FIR2023-0093_Fire_Sprinkler_Equipment_Specification_Sheets_9.21.2023_1.39.08_PM_3797336Bulletin 074 January 2023
Rel
® F1 FR56 Series
Quick Response Sprinklers
K-factor 5.6 (80)
Features
• Standard coverage quick -response sprinklers
• Upright, pendent, horizontal sidewall, and vertical sidewall
deflectors
• Low profile, compact design
• Available in a wide variety of finishes
Product Description
Reliable Model F1 FR56 series sprinklers are quick -response
standard spray automatic fire sprinklers utilizing a sensitive 3.0
mm glass bulb thermal element.
Pendent and horizontal sidewall sprinklers may be installed
exposed or surface mounted using escutcheons such as the
Reliable Models B, C, or HB (reference Technical Bulletin 204).
When installed recessed or concealed, the Model F1 FR56 series
sprinklers are specifically listed with and may only be installed
with listed Reliable escutcheons and cover plates. Refer to the
technical information on the following pages for specific listings
for recessed and concealed installations and refer to Figures 5
and 6 for dimensional information.
When fitted with an approved water shield, these sprinklers may
considered intermediate sprinklers for use in racks, below grated
walkways, and other areas where intermediate level sprinklers are
required.
Table A provides a summary of the approvals and availability of
specific Model F1 FIR series sprinkler configurations. Additional
technical information for each sprinkler model is provided on the
following pages.
F1 FR Series Sprinkler Summary
Model F1 FR56 Pendent Model F1 FR56 Upright
Model F1 FR56 Vertical Sidewall Model F1 FR56
Horizontal Sidewall
Note: Not all versions of the product are shown.
Note: This bulletin may contain information on New and Legacy
sprinklers that reflects a dimensional change only. Sprinkler Iden-
tification Number (SIN), application, performance, and listings/
approval are not otherwise affected. Sprinklers with New frames
will include the suffix "N" in the order.
Sprinkler
K-Factor gpm/psi'/2
Orientation
Listings & Approvals
Max. Working Pressure
Sprinkler
Identification
Model
(Ipm/bar'/2)
psi (bar)
Number (SIN)
Upright
cULus, FM, _PCB, VdS,
175 (12)
RA1425
Intermediate Upright
EC, WM, UKCA
250 (17) (cULus only)
Pendent
cULus, FM, LPCB, VdS,
175 (12)
RA1414
EC, WM, UKCA
250 (17) (cULus only)
Concealed Pendent
cULus, VdS, EC, WK
175 (12)
RA1414
F1 FR56
5.6(80)
UKCA
250 (17) (cULus only)
Horizontal Sidewall
cULus, FIV
175 (12)
250 (17) (cULus only)
RA1435
Vertical Sidewall
cULus, FM, LPCB,
175 (12)
RA1485
UKCA
www.reliablesprinkler.com
Technical Specifications
Style: Upright, Intermediate Upright
Threads: 112" NPT or ISO 7-R1/2
Nominal K-Factor: 5.6 (80 metric)
Max. Working Pressure:
175 psi (12 bar)
250 psi (17 bar) (cULus only)
Material Specifications
Thermal Sensor: 3 mm Glass Bulb
Sprinkler Frame: Brass Alloy
Cap: Bronze Alloy
Sealing Washer: Nickel with PTFE
Load Screw: Copper Alloy
Deflector: Brass Alloy
Sprinkler Finishes
(See Table B)
Sensitivity
Quick response
Temperature Ratings
135°F (57°C)
155°F (68°C)
175°F (79°C)
200-F(93°C)
286°F (141°C)
Guards & Shields (New Frames)
Factory Water Shield (cULus, FM)
F-1 Guard (cULus, FM)
F-3 Guard with Shield (cULus, FM)
Guards and Shields (Legacy Frames)
Factory Water Shield
C-1 Guard (FM)
C-3 Guard with Shield (cULus, FM)
D-1 Guard (cULus)
D-3 Guard with Shield (cULus)
Sprinkler Wrench
Model W2
Model J (New frame with guard installed)
Model JD (Legacy frame with guard
installed)
Listings and Approvals
cULus Listed
FM Approved
-PCB
VdS
EC
WM
U KCA: 0832-U KCA-CPR-S5045
Model F1 FR56 Upright Sprinkler Components and Dimensions
Deflector
Glass Bull
(3 mm
Wrench FIB
Threads
-�d Screw
F1FR-HALF-UPR-INT
Cap/Seal Assem
3 1/4" [83mm]
Shown with Optional
Factory Installed Water Shield
( Intermediate Upright)
mm]
Bulletin 074 Reliable Page 2 of 9
January 2023 www.reliablesprinkler.com
Technical Specifications
Style:
Pendent
Recessed Pendent
Concealed Pendent
Threads: 1/2" NPT or ISO 7-R1/2
Nominal K-Factor: 5.6 (80 metric)
Max. Working Pressure:
175 psi (12 bar)
250 psi (17 bar) (cULus only)
Material Specifications
Thermal Sensor: 3 mm Glass Bulb
Sprinkler Frame: Brass Alloy
Cap: Bronze Alloy
Sealing Washer: Nickel with PTFE
Load Screw: Copper Alloy
Deflector: Brass Alloy
Sprinkler Finishes
(See Table B)
Sensitivity
Quick response
Temperature RatingsM
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F(93°C)
286°F (141°C)
Recessed Escutcheons
Model F1 (cULus, LPCB, VdS, CE, WM)
Model F2 (cULus, FM, LPCB, VdS, CE,
WM)
Model FP (cULus, VdS, CE, WM)
Cover Plate
Model CCP (cULus, VdS(2), CE(2))
Guards & Shields (New Frames)(')
F-1 Guard (FM)
F-5 Guard/Shield Kit (FM)
F-7 Guard (cULus)
F-8 Guard/Shield Kit (cULus)
S-1 Shield (cULus, FM)
Guards & Shields (Legacy Frames)(')
C-1 Guard (FM)
C-5 Guard/Shield Kit (FM)
D-1 Guard (cULus, FM)
D-4 Guard/Shield Kit (FM)
D-5 Guard/Shield Kit (cULus, FM)
S-1 Shield (cULus, FM)
Sprinkler Wrenches
Model W2 (pendent)
Model W4 (recessed or concealed)
Model J (New frame with guard installed)
Model JD (Legacy frame with guard
installed)
Listings and Approvals(4)
cULus Listed
FM Approved
LPCB
VdS
EC
WM
U KCA: 0832-U KCA-CPR-S 5045,
0831-UKCA-CPR-5072 (CCP)
Notes:
1. 286°F (141 °C) temperature rated sprinkler not listed for recessed or concealed use.
2. VdS and CE approval for CCP concealed use is for 155°C (68°C) sprinkler ONLY.
3. Not suitable for recessed or concealed pendent installations.
4. When used surface mounted or exposed. See Recessed Escutcheon and Cover Plate section for specific approvals when installed recessed or concealed.
Model F1 FR56 Pendent Sprinkler Components and Dimensions
Threads
Wrench Flat
Glass Bulb
(3 mm)
Deflector
F1FR_HALF _PEND_INT
Cap/Seal
Assembly
— Screw
Note: Please refer to Figure 8 for recessed and concealed installation.
3 1/4" [83mm]
Sit
2 1/4" [57mm]
1" [25mm]
Shown with Optional S-1 Water
Shield (Ordered Separately)
Bulletin 074 Reliable Page 3 of 9
January 2023 www.reliablesprinkler.com
Technical Specifications
Style:
Horizontal Sidewall
Recessed Horizontal Sidewall
Threads: 1/2" NPT or ISO 7-R1/2
Nominal K-Factor: 5.6 (80 metric)
Max. Working Pressure:
175 psi (12 bar)
250 psi (17 bar) (cULus only)
Material Specifications
Thermal Sensor: 3 mm Glass Bulb
Sprinkler Frame: Brass Alloy
Cap: Bronze Alloy
Sealing Washer: Nickel with PTFE
Load Screw: Copper Alloy
Deflector: Brass Alloy
Sprinkler Finishes
(See Table B)
Sensitivity
Quick response
Temperature Ratings
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F(93°C)
286°F (141°C)
Recessed Escutcheons(2)
Model F1 (cULus)
Model F2 (cULus, FM)
Model FP (cULus)
Guards & Shields (New Frames)(3)
F-4 Guard (FM)
F-7 Guard (cULus)
Guards & Shields (Legacy Frames)(')
C1 Guard (FM)
D1 Guard (cULus)
Sprinkler Wrenches
Model W2 (non -recessed)
Model W4 (recessed)
Model J (New frame with guard installed)
Model JD (Legacy frame with guard
installed)
Listings and Approvals
cULus Listed(4)
FM Approved(')
Notes:
1. 286°F (141 °C) temperature rated sprinkler not listed for recessed use.
2. FM approved recessed installation when used with Model F2 escutcheon ONLY.
3. Not suitable for recessed horizontal sidewall installations.
4. cULus Listed for Light and Ordinary Hazard when installed exposed or surface mounted
installed recessed.
5. FM Approved for Light Hazard ONLY.
Model F1 FR56 Horizontal Sidewall Sprinkler Components and Dimensions
Deflector
Glass Bul
(3 mn
Wrench R
Note: Please refer to Figure 9 for recessed installation.
iad Screw
Frame
F1FR_HALF_HSW
Cap/Seal Assembly
Threads
Listed for Light Hazard ONLY when
1 1/8" [28mm]
2 3/4" [70mm]
Bulletin 074 Reliable Page 4 of 9
January 2023 www.reliablesprinkler.com
Technical Specifications
Style:
Upright Vertical Sidewall
Pendent Vertical Sidewall
Threads: 1/2" NPT or ISO 7-R1/2
Nominal K-Factor: 5.6 (80 metric)
Max. Working Pressure: 175 psi (12 bar)
Material Specifications
Thermal Sensor: 3 mm Glass Bulb
Sprinkler Frame: Brass Alloy
Cap: Bronze Alloy
Sealing Washer: Nickel with PTFE
Load Screw: Copper Alloy
Deflector: Brass Alloy
Sprinkler Finishes
(See Table B)
Sensitivity
Quick response
Temperature Ratings
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F(93°C)
286°F (141°C)
Guards & Shields (New Frames)
F-2 Guard (FM)
Guards & Shields (Legacy Frames)
C1 Guard (FM)
Sprinkler Wrenches
Model W2
Model J (New frame with guard installed)
Model JD (Legacy frame with guard
installed)
Listings and Approvals0)
cULus Listed
FM Approved
LPCB(2)
UKCA:0832-UKCA-CPR-S5045
Notes:
1. Listed and approved for Light Hazard ONLY.
2. LPCB approved for use in pendent position ONLY.
Model F1 FR56 Vertical Sprinkler Components and Dimensions • -
Deflector
Glass Bulb
(3 mm)
Wrench Flat
-- 1 Screw
Frame
F1FR_HALF_VSW
Cap/Seal Assembly
Threads
1 1/2" [38mm]
2 1/4" [57mm]
RA CCU
Bulletin 074 Reliable Page 5 of 9
January 2023 www.reliablesprinkler.com
Recessed and Concealed Installation: Pendent Sprinklers
2-1/4"
2-1/4"
(57 mm) Dia.
(57 mm) Dia.
Hole in Ceiling
Hole in Ceiling
1-15/16"
1-15/16"
(49 mm) Dia.
Reducing
(49 mm) Dia.
Reducing
Fitting
Fitting
Face of Fitting
Face of Fitting
to Face of Ceiling
to Face of Ceiling
1-1/8" (29 mm) at
7/8" (22 mm) at
Max. Recess
Max. Recess
3/8" (10 mm) at
3/8" (10 mm) at
Min. Recess
Min. Recess
1-3/4"
(44 mm) 1"
(25 mm)
Minimum Maximum
Recess 2-7/8"(72 mm) Dia. Recess
Models F1 & F1 FIR Pendent Sprinkler
with Model F1 Recessed Escutcheon
3/4" (19mm) Nominal Adjustment
2-1/2"
(64 mm) Dia.
Hole in Ceiling
2-5/16"
(59 mm) Dia.
Vented Cup
F1_REC PEND CCP
Reducing
Fitting
Face of Fitting
to Face of Ceiling
1-1/2" (38 mm) at
Max. Recess
1" (25 mm) at
Min. Recess
(25 mm) 1/2"
(12 mm)
Minimum
Recess 3-3/16" (78 mm) Dia.
Maximum
Recess
Models F1 & F1 FIR Pendent Sprinkler
with Model FP Recessed Escutcheon
1/2" (13mm) Nominal Adjustment
Note: Model FP recessed assemblies may not be used where the
pressure in the space above the ceiling is positive with respect to
the protected area. Ensure that the openings in the Model FP cup
are unobstructed following installation.
F1 Escutcheon
(F2 Similar)
7L ri
1-3
(44 mm) 1-1/4"
(32 mm)
Minimum Maximum
Recess 2-7/8" (72 mm) Dia. Recess
Models F1 & F1 FR Pendent Sprinkler
with Model F2 Recessed Escutcheon
1/2" (13mm) Nominal Adjustment
2-1/2"
(64 mm) Dia.
Hole in Ceiling
2-5/16"
(59 mm) Dia.
Vented Cup ,
1"
(25 mm)
Minimum
Recess
Reducing
Fitting
Face of Fitting
to Face of Ceiling
1-1/2" (38 mm) at
Max. Recess
1" (25 mm) at
Min. Recess
1/2"
(12 mm)
Maximum
i3-5/16" (84 mm) Dia. Recess
Model F1 FR56 CCP Conical Concealed Sprinkler
1/2" (13mm) Nominal Adjustment
(Nominal Cover Plate Projection is 1" (25 mm))
Note: Model CCP concealed assemblies may not be used where
the pressure in the space above the ceiling is positive with
respect to the protected area. Ensure that the openings in the
Model CCP cup are unobstructed following installation.
FP Escutcheon
CCP Cover Plate
Bulletin 074 Reliable Page 6 of 9
January 2023 www.reliablesprinkler.com
Recessed Installation: Horizontal Sidewall Sprinklers
1/2" (12 mm)
Reducing +/ 3/8" (10 mm) 1-3/8" (35 mm) Maximum Recess
Fitting Face of fitting
to face of wall
1 4,� _ 12"
(102 mm - 305 mm)
Deflector to ceiling
2-1/4" 1-15/16" 2-7/8"
(57 mm) (49 mm) - - - - (73 mm)
Dia. Hole Dia. Dia.
1 9/16" [14mm]
F1 Recessed escutcheon
3/4" (19 mm) Adjustment E 2 1/8" (54 mm) Minimum Recess
Model F1FR Horizontal Sidewall Sprinkler
with Model F1 Recessed Escutcheon
3/4" (19mm) Nominal Adjustment HFR REC-HSW
3/8" (16 mm)
ReducingN/ 1/4" (6 mm)
FittingFace of fitting 1-5/8" (42 mm) Maximum Recess
o face of wall
1 4'- _ 12"
(102 mm - 305 mm)
T9/16-
Deflector to ceiling
2-1/4" 1-15/16" 2-7/8"
(57 mm) (49 mm) - - - - - (73 mm)
Dia. DIA. Dia.
Hole14mm]
F2 Recessed escutcheon
1/2" (13 mm) Adjustment 2-1/8" (54 mm) Minimum Recess
Model F1FR Horizontal Sidewall Sprinkler
with Model F2 Recessed Escutcheon
1/2" (13mm) Nominal Adjustment
1-1/4" (32 mm)
Reducing +/- 1/4" (6 mm)
Fitting Face of fitting 7/8" (22 mm) Maximum Recess
to face of wall
1 4" _ 12"
(102 mm - 305 mm)
Deflector to ceiling
2-5/8" 2-5/16" 3-1/4"
(67 mm) (58 mm) - - - - (83 mm)
Dia Dia. Dia.
Hole.
9/16" [14mm]
Vented Cup 1-3/8" (35 mm) Minimum Recess
Model F1FR Horizontal Sidewall Sprinkler
with Model FP Recessed Escutcheon
1/2" (13mm) Nominal Adjustment
Note: Model FP recessed assemblies may not be used where the
pressure in the space behind the sprinkler is positive with respect
to the space in the protected area. Ensure that the openings in
the Model FP cup are unobstructed following installation.
Bulletin 074 Reliable Page 7 of 9
January 2023 www.reliablesprinkler.com
Model W2 (upright, pendent)
Model J (New frame with guard installed)
Model JD (Legacy frame with guard installed, similar but with zinc finish)
Finishes')
Model W4
(recessed, concealed pendent)
Standard Finishes
Special Application Finishes
Sprinkler
F1, F2 and FPM
Escutcheons
CCP Cover
Plate(2)
Sprinkler
F1, F2 and FP(2)
Escutcheons
CCP Cover Plate(2)
Bronze
Brass
Chrome
Electroless Nickel PTFE(3)(4)
Bright Brass
Bright Brass
Chrome
Chrome
White Paint
Bright Brass(-')
Satin Chrome
Satin Chrome
White Polyester(3)
White Polyester
Satin Chrome
Custom Color Polyester
Custom Color Paint
Custom Color Polyester(3)
Notes:
1. Paint or any other coating applied over the factory finish will void all approvals and warranties.
2. Model FP escutcheons and Model CCP sprinklers utilize a galvanized steel cup with a finished trim ring or cover plate.
3. cULus Listed as corrosion resistant.
4. FM Approved as corrosion resistant.
5. For 200T (93°C) maximum temperature rated sprinklers only.
Installation
Model F1 FIR Series sprinklers must be installed in accordance with
NFPA13 and the requirements of all applicable authorities having
jurisdiction. Model F1 FIR Series sprinklers must be installed with
the Reliable sprinkler installation wrench identified in this Bulletin.
Any other wrench may damage the sprinkler. The Models W2 and
W4 wrenches have two sets of jaws. Use the smallest set of jaws
that fit on the wrench flats of the sprinkler. A leak tight sprinkler
joint can be obtained with a torque of 8 to 18 lb-ft (11 to 24
N•m). Do not tighten sprinklers over the maximum recommended
installation torque. Exceeding the maximum recommended
installation torque may cause leakage or impairment of the
sprinkler.
Glass bulb sprinklers have orange bulb protectors or protective
caps to minimize bulb damage during shipping, handling and
installation. Reliable sprinkler installation wrenches are designed
to install sprinklers with bulb protectors in place. Remove the bulb
protector at the time when the sprinkler system is placed in service
for fire protection. Removal of the bulb protector before this time
may leave the bulb vulnerable to damage. Remove bulb protectors
by undoing the clasp by hand. Do not use tools to remove bulb
protectors.
Maintenance
Reliable Model F1 FIR series sprinklers should be inspected and
the sprinkler system maintained in accordance with NFPA 25, as
well as the requirements of any Authorities Having Jurisdiction.
Prior to installation, sprinklers should remain in the original
cartons and packaging until used. This will minimize the potential
for damage to sprinklers that could cause improper operation or
non -operation.
Do not clean sprinklers with soap and water, ammonia liquid or
any other cleaning fluids. Remove dust by gentle vacuuming
without touching the sprinkler.
Replace any sprinkler which has been painted (other than factory
applied). A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprinklers.
Failure to properly maintain sprinklers may result in inadvertent
operation or non -operation during a fire event.
Bulletin 074 Reliable Page 8 of 9
January 2023 www.reliablesprinkler.com
Guarantee
For the guarantee, terms, and conditions, visit www.
reliablesprinkler.com.
Ordering Information
Specify the following when ordering:
Model
F1FR56
Deflector/Orientation
• Upright
• Intermediate Upright
• Pendent
• CCP Concealed Pendent
• Horizontal Sidewall
• Vertical Sidewall
Temperature Rating
• See sprinkler technical specifications
Sprinkler Finish
• See Table B
Recessed EscutcheonO)(2)
• F1
• F2
• FP
Escutcheon Finish
• See Table B
CCP Cover Plate Temperature Rating
• 135°F (57°C) [For use with 135°F (57°C)
and 155°F (68°C) sprinklers.]
• 165°F (74°C) [For use with 175°F (79°C)
and 200oF (93°C) sprinklers.]
CCP Cover Plate Finish
• See Table B
Sprinkler Wrench
• Model W2
• Model W4 (recessed, concealed)
• Model J (New frame with guard installed)
• Model JD (Legacy frame with guard installed)
Notes:
1. 286°F (141°C) sprinklers are not listed to be used recessed or concealed.
2. For FM, recessed sprinklers must use the Model F2 escutcheon.
co
N
co
0
rn
M
rn
rn
rn
:1
Bulletin 074 Reliable Page 9 of 9