BLD2023-1360_Other_10.27.2023_11.30.07_AM_3865938PV Single Line
- - - - - - - - - - - - - - - -
String 1 — +�
z
13 modules PI
o
V
String 2 U
10 modules String 3
8 modules
0 Equipment Schedule
A
Storage Single Line I 0
------
I I I
I I
I I A
A 60A/2p I I
• I I
I I
30A/2p I I
2
L--
30A/2p
Battery
Disconnect,
Located within
10' of net meter
PV breaker in Gateway
to serve as exterior
solar rapid shutdown
initiation device
200A TESLA Gateway2 with
200A Internal Panelboard
Solar OCPD:60A
Battery OCPD:60A
Co -Located with Net Meter
Battery combiner panel I I I
Bus Rating: 125A I o
' I I
I 4/0 XHHW-2
(
I L1 & L2)
----------------------------—-=--———————————————------------------------- 2/ 0 XHHW-2
Ref.
Category
Equipment
QTY
1
Modules
Q.Peak DUO BLK ML-G10+ 405
31
2
Optimizers
S440 SolarEdge Optimizer
31
3
Jbox
Soladeck
5
41
Inverters
I Solar Edge SE10000H
1
Monitoring
I SolarEdge PV Inverter Monitoring
1
0 Conductor Schedule
I nverter Specs
Watts
LW-1
Output
AC
Voltage
# of
Inverters
OCPD
u
Solar Edge SE11400H
11400
47.5
240
1
60
****N/A****
0
0
0
0
0
****N/A****
0
0
0
0
0
Module Specs
Watts w
LrKLp
Vmp
Voc
Isc
Q.Peak DUO BLK VIL-G10+4
405
10.83
37.39
45.34
11.17
Temp. Adjusted
0
0
32.8
1 49.3
0
Summary
Distance
(ft)
Current
@125%
Operating
Voltage
Voltage
Drop
V. Drop
(total)
A
(2)#10 CU, (1)#6 EGC, PV Wire 600V, AIR
50
18.75A
400V
0.41%
0.99%
B
(6)#10 CU, (1)#10 EGC, THWN-2, 0.75"EMT(min)
50
18.75A
400V
0.41%
C
(2)#6 CU, (1)#8 N, (1)#10 EGC, THWN-2, 0.75"EMT(min)
10
52.5A
240V
0.17%
(N)
#6 THWN-2 200A/2p
(EGC)
Protected Loads Panel
(Existing)
Main Service Panel
(lph 240V Service)
Main Breaker: 200A
Bus Rating:200A
0 Equipment Schedule
Ref.
Category
Equipment
QTY
1
Gateway
Tesla Backup Gateway2: Service Rated
1
Breakers
200A Main Breaker (Eaton CSR2200N)
1
Misc.
Tesla 200A Internal Panelboard Kit
1
Breakers
2p60A, 2p60A
2
Battery
Tesla Powerwall 2, 13.5 kWh
2
Misc.
Powerwall Stack Kit
1
3
Loadcenters
MLO, 125A, 240V, 1ph, Nema 1, Flush, 8 space (min.)
1
Breakers
2p60A, 2p30A, 2p30A
Misc.
Breaker Hold down kit
1
4
Disconnect
60A 600V 2 Pole I Heavy Duty, No Fuse, Lockable
1
Misc.
Neurio Meter Kit
1
0 Conductor Schedule
■=A&RScope `,'I'
I
= Existing or A&RSOLAR
Others Scope
3211 Martin Luther King Jr Way S.
Seattle, WA 98144 (206)707-9937
OI Net Meter
4/0 XHHW-2
(L1 & L2)
2/0 XHHW-2
(N)
200A/2p
Unprotected Loads Panel
(Existing)
Main Service Panel
(lph 240V Service)
Main Breaker: 200A
Bus Rating:200A
Inverter Specs
Watts
Output
AC
Voltage
# of
Inverters
OCPD
LW-1
Tesla Powerwall 2
5000
1 24
240
2
30
Summary
Distance
(ft)
Current
@125%
Operating
Voltage
Voltage
Drop
A
(4)#10 CU, (2)#10 N, (1)#10 EGC, THWN-2, & com wire, 1"EMT(min)
10
30A
240V
0.25%
B
(2)#6 CU, (1)#6 N, (1)#10 EGC, THWN-2, & com wire, 1"EMT(min)
10
60A
240V
0.20%
THIS DRAWING CONSTITUTES THE
:ONFFIDENTIAL INFORMATION OF A&R SOLAR
AND ITS RECEPTOR POSSESSION DOES NOT
:ONFER ANY RIGHT IN OR LICENSE TO USE IT
OR THE INFORMATTION DISCLOSED HERE IN
NOR ANY RIGHT TO REPRODUCE THIS
DRAWING OR ANY PART HERE IN WITHOUT
THE WRITTEN CONSENT OF A&R SOLAR.
L
O
07
p�
O
C:
O
N
a-+
O
CO
00)Lnm
■
Q
Q
I
O
00
N
Q
Q
4W
U
O
o
(f)
a-+
O
N
Ln
�10
U
O
��
U
w
a�
Ln
Ln
Ln
N
REVISIONS
Rev. #: Date:
1 1 Oct 23, 2023
General Notes:
Designed by: Thomas N
Utility: Snohomish PUD PM: Will MacArthur
1. EGC Where exposed to physical damage will be #6AWG (206) 307-1741
Bare CU Current Date:Oct 23, 2023
2. If installing conduit on the roof, maintain greater than 7/8"
above the surface
3. NEC 690.12: Rapid Shutdown initiated by AC Disconnect I E1 Single Line