hourly rating, type of stud and type of faceplate are specified below. CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with max 4 by 4 by max 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel cover plates in 1 and 2 hr. fire rated gypsum wallboard wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed as specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with max 4-11/16 by 4-11/16 by max 2-1/8 in., or max 4-3/8 by 4-7/8 by max 2-1/8 in., flush device UL Listed Metallic Outlet Boxes installed with steel cover plates for use in 1 hr fire rated V446 gypsum board/steel stud or U341 gypsum board/wood stud Wall and Partition Design No. in the Fire Resistance Directory. When U341 wall design is used, wall shall be sheathed with 5/8 in. gypsum board, and glass or mineral fiber batt insulation shall be installed in stud cavities in accordance with U341 design. Boxes may be installed back-to-back. CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with max 4-11/16 by 4-11/16 by max 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel cover plates for use in 1 and 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Min 0.8 pcf density fiberglass batt insulation is to be installed within the wall cavity required for 1 hr fire rated gypsum board wall assemblies and optional in 2 hr fire rated gypsum wallboard assemblies. CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with max 4 by 3-3/4 by 3 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Carlon Electrical Products, made from polyvinyl chloride, and bearing a 2 hr rating under the "Outlet Boxes and Fittings Classification for Fire Resistance" category in the Fire Resistance Directory. Putty pads and boxes for use in 1 and 2 hr fire rated gypsum wallboard assemblies, framed with min 3-1/2 in. deep wood studs and constructed as specified in the individual U300 Series Wall and Partition Designs in the Fire Resistance Directory. Outlet box secured to wood stud by means of two nailing tabs supplied with the outlet box. Putty pads shall lap min 1/2 in. onto the stud and gypsum board within the stud cavity. Outlet boxes installed with steel or plastic cover plates. CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with max 4 by 4 by 2-7/8 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Carlon Electrical Products, made from polyvinyl chloride, and bearing a 2 hr rating under the "Outlet Boxes and Fittings Classification for Fire Resistance" category in the Fire Resistance Directory. Putty pads and boxes for use in the 1 hr fire rated V446 gypsum board/steel stud or U341 gypsum board/wood stud Wall and Partition Design in the Fire Resistance Directory. When U341 wall design is used, wall shall be sheathed with 5/8 in. gypsum board, and glass or mineral fiber batt insulation shall be installed in stud cavities in accordance with U341 design. Outlet box secured to steel stud by means of fastening tab supplied with the outlet box. Putty pads shall lap min 1/2 in. onto the stud and gypsum board within the stud cavity. Outlet boxes installed with steel or plastic cover plates. Boxes may be installed back to back. CP 617(-L, -XL) Firestop Putty Pads, for use with max 2-1/4 by 3-3/4 by 2-3/4 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Pass and Seymore, Inc., and bearing a 2 hr rating under the "Outlet Boxes and Fittings Classification for Fire Resistance" category in the Fire Resistance Directory. Putty pads and boxes for use in 1 and 2 hr fire rated gypsum wallboard assemblies, framed with min 3-1/2 in. deep wood studs and constructed as specified in the individual U300 Series Wall and Partition Designs in the Fire Resistance Directory. Outlet box secured to wood stud by means of two nailing tabs supplied with the outlet box.Putty pads shall lap min 1/2 in. onto the stud and gypsum board within the stud cavity. Outlet boxes installed with steel or plastic cover plates. CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with max 4 by 3-3/4 by 3 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Allied Molded Products, Inc., made from fiber reinforced thermoplastic and bearing a 2 hr rating under the "Outlet Boxes and Fittings Classification for Fire Resistance" category in the Fire Resistance Directory. Putty pads and boxes for use in 1 hr fire rated gypsum wallboard assemblies, framed with min 3-1/2 in. deep wood studs and constructed as specified in the individual U300 Series Wall and Partition Designs in the Fire Resistance Directory. Outlet box secured to wood stud by means of two nailing tabs supplied with the outlet box. Putty pads shall lap min 1/2 in. onto the stud and gypsum board within the stud cavity. Outlet boxes installed with plastic cover plates. W co z X 0 m 0- 0 N w W a a a cis U_ U ti a t� Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. Hllti FirestopSystems January 30, 2019 Y Page: 3 of 7 Wall Opening Protective Materials (CLIV, CLIV7) CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with max 4 by 4 in. by 1-1/2 in. deep flush device UL Listed Metallic Outlet Boxes installed with steel cover plates in 1 hr. fire rated gypsum wallboard wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed as specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. The boxes are installed back to back with 5 in. by 4 in. UL Classified fire block, CP 657 or CFS-BL Firestop Block installed in the cavity between the two boxes. CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with max 14 by 4 by max 2-1/2 in. flush device UL Listed Metallic Outlet Boxes installed with steel cover plates in 1 and 2 hr. fire rated gypsum board wall assemblies framed with min 5-1/2 in. deep wood or steel studs for 2 hr fire rated walls and min 3-1/2 in. deep wood or steel studs for 1 hr fire rated walls. Walls constructed as specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Stud cavity insulation is required and shall consist of min 5-1/2 in. (2 hr rated walls) or min 3-1/2 in. (1 hr rated walls) thick fiberglass (min 0.8 pcf) or mineral fiber (min 4 pcf). Putty pads shall lap min 1/2 in. onto the stud and gypsum board within the stud cavity. When boxes are interconnected by means of electrical metallic tube (EMT) or conduit, a ball of putty pad material shall be used to completely plug the open end of each EMT or conduit within the box. CP 617(-L, -XL) or CFS-P PA Firestop Putty Pads, for use with max 4-11/16 by 4-11/16 by max 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel or plastic cover plates for use in 1 and 2 hr fire rated gypsum board wall assemblies framed with min 5-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Putty pads shall lap min 1/2 in. onto the stud and gypsum board within the stud cavity. When boxes are interconnected by means of electrical metallic tube (EMT) or conduit, a ball of putty pad material shall be used to completely plug the open end of each EMT or conduit within the outlet boxes. Metallic outlet boxes may be provided with steel attachment brackets which offset box min 1/4 in. from stud. When steel attachment brackets are used, putty pad to be affixed to the back and all four sides of the box. CFS-P PA Moldable Putty Pads, for use with max 4-11/16 by 4-11/16 in. by max 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel cover plates in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 and V400 Series Wall and Partition Designs in the Fire Resistance Directory. An additional 3/4 in. ball of putty pad material shall be used to plug the end of each electrical metallic tube or conduit at its connection to the box. CFS-P PA Moldable Putty Pads, for use with max 4 by 4 by 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel or plastic cover plates in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 and V400 Series Wall and Partition Designs in the Fire Resistance Directory. An additional 3/4 in. ball of putty pad material shall be used to plug the end of each electrical metallic tube or conduit at its connection to the box. CFS-P PA Moldable Putty Pads, for use with max 14-1/4 by 4-1/2 by 2-1/2 in. flush device UL Listed Metallic Outlet Boxes installed with steel cover plates in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 and V400 Series Wall and Partition Designs in the Fire Resistance Directory. An additional 3/4 in. ball of putty pad material shall be used to plug the end of each electrical metallic tube or conduit at its connection to the box. HILTI Firestop Box Insert, for use with flush device UL Listed Metallic Outlet Boxes installed with steel mud rings or UL Listed Nonmetallic Outlet Boxes in framed wall assemblies as specified below. When protective material is used on outlet boxes on both sides of the wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back (unless otherwise indicated). Installation shall comply with the National Electrical Code (NFPA 70). The box composition, max device dimensions, hourly rating, type of stud and type of faceplate are specified below. HILTI Firestop Box Insert, for use with max 4-11/16 by 4-11/16 by 2-1/8 in. deep UL Listed Metallic Outlet Boxes without internal clamps in 1 or 2 hr fire rated gypsum wallboard wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed of materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Outlet boxes in 1 hr fire rated walls may be installed with plastic or steel cover plates. Outlet boxes in 2 hr fire rated walls shall be installed with steel cover plates. One 4-3/8 by 4-3/8 in. insert adhered to the interior back wall of the outlet box in accordance with the instructions supplied with the product. Smaller sized inserts may be cut and combined to achieve the 4-3/8 x 4-3/8 in coverage. HILTI Firestop Box Insert, for use with max 4 by 4 by 1-1/2 in. deep and 2-1/8 in. deep UL Listed Metallic Outlet Boxes without internal clamps in 1 or 2 hr fire rated gypsum wallboard wall assemblies framed with min 3 1/2 in. deep steel or wood studs and constructed of materials and in the manner specified in the individual U400, V400 or U300 Series Wall and Partition Designs in the Fire Resistance Directory, as summarized in the Table below. One 3-11/16 by 3-3/4 in. insert adhered to the interior back wall of the outlet box in accordance with the instructions supplied with the product. Smaller sized inserts may be cut and combined to achieve the 3-11/16 x 3-3/4 in coverage. W co z X 0 m 0- 0 W w a a a cis U_ U ti a t� Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. Hllti FirestopSystems January 30, 2019 Y Page: 4 of 7 Wall Opening Protective Materials (CLIV, CLIV7) W Cn Z X 0 m a 0 Cn w a a a Box Size Type of Box and Cover Plate Hourly Rating Wall Type 4 x 4 x 2-118 in deep Metallic w/ steel cover plates 2-hour U300, U400 or V400 -wood or steel studs Box Size Inserts Used Fire Rating Wall Type 4-1/2 x 8-1/2 x 1-5/8 in deep Two 3-11/16 x 3-3/4 in. inserts 2 hour U300, U400 or V400 -wood or steel studs ** 3-314 x 5-1/2 x 2-112 in deep One 3-11116 x 3-314 in. insert and one 1-718 1 hour U300, U400, or V400 -wood or steel studs x 2-13116 in. insert ** -Min 314 in. deep plaster rings installed over outlet box. After installation of gypsum board, nom 114 in. thickness of Hilti FS-ONE Sealant or FS-ONE MAX Intumescent Sealant, bearing the UL Classification Marking for Fill, Void or Cavity Materials, applied between the base layer of wallboard and the plaster ring. Wall Opening Protective Materials (CLIV, CLIV7) Firestop Box Inserts, for use with max 4 by 4 by 2-1/8 in deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 94 mm wide by 95 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with steel cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Firestop Box Inserts, for use with max 4 by 4 by 1-1/2 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep wood studs and with max 4 by 4 by 2-1/8 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 94 mm wide by 95 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with plastic cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Firestop Box Inserts, for use with 4-11/16 by 4-11/16 by 2-1/8 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 111 mm wide by 111 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Smaller sized inserts may be cut and combined to achieve the 111 mm by 111 mm coverage and adhered to the interior back wall of the outlet box. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with plastic or steel cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Firestop Box Inserts, for use with 4-11/16 by 4-11/16 by 2-1/8 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 111 mm wide by 111 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Smaller sized inserts may be cut and combined to achieve the 111 mm by 111 mm coverage and adhered to the interior back wall of the outlet box. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with steel cover plates. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Firestop Box Inserts, for use with max 3-3/4 by 5-1/2 by 2-1/2 in deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel or wood studs and constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 94 mm wide by 95 mm high and one 47 mm wide by 71 mm high inserts adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with steel cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Firestop Box Inserts, for use with 4-3/8 by 4-7/8 by 2-1/4 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 1 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 111 mm wide by 111 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Smaller sized inserts may be cut and combined to achieve the 111 mm by 111 mm coverage and adhered to the interior back wall of the outlet box. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with plastic or steel cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. W co z x O m 0- 0 H Cn w W a a a cis U ti a U Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. Hllti FirestopSystems January 30, 2019 Y Page: 6 of 7 Wall Opening Protective Materials (CLIV, CLIV7) W Cn Z X 0 m a 0 Cn w a a a Cn U_ U ti d U Firestop Box Inserts, for use with max 4 by 4 by 2-1/8 in deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 94 mm wide by 95 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with steel cover plates. A max 3/8 in. diam opening at one edge may be provided Firestop Box Inserts, for use with 4-3/8 by 4-7/8 by 2-1/4 in. deep flush device UL Listed Metallic Outlet Boxes without internal clamps in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the Fire Resistance Directory. One 111 mm wide by 111 mm high insert adhered to the interior back wall of the outlet box in accordance with the installation instructions supplied with the product. Smaller sized inserts may be cut and combined to achieve the 111 mm by 111 mm coverage and adhered to the interior back wall of the outlet box. Installation to comply with the National Electrical Code, (NFPA 70). Outlet boxes installed with steel cover plates. A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Firestop Box Inserts, for use with max 4-11/16 by 4-11/16 by 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel mud rings and plastic or steel cover plates in 1 h or 2 h fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Min 3-1/2 in. thick fiberglass (min 0.5 pcf) or mineral wool (min 4.0 pcf) batt insulation is to be installed within the wall cavity. One 4-3/8 by 4-3/8 in. insert adhered to the interior back wall of the outlet box in accordance with the instructions supplied with the product. Installation to comply with the National Electrical Code (NFPA 70). A max 3/8 in. diam opening at one edge may be provided to permit access to the electrical box ground screw. When protective material is used within outlet boxes on both sides of the wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back. Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. Hllti FirestopSystems January 30, 2019 Y Page: 7 of 7 c us Classified by Underwriters Laboratories, Inc. to UL 1479 and CAN/ULC-S115 System No. F-C-1009 ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Rating —1 and 2 Hr (See Item 1) F Rating —1 and 2 Hr (See Item 1) T Rating —1/4 Hr FT Rating —1/4 Hr L Rating At Ambient — Less Than 1 CFM/sq ft FH Rating —1 and 2 Hr (See Item 1) L Rating At 400 F — 4 CFM/sq ft FTH Rating —1/4 Hr L Rating At Ambient — Less Than 1 CFM/sq ft L Rating At 400 F — 4 CFM/sq ft 0 n SECTION A -A Floor -Ceiling Assembly — The 1 or 2 hr fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The F Rating of the firestop system is equal to the rating of the floor -ceiling assembly. The general construction features of the floor -ceiling assembly are summarized below: A. Flooring System — Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Diam of opening to be max 1 in. (25 mm) larger than diam of pipe. As an alternate, the opening may be square -cut with a max dimension 1 in. (25 mm) greater than the diam of the pipe. B. Wood Joists* — Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Furring Channels — (Not Shown) —(As required ) Resilient galvanized steel furring installed in accordance with the manner specified in the individual L500 Series Designs in the Fire Resistance Directory. D. Gypsum Board* — Thickness, type, number of layers and fasteners shall be as specified in the individual Floor -Ceiling Design. Diam of opening to be max 1 in. (25 mm) larger than diam of pipe. Reproduced by HILTI, Inc. Courtesy of I Ed3 Underwriters Laboratories, Inc. Hilti Firesto March 08, 2018 p Systems Page: 1 of 2 System No. F-C-1009 2. Chase Wall — (Optional) - The through penetrant (Item 3) may be routed through a fire rated or non -rated single, double, or staggered wood stud/gypsum board chase wall. Depth of chase wall to be min 1 in. greater than the diameter of the through penetrant. The chase wall shall be constructed to include the following construction features: A. Studs — Nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 by 152 mm) or double nom 2 by 4 in. (51 by 102 mm) lumber studs. Nom 2 by 4 in. (51 by 102 mm) studs are allowed for through -penetrants (Item 3) not exceeding nom 2 in. (51 mm) diam. B. Sole Plate — Nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 by 152 mm) or parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Diam of opening is to be max 1 in. (925 mm) larger than diam of pipe. As an alternate, the opening may be square -cut with a max dimension 1 in. (25 mm) greater than the diam of the pipe. Plates may be discontinuous over opening, terminating at two opposing edges of opening. Max length of discontinuity to be 1 in. (25 mm) greater than diam of through penetrant. C. Top Plate — The double top plate shall consist of two nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 by 152 mm) or two sets of parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Diam of opening is to be max 1 in. (25 mm) larger than diam of pipe. As an alternate, the opening may be square -cut with a max dimension 1 in. (25 mm) greater than the diam of the pipe. Plates may be discontinuous over opening, terminating at two opposing edges of opening. Max length of discontinuity to be 1 in. (25 mm) greater than diam of through penetrant. D. Gypsum Board* — One or two layers of min 112 in. (13 mm) gypsum board. E. Steel Plate — (Not Shown) When lumber plates are discontinuous, nom 1-112 in. (38 mm) wide No. 20 gauge (or heavier) galv steel plates shall be installed to connect each discontinuous lumber plate and to provide a form for the fill material. Steel plates sized to lap 2 in. (51 mm) onto each discontinuous lumber plate and secured to lumber plates with steel screws or nails. 3. Through Penetrants — One metallic pipe, conduit or tubing to be installed within the firestop system. Pipe, conduit or tubing to be rigidly supported on both sides of floor assembly. The annular space within the firestop system shall be min 0 in. (point contact) to max 1 in. (25 mm). The following types and sizes of metallic pipes or conduits may be used: A. Steel Pipe — Nom 4 in. (102 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe — Nom 4 in. (102 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing or steel conduit. D. Copper Tubing — Nom (102 mm) 4 in. diam (or smaller) Type L (or heavier) copper tubing. E. Copper Pipe — Nom (102 mm) 4 in. diam (or smaller) Regular (or heavier) copper pipe. 4. Fill, Void or Cavity Material* — Sealant — Min 314 in. (19 mm) thickness of fill material applied within the annulus, flush with the top surface of the floor or the sole plate. Min 518 in. (16 mm) thickness of fill material applied within the annulus, flush with bottom surface of ceiling or lower top plate. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP601S, CFS-S SIL GG, CP606, FS-One Sealant or FS-ONE MAX Intumescent Sealant (Note: L Ratings apply only when FS-ONE Sealant is used.) * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. I I I �_E Ed3 Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. March 08, 2018 Page: 2 of 2 c us Classified by Underwriters Laboratories, Inc. to UL 1479 and CAN/ULC-S115 System No. F-C-1059 ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings —1 and 2 Hr (See Item 1) F Ratings —1 and 2 Hr (See Iteml ) T Ratings — 0 and 1/2 Hr (See Item 1) FT Ratings — 0 and 1/2 Hr (See Iteml ) L Rating At Ambient — Less Than 1 CFM/sq ft FH Ratings —1 and 2 Hr (See Item 1) L Rating At 400 F — 4 CFM/sq ft FTH Ratings — 0 and 1/2 Hr (See Item 1) L Rating At Ambient — Less Than 1 CFM/sq ft L Rating At 400 F — 4 CFM/sq ft SECTION A -A 0) LO 0 U Floor -Ceiling Assembly — The 1 or 2 hr fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The F, FH Rating of the firestop system is equal to the rating of the floor -ceiling and wall assemblies. The T, FT and FTH Rating of the firestop system is 0 hr for 1 hr rated floor ceiling assembly and 1/2 hr for 2 hr rated floor ceiling assembly. The general construction features of the floor -ceiling assembly are summarized below: A. Flooring System — Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Max diam of opening shall be 7-5/8 in. (194 mm). B. Wood Joists* — Nom 10 in (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Gypsum Board* — Thickness, type, number of layers and fasteners shall be as specified in the individual Floor -Ceiling Design. Max diam of opening shall be 7-5/8 in. (194 mm). D. Furring Channels — (Not Shown) (As required) Resilient galvanized steel furring installed in accordance with the manner specified in the individual L500 Series Designs in the Fire Resistance Directory. Reproduced by HILTI, Inc. Courtesy of I Ed3 Underwriters Laboratories, Inc. Hllti Firesto December06,2018 p Systems Page: 1 of 2 System No. F-C-1059 M LO 0 U 1.1 Chase Wall — (Not Shown, Optional) —The through penetrants (Item 2) may be routed through a 1 or 2 hr fire -rated single, double or staggered wood stud/gypsum wallboard chase wall having a fire rating consistent with that of the floor -ceiling assembly. The chase wall shall be constructed of the materials and in the manner specified in the individual U300 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features : A. Studs — Nom 2 by 8 in. (51 by 203 mm) lumber or double nom 2 by 6 in. (51 by 152 mm) lumber studs. B. Sole Plate — Nom 2 by 8 in. (51 by 203 mm) lumber or parallel 2 by 6 in. (51 by 152 mm) lumber plates, tightly butted. Max diam of opening shall be 7-5/8 in. (194 mm). C. Top Plate — The double top plate shall consist of two nom 2 by 8 in. (51 by 203 mm) lumber plates or two sets of nom 2 by 6 in. (51 by 152 mm) lumber plates tightly butted. Max diam of opening is 7-5/8 in. (194 mm). D. Gypsum Board* — Thickness, type, number or layers and fasteners shall be as specified in individual Wall and Partition Designs. 2. Through Penetrants — One metallic tubing, pipe or conduit to be installed concentrically or eccentrically within the firestop system. Annular space between pipe or conduit and edge of opening to be min 1/4 in. (6 mm) and max 3/4 in. (19 mm). Pipe, tubing or conduit to be rigidly supported on both sides of floor -ceiling assembly. The following types and sizes of metallic pipes, tubing or conduit may be used: A. Steel Pipe — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 (or heavier) steel pipe. B. Iron Pipe — Nom 6 in. (152 mm) diam (or smaller) cast or ductile pipe. C. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing or nom 6 in. diam (or smaller) steel conduit. D. Steel Flexible Metal Conduit + — Nom 2 in. (51 mm) diam (or smaller) steel flexible metal conduit. See Flexible Metal Conduit (DXUZ) category in the Electrical Construction Materials Directory for names of manufacturers. 3. Fill, Void or Cavity Material* —Sealant — Min 5/8 in. (16 mm) or 1-1/4 in. (32 mm) thickness of sealant applied within annular space, flush with the bottom surface of gypsum wallboard or lower top plate for 1 and 2 hr floors respectively. Min. 3/4 in. (19 mm) thickness of sealant applied within annular space, flush with top surface of floor or sole plate. HILTI INC — FS-ONE Sealant or FS-ONE MAX Intumescent Sealant +Bearing the UL Listing Mark. * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. I I I �_E Md3 Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. December 06, 2018 Page: 2 of 2 (�15 Classified by Underwriters Laboratories, Inc. to UL 1479 System No. F-C-2029 F Rating - 2 Hr System tested with a pressure differential of 2.5 Pa between the exposed and the unexposed surfaces with the higher pressure on the exposed side. 1. Floor -Ceiling Assembly — The fire -rated wood joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L 500 Series Floor -Ceiling Design in the UL Fire Resistance Directory, as summarized below: A. Flooring System — Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. B. Wood Joists — Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Furring Channels — (Not Shown) — (As required) Resilient galvanized steel furring installed in accordance with the manner specified in the individual L500 Series Designs in the Fire Resistance Directory. D. Gypsum Board* — Thickness, type, number of layers and fasteners shall be as specified in the individual Floor -Ceiling Design. 2. Through -Penetrants — One nonmetallic pipe, conduit or tubing to be installed within the firestop system. Diam of openings hole -sawed through flooring system and through two layers gypsum wallboard ceiling to be 0 to 1/2 in. (13 mm) larger than the outside diam of through -penetrant. Pipe or conduit to be rigidly supported on both sides of the floor -ceiling assembly. The following types and sizes of nonmetallic pipes may be used: A. Polyvinyl Chloride (PVC) Pipe — Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid -core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 4 in. (102 mm) diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. 3. Firestop System — The details of the firestop system shall be as follows: A. Steel Collar— Collar fabricated from coils of precut min 0.017 in. (0.43 mm) thick (No. 28 MSG) galv steel available from the sealant manufacturer. Collar shall be nom 1-3/4 in. (44 mm) deep with 1 in. (25 mm) wide by 2 in. (51 mm) long anchors tabs on 2 in. (51 mm) centers for securement to floor and ceiling surfaces. The anchor tabs shall be bent 90 degree outward for securement to the floor and ceiling surfaces. The opposite side incorporates retainer tabs, 1/2 in. (13 mm) wide by 3/16 in. (5 mm) long, prebent toward the pipe surface. Collar shall be wrapped around pipe maintaining a 1 in. (25 mm) distance between pipe and collar, and overlapping min 1 in. (25 mm) at seam. Collar secure to subfloor with wood screws and washers at every other tab. Collar secured to gypsum board ceiling using 3/16 in. (5 mm) diam steel toggle bolts in conjunction with 1-1/4 in. (32 mm) diam steel fender washers at every other tab. After sealant is installed (Item 3B), the collars shall be compressed around the pipe using a 1/2 in. (13 mm) wide by 0.028 in. (0.7 mm) thick stainless steel band clamp fastened at the collar mid -height. B. Fill, Void or Cavity Material* — Sealant — Fill material to be installed to completely fill the collar and provide a min 1 /4 in. (6 mm) thickness in the annular spaces at the floor and ceiling. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant or FS-ONE MAX Intumescent Sealant. * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. I I 1 ;3 Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. January 20, 2015 19 (�15 Classified by Underwriters Laboratories, Inc. to UL 1479 r^ Lq System No. F-C-2071 F Ratings —1 and 2 Hr T Rating — 0 Hr SECTION A -A Floor -Ceiling Assembly —The 1 or 2 hr fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The F Rating of the firestop system is equal to the rating of the floor -ceiling and wall assemblies. The general construction features of the floor -ceiling assembly are summarized below: A. Flooring System — Lumber of plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Diam of opening shall be 1 in. (25 mm) larger than the nom diam of through -penetrant (Item 3). B. Wood Joists* — Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Furring Channels — (Not Shown) — (As required) - Resilient galvanized steel furring installed in accordance with the manner specified in the individual L500 Series Designs in the Fire Resistance Directory. D. Gypsum Board* — Thickness, type, number of layers and fasteners shall be as specified in the individual Floor -Ceiling Design. Diam of opening shall be 1 in. (25 mm) larger than the nom diam of through -penetrant (Item 3). Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. H i Iti F i resto Systems January 20, 2015 p Y ms Page: 1 of 2 20 System No. F-C-2071 Chase Wall — (Optional) - The through penetrant (Item 3) may be routed through a 1 or 2 hr fire -rated single, double or staggered wood stud/gypsum wallboard chase wall having a fire rating consistent with that of the floor -ceiling assembly. The chase wall shall be constructed of the materials and in the manner specified in the individual U300 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs — Nom 2 by 4 in. (51 by 102 mm) lumber studs. B. Sole Plate — Nom 2 by 4 in. (51 by 102 mm) lumber plates. Diam of opening shall be 1 in. (25 mm) larger than the nom diam of through -penetrant (Item 3). C. Top Plate — The double top plate shall consist of two nom 2 by 4 in. (51 by 102 mm) lumber plates. Diam of opening shall be 1 in. (25 mm) larger than the nom diam of through -penetrant (Item 3). D. Gypsum Board* — Thickness, type, number of layers and fasteners shall be as specified in individual Wall and Partition Design. Through -Penetrants — One nonmetallic pipe to be installed within the firestop system. An annular space of min 1/4 in. (6 mm) to max 3/8 in. (10 mm) is required within the firestop system. Pipe to be rigidly supported on both sides of the floor -ceiling assembly. The following types of nonmetallic pipes may be used: A. Polyvinyl Chloride (PVC) Pipe — Nom 2 in. (51 mm) diam (or smaller) Schedule 40 solid core PVC pipe for use in closed (process or supply) piping system. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 2 in. (51 mm) diam (or smaller) SDR17 CPVC pipe for use in closed (process or supply) piping systems. Fill, Void or Cavity Material* — Sealant — Min 3/4 in. (19 mm) thickness of fill material applied within the annulus, flush with top surface of floor or sole plate. Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with bottom surface of ceiling or lower top plate. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant or FS-ONE MAX Intumescent Sealant. * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. I I I �_n ;a Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. January 20, 2015 Page: 2 of 2 21 Classified by Underwriters Laboratories, Inc. to UL 1479 �A 3 2 yA System No. F-C-2160 F Rating —1 and 2 Hr T Rating —1 and 2 Hr VLV I IW111 A -A 1. Floor -Ceiling Assembly — The 1 and 2 hr fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The general construction features of the floor -ceiling assembly are summarized below: A. Flooring System — Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Diam of opening shall be 2 in. (51 mm) larger than the nom diam of through penetrant (Item 2). B. Wood Joists* — Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Furring Channels (Not Shown) — Resilient galv steel furring installed perpendicular to wood joists between first and second layers of wallboard (Item 1 D). Furring channels spaced max 24 in. (610 mm). D. Gypsum Board* — Nom 4 ft (1.2 m) wide by 5/8 in. (16 mm) thick as specified in the individual Floor -Ceiling Design. First layer of wallboard nailed to wood joists. Second layer of wallboard screw -attached to furring channels. Diam of opening shall be 2 in. (51 mm) larger than the nom diam of through penetrant (Item 2). 1.1 Chase Wall — (Optional, not Shown) — The through penetrants (Item No. 2) may be routed through a fire -rated or non -rated single, double or staggered wood stud/gypsum wall board chase wall. The chase wall shall be constructed to include the following construction features: A. Studs — Nom 2 by 6 in. (51 by 152 mm) or double nom 2 by 4 in. (51 by 102 mm) lumber studs. B. Sole Plate — Nom 2 by 6 in. (51 by 152 mm) or parallel nom 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Diam of opening shall be 2 in. (51 mm) larger than the nom diam of through penetrant (Item 2). C. Top Plate — The double top plate shall consist of two nom 2 by 6 in. (51 by 152 mm) or two sets of parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Diam of opening shall be 2 in. (51 mm) larger than the nom diam of through penetrant (Item 2). D. Gypsum Board* — One or two layers of min 1/2 in. (14 mm) gypsum board. Reproduced by HILTI, Inc. Courtesy of I Ed3 Underwriters Laboratories, Inc. April 06 Hilti Firesto , 2018 p Systems Page: 1 of 2 System No. F-C-2160 2. Through Penetrants — One nonmetallic pipe or conduit to be installed concentrically or eccentrically within the firestop system. Annular space between pipe or conduit and edge of opening to be min 1/2 in. (13 mm) and max 1-1/8 in. (29 mm). Pipe or conduit to be rigidly supported on both sides of floor -ceiling assembly. The following types and sizes of nonmetallic pipes or conduits may be used: A. Polyvinyl Chloride (PVC) Pipe — Nom 2 in. (51 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 2 in. (51 mm) diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) piping systems. 3. Fill, Void or Cavity Materials* -Sealant — Fill Material forced into annular space to fill space to max extent possible. Sealant shall be installed flush with top surface of floor or sole plate and bottom surface of ceiling or lower top plate. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant or FS-ONE MAX Intumescent Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. I I I �_E W3 Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. April 06, 2018 Page: 2 of 2 (�15 Classified by Underwriters Laboratories, Inc. to UL 1479 System No. F-C-2189 F Rating -1 Hr T Rating -1 Hr Floor -Ceiling Assembly — The fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The general construction details of the floor -ceiling assembly are summarized below: A. Flooring System — Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Rectangular cutout in flooring to accommodate the bathtub drain piping (Item 2) to be max 8 by 12 in. (203 by 305 mm). B. Wood Joists — Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Gypsum Board* — Nom 4 ft (122 cm) wide by 518 in. (16 mm) thick as specified in the individual Floor -Ceiling Design. Gypsum board secured to joists as specified in the individual Floor -Ceiling Design. Three pieces of gypsum board, each min 4 in. longer and wider than the cutout in the flooring, screw attached to bottom of flooring concentric with cutout. In addition, min 112 in. (13 mm) diam by 2 in. (51 mm) high wavy bead of FS-One Sealant to be applied to the top perimeter of each piece of gypsum board prior to its installation. Diam of opening hole -sawed through both layers of the gypsum board patch to be 112 in. (13 mm) larger than outside diam of bathtub drain piping (Item 2). M 00 N U Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. Hilti Firesto Systems January 15, 2015 p Y ms Page: 1 of 2 24 System No. F-C-2189 Drain Piping — Nom 2 in. (51 mm) diam (or smaller) Schedule 40 cellular or solid core PVC or ABS pipe and drain fittings cemented together and provided with PVC or ABS bathtub waste/overflow fitting. Firestop System — The firestop system shall consist of the following: A. Fill, Void or Cavity Material* — Wrap Strip — Nom 3/16 in. (5 mm) thick by 1 in. (25 mm) wide intumescent wrap strip. One wrap strip is continuously wrapped around the outer circumference of the drain pipe within joist cavity and held in place with pieces of tape. Wrap strip slid into annular space of cut-out in gypsum board such that the bottom surface of the wrap strip is flush with the bottom surface of the gypsum board. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP648-E W25/1" Wrap Strip Al. Fill, Void or Cavity Material* — Wrap Strip — (As an alternate to the wrap strip in Item 3A on nom 1-1/2" and 2" (38 and 51 mm) diam pipes only) - Nom 3/16 in. (5 mm) thick by 1-1/2 or 2 in. (38 or 51 mm) wide intumescent wrap strip. One layer of intumescent wrap strip is tightly wrapped around the pipe with ends butted and held in place with integrated tape. Wrap strip slid into annular space of cut-out in gypsum board such that the bottom surface of the wrap strip is flush with the bottom surface of the gypsum board. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP648-S-1.5" US, CP648-S-2" US B. Fill, Void or Cavity Material* — Caulk — Min 1/2 in. (13 mm) diam bead of Sealant to be applied around the perimeter of the gypsum board at its interface with the wood floor. Additional 1/2 in. (13 mm) diam bead to be applied to the bottom of the wrap strip at its interface with the drain pipe. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant or FS-ONE MAX Intumescent Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), I I I �_E ;a Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. January 15, 2015 M 00 N U 2of2 25 (`15 s Classified by Underwriters Laboratories, Inc. to UL 1479 System No. F-C-2205 F Rating -1 Hr T Rating -1 Hr O O -- — — — — OI IO O� �O A L--------I A 0 0 0 SECTION A -A 1. Floor -- Ceiling Assembly -- The 1 hr fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The general construction features of the floor -ceiling assembly are summarized below: A. Flooring System -- Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Rectangular cutout in flooring to accommodate the bathtub drain piping (Item 2) to be max 8 in. by 12 in. Cutout to be patched on underside of subfloor using one layer of min 3/4 in. thick plywood or min 5/8 in. thick gypsum board (Item 1 C) sized to lap min 2 in. beyond each edge of rectangular cutout. Patch split into two pieces at opening and hole -sawed for bathtub drain piping. Diam of opening hole sawed through patch to accommodate drain piping (Item 2) to be 1/2 in. larger than outside diam of drain piping and positioned such that the drain piping is centered in opening. Two pieces positioned around drain piping, with cut edges tightly butted, and screw -attached to underside of subfloor with 1-1/4 in. long steel screws spaced max 6 in. OC. B. Wood Joists* -- Nom 10 in. deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Gypsum Board* -- Nom 5/8 in. thick, 4 ft wide as specified in the individual Floor -Ceiling Design. Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. April 25, 2005 0 N N U e: 1 of 2 26 (�15s Classified by Underwriters Laboratories, Inc. to UL 1479 System No. F-C-2205 F Rating -1 Hr T Rating -1 Hr 2. Drain Piping -- Nom 1-1/2 in. (or smaller) diam Schedule 40 acrylonitrile butadiene styrene (ABS) or polyvinyl chloride (PVC) pipe and drain fittings cemented together and provided with ABS or PVC bathtub waste/overflow fittings. Annular space shall be 1/4 in. 3. Fill Void or Cavity Materials* -- Wrap Strip -- Nom 3/16 in. thick by 1 in. wide intumescent wrap strip. One layer of wrap strip wrapped around drain piping with ends butted and held in place with tape. Wrap strip installed within annulus flush with bottom surface of plywood or gypsum board patch. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- 648-E W25/1" Wrap Strip A. Fill, Void or Cavity Material* -- Wrap Strip -- (As an alternate to the wrap strip in Item 3 on nom 1-1/2" diam pipes only) - Nom 3/16 in. thick by 1-1/2 in. wide intumescent wrap strip One layer of intumescent wrap strip is tightly wrapped around the pipe with ends butted and held in place with integrated tape. Wrap strip slid into annular space of cut-out in gypsum board such that the bottom surface of the wrap strip is flush with the bottom surface of the gypsum board. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- CP648-S-1.5" US *Bearing the UL Classification Mark I I 1 13 Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. April 25, 2005 0 N N U e: 2 of 2 27 (�15 Classified by Underwriters Laboratories, Inc. to UL 1479 A System No. F-C-2230 F Rating -1 Hr T Rating -114 Hr SECTION A -A Floor -Ceiling Assembly —The 1 hr fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The general construction features of the floor -ceiling assembly are summarized below: A. Flooring System — Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Max diam of opening shall be 1-518 in. (41 mm). B. Wood Joists* — Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Gypsum Board* — Nom 518 in. (16 mm) thick, 4 ft (122 cm) wide as specified in the individual Floor -Ceiling Design. I I I ML-0 ;3 Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. January 21, 2015 0 M N N U Page: 1 of 2 28 System No. F-C-2230 Through Penetrants — One non-metallic tube to be installed concentrically within the firestop system. Annular space between tube and periphery of opening shall be 1/4 in. (6 mm). Tube to be rigidly supported on both sides of floor -ceiling assembly. The following types and sizes of non-meyallic tubes or pipes may be used: Crosslinked Polyethylene (PEX) Tubing — Nom 1 in. (25 mm) diam (or smaller) SDR9 PEX tubing for use in closed (process or supply) or vented (drain, waste or vent) piping systems. Fill, Void or Cavity Materials* - Wrap Strip — Nom 3/16 in. (5 mm) thick by 1 in. (25 mm) wide intumescentwrap strip. One layer of wrap strip tightly wrapped around tube and held in place with tape. Wrap strip centered in annular space extending from both sides of gypsum board. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP648-E W25/1" Wrap Strip Fill, Void or Cavity Materials* - Sealant — Min 3/4 in. (19 mm) depth of fill material applied within the annulus, flush with the top surface of floor. A 1/4 in. (6 mm) diam bead of fill material shall also be applied at the wrap strip/gypsum board interface. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — Sealant - FS-ONE Sealant or FS-ONE-MAX Intumescent Sealant Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), I I I �_n ;a Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. January 21, 2015 0 M N N U Page: 2 of 2 29 (�15 Classified by Underwriters Laboratories, Inc. to UL 1479 System No. F-C-2231 F Rating -1 Hr T Rating -1 Hr F10-A 3B o O X. O O 3A 2 L-0--A SECTION A -A Floor -Ceiling Assembly — The 1 hr fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The general construction features of the floor -ceiling assembly are summarized below: A. Flooring System — Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Max diam of opening shall be 2-518 in. (67 mm). B. Wood Joists* — Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Gypsum Board* — Nom 518 in. (16 mm) thick, 4 ft (122 cm) wide as specified in the individual Floor -Ceiling Design. I I 1 ;3 Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. January 15, 2015 Page: 1 of 2 30 System No. F-C-2231 Through Penetrants — One nonmetallic pipe to be installed concentrically or eccentrically within the firestop system. Annular space between pipe and edge of opening to be min 0 in. (point contact) and max 1/4 in. (6 mm). Pipe to be rigidly supported on both sides of floor -ceiling assembly. The following types and sizes of nonmetallic pipes or conduits may be used: A. Polyvinyl Chloride (PVC) Pipe — Nom 2 in. (51 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Acrylonitrile Butadiene Styrene (ABS) Pipe — Nom 2 in. (51 mm) diam (or smaller) Schedule 40 solid or cellular core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. C. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 2 in. (51 mm) diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) piping systems. Firestop System — The firestop system shall consist of the following: A. Fill, Void or Cavity Material* - Wrap Strip — Nom 3/16 in. (5 mm) thick by 1-3/4 in. (44 mm) wide intumescent wrap strip. One layer of wrap strip tightly wrapped around the pipe and held in place with tape. Wrap strip butted tightly against surface of ceiling. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP648-E-W45/1-3/4" Firestop Wrap Strip B. Steel Collar — Collar fabricated from coils of precut min 0.017 in. thick (No. 28 MSG) galv steel available from the sealant manufacturer. Collar shall be nom 1-3/4 in. (44 mm) deep with 1 in. (25 mm) wide by 2 in. (51 mm) long anchors tabs on 2 in. (51 mm) centers for securement to floor/ceiling assembly. The opposite side incorporates retainer tabs, 1/2 in. (13 mm) wide by 3/16 in. (4.8 mm) long, prebent toward the pipe surface. Collar shall be tightly wrapped over the wrap strip, overlapping min. 1 in. (25 mm) at seam. A nom 1/2 in. (13 mm) wide stainless steel hose clamp shall be secured to the collar at its mid -height. Every other anchor tab of collar secured to gypsum ceiling with 1/4 in. (6 mm) diam by 1-1/2 in. (38 mm) long steel toggle bolts in conjunction with 1/4 in. by 3/4 in. (6 mm by 19 mm) diameter steel washers. C. Fill, Void or Cavity Materials* -Sealant — Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with the bottom surface of the gypsum board. Min 3/4 in. (19 mm) thickness of fill material applied within the annulus, flush with the top surface of the floor. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant, FS-ONE MAX Intumescent Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. I I I �_n ;a Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. January 15, 2015 M N N U Page: 2 of 2 31 (�15 s Classified by Underwriters Laboratories, Inc. to UL 1479 System No. F-C-2232 F Rating —1 Hr T Rating — 3/4 and 1 Hr (See Item 3) SECTION A -A N M N N U Floor -Ceiling Assembly — The 1 hr fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The general construction features of the floor -ceiling assembly are summarized below: A. Flooring System — Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Max diam of opening shall be 5 in. (127 mm). B. Wood Joists* — Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Gypsum Board* — Nom 5/8 in. (16 mm) thick, 4 ft (122 cm) wide as specified in the individual Floor -Ceiling Design. Max diam of opening shall be 5 in. (127 mm). Through Penetrants — One nonmetallic pipe or conduit to be installed concentrically or eccentrically within the firestop system. Annular space between pipe or conduit and edge of opening to be min 0 in. (point contact) and max 1/2 in. (13 mm). Pipe or conduit to be rigidly supported on both sides of floor -ceiling assembly. The following types and sizes of nonmetallic pipes or conduits may be used: A. Polyvinyl Chloride (PVC) Pipe — Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 4 in. (102 mm) diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) piping systems. C. Acrylonitrile Butadiene Styrene (ABS) Pipe — Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid or cellular core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. Hilti Firesto Systems January 15, 2015 p Y ms Page: 1 of 2 32 System No. F-C-2232 Nonmetallic Pipe Coupling — (Optional) Nom 4 in. (102 mm) diam (or smaller) Schedule 40 PVC, Schedule 40 ABS or SDR13.5 CPVC coupling corresponding to pipe type installed such that the top of the coupling is flush with the bottom surface of the ceiling and extending downward. Firestop System — The firestop system shall consist of the following: A. Fill, Void or Cavity Material* - Wrap Strip — Nom 3/16 in. (5 mm) thick by 1-3/4 in. (44 mm) wide intumescent wrap strip. Layers of wrap strip continuously wrapped around the pipe and held in place with tape. Wrap strip butted tightly against surface of ceiling. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP648-E W45/1-3/4" Wrap Strip Nom Diam of Pipe, in. (mm) Number of Wrap Strips Min/Max Annular Space, in. (mm) T-Rating - Hr. 2 (51) 1 0-1/4 (0-6) 1 3 (76) 2 0-1/2 (0-13) 3/4 4 (102) 2 0-1/2 (0-13) 3/4 B. Steel Collar — Collar fabricated from coils of precut min 0.017 in. (0.43 mm) thick (No. 28 MSG) galv steel available from the sealant manufacturer. Collar shall be nom 1-3/4 in. (44 mm) deep with 1 in. (25 mm) wide by 2 in. (51 mm) long anchors tabs on 2 in. (51 mm) centers for securement to floor/ceiling assembly. The opposite side incorporates retainer tabs, 1/2 in. (13 mm) wide by 3/16 in. (5 mm) long, prebent toward the pipe surface. Collar shall be tightly wrapped over the wrap strip, overlapping min. 1 in at seam. A nom 1/2 in. (13 mm) wide stainless steel hose clamp shall be secured to the collar at its mid -height. Every other anchor tab of collar secured to gypsum ceiling with 1/4 in. (6 mm) diam by 1-1/2 in. (38 mm) long steel toggle bolts in conjunction with 1/4 in. by 3/4 in. (6 by 19 mm) diameter steel washers. C. Fill, Void or Cavity Materials* -Sealant — Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with the bottom surface of the gypsum board ceiling. Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with the top surface of the floor. When ABS pipe is installed at point contact, a min 1/2 in. (13 mm) diam bead of fill material shall be applied at the pipe/floor interface on top surface of floor. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant or FS-ONE MAX SEALANT 4A. Firestop System — (Optional, Not shown) As an option to Item 4, the firestop system shall consist of the following: A. Firestop Device* — Galy steel collar lined with an intumescent material sized to fit the specific diam of pipe shall be installed in accordance with the accompanying installation instructions. Collar to be installed and latched around the pipe and secured to the gypsum board ceiling with 1/4 in. diam by 1-1/2 in. (38 mm) long steel toggle bolts with 3/4 in. (19 mm) diam steel washers through hanger tabs provided. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 643 50/1.5"N, CP 643 63/2"N, CP 643 90/3"N or CP 643 110/4"N Firestop Collar. B. Fill, Void or Cavity Materials* -Sealant — Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with the bottom surface of the gypsum board ceiling. Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with the top surface of the floor. When ABS pipe is installed at point contact, a min 1/2 in. (13 mm) diam bead of fill material shall be applied at the pipe/floor interface, flush with top surface of floor. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant or FS-ONE-MAX Intumescent Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. January 15, 2015 N M N N U Page: 2 of 2 33 (�15 Classified by Underwriters Laboratories, Inc. to UL 1479 L System No. F-C-2401 F Rating -1 Hr T Rating -1 Hr SECTION A -A Floor -Ceiling Assembly — The 1 hr fire rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The general construction details of the floor -ceiling assembly are summarized below: A. Flooring System — Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Diam of floor opening shall be 118 in. (3.2 mm) larger than the outside diam of the through -penetrant (Item 3). B. Wood Joists — Nom 2 by 10 in. (51 by 254 mm) lumber joists spaced 16 in. (406 mm) OC with nom 1 by 3 in. (25 by 76 mm) lumber bridging and with ends firestopped. As an alternate to lumber joists, nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required with ends firestopped. C. Furring Channels — (Not shown) — Resilient galv steel furring installed perpendicular to wood joists (Item 1 B) between wallboard (Item 1 D) and wood joists as required in the individual Floor -Ceiling Design. D. Gypsum Board* — Nom 4 ft (1.2 m) wide by 518 in. (16 mm) thick as specified in the individual Floor -Ceiling Design. Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. January 20, 2015 0 N U U_ Page: 1 of 2 34 System No. F-C-2401 Chase Wall — The through penetrant (Item No. 3) shall be routed through a wood stud/gypsum board chase wall and shall include the following construction features: A. Studs — Nom 2 by 6 in. (51 by 152 mm) lumber studs. B. Sole Plate — Nom 2 by 6 in. (51 by 152 mm) lumber plates. Diam of opening shall be 1/8 in. (3.2 mm) larger than the outside diam of the through -penetrant. C. Top Plate — The double top plate shall consist of two nom 2 by 6 in. (51 by 152 mm) lumber plates. Diam of opening shall be 1/8 in. (3.2 mm) larger than the outside diam of the through -penetrant. D. Gypsum Board — Min 5/8 in. (16 mm) thick rated or nonrated gypsum board. Through Penetrant — One nonmetallic pipe to be centered within the opening. The annular space between the through penetrant and the periphery of the opening shall be 1/16 in. (1.6 mm). Pipe to be min 1/16 in. (1.6 mm) from chase wall stud. Pipe to be rigidly supported on both sides of the floor -ceiling assembly. The following types and sizes of nonmetallic pipes may be used. A. Polyvinyl Chloride (PVC) Pipe — Nom 4 in. (102 mm) diam (or smaller) Schedule 40 cellular core PVC for use in closed (process or supply) or vented (drain, waste or vent) piping systems. Firestop System — The firestop system shall consist of the following: A. Fill, Void or Cavity Material* - Sealant — Min 1/2 in. (13 mm) crown of fill material applied over the annulus, flush with top surface of floor or sole plate. Min 1/2 in. (13 mm) thickness of fill material applied within the annulus, flush with bottom surface of lower top plate. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant or FS-ONE MAX Intumescent Sealant B. Fill, Void or Cavity Material* - Wrap Strip — Nom 3/16 in. (4.8 mm) thick by 1-3/4 in. (44 mm) wide intumescent wrap strip. Min two layers of wrap strip wrapped around pipe in a U-Shaped manner with the ends tightly butted against the chase wall stud. Wrap strip butted tightly against lower surface of top plates. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP648-E W45/1-3/4" Wrap Strip C. Steel Collar — Collar fabricated from coils of precut min 0.017 in. (0.43 mm) thick (No. 28 MSG) galv steel available from the sealant manufacturer. Collar shall be nom 1-3/4 in. (44 mm) deep with 1 in. (25 mm) wide by 2 in. (51 mm) long anchors tabs on 2 in. (51 mm) centers for securement to floor/ceiling assembly. The opposite side incorporates retainer tabs, 1/2 in. (13 mm) wide by 3/16 in. (4.8 mm) long, pre -bent toward the pipe surface. Collar shall be tightly wrapped over the wrap strip, overlapping min. 1 in. (25 mm) onto chase wall stud at both ends. A min two anchor tabs of collar to be secured to top plate opposite the stud with min 1/4 in. (6 mm) diam by 1-1/2 in. (38 mm) long steel wood screws in conjunction with min 3/4 in. (19 mm) diam steel washers. Both ends of collar to be secured to the stud with min 1/4 in. (6 mm) diam by 1-1/2 in. (38 mm) long steel wood screws in conjunction with min 3/4 in. (19 mm) diam steel washers. * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. I I I �_n ;a Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. January 20, 2015 0 N U Page: 2 of 2 35 C US Classified by Underwriters Laboratories, Inc. to UL 1479 and CAN/ULC-S115 System No. F-C-2516 ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Rating —1 Hr F Rating —1 Hr T Ratings —1/2 and 1 Hr (See Items 3A and 3A1) FT Ratings —1/2 and 1 Hr (See Items 3A and 3A1) FH Rating —1 Hr FTH Ratings —1/2 and 1 Hr (See Items 3A and 3A1) I I I Md3 Hilti Firestop Systems SECTION A -A Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. October 31, 2019 LO N U ILL Page: 1 of 3 System No. F-C-2516 co LO N U System tested with a pressure differential of 2.5 Pa between the exposed and the unexposed surfaces with the higher pressure on the exposed side. 1. Floor -Ceiling Assembly — The 1 hr fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The general construction features of the floor -ceiling assembly are summarized below: A. Flooring System — Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Max diam of opening shall be 5-1/2 in. (140 mm). B. Wood Joists* — Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Gypsum Board* — Min 1/2 in. (13 mm) thick as specified in the individual Floor -Ceiling Design. Gypsum board secured to wood joists or furring channels as specified in the individual Floor -Ceiling Design. Max diam of opening shall be 5-1/2 in. (140 mm). 1.1. Chase Wall — (Optional, not shown) The through penetrant may be routed (Item 2) through a fire rated or non -rated single, double or staggered wood stud/gypsum wallboard chase wall constructed to include the following construction details: A. Studs — Nom 2 by 6 in. (51 by 152 mm) or double nom 2 by 4 in. (51 by 102 mm) lumber studs. B. Sole Plate — Nom 2 by 6 in. (51 by 152 mm) or parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Max diam of opening is 5-1/2 in. (140 mm). C. Top Plate — The double top plate shall consist of two nom 2 by 6 in. (51 by 152 mm) or two sets of parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Max diam of opening is 5-1/2 in. (140 mm). D. Gypsum Board* — One layer of min 1/2 in. (13 mm) gypsum board. 2. Through Penetrants — One non-metallic pipe or conduit to be installed concentrically or eccentrically within the opening. Annular space within the firestop system is dependent upon the max diam of penetrant and type of firestop wrap strip used as tabulated in Item 3A. Pipe or conduit to be rigidly supported on both sides of floor -ceiling assembly. The following types and sizes of non-metallic pipes or conduit may be used: A. Polyvinyl Chloride (PVC) Pipe — Nom 4 in. (102 mm) diam (or smaller) Schedule 40 cellular core or solid core PVC pipe for use in vented (drain, waste or vent) or closed (process or supply) piping systems. B. Chlorinated Polyvinyl (CPVC) Pipe — Nom 4 in. (102 mm) diam (or smaller) SDR13.5 CPVC pipe for use in vented (drain, waste or vent) or closed (process or supply) piping systems. C. Rigid Nonmetallic Conduit+ — Nom 4 in. (102 mm) diam (or smaller) PVC conduit installed in accordance with the National Electrical Code (NFPA 70). 3. Firestop System — The firestop system shall consist of the following: A. Fill, Void or Cavity Material* - Wrap Strip — One layer of wrap wrapped around pipe with ends tightly butted and held in place with supplied tape. Wrap strip slid into the annular space such that the wrap strip is centered in the gypsum board ceiling, or extending below lower top plate for half of the wrap strip height. The size of wrap strip for a given size penetrant are shown in table below: HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 648S-1.5"(38 mm) US, CP 648S - 2"(51 mm) US, CP 648S - 3"(76 mm), CP 648S - 4"(102 mm). Product Nom Pipe Max Annular Annular Nom Wrap Strip Nom Wrap Nom Wrap Designation Size, in. (mm) Opening Diam, Space Min, Space Length, in. Strip Strip in. (mm) in. (mm) Max, in. (mm) Thick, in. (mm) Width, in. (mm) CP648-S-1.5" 1-1/2 (38) 3 (76) 3/16 (4.8) 5/16 (8) 6.5(165) 0.18 (4.6) 1 (25) US CP648-S-2" 2 (51) 3-1/2 (89) 3/16 (4.8) 5/16 (8) 8 (203) 0.18 (4.6) 1 (25) US CP648-S-3" 3 (76) 4 (102) 3/16 (4.8) 5/16 (8) 11.5 (292) 0.18 (4.6) 1-3/4 (45) US CP648-S-4" 4 (102) 5-1/2(140) 3/8 (10) 3/4 (19) 15.1 (384) 0.36(9) 1-3/4 (45) US I I I �_E W3 Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. October 31, 2019 Page: 2 of 3 System No. F-C-2516 The T Rating is 1/2 Hr for penetrants with a nom diam of 2 in (51 mm) or smaller. The T Rating is 0 Hr for nom 3 in. (76 mm) penetrants. The T Rating is 1 Hr for nom 4 in. (102 mm) penetrants. Al. Fill, Void or Cavity Material* - Wrap Strip — (As an alternate to the wrap strip in Item 3A) — Layers of intumescent wrap strip are continuously wrapped around the pipe with ends held in place with tape. Wrap strip slid into the annular space such that the wrap strip is centered in the gypsum board ceiling, or extending below lower top plate for half of the wrap strip height. The number of layers of wrap strip for a given size penetrant are shown in table below: HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP648-E W45/1-3/4" Firestop Wrap Strip Product Nom Pipe Max Opening Annular Space Annular Space Number of Nom Wrap Strip Designation Size, in. (mm) Diam, in. (mm) Min, in. (mm) Max, in. (mm) Layers Width, in. (mm) CP648-E 1-1/2 (38) 3 (76) 3/16 (4.8) 5/16 (8) 1 1-3/4 (45) W45/1-3/4" CP648-E 2 (51) 3-1/2 (89) 3/16 (4.8) 5/16 (8) 1 1-3/4 (45) W45/1-3/4" CP648-E 3 (76) 4 (102) 3/16 (4.8) 5/16 (8) 1 1-3/4 (45) W45/1-3/4" CP648-E 3 (76) 5 (127) 3/8 (10) 5/8 (16) 2 1-3/4 (45) W45/1-3/4" CP 4 (102) 6 (152) 3/8 (10) 5/8 (16) 2 1-3/4 (45) W4511-3/4-314" The T Rating is 1/2 Hr when CP648-E is used. B. Fill, Void or Cavity Material* - Sealant— Min 1/2 in. (13 mm) thickness applied within the anulus, flush with the bottom surface of the ceiling or lower top plate. An additional min 1/2 in. (13 mm) bead applied around periphery of wrap strip, at the wrap strip gypsum board interface or at the underside of the top plate. Min 3/4 in (19 mm) depth applied within the annulus, flush with the top surface of the floor or the top surface of the sole plate. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE-MAX Intumescent Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. I I I �—E Ed3 Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. October 31, 2019 Page: 3 of 3 C S Classified by Underwriters Laboratories, Inc. to UL 1479 and CAN/ULC-S115 System No. F-C-3012 ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings —1 and 2 Hr (See Item 1) F Ratings —1 and 2 Hr (See Item 1) T Ratings — 0, 1 and 1-3/4 Hr (See Item 3) FT Ratings — 0, 1 and 1-3/4 Hr (See Item 3) FH Ratings —1 and 2 Hr (See Item 1) FTH Ratings — 0, 1 and 1-3/4 Hr (See Item 3) JCV I IUIV H-A 1. Floor -Ceiling Assembly — The 1 or 2 hr fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The general construction features of the floor -ceiling assembly are summarized below: A. Flooring System — Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Max diam of opening for 1 or 2 hr assembly is 2-1/2 in. (64 mm) or 2 in. (51 mm), respectively. B. Wood Joists* — Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Furring Channels — (Not Shown) — (As required) - Resilient galvanized steel furring installed in accordance with the manner specified in the individual L500 Series Designs in the Fire Resistance Directory. D. Gypsum Board* — Thickness, type, number of layers and fasteners shall be as specified in the individual Floor -Ceiling Design. Max diam of opening for 1 or 2 hr assembly is 2-1/2 in. (64 mm) or 2 in. (51 mm), respectively. The F Rating of the firestop system is equal to the rating of the floor -ceiling assembly. Reproduced by HILTI, Inc. Courtesy of I Ed3 Underwriters Laboratories, Inc. Hilti Firesto April 06, 2018 p Systems Page: 1 of 2 System No. F-C-3012 2. Chase Wall — (Optional) - The through penetrant (Item 3) may be routed through a fire -rated or non -rated single, double or staggered wood stud/gypsum wallboard chase wall. The chase wall shall be constructed to include the following construction features: A. Studs — Nom 2 by 6 in. (51 by 152 mm) or double nom 2 by 4 in. (51 by 102 mm) lumber studs. B. Sole Plate — Nom 2 by 6 in. (51 by 152 mm) or parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Max diam of opening for 1 or 2 hr rated assembly is 2-1/2 in. (64 mm) or 2 in. (51 mm), respectively. C. Top Plate — The double top plate shall consist of two nom 2 by 6 in. (51 by 152 mm) or two sets of parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Max diam of opening for 1 or 2 hr rated assembly is 2-1/2 in. (64 mm) or 2 in. (51 mm), respectively. D. Gypsum Board* — One or two layers of min 1/2 in. (13 mm) gypsum board. 3. Cables — In 1 hr fire -rated assemblies, aggregate cross -sectional area of cables in opening to be max 45 percent of the cross -sectional area of the opening (max 2 in. (51 mm) diam bundle). Cables to be rigidly supported on both sides of floor assembly. Any combination of the following types and sizes of copper conductors may be used: A. RG 59 coaxial cable with single copper conductor, cellular polyethylene cellular foam insulation and polyvinyl chloride (PVC) jacket. B. Max 8/C No. 22 AWG telephone cable with polyvinyl chloride (PVC) jacketing. C. Max 2/C No. 12 AWG cable with polyvinyl chloride (PVC) insulation and jacketing. D. Max 3/C with ground No. 2/0 AWG aluminum or copper Type SER cable with polyvinyl chloride (PVC) insulation. E. Max 3/C with ground No. 2/0 AWG Type NM cable with polyvinyl chloride (PVC) insulation. F. Max 3/C No. 12 AWG MC (BX) cable with polyvinyl chloride (PVC) insulation. G. Max 1 in. diam metal clad TEK cable with PVC jacket. H. Max 4/C with ground No. 300 kcmil (or smaller) aluminum SER cable with PVC insulation and jacket. I. Through Penetrating Product* - Any cables, Metal -Clad Cable+ or Armored Cable+ currently Classified under the Through Penetrating Products category. See Through Penetrating Product (XHLY) category in the Fire Resistance Directory for names of manufacturers. The T Rating is 1 and 1-3/4 hr for 1 and 2 hr rated assemblies, respectively, for cables 3A through 3G. The T Rating is 0 hr for cables 3H and 31. 4. Fill, Void or Cavity Material* — Sealant — Min 3/4 in. (19 mm) thickness of fill material applied within the annulus, flush with top surface of floor or sole plate. Min 5/8 in. (16 mm) thickness of fill material also applied within the annulus, flush with bottom surface of ceiling or lower top plate. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS611A Sealant or FS-One Sealant or FS-ONE MAX Intumescent Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. I I I �_E W3 Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. April 06, 2018 Page: 2 of 2 (�15 S I F/moo C uS Classified by Underwriters Laboratories, Inc. to UL 1479 and CANIULC-S115 System No. F-C-5004 ANSI/UL1479 (ASTM E814) F Rating —1 and 2 Hr (See Item 1) T Rating —1 and 1-3/4 Hr (See Item 1) L Rating At Ambient — 4 CFM/Sq Ft (See Item 4) L Rating At 400 F — Less Than 1 CFM/Sq Ft (See Item 4) �A 3 5 4 CAN/ULC S115 F Rating —1 and 2 Hr (See Item 1) FT Rating —1 and 1-3/4 Hr (See Item 1) FH Rating —1 and 2 Hr (See Item 1) FTH Rating —1 and 1-3/4 Hr (See Item 1) L Rating At Ambient — 4 CFM/Sq Ft (See Item 4) L Rating At 400 F — Less Than 1 CFM/Sq Ft (See Item 4) 0 0 U Floor -Ceiling Assembly — The 1 or 2 hr fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The F Rating of the firestop system is equal to the rating of the floor -ceiling assembly. The T Rating is 1 and 1-3/4 hr for 1 and 2 hr rated assemblies, respectively. The general construction features of the floor -ceiling assembly are summarized below: A. Flooring System — Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Max diam of floor opening is 3-1/2 in. (89 mm). B. Wood Joists* — Nom 10 in (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Furring Channels — (Not Shown) — (As required) - Resilient galvanized steel furring installed in accordance with the manner specified in the individual L500 Series Designs in the Fire Resistance Directory. D. Gypsum Board* — Thickness, type, number of layers and fasteners shall be as specified in the individual Floor -Ceiling Design. Max diam of floor opening is 3-1/2 in. (89 mm). ;3 Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. H i Iti Firesto Systems January 20, 2015 p Y Page: 1 of 2 41 System No. F-C-5004 0 0 U 2. Chase Wall — (Optional) - The through penetrant (Item 3) may be routed through a fire -rated single, double or staggered wood stud/gypsum wallboard chase wall having a fire rating consistent with that of the floor -ceiling assembly. The chase wall shall be constructed of the materials and in the manner specified in the individual U300 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs — Nom 2 by 6 in. (51 by 152 mm) or double nom 2 by 4 in. (51 by 102 mm) lumber studs. B. Sole Plate — Nom 2 by 6 in. (51 by 152 mm) or parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Max diam of opening shall be 3-1/2 in. (89 mm). C. Top Plate — The double top plate shall consist of two nom 2 by 6 in. (51 by 152 mm) or two sets of parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Max diam of opening is 3-1/2 in. (89 mm). D. Gypsum Board* — Thickness, type, number of layers and fasteners shall be as specified in the individual Wall and Partition Design. 3. Through Penetrants — One metallic pipe or tubing to be installed within the firestop system. Pipe or tubing to be rigidly supported on both sides of floor assembly. The following types and sizes of metallic pipes or tubing may be used: A. Steel Pipe — Nom 2 in. (51 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Copper Tubing — Nom 2 in. (51 mm) diam (or smaller) Type L (or heavier) copper tubing. C. Copper Pipe — Nom 2 in. (51 mm) diam (or smaller) Regular (or heavier) copper pipe. 4. Pipe Covering* — Nom 1/2 in. (13 mm) thick hollow cylindrical heavy density (min 3.5 pcf (56 kg/m3)) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory -applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product. A nom annular space of 1/8 in. (3 mm) is required within the firestop system. See Pipe and Equipment Covering — Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. 4A. Tube Insulation — Plastics+ — Nom 3/4 in. (19 mm) thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. An annular space of min 1/8 in. (3 mm) to max 3/8 in. (10 mm) is required within the firestop system. See Plastics+ (QMFZ2) category in the Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation material meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may be used. (Note: L Ratings apply only when glass fiber insulation is used). 5. Fill, Void or Cavity Material* — Sealant — Min 3/4 in. (19 mm) thickness of fill material applied within the annulus, flush with top surface of floor or sole plate. Min 5/8 in. (16 mm) thickness of fill material also applied within the annulus, flush with bottom surface of ceiling or lower top plate. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant or FS-ONE MAX Intumescent Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. I I I �_Ewi Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. January 20, 2015 Page: 2 of 2 42 (�15 C US Classified by Underwriters Laboratories, Inc. to UL 1479 and CAN/ULC-S115 System No. F-C-5037 ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings —1 and 2 Hr (See Item 1) F Ratings —1 and 2 Hr (See Item 1) T Ratings-1/4 and 1-3/4 Hr (See Item 1) FT Ratings —1/4 and 1-3/4 Hr (See Item 1) FH Ratings —1 and 2 Hr (See Item 1) FTH Ratings-1/4 and 1-3/4 Hr (See Item 1) %7LV 1 IVIY /1-r% 1. Floor -Ceiling Assembly — The 1 and 2 hr fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The F and FH Rating are dependent on the hourly rating of the floor ceiling assembly. The T, FT and FTH Rating are 1/4 hr for 1 hr rated floor ceiling assemblies and 1-3/4 hr for 2 hr rated floor ceiling assemblies. The general construction features of the floor -ceiling assembly are summarized below: A. Flooring System — Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Diam of opening shall be 5-1/8 in. (130 mm). B. Wood Joists* — Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Furring Channels (Not Shown) — Resilient galv steel furring installed perpendicular to wood joists between first and second layers of wallboard (Item 1D). Furring channels spaced max 24 in. (610 mm). D. Gypsum Board* — Nom 4 ft (1.2 m) wide by 5/8 in. (16 mm) thick as specified in the individual Floor -Ceiling Design. First layer of wallboard nailed to wood joists. Second layer of wallboard screw -attached to furring channels. Max diam of ceiling opening is 5-1/8 in. (130 mm). 1.1 Chase Wall — (Not Shown, Optional) The through penetrants (Item 2) may be routed through fire -rated single, double or staggered wood stud/gypsum wallboard chase wall having a fire rating consistent with that of the floor -ceiling assembly. The chase wall shall be constructed of the materials and in the manner specified in the individual U300 Series Wall and Partition Designs in the UL Fire Resistance Drectory and shall include the following construction features: A. Studs — Nom 2 by 6 in. (51 by 152 mm) lumber or double nom 2 by 4 in. (51 by 102 mm) lumber studs. B. Sole Plate — Nom 2 by 6 in. (51 by 152 mm) lumber or parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Max diam of opening shall be 5-1/8 in. C. Top Plate — The double top plate shall consist of two nom 2 by 6 in. (51 by 152 mm) lumber plates or two sets of nom 2 by 4 in. (51 by 102 mm) lumber plates tightly butted. Max diam of opening is 5-1/8 in. (130 mm). D. Gypsum Board* — Thickness, type, number of layers and fasteners shall be as specified in individual Wall and Partition Design. Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. H i Iti F i resto Systems January 20, 2015 p Y ms Page: 1 of 2 43 System No. F-C-5037 Through Penetrants — One metallic tube or pipe to be installed within the firestop system. Tube or pipe to be rigidly supported on both sides of floor -ceiling assembly. The following types and sizes of metallic tubes or pipes may be used: A. Copper Tubing — Nom 2 in. (51 mm) diam (or smaller) Type L (or heavier) copper tubing. B. Copper Pipe — Nom 2 in. (51 mm) diam (or smaller) Regular (or heavier) copper pipe. C. Steel Pipe — Nom 2 in. (51 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. Tube Insulation -Plastics+ — Nom 314 in. (19 mm) thick acrylonitrile butadienelpolyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. The annular space shall be min 318 in. (10 mm) to max 1 in. (25 mm). See Plastics+ (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation material meeting the above specifications and having a UL94 Flammability Classification of 94-5VA may be used. Fill, Void or Cavity Materials* -Sealant — Fill material forced into annular space to fill space to max extent possible. Sealant shall be installed flush with top surface of floor or sole plate and bottom surface of ceiling or lower top plate. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant or FS-ONE MAX Intumescent Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. I I I �_Ewl Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. January 20, 2015 Page: 2 of 2 44 (�15 C us Classified by Underwriters Laboratories, Inc. to UL 1479 and CAN/ULC-S115 System No. F-C-5088 ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Rating —1 or 2 Hr (See Item 1) F Rating —1 or 2 Hr (See Item 1) T Rating —1 or 2 Hr (See Item 1) FT Rating —1 or 2 Hr (See Item 1) FH Rating —1 or 2 Hr (See Item 1) FTH Rating —1 or 2 Hr (See Item 1) �A �a SECTION A -A Floor -Ceiling Assembly — The 1 or 2 hr fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The Ratings of the firestop system are equal to the rating of the floor -ceiling and wall assemblies. The general construction features of the floor -ceiling assembly are summarized below: A. Flooring System — Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Max diam of opening shall be 7 in. (178 mm). B. Wood Joists* — Nom 10 in (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Gypsum Board* — Thickness, type, number of layers and fasteners shall be as specified in the individual Floor -Ceiling Design. Max diam of opening shall be 7 in. (178 mm). D. Furring Channels — (Not Shown) (As required) Resilient galvanized steel furring installed in accordance with the manner specified in the individual L500 Series Designs in the Fire Resistance Directory. co co 0 U U_ 13 Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. Hllti Firesto Systems February 23, 2015 p Y Page: 1 of 2 45 System No. F-C-5088 1.1. Chase Wall — (Not Shown, Optional) — The through penetrants (Item 2) may be routed through a 1 or 2 hr fire -rated single, double or staggered wood stud/gypsum wallboard chase wall having a fire rating consistent with that of the floor -ceiling assembly. The chase wall shall be constructed of the materials and in the manner specified in the individual U300 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs — Nom 2 by 8 in. (51 by 203 mm) lumber or double nom 2 by 6 in. (51 by 152 mm) lumber studs. B. Sole Plate — Nom 2 by 8 in. (51 by 203 mm) lumber or parallel 2 by 6 in. (51 by 152 mm) lumber plates, tightly butted. Max diam of opening shall be 7 in. (178 mm). C. Top Plate — The double top plate shall consist of two nom 2 by 8 in. (51 by 203 mm) lumber plates or two sets of nom 2 by 6 in. (51 by 152 mm) lumber plates tightly butted. Max diam of opening is 7 in. (178 mm). D. Gypsum Board* — Thickness, type, number or layers and fasteners shall be as specified in individual Wall and Partition Designs. 2. Through Penetrants — One metallic pipe or tubing to be installed concentrically or eccentrically within the firestop system. Pipe or tubing to be rigidly supported on both sides of floor -ceiling assembly. The following types and sizes of metallic pipes or tubing may be used: A. Steel Pipe — Nom 4 in. (102 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe — Nom 4 in. (102 mm) diam (or smaller) cast or ductile iron pipe. C. Copper Tubing — Nom 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tubing. D. Copper Pipe — Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe. 3. Pipe Covering — Nom 1 in. (25 mm) thick hollow cylindrical heavy density (min 3.5 pcf or 56 kg/m3) glass fiber units jacketed on the outside with an all -service jacket. Longitudinal joints sealed with metal fasteners or factory -applied, self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product. The annular space between the insulated pipe and the edge of the periphery of the opening shall be min of 0 in. (point contact) to a max of 1/2 in. (29 mm). 4. Fill, Void or Cavity Material* — Sealant — Min 3/4 in. (19 mm) thickness of fill material applied within annulus flush with top surface of floor or sole plate. Min 5/8 in. (16 mm) thickness of fill material applied within annulus flush with bottom surface of ceiling or bottom surface of lower top plate. A min 1/2 in. (13 mm) bead of fill material is applied to area of point contact on both sides of floor ceiling assembly. HILTI INC — FS-ONE MAX Intumescent Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. I I I �_E 13 Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. February 23, 2015 co co 0 U e: 2 of 2 46 Product information FIRESTOP BLOCK CFS-BL Product description Ready -to -use, intumescent flexible block designed to seal medium to large size openings Applications for use Temporary or permanent sealing of cables, cable trays and pipes in wall and floor openings Sealing single or multiple penetrations in small to large openings Temporary or permanent sealing of insulated and non -insulated metallic pipes and combustible pipe penetrations Advantages Integrated "Grid -Tech" increases Annular Space up to 12" with no wire mesh Suitable for re -penetration or new penetrations Economical to use with short installation times Easy installation — no special tools required Ideal for use in floors — no forming required One sided wall systems available Halogen, asbestos and solvent free Operational immediately after installation Smoke resistant Completely dust and fiber free for "clean room" installation Installation instructions See Hilti literature or third -party listings for complete application and installation details Technical Data Chemical basis Color Recommended application temperature Storage and transportation temperature range Temperature resistance range Density Mold and mildew performance Tested in accordance with Surface burning characteristics (ASTM E84) Intumescent activation LEED VOC Can be painted Acoustics performance Shelf life Expansion ratio Polyurethane Foam Red 40' F to 104° F (5° C to 40' C) 32' F to 140°F (0' C to 60' C) 5° F to 140°F (-15° C to 60° C) 0.27 g/cm3 Class 0 (ASTM G21-96) UL 1479, CAN/ULC-S115, ASTM E814 Flame Spread 10 Smoke Development 15 392° F (200° C) 5.4 g/L Yes 52 (relates to specific construction) ASTM E90 Unlimited 1:3 Order designation Sales pack quantity Item number CFS-BL Firestop Block 1 2030020 CFS-BL MC 20 3484119 CFS-BL Pallet 480 3541548 Dimensions Size (LxWxH) CFS-BL Firestop Block 8" x 5" x 2" (20xl3x5cm) ``psSlf!, FM C �L US APPROVED r Hilti Firestop Saving lives through innovation 1 and education f WI C ® in 47 Certificate Number 20111214-R13240 Page 1 of 1 Report Reference File R13240 Issue Date 2011 December 14 OUnderwriters Laboratories Issued to: Hilti Construction Chemicals, Div of Hilti Inc. 5400 S 122nd East Ave Tulsa, OK 74146 This is to certify that Fill, Void or Cavity Materials representative samples of CFS-BL Firestop Block Have been investigated by Underwriters Laboratories in accordance with the Standards) indicated on this Certificate. Standard(s) for Safety: ANSUUL 1479, "Fire Tests of Through -Penetration Firestops," CAN/ULC-S 115, "Standard Method of Fire Tests of Firestop Systems." Third Edition revised March 1, 2010 Additional Information: See UL On-line Certification Directory at WWW.UL.COM for additional information. CFS-BL Firestop Block for use in Through -Penetration Firestop Systems as currently described in the UL Fire Resistance Directory. Only those products bearing the UL Classification Mark should be considered as being covered by UL's Classification and Follow -Up Service. The UL Classification Mark includes: UL in a circle symbol: uL with the word "CLASSIFIED" (as shown); a control number (may be alphanumeric) assigned by UL; a statement to indicate the extent of UL's evaluation of the product; and, the product category name (product identity) as indicated in the appropriate UL Directory. Look for the UL Classification Mark on the product William R. Carney Director, North American Certification Programs Underwriters Laboratories Inc. Any information and documentation involving UL Mark services are provided on behalf of Underwriters Laboratories Inc. (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at http://Www.ul.com/global/eng/Wages/corporate/contactus 48 Material Information Statement Articles According to Regulation (EC) 1907/2006, Article 32 Revision: 11.08.2021 Version: 20 1.1 Product identifier Trade name: • Firestop Bandage CFS-B / CP 646 • Firestop Plug CFS-PL / CP 658 • Firestop Back Pan Strip CFS-BPS . Firestop Plug Seal CFS-T RR / CFS-T RRS • Firestop Block CFS-BL / CFS-BL P Firestop Retrofit Sleeve CFS-SL RK • Firestop Board CP 675 Firestop Sleeve CP 645 • Firestop Boot CFS-BO Firestop Sleeve Kit CFS-SL SK • Firestop Box Insert • Firestop Speed Sleeve CFS-SL / CFS-SL GA / CP 653 • Firestop Cable Collar CFS-CC / CFS-RCC / CFS-RCC EXT • Firestop Top Track Seal CFS-TTS • Firestop Cable Module CFS-T Firestop Top Track Seal CFS-TTS MD • Firestop Cast -in device and accessories CP 680 / CP 681 / Firestop Top Track Cover CFS-TTS MD C CFS-CID / CFS-CID MD P/M/ CFS-CID MD HS GUI / CFS- Firestop Top Track Plug CFS-TTS MD P CID MD PLT W2/W3 / CFS-CID MD HS / CFS-CID ARB TE- Firestop Top Track Seal CFS-TTS 212 Y / CFS-CID ARB TE-C . Firestop Top Track Seal CFS-TTS R • Firestop Coated Board CFS-CT B / CP670 / CP673 / CP676 . Firestop Wedge Seal CFS-T WD120 • Firestop Collar CFS-C / CFS-C P . Firestop Wrap Strip CFS-W EL / SG / P / CP 648 • Firestop Collar CP 643 / CP 644 Foil Tapes CS -FT • Firestop Composite Sheet CFS-COS Intumescent fagade cavity closer CP674 • Firestop Cord CFS-CO . Joint Sealing Tapes CS-JST • Firestop Cushion CP 651 N . Mineral Wool • Firestop Drop -In Device CFS-DID . Mineral Wool Boards • Firestop Edge of Slab QuickSeal CFS-EOS QS Multifunctional Tapes CS-MFT • Firestop Endless Collar CFS-C EL Pre -coated Mineral Wool Boards • Firestop Filler Module CFS-T FB Smoke & Acoustic Track Seal CS-TTS SA • Firestop Gangplate CFS-SL GP . Speed Plug CP 777 • Firestop Module Box CFS-MB / CP 657 • Speed Strip CP 767 1.2 he li Construction industry. Refer to Hilti product literature, technical data sheets, 3rd party published listings and national approvals for specific application information. For more details, please contact your local Hilti organization through http://www.hilti.group 1.3 Manufacturer / Supplier HIM AG Feldkircherstr. 100 FL-9494 Schaan Liechtenstein Customer Service Phone +423 (0)844 84 84 85 Fax +423 (0)844 84 84 86 A Safety Data Sheet is not required due to the classification of these products as "articles" according to Regulation (EC) No. 1907/2006 of 18 December 2006 (EU) / 29CFR 1910.1200 (U.S.A.). Consequently, these products are exempted from CLP / OSHA Labeling and SIDS requirements. These data are based on our present knowledge. However, they shall not constitute a guarantee for any specific product features and shall not establish a legally valid contractual relationship. Informing department: chemicals. hseO,)hilti.com 49 September 24, 2015 To Whom It May Concern: Re: Hilti CFS-BL, Firestop Block — LEED Info. Item Number: 2030020 The CFS-BL is manufactured in Kaufering, Germany There is no post -consumer or post-industrial content in CFS-BL and it cannot be recycled. The CFS-BL does not contain any Rapidly Renewable Materials. The VOC content for CFS-BL is 5.4 grams/liter. CFS-BL is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non -regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state regulatory agencies for direction on disposal. Please feel free to contact me at (918) 872-3704 if you have questions. Sincerely, )z2- 406;;;q7 Jerry Metcalf MPH, CHMM Sr. Mgr. Safety/Environmental Hilti Inc. 918 872 3704 a errv.metcalf(cOilti.com Rev. Date: 9/24/15 The manufacturing plant location on this certificate has been provided for LEEDS reporting purposes only. It should never be used for Country of Origin certification or a representation of compliance/non-compliance with Buy American or Buy America requirements, as those requirements differ. The manufacturing plant location(s) identified on the certificate represent standard Hilti catalog products only. "Specially" produced non -catalog Hilti products may have differing manufacturing plant locations. Contact your Hilti representative in cases of "specially" produced products for a custom LEEDS certificates Hilti, Inc. 5400 South 122nd East Avenue Tulsa, OK 74146 1-800-879-8000 www.hilti.com 50 F11` Firestop Gun Grade Silicone Sealant CFS-S SIL GG Product description ■ A silicone based firestop sealant that provides maximum movement in fire -rated joints, and seals through -penetration applications Product features ■ Halogen and solvent free ■ Asbestos free ■ Simple to use and apply ■ Good adhesion without use of a primer ■ Smoke, fume, water and UV resistant ■ Excellent movement capability, meets 500 cycle requirements (ASTM E 1966 and UL 2079) ■ Meets Class I W-rating requirements ■ Meets LEEDTM requirements for indoor environmental quality credit 4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paints and Coatings Areas of application ■ Sealing construction/expansion joints ■ Top -of -wall joints ■ Metal pipes ■ Cable bundles ■ HVAC penetrations For use with ■ Various base materials such as masonry, concrete, metal, etc. ■ Wall and floor assemblies rated up to 4 hours Examples ■ Where a gypsum wall assembly meets the underside of a metal or concrete deck ■ Sealing expansion joints to impede the passage of fire, smoke and toxic fumes ■ Sealing around penetrations through fire -rated assemblies Installation instructions ■ Refer to what is included in the package, the MSDS, and the applicable listing. Technical Data* CFS-S SIL GG Chemical basis Neutral elastic silicone Density Approx. 1.4 g/cm3 Color Available in red, white, and gray Application temperature 40OF to 1040F (5°C to 40°C) Skin -forming time Approx. 15 min. Curing time Approx. 2 mm / 3 days Volume shrinkage Approx. 0 - 5% Movement capability Approx. 33% (UL 2079) Temperature resistance -40OF to 300OF (-40°C to 149°C) Surface burning characteristics Flame spread: 0 (ASTM E84-12) Smoke development: 25 Sound transmission classification 59 (Relates to specific construction) (ASTM E 90-09) Tested in accordance with UL 2079 ASTM E 814 ASTM E 1966 ASTM C 920 UL 1479 ASTM E 84 ASTM G21 'At 73°F (23°C) and 50% relative humidity p551p� FILL, VOID OR CAVITY MATERIAL F 6a '' FOR USE IN THROUGH -PENETRATION FIRESTOP SYSTEMS AND F M (�' ®� OS JOINTSYSTEMS SEE UL FIRE RESISTANCE DIRECTORY APPROVED Uisiubcsystemcompatible.com. 5BP5 Fi is a trademark of the Lubrizol Corporation. } rated Hilti. Outperform. Outlast. Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com • www.us.hilti.com/firestop • en espanol 1-800-879-5000 51 CERTIFICATE OF COMPLIANCE Certificate Number Report Reference Issue Date 20131115-R13240 R13240 2013-November-15 Issued to: Hilti Construction Chemicals, Div of Hilti Inc. 5400 S 122"d East Ave Tulsa, OK 74146 This is to certify that Fill, Void or Cavity Materials representative samples of Fill, Void or Cavity Materials Certified for Canada CFS-S SIL GG and CFS-S SIL SL for use in Through - Penetration Firestop and Joint Systems in the UL Fire Resistance Directory and in the Products Certified for Canada Directory. Have been investigated by UL in accordance with the Standard(s) indicated on this Certificate. Standard(s) for Safety: ANSI/UL 1479, "Fire Tests of Through -Penetration Firestops," — Edition 3 — Revision Date 2012/10/19 ANSI/UL 2079, "Tests for Fire Resistance of Building Joint Systems," — Edition 4 — Revision Date 2012/12/12 CAN/ULC-S115, "Standard Method of Fire Tests of Firestop Systems." — Edition 4 — Issue Date 2011/06/01 Additional Information: See the UL Online Certifications Directory at www.ul.com/database for additional information Only those products bearing the UL Classification Mark should be considered as being covered by UL's Classification and Follow -Up Service. The UL Classification Mark includes: UL in a circle: with the word "CLASSIFIED" 0 (as shown); a control number (may be alphanumeric) assigned by UL; a statement to indicate the extent of UL's evaluation of the product; and the product category name (product identity) as indicated in the appropriate UL Directory. Look for the UL Classification Mark on the product. ,4 ,► If L"7 William R. Carney, Director, North American Certification Programs UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at www.ul.com/contactus Page 1 of 1 52 CFS-S SIL SL / CFS-S SIL GG Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations Issue date: 05/26/2020 Revision date: 05/26/2020 Supersedes: 12/21/2016 �Rificati Product form Mixture Product name CFS-S SIL SL / CFS-S SIL GG Product code BU Fire Protection Chemical structure Version: 3.2 1.2. Relevant identified uses of the substance or mixture and uses advised against Use of the substance/mixture Firestop silcone sealant 1.3. Details of the supplier of the safety data sheet Hilti, Inc. Legacy Tower, Suite 1000 7250 Dallas Parkway TX 75024 Plano - USA T +1 9724035800 1-800-879-8000 toll free - F +1 918 254 0522 Supplier Hilti, Inc. Legacy Tower, Suite 1000 7250 Dallas Parkway TX 75024 Plano - USA T +1 9724035800 1-800-879-8000 toll free - F +1 918 254 0522 1.4. Emergency telephone number Department issuing data specification sheet Hilti AG Feld ki rcherstra Re 100 9494 Schaan - Liechtenstein T +423 234 2111 ch em icals. hse(a) h i Iti. com Emergency number Chem-Trec Tel.: 1 800 424 9300 (USA, PR, Virgin Islands, Canada) Tel.: 703 527 3887 (Other countries) +1 918 8723000 1-800-879-8000 toll free 2.1. Classification of the substance or mixture GHS-US classification Skin Sens. 1 H317 - May cause an allergic skin reaction. Repr. 2 H361 - Suspected of damaging fertility or the unborn child. Full text of H statements : see section 16 2.2. Label elements GHS US labelling Hazard pictograms (GHS US) < 0 > GHS07 GHS08 26/05/2020 US -OSHA - en 1/9 53 CFS-S SIL SL / CFS-S SIL GG Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations Signal word (GHS US) Warning Hazard statements (GHS US) H317 - May cause an allergic skin reaction. H361 - Suspected of damaging fertility or the unborn child. Precautionary statements (GHS US) P202 - Do not handle until all safety precautions have been read and understood. P261 - Avoid breathing vapours. P280 - Wear protective gloves, protective clothing, eye protection. P302+P352 - If on skin: Wash with plenty of water. P308+P313 - If exposed or concerned: Get medical advice/attention. Other hazards not contributing to the In use the product releases 2-butanone oxime (methyl ethyl ketoxime; MEKO) (0-24h: <0.2%/h classification & 24-48h: <0.02%/h) which vaporises. In cases of prolonged exposure MEKO may damage nasal membranes. If MEKO is inhaled in large quantities over prolonged periods of time there may be irreversible damage to health: H351: Suspected of causing cancer. 2.4. Unknown acute toxicity (GHS US) Not applicable Substances Not applicable Mixtures Name Product identifier % GHS-US classification Methyltris(1-methylpropylideneaminooxy)silane (CAS -No.) 22984-54-9 2.5 - 5 Skin Irrit. 2, H315 Eye Irrit. 2A, H319 Skin Sens. 1, H317 Titanium dioxide (CAS -No.) 13463-67-7 1 - 2.5 Carc. 2, H351 octamethylcyclotetrasiloxane (CAS -No.) 556-67-2 0.1 - 1 Flam. Liq. 3, H226 Repr. 2, H361 Aquatic Chronic 4, H413 Full text of H-statements: see section 16 First -aid measures general IF exposed or concerned: Get medical advice/attention. First -aid measures after inhalation Remove person to fresh air and keep comfortable for breathing. Get medical advice/attention if you feel unwell. First -aid measures after skin contact Wash skin with plenty of water. Take off contaminated clothing. If skin irritation or rash occurs: Get medical advice/attention. First -aid measures after eye contact Rinse cautiously with water for several minutes. Remove contact lenses, if present and easy to do. Continue rinsing. If eye irritation persists: Get medical advice/attention. First -aid measures after ingestion Call a poison center or a doctor if you feel unwell. 4.2. Most important sympto Symptoms/effects after skin contact May cause an allergic skin reaction. 4.3. Immediate medical Treat symptomatically. 26/05/2020 US -OSHA - en 2/9 54 CFS-S SIL SL / CFS-S SIL GG Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations 5.1. Extinguishing media Suitable extinguishing media 5.2. Special hazards arising from the su Reactivity 5.3. Advice for firefighters Protection during firefighting Water spray. Dry powder. Foam. Carbon dioxide. The product is non -reactive under normal conditions of use, storage and transport. Self-contained breathing apparatus. Complete protective clothing. Do not attempt to take action without suitable protective equipment. 6.1. Persq�al precautions, protective equipment and emergency procedures 6.1.1. For non -emergency personnel Emergency procedures Ventilate spillage area. Avoid contact with skin and eyes. Avoid breathing vapours. 6.1.2. For emergency responders Protective equipment Do not attempt to take action without suitable protective equipment. For further information refer to section 8: "Exposure controls/personal protection". Avoid release to the environment. Methods for cleaning up Mechanically recover the product. Notify authorities if product enters sewers or public waters. Other information Dispose of materials or solid residues at an authorized site. For further information refer to section 13. 7.1. Precautions for safe handling Precautions for safe handling Ensure good ventilation of the work station. Wear personal protective equipment. Obtain special instructions before use. Do not handle until all safety precautions have been read and understood. Avoid contact with skin and eyes. Avoid breathing vapours. Hygiene measures Wash contaminated clothing before reuse. Do not eat, drink or smoke when using this product. Always wash hands after handling the product. Contaminated work clothing should not be allowed out of the workplace. Storage conditions Keep cool. Store in a dry place. Store locked up. Store in a well -ventilated place. Storage temperature 41 - 77 °F 8.1. Control parameters - Methyltris(1-methylpropylideneaminooxy)silane (22984-54-9) Not applicable 26/05/2020 US -OSHA - en 3/9 55 CFS-S SIL SL / CFS-S SIL GG Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations Titanium dioxide (13463-67-7) ACGIH ACGIH TWA (mg/m') 10 mg/m' ACGIH Remark (ACGIH) LRT irr; A3 OSHA OSHA PEL (TWA) (mg/m') 15 mg/m' octamethylcyclotetrasiloxane (556-67-2) Not applicable Additional information The product has a pasty consistency. Exposure limit values for respirable dusts are not relevant for this product. 8.2. Exposure controls Appropriate engineering controls Ensure good ventilation of the work station. Personal protective equipment Protective clothing. Safety glasses. Gloves. Hand protection protective gloves. EN 374. Eye protection EN 166. Skin and body protection Wear suitable protective clothing. Respiratory protection In case of inadequate ventilation wear respiratory protection. Environmental exposure controls Avoid release to the environment. lWnformation on basic physical and chemical properties Physical state Liquid Appearance Pasty. Colour red white Odour odourless Odour threshold Not determined pH 8.5 Melting point Not applicable Freezing point No data available Boiling point No data available Flash point 412 °F Relative evaporation rate (butylacetate=1) No data available Flammability (solid, gas) No data available Explosive limits No data available Explosive properties No data available Oxidising properties No data available Vapour pressure No data available Relative density No data available Relative vapour density at 20 °C No data available Density 1.38 g/cm' Molecular mass Not determined Solubility No data available Log Pow No data available Auto -ignition temperature No data available 26/05/2020 US -OSHA - en 4/9 56 CFS-S SIL SL / CFS-S SIL GG Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations Decomposition temperature Viscosity Viscosity, kinematic Viscosity, dynamic 9.2. Other information No additional information available No data available No data available No data available No data available 10.1. Reactivity The product is non -reactive under normal conditions of use, storage and transport. 10.2. Chemical stability i Stable under normal conditions. No dangerous reactions known under normal conditions of use. Not established. 10.4. Conditions to avoid None under recommended storage and handling conditions (see section 7). 0.5. Incompatible material No additional information available 10.6. Hazardous decomposition produ Under normal conditions of storage and use, hazardous decomposition products should not be produced. 11.1. Information on toxicological effects Acute toxicity Not classified Methyltris(1-methylpropylideneam1nooxy)silane (22984-54-9) LD50 oral rat 2250 mg/kg (Rat; Literature study) ATE US (oral) 2250 mg/kg bodyweight Titanium dioxide (13463-67-7) LD50 oral rat > 5000 mg/kg bodyweight (OECD 425: Acute Oral Toxicity: Up -and -Down Procedure, Rat, Female, Experimental value, Oral, 14 day(s)) LC50 inhalation rat (mg/1) > 6.82 mg/I (Other, 4 h, Rat, Male, Experimental value, Inhalation (dust), 14 day(s)) ATE US (vapours) 5.09 mg/l/4h ATE US (dust,mist) 5.09 mg/l/4h octamethylcyclotetrasiloxane (556-67-2) LD50 oral rat > 4800 mg/kg (Equivalent or similar to OECD 401, Rat, Male, Experimental value, Oral) LD50 dermal rat > 2400 mg/kg bodyweight (Equivalent or similar to OECD 402, Rat, Male / female, Experimental value, Dermal) LC50 inhalation rat (mg/1) 36 mg/I (OECD 403: Acute Inhalation Toxicity, 4 h, Rat, Male / female, Experimental value, Inhalation (aerosol)) ATE US (vapours) 36 mg/l/4h ATE US (dust,mist) 36 mg/l/4h 26/05/2020 US -OSHA - en 5/9 57 CFS-S SIL SL / CFS-S SIL GG Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations Skin corrosion/irritation Serious eye damage/irritation Respiratory or skin sensitisation Germ cell mutagenicity Carcinogenicity Not classified pH: 8.5 Not classified pH: 8.5 May cause an allergic skin reaction. Not classified Not classified Titanium dioxide (13463-67-7) IARC group 2B - Possibly carcinogenic to humans Reproductive toxicity Suspected of damaging fertility or the unborn child. STOT-single exposure Not classified STOT-repeated exposure Not classified Aspiration hazard Not classified Symptoms/effects after skin contact May cause an allergic skin reaction. Ecology - general The product is not considered harmful to aquatic organisms nor to cause long-term adverse effects in the environment. Methyltris(1-methylpropylideneaminooxy)silane (22984-54-9) LC50 fish 1 > 560 mg/I (96 h; Pisces; Reaction product) EC50 Daphnia 1 750 mg/I (48 h; Daphnia magna; Reaction product) Titanium dioxide (13463-67-7) LC50 fish 1 > 100 mg/I (Equivalent or similar to OECD 203, 96 h, Oncorhynchus mykiss, Static system, Fresh water, Experimental value, Nominal concentration) LC50 other aquatic organisms 1 > 500 mg/I ErC50 (algae) 61 mg/I (EPA 600/9-78-018, 72 h, Pseudokirchneriella subcapitata, Static system, Fresh water, Experimental value, Nominal concentration) octamethylcyclotetrasiloxane (556-67-2) LC50 fish 1 > 0.022 mg/I (EPA OTS 797.1400, 96 h, Oncorhynchus mykiss, Flow -through system, Fresh water, Experimental value) EC50 Daphnia 1 > 0.015 mg/I (EPA OTS 797.1300, 48 h, Daphnia magna, Flow -through system, Fresh water, Experimental value, GLP) 12.2. Persistence and degradability Methyltris(1-methylpropylideneaminooxy)silane (22984-54-9) Persistence and degradability Readily biodegradable in water. No (test)data on mobility of the substance available. Titanium dioxide (13463-67-7) Persistence and degradability Biodegradability: not applicable. Chemical oxygen demand (COD) Not applicable (inorganic) ThOD Not applicable (inorganic) octamethylcyclotetrasiloxane (556-67-2) Persistence and degradability Not readily biodegradable in water. 12.3. Bioaccumulative potential 26/05/2020 US -OSHA - en 6/9 58 CFS-S SIL SL / CFS-S SIL GG Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations Methyltris(1-methylpropylideneaminooxy)silane (22984-54-9) Bioaccumulative potential No bioaccumulation data available. Titanium dioxide (13463-67-7) Bioaccumulative potential Not bioaccumulative. octamethylcyclotetrasiloxane (556-67-2) BCF fish 1 12400 (Other, 672 h, Pimephales promelas, Flow -through system, Experimental value, GLP) Log Pow 4.45 - 5.1 (Literature) Bioaccumulative potential High potential for bioaccumulation (BCF > 5000). 12.4. Mobility in soil 1 Titanium dioxide (13463-67-7) Ecology - soil Low potential for mobility in soil. octamethylcyclotetrasiloxane (556-67-2) Log Koc 4.22 (log Koc, OECD 106: Adsorption/Desorption Using a Batch Equilibrium Method, Experimental value, GLP) Ecology - soil Low potential for mobility in soil. k2.5. Other adverse effectS� No additional information available 13.1. Waste treatment methods _ Waste treatment methods Product/Packaging disposal recommendations In accordance with ADR / RID / IMDG / IATA / ADN Dispose of contents/container in accordance with licensed collector's sorting instructions. Recycle the material as far as possible. • D - IIVIDG IATA RID 14.1. UN number Not applicable Not applicable Not applicable Not applicable 14.2. UN proper shipping name Not applicable Not applicable Not applicable Not applicable 14.3. Transport hazard class(es) Not applicable Not applicable Not applicable Not applicable 14.4. Packing group Not applicable Not applicable Not applicable Not applicable 14.5. Environmental hazards Dangerous for the environment: No Dangerous for the environment : No Marine pollutant : No Dangerous for the environment : No Dangerous for the environment No No supplementary information available 26/05/2020 US -OSHA - en 7/9 59 CFS-S SIL SL / CFS-S SIL GG Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations 14.6. Special precautions for user = - Overland transport - Transport by sea No data available - Air transport No data available - Rail transport Carriage prohibited (RID) No 14.7. Transport in bulk according to Annex II of MARPOL and the IBC Code 15.1. US Federal regulations All components of this product are listed, or excluded from listing, on the United States Environmental Protection Agency Toxic Substances Control Act (TSCA) inventory octamethylcyclotetrasiloxane (556-67-2) EPA TSCA Regulatory Flag I T - T - indicates a substance that is the subject of a final TSCA section 4 test rule. 15.2. International regulations CANADA Methyltris(1-methylpropylideneamiinooxy)silane (22984-54-9) Listed on the Canadian DSL (Domestic Substances List) Titanium dioxide (13463-67-7) Listed on the Canadian DSL (Domestic Substances List) octamethylcyclotetrasiloxane (556-67-2) Listed on the Canadian DSL (Domestic Substances List) EU-Regulations No additional information available National regulations Titanium dioxide (13463-67-7) Listed on IARC (International Agency for Research on Cancer) 15.3. US State regulations California Proposition 65 - This product does not contain any substances known to the state of California to cause cancer, developmental and/or reproductive harm 26/05/2020 US -OSHA - en 8/9 I CFS-S SIL SL / CFS-S SIL GG Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations Component State or local regulations Methyltris(1-methylpropylideneaminooxy)silane(22984- 54-9) Titanium dioxide(13463-67-7) octamethylcyclotetrasiloxane(556-67-2) Revision date Full text of H-statements: 05/26/2020 H226 Flammable liquid and vapour. H315 Causes skin irritation. H317 May cause an allergic skin reaction. H319 Causes serious eye irritation. H351 Suspected of causing cancer. H361 Suspected of damaging fertility or the unborn child. H413 May cause long lasting harmful effects to aquatic life. NFPA health hazard 2 - Materials that, under emergency conditions, can cause temporary incapacitation or residual injury. NFPA fire hazard 1 - Materials that must be preheated before ignition can occur. NFPA reactivity 0 - Material that in themselves are normally stable, even under fire conditions. Hazard Rating Health 0 Minimal Hazard - No significant risk to health Flammability 0 Minimal Hazard - Materials that will not burn Physical 0 Minimal Hazard - Materials that are normally stable, even under fire conditions, and will NOT react with water, polymerize, decompose, condense, or self -react. Non -Explosives. Personal protection B B - Safety glasses, Gloves Indication of changes: Section Fchanged item Change Comments general update SDS US Hilt! This information is based on our current knowledge and is intended to describe the product for the purposes of health, safety and environmental requirements only. It should not therefore be construed as guaranteeing any specific property of the product. 26/05/2020 US -OSHA - en 9/9 61 LEGEND Technical Services, Inc. 88 Empire Drive • St. Paul, Minnesota • 55103 (651) 642-1150 • fax (651) 642-1239 VOC Content Test Certificate June 25, 2020 Supplier: Hilti Entwicklungsgesellschaft mbH BU Chemicals Hiltistrasse 6 86916 Kaufering GERMANY Sample Description: CFS-S SIL GG Date Tested: June 4, 2020 Test Method: SCAQMD method 304-91 "Determination of Volatile Organic Compounds (VOC) in Various Materials" as referenced by South Coast Air Quality Management District (SCAQMD) Rule 1168. The values also comply with the requirements of EPA test method #24. Test Data: Specification Product LEED 4.1 Low -Emitting Materials — Adhesives and Sealants CFS-S SIL GG Green Building Council of Australia Green Star Office Design 3.0, IEQ-13 Green Star Office Design 2.0, IEQ-13 Green Star Office Interiors 1.1, IEQ-11 All Other Sealants VOC Limit: 420 g/L Product contains: 41 g/L of VOC Digitally signed by Tom Barrett DIN: cn=Tom Barrett, o=Legend Technical Services, ou, email=tbarrett@legend- j group.com, c=US Date: 2020.06.25 13:27:41-05'00' Tom Barrett Vice President/Strategic Analytical Services A Flexible Firestop Sealant (CP 606) Product description ■ An acrylic based firestop sealant that provides movement capability in fire rated joints and seals through -penetrations applications Product features ■ Silicone free ■ Halogen, asbestos and solvent free ■ Paintable ■ Tested up to 33% movement with 500 cycles in accordance to UL 2079 and ASTM 1966 ■ Smoke and fume resistant ■ Easy clean up with water ■ Single component systems available ■ Meets LEEDT"M requirements for indoor environmental quality credit 4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paints and Coatings Areas of application ■ Sealing construction/expansion joints ■ Top -of -wall joints ■ Metal pipes ■ Cable bundles ■ HVAC penetrations For use with ■ Various base materials such as masonry, concrete, gypsum, etc. ■ Wall and floor assemblies rated up to 3 hours Examples ■ Where a gypsum wall assembly meets the underside of a metal or concrete deck Technical Data* Chemical basis CP 606 Acrylic based firestop sealant Color Available in red, white and gray Application temperature 40oF to 104°F (5°C to 40oC) Skin -forming time Approx. 15 min Curing time Approx. 3 mm / 3 days Average volume shrinkage (ASTM C1241) 22.2% Movement capability Approx. 10% Temperature resistance -22°F to 176°F (-30°C to 80°C) Surface burning characteristics (ASTM E 84-96) Flame Spread: 10 Smoke Development: 0 Sound transmission classification (ASTM E 90-99) 56 (Relates to specific construction) Tested in accordance with • UL 2079 • ASTM E 814 • ASTM E 1966 • ASTM E 84 • UL 1479 • ASTM G21 'At 73°F (23°C) and 50% relative humidity ■ Sealing expansion joints to impede the passage of fire, smoke and toxic fumes ■ Sealing around HVAC penetrations through fire -rated assemblies psstp oOo U C US FILL, VOID OR CAVITY MATERIAL FOR USE IN THROUGH -PENETRATION FIRESTOP SYSTEMS AND JOINT SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY FM APPROVED 66Y7 Installation instructions for CP 606 Notice • Before handling, read Material Safety Data Sheet and product label for safe usage and health information. • Instructions below are general guidelines — always refer to the applicable drawing in the UL Fire Resistance Directory or Hilti Firestop Systems Guide for complete installation information • The use of backing material is recommended to control the sealant depth and help ensure assembly seal is complete Opening 1. Clean the opening. Surfaces to which CP 606 will be applied should be cleaned of loose debris, dirt, oil, wax and grease. The surface should be moisture and frost free. permanently marked with an identification plate and fastened in a visible position next to the seal. Not for use • On areas immersed in water Application of firestop 2. Insert fill of mineral wool or backer (as required). 3. Apply firestop over backer. 4. Smooth firestop sealant with a trowel before the skin forms. Once cured, CP 606 can only be removed mechanically. 5. For maintenance reasons, a penetration seal can be 1. Clean opening Hilti. Outperform. Outlast. 2. Insert backing material compressed per UL System 4!9Z 2. Insert backing material Storage • Store only in the original packaging in a location protected from moisture at a temperature of 40°F to 77°F (5°C to 25°C) • Observe expiration date on package 3. Apply CP 606 4. Smooth CP 606 5. Fasten identification plate (if required) t 1 3. Apply CP 606 4. Smooth CP 606 1!11 n5_ biaim 5. Fasten identification plate (if required) Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en espanol 1-800-879-5000 • Hilti Firestop Systems Guide 63 CERTIFICATE OF COMPLIANCE Certificate Number Report Reference Issue Date 20160930-R13240 R13240 2016-September-30 Issued to: Hilti Construction Chemicals, Div of Hilti Inc. 5400 S 122nd East Ave Tulsa, OK 74146 This is to certify that Fill, Void or Cavity Materials representative samples of Fill, Void or Cavity Materials Certified for Canada CP 606 Sealant for use in Through -Penetration Firestop, Joint in wall and partition Systems as currently decribed in the UL Fire Resistance Directory and in the Products Certified for Canada Directory. Have been investigated by UL in accordance with the Standard(s) indicated on this Certificate. Standard(s) for Safety: ANSI/UL 1479, "Fire Tests of Through -Penetration Firestops," ANSI/UL 2079, "Tests for Fire Resistance of Building Joint Systems," CAN/ULC-S115, "Standard Method of Fire Tests of Firestop Systems." Additional Information: See the UL Online Certifications Directory at www.ul.com/database for additional information Only those products bearing the UL Certification Mark should be considered as being covered by UL's Certification and Follow -Up Service. Look for the UL Certification Mark on the product. Bruce Mahrenholz, Director North American Certification Program UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at http:/Iul.comlaboutulliocations/ Page 1 of 1 64 Hilti Firestop Acrylic Sealant CFS-S ACR; CP 606 Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations Date of issue: 01/07/2016 Revision date: 01/07/2016 Supersedes: 01/07/2016 Version: 4.2 1.1. Identification Product form Mixture Name Hilti Firestop Acrylic Sealant CFS-S ACR; CP 606 Product code BU Chemicals Chemical structure 1.2. Relevant identified uses of the substance or mixture and uses advised against No additional information available 1.3. Details of the supplier of the safety data sheet Hilti, Inc. Legacy Tower, Suite 1000 75024 Plano - USA T +1 9724035800 1-800-879-8000 toll free - F +1 918 254 0522 Supplier Hilti, Inc. Legacy Tower, Suite 1000 75024 Plano - USA T +1 9724035800 1-800-879-8000 toll free - F +1 918 254 0522 1.4. Emergency telephone number Department issuing data specification sheet Hilti AG FeldkircherstraRe 100 9494 Schaan - Liechtenstein T +423 234 2111 chemicals.hse anhilti.com Emergency number Chem-Trec Tel.: 1 800 424 9300 (USA, PR, Virgin Islands, Canada) Tel.: 703 527 3887 (Other countries) +1 918 8723000 1-800-879-8000 toll free 2.1. Classification of the substance or mixture GHS-US classification Not classified 2.2. Label elements GHS-US labelling No labelling applicable 2.3. Other hazards No additional information available 2.4. Unknown acute toxicity (GHS US) Not applicable 07/01/2016 EN (English) 1/7 65 Hilti Firestop Acrylic Sealant CFS-S ACR; CP 606 Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations 3.1. Substance Not applicable 3.2. Mixture Full text of H-statements: see section 16 4.1. Description of first aid measures First -aid measures after inhalation Get medical advice/attention if you feel unwell. First -aid measures after skin contact Wash skin with plenty of water. If skin irritation occurs: Get medical advice/attention. First -aid measures after eye contact Rinse cautiously with water for several minutes. Remove contact lenses, if present and easy to do. Continue rinsing. If eye irritation persists: Get medical advice/attention. First -aid measures after ingestion Get medical advice/attention if you feel unwell. 4.2. Most important symptoms and effects, both acute and delayed No additional information available 4.3. Indication of any immediate medical attention and special treatment needed No additional information available 5.1. Extinguishing media Suitable extinguishing media Water spray. Dry powder. Foam. Carbon dioxide. 5.2. Special hazards arising from the substance or mixture Reactivity The product is non -reactive under normal conditions of use, storage and transport. 5.3. Advice for firefighters Protection during firefighting Self-contained breathing apparatus. Complete protective clothing. 6.1. Personal precautions, protective equipment and emergency procedures 6.1.1. For non -emergency personnel No additional information available 6.1.2. For emergency responders Protective equipment For further information refer to section 8: "Exposure controls/personal protection". 6.2. Environmental precautions No additional information available 6.3. Methods and material for containment and cleaning up Methods for cleaning up Recover mechanically the product. 6.4. Reference to other sections For further information refer to section 13. 07/01/2016 EN (English) 2/7 66 Hilti Firestop Acrylic Sealant CFS-S ACR; CP 606 Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations 7.1. Precautions for safe handling Precautions for safe handling Wear personal protective equipment. Hygiene measures Wash contaminated clothing before reuse. Do not eat, drink or smoke when using this product. Always wash hands after handling the product. 7.2. Conditions for safe storage, including any incompatibilities Storage conditions Keep cool. Store in a dry place. Storage temperature 41 - 77 °F 8.1. Control parameters No additional information available 8.2. Exposure controls Personal protective equipment Hand protection Eye protection Skin and body protection Protective clothing. Safety glasses. Gloves. 0 OO Protective gloves. EN 374. Safety glasses. EN 166. EN 170. Wear suitable protective clothing. 9.1. Information on basic physical and chemical properties Physical state Liquid Appearance Pasty. Colour red white Grey Odour characteristic Odour threshold Not determined pH = 9 Not applicable Melting point Not applicable Freezing point No data available Boiling point No data available Flash point Not applicable Relative evaporation rate (butylacetate=1) No data available Flammability (solid, gas) No data available Explosive limits No data available Explosive properties No data available Oxidising properties No data available Vapour pressure No data available Relative density No data available Relative vapour density at 20 °C No data available Density 1.6 g/cm' Molecular mass Not determined Solubility No data available 07/01/2016 EN (English) 3/7 67 Hilti Firestop Acrylic Sealant CFS-S ACR; CP 606 Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations Log Pow Auto -ignition temperature Decomposition temperature Viscosity Viscosity, kinematic Viscosity, dynamic 9.2. Other information No additional information available No data available No data available No data available No data available No data available No data available 10.1. Reactivity The product is non -reactive under normal conditions of use, storage and transport 10.2. Chemical stability Stable under normal conditions. 10.3. Possibility of hazardous reactions No dangerous reactions known under normal conditions of use. 10.4. Conditions to avoid None under recommended storage and handling conditions (see section 7). 10.5. Incompatible materials No additional information available 10.6. Hazardous decomposition products Under normal conditions of storage and use, hazardous decomposition products should not be produced. 11.1. Information on toxicological effects Acute toxicity Not classified Skin corrosion/irritation Not classified pH: = 9 Not applicable Serious eye damage/irritation Not classified pH: = 9 Not applicable Respiratory or skin sensitisation Not classified Germ cell mutagenicity Not classified Carcinogenicity Not classified Reproductive toxicity Not classified Specific target organ toxicity (single exposure) Not classified Specific target organ toxicity (repeated Not classified exposure) Aspiration hazard Not classified 07/01/2016 EN (English) 4/7 68 Hilti Firestop Acrylic Sealant CFS-S ACR; CP 606 Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations Ecology - general 12.2. Persistence and degradability No additional information available �ioajjWative potential No additional information available �bility in soil No additional information available 12.5. Other adverse effects Effect on the global warming 13.1. Waste treatment meth( Waste treatment methods Waste disposal recommendations In accordance with ADR / RID / IMDG / IATA / ADN The product is not considered harmful to aquatic organisms or to cause long-term adverse effects in the environment. No known ecological damage caused by this product. Dispose of contents/container in accordance with licensed collector's sorting instructions. Dispose in a safe manner in accordance with local/national regulations. 14.1. UN number Not regulated for transport 14.2. UN proper shipping name Proper Shipping Name (ADR) Not applicable Proper Shipping Name (IMDG) Not applicable Proper Shipping Name (IATA) Not applicable Proper Shipping Name (ADN) Not applicable Proper Shipping Name (RID) Not applicable W3. Transport hazard class(es) - ADR Transport hazard class(es) (ADR) Not applicable IMDG Transport hazard class(es) (IMDG) Not applicable IATA Transport hazard class(es) (IATA) Not applicable ADN Transport hazard class(es) (ADN) Not applicable RID 07/01/2016 EN (English) 5/7 69 Hilti Firestop Acrylic Sealant CFS-S ACR; CP 606 Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations Transport hazard class(es) (RID) 14.4. Packing group Packing group (ADR) Packing group (IMDG) Packing group (IATA) Packing group (ADN) Packing group (RID) 14.5. Environmental hazards Dangerous for the environment Marine pollutant Other information 14.6. Special precautions for user - Overland transport - Transport by sea No data available - Air transport No data available - Inland waterway transport Carriage prohibited (ADN) Not subject to ADN - Rail transport Carriage prohibited (RID) Not applicable Not applicable Not applicable Not applicable Not applicable Not applicable No No No supplementary information available No No IR.' 14.7. Transport in bulk according to Annex II of MARPOL 73/78 and the IBC Code 15.1. US Federal regulations This product or mixture does not contain a toxic chemical or chemicals in excess of the applicable de minimis concentration as specified in 40 CFR §372.38(a) subject to the reporting requirements of section 313 of Title III of the Superfund Amendments and Reauthorization Act of 1986 and 40 CFR Part 372. 15.2. International regulations CANADA Hilti Firestop Acrylic Sealant CFS-S ACR; CP 606 WHMIS Classification I Uncontrolled product according to WHMIS classification criteria EU-Regulations No additional information available Classification according to Regulation (EC) No. 1272/2008 [CLP] Not classified National regulations No additional information available 07/01/2016 EN (English) 6/7 70 Hilti Firestop Acrylic Sealant CFS-S ACR; CP 606 Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations 15.3. US State regulations California Proposition 65 - This product does not contain any substances known to the state of California to cause cancer, developmental and/or reproductive harm Revision date 01/07/2016 HMIS III Rating Health 0 Minimal Hazard - No significant risk to health Flammability 0 Minimal Hazard - Materials that will not burn Physical 0 Minimal Hazard - Materials that are normally stable, even under fire conditions, and will NOT react with water, polymerize, decompose, condense, or self -react. Non -Explosives. Personal Protection B B - Safety glasses, Gloves SIDS US Hilti This information is based on our current knowledge and is intended to describe the product for the purposes of health, safety and environmental requirements only. It should not therefore be construed as guaranteeing any specific property of the product 07/01/2016 EN (English) 7/7 71 February 26, 2010 To Whom It May Concern: Re: Hilti CP 606 Flexible Firestop — LEEDs Info. The Hilti CP 606 Flexible Firestop Sealant is manufactured in Germany. The CP 606 pail is made of polyethylene and can be completely recycled. There is no post - consumer or post-industrial content in CP 606 and it cannot be recycled. The CP 606 does not contain any Rapidly Renewable Materials. The VOC content for CP 606 is 71.0 grams/liter. CP 606 is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non -regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state regulatory agencies for direction on disposal. Please feel free to contact me at (918) 872-3704 if you have questions. Sincerely, Jerry Metcalf MPH, CHMM Safety/Environmental Manager Hilti Inc. 918 872 3704 a erry.metcalf(a).hilti.com Om By. aPzylito] Hilti, Inc. 5400 South 122nd East Avenue Tulsa, OK 74146 1-800-879-8000 www.hilti.com 72 11111-1700 FI RESTOP CP 617 PUTTY PADS Product description A moldable firestop putty designed to help protect electrical outlet boxes, junction boxes, and large steel boxes Applications for use Protection of electrical outlet boxes, large steel boxes and junction boxes General gypsum wall assemblies with wood or metal studs When two outlets on opposite sides of the wall are located within a single stud / cavity or within 24" measured horizontally (not back-to-back unless specified by specific UL approval) Advantages Applied by hand, no tools required. Pad can be molded without leaving residue on hands No electrical conductivity Quick and simple to install Can be used for commercial and residential applications Asbestos, formaldehyde and LABS free Red list compliant No oil migration. Putty remains flexible over time Excellent adhesion to gypsum, metal and plastic Hilti-branded paper has integrated IFU on each pad No methylene diisocynate, phthalates, volatile solvents or abestos fibers Installation instructions See Hilti literature or third -party listings for complete application and installation details Technical Data Chemical basis Color Recommended application temperature Storage and transportation temperature range Density Temperature resistance range Mold and mildew performance Tested in accordance with Surface burning characteristics LEED v4.1 compliance LEED VOC Dimensions (LxWxH) Package includes Acoustics performance Shelf life Curing time Butyl rubber Red 32' to 104' F Product information Order designation Sales pack quantity Item number CP 617 6"x7" 20 309760 CP 617 L 7"x7" 20 333583 CP 617 XL 9"x9" 20 373387 23' to 104' F 1.6 g/cm3 -40' to 104' F Class 0 (ASTM G21-96) "TA UL 1479, CAN / ULC-S115, ASTM E814 Flame spread 15 (ASTM E84) Smoke development 10 (ASTM E84) Complies with CDPH standard method vl.2-2017 2 g/L CP 617 6"x7": 6"x7"x1/8" (15x18x0.3 cm) CP 617 L 7"x7": TW"x1/8" (18x18x0.3 cm) CP 617 XL 9"x9": 9"x9"x1/8" (23x23x0.3 cm) 20 pcs per box 64 (relates to specific construction) ASTM E90 Not relevant Non -curing SUL" �`p F C �L us APPROVED <�R r Hilti Firestop Saving lives through innovation 1 flE and education f VI YID ® i n 73 CERTIFICATE OF COMPLIANCE Certificate Number R13240 Report Reference R13240-20191125 Issue Date 2019-DECEMBER-11 Issued to: HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC 7250 Dallas Pky, Legacy Tower Suite 1000 Plano TX 75024 This certificate confirms that FILL, VOID OR CAVITY MATERIALS representative samples of See Addendum Page Have been investigated by UL in accordance with the Standard(s) indicated on this Certificate. Standard(s) for safety: ANSI/UL 1479 : Fire Tests of Penetration Firestops CAN/ULC-S115 : Method of Fire Tests of Firestops Systems Additional Information: See the UL Online Certifications Directory at https://ig.ulprospector.com for additional information. This Certificate of Compliance does not provide authorization to apply the UL Mark. Only the UL Follow -Up Services Procedure provides authorization to apply the UL Mark. Only those products bearing the UL Mark should be considered as being UL Certified and covered under UL's Follow -Up Services. Look for the UL Certification Mark on the product. Bruce Mahrenholz, Director North American Certification Program UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at hftp://ul.com/aboutul/locations/ Page 1 of 2 74 CERTIFICATE OF COMPLIANCE Certificate Number R13240 Report Reference R13240-20191125 Issue Date 2019-DECEMBER-11 This is to certify that representative samples of the product as specified on this certificate were tested according to the current UL requirements. USC, CNC Putty Pads identified as Hilti CP 617, CP 617L, CP 617XL Putty Pads to be used as a "Wall Opening Protective Material". Hilti CP 619T Putty Rolls to be used in Through -Penetration Firestop Systems. Bruce Mahrenholz, Director North American Certification Program UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at hftp://ul.com/aboutul/locations/ Page 2 of 2 75 CFS-P BA, CP 617, CP 618, CP 619, CFS-D 111, CFS-D 25 Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations Date of issue: 10/18/2019 Revision date: 10/18/2019 Supersedes: 09/22/2016 Version: 2.7 1.1. Identification Product form Mixture Trade name CFS-P BA, CP 617, CP 618, CP 619, CFS-D 1", CFS-D 25 Product code BU Fire Protection 1.2. Relevant identified uses of the substance or mixture and uses advised against Use of the substance/mixture Firestop putty pad 1.3. Details of the supplier of the safety data sheet Hilti, Inc. Legacy Tower, Suite 1000 7250 Dallas Parkway TX 75024 Plano - USA T +1 9724035800 1-800-879-8000 toll free - F +1 918 254 0522 Supplier Hilti, Inc. Legacy Tower, Suite 1000 7250 Dallas Parkway TX 75024 Plano - USA T +1 9724035800 1-800-879-8000 toll free - F +1 918 254 0522 1.4. Emergency telephone number Department issuing data specification sheet Hilti AG FeldkircherstraRe 100 9494 Schaan - Liechtenstein T +423 234 2111 chemicals.hse(aDhilti.com Emergency number Chem-Trec Tel.: 1 800 424 9300 (USA, PR, Virgin Islands, Canada) Tel.: 703 527 3887 (Other countries) +1 918 8723000 1-800-879-8000 toll free 2.1. Classification of the substance or mixture GHS-US classification Not classified 2.2. Label elements GHS US labelling No labelling applicable 2.3. Other hazards No additional information available 2.4. Unknown acute toxicity (GHS US) Not applicable 18/10/2019 US -OSHA - en 1/8 76 CFS-P BA, CP 617, CP 618, CP 619, CFS-D 1", CFS-D 25 Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations 3.1. Substances Not applicable 3.2. Mixtures Full text of H-statements: see section 16 4.1. Description of first aid measures First -aid measures general First -aid measures after inhalation First -aid measures after skin contact First -aid measures after eye contact First -aid measures after ingestion JL Never give anything by mouth to an unconscious person. If you feel unwell, seek medical advice (show the label where possible). Get medical advice/attention if you feel unwell. Allow affected person to breathe fresh air. Allow the victim to rest. Wash skin with plenty of water. If skin irritation occurs: Get medical advice/attention. Remove affected clothing and wash all exposed skin area with mild soap and water, followed by warm water rinse. Rinse cautiously with water for several minutes. Remove contact lenses, if present and easy to do. Continue rinsing. If eye irritation persists: Get medical advice/attention. Rinse immediately with plenty of water. Obtain medical attention if pain, blinking or redness persists. Get medical advice/attention if you feel unwell. Rinse mouth. Do NOT induce vomiting. Obtain emergency medical attention. 0. Most important symptoms and effects (acute and delayed) Potential adverse human health effects and Based on available data, the classification criteria are not met. symptoms Symptoms/effects Not expected to present a significant hazard under anticipated conditions of normal use. _ Immediate medical attention and special treatment, if necessary €xtinguishing Suitable extinguishing media Water spray. Dry powder. Foam. Carbon dioxide. Sand. Unsuitable extinguishing media Do not use a heavy water stream. 5.2. Special hazards arising from the substance or mixture Reactivity The product is non -reactive under normal conditions of use, storage and transport 5.3. Advice for firefighters Firefighting instructions Use water spray or fog for cooling exposed containers. Exercise caution when fighting any chemical fire. Prevent fire fighting water from entering the environment. Protection during firefighting Self-contained breathing apparatus. Complete protective clothing. Do not enter fire area without proper protective equipment, including respiratory protection. 18/10/2019 US -OSHA - en 2/8 77 CFS-P BA, CP 617, CP 618, CP 619, CFS-D 111, CFS-D 25 Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations 6.1. Personal precautions, protective equipment and emergency procedures 6.1.1. For non -emergency personnel Emergency procedures Evacuate unnecessary personnel. 6.1.2. For emergency responders Protective equipment For further information refer to section 8: "Exposure controls/personal protection". Equip cleanup crew with proper protection. Emergency procedures Ventilate area. 6.2. Environmental precautions Mow Prevent entry to sewers and public waters. Notify authorities if liquid enters sewers or public waters. L6.3. Met ial for containment and cleaning up Methods for cleaning up Mechanically recover the product. On land, sweep or shovel into suitable containers. Minimise generation of dust. Store away from other materials. For further information refer to section 13. See Heading 8. Exposure controls and personal protection. 7.1. Precautions for safe handling Precautions for safe handling Wear personal protective equipment. Wash hands and other exposed areas with mild soap and water before eating, drinking or smoking and when leaving work. Provide good ventilation in process area to prevent formation of vapour. Hygiene measures Wash contaminated clothing before reuse. Do not eat, drink or smoke when using this product. Always wash hands after handling the product. 7.2. Conditions for safe 4orage, including any incompatibilities A Storage conditions Keep cool. Store in a dry place. Keep only in the original container in a cool, well ventilated place away from : Keep container closed when not in use. Incompatible products Strong bases. Strong acids. Incompatible materials Sources of ignition. Direct sunlight. Storage temperature 23 - 104 °F Wontrol parameter Additional information The product has a pasty consistency. Exposure limit values for respirable dusts are not relevant for this product. 8.2. Exposure controls W� i Personal protective equipment Protective clothing. Safety glasses. Gloves. Avoid all unnecessary exposure. 0O J1 Hand protection Protective gloves. EN 374. Wear protective gloves. 18/10/2019 US -OSHA - an 3/8 78 CFS-P BA, CP 617, CP 618, CP 619, CFS-D 1", CFS-D 25 Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations Eye protection Chemical goggles or safety glasses. Skin and body protection Wear suitable protective clothing. Respiratory protection Wear appropriate mask. Other information Do not eat, drink or smoke during use. t7_ Information on basic physical and the ' Physical state Solid Appearance Pasty. Colour red Odour characteristic Odour threshold Not determined pH Not relevant Melting point Not applicable Freezing point No data available Boiling point No data available Flash point Not applicable Relative evaporation rate (butylacetate=1) No data available Flammability (solid, gas) No data available Explosive limits No data available Explosive properties No data available Oxidising properties No data available Vapour pressure No data available Relative density No data available Relative vapour density at 20 °C No data available Density 1.6 g/cm' Molecular mass Not determined Solubility No data available Log Pow No data available Auto -ignition temperature No data available Decomposition temperature No data available Viscosity No data available Viscosity, kinematic No data available Viscosity, dynamic No data available No additional information available M. Reacti The product is non -reactive under normal conditions of use, storage and transport. chemical s Stable under normal conditions. Not established. 18/10/2019 US -OSHA - en 4/8 79 CFS-P BA, CP 617, CP 618, CP 619, CFS-D 1", CFS-D 25 Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations No dangerous reactions known under normal conditions of use. Not established. 10.4. Conditions to avoid None under recommended storage and handling conditions (see section 7). Direct sunlight. Extremely high or low temperatures. NEI.& I Strong acids. Strong bases. 10.6. Hazardous decomposition produ Under normal conditions of storage and use, hazardous decomposition products should not be produced. fume. Carbon monoxide. Carbon dioxide. 11.1. InfornII&p on toxicological effects Acute toxicity Not classified Skin corrosion/irritation Not classified pH: Not relevant Serious eye damage/irritation Not classified pH: Not relevant Respiratory or skin sensitisation Not classified Germ cell mutagenicity Not classified Based on available data, the classification criteria are not met Carcinogenicity Not classified Reproductive toxicity Not classified Based on available data, the classification criteria are not met STOT-single exposure Not classified STOT-repeated exposure Not classified Aspiration hazard Not classified Potential adverse human health effects and Based on available data, the classification criteria are not met. symptoms Ecology - general The product is not considered harmful to aquatic organisms nor to cause long-term adverse effects in the environment. 12.2. Persistence and degradability - CFS-P BA, CP 617, CP 618, CP 619, CFS-D 1", CFS-D 25 Persistence and degradability I Not established. 12.3. Bioaccumulative potential CFS-P BA, CP 617, CP 618, CP 619, CFS-D 1", CFS-D 25 Bioaccumulative potential I Not established. 18/10/2019 US -OSHA - en 5/8 80 CFS-P BA, CP 617, CP 618, CP 619, CFS-D 1", CFS-D 25 Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations No additional information available 12.5. Other advers;]Wcts Other information Avoid release to the environment. 13.1. Waste treatment methods Waste treatment methods Dispose in a safe manner in accordance with local/national regulations. Product/Packaging disposal recommendations Dispose in a safe manner in accordance with local/national regulations. Ecology - waste materials Avoid release to the environment. In accordance with ADR / RID / IMDG / IATA / ADN . D 14.1. UN number Not applicable Not applicable Not applicable Not applicable 14.2. UN proper shipping name Not applicable INot applicable Not applicable Not applicable 14.3. Transport hazard class es Not applicable Not applicable Not applicable Not applicable 14.4. Packing group Not applicable Not applicable Not applicable Not applicable 14.5. Environmental hazards Dangerous for the environment: No Dangerous for the environment : No Marine pollutant: No Dangerous for the environment : No Dangerous for the environment No No supplementary information available 14.6. Special precautions for user - Overland transport - Transport by sea No data available - Air transport No data available - Rail transport Carriage prohibited (RID) No 18/10/2019 US -OSHA - en 6/8 81 CFS-P BA, CP 617, CP 618, CP 619, CFS-D 1", CFS-D 25 Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations 14.7. Transp�ulk according to Annex II of MARPOL and the IBC Code 15.1. US Federal regulations - All components of this product are listed, or excluded from listing, on the United States Environmental Protection Agency Toxic Substances Control Act (TSCA) inventory regulations - CANADA No additional information available EU-Regulations No additional information available National regulations No additional information available 15.3. US State regulations California Proposition 65 - This product does not contain any substances known to the state of California to cause cancer, developmental and/or reproductive harm • . Other intormation Revision date 10/18/2019 Data sources REGULATION (EC) No 1272/2008 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 December 2008 on classification, labelling and packaging of substances and mixtures, amending and repealing Directives 67/548/EEC and 1999/45/EC, and amending Regulation (EC) No 1907/2006. Other information None. NFPA health hazard 0 - Materials that, under emergency conditions, would offer no hazard beyond that of ordinary combustible materials. NFPA fire hazard 0 - Materials that will not burn under typical fire conditions, including intrinsically noncombustible materials such as 0 4 concrete, stone, and sand. NFPA reactivity 0 - Material that in themselves are normally stable, even under fire conditions. 18/10/2019 US -OSHA - en 7/8 82 CFS-P BA, CP 617, CP 618, CP 619, CFS-D 1", CFS-D 25 Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations Hazard Rating Health 0 Minimal Hazard - No significant risk to health Flammability 0 Minimal Hazard - Materials that will not burn Physical 0 Minimal Hazard - Materials that are normally stable, even under fire conditions, and will NOT react with water, polymerize, decompose, condense, or self -react. Non -Explosives. Personal protection B B - Safety glasses, Gloves Indication of changes: Section Changed item Change Comments general update SDS US Hilti This information is based on our current knowledge and is intended to describe the product for the purposes of health, safety and environmental requirements only. It should not therefore be construed as guaranteeing any specific property of the product. 18/10/2019 US -OSHA - en 8/8 83 eco-INSTITUT, Schanzenstr. 6-20, D-51063 Koln Hilti Entwicklungsgesellschaft mbH Mr. Sebastian Simon HiltistralRe 6 D-86916 Kaufering Dear Mr. Simon, based on the evaluation of Test Report No. 54536-002 dated 2019-09-OS the testing results of product HILTI Firestop Putty Pad CP 617 manufactured by Hilti Entwicklungsgesellschaft mbH comply with the requirements of - VOC product emissions acc. to California Department of Public Health (CDPH) Standard Method v1.2-2017 (California Specification 01350 (01/2017)) These criteria meet the requirements for low -emitting Adhesives and Sealants in credit EQc2 of the LEEDv4 and LEEDv4.1 Rating System. Cologne, 2019-11-08 Marc -Anton Dobaj, M.Sc. Crystalline Materials (Project manager) eco-INSTITUT Germany GmbH L a b o r p r 0 f u n g Laboratory testing Nadi DIN IN ISO/IE(17025 akkledllieltes Pi00ab01 eco-INSTITUT Germany GmbH / Schanzenstrasse 6-20 / Carlswerk 1.19 / D-51063 Koln / Germany Tel. +49 221.931245-0 / Fax +49 221.931245-33 / eco-institut.de / Geschaftsf0hrer: Dr. Frank Kuebart, Daniel Tigges DAkkS HRB 17917 / USt-ID: DE 122653308 / Raiffeisenbank Frechen-HOrth, IBAN: DE60370623651701900010, BIC: GENODEDI FHH Akk,edide,ungsstelle D-PL-20051-01-00 84 Firestop Collar (CP 643N) Product description ■ A ready -to -use firestop collar, made of a galvanized steel housing and intumescent inserts for firestopping combustible pipes Product features ■ Ready -to -use collar ■ No construction required ■ Fast installation time ■ Adjustable mounting tabs ■ Low profile for tight installations Areas of application ■ Firestopping combustible pipes up to 6" diameter in penetrations through fire walls and floors ■ Suitable for the following pipe materials: ■ PVC, CPVC, ABS, PVDF, PP and FRPP For use with ■ Concrete, masonry, wood floor and gypsum wall assemblies ■ Wall and floor assemblies rated up to 4 hours Types of installation ■ Wall: two collars, one on each side ■ Floor: one collar on underside (bottom) Example ■ Waste water pipes ■ Fresh water pipes Installation instructions for CP 643N Notice • Before handling, read Material Safety Data Sheet and product label for safe usage and health information. • Instructions below are general guidelines — always refer to the applicable drawing in the UL Fire Resistance Directory or Hilti Firestop Systems Guide for complete installation information Opening 1. Clean the plastic pipes. Expansion of the intumescent material during a fire acts to close the plastic pipe. Very dirty pipes (ie: with remains of mortar) may lead to a delay in this closing action. Soiled plastic pipes should, therefore, be cleaned in the area where the CP 643N Firestop Collar is to be installed. Technical Data Description Pipe outside dia (in.) Collar outside dia. (in.) CP 643N Collar Height (in.) No. of hooks and fasteners CP 643-50/1.5"N 1.4-2.0 2.8 0.9 2 CP 643-63/2"N 2.0-2.5 3.4 1.3 2 CP 643-90/3"N 2.6-3.6 4.9 1.7 3 CP 643-110/4"N 3.6-4.5 6.0 1.9 3 CP 643-160/6"N 6.6 9.8 1.9 4 Temperature resistance -40°F to 140°F (-40°C to 60°C) Intumescent activation Approx. 3920F (200°C) Expansion ratio (unrestricted) Up to 1:10 Tested in accordance with • UL 1479 • ASTM E 814 • ASTM G21 psst,c6F FIRESTOP DEVICE °OO FOR USE IN THROUGH -PENETRATION FM F� FIRESTOP SYSTEMS r• �'SSEE f111rM UL FIRE RESISTANCE DIRECTORY APPROVED Visit ft—ystemcompatible.com. 5N76 F13G1 Is a trademark of the Wbrizol Corporation. Application of firestop system 2. Seal the opening if required. Gaps may be closed with FS-ONE. The approved methods vary and are given in the specific UL system. 3. Close the CP 643N Firestop Collar. Place the CP 643N Firestop Collar around the plastic pipe and lock the closure by applying firm pressure until it latches. 4. Attach fastening hooks. The fastening hooks can be attached to various points on the metal housing. This allows the fastening points to be made to suit the space available in each case. The hooks must be positioned as symmetrically as possible. The required number of fastening hooks is indicated on the packaging. 5. Fastening the CP 643N Firestop Collar. Only when fastened properly can CP 643N offer protection against fire. a. Mark the fastening points. b. Drill holes with a Hilti rotary hammer drill (i.e. TE 4-A18) or, depending on base material, fasten using Hilti powder -actuated tool. c. To secure the CP 643N Firestop Collar, use Hilti anchors/fasteners. d. For maintenance reasons, a penetration can be permanently marked with an identification plate and fastened in a visible position next to the seal. Not for use • With metal pipes • In highly corrosive surroundings With unapproved anchors/fasteners • � Storage Store only in the original packaging in a location protected from moisture 1. Clean plastic pipe. 2. Close remaining gap to 3. Close collar. 4. Attach fastening hooks. 5. Fasten "collar and provide smoke and gas identification plate resistant seal. (if required). Hilti Firestop Saving lives through innovation and education Hilti. Outperform. Outlast. Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en espanol 1-800-879-5000 • Hilti Firestop Systems Guide 85 CERTIFICATE OF COMPLIANCE Certificate Number 20160125-R15431 Report Reference R15431-19980323 Issue Date 2016-JAN UARY-25 Issued to: HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC 5400 S 122ND EAST AVE TULSA OK 74146 This is to certify that FIRESTOP DEVICES representative samples of Firestop devices designated CP 643 50/1.5" N, CP 643 63/2" N, CP 643 75/2.5" N, CP 643 90/3" N, CP 643 110/4" N, CP 643 125/5" N, CP 643 160/6" N, CP 644 200/8" and CP 644 250/10" for use in specific through -penetration firestop systems. The various suffixes for the designations of the firestop devices indicates the nominal outside diameter of the pipe (mm/in.) on which the device is intended to be installed. Have been investigated by UL in accordance with the Standard(s) indicated on this Certificate. Standard(s) for Safety: UL 1479 STANDARD FOR FIRE TESTS OF PENETRATION FIRESTOPS. CAN/ULC S115 STANDARD METHOD OF FIRE TESTS OF FIRESTOP SYSTEMS Additional Information: See the UL Online Certifications Directory at www.u1.com/database for additional information Only those products bearing the UL Certification Mark should be considered as being covered by UL's Certification and Follow -Up Service. Look for the UL Certification Mark on the product. Bruce Mahrenholz, Director North American Certification Program UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/ Page 1 of 1 86 Material Information Statement Articles According to Regulation (EC) 1907/2006, Article 32 Revision: 11.08.2021 Version: 20 1.1 Product identifier Trade name: • Firestop Bandage CFS-B / CP 646 • Firestop Plug CFS-PL / CP 658 • Firestop Back Pan Strip CFS-BPS . Firestop Plug Seal CFS-T RR / CFS-T RRS • Firestop Block CFS-BL / CFS-BL P Firestop Retrofit Sleeve CFS-SL RK • Firestop Board CP 675 Firestop Sleeve CP 645 • Firestop Boot CFS-BO Firestop Sleeve Kit CFS-SL SK • Firestop Box Insert • Firestop Speed Sleeve CFS-SL / CFS-SL GA / CP 653 • Firestop Cable Collar CFS-CC / CFS-RCC / CFS-RCC EXT • Firestop Top Track Seal CFS-TTS • Firestop Cable Module CFS-T Firestop Top Track Seal CFS-TTS MD • Firestop Cast -in device and accessories CP 680 / CP 681 / Firestop Top Track Cover CFS-TTS MD C CFS-CID / CFS-CID MD P/M/ CFS-CID MD HS GUI / CFS- Firestop Top Track Plug CFS-TTS MD P CID MD PLT W2/W3 / CFS-CID MD HS / CFS-CID ARB TE- Firestop Top Track Seal CFS-TTS 212 Y / CFS-CID ARB TE-C . Firestop Top Track Seal CFS-TTS R • Firestop Coated Board CFS-CT B / CP670 / CP673 / CP676 . Firestop Wedge Seal CFS-T WD120 • Firestop Collar CFS-C / CFS-C P . Firestop Wrap Strip CFS-W EL / SG / P / CP 648 • Firestop Collar CP 643 / CP 644 Foil Tapes CS -FT • Firestop Composite Sheet CFS-COS Intumescent fagade cavity closer CP674 • Firestop Cord CFS-CO . Joint Sealing Tapes CS-JST • Firestop Cushion CP 651 N . Mineral Wool • Firestop Drop -In Device CFS-DID . Mineral Wool Boards • Firestop Edge of Slab QuickSeal CFS-EOS QS Multifunctional Tapes CS-MFT • Firestop Endless Collar CFS-C EL Pre -coated Mineral Wool Boards • Firestop Filler Module CFS-T FB Smoke & Acoustic Track Seal CS-TTS SA • Firestop Gangplate CFS-SL GP . Speed Plug CP 777 • Firestop Module Box CFS-MB / CP 657 • Speed Strip CP 767 1.2 he li Construction industry. Refer to Hilti product literature, technical data sheets, 3rd party published listings and national approvals for specific application information. For more details, please contact your local Hilti organization through http://www.hilti.group 1.3 Manufacturer / Supplier HIM AG Feldkircherstr. 100 FL-9494 Schaan Liechtenstein Customer Service Phone +423 (0)844 84 84 85 Fax +423 (0)844 84 84 86 A Safety Data Sheet is not required due to the classification of these products as "articles" according to Regulation (EC) No. 1907/2006 of 18 December 2006 (EU) / 29CFR 1910.1200 (U.S.A.). Consequently, these products are exempted from CLP / OSHA Labeling and SIDS requirements. These data are based on our present knowledge. However, they shall not constitute a guarantee for any specific product features and shall not establish a legally valid contractual relationship. Informing department: chemicals. hseO,)hilti.com 87 Firestop Wrap Strip (CP 648-E) Product description ■ An intumescent, flexible firestop wrap strip for plastic and insulated pipe penetrations Product features ■ Highly Intumescent ■ Long length avoids waste ■ Can be continuously wrapped ■ Cost effective ■ Quick and easy closure without tools ■ Ideal for very tight installations Areas of application ■ Firestopping combustible pipe penetrations ■ Difficult applications where space is limited ■ Penetrations through concrete over metal deck ■ Plastic and insulated penetrations using PVC, CPVC, ABS, FRPP and PEX For use with ■ Concrete, masonry, wood floor and gypsum wall assemblies ■ Wall and floor assemblies rated up to 4 hours Examples ■ Waste water pipes ■ Fresh water pipes ■ Decking penetrations Installation instructions for CP 648-E Notice • Before handling, read Material Safety Data Sheet and product label for safe usage and health information. • Instructions below are general guidelines — always refer to the applicable drawing in the UL Fire Resistance Directory or Hilti Firestop Systems Guide for complete installation information Technical Data* Density CP 648-E Approx. 1.35 g/cma Dimensions (approximate) 3/16" x 1" x 33 ft or 3/16" x 1-3/4" x 33 ft Color Black with foil backing Temperature resistance -40°F to 212°F (-40°C to 100°C) Intumescent activation Approx. 320°F (160°C) Expansion ratio (unrestricted) 1:40 Tested in accordance with • UL 1479 • ASTM E 814 • ASTM G21 *At 73°F (23°C) and 50% relative humidity pSSfFyFILL, VOID OR CAVITY MATERIAL FOR USE IN THROUGH -PENETRATION GVUSSEE FM FIRESTOP SYSTEMS �179M� ,' UL FIRE RESISTANCE DIRECTORY 66Y7 APPROVED Msit fbcsystemcompatible.com. FI3 - Is a trademark of the Lubrizol Corporation. Opening 1. Clean the plastic or insulated pipe penetration. Expansion of the intumescent material during a fire closes the plastic or insulated pipe penetration. Very dirty pipes (ie: with remains of mortar) may lead to a delay in this closing action. Soiled plastic pipes or insulated pipe penetrations should, therefore, be cleaned in the area where the CP 648-E Firestop Wrap Strip is to be installed. 1. Clean penetration 2. Wrap strips around 3. Push Wrap Strips 4. Seal penetration against 5. Fasten installation plate pipe the specified number into hole smoke with FS-ONE (If required) of times Hilti Firestop Saving lives through innovation L flE and education Application of firestop system 2. Tightly wrap the required number of strips continuously around the penetrant, and hold in place with tape. 3. Push the Hilti Wrap Strip into the opening until it is flush with the substrate surface unless otherwise required by the UL system. It may be required by the UL system to clamp, wire or use a Hilti Retaining Collar to secure the wrap strip in place for some applications. 4. If the UL system requires a cold smoke seal, then apply the proper amount of Hilti FS-ONE sealant in the opening over the wrap strip. 5. For maintenance reasons, a penetration seal can be permanently marked with an identification plate and fastened in a visible position next to the seal. Not for use • In highly corrosive surroundings • With unapproved retaining collars, anchors/fasteners • Outdoors Storage • Store only in the original packaging in a location protected from moisture at temperatures between 230F and 860F (-5°C and 300C). Hilti. Outperform. Outlast. Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en espanol 1-800-879-5000 • Hilti Firestop Systems Guide 88 CERTIFICATE OF COMPLIANCE Certificate Number R13240 Report Reference R13240-20040518 Issue Date 2020-JAN UARY-22 Issued to: HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC 7250 Dallas Pky, Legacy Tower Suite 1000 Plano TX 75024 This certificate confirms that FILL, VOID OR CAVITY MATERIALS representative samples of The product covered by this Section of the Procedure is a one -part wrap strip designated as CP648-E or CP648-S. (The CP 648-S may include an optional "US" suffix.) The material is for use in through -penetration firestop systems in its final form as field installation.. Have been investigated by UL in accordance with the Standard(s) indicated on this Certificate. Standard(s) for Safety: ANSI/UL 1479, Fire Tests of Penetration Firestops CAN/ULC-S115, Standard Method of Fire Tests of Firestop Systems Additional Information: See the UL Online Certifications Directory at https://ig.uIprospector.com for additional information. This Certificate of Compliance does not provide authorization to apply the UL Mark. Only the UL Follow -Up Services Procedure provides authorization to apply the UL Mark. Only those products bearing the UL Mark should be considered as being UL Certified and covered under UL's Follow -Up Services. Look for the UL Certification Mark on the product. Bruce Mahrenholz, Director North American Certification Program UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at hftp://ul.com/aboutul/locations/ Page 1 of 1 89 Material Information Statement Articles According to Regulation (EC) 1907/2006, Article 32 Revision: 11.08.2021 Version: 20 1.1 Product identifier Trade name: • Firestop Bandage CFS-B / CP 646 • Firestop Plug CFS-PL / CP 658 • Firestop Back Pan Strip CFS-BPS . Firestop Plug Seal CFS-T RR / CFS-T RRS • Firestop Block CFS-BL / CFS-BL P Firestop Retrofit Sleeve CFS-SL RK • Firestop Board CP 675 Firestop Sleeve CP 645 • Firestop Boot CFS-BO Firestop Sleeve Kit CFS-SL SK • Firestop Box Insert • Firestop Speed Sleeve CFS-SL / CFS-SL GA / CP 653 • Firestop Cable Collar CFS-CC / CFS-RCC / CFS-RCC EXT • Firestop Top Track Seal CFS-TTS • Firestop Cable Module CFS-T Firestop Top Track Seal CFS-TTS MD • Firestop Cast -in device and accessories CP 680 / CP 681 / Firestop Top Track Cover CFS-TTS MD C CFS-CID / CFS-CID MD P/M/ CFS-CID MD HS GUI / CFS- Firestop Top Track Plug CFS-TTS MD P CID MD PLT W2/W3 / CFS-CID MD HS / CFS-CID ARB TE- Firestop Top Track Seal CFS-TTS 212 Y / CFS-CID ARB TE-C . Firestop Top Track Seal CFS-TTS R • Firestop Coated Board CFS-CT B / CP670 / CP673 / CP676 . Firestop Wedge Seal CFS-T WD120 • Firestop Collar CFS-C / CFS-C P . Firestop Wrap Strip CFS-W EL / SG / P / CP 648 • Firestop Collar CP 643 / CP 644 Foil Tapes CS -FT • Firestop Composite Sheet CFS-COS Intumescent fagade cavity closer CP674 • Firestop Cord CFS-CO . Joint Sealing Tapes CS-JST • Firestop Cushion CP 651 N . Mineral Wool • Firestop Drop -In Device CFS-DID . Mineral Wool Boards • Firestop Edge of Slab QuickSeal CFS-EOS QS Multifunctional Tapes CS-MFT • Firestop Endless Collar CFS-C EL Pre -coated Mineral Wool Boards • Firestop Filler Module CFS-T FB Smoke & Acoustic Track Seal CS-TTS SA • Firestop Gangplate CFS-SL GP . Speed Plug CP 777 • Firestop Module Box CFS-MB / CP 657 • Speed Strip CP 767 1.2 he li Construction industry. Refer to Hilti product literature, technical data sheets, 3rd party published listings and national approvals for specific application information. For more details, please contact your local Hilti organization through http://www.hilti.group 1.3 Manufacturer / Supplier HIM AG Feldkircherstr. 100 FL-9494 Schaan Liechtenstein Customer Service Phone +423 (0)844 84 84 85 Fax +423 (0)844 84 84 86 A Safety Data Sheet is not required due to the classification of these products as "articles" according to Regulation (EC) No. 1907/2006 of 18 December 2006 (EU) / 29CFR 1910.1200 (U.S.A.). Consequently, these products are exempted from CLP / OSHA Labeling and SIDS requirements. These data are based on our present knowledge. However, they shall not constitute a guarantee for any specific product features and shall not establish a legally valid contractual relationship. Informing department: chemicals. hseO,)hilti.com 90 VG E N D ical Services, Inc. e g e n d- g r o u p. c o m 88 Empire Drive • St. Paul, Minnesota • 55103 (651) 642-1150 • fax (651) 642-1239 VOC Content Test Certificate April 12, 2011 Supplier: Hilti Entwicklungsgesellschaft mbH BU Chemicals Hiltistrasse 6 86916 Kaufering GERMANY Sample Description: Hilti CP648 Sealant Strip Date Tested: April 4, 2011 Test Method: SCAQMD method 304-91 "Determination of Volatile Organic Compounds (VOC) in Various Materials" as referenced by South Coast Air Quality Management District (SCAQMD) Rule 1168. The values also comply with the requirements of EPA test method #24. Test Data: Specification Product LEED 2009 (LEED 3.0) LEED 2.2 IEQ-4.1: Low -Emitting Materials — Adhesives and Sealants Hilti CP648 Sealant Strip Green Building Council of Australia Green Star Office Design 3.0, IEQ-13 Green Star Office Design 2.0, IEQ-13 Green Star Office Interiors 1.1, IEQ-11 Architectural Sealant; VOC Limit: 250 g/L Product contains: 3.1 g/L of VOC William Welbes Vice President of Laboratory Operations Tom Barrett Senior Chemist I Firestop Wrap Strip (CP 648-S) Product description ■ A single wrap strip of intumescent, flexible firestop for use with plastic and insulated pipe penetrations Product features ■ Highly intumescent ■ Pre -measured — no cutting required ■ Integrated fastening tape ■ Cost effective ■ Quick and easy closure without tools ■ Ideal for very tight installations Areas of application ■ Firestopping combustible pipe penetrations ■ Difficult applications where space is limited ■ Penetrations through concrete over metal deck ■ Suitable for the following plastic pipe materials: PVC, CPVC, ABS, FRPP For use with ■ Concrete, masonry, wood floor and gypsum wall assemblies ■ Wall and floor assemblies rated up to 3 hours Examples ■ Waste water pipes ■ Fresh water pipes ■ Decking penetrations Installation instructions for CP 648-S Notice • Before handling, read Material Safety Data Sheet and product label for safe usage and health information. • Instructions below are general guidelines — always refer to the applicable drawing in the UL Fire Resistance Directory or Hilti Firestop Systems Guide for complete installation information Installation 1. Clean the plastic or insulated pipe penetration. Expansion of the intumescent material during a fire closes the plastic pipe. Very dirty pipes (ie: with remains of mortar) may lead to a delay in the closing action. Soiled plastic or insulated pipes should, therefore, be cleaned in the area where the CP 648-S Firestop Wrap Strip is to be installed. 2. Install Wrap Strip. First check the annular space to ensure compatibility with the appropriate UL System. Use the CP 648-S Firestop Wrap Strip corresponding to the diameter of the pipe to be installed. Wrap the CP 648-S strip around the pipe and fasten it tightly using the integrated adhesive strip. Push the CP 648-S Firestop Wrap Strip into the annular space in accordance with the UL listing. Technical Data* CP 648-S Density Approx. 1.35 g/cm3 Dimension (approximate) 1.5": 3/16" x 1" x 6-3/4" (thkns" x width" x length") 2": 3/16" x 1" x 8-1/4" 3": 3/16" x 1-3/4" x 11-1/2" 4": 3/8" x 1-3/4" x 15" 6": 1/2" x 1-3/4" x 22-1/4" Color Black with foil backing Temperature resistance -40°F to 212°F (-40°C to 100°C) Intumescent activation Approx. 320°F (160°C) Expansion ratio (unrestricted) 1:40 Tested in accordance with • UL 1479 • ASTM E 814 • ASTM G21 *At 73°F (23°C) and 50% relative humidity p$e1F6$O OR CAVITY MATERIAL F MM 4 FOR USE ION THR UG PENETRATION UFIRESTOP SYSTEMS�� U " SSEE UL FIRE RESISTANCE DIRECTORY APPROVED visa tbcsystemcompatible.com. 66Y7 `BC' is a trademark of the Lubrizol corporation. 3. Seal against smoke and gas. Seal the remaining gap with Hilti FS-ONE sealant. 4. For maintenance reasons, a penetration seal can be permanently marked with an identification plate and fastened in a visible position next to the seal. Not for use • In highly corrosive surroundings • Outdoors Storage • Store only in the original packaging in a location protected from moisture at temperatures between 23°F and 86°F (-5°C and 30oC). 1. Clean penetration 2A. Wrap the CP 648-S 26. Push the CP 648-S 3. Seal penetration against 4. Fasten installation plate Wrap Strip around Wrap Strip along the pipe smoke with FS-ONE (If required) the pipe and fasten it and into the annular space sealant. tightly with the as indicated above. adhesive strip. fl Hilti Firestop Saving lives through innovation and education Hilti. Outperform. Outlast. Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en espanol 1-800-879-5000 • Hilti Firestop Systems Guide W CERTIFICATE OF COMPLIANCE Certificate Number R13240 Report Reference R13240-20040518 Issue Date 2020-JAN UARY-22 Issued to: HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC 7250 Dallas Pky, Legacy Tower Suite 1000 Plano TX 75024 This certificate confirms that FILL, VOID OR CAVITY MATERIALS representative samples of The product covered by this Section of the Procedure is a one -part wrap strip designated as CP648-E or CP648-S. (The CP 648-S may include an optional "US" suffix.) The material is for use in through -penetration firestop systems in its final form as field installation.. Have been investigated by UL in accordance with the Standard(s) indicated on this Certificate. Standard(s) for Safety: ANSI/UL 1479, Fire Tests of Penetration Firestops CAN/ULC-S115, Standard Method of Fire Tests of Firestop Systems Additional Information: See the UL Online Certifications Directory at https://ig.uIprospector.com for additional information. This Certificate of Compliance does not provide authorization to apply the UL Mark. Only the UL Follow -Up Services Procedure provides authorization to apply the UL Mark. Only those products bearing the UL Mark should be considered as being UL Certified and covered under UL's Follow -Up Services. Look for the UL Certification Mark on the product. Bruce Mahrenholz, Director North American Certification Program UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at hftp://ul.com/aboutul/locations/ Page 1 of 1 93 Material Information Statement Articles According to Regulation (EC) 1907/2006, Article 32 Revision: 11.08.2021 Version: 20 1.1 Product identifier Trade name: • Firestop Bandage CFS-B / CP 646 • Firestop Plug CFS-PL / CP 658 • Firestop Back Pan Strip CFS-BPS . Firestop Plug Seal CFS-T RR / CFS-T RRS • Firestop Block CFS-BL / CFS-BL P Firestop Retrofit Sleeve CFS-SL RK • Firestop Board CP 675 Firestop Sleeve CP 645 • Firestop Boot CFS-BO Firestop Sleeve Kit CFS-SL SK • Firestop Box Insert • Firestop Speed Sleeve CFS-SL / CFS-SL GA / CP 653 • Firestop Cable Collar CFS-CC / CFS-RCC / CFS-RCC EXT • Firestop Top Track Seal CFS-TTS • Firestop Cable Module CFS-T Firestop Top Track Seal CFS-TTS MD • Firestop Cast -in device and accessories CP 680 / CP 681 / Firestop Top Track Cover CFS-TTS MD C CFS-CID / CFS-CID MD P/M/ CFS-CID MD HS GUI / CFS- Firestop Top Track Plug CFS-TTS MD P CID MD PLT W2/W3 / CFS-CID MD HS / CFS-CID ARB TE- Firestop Top Track Seal CFS-TTS 212 Y / CFS-CID ARB TE-C . Firestop Top Track Seal CFS-TTS R • Firestop Coated Board CFS-CT B / CP670 / CP673 / CP676 . Firestop Wedge Seal CFS-T WD120 • Firestop Collar CFS-C / CFS-C P . Firestop Wrap Strip CFS-W EL / SG / P / CP 648 • Firestop Collar CP 643 / CP 644 Foil Tapes CS -FT • Firestop Composite Sheet CFS-COS Intumescent fagade cavity closer CP674 • Firestop Cord CFS-CO . Joint Sealing Tapes CS-JST • Firestop Cushion CP 651 N . Mineral Wool • Firestop Drop -In Device CFS-DID . Mineral Wool Boards • Firestop Edge of Slab QuickSeal CFS-EOS QS Multifunctional Tapes CS-MFT • Firestop Endless Collar CFS-C EL Pre -coated Mineral Wool Boards • Firestop Filler Module CFS-T FB Smoke & Acoustic Track Seal CS-TTS SA • Firestop Gangplate CFS-SL GP . Speed Plug CP 777 • Firestop Module Box CFS-MB / CP 657 • Speed Strip CP 767 1.2 he li Construction industry. Refer to Hilti product literature, technical data sheets, 3rd party published listings and national approvals for specific application information. For more details, please contact your local Hilti organization through http://www.hilti.group 1.3 Manufacturer / Supplier HIM AG Feldkircherstr. 100 FL-9494 Schaan Liechtenstein Customer Service Phone +423 (0)844 84 84 85 Fax +423 (0)844 84 84 86 A Safety Data Sheet is not required due to the classification of these products as "articles" according to Regulation (EC) No. 1907/2006 of 18 December 2006 (EU) / 29CFR 1910.1200 (U.S.A.). Consequently, these products are exempted from CLP / OSHA Labeling and SIDS requirements. These data are based on our present knowledge. However, they shall not constitute a guarantee for any specific product features and shall not establish a legally valid contractual relationship. Informing department: chemicals. hseO,)hilti.com 94 VG E N D ical Services, Inc. e g e n d- g r o u p. c o m 88 Empire Drive • St. Paul, Minnesota • 55103 (651) 642-1150 • fax (651) 642-1239 VOC Content Test Certificate April 12, 2011 Supplier: Hilti Entwicklungsgesellschaft mbH BU Chemicals Hiltistrasse 6 86916 Kaufering GERMANY Sample Description: Hilti CP648 Sealant Strip Date Tested: April 4, 2011 Test Method: SCAQMD method 304-91 "Determination of Volatile Organic Compounds (VOC) in Various Materials" as referenced by South Coast Air Quality Management District (SCAQMD) Rule 1168. The values also comply with the requirements of EPA test method #24. Test Data: Specification Product LEED 2009 (LEED 3.0) LEED 2.2 IEQ-4.1: Low -Emitting Materials — Adhesives and Sealants Hilti CP648 Sealant Strip Green Building Council of Australia Green Star Office Design 3.0, IEQ-13 Green Star Office Design 2.0, IEQ-13 Green Star Office Interiors 1.1, IEQ-11 Architectural Sealant; VOC Limit: 250 g/L Product contains: 3.1 g/L of VOC William Welbes Vice President of Laboratory Operations Tom Barrett Senior Chemist I High-performance intumescent firestop sealant FS-ONE MAX Applications ■ For effectively sealing most common through penetrations in a variety of base materials ■ For use on concrete, masonry and drywall ■ Mixed and multiple penetrations ■ Metal pipe penetrations: copper, steel and EMT ■ Insulated metal pipe penetrations: steel and copper ■ Plastic pipe penetrations: closed or vented Advantages ■ US -produced: "Buy American" compliant ■ One product for a variety of common through penetrations ■ Cost-effective, easy -to -use solution ■ Water -based and paintable ■ Industry -leading VOC results ■ Ethylene glycol -free FBG .,.�} SYSTEM COMPATIBLE ' c-A Chemical Mold and mildew resistant resistant pSSIF�F FILL, VOID OR CAVITY MATERIAL o FOR USE IN THROUGH -PENETRATION W llll� F M FIRESTOP SYSTEMS c OS FIRE RESISTANCE DIRECTORY V.S APPROVED SEE UL `"' s6Y7 Intertek Order Designation FS-ONE MAX 20oz foil (3 case + disp) FS-ONE MAX 1Ooz tube (1 case) FS-ONE MAX 5 gallon (18 pails) FS-ONE MAX 20oz foil (1 case) FS-ONE MAX 20oz foil (3 cases) FS-ONE MAX 20oz Foil -Pallet FS-ONE MAX 10 oz cartridge FS-ONE MAX 5 gallon pail Technical data Chemical basis Water -based acrylic dispersion Approx. Density 84.3 Ib/ft3 Color Red Application temperature range 41 - 104 OF Approx. cure time') 4 mm/3 days Temperature resistance range -4 to 212 OF Mold and mildew performance Class 0 (ASTM G21-96) Mold and mildew resistance Yes Surface burning characteristics UL 723 (ASTM E84) Flame spread: 0 Smoke development: 10 Tested in accordance with UL 1479, ASTM E814, ASTM E84, CAN/ ULC-S115, ASTM G21, ASTM E90 California State fire marshal approval CSFM Listing 4485-1200:0108 for FS-ONE MAX Intumescent Firestop Sealant Expansion ratio (unrestricted, up to) 1:5 11 at 75°F/24°C, 50% relative humidity Package Content Item number 1x Foil pack dispenser manual CS 270-P1, 75x Firestop sealant FS-ONE MAX 20 oz foil 3530252 12x Firestop sealant FS-ONE MAX 10 oz cartridge 3530249 18x Firestop sealant FS-ONE MAX 5 gallon pail 3530263 25x Firestop sealant FS-ONE MAX 20 oz foil 3530250 75x Firestop sealant FS-ONE MAX 20 oz foil 3530251 600x FSONE-MAX 20 oz foil, 290x Bulk Shipping Condition 3534713 2101531 m 2101533 �2 N Hilti. Outperform. Outlast. 1113 LOU ru Hilti, Inc. (USA) 1-800-879-8000 1 www.us.hilti.com I en espanol 1-800-879-5000 1 Hilti (Canada) Corp. 1-800-363-4458 1 www.hilti.ca CERTIFICATE OF COMPLIANCE Certificate Number Report Reference Issue Date 20150108-R13240 R13240 2015-January-08 Issued to: Hilti Construction Chemicals, Div of Hilti Inc. 5400 S 122"d East Ave Tulsa, OK 74146 This is to certify that Fill, Void or Cavity Materials representative samples of Fill, Void or Cavity Materials Certified for Canada FS-ONE MAX Intumescent Sealant for use in Through - Penetration Firestop and Joint Systems in the UL Fire Resistance Directory and in the Products Certified for Canada Directory. Have been investigated by UL in accordance with the Standard(s) indicated on this Certificate. Standard(s) for Safety: ANSI/UL 1479, "Fire Tests of Through -Penetration Firestops," — Edition 4 ANSI/UL 2079, "Tests for Fire Resistance of Building Joint Systems," — Edition 4 — Revision Date 2014/12/17 CAN/ULC-S115, "Standard Method of Fire Tests of Firestop Systems." — Edition 4 — Issue Date 2011/06/01 Additional Information: See the UL Online Certifications Directory at www.ul.com/database for additional information Only those products bearing the UL Classification Mark should be considered as being covered by UL's Classification and Follow -Up Service. The UL Classification Mark includes: UL in a circle: with the word "CLASSIFIED" 0 (as shown); a control number (may be alphanumeric) assigned by UL; a statement to indicate the extent of UL's evaluation of the product; and the product category name (product identity) as indicated in the appropriate UL Directory. Look for the UL Classification Mark on the product. ,4 ,► If L"7 William R. Carney, Director, North American Certification Programs UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at www.ul.com/contactus Page 1 of 1 97 FS-ONE MAX; CFS-FIL Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations Date of issue: 07/04/2017 Revision date: 07/04/2017 Supersedes: 12/17/2015 1.1. Identification Product form Name Product code Chemical structure Mixture FS-ONE MAX; CFS-FIL BU Fire Protection Am Version: 1.3 0. Relevant identified uses of the substance or mixture and uses advised against No additional information available 1.3. Details of the supplier of the safety Hilti, Inc. Legacy Tower, Suite 1000 75024 Plano - USA T +1 9724035800 1-800-879-8000 toll free - F +1 918 254 0522 Supplier Hilti, Inc. Legacy Tower, Suite 1000 75024 Plano - USA T +1 9724035800 1-800-879-8000 toll free - F +1 918 254 0522 1.4. Emergency telephone number Department issuing data specification sheet Hilti AG Feld ki rcherstrage 100 9494 Schaan - Liechtenstein T +423 234 2111 chem icals. hse(a)h i Iti.com Emergency number Chem-Trec Tel.: 1 800 424 9300 (USA, PR, Virgin Islands, Canada) Tel.: 703 527 3887 (Other countries) +1 918 8723000 1-800-879-8000 toll free 2.1. Classification of the substance or GHS-US classification Not classified 2.2. Label elements GHS-US labelling No labelling applicable 2.3. Other hazards No additional information available 2.4. Unknown acute toxicity (GHS US) Not applicable 05/07/2017 US -OSHA - en 1/7 98 FS-ONE MAX; CFS-FIL Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations 3.1. Substance - Not applicable 1&2• Name Product identifier % GHS-US classification Quartz (cas No) 14808-60-7 2.5 - 5 Carc. 1A, H350 Full text of H-statements: see section 16 4.1. Description of first aid measures First -aid measures after inhalation Get medical advice/attention if you feel unwell. First -aid measures after skin contact Wash skin with plenty of water. If skin irritation occurs: Get medical advice/attention. First -aid measures after eye contact Rinse cautiously with water for several minutes. Remove contact lenses, if present and easy to do. Continue rinsing. If eye irritation persists: Get medical advice/attention. First -aid measures after ingestion Get medical advice/attention if you feel unwell. 4.2. Most important symptoms and effects, both acute and delayed No additional information available 10. Ind icatio ediate medical attention and special treatme No additional information available 5.1. Extinguishing media Suitable extinguishing media Water spray. Dry powder. Foam. Carbon dioxide. 5.2. Special hazards arising from the substance or mixture Reactivity The product is non -reactive under normal conditions of use, storage and transport. 5.3. Advice for firefighters Protection during firefighting Self-contained breathing apparatus. Complete protective clothing. ctive equipment and emergency procedures 6.1.1. For non -emergency personnel No additional information available 6.1.2. For emergency responders Protective equipment For further information refer to section 8: "Exposure controls/personal protection". 6.2. Environmental precautions No additional information available 6.3. Methods and material for containment and cleaning up � Methods for cleaning up Mechanically recover the product. 6.4. Reference to other sections For further information refer to section 13. 05/07/2017 US -OSHA - en 2/7 99 FS-ONE MAX; CFS-FIL Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations &LPrecautions for safe handling Precautions for safe handling Wear personal protective equipment. Hygiene measures Wash contaminated clothing before reuse. Do not eat, drink or smoke when using this product. Always wash hands after handling the product. 7.2. Conditions for safe storage, including any incompatibilities W Storage conditions Keep cool. Store in a dry place. Storage temperature 41 - 77 °F 8.1. Control parameters Quartz (14808-60-7) OSHA Remark (OSHA) (3) See Table Z-3. Additional information The product has a pasty consistency. Exposure limit values for respirable dusts are not relevant for this product 8.2. Exposure controls MIL Personal protective equipment Protective clothing. Safety glasses. Gloves. 00 Hand protection Protective gloves. EN 374. Eye protection Chemical goggles or safety glasses. Skin and body protection Wear suitable protective clothing. 9.1. Information on basic physical and chemical properties Physical state Liquid Appearance Pasty. Colour red Odour characteristic Odour threshold Not determined pH = 7.85 Melting point Not applicable Freezing point No data available Boiling point No data available Flash point Not applicable Relative evaporation rate (butylacetate=1) No data available Flammability (solid, gas) No data available Explosive limits No data available Explosive properties No data available Oxidising properties No data available Vapour pressure No data available Relative density No data available Relative vapour density at 20 °C No data available 05/07/2017 US -OSHA - en 3/7 100 FS-ONE MAX; CFS-FIL Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations Density = 1.35 g/cm' Molecular mass Not determined Solubility No data available Log Pow No data available Auto -ignition temperature No data available Decomposition temperature No data available Viscosity No data available Viscosity, kinematic No data available Viscosity, dynamic No data available n VOC content 9 g/I 10.1. Reactivity The product is non -reactive under normal conditions of use, storage and transport. 10.2. Chemical stability Stable under normal conditions. 10.3. Possibility of hazardous reactions No dangerous reactions known under normal conditions of use. 10.4. Conditions to avoid None under recommended storage and handling conditions (see section 7). 10.5. Incompatible material No additional information available WA Hazardous decomposi Under normal conditions of storage and use, hazardous decomposition products should not be produced. 11.1. Information on toxicological effects Acute toxicity Not classified Skin corrosion/irritation Not classified pH: = 7.85 Serious eye damage/irritation Not classified pH: = 7.85 r J Respiratory or skin sensitisation Not classified Germ cell mutagenicity Not classified Carcinogenicity Not classified Quartz (14808-60-7) IARC group 1 - Carcinogenic to humans Reproductive toxicity Not classified Specific target organ toxicity (single exposure) Not classified Specific target organ toxicity (repeated Not classified exposure) 05/07/2017 US -OSHA - en 4/7 101 FS-ONE MAX; CFS-FIL Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations Aspiration hazard 12.1. Toxicity Ecology - general 12.2. Persistence and degradability No additional information available 12.3. Bioaccumulative potential No additional information available No additional information available F2.5. Other adverse effects Effect on the global warming 13.1. Waste treatment methojs Waste treatment methods Waste disposal recommendations In accordance with ADR / RID / IMDG / IATA / ADN Not classified The product is not considered harmful to aquatic organisms nor to cause long-term adverse effects in the environment. No known effects from this product. Dispose of contents/container in accordance with licensed collector's sorting instructions. Dispose in a safe manner in accordance with local/national regulations. • D - IMDG IATA RID UN number Not regulated for transport 14.2. UN proper shipping name Not applicable INot applicable Not applicable Not applicable 14.3. Transport hazard class es Not applicable Not applicable Not applicable Not applicable Not applicable Not applicable Not applicable Not applicable 14.4. Packing group Not applicable Not applicable Not applicable Not applicable 14.5. Environmental hazards Dangerous for the environment : No Dangerous for the environment : No Marine pollutant: No Dangerous for the environment : No Dangerous for the environment No No supplementary information available 05/07/2017 US -OSHA - en 5/7 102 FS-ONE MAX; CFS-FIL Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations 14.6. Special precautions for user - Overland transport - Transport by sea No data available - Air transport No data available - Rail transport Carriage prohibited (RID) No 14.7. Transport in bulk according to Annex II of MARPOL 73/78 and the IBC Code 15.1. US Federal regulations All components of this product are listed, or excluded from listing, on the United States Environmental Protection Agency Toxic Substances Control Act (TSCA) inventory 15.2. International regulations CANADA FS-ONE MAX; CFS-FIL WHMIS Classification Uncontrolled product according to WHMIS classification criteria EU-Regulations No additional information available Classification according to Regulation (EC) No. 1272/2008 [CLP] Not classified National regulations Quartz (14808-60-7) Listed on IARC (International Agency for Research on Cancer) 15.3. US State regulations California Proposition 65 - This product does not contain any substances known to the state of California to cause cancer, developmental and/or reproductive harm Revision date 07/04/2017 Full text of H-statements: H350 I May cause cancer 05/07/2017 US -OSHA - en 6/7 103 FS-ONE MAX; CFS-FIL Safety Data Sheet according to Federal Register / Vol. 77, No. 58 / Monday, March 26, 2012 / Rules and Regulations NFPA health hazard 0 - Materials that, under emergency conditions, would offer no hazard beyond that of ordinary combustible materials. NFPA fire hazard 0 - Materials that will not burn under typical dire conditions, including intrinsically noncombustible materials such as concrete, stone, and sand. NFPA reactivity 0 - Material that in themselves are normally stable, even under fire conditions. Hazard Rating Health 0 Minimal Hazard - No significant risk to health Flammability 0 Minimal Hazard - Materials that will not burn Physical 0 Minimal Hazard - Materials that are normally stable, even under fire conditions, and will NOT react with water, polymerize, decompose, condense, or self -react. Non -Explosives. Personal protection B - Safety glasses, Gloves SDS US Hilti This information is based on our current knowledge and is intended to describe the product for the purposes of health, safety and environmental requirements only. It should not therefore be construed as guaranteeing any specific property of the product 05/07/2017 US -OSHA - en 7/7 104 June 17, 2019 To Whom It May Concern: Re: Hilti FS-ONE Max Firestop — LEED Info. Item Numbers: 2101531 2101532 2101533 The Hilti FS-ONE MAX Firestop is manufactured in the United States There is no post -consumer or post-industrial recycled content in FS-ONE MAX and it cannot be recycled. The VOC content for FS-ONE MAX is 9 grams/liters. FS-ONE MAX is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non - regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state regulatory agencies for direction on disposal. Please feel free to contact me at (918) 872-3704 if you have questions Sincerely, Jerry Metcalf MPH, CHMM Sr. Manager, Safety/Environmental Hilti Inc (918) 872 3704 ierry.metcalf(a)hilti.com Rev. Date: 5/30/19 The manufacturing plant location on this certificate has been provided for LEED reporting purposes only. It should never be used for Country of Origin certification or a representation of compliance/non-compliance with Buy American or Buy America requirements, as those requirements differ. The manufacturing plant location(s) identified on the certificate represent standard Hilti catalog products only. "Specially" produced non -catalog Hilti products may have differing manufacturing plant locations. Contact your Hilti representative in cases of "specially" produced products for a custom LEED certificate. Hilti, Inc. 5400 South 122n1 East Avenue Tulsa, OK 74146 1-800-879-8000 www.hilti.com 105 Product Information FIRESTOP BOX INSERT Product description An intumescent insert designed for easy installation inside of outlet and switch boxes to help protect fire -rated assemblies Product features No expiration date alleviates shelf life concerns Fast installation thru self adhesive back Applied by hand, no tools required Easy installation access from outside the wall ram• Areas of application Electrical outlet and switch boxes For use with Gypsum wall assemblies with metal or wood studs In accordance with Hilti's (CLIV "LIL classification code") approval, when the Firestop Box Inserts are installed on boxes on both sides of a wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back to back. Examples Renovation projects applications, where only the interior of box is accessible Installation instructions See Hilti Literature or third -party listings for complete application and installation details 0 Technical Data o p00 C 1 US L WALL OP NING MATER A OTECTIVE FIRE RESISTANCE CLASSIFICATION SEE PRODUCT CATEGORY IN Dimensions 1 13/16" x 2-13/16" x 1/4" (for use with 2" x 4" boxes) UL FIRE RESISTANCE DIRECTORY 66Y7 3-11/16" x 3-3/4" x 1/4" (for use with 4" x 4" boxes) 4-3/8" x 4-3/8" x 1/4" (for use with 4-11/16" x 4-11/16" boxes) 4e> Color Black APPROVED Surface burning characteristics (ASTM E 84) Flame Spread: 5 Smoke development: 5 Tested in accordance with ASTM E 84, ASTM E 119 / UL 263, ASTM E 90 (Sound transmission classification 53') Notice about approvals Hilti Firestop Box Insert is classified by Underwriters' Laboratories, Inc. as a "Wall Openings Protecting Material." Specific requirements should be consulted in the UL Fire Resistance Directory Volume 1 or Hilti documentation Not for use In areas under water Safety precautions • Before handling, read the product Safety Data Sheet for detailed use and health information • Wear suitable gloves and eye protection • Keep out of the reach of children Storage Store only in the original packaging in a location at temperatures 40oF (5°C) to 104°F (40oC) ` U411 Wall Assembly r Hilti Firestop Saving lives \ through innovation l and education m Hilti, Inc. (U.S.) Hilti (Canada) Corporation 1-17-071 1-800-879-8000 1 en espahol1-800-879-5000 1-800-363-4458 © Q www.hilti.com www.hilti.ca Tune 106 Certificate Number 20080325-R13240 Report Reference 2008 March 25 Issue Date 2008 March 25 Issued to: Hilti, Inc. 5400 S 122ND East Ave Tulsa, OK 74146 USA This is to certify that Hilti Firestop Box Insert representative samples of Wall Opening Protective Materials Page 1 of 1 VUnderwriters L Laboratories Inca Have been investigated by Underwriters Laboratories Inc.© (UL) or any authorized licensee of UL in accordance with the Standards) indicated on this Certificate. Standard(v) for Safety: ANSI/UL 263, Thirteenth Edition, "Fire Tests of Building Construction and Materials. CAN/ULC-S101-04, "Standard Method of Fire Endurance Tests of Building Construction and Materials." Additional 111 formation: Hilti Firestop Box Insert for use in fire -resistance designs as detailed in the UL Fire Resistance Directory. Only those products bearing the UL Classification Mark should be considered as being covered by UL's Classification and Follow -Up Service. 4*6 The UL Classification Mark includes: UL in a circle symbol: ® with the word "CLASSIFIED" (as shown); a control number (may be alphanumeric) assigned by UL; a statement to indicate the extent of UL's evaluation of the product; and, the product category naive (product identity) as indicated in the appropriate UL Directory. Look for the UL Classification Mark on the product Is ue by: Reviewed by: Mo ra Couloute teve l4offm Underwriters Laboratories Inc Underwriters Laboratories Inc. 107 Material Information Statement Articles According to Regulation (EC) 1907/2006, Article 32 Revision: 11.08.2021 Version: 20 1.1 Product identifier Trade name: • Firestop Bandage CFS-B / CP 646 • Firestop Plug CFS-PL / CP 658 • Firestop Back Pan Strip CFS-BPS . Firestop Plug Seal CFS-T RR / CFS-T RRS • Firestop Block CFS-BL / CFS-BL P Firestop Retrofit Sleeve CFS-SL RK • Firestop Board CP 675 Firestop Sleeve CP 645 • Firestop Boot CFS-BO Firestop Sleeve Kit CFS-SL SK • Firestop Box Insert • Firestop Speed Sleeve CFS-SL / CFS-SL GA / CP 653 • Firestop Cable Collar CFS-CC / CFS-RCC / CFS-RCC EXT • Firestop Top Track Seal CFS-TTS • Firestop Cable Module CFS-T Firestop Top Track Seal CFS-TTS MD • Firestop Cast -in device and accessories CP 680 / CP 681 / Firestop Top Track Cover CFS-TTS MD C CFS-CID / CFS-CID MD P/M/ CFS-CID MD HS GUI / CFS- Firestop Top Track Plug CFS-TTS MD P CID MD PLT W2/W3 / CFS-CID MD HS / CFS-CID ARB TE- Firestop Top Track Seal CFS-TTS 212 Y / CFS-CID ARB TE-C . Firestop Top Track Seal CFS-TTS R • Firestop Coated Board CFS-CT B / CP670 / CP673 / CP676 . Firestop Wedge Seal CFS-T WD120 • Firestop Collar CFS-C / CFS-C P . Firestop Wrap Strip CFS-W EL / SG / P / CP 648 • Firestop Collar CP 643 / CP 644 Foil Tapes CS -FT • Firestop Composite Sheet CFS-COS Intumescent fagade cavity closer CP674 • Firestop Cord CFS-CO . Joint Sealing Tapes CS-JST • Firestop Cushion CP 651 N . Mineral Wool • Firestop Drop -In Device CFS-DID . Mineral Wool Boards • Firestop Edge of Slab QuickSeal CFS-EOS QS Multifunctional Tapes CS-MFT • Firestop Endless Collar CFS-C EL Pre -coated Mineral Wool Boards • Firestop Filler Module CFS-T FB Smoke & Acoustic Track Seal CS-TTS SA • Firestop Gangplate CFS-SL GP . Speed Plug CP 777 • Firestop Module Box CFS-MB / CP 657 • Speed Strip CP 767 1.2 he li Construction industry. Refer to Hilti product literature, technical data sheets, 3rd party published listings and national approvals for specific application information. For more details, please contact your local Hilti organization through http://www.hilti.group 1.3 Manufacturer / Supplier HIM AG Feldkircherstr. 100 FL-9494 Schaan Liechtenstein Customer Service Phone +423 (0)844 84 84 85 Fax +423 (0)844 84 84 86 A Safety Data Sheet is not required due to the classification of these products as "articles" according to Regulation (EC) No. 1907/2006 of 18 December 2006 (EU) / 29CFR 1910.1200 (U.S.A.). Consequently, these products are exempted from CLP / OSHA Labeling and SIDS requirements. These data are based on our present knowledge. However, they shall not constitute a guarantee for any specific product features and shall not establish a legally valid contractual relationship. Informing department: chemicals. hseO,)hilti.com 108 August 26, 2015 To Whom It May Concern: Re: The Hilti Firestop Box Insert — LEED Information Item Numbers: 3416772 3417183 3417184 The Hilti Firestop Box Inserts are manufactured in Texas. The Hilti Firestop Box Inserts have a VOC content of 1.9 grams/liter The amount of post -consumer or post-industrial content in Hilti Firestop Box Inserts is not known. The packaging is recyclable. The Hilti Firestop Box Inserts do not contain any Rapidly Renewable Materials. The Hilti Firestop Box Inserts are not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non -regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state regulatory agencies for direction on disposal. Please feel free to contact me at (918) 872-3704 if you have questions Sincerely, y rA Jerry Metcalf MPH, CHMM Sr. Manager, Safety/Environmental Hilti Inc. (918) 872 3704 0errv.metcalf(a-)h ilti.com Rev. Date: 8/14/15 The manufacturing plant location on this certificate has been provided for LEEDS reporting purposes only. It should never be used for Country of Origin certification or a representation of compliance/non-compliance with Buy American or Buy America requirements, as those requirements differ. The manufacturing plant location(s) identified on the certificate represent standard Hilti catalog products only. "Specially" produced non -catalog Hilti products may have differing manufacturing plant locations. Contact your Hilti representative in cases of "specially" produced products for a custom LEEDS certificates. Hilti, Inc. 5400 South 122"d East Avenue Tulsa, OK 74146 1-800-879-8000 www.hilti.com 109